Questions? Call (315) 298-5121, or visit us online at www.fulton.com
1-1
INTRODUCTIONFTCS-IOM-2013-1114 SECTION 1
Overview
Prior to shipment, the following inspections and tests are
made to ensure the highest standards of manufacturing for
our customers:
Material inspections
Manufacturing process inspections
American Society of Mechanical Engineers (ASME)
welding inspection
ASME hydrostatic test inspection
Electrical components inspection
Operating test
Final engineering inspection
Crating inspection
This manual is provided as a guide to the correct operation
and maintenance of your Fulton equipment, and should be
read in its entirety and be made permanently available to the
sta responsible for the operation of the heater. It should not,
however, be considered as a complete code of practice, nor
should it replace existing codes or standards which may be
applicable. Fulton reserves the right to change any part of
this installation, operation and maintenance manual.
Installation, start-up, and maintenance of this equipment
can be hazardous and requires trained, quali ed installers
and service personnel. In order to meet Fulton warranty
requirements, this unit must be commissioned by a Fulton
Factory Technician. Trained personnel are responsible
for the operation and maintenance of this product, and
for the safety assurance of operation and maintenance
processes.
Warnings & Cautions
WARNINGS and CAUTIONS appear in various chapters of this
manual. It is critical that all personnel read and adhere to all
information contained in WARNINGS and CAUTIONS.
WARNINGS must be observed to prevent serious injury
or death to personnel.
CAUTIONS must be observed to prevent damage
or destruction of equipment or loss of operating
e ectiveness.
All Warnings and Cautions are for reference and guidance
purposes, and do not substitute for required professional
training, conduct, and strict adherence to applicable
jurisdictional/professional codes or regulations.
Disclaimers and Local Codes
Installation of the equipment shall conform to all the
requirements or all national, state and local codes established
by the authorities having jurisdiction or, in the absence
of such requirements, in the US to the National Fuel Gas
Code ANSI Z2231/NFPA 54 latest edition, and the speci c
instructions in this manual. Authorities having jurisdiction
should be consulted prior to installation.
The boiler heat exchanger is manufactured and stamped
in accordance with ASME Boiler and Pressure Vessel Code,
Section VIII, Div. 1 or Section I. It is the responsibility of the
customer to ensure equipment conforms to requirements
and codes.
Do not install, operate, service or repair any component
of this equipment unless you are quali ed and fully
understand all requirements and procedures.
When working on this equipment, observe all warnings,
cautions, and notes in literature, on stickers and labels, and
any additional safety precautions that apply. Follow all safety
codes and wear appropriate safety protection. Follow all
jurisdictional codes and consult any jursidictional authorities
prior to installation.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-1
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Unless otherwise noted, this heater is
certi ed for indoor installation only.
A competent rigger experienced in
handling heavy equipment should
handle rigging your equipment into
position.
The equipment must be installed on a
non-combustible surface.
Ensure all labels on the heater are
legible. All connections and safety
devices, both mechanical and
electrical, must be kept clean, with
ease of access for inspection, use and
maintenance.
Do not store or use gasoline or other
ammable vapors and liquids or
corrosive materials in the vicinity of
this or any other appliances.
Placement & Rigging
Proper placement of your Fulton Product (see Figures 1 and 2, and Tables 1
and 2) is essential. Attention paid to the following points will save a great deal
of di culty in the future. Correct placement is the rst step to trouble-free
installation, operation and maintenance.
Adhere to the following for equipment placement and rigging:
1. Consult authorities with jurisdiction over any national or local codes
(including but not limited to National Fire Protection Agency (NFPA),
American National Standards Institute (ANSI), Underwriters Laboratories
(UL), SCA, and ASME, which might be applicable to heater applications
before beginning.
2. Make appropriate determinations for placement, based on the following:
Check building speci cations and Table 3 for permissible oor loading.
Ensure the equipment is to be placed on a non-combustible level base
with adequate clearances from combustible materials. See Clearances &
Serviceability section.
Locate heater as close as possible to the place where the heat will be used
in order to keep pipe work costs to a minimum.
Ensure that there is adequate clearance around the unit to provide
access for operators and maintenance personnel to all parts of the
equipment. Ensure also that clearance provides for component removal for
maintenance. See Clearances & Serviceability section. The equipment
should be placed in a suitable heater house or well ventilated separate
room through which personnel do not normally pass. The layout should
eliminate tra c in potentially hazardous areas. For instance, the service
engineer or the operator should not have to pass exposed, hot pipe work
to make adjustments to the heater controls.
4 CAUTION
Do not allow weight to bear on
equipment components to prevent
damage.
2-2
Ensure the equipment is to be placed in such a way that the electrical
components are protected from exposure to water or excessive humidity.
3. Determine rigging procedure, based on the following:
Units are shipped upright and crated for forklift transport. Once
uncrated, all units can be transported with a forklift with the exception of
freestanding models FT-0080C, FT-0120C, FT-0160C and FT-0240C. These
four models can only be lifted for unloading and moving by means of
lifting lugs at the top of the heaters. All skidded units can be moved with
forklifts.
If means of lifting are not available, place rollers beneath the frame of the
equipment for guidance to the position of where it is to be installed.
Under no circumstances allow weight to bear on the jacket, control panel,
burner, fuel train or fan housing of any Fulton heater.
4. Install a 4 inch (102 mm) curb completely around the unit. In the event of a
large spill, this will help contain the uid.
Adhere to the following for equipment clearances and serviceability:
1. Ensure appropriate front, back, sides and top clearances are met. This
will allow access around the equipment to facilitate maintenance and a
safe work environment, and ensure technicians will commission the unit.
Technicians will not commence commissioning if hazardous conditions
exist.
2. Place heater with clearances to unprotected combustible materials,
including plaster or combustible supports, not less than the following:
Heater Front 36” (1m)
Heater Sides 18” (0.5 m)
Heater Rear 18” (0.5 m)
Flue Pipe 18” (0.5 m)
Minimum clearances for personnel access and burner removal: refer to
Table 4.
» In cases where the available height is insu cient, a roof or ceiling
trap must be considered. Fulton Vertical Coil design units need
su cient headroom for burner maintenance. Larger models
of the vertical coil design unit (FT-0320C and above) require an
access ladder/gantry to be provided by the customer to allow
clear access to the top of the heater for maintenance purposes.
Fulton Thermal Corporation will advise on the suitability of the
access provided and will provide assistance that may be required
in this respect.
» Access provision should avoid possible contact with hot
pipework, ues etc.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Crystalline silica may be present
in components of this equipment.
Exposure to crystalline silica may
pose signi cant health hazards,
including but not limited to eye and
respiratory system damage. Per
the Centers for Disease Control and
Prevention (CDC) and Occupational
Safety and Health Administration
(OSHA), appropriate personal
protective equipment must be worn
to minimize exposure to hazardous
substances. Refer to most current
guidelines o ered by the CDC and
OSHA for more information, including
personal protective equipment
recommendations.
Failure to provide required and
safe access to the equipment
could impede commissioning and
maintenance. Service technicians
are instructed not to commence
commissioning if hazardous
conditions exist.
NOTE: Burners may weigh up to 550 lbs (249 kg) depending on the type and
con guration.
NOTE: For UL listed units, see the speci cation plate on the Fulton Thermal Fluid
Heater for these clearances.
3. Pipes must not be run within 10” (254 mm) of any control cabinets or
combustible material.
4. Verify that all clearances are acceptable with the local ordinances.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
Failure to provide proper minimum
clearances between equipment and
combustible materials may result in
re.
2-3
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
Environment, Ventilation and
Combustion Air Requirements
Ventilation must be su cient to maintain a building
temperature of 120°F (49°C) or less. Consistent proper
ventilation of the equipment room is essential for good
combustion.
losses from the Fulton equipment (and other equipment)
should be considered.
Adhere to the following to meet ventilation and combustion
air requirements:
1. Install two fresh air openings, one at a low level, 24” (610
mm) from the oor, and one at a higher level on the
equipment room wall. This will provide a ow of air to
exhaust the hot air from the equipment room.
2. Ensure the burner has an adequate supply of air. Based
on NBIC recommendations, unobstructed air openings
must be sized on the basis of 0.5 square inch of free
area per 1,000 BTU/hr input maximum fuel input of
the combined burners in the equipment room or as
speci ed by applicable codes.
FIGURE 1 COMPONENT VIEW OF THE FTC / FTS
THERMAL FLUID HEATER
Legend
A - Fluid Outlet
B - Fluid Inlet
C - Top Mounted Burner
D - Control Panel
E - Fan Inlet
Notes
1. Thermal uid heater is of four-pass combustion
design.
D
A
B
C
2. First pass (radiant): combustion air enters burner fan
and travels upward between inner and outer jacket
before it enters top-mounted burner.
3. Second pass (convection): Gases travel back across
the inner row of coils.
4. Third pass (convection): Gases continue back down
between inner and outer coil.
5. Fourth pass: Upward between the outer coil and
inner jacket to the ue outlet.
Model FT-C00800120016002400320040006000800100012001400
Heat Output
Thermal Fluid Content
Recommended Flow Rate
Typical Circulating Pump Motor
Typical Burner Motor*
Fuel Consumption @
Full Output No.2 Oil
Natural Gas
1000 BTU/HR
1000 KCAL/HR
GAL
LITERS
GPM
M3/HR
HP
KW
HP
KW
GPH
LITER/HR
FT3/HR
M3/HR
800
200
11.4
7.5
1.5
1.1
7.1
998
38.3
1,200
300
10
38
50
10
27
7.5
2.2
10.7
40.6
1,498
42.4
1,600
400
21
80
75
17
10
3
100
22.7
11.2
2.2
14.3
54.1
1,998
56.5
2,400
600
19
72
15
3
116
150
11.2
2.2
21.4
2,999
84.9
3,200
800
31
34
15
3
81
258
250
56.8
14.9
3.7
108.8
4,000
113.2
4,000
1,000
68
20
5
28
288
250
56.8
14.9
3.7
35.3
136
4,997
141.5
6,000
1,500
76
20
5
132
498
375
85.2
22.5
201
7,498
212.3
7.5
5.6
8,000
2,000
113.6
30
53
29.5
11.2
69.3
263.7
9,997
171
648
500
40
15
283
10,000
2,500
290
1,097
615
139
37.3
87.1
329.6
12,496
353.8
12,000
3,000
1,448
50
37.3
20
15
104.5
395.5
14,998
424.6
383
730
167
50
20
15
14,000
3,500
460
1,741
800
182
60
45
20
15
122
461.5
17,500
495.5
* Std burner, single fuel applications.
Notes: Voltage 3 Phase for Burner and Pump - Each unit has an incorporated stepdown transformer. Fuel up to No. 6 Oil Available for Large Units (FT-0600-C and larger). E ciency up to 80%
Minimum Based on High Heating Value of the Fuel (No. 2 Oil @ 140,000 BTU/GHHV; Natural Gas @ 1000 BTU/ft3HHV. Modulation 3 to 1 Turn Down Ratio (5 to 1 for 320). Optional on FT-0080, 0120,
and 0160-Standard on all others. Circulating pump motor sizes based on standard pressure (55 PSIG) and viscosity 1 cs, speci c gravity 0.7, with 25-37 PSID available head for installation.
Model FT-C00800120016002400320040006000800100012001400
Heater Inlet/ Outlet Connections
(A) Overall Height
(B) Overall Width
(C) Overall Depth
(D) Flue Outlet Diameter
Recommended Vertical
Stack Diameter
Approximate Dry Weight
MM
MM
MM
MM
MM
MM
LBS
KG
IN
IN
IN
IN
IN
IN
1.25
73.7
1,872
31.6
803
46.2
1,173
254
254
1,500
700
32
10
10
1.5
38
80.7
2,050
34.4
873
60.6
1,540
10
254
12
304
2,100
950
51
80.6
2,046
45.9
1,165
60.6
1,540
10
254
12
304
2,550
1,150
2
2.5
64
89.7
2,278
50.1
1,273
66.6
1,691
12
305
14
356
3,400
1,550
76.3
100.6
2,556
49.3
1,252
80.6
2,046
14
356
18
457
5,300
2,400
3
112.4
2,856
49.3
1,252
80.6
2,046
356
457
5,300
2,400
3
76
14
18
102
143.6
3,648
63.4
1,611
88.1
2,237
457
558
8,250
3.750
4
18
22
102
143
3,632
70.5
1,791
107.75
2,736
508
609
11,450
5,200
4
20
24
152
146.5
3,721
2,413
135.1
3,432
508
609
19,250
8,750
6
95
20
24
152
146.4
3,718
108.4
2,753
152.9
3,882
22
559
26
661
21,700
9,850
6
6
152
163.1
4,144
108.4
2,753
152.9
3,882
22
559
26
661
23,000
10,455
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-5
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
A quali ed installer, service agency
or the gas supplier must perform
installation and service on the fuel
delivery system.
Do not use matches, candles, ame or
other sources of ignition to check for
gas leaks.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light the appliance.
Do not touch any electrical switch.
Do not use any phone in the building.
Leave building and contact gas
supplier from neighbor’s phone. If you
cannot reach gas supplier, phone the
re department.
3. Ensure the equipment room air supply openings are kept clear at all times.
4. See Table 5 for minimum make-up air required and the recommended area
of each opening for each model.
TABLE 3 APPROXIMATE FLOOR LOADING
ModelHeater Only*
FT-0080C500
FT-0120C400
FT-0160C450
FT-0240C450
FT-0320C450
FT-0400C450
FT-0600C550
FT-0800C500
FT-1000C500
FT-1200C400
FT-1400C450
FT-0400S675
FT-0600S675
FT-0800S525
*All weights are lbs/ft
TABLE 4 RECOMMENDED MINIMUM CLEARANCES FOR PERSONNEL ACCESS/BURNER
2
REMOVAL
When making gas piping joints,
maintain proper ventilation to reduce
breathing hazards.
An exhaust fan may draw products of
combustion into the work environment
creating a possible hazard to personnel.
4 CAUTION
It is essential that only fresh air be
allowed to enter the combustion air
system. Foreign substances, such
as combustible volatiles and lint in
the combustion system can create
hazardous conditions. If foreign
substances can enter the air stream, the
combustion air inlet must be piped to
an outside location. Failure to do so will
void the warranty.
To avoid failures due to poor
combustion, ensure make-up air system
is properly designed.
ModelInches (Meters)
FT-0080C109 (2.8)
FT-0120C115 (3.0)
FT-0160C119 (3.1)
FT-0240C125 (3.2)
FT-0320C133 (3.4)
FT-0400C145 (3.7)
FT-0600C171 (4.4)
FT-0800C172 (4.4)
FT-1000C173 (4.4)
FT-1200C172 (4.4)
FT-1400C188 (4.8)
FT-0400S162 (4.2)
FT-0600S170 (4.4)
FT-0800S171 (4.4)
5. If positive forced ventilation is adopted, ensure that there will be no
appreciable pressure variation in the equipment room.
6. Avoid ventilation which creates a negative pressure in the building as it
will seriously a ect combustion and proper operation of the stack. Please
note that exhaust fans or similar equipment can create a down draft in the
chimney or starve the burner’s air supply. Either case may result in poor
*Minimum make-up air requirements are based on 25% excess air at high re.
**Opening areas are calculated based input of a single heater and do not account
for the ventilation needs of the equipment room. These measurements are
subject to state and local regulations.
Opening Area
(in2)**Lower
Ven t
Opening
Area (in2)
Upper Vent
NOTE: A properly designed make-up air system in the
equipment room will preclude these possibilities and is
required to maintain proper combustion.
7. Eliminate potential for high risk situations for particulate
matter to be in the combustion air supply (e.g., as a
result of construction and maintenance activities).
Utilities
The Gas Supply
Adhere to the following for gas supply installation:
1. Install gas piping in accordance with all applicable
codes.
2. Ensure pipe and ttings used are new and free of dirt or
other deposits.
3. Ensure piping is of the proper size for adequate gas
supply to the gas head assembly. Consult your gas
company for speci c recommendations.
4. When making gas piping joints, use a sealing
compound resistant to the action of lique ed
petroleum gases. Do not use Te on tape on gas line
heads.
5. Ensure no piping stresses are transmitted to the
equipment. The equipment shall not be used as a pipe
anchor.
6. Ensure all vent connections on diaphragms, gas valves,
pressure regulators, and pressure switches (gas- red
units) are vented per local code.
7. On gas- red units with NFPA valve trains, ensure the
vent valve is piped to atmosphere per local code. See
Figure 4.
FIGURE 2 DIMENSIONS REFER TO TABLE 2
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
8. During any pressure testing of the system at pressures
in excess of 1/2 psig (14 inch W.C.)., disconnect the
heater at the heater manual shuto valve (located at
the end of the supplied gas train) from the gas supply
piping system.
9. Ensure the supply pressure is regulated by a nonstacking, tight, shut-o regulator.
10. Arrange gas piping so that it does not interfere with
any cover or burner, inhibit service or maintenance,
or prevent access between unit and walls or another
unit.The burner assembly and gas controls terminate
at a manual stop valve to which the gas supply should
be connected. Piping must be sized for a gas ow
consistent with the required BTU/Hr input. Large
pressure drops must be avoided. Fulton recommends
that the supply piping between the pressure regulator
and the inlet to the heater be kept to a minimum. The
minimum required gas pressure at the stop valve varies
TO LOW PRESSURE OIL
SWITCH ON CONTROL PANEL
PUMP
INLET
1/4" COPPER
TUBING
PI
0400 PSIG
SUPPLY
with the model of heater. The requirements for natural
gas- red coil design models are as follows:
Models FT-0080-C to FT-0400-C 14”w.c.
Models FT-0600-C to FT-0800-C 60”w.c.
Models FT-1000-C to FT-1400-C 120”w.c.
NOTE: Note: Low emissions burners for all models
require 5 psi.
NOTE: Even when the unit is shut down, the gas supply
pressure must never exceed these values.
NOTE: When operating, the supply pressure must not drop
below these limits: Not less than 11 “ w.c. where 14” w.c is
required. Not less than 50” w.c. where 60” w.c. is required.
Not less than 100” w.c. where 120” w.c. is required.
OIL S.S.O.V.
BURNER
3/8” COPPER TUBING
OR ½” SCHEDULE 40
CARBON STEEL PIPING
RETURN
TO TANK
MODULATING
OIL VALVE
IF APPLICABLE
MOUNTED
TO SKID
INLET
RETURN
FUEL
OIL PUMP
MOUNTED TO
TOP OF UNIT
RETURN
PI0200 PSIG
PRESSURE
INDICATOR
BURNER
CHECK
VALV E
MODULATING
OIL VALVE
1/4" NPT
CHECK VALVE
3/8” COPPER TUBING
OR ½” SCHEDULE 40
CARBON STEEL PIPING
NC OIL VALVE
FIGURE 5 TYPICAL NO. 2 OIL FIRED FUEL TRAIN
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
MOUNTING
BRACKET
2-9
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
The vent line connection on the
gas pressure regulator must be
piped to outdoor air by the installer
in accordance with National Fuel
Gas Code, ANSI Z223-1-1991 or
latest addenda. In Canada, gas
installations must be in accordance
with the current CAN/CGA B149.1 and
2 and/or local codes.
4 CAUTION
Some soap used for leak testing is
corrosive to certain types of metals.
Clean all piping thoroughly after
completing the leak check.
11. After gas piping is completed and before wiring installation is started,
carefully check all piping connections, (factory and eld), for gas leaks. Use
a soap and water solution.
The Oil Supply
Fuel Oil ViscositySpeci c GravitySulfur Content
#2Less than 31.9 Seconds Redwood #1 at
100°F (38°C)
#4Less than 81 Seconds Redwood #1 at
100°F (38°C)
#6*Less than 3000 Seconds Redwood #1 at
100°F (38°C)
*Notes: Propane gas pilot required. Oil must be delivered to the Fulton equipment at 160°F, 3 psi. Fulton
equipment will then preheat the oil from 160°F to 230°F. All fuel train components to be rated for the
temperature and pressure. Fuel train to be heat traced and insulated.
Adhere to the following for installation:
1. Fuel pipes must be of approved materials and of a diameter suitable for the
quantity of oil being delivered to the burner and the static head available.
See Figure 5.
2. Make fuel connection in accordance with the details on the enclosed fuel
pump cut sheet.
3. Ensure fuel oil piping is in accordance with local/national requirements.
In addition, if a two pipe system is employed, a check valve must be tted
into the return pipe.
0.824 to 0.852 at 59°F (15°C) less than 0.40%
by weight
0.90 to 0.93 at 59°F (15°C)less than 1.6%
by weight
0.95 to 0.98 at 59°F (15°C)less than 2.12%
by weight
4. Meet the maximum pressure allowed at the fuel oil pump inlet per the
National Fire Protection Association (NFPA).
NOTE: If for some reason the pressure of the fuel supply will exceed NFPA
maximum, tting a regulator to the fuel line must be considered, e.g. when there is
a tank situated with an oil level eight feet (2.4 m) or more above the pump.
5. On units tted with NFPA controls, ignition is obtained by means of a gas
pilot. A natural gas or LP supply is required for these units. The required
gas supply pressure is 7” w.c. If a guaranteed supply of natural gas is not
available, then a supply of bottled gas at 11“w.c. is required. For details
contact a local liquid propane dealer.
Instrument Air
Instrument air provision for pneumatically actuated control devices should meet
the minimum and maximum ow rate and delivery pressures speci ed by the
individual equipment. Additionally, it should be a dry, dust free supply with a
dew point of -40°F (-40°C).
Adhere to the following for electrical supply installation:
1. Install wiring and ground in equipment in accordance with authority
having jurisdiction or in absence of such requirements the National
Electrical Code, ANSI/NFPA 70.
2. Provide a wall-mounted, fused disconnect sized for the unit. This must be
tted by the client/contractor if disconnect is not supplied on the panel.
3. Size fuses according to motor name plates and local electrical codes.
4. Connect power to the terminal strip as supplied on the inside of the panel
box.
NOTE: Single skid systems are generally shipped completely prewired.
NOTE: The liquid level switch on the expansion tank, when supplied, will be
shipped in the parts box and must be installed in the eld.
5. Determine multiple skid systems wiring requirements (between the skids).
Fulton will run conduit and wire the devices on each skid. For the devices
that have to come down for shipping, the wire will be left at the end of the
conduit where possible and wired in the eld (by others). When the system
has multiple skids that are adjoining, the conduit will be installed to break
at the skid joints. The wire for the conduit running between the skids
will be shipped loose to prevent damage when the skids are put back
together. These wires will need to be run by the installing contractor in the
eld and wired to proper locations. If there is wiring between skids that are
not adjoining, then this will need to be done by quali ed personnel.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Assure all electrical connections are
powered down prior to attempting
replacement or service of electrical
components or connections of the
equipment.
NOTE: If the unit is not skid-mounted at the factory, the client/contractor is
required to wire the circulating / feed water pump starter.
NOTE: If the circulating pump motor is not supplied by Fulton, the motor starter
will not be supplied.
6. Locate electrical schematic diagram, a copy of which is inside of the panel
box.
7. Ensure the information on the electrical drawing corresponds to your
voltage and frequency. Adhere to the following:
Typical 120 VAC controls allow for a +10% and -15% voltage uctuation.
Motors are designed to operate within the following limits at the motor
terminals: AC power supplied is within +/- 10% of the motor rated voltage
with the rated frequency applied; or AC power supplied is within +/- 5% of
the rated frequency and with the rated voltage; or a combined variation
in voltage and frequency of +/- 10% (sum of absolute values) of rated
values provided the frequency variation does not exceed +/-5% of rated
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-11
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
If a re does occur, extinguish using
, foam or dry chemical. DO NOT
CO
2
USE WATER.
4 CAUTION
Some plastics can be dissolved by
thermal uid.
frequency.
For 3-phase motors, the line to line full load voltage must be balanced
within 1% of the rated motor voltage. If the motor is rated 208-230V, the
voltage deviations must be calculated from 230V. Operation outside of
these limits will degrade motor performance. 575V rated motors cannot be
operated at voltages above 600V. Depending on the motor manufacturer,
a 208V rated motor may not be able to run below the design voltage.
Electric elements will have an increase n watt density if the applied voltage
is higher than the element design voltage. Therefore, electric elements
have a 0% tolerance for operation over design voltage. Electric elements
can tolerate a lower than design voltage but the kW must be derated
accordingly.
Normal supply will be 460 volts, 3 phase, 60 Hz, AC unless otherwise
speci ed.
Thermal Fluids
Thermal Fluids at Elevated Temperatures
Personnel must be familiar with the nature of potential hazards when working
with thermal uids at operating temperatures. Unlike steam or high-pressure
water systems, thermal uid attains extremely high temperatures without a
corresponding increase in pressure.
Adhere to the following:
1. Be aware that certain types of thermal uid may have operating
temperatures reaching 650°F (345°C) and above, so all exposed pipework is
hazardous and should be insulated.
2. Check that anged joints are tight during and after the rst warming up of
the system. Turn Burner and pump o before ttings are tightened. After
these checks, exposed hot anges, pumps, valves and ttings should be
tted with some sort of shield.
3. Remember that there is pressure generated in the system by the circulating
pump. Care should be exercised when opening any drain or vent valves in
the system. This is especially important during commissioning, when any
air trapped in the system is vented at high points, and when water, which
will ash into steam, is either expelled from the deaerator vent or drained
o at low points.
Selecting a Thermal Fluid
The selection of the thermal uid most suited to your application is very
important. Factors to be considered include e ciency, thermal stability,
adaptability to various systems, and physical properties, including vapor
pressure, freezing point, and ash and re points.
2-12
Heat transfer uids of both mineral and synthetic origin have been specially
developed to give thermal stability over a very wide range of temperature. A
wide variety of thermal uids have been used successfully in Fulton Thermal
Fluid Heater systems, however, your nal selection should be made in
conjunction with recommendations from Fulton Thermal Corporation or the uid
manufacturer.
Consider the following for selection:
1. The Fulton coil design heater is a red heat exchanger and the safe
control and monitoring of the thermal uid temperature is of paramount
importance.
2. The safe maximum bulk temperature of the uid must be strictly adhered
to. The safe maximum temperature of the uid varies.
3. Special care must be taken when consulting uid manufacturers’ literature,
as maximum uid temperatures quoted are the actual limit to which any
of the uids may be subjected. It is important to remember that in any
red heater there exists a “ lm temperature” which is higher than the
temperature of the “bulk” of the uid. It is the BULK uid temperature and
NOT the FILM temperature that is indicated by the instruments.
4. As a general guide, the following list of uids that have given satisfactory
service over many years is provided. This is by no means a complete list.
Any uid speci cally designed for heat transfer use may be considered;
multipurpose oils are not acceptable.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Fulton Companies is not responsible
for any injury or damage caused by
the use of inadequate uid.
AMOCO Transfer Oil 4199
CHEVRON
DOW G
EXXON 43
MOBIL
MONSANTO
MULTITHERM
PARATHERM
PETROCANADA T
SHELL
TEXACO
5. Any uid speci cally designed for heat transfer use must also exhibit these
characteristics:
Be a stable and homogenous liquid to a temperature of at least
100°F (38°C) over and above the maximum intended temperature
of utilization, compatible with metals used in the installation, and
tolerating contact with atmospheric air.
No solid matter in suspension.
Non-toxic in the case of leakage.
Su cient lubricity, i.e. not likely to cause seizure.
6. The thermal uid manufacturer must guarantee the characteristics of the
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-13
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
4 CAUTION
Proper selection of thermal uid is
critical to system performance.
If excessive amounts of thermal
uid are vented from the system,
additional thermal uid may be
required in the system. Contact Fulton
for further information.
product, and verify that the uid bulk temperature limitation exceeds the
expected operating temperature
7. After a uid is selected, refer to the manufacturer’s recommendations,
published in compliance with the Occupational Safety and Health
Administration (OSHA).
8. If the uid expansion volume from 50°F to 600°F (10 C to 316°C) exceeds
20% of the initial uid volume, consult Fulton Thermal Corporation.
Routine Analysis of Heat Transfer Fluid
Nearly all leading manufacturers of heat transfer uids provide an after
sales service to monitor the condition of the uid in operation and make
recommendations when replacement becomes necessary.
Each uid manufacturer has procedures for regular testing and analysis of the
uid. These usually allow for a sample to be taken and analyzed at least once a
year, although actual frequency will depend on operating temperature, number
of hours operated weekly, and the results of tests made during the rst weeks of
system operation.
Fulton Thermal Corporation recommends that the thermal uid in your system
be analyzed within the rst two months after startup and annually thereafter.
During the rst few months of operation, sampling may be carried out at
frequent intervals to con rm that system performance has been predicted
correctly.
If the supplier of your thermal uid does not contact you within four weeks of
commissioning, contact the supplier and make certain that the “ ll” is registered
for routine analysis.
Thermal Fluid Breakdown
The possibilities of thermal uid breakdown are very slim in a typical closed loop
thermal uid system. Fulton’s combination expansion/deaerator/thermal bu er
tank creates a “cold seal” of uid that is slightly above ambient temperature. This
prevents oxidation that will otherwise happen when high temperature uid
contacts air.
Oxidation of the uid will also occur when hot thermal uid contacts air at a leak
in the system piping. Oxidized thermal uid becomes acidic and will damage the
thermal uid system. Thermal uid breakdown can occur in sections of piping
where there is a low ow condition. A low ow rate through the heater will result
in high lm temperatures leading to breakdown of the thermal uid.
THERMAL FLUID BREAKDOWN PREVENTION
Multiple pressure switches and a di erential pressure switch are used to
prevent this condition from occurring. See Figure 6. These safeties must
not be bypassed at any time.
2-14
Exceeding the maximum operating temperature of the thermal uid will
also result in thermal uid breakdown. Fulton heaters are equipped with a
temperature limit switch (located on the front of the panel box) to prevent
this from occurring.
A high temperature limit switch is an over temperature safety device.
If the high temperature limit shuts down the unit, the manual reset
button on the limit switch must be pressed. The reset button on the
ame programmer must also be pressed to reset the unit before it can be
restarted. See Figure 7. Refer to Maintenance section of this manual for
troubleshooting activities.
FIGURE6 PRESSURE SWITCHES
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
4 CAUTION
The weight of all piping must be
properly supported. Failure to support
piping may result in equipment
damage and/or system leakage.
Piping must take into consideration
potential for damage as a result of
expansion, contraction, vibration, or
other movements.
FIGURE 6 PRESSURE SWITCHES
FIGURE 7 TEMPERATURE LIMIT DISPLAY
Piping Specifi cations
Dirt, water, and/or other debris in the
piping system after welding may result
in equipment failure.
For piping, the basic considerations are: the design temperature, the pressure
retained by the pipe, the uid in the pipe, the load resulting from thermal
expansion or contraction, impact or shock loads imparted such as water hammer,
external loads, wind loads and vibration from equipment.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-15
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
Adhere to the following for piping installation (see Figure 8):
1. Ensure the arrangement of the piping and its
appurtenances takes into consideration the location
of other structures and equipment adjacent to the
piping, which may result in freezing interference and/or
damage as a result of expansion, contraction, vibration,
or other movements.
2. Consider the appropriate location and orientation of
valves necessary for safe operation and isolation of the
piping. Valves are used in piping systems to stop and
start the ow of uids, to regulate ow, to prevent the
back ow, and to relieve excessive pressure build up in
the piping.
Legend
1. Thermal Fluid Heater
2. Thermal Fluid Circulating Pump
3. Safety Relief Valve
4. Thermometer
5. Pressure Gauge
6. Thermal Fluid Heated Equipment
7. Bypass Valve
8. Expansion Joints
9. Anchor and Pipe Guides
10. Expansion Tank
11. Vent Piping
12. Deaerator Tank
13. Deaerator Tank Inlet (must be highest point of piping)
14. Thermal Bu er Tank
15. Catch tank (for drain of pressure relief valve, cold seal, expnasion tank, vent)
16. Valve
17. Strainer
18. 3/4” System Fill Connection
19. Flexible Connection
20. Isolating Valve
21. Manual Low Level Test Line
22. Manual High Level Test Line
23. Bu er Drain
3. Ensure all piping and piping components are suitable
for the design temperatures, pressure and uid used in
the system.
4. Ensure all components exposed to thermal uid ow,
including pipe, valves, and screens, are not copper,
copper alloys, bronze, brass, aluminum, or cast iron.
Cast iron is porous to thermal uids, and copper and
aluminum act as catalysts in the degradation of some
thermal uids. Carbon or stainless steel, or ductile iron,
are recommended.
5. Ensure all pipework is constructed from seamless mild
steel pipe, conforming to ASME SA 106B or SA 53B,
Schedule 40, Schedule 80, or equal, based on design
temperature and pressure of the system.
6. If an isolating valve is completely closed, the pressure
in the system will rise to the deadhead pressure of the
pump. Suitably sized pipe will enable the system to
withstand the total head generated by the circulating
pump, should this occur. In applications where it is
desirable to design to pressures lower than 100 psig,
an alternative safeguard is to install appropriately sized
safety valves.
7. Where secondary circulating pumps are installed,
ensure the system is suitable for the aggregate head,
against a closed valve, of both pumps.
8. During construction of the installation, ensure that no
dirt, water, or residue from welding is left in the system.
9. Consider expansion joints or pipe loops to
accommodate thermal expansion. Design should be
per latest edition of ASHRAE Systems and Equipment
Handbook to prevent detrimental forces and stresses at
connected equipment. Thermal expansion should be
calculated using the maximum possible utilization uid
temperature, regardless of whether the pipe considered
is in the feed or return circuit. Steel pipe will grow
axially and can be expected to expand approximately
1” over 100ft @ 100°F temperature rise (1mm per meter
over 100 C rise).
piping where necessary to prevent undue stress from
being imparted on equipment such as pumps, valves
and the heater. Care should be taken as end reactions
transmitted to rotating equipment, such as pumps,
may deform the equipment. Therefore equipment
manufacturers’ recommendations on allowable forces
and movements should be followed. See Figure 9.
11. Ensure all pipe joints are of either welded or anged
construction. Screwed joints must be avoided where
possible. In no instance should screwed joints be used
in the ow circuit. All anges should be welded to the
pipe and not screwed. Depending on the size, anges
should be 150# or 300# raised face anges, SA105.
12. Ensure heaters that are skid mounted with pumps and
tanks are equipped with a y-strainer, a ex connector
and a valve in the inlet run between the pump and the
combination tank. Piping between the discharge of
the pump and the inlet of the heater will include a ex
connector and a valve.
13. If screwed connections have to be made, e.g., to items
of control equipment, use a thread sealant suitable for
use with uids at elevated temperature. Te on tape,
standard pipe sealant, or hemp and paste are not
acceptable.
10. Provide properly designed supports and anchors for all
Pipe Must Be
Diameter of
Pump Intake
Pump
14. Cut screw threads carefully and accurately. If possible,
From Outlet of Deaerator
First
Fitting
Pipe Support Must Be
Provided (Not To Be
Welded On Both Ends)
FIGURE 9 TYPICAL PUMP PIPING
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
6 - 10 Pipe Diameters
2-17
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
new tools should be used. Threaded connections larger than 1” are not to
be used. It is recommended that GR5 or higher tensile steel bolts be used
for all anged joints.
15. Use gaskets to make all anged connections. Gasketing material must be
suitable for use with the pressure, temperatures and uids in the system.
Flexible graphite gaskets are suited for most applications. Recommended
gasket thickness is 1/10 - 1/8 inch. Ensure that all bolts are tightened
evenly and to the torque recommended values provided by the gasket
manufacturer. Refer to Figure 10 and Tables 6-9 for guidelines.
NOTE: Typical gaskets used by Fulton include JM Clipper Elastograph gaskets and
Flexitallic gaskets. Adhere to installation instructions and torque requirements for
these gaskets.
16. Install high point bleeds at all high points in the system piping. 1/2” x 12”
nipples welded in the top of the piping with ball valves and plugs attached
are to be used.
NOTE: It will save a considerable amount of time during the cold ltration if the
system piping is cleaned prior to assembly. The mill scale (the results of oxidation)
on the inside of the piping as well as construction debris can foul the uid and
cause the need for the lters (strainers) to be cleaned more than need be. This can
range from simply using a rag to ordering pickled pipe. (“Pickling” is a process
where the piping is rst soaked in an acid bath, then soaked in a neutralizing bath,
then given a protective oil coating.)
17. Install all pipes with a pitch to facilitate draining and venting.
1
5
3
7
2
FIGURE 10 BOLTING SEQUENCE FOR 4 AND 8 BOLT FLANGES
TABLE 6 RECOMMENDED GASKET LOADS FOR FLEXITALLIC SPIRAL WOUND CLASS 150#
GASKETS SAE GRADE 5 BOLTS OR EQUAL
Nominal Flange Size
(inches)
1/241/245
3/441/245
141/245
1 1/44 1/245
1 1/2 4 1/245
2 4 5/890
2 1/24 5/890
3 4 5/890
3 1/285/890
485/890
583/4150
683/4150
883/4150
10127/8240
Number of BoltsDiameter of Bolts
(inches)
Preferred Torque Req.
Per Bolt (ft-lb)
TABLE 7 RECOMMENDED LOADS FOR FLEXITALLIC SPIRAL WOUND CLASS 300# GASKETS
SAE GRADE 5 BOLTS OR EQUAL
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
Nominal Flange Size
(inches)
1/241/245
3/445/890
145/890
1 1/44 5/890
1 1/2 4 3/4150
2 8 5/890
2 1/283/4150
3 83/4150
3 1/283/4150
483/4150
583/4150
6123/4150
8127/8240
10161368
Number of BoltsDiameter of Bolts
(inches)
Preferred Torque Req.
Per Bolt (ft-lb)
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-19
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
TABLE 8 RECOMMENDED LOADS FOR JM CLIPPER ELASTOGRAPH 150# GASKETS SAE
GRADE 5 BOLTS OR EQUAL
Nominal Flange Size
(inches)
1/241/230
3/441/230
141/230
1 1/44 1/2 30
1 1/2 4 1/2 30
2 4 5/860
2 1/24 5/860
3 4 5/860
485/860
583/4100
683/4100
883/4100
10127/8160
Number of BoltsDiameter of Bolts
(inches)
Preferred Torque Req.
Per Bolt (ft-lb)
TABLE 9 RECOMMENDED LOADS FOR JM CLIPPER ELASTOGRAPH 300# GASKETS SAE
After the appropriate system tests have been satisfactorily completed
(see Testing section of this manual), all hot pipework and vessels must be
adequately insulated with material suited to the temperature and application
to prevent both heat loss and personnel injury.
Adhere to the following for insulation installation:
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
1. For inspection and maintenance purposes, leave pumps, anges, valves
and ttings uninsulated but suitably shielded for safety.
2. Insulate the deaerator section of the combination tank.
3. Do not insulate the thermal bu er and expansion sections of the
combination tank. On units operated with inert gas blankets above the
uid in the expansion tank, the entire combination tank, including the
expansion and thermal bu er sections, may be insulated but it is not
necessary.
4. Ensure hot oil pipe insulation is a minimum of 2” (51 mm) thick,
high temperature, laminated, foamglass cellular glass insulation as
manufactured by Pittsburgh Corning Corporation or equal.
5. For heaters equipped with ue gas recirculation (FGR) on the burner, the
ducting must be insulated to prevent personnel injury.
System Interfaces
Proper selection and installation of the components in the hot oil system will
ensure proper and safe operation of the heater.
Heater Connections
Adhere to the following for heater connections:
1. Connect the outlet of the pump directly to the inlet of the heater via
an isolating valve (preferably a throttling valve) and pump exible
connector.
To maintain a reasonable
temperature in the equipment area
and ensure safety to personnel, the
section of the chimney duct within
the building should be insulated.
Due to extremely high operating
temperatures of the thermal uid,
all exposed pipework should be
insulated, and exposed hot anges,
pump, valve, and ttings should be
shielded. Refer to Insulation section of
this manual for details.
No shuto of any kind may be
placed between the safety relief
valve and the equipment, or in the
discharge pipe between such valve
and the atmosphere. Doing so may
cause accidental explosion from
overpressure.
Discharge from safety relief valve
must be con gured so that there
is no danger of scalding personnel
or causing equipment damage.
Provisions must be made to properly
drain safety relief valve discharge
piping.
2. Pipe heater outlets directly to the system via an isolating valve.
3. A safety relief valve may be shipped in the parts box accompanying the
fuel- red heater, and must be installed in the outlet manifold. On all units,
the outlet must be piped to a safe discharge area. The piping from the
outlet of the safety valve must be piped to a catch tank. The discharge
ow must not be restricted, i.e. no valve should be installed. The weight of
the piping must be properly supported in order to prevent damage to the
safety valve. If the valve body becomes warped, leakage may result.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
Failure to insulate ducting
on equipment with Flue Gas
Recirculation on the burner may
result in personnel injury.
2-21
INSTALLATIONFTCS-IOM-2013-1114 SECTION 2
Thermal Fluid Circulating Pump
Installing the pump in accordance with the manufacturer’s
speci cations and these instructions will prolong the life
of the pump and contribute signi cantly to the successful
operation of your Fulton heater system. The pump
manufacturer’s installation and operation instructions can be
obtained from the manufacturer.
Adhere to the following for pump installation (see Figure 9):
1. Locate pump adjacent to the heater. Its base must be
rm, level (preferably concrete), and free from vibration.
2. Route pump per the manufacturer’s requirements. It
should be equipped with exible connections at the
suction and discharge sides. The primary function of
these connections are to prevent stresses due to pipe
expansion from being placed on the pump and to
isolate pump vibrations from the pipe work and the
heater. They also allow for expansion and de ection of
the pipe work. These connections should be rated for
high temperature since they are considered part of the
piping system.
3. Connect suction pipe work directly to the deaerator
section via a vertical run with as few elbows as possible.
It should contain the strainer and an isolating valve.
The discharge pipe work must be connected directly to
the heater inlet, and should contain an isolating valve.
See that pipe work connections match up accurately
with pump anges. Refer to the pump manufacturer’s
recommendations for the speci c pump inlet piping
requirements. Typically these requirements are that:
It be a straight run of pipe.
The straight run from the pump inlet to the rst tting,
valve, or ex connector be a minimum of 6-10 pipe
diameters in length.
The pipe used should be the same size as the inlet of
the pump.
The piping in the immediate vicinity of the pump
must not be supported by the pump. The pump is not
designed to bear the weight of the piping, and weight
on any part of the pump will throw it out of alignment.
and seal life expectancy. The pump is properly aligned
before it leaves the factory. Because the system expands
in operation, pump must be realigned when the system
is at operating temperature.