The PRIMERGY BX600 S2 Blade Server System represents a highly compact,
power-saving and scalable servers for integration in 19-inch rack systems.
Figure 1: PRIMERGY BX600 S2 Basic Unit
The PRIMERGY BX600 S2 basic unit occupies seven height units in the rack
and can accommodate up to ten server blades of different models and configurations.
As economical, ultra-compact systems, the server blades with up to eight CPUs
are ideal for use by company data centers and Internet service providers. They
are perfectly suited for large application servers, terminal servers for CPUintensive applications, and DBMS servers.
The PRIMERGY BX600 S2 Blade Server System offers a high level of reliability
and availability through highly developed hardware and software components.
This includes hot-swappable server blades, switch blades, Fibre Channel (FC)
and Ethernet pass-thru blades, management blades, hot-swappable power
supply units and fan modules, the server management software ServerView, and Remote-Deploy, Prefailure Detection and Analyzing (PDA), and Automatic Server
Reconfiguration and Restart (ASR&R).
PRIMERGY BX600 S2 Basic Unit 7
Overview of the DocumentationIntroduction
Security functions in the BIOS Setup protect the data on the server blades
against manipulation. Additional security is provided by the lockable rack door.
1.1Overview of the Documentation
I PRIMERGY manuals are available in PDF format on the ServerBooks
DVD. The ServerBooks DVD is part of the PRIMERGY ServerView Suite
delivered with each server system.
The PDF files for the manuals can also be downloaded free of charge
from the Internet. The overview page showing the online documentation
available in the Internet can be found via the URL:
This operating manual is intended for those responsible for installing the
hardware and operating the system. The manual contains all the information
required for mounting and operating your PRIMERGY BX600 S2 basic unit.
For a brief overview of the installation steps please see chapter 2 on page 19ff.
To understand the different expansion options, you need a knowledge of
hardware and data transmission, as well as basic knowledge of the operating
system used.
Additional server documentation
The PRIMERGY BX600 S2 documentation also includes:
– “Quick Start Hardware - PRIMERGY BX600 S2/S3” (leaflet)
– “Quick Start Software - PRIMERGY ServerView Suite” (leaflet)
– “Warranty” manual (print version supplied with the system, PDF file available
on the ServerBooks DVD supplied)
– “Safety notes and other important information” manual (print version
supplied with the system, PDF file available on the ServerBooks DVD
supplied)
– “Ergonomics” manual (PDF file available on the ServerBooks DVD supplied)
– “Returning used devices” manual (PDF file available on the ServerBooks DVD
supplied)
– “Helpdesk” (leaflet with worldwide helpdesk telephone numbers)
– Technical Manual for the Dxxxx system board (PDF file available on the
ServerBooks DVD supplied)
8 PRIMERGY BX600 S2 Basic Unit
IntroductionOverview of the Documentation
– “BIOS Setup” (PDF file available on the ServerBooks DVD supplied)
– “ServerView Suite” includes the ServerStart Disc 1, the ServerStart Disc 2
and the ServerBooks DVD. The PDF version of the “PRIMERGY ServerView
Suite - ServerStart” user manual is also available on the ServerBooks DVD.
I If you need a replacement copy of the ServerBooks DVD, send the
details of your sever to the following e-mail address:
Reklamat-PC-LOG@fujitsu-siemens.com
– „PRIMERGY BX Blade Server Systems: RemoteView Management Blade -
User Interface Description“ (PDF-Version auf ServerBooks-DVD enthalten)
– „PRIMERGY BX Blade Server Systems: LAN Switch Blade - User Interface
Description“ (PDF-Version auf ServerBooks-DVD enthalten)
- Hardware Installation Guide“ (PDF-Version auf ServerBooks-DVD enthalten)
– „PRIMERGY BX Blade Server Systems: LAN Router and Switch Blade -
User Interface Description“ (PDF-Version auf ServerBooks-DVD enthalten)
– „BX600 Digital KVM Switch: User Guide“ (PDF-Version auf ServerBooks-DVD
enthalten)
Further Sources of Information
Further information is provided in:
– the RemoteDeploy manual (only relevant for cloning server blades)
– the technical manual for the rack
– the manual for the monitor
– the ServerView Server Management manual
– the manual for the Remote Test and Diagnostic System RemoteView
– your operating system documentation
– the information files of your operating system
(see also “Related Publications” on page 165).
PRIMERGY BX600 S2 Basic Unit 9
FeaturesIntroduction
1.2Features
The PRIMERGY BX600 S2 basic unit provides a high-level infrastructure for the
installed server blades.
Server capacity
The PRIMERGY BX600 S2 basic unit provides slots for up to ten hot-pluggable
server blades. For details of the performance features of the different server
blade models, see the relevant operating manuals listed under “Related Publi-
cations” on page 165.
Communication interfaces
The PRIMERGY BX600 S2 basic unit has four slots on the back for installing
different types of communication blades which allow the installed server blades
to be connected to the Ethernet LAN or to SAN environments. The connections
can be implemented via switch blades and/or pass-thru blades.
● Ethernet LAN switch blade
To connect the server blades to the LAN the following switch blade models
are available:
Gbit Ethernet LAN switch blade (SB9) 6x1Gbit
– 10 internal 1Gbit downlink ports to the server blades
– 6 external 1Gbit uplink ports (RJ45)
Gbit Ethernet LAN switch blade (SB9) 10Gbit multi-mode
– 10 internal 1Gbit downlink ports to the server blades
– 6 external 1Gbit uplink ports (RJ45)
– 2 external 10Gbit uplink ports (1xSFP, 1xCX4)
Cisco Catalyst Blade Switch 3040
– 10 internal 10 1Gbit downlink ports to the server blades
– 2 external 10/100/1000BASE-T copper Gigabit Ethernet uplink
ports
– 4 external uplink ports via Cisco SFP modules for 1000BASE-SX
Fibre Optic and 10/100/1000BASE-T copper)
10PRIMERGY BX600 S2 Basic Unit
IntroductionFeatures
10 Gbit switch blade 10/2
– 10 internal 10 Gbit/s ports to the server blades
– 2 external 10 Gbit/s ports with optional X2 transceiver modules for
Fiber optical or CX4 copper cable
I The 10 Gbit switch blade 10/2 only supports server blades,
each equipped with a 10 GbE daughter card.
All switch blades are hot-swappable. By installing two switch blades,
redundant LAN connections can be provided for the server blades.
● Ethernet LAN Pass-Thru-Blade
The Ethernet LAN Pass-Thru-Blade is an alternative to the switch blade. It
provides direct (“pass-thru”) connections to the LAN for the onboard LAN
controllers and the optional Gigabit Ethernet I/O modules of the server
blades. The Ethernet LAN Pass-Thru-Blade has ten RJ45 connectors.
● Fibre Channel pass-thru blade
The PRIMERGY BX600 S2 basic unit can have one or two Fibre Channel
pass-thru blades to provide Fibre Channel functionality for the installed
server blades. A Fibre Channel (FC) pass-thru blade offers 10 ports for
bypass connections between FC daughter cards installed in the server
blades and the optical transceivers for serial FC I/O and general I/O signals.
● Fibre Channel switch blade
The FC switch blade is an alternative to the FC pass-thru blade. An FC
switch blade provides the FC daughter cards of the server blades with up to
ten internal fabric ports and up to four external fabric ports. The complete
Brocade Fabric OS 5.0.4 scope of supply and services is available as an
operating system for the FC switch blade.
Management blade
The PRIMERGY BX600 S2 basic unit accommodates two hot-swappable,
redundant management blades with an integrated management solution for
complete remote administration of the system.
PRIMERGY BX600 S2 Basic Unit 11
FeaturesIntroduction
KVM-Blade
For administering the server blades, the PRIMERGY BX600 S2 basic unit offers
a KVM blade, which allows the individual server blades to be connected to a
console.
– The standard KVM blade allows a monitor, PS2 keyboard and PS2 mouse
to be connected for local administration of the server blades.
– The adv. KVM blade offers the same functionality as the standard version
of the KVM blade plus a LAN port for connecting a Web-based console.
– The digital KVM blade offers the same functionality as the standard version
of the KVM blade plus a LAN port for connecting a Web-based console.
Power Supply
Up to four hot-swappable power supply units which adjust automatically to any
power voltage in the range 200 - 240 V in a 2+2 redundant power supply configuration ensure enough power for the system. If one of these units fails, the
others ensure that operation continues unimpaired. The defective power supply
unit can be replaced during operation (hot-swap).
Ventilation
The system is kept cool by three fans in each power supply unit and four single
fans, with two of them mounted one after the other in a housing in the rear
chassis. This configuration is redundant and hot-swappable.
High Level of Availability and Failure Protection
When memory data is accessed, 1-bit errors in the main memory are recognized and automatically corrected with the ECC (Error Correcting Code)
method.
ASR&R (Automatic Server Reconfiguration and Restart) restarts the system in
the case of an error and automatically “hides” the defective system components.
The PDA (Prefailure Detection and Analyzing) technology from Fujitsu Siemens
Computers analyzes and monitors all components relevant for system reliability.
The hot-swappable components provide additional failure protection. Failure
protection on a complete blade system is ensured by up to four redundant, hotswap power supply units (PSU), as well as hot-swap, redundant fans.
12PRIMERGY BX600 S2 Basic Unit
IntroductionFeatures
Server Management
Server management is implemented via the supplied ServerView software and
PDA (Prefailure Detection and Analyzing) technology from Fujitsu Siemens
Computers. PDA warns of system errors or overloading before they occur so
that preventive measures can be taken.
ServerView allows the management of all PRIMERGY servers in the network via
a central console. Here ServerView supports the following functions:
● Remote startup (Wake On LAN)
● Temperature monitoring of the CPU and the surrounding area
● Watchdog timer for Automatic Server Reconfiguration and Restart (ASR&R)
in the event of memory modules or processors failing
● Power monitoring
● End-of-life monitoring of the fans with timely notification before a failure
● Watchdog timer for operating system monitoring and application monitoring
with ASR&R
Deployment software makes installing multiple servers fast and easy. For further
information, see the corresponding documentation (see “Related Publications”
on page 165).
Information on server management with ServerView is provided in the associated
documentation (see also “Related Publications” on page 165).
ServerStart
You can configure the server quickly and precisely with the ServerStart software
provided. User-guided menus are available for installing the server operating
systems.
Service and Support
PRIMERGY servers are service-friendly and modular, thus allowing quick and
easy maintenance.
I For easy and immediate recognition, the levers or handles and locking
buttons (touch points) of the locking mechanisms for the different components have the color green.
PRIMERGY BX600 S2 Basic Unit 13
Notational ConventionsIntroduction
The flash EPROM program supplied with the Fujitsu Siemens utilities supports
fast BIOS update. The two redundant and hot-swappable management blades
with independent management LAN and COM ports ensure complete remote
control. Together they facilitate remote diagnosis for system analysis, remote
configuration and remote restart, should the operating system or hardware fail.
1.3Notational Conventions
The following notational conventions are used in this manual:
Italicsindicate commands, menu items or software programs.
“Quotation marks”indicate names of chapters and terms that should be
emphasized.
ÊText which follows this symbol describes activities that
must be performed in the order given.
V CAUTION!Pay particular attention to text marked with this symbol.
Failure to observe this warning may endanger your life,
damage the server, or lead to loss of data.
IThis symbol introduces supplementary information,
remarks and tips.
Table 1: Notational conventions
14PRIMERGY BX600 S2 Basic Unit
IntroductionTechnical Data
1.4Technical Data
Electrical Data (single power supply unit)
Rated voltage range 200 - 240 V
Rated frequency 50 Hz - 60 Hz
Max. rated current230V / 11,6 A
Max. active power230 V / 2650 W
Max. apparent power2680 VA (230V)
Thermal dissipation2050 kJ/h
Protection classI
Electrical Data (basic unit without server blades)
Power consumption360 W
Thermal dissipation1300 kJ/h
Compliance Standards
Product safety and ergonomics IEC 60950 / EN 60950 UL 1950 3rd Edition,
CSA 22.2 No. 950
Electromagnetic compatibilityFCC class A
Emitted interferenceEN 55022 class A
Harmonic currentEN 61000-3-2
Noise immunityEN 55024
Width446 mm
Installation depth740 mm
Height307 mm oder 7 HE
Weight
max. 131.5 kg (depending on the configuration)
16PRIMERGY BX600 S2 Basic Unit
IntroductionTechnical Data
Environmental Conditions
Environment class 3K2
Environment class 2K2
DIN IEC 721 section 3-3
DIN IEC 721section 3-2
Temperature:
Operation (3K2)
Transport (2K2)
5 ºC .... 35 ºC
-20 °C .... 60 °C
Relative humidity10%...85%
Condensation during operation must be avoided.
Noise Level
Sound power level L
(ISO 7779)7.8 BA
WAd
Sound pressure level at bystander position
(ISO 9296)
L
pAm
≤ 59 dB(A) (in the
standard configuration)
PRIMERGY BX600 S2 Basic Unit 17
2Overview: Basic Unit Installation
Steps
In this chapter you will find an overview of the steps necessary to install your
BX600 S2 basic unit. Links guide you to sections where you can find more
detailed information on the individual steps.
Ê Before you begin, please read the chapter “Important Notes” beginning on
page 21, especially the section “Notes on Safety”.
Ê Unpack the system, check the contents of the package for visible transport
damage, and check whether the delivery matches the details in the delivery
note (see section 4.2 on page 34).
Ê Mount the system in the rack (see section 4.3 on page 35 and also the layout
arrangement on the order lists).
Ê Cable the system (see section 4.4 on page 41). Please also see the section
“Cable Routing” on page 43 and the section “Instructions on Connecting and
Disconnecting Cables” on page 45.
Ê Connect the system to the mains voltage (see section 4.5 on page 46).
Ê Familiarize yourself with the operating and indicator elements on the front
and rear sides of the BX600 S2 basic unit (see chapter 5 beginning on
page 49).
Ê Insert the server blades into the slots in the front of the BX600 S2 basic unit
(see chapter 7 on page 71).
Ê Configure the management blades (see section 5.3 on page 55) so that you
can perform further administration of the blade server system via LAN.
Ê Install the desired operating systems and applications on the server blades.
To do so, you have the following options:
– Cloning a server blade from a remote image server with RemoteDeploy
Recommended if the following requirements are satisfied:
– the RemoteDeploy software is available
– an appropriate cloning image is available
– deployment server and LAN connection are available
PRIMERGY BX600 S2 Basic Unit 19
Overview: Basic Unit Installation Steps
– Remote installation with ServerStart
This installation method is recommended if a LAN connection and a
DHCP server are available but the requirements for cloning are not
satisfied.
– Local installation with or without ServerStart
Since the local installation is the least convenient installation method, it
is only recommended if the requirements for remote installation or
cloning are not satisfied.
If you wish to install an operating system that is not supported by ServerStart, you can perform the installation directly without using ServerStart.
I For further information on remote or local installation of server blades,
please see the ServerStart manual, which contains a “Quick Step
Guide” as well as a detailed description of the different installation
options and installation wizards. A print version of the ServerStart
manual is included in the PRIMERGY ServerView Suite, which comes
with the BX600 S2 basic unit. A PDF version of the manual is
contained on the PRIMERGY ServerBooks DVD.
Cloning of server blades is described in the RemoteDeploy manual
(print version delivered with RemoteDeploy, PDF version contained
on the PRIMERGY ServerBooks DVD).
20PRIMERGY BX600 S2 Basic Unit
3Important Notes
In this chapter you will find essential information on safety when working with
your system.
3.1Notes on Safety
I You will also find the following safety instructions in the manual entitled
“Safety“, which also includes additional notes on the guarantee and
ergonomics.
This device complies with the relevant safety regulations for data processing
equipment, including electronic office machines for use in an office
environment.
If you have any questions, please contact your sales outlet or the customer
service center of Fujitsu Siemens Computers.
V CAUTION!
The actions described in these instructions should only be performed by
technicians, service personnel or technical specialists. Equipment
repairs should only be performed by qualified staff. Any failure to observe
the guidelines in this manual could expose the user to risks (electric
shock, fire hazards) and could also damage the equipment. Note that
any unauthorized opening of the device will result in the invalidation of
the warranty and exclusion from all liability.
PRIMERGY BX600 S2 Basic Unit 21
Notes on SafetyImportant Notes
Before Setting Up
V CAUTION!
● During installation and before operating the device, observe the
instructions on environmental conditions for your device in the section
“Technical Data” on page 15.
● If the device is brought in from a cold environment, condensation may
form on both the inside and outside of the machine.
Before operating the device, wait until it is absolutely dry and has
reached approximately the same temperature as the installation site.
Failure to observe these guidelines can lead to physical damage of
the device.
● Transport the device only in the original packaging or in packaging
which protects it from knocks and jolts.
Installation and Operation
V CAUTION!
● For safety reasons, make sure you read any warning labels when
removing modules from the server.
● Beware of energy hazards on the plug-in contacts of the midplane. A
short circuit on these connections can lead to damage to the system.
● PRIMERGY BX620 S4 server blades are not for use in slots 4 an 10
of the PRIMERGY BX600 S2 basic unit.
● If the server is integrated in a (rack) installation that receives power
from an industrial (public) power supply network with the IEC309
connector, the (public) power supply protection must comply with the
requirements for the non-industrial (public) power supply networks for
the type-A connector.
● For the PRIMERGY BX600 S2 basic unit only 2100W PSUs are
allowed (Product no. A3C40073262)! The 1200W PSUs of the
PRIMERGY BX600 S1 basic unit is not allowed for the PRIMERGY
BX600 S2 basic unit.
The 2100W PSU is not allowed for the PRIMERGY BX600 S1 basic
unit.
22PRIMERGY BX600 S2 Basic Unit
Important NotesNotes on Safety
● Make sure that the PRIMERGY BX600 S2 basic unit is connected to
the mains for at least one minute before pressing the power ON/OFF
button to switch the system ON.
V CAUTION!
● The server automatically adjusts to a mains voltage of 200 - 240 V.
The server may only be put into operation if the mains voltage range
set on the server corresponds to the local mains voltage.
● This device has safety-tested power cables and must only be
connected to properly grounded power sockets or CEE sockets.
● The power button does not disconnect the device from the mains
voltage. To completely disconnect it from the mains voltage, the
power plugs must be removed from the power socket.
● Data transmission cables must not be connected or disconnected
during a thunderstorm (lightning hazard).
● Make sure that no objects (such as bracelets or paper clips) or liquids
fall/spill into the device (risk of electric shock or short circuit).
● Data cables must be adequately shielded to avoid interference.
● The LAN wiring must comply with the standards EN 50173 and EN
50174-1/2. The minimum requirement is a protected LAN line of
category 5 for 10/100 MBps Ethernet, and/or of category 5e for
Gigabit Ethernet. The requirements of the specification ISO/IEC
11801 must be observed.
● In an emergency (e.g. damage to housing, control elements or
cables, the ingress of liquids or foreign bodies), switch the unit off
immediately, pull the power plug out of the grounding outlet or the
CEE outlet, and contact Service.
● Proper operation of the device (in accordance with IEC 60950/DIN
EN 60950) is only ensured if the casing is completely assembled and
the dummy units for the installation openings have been put in place
(electric shock, cooling, fire protection, interference suppression).
● Install only system extensions that satisfy the requirements and rules
governing safety and electromagnetic compatibility and relating to
telecommunications terminal equipment. If you install other extensions, you may damage the system or violate the safety regulations
PRIMERGY BX600 S2 Basic Unit 23
Notes on SafetyImportant Notes
and regulations on RFI suppression. Information on which system
extensions are suitable can be obtained from the customer service
center or your sales outlet.
V CAUTION!
● The components (e.g. power supply) marked with a warning label
(e.g. lightning symbol) may only be opened, removed or exchanged
by authorized, qualified personnel. The hot-swap or hot-plug components are exceptions to this rule.
● The warranty is invalidated if the device is damaged during the instal-
lation or replacement of system extensions.
● You may set only those resolutions and refresh rates specified in the
“Technical data” section of the monitor description. Otherwise, you
may damage your monitor. If you are in any doubt, contact your sales
outlet or customer service center.
Batteries
V CAUTION!
● Incorrect replacement of batteries may lead to a risk of explosion. The
battery may only be replaced with an identical battery or with a type
recommended by the manufacturer.
● Do not throw batteries into the trash can. They must be disposed of
in accordance with local regulations concerning special waste.
● Replace the lithium battery on the relevant components according to
the instructions in this manual.
● All batteries containing pollutants are marked with a symbol (a
crossed-out garbage can) as well as the chemical symbol for the
heavy metal which classifies it as a pollutant:
Cd Cadmium
Hg Mercury
Pb Lead
Other Important Notes:
● Keep this operating manual and all additional documentation together with
the device.
If you pass on the device to third parties, you should also pass on the
complete documentation.
24PRIMERGY BX600 S2 Basic Unit
Important NotesComponents With Electrostatic-Sensitive Devices
3.2Components With Electrostatic-Sensitive
Devices
Electrostatic-sensitive components are identified by the following sticker:
Figure 2: ESD label
When you handle components fitted with ESDs, you must observe the following
points under all circumstances:
● Always discharge static build-up (e.g. by touching a grounded object) before
working.
● The equipment and tools you use must be free of static charge.
● Always hold components with ESDs by their edges.
● Do not touch any exposed pins or conductors on a component.
● Use a grounding cable designed for this purpose to connect yourself to the
system unit as you install components.
● Place all components on a static-proof base.
I You will find a detailed description of how to handle ESD components in
the relevant European or international standards (EN 61340-5-1,
ANSI/ESD S20.20).
3.3CE Certificate
The shipped version of this device complies with the requirements
of the EEC directives 89/336/EEC “Electromagnetic compatibility”
and 73/23/EEC “Low voltage directive”. The device therefore
qualifies for the CE certificate (CE=Communauté Européenne).
PRIMERGY BX600 S2 Basic Unit 25
FCC Class A Compliance StatementImportant Notes
3.4FCC Class A Compliance Statement
If there is an FCC statement on the device, then:
The following statement applies to the products covered in this manual, unless
otherwise specified herein. The statement for other products will appear in the
accompanying documentation.
NOTE:
This equipment has been tested and found to comply with the limits for a
“Class A” digital device, pursuant to Part 15 of the FCC rules, and meets all
requirements of the Canadian Interference-Causing Equipment Standard
ICES-003 for digital apparatus. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in strict accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined
by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between equipment and the receiver.
● Connect the equipment to an outlet on a circuit different from that to which
the receiver is connected.
● Consult the dealer or an experienced radio/TV technician for help.
Fujitsu Siemens Computers is not responsible for any radio or television interference caused by unauthorized modifications of this equipment or the substitution or attachment of connecting cables and equipment other than those
specified by Fujitsu Siemens Computers. The correction of interferences
caused by such unauthorized modification, substitution or attachment will be the
responsibility of the user.
The use of shielded I/O cables is required when connecting this equipment to
any and all optional peripheral or host devices. Failure to do so may violate FCC
and ICES rules.
26PRIMERGY BX600 S2 Basic Unit
Important NotesTransporting the Basic Unit
3.5Transporting the Basic Unit
V CAUTION!
Transport the PRIMERGY BX600 S2 basic unit only in its original
packaging or in a packaging which protects it from knocks and jolts. Do
not unpack the basic unit until you have finished transporting it.
For safety reasons, at least two people are needed to install the basic unit
because of its weight and size.
Before lifting the basic unit into the rack, remove server blades, fan units
and power supplies from the system unit to reduce weight.
Use the handles on the front and the fold-away handles on the long sides
to lift or carry the base unit.
Never lift or transport the basic unit using the handles on the rear.
PRIMERGY BX600 S2 Basic Unit 27
Notes on Installing in the RackImportant Notes
3.6Notes on Installing in the Rack
V CAUTION!
● For safety reasons, at least two people are needed to install the
basic unit because of its weight and size.
● For lifting the basic unit, use the handles on the front and the fold-out
handles on the long sides of the chassis.
● Before lifting the basic unit into the rack, remove server blades, fan
units and power supplies from the system unit to reduce weight.
● For lifting the basic unit, use the handles on the front and the fold-out
handles on the long sides of the chassis.
● Never lift or transport the server using the handles on the rear.
● For safety reasons only one unit may be withdrawn from the rack at a
time when performing assembly or service work.
● Ensure that the anti-tilt bracket is correctly mounted when you set up
the rack.
● If more than one unit is withdrawn from the rack at any one time, the
rack is in danger of tilting forward.
● When connecting and disconnecting cables, read the relevant notes
in the “Important notes” chapter in the technical manual for the
relevant rack. The technical manual is supplied with the corresponding rack.
● The power connection for the rack must be installed by an authorized
technician (electrician).
● If the server is integrated in a (rack) installation that receives power
from an industrial (public) power supply network with the IEC309
connector, the (public) power supply protection must comply with the
requirements for the non-industrial (public) power supply networks for
the type-A connector.
● The power supply for the rack should be divided amongst the three
phases of a three-phase power connection.
28PRIMERGY BX600 S2 Basic Unit
Important NotesEnvironmental Protection
3.7Environmental Protection
Environmentally Friendly Product Design and Development
This product has been designed in accordance with the Fujitsu Siemens
Computers standards for ”environmentally friendly product design and development“. This means that the designers have taken into account important
criteria such as durability, selection of materials and coding, emissions,
packaging, the ease with which the product can be dismantled and the extent to
which it can be recycled.
This saves resources and thus reduces the harm done to the environment.
Notes on Saving Energy
Devices that do not have to be on permanently should not be switched on until
they need to be used and should be switched off during long breaks and on
completion of work
Notes on Packaging
Please do not throw away the packaging. It may be needed later for transporting
your system unit. If possible, devices should be transported in their original
packaging.
Notes on Dealing with Consumables
Please dispose of printer consumables and batteries in accordance with local
government regulations.
Do not throw batteries and accumulators into the household waste. They must
be disposed of in accordance with local regulations concerning special waste
(see also “Returning Batteries” on page 31).
Notes on Labeling Plastic Housing Parts
Please avoid attaching your own labels to plastic housing parts wherever
possible, since this makes it difficult to recycle them.
PRIMERGY BX600 S2 Basic Unit 29
Environmental ProtectionImportant Notes
Returning Used Electrical and Electronic Devices in EU Countries
– Separate collection
Users of electrical and electronic devices are obligated to collect used
devices separately. Electrical (electronic) used devices may not be disposed
of together with unsorted household refuse. The separate collection is a
condition for reuse, recycling and utilisation of used electrical (electronic)
devices, which ensures the protection of resources.
– Return and collection systems
Electrical (electronic) used devices from private households can be returned
free of charge. To return your used device, please use the country-specific
return and collection systems available to you (see “Local Contacts” on
page 31).
The return of used devices which pose a health or safety risk for human
beings due to soiling during use may be refused.
– Reuse, recycling and utilisation
By actively using the offered return and collection systems, you make your
contribution to the reuse, recycling and utilisation of electrical (electronic)
devices.
– Effects on the environment and human health
Electrical (electronic) used devices contain parts which must be handled
selectively according to the EU directive. Separate collection and selective
treatment are the basis for environment-friendly disposal and the protection
of human health.
– Meaning of the symbol "Crossed out rubbish bin on wheels"
Electrical (electronic) devices which are marked with one of the following
symbols may not be disposed of with household refuse in accordance with
the EU directive.
Figure 3: Symbols for electrical (electronic) devices
30PRIMERGY BX600 S2 Basic Unit
Important NotesEnvironmental Protection
Returning Batteries
Batteries which are marked with one of the following symbols may not be
disposed of together with household refuse according to the applicable EU
directive.
Figure 4: Symbols for batteries
With batteries containing harmful substances, the chemical symbol for the
heavy metal contained is indicated below the waste bin.
Cd Cadmium
Hg Mercury
Pb Lead
The following applies to Germany:
– Private consumers can return batteries at the point of sale or the immediate
vicinity thereof free of charge (exception: starter batteries).
– The final consumer is obligated to return defective or used batteries to the
seller or to the return points established for this purpose.
Local Contacts
For details on take-back and reuse of devices and consumables within Europe,
contact your Fujitsu Siemens Computers branch office/subsidiary or our
recycling centre in Paderborn:
Fujitsu Siemens Computers
Recycling Center
D-33106 Paderborn
Please note the safety instructions in the chapter “Important Notes” on
page 21.
Do not expose the PRIMERGY BX600 S2 basic unit to extreme environmental conditions (see section “Technical Data” on page 15). Protect it
from dust, moisture, and heat.
4.1Installation Steps
The installation steps are described in detail in the following sections of this
chapter:
● Unpacking the basic unit (see section “Unpacking the Basic Unit” on
page 34).
● Mounting the basic unit in the rack (see section “Installing the System in the
Rack” on page 35 and also the layout arrangement on the order lists).
● Cabling the basic unit (see section “Connecting External Devices” on
page 41). See also the section “Cable Routing” on page 43 and the section
“Instructions on Connecting and Disconnecting Cables” on page 45.
● Connecting the basic unit to the mains voltage (see section “Connecting the
System to the Mains” on page 46).
PRIMERGY BX600 S2 Basic Unit 33
Unpacking the Basic UnitInstalling the Hardware
4.2Unpacking the Basic Unit
V CAUTION!
Please note the safety instructions in the chapter “Important Notes” on
page 21.
Do not unpack the PRIMERGY BX600 S2 basic unit until you have
finished transporting it.
We recommend that you do not throw away the original packaging material! It
may be required for future transportation.
Ê Unpack all the individual parts.
Ê Check the contents of the package for visible transport damage.
Ê Check whether the delivery matches the details in the delivery note.
The identification rating plate is located on the front edge of the left side of the
basic unit.
If you find transport damage or inconsistencies between the contents of the
package and the delivery note, inform your supplier immediately!
34PRIMERGY BX600 S2 Basic Unit
Installing the HardwareInstalling the System in the Rac
k
4.3Installing the System in the Rack
V CAUTION!
● For safety reasons, at least two people are required to install the
PRIMERGY BX600 S2 basic unit because of its weight and size.
● Please observe the safety precautions and references to rack instal-
lation in the chapter “Important Notes” on page 21.
● The rack may tip over if more than one unit is removed at the same
time.
Requirements of the Rack
The rack systems from Fujitsu Siemens Computers GmbH (PRIMECENTER
rack; DataCenter rack) fully support the installation of the PRIMERGY server
systems. Installation in the common rack systems of other manufacturers (3rd-party rack) is supported to a large degree.
To accommodate the ventilation concept and ensure proper ventilation of the
components in the rack, any unused areas must be closed using dummy covers.
The unit is connected to the power supply via an external distribution board or
a UPS device.
The main features of the rack systems from Fujitsu Siemens Computers GmbH
are:
PRIMECENTER/DataCenter Rack
– Frontally bolted rails.
The rails have a linear alignment option to also allow adjustment to different
rack depths.
– Extended cable management within the lateral rack area.
The following applies to rack systems from third-party manufacturers:
PRIMERGY BX600 S2 Basic Unit 35
Installing the System in the RackInstalling the Hardware
3rd-Party Rack
Certain framework conditions must be fulfilled:
– Installation dimensions (see the dimensions shown in figure 5 on page 37).
1rack front
2rack rear
Arack depth (comparison PRIMECENTER rack 940/1000 mm)
Brack width (comparison PRIMECENTER rack 700 mm)
Cclearance of the 19-inch installation level
C1front 19-inch installation level
C2rear 19-inch installation level
Darea for cable routing (cable area depth) and ventilation
Earea for front panel and ventilation
Fright and left area for support systems
PPRIMERGY installation depth
a1front left support upright
a2front right support upright
b1rear left support upright
b2rear right support upright
– Please ensure that the security mechanism (e.g. stopper or retention
system) on the server is working.
– The rack support uprights must allow the rails to be screwed on at the front.
– Frontally bolted rails.
The rails have with a linear alignment option to also allow adjustment to
different rack depths.
– No support for the cable management delivered with the mounting kit. This
cable management is customized for the Fujitsu Siemens Computers
PRIMECENTER rack.
– Climatic conditions.
For the ventilation of the installed server, there must be sufficiently large
gaps for air intake at the front of the rack and air discharge at the back of the
rack.
36PRIMERGY BX600 S2 Basic Unit
Installing the HardwareInstalling the System in the Rac
k
In principle the ventilation concept allows for the necessary cooling through
horizontal self-ventilation of the installed devices (air flow from the front to
the rear).
– Power supply.
For installation in 3rd-party racks, you must ensure that appropriate socket
strips are present.
Figure 5: Mechanical conditions
PRIMERGY BX600 S2 Basic Unit 37
Installing the System in the RackInstalling the Hardware
4.3.1Mounting the Assembly Kit
Mounting the server in the PRIMECENTER/DataCenter Rack requires the
following parts:
– two support brackets
– two carrier rails (assembled)
– 12 plug washers (figure 7 on page 39) and screws
I For general information see the technical manual for the relevant rack
(see also “Related Publications” on page 165).
To mount the PRIMERGY BX600 S2 basic unit in the rack, you must first mount
two support brackets on the rear left support upright of the rack. The first one
must be mounted level with the lower edge of the device, while the second must
be mounted level with the upper edge of the first. The brackets are used for the
rear fixing of the left carrier rail.
Ê See the installation instructions in the technical manual for the relevant rack
model.
Ê Mark the position of the lower edge of the basic unit on the support uprights.
1
Figure 6: Mounting the support brackets
Ê Place the first support bracket at the appropriate height (level with the lower
edge of the device) on the left rear support upright by inserting the
positioning nubs (1 in figure 6) in the corresponding holes of the support
upright.
Ê Place the plug washers in the holes of the support uprights and secure the
bracket with two screws.
38PRIMERGY BX600 S2 Basic Unit
Installing the HardwareInstalling the System in the Rac
k
Ê Repeat the procedure with the second support bracket.
Note that the second bracket will be mounted level with the upper edge of
the first support bracket mounted (see figure 6 on page 38).
Figure 7: Mounting the left carrier rail
Ê Undo the six screws (1) for adjusting the rail length and place the guide lugs
(a) in the corresponding holes of the support brackets.
Ê Place three plug washers (3) in the appropriate holes of the support brackets
and, while holding the rail in place, fasten it with three screws.
Ê Place two plug washers in the holes of the front left support upright at the
marked attachment points, adjust the rail length (2) and, while holding the
rail in place, fasten it with three screws (4).
Ê Pull the carrier rail of the rack-mounting kit forward as far as possible in the
direction of the arrow (2).
Ê Fasten the six screws for adjusting the rail length (1).
Ê Repeat the procedure for the second rail. Note that for this rail no support
bracket is necessary.
PRIMERGY BX600 S2 Basic Unit 39
Installing the System in the RackInstalling the Hardware
4.3.2Mounting/Removing the Basic Unit
V CAUTION!
For safety reasons, at least two people are required to mount or
remove the PRIMERGY BX600 S2 basic unit because of its weight
and size.
Please note the relevant safety instructions in section “Notes on Installing
in the Rack” on page 28.
Before lifting the basic unit into the rack, remove server blades, fan units
and power supplies from the basic unit to reduce weight.
Figure 8: Mounting the basic unit
Ê Note the slot assignment of the server blades so that you can insert them
correctly again once you have lifted the basic unit into the rack.
Ê Remove server blades, fan units and power supplies from the system unit to
reduce weight (for assembly instructions see section “Adding a Server Blade
to the Basic Unit” on page 76, section “Replacing a Power Supply Unit” on
page 142 and section “Replacing the Fan Unit” on page 151).
Ê Lift the basic unit onto the two carrier rails.
Ê Slide the basic unit into the rack (1).
Ê Secure the basic unit in the rack using the four knurled screws (2).
40PRIMERGY BX600 S2 Basic Unit
Installing the HardwareConnecting External Devices
Ê Insert the server blades into their slots (see section “Adding a Server Blade
to the Basic Unit” on page 76). Return the power supply units and fan units
to the basic unit (see section “Replacing a Power Supply Unit” on page 142
and section “Replacing the Fan Unit” on page 151).
You remove the basic unit by following the above steps in reverse order:
V CAUTION!
Please note the relevant safety instructions in section “Notes on Installing
in the Rack” on page 28.
Ê Note the slot assignment of the server blades so that you can insert them
correctly again after you have removed the basic unit from the rack.
Ê Remove server blades, fan units and power supplies from the basic unit to
reduce weight.
Ê Remove the four knurled screws.
Ê Pull out the basic unit and carefully remove it from the rack.
4.4Connecting External Devices
The external connectors of the PRIMERGY BX600 S2 basic unit are located on
the rear of the basic unit. The external connectors of the server blades are
located on the front of the basic unit. For information on these connectors see
the operating manuals of the different server blade types (see “Related Publica-
tions” on page 165).
PRIMERGY BX600 S2 Basic Unit 41
Connecting External DevicesInstalling the Hardware
Connectors on the back of the basic unit
1
2
3
4
Figure 9: Connectors for external devices
1, 9Slots for various types I/O blades, connected to the server blades on-board NICs.
These I/O blades can be Ethernet switch blades or Ethernet pass-thru blades, see
“Ethernet LAN Switch Blades” on page 81 and “Ethernet Pass-Thru Blade” on
page 99.
2, 8Slots for various types I/O blades, connected to the optional I/O modules of the
server blades. These I/O blades can be Ethernet or Fibre Channel switch blades or
pass-thru blades, see “Ethernet LAN Switch Blades” on page 81, “Ethernet Pass-
Thru Blade” on page 99, “Fibre Channel Switch Blade” on page 105 and “Fibre
Channel Pass-Thru Blade” on page 113.
3Serial port connector on management blade 2 (see also figure 53 on page 100).
Standard serial port, management communication port.
4LAN connector on management blade 2 (see also figure 53 on page 100). LAN
port, RJ45, 10Mb management LAN.
5Serial port connector on management blade 1 (see also figure 53 on page 100).
Standard serial port, management communication port.
6LAN connector on management blade 1 (see also figure 53 on page 100). LAN
port, RJ45, 10Mb management LAN.
7KVM connector on rear KVM blade, which offers VGA, PS2 keyboard and mouse
support via a special cable (see figure 10 below). The Adv. KVM bladeand the digital
KVM blade also offers a LAN connectors (RJ45, 10 Mb) (see also figure 85 on
page 134).
9
8
7
6
5
42PRIMERGY BX600 S2 Basic Unit
Installing the HardwareConnecting External Devices
VGAmouse
Figure 10: Special cable
keyboard
(purple)
(green)
to rear
KVM board
4.4.1Cable Routing
The cables are routed directly on the rack support uprights.
PCI Cards with Cable at the Front
If a PCI expansion module is installed in a server blade, you will have to connect
the PCI port with an external device on the back of the rack. To route the cable
from the front to the back of the rack, use the side slots of the rack with a cable
bezel as shown in figure 11 below. You may also route the cable to the back of
the rack, using the space below the basic unit.
PRIMERGY BX600 S2 Basic Unit 43
Connecting External DevicesInstalling the Hardware
Figure 11: Cable routing from the front to the back of the server (top view)
Server blades with SCSI boards installed via PCI expansion modules can only
be installed in slots 5 and 6 of the basic unit. This is why about 100 mm of space
is required in front of the server due to the bend radius of the SCSI cable. The
curved design of the PRIMECENTER rack door ensures that there is sufficient
room for slots 5 and 6.
100mm
Figure 12: Routing a SCSI cable
44PRIMERGY BX600 S2 Basic Unit
Installing the HardwareConnecting External Devices
4.4.2Instructions on Connecting and Disconnecting
Cables
V CAUTION!
Make sure you read the documentation on the devices before connecting
them.
Do not connect or disconnect data cables during a thunderstorm.
When removing a cable, always hold it by the plug.
Connect and disconnect the cables in the order described below.
Connecting Cables
Ê Turn off all power and equipment switches.
Ê Pull all power plugs out of grounded power sockets or CEE sockets.
Ê Plug all cables into the system and peripherals. Secure the data trans-
mission cable connections (e.g. nut retention).
Ê Plug all data communication cables into the utility sockets.
Ê Plug all power cables into the grounded power sockets or CEE sockets.
Disconnecting Cables
Ê Turn off all power and equipment switches.
Ê Pull all power plugs out of grounded power sockets or CEE sockets.
Ê Unplug all data communication cables from the utility sockets.
Ê Undo the nut retention on the connector housings and pull the corre-
sponding cables out of the basic unit and the peripherals.
PRIMERGY BX600 S2 Basic Unit 45
Connecting the System to the MainsInstalling the Hardware
4.5Connecting the System to the Mains
There are slots for four hot-swappable 2100 W power supply units on the rear
of the basic unit. The base system is equipped with two power supply units.
V CAUTION!
● Make sure you observe the information on determining how many
power supply units are required (see chapter “Power Supply
Concept” on page 139).
● The power supply units switch on automatically at a mains voltage
between 200 - 240 V. The base unit may only be commissioned if the
local mains voltage is within the voltage range of the system.
● The 2100 W power supply units may only be connected to 16 Amp
grounding outlets or CEE outlets. When ordering the base unit,
indicate the type of outlet available at the installation site. This will
allow us to supply a cable with suitable inlet connectors for nonheating appliances with the order.
2
1
Figure 13: Connecting the basic unit to the mains
Ê First connect the insulated connector of the power cables to the power
supply units of the basic unit (1), and then plug the power plug (2) into the
USV, Power Distribution Unit (PDU) or into an external socket.
V CAUTION!
Always connect the power cable to the power supply units first, and then
to the mains.
46PRIMERGY BX600 S2 Basic Unit
Installing the HardwareConnecting the System to the Mains
I Please make sure that each of the power supply units is connected to a
different phase. This will provide you with additional phase redundancy
for high availability configurations. If one phase has failed, the power
supply units connected to the other phases keep active. You can get full
phase redundancy with up to three power supply units. With four power
supply units, two of them are to be connected to one phase (see also
“Related Publications” on page 165).
Phase redundancy is possible in regions, where a single phase provides
200 - 240V; in other regions with lower single phase voltage, two phases
must be coupled and complete phase redundancy thus is not possible.
PRIMERGY BX600 S2 Basic Unit 47
5Preparation for Use and
Operation
V CAUTION!
● Please note the safety instructions in the chapter “Important Notes”
on page 21.
● Beware of energy hazards on the plug-in contacts of the midplane. A
short circuit on these connections can lead to damage to the system.
All unoccupied component slots are fitted with corresponding dummy modules
to ensure that the electromagnetic emission properties of the system are
observed and that the system components are cooled properly.
Figure 14: PRIMERGY BX600 S2 basic unit
PRIMERGY BX600 S2 Basic Unit 49
Operating and Indicator ElementsPreparation for Use and Operation
5.1Operating and Indicator Elements of the
Basic Unit
5.1.1The Front
1234
Figure 15: System operating and indicator elements on the front
1Power indicator (bicolor LED)
Lights amber: basic unit is ready for powering ON (5 V standby
power present).
Lights green: basic unit is switched ON.
2System power ON/OFF button
When the basic unit is switched OFF, pressing the power button for 2
seconds will switch it ON.
When the basic unit is operating and the button is kept pressed for 4
seconds, the basic unit will be gracefully shut down.
When the basic unit is switched ON, pressing the power button for 10
seconds will switch it OFF.
50PRIMERGY BX600 S2 Basic Unit
Preparation for Use and OperationOperating and Indicator Elements
3Front identify/Fault indicator (amber LED)
Unlit:The system is normal and not highlighted.
If power indicator LED lights green, basic unit is
switched ON (5 V standby power present).
Lights amber:This system has been selected by pressing the front or
rear identify button.
To deactivate, press one of the buttons again.
You also can activate the LED via CLI.
Blinks amber:The system is directly controlled via the management
blade user interface.
or
SUM error: A malfunction has occurred in the system.
4Front identify button
Pressing this button lights up the integrated front identify indicator. The
ID
front and rear identify indicators will be synchronized.
PRIMERGY BX600 S2 Basic Unit 51
Operating and Indicator ElementsPreparation for Use and Operation
5.1.2The Rear
12
Figure 16: System operating and indicator elements on the rear
1Rear identify button
1
Pressing this button lights up the rear identify indicator. The front and
rear identify indicators will be synchronized.
2Rear identify/Fault indicator (green LED)
1
Lights green:This system has been selected for identification
(identify LED is lit) by pressing the front or rear identify
button.
To deselect the system, press either of the identify
buttons again.
Blinks green:SUM error: A malfunction has occurred in the system.
1
Figure 16 shows the operator panel of the standard KVM blade. For further information on
this KVM blade and on the adv. KVM blade, see chapter “KVM Blade” on page 133.
52PRIMERGY BX600 S2 Basic Unit
Preparation for Use and OperationSwitching the Blade Server ON/OFF
5.2Switching the Basic Unit ON/OFF
V CAUTION!
● Make sure that the PRIMERGY BX600 S2 basic unit is connected to
the mains for at least one minute before pressing the power ON/OFF
button to switch the system ON.
● If, after switching the basic unit ON, you can only see flickering stripes
on the attached monitor, switch the system OFF immediately (see
chapter “Troubleshooting and Tips” on page 155).
● The system ON/OFF power button does not disconnect the system
from the mains voltage. To completely disconnect it, you must remove
the power plugs from the sockets.
Switching ON the Basic Unit ( Basic Unit is Powered OFF)
Ê Press the basic unit power ON/OFF button (position 2 in figure 15 on
page 50) for 2 seconds. Depending on the BIOS settings, the server blades
can be switched on automatically one after another according to the slot
numbering (see figure 29 on page 72).
Ê If necessary, switch ON the required server blades (see “Switching the
Server Blades ON/OFF” on page 54).
The basic unit is switched ON and the activated server blades perform a system
test and boot the operating system.
Switching OFF the Basic Unit (System is Powered ON)
The basic unit is operating (server blades are also switched ON).
Ê For graceful shutdown of all server blades, press the system power
ON/OFF button (position 2 on figure 15 on page 50) for 4 seconds. The
server blades will then be powered OFF.
Ê For hard shutdown of all server blades, press the system power ON/OFF
button (position 2 on figure 15 on page 50) for 10 seconds. The server
blades will be powered OFF immediately.
PRIMERGY BX600 S2 Basic Unit 53
Switching the Blade Server ON/OFFPreparation for Use and Operation
Other Ways to Switch ON the Basic Unit
– Using the web interface of the management blade
Using the web interface of the management blade, you can switch on the
basic unit as well as each of the server blades.
– After power failure
The basic unit automatically switches ON following a power failure, and the
server blades which were operating before the power failure are booted
automatically.
Switching the Server Blades ON/OFF
The basic unit must be powered ON.
The server blade can be switched ON and OFF in the following ways:
– To switch ON the server blade, press the power button of the server blade
(see the manual for the relevant server blade type).
To switch OFF the server blade, press the power button of the server blade
(see the manual for the relevant server blade type) for 4 seconds.
– Specified switch-ON time/switch-OFF time
The server blade is switched ON or OFF at a time specified in the ServerView
program.
– Ring indicator
The server blade is switched ON via an external modem.
– After power failure
The server blade automatically switches ON following a power failure
(depending on the settings in the BIOS).
54PRIMERGY BX600 S2 Basic Unit
Preparation for Use and OperationManagement Blade Configuration
5.3Management Blade Configuration
The two redundant management blades provide functionality for remote control
of the PRIMERGY BX600 S2 base unit over the LAN (see chapter
“Management Blade” on page 125 and the „PRIMERGY BX Blade Server
Systems: RemoteView Management Blade - User Interface Description“
manual). To commission the base unit, the LAN parameters of the management
blades must be set using a local client computer.
To configure the management blade, follow the steps listed below.
Pre-Configuration Requirements
The procedures that follow assume that the basic unit is connected to the power
line.
Cabling the System
Ê Connect the serial interface of the client (COM1) to the serial interface of the
master management blade using an RS232 cable (null modem cable).
I The master management blade is indicated by a green LED (see
section “Control and Connection Panel” on page 126).
Initial Configuration via Serial Connection to Client
Ê Open a HyperTerminal session from the client to the master management
blade. Use the following settings:
Bits per second115200
Data bits8
Parity None
Stop bit1
Flow controlNone
Terminal typeVT100
PRIMERGY BX600 S2 Basic Unit 55
Management Blade ConfigurationPreparation for Use and Operation
Once you have opened the HyperTerminal session the welcome screen of
the console menu will be displayed (see figure 17 below).
Figure 17: Welcome screen
Ê Log in as root. The initial password reads root.
V CAUTION!
Change the root password as soon as possible (see page 56). Failure
to do so may result in unauthorized access and loss of customer data.
I You can change the root password of the management blade via
menu item 6 (Username and Password) of the Management Agent menu
(see figure 19 on page 57).
When you have logged on, the main menu of the console menu will be
displayed.
Figure 18: Console menu
56PRIMERGY BX600 S2 Basic Unit
Preparation for Use and OperationManagement Blade Configuration
Ê Enter 1 to call up the Management Agent menu.
The Management Agent menu looks like this:
Figure 19: Management Agent menu.
Ê Enter 1 to call up the Management Agent Information menu.
The Management Agent Information menu provides access to the parameters
required by the LAN connection.
PRIMERGY BX600 S2 Basic Unit 57
Management Blade ConfigurationPreparation for Use and Operation
Figure 20: Management Agent Information menu
Follow the steps below to make the management blade accessible via the
LAN.
Ê Select 1 to set the IP address of the management blade.
Ê Select 2 to enter the network mask of your subnet.
Ê Select 3 to enter the IP address of your gateway.
Ê Select 18 to call up the Agent NTC Duplex Mode menu.
58PRIMERGY BX600 S2 Basic Unit
Preparation for Use and OperationManagement Blade Configuration
I The management blade LAN controller only runs at 10 Mbit/sec.
Duplex mode must be defined manually via the Agent NTC Duplex
Mode (see figure 21 below).
Figure 21: Agent NIC Duplex Mode menu
Ê Enter 2 if the preset duplex mode value needs to be altered or 0.
I The transfer rate of 10 Mbit/sec and the duplex mode of the
management blade must comply with the client LAN controller!
Automatic synchronization is not supported by the management
blade LAN controller.
Ê Enter 0 in this menu and in the preceding menus to leave the management
blade console menu.
Ê Close the HyperTerminal session.
Ê Unplug the power cable from the basic unit and plug it in again to reboot the
management blade.
I This ensures that the management blade continues to act as the
master after the restart. A restart without interruption to the power
supply would cause the master/slave assignment to change.
The management blade can now be accessed via the LAN. For more information on the management blade configuration, see the manual “PRIMERGY
BX Blade Server Systems: RemoteView Management Blade - User Interface
Description”. Information on the configuration of the various switch blade
models can be found in sparate manuals, see “Related Publications” on
page 165.
PRIMERGY BX600 S2 Basic Unit 59
Updating BX600 System ComponentsPreparation for Use and Operation
5.4Updating System Components
All files required for updating the PRIMERGY BX600 S2 basic unit components
are available from http://www.fujitsu-siemens.com/support/downloads.html.
5.4.1Updating the Server Blade Firmware (BIOS and
BMC)
You can update both the firmware of the server blade BIOS and the firmware of
the server blade BMC.
I BMC stands for Baseboard Management Controller. The BMC on the
server blade collects management information and forwards it to the
management blade.
There are two possible procedures for updating the firmware of the server blade
BIOS and the server blade BMC:
– Updating the server blade firmware from a USB floppy drive
This procedure is described in the Operating Manual for the server blade
(see “Related Publications” on page 165).
– Updating the firmware of the server blade with TFTP (see below).
Proceed as follows:
Ê Install your TFTP server software and start it.
Ê Download the TFTP update package BX600 S2_TFTP-
IMAGES_<version>.exe from the Fujitsu Siemens download server
Ê Extract the desired BIOS and/or BMC firmware files to the root directory of
the TFTP file system. For information on the image file names, see the
readme file of the update package.
Ê Check the LAN connection by pinging the relevant server blade.
Ê Update the firmware of the server blade (BIOS and BMC).
You have two options for doing this:
1. In the management console (Telnet) select the TFTP Update submenu.
The update process is similar to the process via the management blade
web user interface (see below).
60PRIMERGY BX600 S2 Basic Unit
Preparation for Use and OperationUpdating BX600 System Components
2. In the web interface of the management blade, select the menu
System Property–Environ./Maintenance–Firmware Update–Server Blade BMC
or
System Property–Environ./Maintenance–Firmware Update–Server Blade BIOS
I For security reasons the BIOS and BMC firmware can only be
updated if the relevant server blade was shut down beforehand,
otherwise the update option is not offered in the web menu.
Figure 22: Updating the server blade BIOS via the web interface
Ê In the TFTP Server IP Address field, enter the IP address of the TFTP server
which provides the BIOS image file for the server blade firmware.
Ê In the Boot Image File Name field, enter the file name of the boot image file for
the server blade.
Ê Use the Add and Delete buttons to select the server blades whose BIOS is to
be updated.
Ê Click the Apply button. The update file is transferred to all selected server
blades and the update process is started. The progress of the update
process is shown in a status screen.
Ê Once the update process is complete, the server blade(s) is (are) restarted.
Ê Repeat the procedure to update the BMC firmware (see figure 23).
PRIMERGY BX600 S2 Basic Unit 61
Updating BX600 System ComponentsPreparation for Use and Operation
Figure 23: Updating the server blade BMC via the web interface
5.4.2Updating the Management Blade Firmware
V CAUTION!
The procedure described below must be performed for each of the two
management blades.
Proceed as follows:
Ê Install your TFTP server software and start it. Copy the relevant firmware file
(*.bin) to the root directory of the TFTP file system.
Ê Check the LAN connection by pinging the relevant management blade.
Ê Enter the IP address of the TFTP server which provides the BMC image file
for the management blade firmware. Enter the path and the file name of the
image file for the management blade.
You have two options for doing this:
1. In the management console (Telnet) select the TFTP Upgrade submenu.
Activate the option Management Blade/TFTP Update.
2. In the web interface of the management blade, select the entry System
Preparation for Use and OperationUpdating BX600 System Components
Figure 24: Updating the management blade firmware via the web interface
Ê Make sure that both management blades are connected to the LAN.
Ê Enter the IP address of the TFTP server on which the image file for the
management blade firmware is provided.
Ê Enter an IP address in the Agent Update IP Address field.
I The IP address in the Agent Update IP Address field is only used tempo-
rarily, so you can enter any IP address that is not used in the LAN
segment of the server.
Ê In the Boot Image File Name field, enter the name of the image file of the
management blade.
Ê Set the value of the TFTP Update Enable field to enable.
Ê Click Apply.
The firmware of the first management blade (Master) will now be updated
(the green LED lights up). When the update process is complete, this
management blade is defined as the Slave, and the second management
blade, which used to be the Slave, is now defined as the Master.
Ê Repeat the update process for the second management blade.
After the update process for the second management blade, the original
Master-Slave configuration is automatically restored.
PRIMERGY BX600 S2 Basic Unit 63
Updating BX600 System ComponentsPreparation for Use and Operation
5.4.3Updating the Switch Blade Firmware
I Before you update the firmware, you must allocate IP addresses to the
individual switch blades.
Proceed as follows:
Ê Switch on the basic unit and start the management console (Telnet) of the
CLI session with the Switch Blade is opened.
To end the CLI session, enter [Exit].
Condole>enable
Console#config
Console(config)#interface vlan 1
Console(config-if)#ip address 10.50.50.51 255.0.0.0
Console(config-if)#exit
Console#show ip interface
TP address and netmask: 10.50.50.51 255.0.0.0 on VLAN 1,
and address mode: User specified
Console#
Ê Enter the commands specified above.
I The specifications for the IP address and the subnet mask are merely
examples and are probably not valid for your system.
Ê Terminate the command line session by pressing {Strg} [Q].
Ê Check the newly created LAN connection by pinging the switch blade on the
client system.
Ê Install your TFTP server software and start it.
Ê Download the TFTP update package BX600 S2_TFTP-
IMAGES_<version>.exe from the Fujitsu Siemens download server at
Updating BX600 System ComponentsPreparation for Use and Operation
Ê Extract the firmware file (*.bix) to the root directory of the TFTP file system.
For information on the image file names, see the readme file of the update
package.
Ê Start an Internet browser on the client server. Enter the IP address specified
above in the address field. Enter the user name and password admin. The
home page is displayed.
Ê In the navigation bar choose Flash/File.
I Only two operation code image files can be stored on the switch blade. If
there are already two image files stored, you must remove at least one of
them before updating the firmware. It is recommended that you remove
the older file (i.e. the file with the lower number).
Ê Expand the File Name list (red arrow) in the Remove Operation Code Image File
section to check if there are already two image files stored on the switch
blade. If so, select the older one in the File Name list and click Remove File.
Figure 25: Removing an operation code image file
Ê Enter TFTP Server IP Address, Source File Name (*.bix) and Destination File
Name.
66PRIMERGY BX600 S2 Basic Unit
Preparation for Use and OperationUpdating BX600 System Components
Figure 26: Transferring the new operation code image file
Ê Click Transfer from Server.
Ê Wait a few minutes until the update process is complete. Refresh the
browser for viewing.
Ê Select the new image file in the pop-up window (red arrow) and click Apply
I After resetting, the switch blade will reboot. However, all settings
specified previously (IP address etc.) will be lost and must be
reentered on the management console.
Ê Repeat the firmware update procedure for each installed switch blade.
PRIMERGY BX600 S2 Basic Unit 67
6Property and Data Protection
The lockable rack door protects the server against unauthorized access.
To protect your system and data internally against unauthorized access, you
can use the BIOS Setup security functions.
Further security options can also be set in the installed operating system. If you
wish to do this, consult your network administrator or refer to the documentation
for the corresponding operating system.
6.1BIOS Setup Security Functions
The Security menu in BIOS Setup offers various options for protecting data
against unauthorized access. By combining these options, you can achieve
optimum protection for the system.
I A detailed description of the Security menu and how to assign passwords
can be found in the manual for the BIOS Setup and on the ServerBooks
CD (see also “Related Publications” on page 165).
Preventing Unauthorized BIOS Setup Calls
This protection mechanism can be activated by setting a supervisor password
in the Security menu. In addition, the Press F2 for Setup message in the
Security menu can be suppressed. This message is then no longer displayed
while the server's startup routine is in progress.
Preventing Unauthorized System Access
This protection mechanism can be activated by setting a user password in the
Security menu.
Preventing Unauthorized Boot Process
This protection mechanism can be activated by setting a password on boot in
the Security menu.
PRIMERGY BX600 S2 Basic Unit 69
7Server Blades
This chapter describes how to install and uninstall server blades and server
blade dummy modules in the PRIMERGY BX600 S2 basic unit, and what you
need to be aware of when doing this.
The information necessary for installing and operating the various server blade
models can be found in separate manuals (see “Related Publications” on
page 165).
When you install a server blade in the basic unit, an important factor is the
height. Figure 28 shows a 2-way server blade, which occupies one slot in the
basic unit.
Figure 28: PRIMERGY BX620 S3/S4 2-way server blade
PRIMERGY BX600 S2 Basic Unit 71
Server Blades
The 4-way server blade is twice the height and occupies two slots (figure 29).
Figure 29: PRIMERGY BX630 scalable server blade (4-way configuration
72PRIMERGY BX600 S2 Basic Unit
Server BladesInstallation Sequence
7.1Installation Sequence
On the front of the PRIMERGY BX600 S2 basic unit are ten slots for server
blades (numbered 1 - 10 from left to right).
12345678910
Figure 30: BX600 S2 basic unit with ten 2-way server blades
All ten slots are connected to the infrastructure modules on the back of the
BX600 S2 basic unit via the midplane of the BX600 S2 basic unit:
PRIMERGY BX620 S4 server blades are not for use in slots 4 an 10 of
the PRIMERGY BX600 S2 basic unit.
In a PRIMERGY BX600 S2 basic unit different models and configurations of
server blades can be operated alongside each other.
PRIMERGY BX600 S2 Basic Unit 73
Installation SequenceServer Blades
The order in which the server blade slots are filled depends on whether you are
using 2-way server blades or 4-way server blades or a mix of the two, and how
the server blades are equipped.
Configuration Diagram for 2-way Server Blades
– Slot 4 is filled first.
– Next, slots 5 through 10 are filled in numerical order, followed by slots 1
through 3.
– 2-way server blades with SCSI controller in a PCI extension module can only
be installed in slots 5 and 6 because of the cabling arrangement in the rack
(see section “Cable Routing” on page 43).
1234567
1234567
8910
Figure 31: Installation sequence for 2-way server blades
8910
74PRIMERGY BX600 S2 Basic Unit
Server BladesInstallation Sequence
Configuration Diagram for 4-way Server Blades
– Slots 3 and 4 are filled first.
– Next, slots 5 through 10 are filled in pairs in numerical order, followed by
slots 1 and 2.
89101234567
1234
5
Figure 32: Installation sequence for 4-way server blades
Configuration Diagram for a Mix of 2-way and 4-way Server Blades
– The 4-way server blades are fitted first, followed by the 4-way server blades
– Begin with a 4-way server blade in slots 3 and 4.
89101234567
134
6
Dummy server blade
Figure 33: Installation sequence for three 2-way and three 4-way server blades
2
5
I 2-way server blades with SCSI controller can only be fitted in slots 5 and
6. If only one 2-way server blade with SCSI controller is to be fitted, it
must go in slot 5, with a dummy server blade in slot 6.
PRIMERGY BX600 S2 Basic Unit 75
Adding a Server Blade to the SystemServer Blades
Configuration Diagram for a Mix of an 8-way Server Blade with 4-way and
2-way Server Blades
Begin with the 8-way server blade in slots 1-4, followed by the 4-way ServerBlades and the 2-way Server-Blades.
I Server blades with SCSI controller can only be fitted in slots 5 and 6.
89101234567
134
Figure 34: Installation sequence for an 8-way, two 4-way and two 2-way server blades
2
5
7.2Adding a Server Blade to the Basic Unit
Depending on the desired configuration, the system can be upgraded with up to
10 server blades.
V CAUTION!
● Read the safety information and the information on handling electro-
static-sensitive components in the section “Components With
Electrostatic-Sensitive Devices” on page 25.
● Energiegefahr - neu.
Removing the Dummy Module
All unoccupied slots in the basic unit are fitted with dummy modules to ensure
that the electromagnetic emission properties of the system are observed and
that the system components are properly cooled.
76PRIMERGY BX600 S2 Basic Unit
Server BladesAdding a Server Blade to the System
123
If you want to add a server blade, you must first remove the dummy module from
the corresponding slot.
Figure 35: Removing a server blade dummy module
Ê Release the locking mechanism of the ejecting handles by pressing the
touch points on the inside of both handles (1) simultaneously. The ejecting
handles of the dummy module will be disengaged.
Ê Swing up the upper handle and swing down the lower handle simultaneously
(2) until the locking mechanism of the dummy module disengages and the
dummy module ejects.
Ê Remove the dummy module completely from the slot (3).
V CAUTION!
Keep the dummy module for future use. If the server blade is removed
and not replaced with a new server blade, then the dummy module must
be reinstalled for cooling, to comply with the applicable EMC regulations
(regulations on electromagnetic compatibility) and for fire protection.
PRIMERGY BX600 S2 Basic Unit 77
Adding a Server Blade to the SystemServer Blades
Installation is the same as for the server blade (see “Inserting the Server Blade”
on page 78).
Inserting the Server Blade
V CAUTION!
Read the safety information and the information on handling electrostatic-sensitive components in the section “Components With Electro-
static-Sensitive Devices” on page 25.
Figure 36: Turning the eject handles into the unlocked position (2-way server blade)
Ê Press the touch points on the inside of the eject handles (1) of the server
blade to disengage the locking mechanism of the handles.
Ê Turn the eject handles outward (2) into the unlocked position.
The 4-way server blade has the same locking mechanism (see figure 37).
Figure 37: Turning the eject handles into the unlocked position (4-way server blade)
I How to install a server blade is described in the following using the
example of a 2-way server blade. 4-way server blades are installed in the
same way.
78PRIMERGY BX600 S2 Basic Unit
Server BladesAdding a Server Blade to the System
1
Figure 38: Inserting the server blade
Ê Push the server blade into the slot as far as possible while keeping the eject
handles in the unlocked position.
I Please make sure you install the server blade in the right direction.
The upper narrow side of the server blade is marked TOP-SIDE (1).
PRIMERGY BX600 S2 Basic Unit 79
Adding a Server Blade to the SystemServer Blades
Figure 39: Final engaging of the locking mechanism
Ê Press the eject handles to enable the locking mechanism to engage fully.
Removing the Server Blade
The server blade is removed in the same way as the dummy module (see
“Removing the Dummy Module” on page 76).
V CAUTION!
Read the safety information and the information on handling electrostatic-sensitive components in the section “Components With Electro-
static-Sensitive Devices” on page 25.
When you remove the server blade and do not replace it with a new one, you
must insert a dummy module in the empty slot. Make sure that the dummy
module engages in the slot correctly.
80PRIMERGY BX600 S2 Basic Unit
8Ethernet LAN Switch Blades
This chapter outlines the main features of the switch blades available with the
PRIMERGY BX600 S2 blade server. For each switch blade it describes the
indicator and connection elements of the control and connection panel. This
chapter also describes the port assignment to the server blades and how to
install and uninstall the switch blades in the basic unit.
The information necessary for configuring and operating the various switch
blade models can be found in separate manuals, see “Related Publications” on
page 165).
The following switch blade models are available:
– Gbit Ethernet LAN Switch Blade (SB9) 6x1Gbit
– Gbit Ethernet LAN Switch Blade (SB9) 6x1 Gbit + 2x10 Gbit
– Cisco Catalyst Blade Switch 3040
– 10 Gbit Switch Blade 10/2
PRIMERGY BX600 S2 Basic Unit 81
LAN Switch Blade (SB9) 6x1GbitEthernet Switch Blades
8.1Gbit Ethernet LAN Switch Blade (SB9)
6x1Gbit
The Gbit Ethernet LAN switch blade (SB9) 6x1Gbit supports layer 2/3/4
functionality and offers the following connections:
– 10 internal 1Gbit downlink ports to the server blades
– 6 external 1Gbit uplink ports via RJ45 connectors
Operating and Indicator Elements
135
AB
Figure 40: Gbit Ethernet LAN switch blade(SB9) 6x1Gbit
1-6 1 Gbit uplink LAN connectors (with two integrated LAN status LEDs each)
LED A:
LED B:
LAN active indicator (bicolor LED)
Glows amber:Port link at 1 Gbit/s
Glows green:Port link at 100 Mbit/s
Dark:Port link at 10 Mbit/s
LAN link indicator (yellow LED)
Glows yellow:Network link
Blinks yellow:Network activity
Dark:No network link or port disabled
Glows green:Selected for identification by the management blade
Blinks green:Error occured
The information necessary for configuring and operating the Gbit Ethernet LAN
switch blade (SB9) 6x1Gbit can be found in the manual „PRIMERGY BX Blade
Server Systems: LAN Router and Switch Blade - User Interface Description“,
see “Related Publications” on page 165).
9Power, system and 10 GbE status indicators (green LEDs)
P:Power indicator (green LED)
Glows green:Power enabled
Dark:Power disabled
S:System indicator (green LED)
Glows green:The switch has been selected for identification by the
Blinks green:Error occured
C:CX4 link/active indicator (green LED)
Glows green:CX4 network link
Blinks green:CX4 port port
X:XFP link/active indicator (green LED)
Glows green:XFP network linkr
Blinks green:XFP port link
management blade.
The information necessary for configuring and operating the Gbit Ethernet LAN
switch blade (SB9) 6x1 Gbit + 2x10 Gbit can be found in the manual
„PRIMERGY BX Blade Server Systems: LAN Router and Switch Blade - User
Interface Description“, see “Related Publications” on page 165).
The Cisco Catalyst Blade Switch 3040 provides the following features:
– 10 internal 1Gbit downlink ports to the server blades
– 1 console port
– 2 external 10/100/1000BASE-T copper Gigabit Ethernet uplink ports
– 4 external small form-factor pluggable (SFP) module uplink ports that
support 1000BASE-SX fiber and 10/100/1000BASE-T copper (only Cisco
SFP modules are supported)
Operating and Indicator Elements
41
32
Figure 42: Cisco Catalyst Blade Switch 3040
1Console port
2Console port indicator (bicolor LED)
Dark:The bootloader is initializing.
Glows green:The blade switch console port is active.
Glows amber:The blade switch console port is inactive; the management
Glows green or
amber
3System status/ID indicator (green LED)
Glows green: ID-The switch has been selected for identification by the management
blade/backplane console is active.
Cisco IOS is operating normally.
4Gigabit Ethernet ports
5Gigabit Ethernet port indicators (bicolor LEDs)
Dark:No link established.
Glows green:Link established but no activity.
Blinks green:Traffic on an established link.
Glows amber:Port disabled, either error or STP1 disabled.
Glows green or
amber
6SFP module ports
7SFP module port indicators (bicolor LEDs)
Dark:No link established.
Glows green:Link established but no activity.
Blinks green:Traffic on an established link.
Glows amber:Port disabled, either error or STP1 disabled.
Glows green or
amber
Link fault.
Link fault.
The information necessary for configuring and operating the Cisco Catalyst
Blade Switch 3040 can be found in the manual „PRIMERGY BX Blade Server
Systems: Cisco Catalyst Blade Switch 3040“, see “Related Publications” on
page 165).
PRIMERGY BX600 S2 Basic Unit 87
10 Gbit Switch Blade 10/2Ethernet Switch Blades
8.410 Gbit Switch Blade 10/2
The 10 Gbit switch blade 10/2 is designed to transport all blade server I/O,
including network and storage, between the server blades and their associated
I/O devices. The 10 Gbit switch blade 10/2 provides the following features:
– 10 internal 10 Gbit/s ports to the server blades
– 2 external 10 Gbit/s ports with optional X2 transceiver modules for Fiber
optical or CX4 copper cable
– 1 console port
V CAUTION!
● You may install 10 Gbit switch blades 10/2 only in slots NET3 and
NET4 of the basic unit, see figure “Slots for the switch blades” on
page 90.
● The 10 Gbit switch blade 10/2 only supports server blades with a
10 GbE daughter card installed. 10 GbE daughter cards can be
installed in server blades BX620 as of version S3 and BX630 as of
version S2.
88PRIMERGY BX600 S2 Basic Unit
Ethernet Switch Blades10 Gbit Switch Blade 10/2
Bedien- und Anschlussfeld
27834561
Figure 43: 10 Gbit Switch Blade 10/2
1Left CX4 port indicator (green LED)
Glows:CX4 link established
Blinks:CX4 link active
1Right CX4 port indicator (green LED)
Glows:CX4 link established
Blinks:CX4 link active
3,4 CX4 ports
5Console port link indicator (green LED)
Glows:Link available
6Console port active indicator (amber LED)
Dark:1 Gbit/s link available
Glows:100 Mbit/s link available
Blinks:Link active
7Power indicator (amber LED)
Dark:Power enabled
Glows:Power disabled
8ID indicator (green LED)
Glows:Switch blade is operating
Blinks:The switch blade has been selected for identification by the
management blade.
PRIMERGY BX600 S2 Basic Unit 89
Port Assignment of the LAN Switch BladesEthernet Switch Blades
8.5Port Assignment of the LAN Switch Blades
For each of the ten server blade slots, connections are available to the two ports
of the onboard LAN controllers and to the two ports of the optional gigabit
Ethernet daughter card. In the case of 4-way server blades, connections for a
total of eight LAN ports are therefore available.
The LAN switch blade in the NET1 slot is connected to port A of the onboard
LAN controller of the installed server blades. The switch blade in slot NET2 is
connected to port B of the onboard LAN controller. In the same way, the LAN
switch blades in slots NET3 and NET4 are connected to port A and B of the
gigabit Ethernet daughter cards.
NET1NET2
NET4NET3
Figure 44: Slots for the switch blades
The installation of two LAN switch blades in NET1 and NET2 (or NET3 and
NET4) enables redundant LAN connections to be provided for the relevant LAN
controllers of the server blades.
V CAUTION
● LAN switch blades must always be installed in slots NET1 and NET3
first. This ensures that port A of the relevant LAN controller is
connected if redundant LAN connections are not used.
● To provide fibre channel functionality, FC pass-thru blades (see
page 113) or FC switch blades (see page 105) must be installed in
slot NET3 and/or slot NET4.
Asynchronous balanced mode of Ethernet blades and fibre channel
blades in slots NET3 and NET4 is not permitted.
90PRIMERGY BX600 S2 Basic Unit
Ethernet Switch BladesPort Assignment of the LAN Switch Blades
The configuration examples below show the assignment of the onboard LAN
controller ports to the LAN switch blades in slots NET1 and NET2. The port
assignment for the gigabit Ethernet daughter cards to the LAN switch blade
ports in slots NET3 and NET4 takes place accordingly.
Configuration with Ten 2-way Server Blades
The following figure illustrates the assignment of the switch blades to the LAN
ports of the server blades in a configuration with ten 2-way server blades.
Switch blade 1Switch blade 2
ABABABABABABABABABAB
Server blade 8
Server blade 9
Server blade 10
Server blade 1
Server blade 2
Server blade 3
Server blade 4
Server blade 5
Server blade 6
Server blade 7
Figure 45: LAN port assignment with ten 2-way server blades
PRIMERGY BX600 S2 Basic Unit 91
Port Assignment of the LAN Switch BladesEthernet Switch Blades
Configuration with Five 4-way Server-Blades
The following figure illustrates the assignment of the switch blades to the LAN
ports of the server blades in a configuration with five 4-way server blades.
Switch blade 1Switch blade 2
ABABABABABABABABABAB
Server
blade 5
Figure 46: LAN port assignment with five 4-way server blades
Server
blade 1
Server
blade 2
Server
blade 3
Server
blade 4
92PRIMERGY BX600 S2 Basic Unit
Ethernet Switch BladesInstalling a LAN Switch Blade
Configuration with a Combination of 2-way and 4-way Server Blades
The following figure illustrates the assignment of the switch blades to the LAN
ports of the server blades in a configuration with two 4-way server blades and
six 2-way server blades.
Switch blade 1Switch blade 2
ABABABABABABABABABAB
4-way
server
blade 1
2-way
server blade 5
2-way
server blade 6
Figure 47: LAN port assignment with 4-way and 2-way server blades
4-way
server
blade 2
2-way
server blade 2
2-way
server blade 3
2-way
2-way
server blade 1
server blade 4
8.6Installing a LAN Switch Blade
Depending on the desired configuration, the system can be upgraded with one
additional switch blade.
V CAUTION!
● Read the safety information and the information on handling electro-
static-sensitive components in the section “Components With
Electrostatic-Sensitive Devices” on page 25.
● LAN switch blades must always be installed in slots NET1 and NET3
first (see page 90).
PRIMERGY BX600 S2 Basic Unit 93
Installing a LAN Switch BladeEthernet Switch Blades
Removing the Dummy Module
All unoccupied slots in the basic unit are fitted with dummy modules to ensure
that the electromagnetic emission properties of the system are observed and
that the system components are properly cooled.
If you wish to install a LAN switch blade, you must first remove the dummy
module from the corresponding slot.
Figure 48: Removing the dummy module (a = green touch point)
Ê Press the spring (1) on the underside of the handle (a) to unlock it.
Ê Swing the handle (a) in the direction of the arrow (2) until the locking
mechanism of the dummy module disengages.
94PRIMERGY BX600 S2 Basic Unit
Ethernet Switch BladesInstalling a LAN Switch Blade
Figure 49: Removing the dummy module (a = green touch point)
Ê Remove the dummy module from the slot (2).
V CAUTION!
Keep the dummy module for future use. If you remove the LAN switch
blade and do not replace it with a new one, you must reinstall the dummy
module.
Installation is the same as for the LAN switch blade (see “Inserting the LAN
Switch Blade” on page 95).
Inserting the LAN Switch Blade
V CAUTION!
Read the safety information and the information on handling electrostatic-sensitive components in the section “Components With Electro-
static-Sensitive Devices” on page 25.
Ê Remove the LAN switch blade from its package.
PRIMERGY BX600 S2 Basic Unit 95
Installing a LAN Switch BladeEthernet Switch Blades
Figure 50: Disengaging the switch blade
Ê Disengage the locking mechanism of the LAN switch blade by swinging the
handle in the direction of the arrow.
Figure 51: Inserting the switch blade (a = green touch point)
Ê Push (1) the LAN switch blade as far as possible into the desired slot (here
slot 2).
Ê Swing up (2) the eject handle (a) of the switch blade until the locking
mechanism of the LAN switch blade engages.
96PRIMERGY BX600 S2 Basic Unit
Ethernet Switch BladesInstalling a LAN Switch Blade
Removing the Switch Blade
The LAN switch blade is removed in the same way as the dummy module (see
“Removing the Dummy Module” on page 94).
V CAUTION!
Read the safety information and the information on handling electrostatic-sensitive components in the section “Components With Electro-
static-Sensitive Devices” on page 25.
If you remove the LAN switch blade and do not replace it with a new one, you
must insert a dummy module in the empty slot to ensure cooling, to comply with
the applicable EMC regulations (regulations on electromagnetic compatibility)
and for fire protection.
Make sure that the dummy module engages in the slot correctly.
PRIMERGY BX600 S2 Basic Unit 97
9Ethernet Pass-Thru Blade
The Ethernet LAN Pass-Thru-Blade provides ten RJ45 ports for direct (“passthru”) connections to the server blades.
Figure 52: Ethernet LAN Pass-Thru-Blade
The PRIMERGY BX600 S2 basic unit offers slots for up to four Ethernet LAN
Pass-Thru-Blades on the back, see figure 54 on page 101. Depending on the
specific slot, an Ethernet LAN Pass-Thru-Blade establishes connections to the
onboard LAN controllers or to the optional Gigabit Ethernet I/O modules
(daughter cards) of the server blades. For information on the optional Gigabit
Ethernet I/O modules (daughter cards), see the operating guides for the
relevant server blade types.
PRIMERGY BX600 S2 Basic Unit 99
Control and Connection PanelEthernet Pass-Thru Blade
9.1Control and Connection Panel
ba
13579
246810
ba
Figure 53: Control and connection panel of the Ethernet LAN Pass-Thru-Blade
The following display and control elements are available:
1 ... 10 RJ45 connectors
The RJ45 connectors are assigned to the server blades in accordance
with their numbering (for server blade slot numbering see figure 30 on
page 73).
aLAN activity indicator (orange LED)
Blinks
amber:
DarkInactive LAN connection
bLAN connection indicator (green LED)
Lights green: LAN connection available
DarkNo LAN connection
Active LAN connection
100PRIMERGY BX600 S2 Basic Unit