Fujitsu 30RLXEH, AOU30RLXEH, Halcyon RLXEH Series Installation Manual

AIR CONDITIONER
PART No. 9379069762
English
OUTDOOR UNIT
FrançaisEspañol
APPAREIL EXTÉRIEUR
UNIDAD EXTERIOR
For authorized service personnel only.
MANUEL D’INSTALLATION
MANUAL DE INSTALACIÓN
Pour le personnel d’entretien autorisé uniquement.
Únicamente para personal de servicio autorizado.
En-2
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions.
If you require help for a special problem, contact our sales/service outlet or your certied
dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
1.2. Special precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected
and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wir­ing diagram and these instructions when wiring. Improper connections and inadequate earthing (grounding) can cause accidental injury or death.
• Earth (Ground) the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible re hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to
help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin
aluminum ns on the air conditioner can cut your ngers.
When Installing...
...In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support
.
...In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause drip-
ping and water damage to walls and oors.
...In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
...In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable air bafe.
...In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow.
When Connecting Refrigerant Tubing
• Keep all tubing runs as short as possible.
• Use the are method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the are and union tubes before
connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before opening the refrigerant valves.
NOTE:
Depending on the syste m type, liquid and gas lines may be ei ther narrow or wide.
Therefore, to avoid confusion the refrigerant tubing for your particular model is specied
as either “small” or “large” rather than as “liquid” or “gas”.
When Servicing
• Turn the power OFF at the main circuit breaker panel before opening the unit to check
or repair electrical parts and wiring.
• Keep your ngers and clothing away from any moving parts.
• Clean up the site after you nish, remembering to check that no metal scraps or bits of
wiring have been left inside the unit being serviced.
• After installation, explain correct operation to the customer, using the operating manual.
WARNING
Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury.
To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 10 minutes or more before you touch the electrical components.
Installation of this product must be done by experienced service technicians or
professional installers only in accordance with this manual. Installation by non­professional or improper installation of the product may cause serious accidents such as injury, water leakage, electric shock, or re. If the outdoor unit is installed in disregard of the instructions in the installation manual, it will void the manufacturer’s warranty.
Do not turn on the power until all work has been completed. Turning on the power
before the work is completed can cause serious accidents such as electric shock or re.
If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant is
exposed to a direct ame, it may produce a toxic gas.
Installation work must be performed in accordance with regulations, codes, or standards for electrical wiring and equipment in each country, region, or the installing place.
Do not use this equipment with air or any other unspecied refrigerant in the refrigerant lines. Excess pressure can cause a rupture.
During installation, make sure that the refrigerant pipe is attached rmly before you run
the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to rupture and even injury.
Contents
1. SAFETY PRECAUTIONS ............................................................................................2
1.1. IMPORTANT! Please read before starting ......................................................... 2
1.2. Special precautions ............................................................................................ 2
2. ABOUT THIS PRODUCT.............................................................................................3
2.1. Precautions for using R410A refrigerant ............................................................ 3
2.2. Special tools for R410A refrigerant ....................................................................3
2.3. Accessories ........................................................................................................ 3
2.4. Optional parts ..................................................................................................... 4
2.5. Operating range .................................................................................................4
3. GENERAL SPECIFICATION .......................................................................................4
3.1. Selecting circuit breaker and wiring ...................................................................4
3.2. Selecting the pipe material ................................................................................. 4
3.3. Protection of pipes .............................................................................................4
3.4. Refrigerant pipe size and allowable piping length .............................................. 4
3.5. For Pre-charge lengths ......................................................................................4
3.6. If additional refrigerant is required ......................................................................4
4. INSTALLATION WORK ............................................................................................... 4
4.1. Selecting an installation location ........................................................................ 4
4.2. Drain installation .................................................................................................5
4.3. Installation dimensions ....................................................................................... 5
4.4. Transporting the unit ..........................................................................................6
4.5. Installation .......................................................................................................... 6
5. PIPE INSTALLATION-1 ...............................................................................................7
5.1. Opening a knock out hole ..................................................................................7
5.2. Brazing ............................................................................................................... 7
5.3. Flare connection (pipe connection) .................................................................... 7
5.4. Sealing test ........................................................................................................8
5.5. Vacuum process ................................................................................................8
5.6. Additional charging .............................................................................................9
6. ELECTRICAL WIRING ................................................................................................9
6.1. Notes for electrical wiring ................................................................................... 9
6.2. Knock out holes for wiring ................................................................................ 10
6.3. Wiring method .................................................................................................. 10
7. PIPE INSTALLATION-2 ............................................................................................ 11
7.1. Installing insulation ........................................................................................... 11
7.2. Filling with putty ................................................................................................11
8. HOW TO OPERATE DISPLAY UNIT .........................................................................12
8.1. Display unit position .........................................................................................12
8.2. Description of display and button ..................................................................... 12
9. FIELD SETTING ........................................................................................................12
9.1. Field setting buttons ......................................................................................... 12
9.2. Function settings .............................................................................................. 13
10. EXTERNAL INPUT AND OUTPUT ............................................................................ 14
10.1. External input ...................................................................................................14
10.2. External output ................................................................................................. 14
10.3. Connection method .......................................................................................... 14
11. TEST RUN .................................................................................................................15
11.1. Pre-test run check items ..................................................................................15
11.2. Test operation method .....................................................................................15
11.3. Check list ..........................................................................................................15
12. ERROR CODE ..........................................................................................................16
12.1. Error display mode ...........................................................................................16
12.2. Error code check table .....................................................................................16
13. PUMP DOWN ............................................................................................................ 17
13.1. Preparation for pump down .............................................................................. 17
13.2. Pump down procedure ..................................................................................... 17
Note: This manual outlines how to install the air conditioner described above. Handling
and installation shall only be done by professionals as outlined in this manual.
1. SAFETY PRECAUTIONS
1.1. IMPORTANT! Please read before starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the
system so it operates safely and efciently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state, and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
WARNING:
This symbol refers to a hazard or unsafe practice which can result in
severe personal injury or death.
CAUTION:
This symbol refers to a hazard or unsafe practice which can result in
personal injury and the potential for product or property damage.
• Hazard alerting symbols
Electrical
Safety/alert
En-3
WARNING
Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping and installation and service tools are special. (See the table below.) Especially, when replacing a conventional refrigerant (R22) model with a new
refrigerant R410A model, always replace the conventional piping and are nuts with the R410A piping and are nuts.
Models that use refrigerant R410A have a different charging port thread diameter
to prevent erroneous charging with conventional refrigerant (R22) and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2-20 UNF.]
Be careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when storing the piping, securely seal the openings by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases. And always charge from the liquid phase where refrigerant composition is stable.
2.2. Special tools for R410A refrigerant
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materials
that have been manufactured specically for R410A use. Because the pressure of R410A refrigerant is approximately 1.6 times higher than R22, failure to use dedicated
piping material or improper installation can cause rupture or injury. Furthermore, it can
cause serious accidents such as water leakage, electric shock, or re.
Tool name Changes
Gauge manifold Pressure is high and cannot be measured with a conventional
gauge. To prevent erroneous mixing of other refrigerants, the
diameter of each port has been changed. It is recommended the gauge with seals –0.1 to 5.3 MPa (-1 to 53 bar) for high pressure. –0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
Charging hose To increase pressure resistance, the hose material and base
size were changed.
Vacuum pump A conventional vacuum pump can be used by installing a
vacuum pump adapter.
Gas leakage detector Special gas leakage detector for HFC refrigerant R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/33ft (10m). Do not use copper pipes having a collapsed, deformed
or discolored portion (especially on the interior surface). Otherwise, the expansion valve
or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using conventional refrigerant, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in the table. Never use copper pipes thinner than that in the table even when it is available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [in. (mm)] Thickness [in. (mm)]
1/4 (6.35) 0.032 (0.80)
3/8 (9.52) 0.032 (0.80) 1/2 (12.70) 0.032 (0.80) 5/8 (15.88) 0.039 (1.00) 3/4 (19.05) 0.047 (1.20)
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts. The use of non-prescribed parts can cause serious accidents such as
the unit falling, water leakage, electric shock, or re.
Following installation parts are supplied. Use them as required. Keep this manual in a safe place, and do not discard any other accessories until the
installation work has been completed.
Name and shape Q’ty Description
Installation manual
1
This manual
Cable tie with clip
1
For binding power supply cable and connection cable
Conduit plate
1
To x Conduit tube
When installing and relocating the air conditioner, do not mix gases other than the specied refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause rupture, injury, etc.
For the air conditioner to work appropriately, install it as written in this manual.
To connect the indoor unit and outdoor unit, use air conditioner piping and cables available locally as standard parts.
This manual describes proper connections using such installation set.
Do not use an extension cable.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
There is no extra refrigerant in the outdoor unit for air purging.
Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
Use a clean gauge manifold, vacuum pump and charging hose for R410A exclusively.
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to rupture and even injury.
Dispose of the packing materials safely. Tear and dispose of the plastic packing bags so that children cannot play with them. There is the danger of suffocation if children play with the original plastic bags.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
CAUTION
Indicates a potentially hazardous situation that may result in minor or moderate injury or damage to property.
This unit must be installed by qualied personnel with a capacity certication of handling refrigerant uids. Refer to regulation and laws in use on installation place.
Install the unit by following local codes and regulations in force in the place of installation, and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. The unit must not be installed alone or be installed with device not authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between contact of 3mm for this unit.
To protect the persons, earth (ground) the unit correctly, and use the power cable combined with an Earth Leakage Circuit Breaker (ELCB).
The units are not explosion proof, and therefore should not be installed in explosive
atmosphere.
This unit contains no user-serviceable parts. Always consult experienced service
technician for repairing.
When moving or relocating the air conditioner, consult experienced service technicians
for disconnection and installation of the unit.
Children should be monitored to ensure they do not play with the device.
Do not touch the aluminum ns of heat exchanger built-in the indoor or outdoor unit to
avoid personal injury when you install or maintain the unit.
Do not place any other electrical products or household belongings under indoor unit or outdoor unit. Dripping condensation from the unit might get them wet, and may cause damage or malfunction of your property.
2. ABOUT THIS PRODUCT
2.1. Precautions for using R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle. If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture.
If there is a refrigerant leak, make sure that it does not exceed the concentration limit. If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other areas. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and
thoroughly ventilate the area. If the refrigerant comes in contact with a ame, it produces a toxic gas.
The basic installation work procedures are the same as conventional refrigerant models. However, pay careful attention to the following points:
En-4
2.4. Optional parts
Parts name Model name
External connect kit
(for External input/output)
UTY-XWZXZ3
2.5. Operating range
Outdoor Cooling/Dry Mode Heating Mode
Temperature
-5 to 115°F
(-20 to 46°C)
-15 to 75°F
(-26 to 24°C)
3. GENERAL SPECIFICATION
3.1. Selecting circuit breaker and wiring
CAUTION
Be sure to install a breaker of the specied capacity.
Regulation of cables and breaker differs from each locality, refer in accordance with local rules.
Voltage rating 1 ø 208/230 V (60 Hz)
Operating range 188-253 V
Cable Description
Power supply cable 2 cable + Earth (Ground), 1 ø 208/230 V
Connection cable
3 cable + Earth (Ground), 1 ø 208/230 V
Select the correct cable type and size according to the country or region’s regulations.
Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
CAUTION
MINIMUM CIRCUIT AMPACITY 25.6 A
MAX. CKT. BKR.
30 A
Before starting work check that power is not being supplied to all poles of the indoor unit and outdoor unit.
Install all electrical works in accordance to the national standard.
Install the disconnect device with a contact gap of at least 2/16 in. (3mm) in all poles
nearby the units. (Both indoor unit and outdoor unit)
Install the circuit breaker nearby the units.
3.2. Selecting the pipe material
CAUTION
Do not use existing pipes.
Use pipes that have clean external and internal sides without any contamination which may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes. Material: Phosphor deoxidized seamless copper pipes. It is desirable that the amount of residual oil is less than 40 mg/33ft (10m).
Do not use copper pipes that have a collapsed, deformed, or discolored portion
(especially on the interior surface). Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A incurs pressure higher than when using conventional refrigerant, it is necessary to choose adequate materials.
Note:
Thicknesses of copper pipes used with R410A are as shown in the table. Never use copper pipes thinner than those indicated in the table even if they are available
on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [in. (mm)] Thickness [in. (mm)]
1/4 (6.35) 0.032 (0.80)
3/8 (9.52) 0.032 (0.80) 1/2 (12.70) 0.032 (0.80) 5/8 (15.88) 0.039 (1.00) 3/4 (19.05) 0.047 (1.20)
3.3. Protection of pipes
Protect the pipes to prevent the entry of moisture and dust. Especially, pay attention when passing the pipes through a hole or connecting the end of
a pipe to the outdoor unit.
Location Working period Protection method
Outdoor
1 month or more Pinch pipes
Less than 1 month Pinch or tape pipes
Indoor - Pinch or tape pipes
3.4. Refrigerant pipe size and allowable piping length
CAUTION
Keep the piping length between the indoor unit and outdoor unit within the allowable tolerance.
Pipe diameter <Liquid/Gas>
(Standard)
[in. (mm)]
3/8 (9.52) / 5/8 (15.88)
Max. piping length (L1)
246 ft. (75 m)
Min. piping length (L1)
16 ft. (5 m)
Max. height difference (H1) <Indoor unit to outdoor unit> 98 ft. (30 m)
View (Example)
L1
H1
Indoor unit
*1: For the standard pipe diameter.
3.5. For Pre-charge lengths
3.5.1. For Pre-charge lengths
Piping length (L) *Pre-charge
66ft. ( 20m )
3.6. If additional refrigerant is required
3.6.1. If additional refrigerant is required
When the piping is longer than pre-charge length, additional charging is necessary.
For the additional amount, see the table below.
Additional charging amount Single type
L1 > Pre-charge length
Piping length
66ft
(20m)
99ft
(30m)
131ft
(40m)
165ft
(50m)
196ft
(60m)
229ft
(70m)
246ft
(75m)
Rate
Additional
charge
None
14.2oz (400g)
1lb 12oz
(800g)
2lb 10oz (1200g)
3lb 8oz
(1600g)
4lb 7oz
(2000g)
4lb 14oz (2200g)
0.43oz/ft (40g/m)
4. INSTALLATION WORK
Make sure to obtain the customer’s approval for selecting and installing the outdoor unit.
4.1. Selecting an installation location
WARNING
Securely install the outdoor unit at a location that can withstand the weight of the unit. Otherwise, the outdoor unit may fall and cause injury.
Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes and typhoons or other strong winds. Improper installation can cause the unit to topple or fall, or other accidents.
Do not install the outdoor unit near the edge of a balcony. Otherwise, children may climb onto the outdoor unit and fall off of the balcony.
En-5
CAUTION
Do not install the outdoor unit in the following areas:
Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area lled with mineral oil or containing a large amount of splashed oil or steam, such as
a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
Area containing equipment that generates electromagnetic interference. It will cause the control system to malfunction, preventing the unit from operating normally.
• Area that can cause combustible gas to leak, contains suspended carbon bers or ammable dust, or volatile inammables such as paint thinner or gasoline. If gas leaks and settles around the unit, it can cause a re.
• Area where small animals may live. It may cause failure, smoke or re if small
animals enter and touch internal electrical parts.
Area where animals may urinate on the unit or ammonia may be generated.
Do not tilt the outdoor unit more than 3 degrees. Install the outdoor unit in a well-ventilated location away from rain or direct sunlight. If the outdoor unit must be installed in an area within easy reach of the general public,
install as necessary a protective fence or the like to prevent their access. Install the outdoor unit in a location that would not inconvenience your neighbors, as
they could be affected by the airow coming out from the outlet, noise, or vibration. If it must be installed in proximity to your neighbors, be sure to obtain their approval.
If the outdoor unit is installed in a cold region that is affected by snow accumulation, snow fall, or freezing, take appropriate measures to protect it from those elements. To ensure a stable operation, install inlet and outlet ducts.
Install the outdoor unit in a location that is away from exhaust or the vent ports that
discharge vapor, soot, dust, or debris.
Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote control cable at least 3.3ft (1m) away from a television or radio receivers. The purpose of this is to prevent TV reception interference or radio noise. (Even if they are installed more than 3.3ft (1m) apart, you could still receive noise under some signal conditions.)
Branch switch and circuit breaker
3.3ft (1m) or more
3.3ft (1m) or more
Branch switch and circuit breaker
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
Keep the length of the piping of the indoor and outdoor units within the allowable range.
For maintenance purposes, do not bury the piping.
4.2. Drain installation
CAUTION
In places where the outdoor temperature drops to 32 °F (0 °C) or lower, the drain water may freeze and may stop up the drain or cause other outdoor unit trouble. Therefore take measures so that the drain water will not freeze and clog the drain.
Please set up the outdoor unit in a high place and please do not arrange the frame of installed stand under the drain port, because the water dropped from the drain port repeats freezing and accumulating, and may block the drain port.
In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with
snow, it might become difcult to get warm and it is likely to because of the breakdown. Please construct a canopy or bafe board. (local congured).
4.3. Installation dimensions
CAUTION
The installation space shown in the following examples is based on an ambient
temperature under cooling operation of 95°F (35°C) (DB) at the air intake of the
outdoor unit. Provide more space around the air intake than shown in the examples if the ambient temperature exceeds 95°F (35°C) (DB) or if the thermal load of all of the outdoor units exceeds the capacity.
Consider the transportation route, installation space, maintenance space, and access,
and install the unit in a location with sufcient space for the refrigerant piping.
Observe the installation space specications that are shown in the gures.
Keep the same space at rear air intake. Provide the same space for the air intake at the rear of the outdoor unit.
If the installation is not performed according to the specications, it could cause a short
circuit and result in a lack of operating performance. As a result, the outdoor unit might easily be stopped by high-pressure protection.
Air intake
Rear view
Installation methods not shown in the following examples are not recommended. Performance may drop signicantly.
4.3.1. Single outdoor unit installation
When the upward area is open (Unit : in. (mm))
(1) Obstacles at rear only
5-29/32 (150) or more
(2) Obstacles at rear and sides only
7-7/8 (200) or more
11-13/16 (300) or more
7-7/8 (200) or more
(3) Obstacles at front only
39-3/8 (1000) or more
(4) Obstacles at front and rear only
39-3/8 (1000) or more
5-29/32 (150) or more
When an obstruction is present also in the upward area (Unit : in. (mm))
(1) Obstacles at rear and above only
11-13/16 (300) or more
Max. 19-11/16 (500)
39-3/8 (1000) or more
(2) Obstacles at rear, sides, and above only
59-1/16 (1500) or more
9-27/32 (250) or more
9-27/32 (250) or more
19-11/16 (500) or more
Max.
19-11/16 (500)
En-6
4.3.2. Multiple outdoor unit installation
Provide at least 9/16in. (15mm) of space between the outdoor units if multiple units are installed.
When routing the piping from the side of an outdoor unit, provide space for the piping.
No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following example when an
obstruction is present also in the upward area.
When the upward area is open (Unit : in. (mm))
(1) Obstacles at rear only
11-13/16 (300) or more
(2) Obstacles at front only
5-29/32 (150) or more
(3) Obstacles at front and rear only
19-11/16 (500) or more
59-1/16 (1500) or more
When an obstruction is present also in the upward area (Unit : in. (mm))
Obstacles at rear and above only
59-1/16 (1500) or more
19-11/16 (500) or more
Max. 11-13/16 (300)
59-1/16 (1500) or more
4.3.3. Outdoor units installation in multi row (Unit : in. (mm))
(1) Single parallel unit arrangement
5-29/32 (150) or more
23-5/8 (600) or more
39-3/8 (1000) or more
78-3/4 (2000) or more
(2) Multiple parallel unit arrangement
19-11/16 (500) or more
23-5/8 (600) or more
59-1/16 (1500) or more
118-1/8 (3000) or more
4.4. Transporting the unit
WARNING
Do not touch the ns. Otherwise, personal injury could result.
CAUTION
When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or ngers may be pinched.
Carry slowly in the manner as shown on “Fig. B” holding the handles “Fig. A” in right
and left sides. (Be careful not to touch with hands or objects.)
Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on the sides of the unit may be deformed.
Fig. A
Handle
Suction grille
Handle
Suction grille
Fig. B
Front view
Rear view
4.5. Installation
(Unit : in. (mm))
5-3/16
(132)
AIR
25-19/32
(650)
4-11/16
(119)
1-31/32
(50)
1-31/32
(50)
5/8 (16)
14-9/32 (363)
4 - Φ 12 Hole
• Install 4 anchor bolts at the locations indicated with arrows in the above gure.
• To reduce vibration, do not install the unit directly on the ground. Install it on a secure
base (such as concrete blocks).
The foundation shall support the legs of the unit and have a width of 1in. (50mm) or more.
• Depending on the installation conditions, the outdoor unit may spread its vibration
during operation, which may cause noise and vibration. Therefore, attach damping materials (such as damping pads) to the outdoor unit during installation.
• Install the foundation, making sure that there is enough space for installing the
connection pipes.
• Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially
available M10 bolts, nuts, and washers.)
• The bolts should protrude 25/32 in. (20 mm). (Refer to the gure below.)
• If overturning prevention is required, purchase the necessary commercially available
items.
Bolt
25/32 in.
(20 mm)
Nut
Base
Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt,
nut and washer.)
Loading...
+ 11 hidden pages