Fulton Reliance High Efficiency Cooper Fin Boiler User Manual

INSTALLATION AND
OPERATION MANUAL
Reliance (RLN)
High E ciency Hydronic Boilers
500,000 - 3,000,000 BTU/HR
Serial/ National Board Number
Model
Sold To
Job Name
Date
RLN-IOM-2012-1205
RLN-IOM-2012-1205 TABLE OF CONTENTS
Introduction 1-1
Overview .............................................................................................................. 1-2
Warnings & Cautions ............................................................................................1-2
Disclaimers and Local Codes ................................................................................1-2
Installation 2-1
Product Overview ................................................................................................. 2-2
Placement & Rigging ........................................................................................... 2-3
Clearances and Serviceability ..............................................................................2-3
Install Boiler Trim .................................................................................................2-5
Install Water Piping .............................................................................................. 2-6
LOW WATER CUT OFF .................................................................................................................210
Meet Water Chemistry Requirements ................................................................2-10
PREVENT FREEZING ...................................................................................................................211
PREVENT OXYGEN CONTAMINATION ........................................................................................211
ELIMINATE SYSTEM AIR ............................................................................................................212
Fill the Boiler With Water ...................................................................................2-12
Install Gas Piping ................................................................................................2-12
Install Condensate Drain (Optional) ................................................................... 2-13
Venting ............................................................................................................... 2-15
COMBUSTION AIR SUPPLY FROM THE BOILER ROOM ..............................................................216
COMBUSTION AIR PIPED FROM OUTSIDE BUILDING WITHOUT SEALED COMBUSTION ........216
Exhaust Venting .................................................................................................2-17
STANDARD VENTING CONFIGURATION, CATEGORY IV .............................................................217
OPTIONAL VENTING CONFIGURATION, CATEGORY I ................................................................217
FOR BOTH VENTING CONFIGURATION OPTIONS ......................................................................218
COMMON AIR INTAKE AND EXHAUST VENTING OF MULTIPLE BOILERS .................................218
Venting Terminations ......................................................................................... 2-19
WALL THIMBLE INSTALLATION .................................................................................................220
HORIZONTAL VENT TERMINATION ............................................................................................220
Electrical Connections ....................................................................................... 2-21
AIR PIPED FROM OUTSIDE BOILER ROOM ................................................................................222
INTAKE DUCT SIZING ................................................................................................................222
Operation 3-1
Test of High Back Pressure Switch ........................................................................3-5
Normal Operation of the Boiler ............................................................................ 3-5
CHANGING THE OPERATING SET POINT .....................................................................................36
SETTING COMBUSTION ................................................................................................................36
Shut Down Procedures .........................................................................................3-7
NORMAL SHUT OFF PROCEDURES .............................................................................................37
EMERGENCY SHUT OFF PROCEDURES .......................................................................................37
SHUTTING THE BOILER DOWN FOR AN EXTENDED PERIOD OF TIME ........................................37
STARTING BOILER AFTER PROLONGED SHUTDOWN ..................................................................37
SOLA Control Features .......................................................................................... 3-7
FLAME DETECTION ......................................................................................................................37
CYCLE AND RUN HOURS MONITORING .......................................................................................38
SETPOINT CONFIGURATION.........................................................................................................38
SETTING THE CENTRAL HEAT SETPOINT .....................................................................................38
REVIEWING STATUS DETAIL ........................................................................................................38
LEAD/LAG OUTDOOR RESET FOR SINGLE BOILER APPLIC ATIONS ...........................................310
Maintenance 4-1
General ................................................................................................................. 4-2
Daily Maintenance and Inspection Schedule ......................................................4-2
Weekly Maintenance and Inspection Schedule .................................................. 4-2
Monthly Maintenance and Inspection Schedule .................................................4-2
Procedure for Cleaning the Air Inlet Filter ..........................................................4-3
Relief Valve Testing ............................................................................................... 4-3
Annual Maintenance and Inspection Schedule ................................................... 4-3
EXAMINE THE VENTING SYSTEM ................................................................................................44
INSPECT HEATING SYSTEM FOR OTHER PROBLEMS ..................................................................45
Procedure for Removing/Cleaning The Burner .................................................... 4-5
After All Repairs and Maintenance ...................................................................... 4-6
Troubleshooting ...................................................................................................4-6
Warranty & Parts 5-1
Standard Warranty for Fulton Reliance Boilers .................................................... 5-2
Parts ..................................................................................................................... 5-3
PARTS LISTING .............................................................................................................................54
Perform Pre-Start-Up Inspection .........................................................................3-2
Fill and Purge the System..................................................................................... 3-2
SOLA Control Program Presets .............................................................................3-3
Commission The Boiler ......................................................................................... 3-3
TEST OF IGNITION SAFETY SYSTEM ............................................................................................34
Perform Test of Low Water Cut O ....................................................................... 3-4
Perform Test of Limit Controls ............................................................................. 3-4
Perform Test of Low Gas Pressure Switch ............................................................ 3-5
Perform Test of High Gas Pressure Switch ............................................................ 3-5
Perform Test of Air Switch .................................................................................... 3-5
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
0-1
TABLE OF CONTENTS RLN-IOM-2012-1205
0-2
© The Fulton Companies 2012
INTRODUCTION
INTRODUCTION
INSTALLATION
1
2
OPERATION MAINTENANCE WARRANTY & PARTS
3 4 5
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
1-1
INTRODUCTION RLN-IOM-2012-1205 SECTION 1
Overview
Prior to shipment, the following inspections and tests are made to ensure the highest standards of manufacturing for our customers:
§ Material inspections
§ Manufacturing process inspections
§ American Society of Mechanical Engineers (ASME)
welding inspection
§ ASME hydrostatic test inspection
§ Electrical components inspection
§ Operating test
§ Final engineering inspection
§ Crating inspection
This manual is provided as a guide to the correct operation and maintenance of your Fulton equipment, and should be read in its entirety and be made permanently available to the sta responsible for the operation of the boiler. It should not, however, be considered as a complete code of practice, nor should it replace existing codes or standards which may be applicable. Fulton reserves the right to change any part of this installation, operation and maintenance manual.
Installation, start-up, and maintenance of this equipment can be hazardous and requires trained, quali ed installers and service personnel. Trained personnel are responsible
for the installation, operation, and maintenance of this product, and for the safety assurance of installation, operation, and maintenance processes. Do not install, operate, service or repair any component of this equipment unless you are quali ed and fully understand all requirements and procedures. Trained personnel refers to those who have completed Fulton Service School training speci c to this product.
Warnings & Cautions
WARNINGS and CAUTIONS appear in various chapters of this manual. It is critical that all personnel read and adhere to all information contained in WARNINGS and CAUTIONS.
§ WARNINGS must be observed to prevent serious injury
or death to personnel.
§ CAUTIONS must be observed to prevent damage
or destruction of equipment or loss of operating e ectiveness.
All Warnings and Cautions are for reference and guidance purposes, and do not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes or regulations.
Disclaimers and Local Codes
Installation of the equipment shall conform to all the requirements or all national, state and local codes established by the authorities having jurisdiction or, in the absence of such requirements, in the US to the National Fuel Gas Code ANSI Z223.1/NFPA 54 latest edition, and the speci c instructions in this manual. Authorities having jurisdiction should be consulted prior to installation.
When required by local codes, the installation must conform to the American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
The boiler heat exchanger is manufactured and stamped in accordance with ASME Boiler and Pressure Vessel Code, Section IV for a maximum allowable working pressure and operating temperature of 160 psig and 210 F (121 C) respectively.
When working on this equipment, observe all warnings, cautions, and notes in literature, on stickers and labels, and any additional safety precautions that apply. Follow all safety codes and wear appropriate safety protection. Follow all jurisdictional codes and consult any jurisdictional authorities prior to installation.
1-2
© The Fulton Companies 2012
INSTALLATION
INTRODUCTION
INSTALLATION
1
2
OPERATION MAINTENANCE WARRANTY & PARTS
3 4 5
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-1
INSTALLATION RLN-IOM-2012-1205 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
Crystalline silica may be present in components of this equipment. Exposure to crystalline silica may pose signi cant health hazards, including but not limited to eye and respiratory system damage. Per the Centers for Disease Control and Prevention (CDC) and Occupational Safety and Health Administration (OSHA), appropriate personal protective equipment must be worn to minimize exposure to hazardous substances. Refer to most current guidelines o ered by the CDC and OSHA for more information, including personal protective equipment recommendations.
Product Overview
Prior to the performance of installation, operation, or maintenance procedures, personnel should become familiar with the equipment (Table 1 and Figure 1) and its components.
The Fulton Reliance hot water boiler is an automatic, fuel- red, high-e ciency boiler. The boiler can either be of the sealed combustion/direct vent type or utilize conventional combustion air intake and  ue methods.
The boiler is capable of sidewall venting when the appropriate venting materials are used, and when permitted by local code requirements. It features low emission pre-mix combustion with pulse width modulation and fully automatic safety controls.
The Fulton Reliance boiler is constructed to ASME Section IV and certi ed to Underwriters Laboratories (UL) 795 Issue 2006/10/27 Edition 6 Standard for Safety Commercial-Industrial Gas Heating Equipment. All Reliance boilers are hydrostatically tested, test  red and shipped as a complete packaged unit.
This boiler is to be installed as part of a hydronic heating system. A quali ed engineer must be consulted for the selection of the equipment and components of the heating system. Various system conditions can result in incorrect heat distribution to users of the heating system.
Each Reliance Boiler is supplied with the following:
4 CAUTION
This boiler is certi ed for indoor installation only.
This boiler is not designed for use in systems where water is continuously replenished. The warranty is valid for closed loop systems only.
Fulton cannot be held responsible for the selection, engineering, installation, or sizing of any additional equipment or components of the hydronic heating system.
A quali ed engineer must be consulted for equipment selection and heating system components.
§ Outer cabinet utilizing an air gap as insulation
§ Integrated combustion supervision and temperature operating control
§ Operating and high temperature dual temperature probe
§ Low water  ow switch
§ Fully matched modulating premix combustion system including burner,
blower and fuel train controls.
§ ASME pressure relief valve
§ Instruction manual
§ Wiring diagram
§ Combustion Air Adapter
§ Temperature and pressure (T&P) gauge
The customer should examine the equipment for any damage. It is the responsibility of the installer to ensure all parts supplied with the equipment are  tted in a correct and safe manner.
2-2
© The Fulton Companies 2012
SECTION 2 RLN-IOM-2012-1205 INSTALLATION
Placement & Rigging
Proper placement of your Fulton product is essential. Attention paid to the following points will save a great deal of di culty in the future. Correct placement is the  rst step to trouble-free installation, operation, and maintenance.
Adhere to the following for placement and rigging:
1. Check building speci cations for permissible  oor loading. Use Table 1 for unit reference.
2. Conform to all the requirements of all national, state and local codes established by the authorities having jurisdiction and/or the U.S. to the National Fuel Gas Code, latest edition. Authorities having jurisdiction should be consulted before installations are made. Where required by local codes, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
3. Since an external electrical source is utilized, the boiler, when installed, must be electrically ground in accordance with the National Electric Code, American National Standards Institute (ANSI) National Fire Protection Association (NFPA) 70, latest edition.
4. This boiler is certi ed for indoor installation only. National Electrical Manufacturers Association (NEMA) 3R Con guration is available as an option from the factory, but an existing boiler cannot be retro tted for outdoor installation.
5. Install so that all system components are protected from water (dripping, spraying, rain, etc.) during boiler operation and service.
6. Install on a level, non-combustible surface in the vertical position. Concrete is strongly recommended.
7. Provide combustion and ventilation air in accordance with applicable provisions of local building codes or: USA – NFPA 54/ANSI Z223.1, Section
5.3, Air for Combustion and Ventilation.
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
Competent personnel in accordance with all applicable local codes should carry out the installation of the Fulton equipment. All state and jurisdictional codes beyond the scope of the applicable ASME Boiler and Pressure Vessel Codes, for its corresponding classi cation, should be followed in all cases. Jurisdictional authorities must be consulted prior to installation.
A competent rigger experienced in handling heavy equipment should handle rigging your equipment into position.
The equipment must be installed on a non-combustible surface.
Failure to provide required and safe access to the equipment could impede commissioning and maintenance. Service technicians are instructed not to commence commissioning if hazardous conditions exist.
Failure to provide proper minimum clearances between equipment and combustible materials may result in  re.
8. Locate the boiler so that the air supply and exhaust piping between the boiler and outside wall/roof are within the maximum lengths for horizontal or vertical venting if sealed combustion will be used. See Clearances and Serviceability section of this manual.
Clearances and Serviceability
Adhere to the following for clearances and serviceability:
1. All local and national codes (NFPA, ANSI, UL, CSA, ASME) must be followed for proper clearances and serviceability for your boiler or heater. Authorities having jurisdiction should be consulted before installations are made.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
4 CAUTION
Do not allow weight to bear on equipment components to prevent damage.
Boiler must be installed in such a way as to protect from water (including dripping,
misting, etc.) during boiler operation.
2-3
INSTALLATION RLN-IOM-2012-1205 SECTION 2
TABLE 1A  OPERATING REQUIREMENTS
Reliance Model Size
Fuel Type Natural Gas or Propane*
Input BTU/Hr Max Min
Electrical Requirements (Amps) (120V/60/1) (240V/60/3)
Water Content Gal Liter
Dry Weight LB KG
500 750 1000 1500 2000 2500 3000
500,000 750,000 1,000,000 1,500,000 2,000,000 2,500,000 3,000,000
100,000 150,000 200,000 300,000 400,000 500,000 600,000
<3
NA
2.7 3 3 7.3 7.3 11 11
10.2 11.4 11.4 27.6 27.6 41.6 41.6
675 700 700 1000 1000 1400 1400
306 318 318 454 454 635 635
<3
NA
<3
NA
<6
NA
<6
NA
NA
<10
NA
<10
Operating Weight LB KG
Anchor Bolt Size IN MM
Dimensions • Reliance Hydronic Boiler
TABLE 1B  BOILER DIMENSIONS REFER TO FIGURE 1
700 725 725 1060 1060 1492 1492
317.5 329 329 481 481 676.75 676.75
.75 .75 .75 .75 .75 .75 .75
19 19 19 19 19 19 19
Reliance Model Size 500 750 & 1000 1500 & 2000 2500 & 3000
A. Boiler Width IN
MM
B. Boiler Height IN
MM
C. Boiler Depth IN
MM
D. Boiler Depth with Trim IN
MM
E. Air Inlet Diameter IN
MM
F. Flue Outlet Diameter IN
MM
G. Water Inlet/Outlet Size IN
MM
H. Min Clearance to Walls IN
MM
I. Min Clearance to Front and Rear IN
MM 914.4 914.4 914.4 914.4
J. Min Clearance to Ceiling
Notes:
Speci cations and dimensions are approximate. We reserve the right to change speci cations and dimensions without notice.
*The use of propane is allowable with concentration of up to 5% propylene, commonly referred to as HD5. The use of o -standard grades of propane,
such as propane HD10 (10% propylene) is not permitted unless a system is in place to reduce propylene concentration to less than 5% prior to
reaching any fuel delivery piping. This is the responsibility of the customer. Verify propylene concentration with supplier prior to commissioning and
operation of equipment.
IN 24 24 24 24
MM 609.6 609.6 609.6 609.6
24 24 32.125 34
610 609.6 815.9 863.6
45 50.7 67.9 72
1143 1287.8 1724.6 1828.8
29.3 29.3 34.3 42.2
744.2 744.2 871.2 1071.8
43.9 43.9 49.3 55.9
1115 1115 1115 1419.8
4 6 8 10
101.6 152.4 203.2 254
4 6 8 10
101.6 152.4 203.2 254
2 2 2.5 3
50.8 50.8 63.5 76.2
1 1 1 1
25.4 25.4 25.4 25.4
36 36 36 36
2-4
© The Fulton Companies 2012
SECTION 2 RLN-IOM-2012-1205 INSTALLATION
A
B
D
J
H
I
C
Front View
Right Side View
F
E
G
2. Appropriate front, back, side and top clearances must be maintained (Figure 1). This will allow access around the equipment to facilitate maintenance and a safe work environment. An 1 inch (25.4 mm) side clearance is acceptable between boilers.
3. Ensure all labels on the boiler will be fully visible for maintenance and inspection.
Install Boiler Trim
Each Reliance boiler is supplied with a safety relief valve sized in accordance with ASME requirements. Adhere to the following installation requirements:
1. The safety relief valve (Figure 2) must:
» Be connected to the coupling located in the
top rear outlet section of the boiler.
» Be installed in the vertical position.
» Be installed with a 4 inch (101.6 mm) nipple
between the boiler and the safety valve.
NOTE: ´ Safety relief valve size is determined by trim pressure
and is supplied in the trim kit along with appropriate bushing, inlet and outlet sizes.
The discharge pipe must:
» Not have a diameter less than the full area of the
valve outlet.
» Be as short and straight as possible and so
arranged as to avoid undue stress on the valve.
» Be supported by means other than the safety
valve itself.
» Be piped to avoid danger of scalding personnel.
NOTE: ´ Each boiler is equipped with a pressure-temperature
gauge to be installed in the outlet piping section of the boiler.
FIGURE 1 RELIANCE HYDRONIC BOILER CLEARANCES REFER TO TABLE 1B
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-5
INSTALLATION RLN-IOM-2012-1205 SECTION 2
! WARNING
Ensure tank return line is not clogged. Obstructions in the line could cause damage to the pump seal.
The discharge from the safety relief valve must be arranged to ensure no danger of scalding personnel, or equipment damage.
Provisions must be made to properly pipe the safety relief discharge away from the boiler to the point of discharge.
No shuto of any kind shall be placed between the safety relief valve and the boiler, or in the discharge pipe between the valve and the atmosphere. Doing so may cause an explosion from overpressure.
The hydronic system should never be  ushed while the boiler is attached to the system since the debris could accumulate in the boiler and block water from passing through the heat exchanger.
Ensure all labels on the boiler are legible. All connections and safety devices, both mechanical and electrical, must be kept clean, with ease of access for inspection, use and maintenance.
Install Water Piping
All water supplies contain some solids, dissolved gases or dissolved minerals. These may promote corrosion, deposition and/or fouling of equipment. To prevent these contaminants from impacting boiler performance, valve operation and general pipe longevity, each location must be analyzed and treated accordingly.
Adhere to the following for water piping installation (See Figure 3-5):
1. Boiler requires a minimum temperature di erential across the heat
exchanger at high  re, and has a minimum  ow requirement. Use Table 2 to identify ideal  ow rates for the Reliance boiler.
TABLE 2  IDEAL FLOW RATES/GALLONS PER MINUTE*
RLN Model
Min. GPM
Max. GPM
*The boiler warranty does not cover heat exchanger failure related to water  ow rates outside
of these parameters. The minimum return water temperature must be greater than 140 F
(60 C) at all times to avoid condensation in the heat exchanger. Warranty does not cover heat
exchanger failure due to condensation of products of combustion.
2. Ensure piping arrangements allow for heat-up times at or below
500 750 1000 1500 2000 2500 3000
23 45 45 75 90 130 140
43 63 83 130 150 200 210
30 seconds; this will reduce condensation which may contribute to equipment failure.
Do not store or use gasoline or other  ammable vapors and liquids or corrosive materials in the vicinity of this or any other appliances.
4 CAUTION
Low  ow conditions will cause excessive cycling, damage and failure of equipment.
Ensure water piping arrangements allow for heat-up times at or below 30 seconds; this will reduce condensation which may contribute to equipment failure.
2-6
3. Pipe unions and isolation valves are recommended on both water connections for ease of service.
4. Install piping so that the boiler is not supporting any additional piping.
5. The top water connection on the back of the boiler is the hot water outlet and must be connected as the supply to the system. The bottom connection is the return/boiler inlet. See Figure 6.
6. Install a hot water circulator, remote mounted from boiler. Do not attach directly to the boiler. Refer to Figures 3 - 5 for proper location of circulators.
7. Install manual purging valves in all loops and zones. Install a pressure reducing (automatic  ll) valve in the cold water  ll line to the boiler system. Check that the proposed operation of zone valves, zone circulator(s) and diverting valves will not isolate air separator(s) and/ or expansion tank(s) from the boiler. Clearance from hot water pipes to combustibles must be at least 6 inch (152.4 mm).
8. The boiler, when used in conjunction with a refrigeration system, must
© The Fulton Companies 2012
SECTION 2 RLN-IOM-2012-1205 INSTALLATION
Dedicated
Pump
T
Safety
Relief Valve
Heating
Loop
Return
12"
Strainer
Cold Water
Supply
Air
Separator
PRV
P
Expansion
Tank
Hot Water
Heating
Loop Supply
System
Pump
Air
Sep.
be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler. If the boilers are connected to heating coils, located in air handling units where they may be exposed to refrigerated air circulation, such boiler piping systems shall be
equipped with  ow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
9. The boiler is not provided with a drain valve directly on the boiler. A drain valve should be installed near the system return (water inlet) connection to the boiler and piped to a drain.
10. Before installing a Reliance boiler into a hydronic loop, be sure that the system piping and any other components of the system are clean and free of debris and any foreign matter. The hydronic system should be completely  ushed prior to installing the boiler itself.
FIGURE 2  SAFETY VALVE
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
FIGURE 3  SAMPLE PIPING LAYOUT: SINGLE BOILER WITH RETURN WATER TEMPERATURE >140 F 60 C
2-7
INSTALLATION RLN-IOM-2012-1205 SECTION 2
Dedicated
Pump
T
Safety
Relief
Valve
Heating
Loop
Return
12"
3-Way
Mixing
Valve
Strainer
Cold Water
Supply
Air
Separator
PRV
P
Expansion
Tank
Hot Water
Heating
Loop Supply
System
Pump
Air
Sep.
2-8
FIGURE 4  SAMPLE PIPING LAYOUT: SINGLE BOILER APPLICATION, WITH MIXING VALVE
© The Fulton Companies 2012
SECTION 2 RLN-IOM-2012-1205 INSTALLATION
Dedicated
Pump
T
Safety
Relief
Valve
T
Safety
Relief
Valve
Dedicated
Pump
T
Safety
Relief
Valve
Dedicated
Pump
Cold Water
Supply
Air
Separator
PRV
P
Expansion
Tank
Hot Water
Heating
Loop Supply
Heating
Loop
Return
System
Pump
Strainer
Strainer
Strainer
FIGURE 5  SAMPLE PIPING LAYOUT: MULTIPLE BOILERS IN A COMMON HYDRONIC LOOP, RETURN TEMPERATURE >140 F 60 C
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-9
INSTALLATION RLN-IOM-2012-1205 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/professional codes and regulations.
The boiler must be disconnected at
the boiler shut o valve from the gas supply piping system during any pressure testing of the system.
4 CAUTION
Small levels of chlorides and/or sulfur presence in the combustion air or fuel will negatively impact the heat exchanger components. Any presence of these contaminants will void the warranty.
Install a strainer upstream of each boiler to ensure that no foreign matter will have the opportunity to get inside the heat exchanger.
¡ Low Water Cut Off
The Reliance boiler comes with an installed  ow-switch type low water cut-o (LWCO). The LWCO does not require  eld piping or wiring. If the  ow switch does not sense  ow, the boiler will shut down and an alarm condition will be annunciated on the SOLA color screen display.
Customer Electrical Connection
Rubber Air Inlet Coupling
Air Inlet
Water Outlet Connection (system supply)
Some soaps used for leak testing are corrosive to certain types of metals. Rinse all piping thoroughly with clean water after leak check has been completed.
Exhaust Outlet Connection
Water Inlet Connection (system supply)
FIGURE 6  WATER INLET AND OUTLET CONNECTIONS
Meet Water Chemistry Requirements
System water chemistry requirements are as follows:
§ Maximum hardness of 8.5 grains (150 ppm)
2-10
§ Acceptable pH range of 7.5-10
§ Solids less than 2500 ppm
§ Alkalinity less than 500 ppm
© The Fulton Companies 2012
SECTION 2 RLN-IOM-2012-1205 INSTALLATION
§ Foreign matter: Oils, fats, grease, and other matter should be limited to 10
ppm.
Adhere to the following:
1. Refer to your water conditioning or chemical treatment supplier for analysis and recommendations for proper system conditions.
2. Follow a program with appropriate monitoring and maintenance of system water conditions as provided by your water conditioning or chemical treatment supplier.
3. Appropriate  ow rates and return water temperature may be achieved
through primary and secondary  ow loops. Please refer back to Figures 3 - 5 for example systems. Multiple pumps, valves and heating zones operating at a variety of conditions will cause system  ow to vary. System design professionals should consider the variety of conditions the heating system will experience.
4. Operate the boiler in a closed-loop system using water or water/glycol (not requiring a make-up water supply). A large amount of improperly treated make-up water can cause premature failure of the heat exchanger
resulting from scale build up. Scale build up will reduce the e ciency and useful life of the boiler.
! WARNING
If the water supply must be temporarily disconnected, the boilers must be turned o to prevent accidental  ue gas emission into the boiler room.
4 CAUTION
Care needs to be taken to eliminate oxygen from the water system, as excess oxygen in the system will reduce the life of any boiler. The boiler warranty does not cover heat exchanger replacement due to oxygen contamination of boiler water.
Heat exchanger failure due to inappropriate water quality, foreign matter or debris damage is not covered under the warranty.
¡ Prevent Freezing
It is imperative to prevent freezing; adhere to the following:
§ If water/glycol is to be used in the system, a hazard analysis should be
performed to determine proper use and disposal. No greater than 40% glycol should be used.
§ Precautions for freeze protection are recommended for boiler installations
where freezing potential exists and for installations that will use sealed combustion with potential for outdoor air to fall below freezing point.
¡ Prevent Oxygen Contamination
There are several ways to prevent boiler water oxygen contamination:
§ Minimize system leaks to minimize make up water requirement
§ Do not use open tanks or  ttings
§ Do not use oxygen permeable materials anywhere in the water system
§ Repair leaks in the system quickly
§ Eliminate  ttings wherever possible
If the piping system attached to this unit will be chemically cleaned, the boiler must be disconnected from the system and a bypass installed so that the chemical cleaning solution does not circulate through the boiler.
The hydronic system should never be
 ushed while the boiler is attached to the system since the debris could accumulate in the boiler and block water from passing through the heat exchanger. This will lead to premature boiler failure.
§ Use air elimination devices in system piping
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-11
INSTALLATION RLN-IOM-2012-1205 SECTION 2
! WARNING
All information in this manual is for reference and guidance purposes, and does not substitute for required professional training, conduct, and strict adherence to applicable jurisdictional/ professional codes and regulations.
Do not use matches, candles,  ame or other sources of ignition to check for gas leaks.
DO NOT USE GASOLINE, CRANKCASE OIL OR ANY OIL CONTAINING GASOLINE. If in doubt, contact your Fulton representative prior to operation.
4 CAUTION
Some soap used for leak testing is corrosive to certain types of metals. Clean all piping thoroughly after completing the leak check.
¡ Eliminate System Air
NOTE: ´ There are no built-in boiler air eliminating features.
Adhere to the following for air elimination:
1. The installation of an air separator and air eliminator (air vent) is required.
2. To prevent scale corrosion in boiler and associated piping, make up water must be kept to a minimum. This is best achieved by ensuring immediate repair of all leaks and that system pressure is maintained.
3. If a sealed diaphragm-type expansion tank is used, install an air eliminator in the hot water piping at the air separator.
4. If an air cushion type expansion tank is used, pipe tank directly into boiler supply.
5. On multi-zoned systems (or a system with both space and domestic water heating), air elimination must be provided either in the common piping or on every loop.
6. When the boiler is installed at a higher level than baseboard radiation (if used), air elimination must be provided directly above the unit.
Fill the Boiler With Water
To be sure that the boiler is not air-bound, open the pressure-relief valve located
at the rear of the boiler. Leave the relief valve open until a steady  ow of water is
observed. Close the valve and  nish  lling the system.
Install Gas Piping
The Reliance boiler is factory test  red and combustion is adjusted per the boiler data plate and test  re sheet.
The gas train (Figure 7) components are UL-795 certi ed to operate at speci c gas pressure requirements. If available gas pressure is greater than 14” W.C., a lock up style gas pressure regulator must be provided to reduce the provided pressure to the acceptable range of 3.5” W.C. to 14” W.C. for natural gas, and 7” W.C to 14” W.C. for propane.
Adhere to the following for gas piping installation:
1. See Table 3 for required natural gas pipe size, based on overall length of pipe from the meter plus equivalent length of all  ttings. Approximate sizing may be based on 1,020 BTU for 1 cubic foot of natural gas.
2-12
2. Piping must be installed such that no piping stresses are transmitted to the boiler. The boiler cannot be used as a pipe anchor.
3. The boiler and all gas piping connections must be pressure-tested and checked for leaks before being placed into service. Test with compressed air or inert gas if possible.
© The Fulton Companies 2012
Loading...
+ 42 hidden pages