Seasonal Energy Efciency Ratio (SEER)23.022.0
Heating Seasonal Performance Factor (HSPF)11. 011. 0
AOU12RLFW1AOU9RLFW1
MODEL
ASU9RLF1ASU12R LF1
WALL MOUNTED TYPE
ASU9-12RLF1
MEASUREMENT CONDITIONS
ANSI/ASHRAE STANDARD 37-1988
High efcient compact design
z
MIN. HEAT Operation
z
*Only available with Wireless RC.
More comfortable airow
z
The room temperature can be set to go no lower than 50°F (10°C),
thus ensuring that the room does not get too cold when not occupied
Caution)
When the room temperature is higher than 50°F (10°C), “ •
temperature at 50°F (10°C) when the temperature drops below 50°F (10°C).
MIN. HEAT
When “ •
” operation stops, the room set temperature quickly returns to the preset temperature.
MIN. HEAT
” operation will not start. Operation starts and maintains the room
- (01 - 01) -
Page 5
WALL MOUNTED TYPE
Powerful
Setting temp.
Normal mode
Time
Temperature
Temp.
Economy operation
Shift
setting
temp
Control maximum current
Normal operation
Time
Set temperature
ASU9-12RLF1
Powerful operation
z
WALL MOUNTED TYPE
ASU9-12RLF1
20 minutes continuous operation by maximum airow and maximum compressor speed is
possible. Rapid cooling and heating makes the room comfortable quickly.
Economy operation
z
Example : Cooling operation
• Economy operation is energy saving, as the set temperature of indoor unit is shifted by 2°F (1°C)
and the maximum electric value of the outdoor unit is suppressed.
Low outdoor air temperature correspondence
z
Corresponds to cooling operation at 14°F (-10°C) outdoor air temperature
Corresponds to heating operation at 5°F (-15°C) outdoor air temperature
CoolingHeating
14 to 115°F
(-10 to 46°C)
5 to 75 °F
(-15 to 24°C)
- (01 - 02) -
Page 6
WIRELESS REMOTE CONTROLLER2.
60min.
2°F (1°C)
4°F (2°C)
Timer setting
30min.
60min.
90min.
8°F
(4°C)
Timer setting
6°F
(3°C)
4°F
(2°C)
2°F
(1°C)
ABCD
AB
C
D
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
REG1U
FEATURES
WALL MOUNTED TYPE
ASU9-12RLF1
Simple function setting
z
4 mode timer setup available (ON / OFF / PROGRAM / SLEEP).
Easy operation.
Easy to change custom code (max. 4 custom codes) by button operation.
WALL MOUNTED TYPE
ASU9-12RLF1
Setting of the air conditioner selection function is performed by remote controller.
Built-in timers
z
Select from four different timer programs (On / Off / Program / Sleep).
Program timer
z
The program timer operates the on and off timer once within a 24-hour period.
Sleep timer
z
The sleep timer function automatically corrects the temperature thermostat setting according to
the timer setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature
automatically rises 2°F (1°C) every hour. The set
temperature can rise up to a maximum of 4°F (2°C).
Simple function setting
z
Heating operation
When the sleep timer is set, the set temperature
automatically drops 2°F (1°C) every 30 minutes. The
set temperature can drop to a maximum of 8°F (4°C).
Setting of the air conditioner selection function is performed by remote controller.
Switching remote controller custom code
z
Code selector switch eliminates unit
•
being wrongly switched.
(Up to 4 custom codes can be set.)
*I.U.=Indoor unit
To change the temperature unit
z
Easy to change the temperature unit (
°F ↔ °C) by button operation.
- (01 - 03) -
Page 7
FUNCTIONS
REG1U
REG1U
Signal
WALL MOUNTED TYPE
ASU9-12RLF1
transmitter
WALL MOUNTED TYPE
ASU9-12RLF1
MIN. HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
ECONOMY button
TIMER ON button
TIMER OFF button
TIMER SELECT button
TIMER SLEEP button
TIMER CANCEL button
MODE button
CLOCK ADJUST button
FAN button
SWING button
SET button
RESET button
°C / °F switching button
Display panel
Mode indicator
Temperature indicator
Send indicator
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation,
however, the display will only show those indicators appropriate to the current operation.
SPECIFICATION
Transmit indicator
Fan Speed indicator
Swing indicator
Clock & Timer
indicator
DIMENSIONS [H × W × D]: in. (mm)8-1/16 (205) × 2-3/8 (61) × 11/16 (17)
WEIGHT oz. (g)4.3 (122)
ACCESSORYHolder
- (01 - 04) -
NOTE: Some button operations may
not be available for all units
or systems.
For details, refer to the
operation manual.
Page 8
SPECIFICATIONS3.
Typ e
Model nameASU9 RLF1ASU12R LF1
WALL MOUNTED TYPE
ASU9-12RLF1
Power source208/230V~60HZ
Available voltage range187-253V~60HZ
Fin pitchFPIMain:23 Sub:18
Rows×StagesMain:2×20 Sub:1×4
Pipe typeCopper
Fin typeAluminum
MaterialPolystyrene
Color
Liquid
GasØ3/8(Ø9.52)
Cooling
Heating°F(° C)88(30) or less
kW2.6373. 516
BTU/h900012000
kW0.50-3.200.90-3.90
BTU/h1700-109003100-13300
kW3.5164.689
BTU/h1200016000
kW0.50-4.400.90-5.60
BTU/h1700-150003100-19100
kW
kW/kW4.053.66
BTU/hW13. 812.5
kW/kW3.953.66
BTU/hW13.5012.50
%
A
CFM
(m3/h)
dB(A)
in. (mm)
mm268 x 840 x 203
in.10-9/16 x 33 -1/16 x 8
mm270 x 884 x 336
in. 10-5/8 x 34-13/16 x 13-1/4
lb.(kg)
in. (mm)
°F(° C)64 to 90(18 to 32)
%RH80 or less
mm
(Reference in.)
0.650.96
3.24.4
8895
6.06.5
4343
Main: 12-5/8 x 24-13/16 x 13/16 (320×630×20)
Sub: 3-5/16 x 24-13/16 x 1/2 (84×630×13.3)
Approximate color of MUNSELL N9. 25/
WALL MOUNTED
INVERTER HEAT PUMP
441(7 50)
White
19(8.5)
Ø1/4(Ø6.35)
Ø 9/16 (13.8) (I.D.)
Ø5/8 to Ø11/16 (15.8 to 16.7) (O.D.)
WALL MOUNTED TYPE
ASU9-12RLF1
Note:
●Specications are based on the following conditions.
Cooling:Indoor temperature of 80°F(26.67°C)DB/67°F(19.44°C)WB,and outdoor temperature of 95°F(35°C)DB/75°F(23.9°C)WB.
Heating:Indoor temperature of 70°F(21.11°C)DB/59°F(15°C)WB,and outdoor temperature of 47°F(8.33°C)DB/43°F(6.11°C)WB.
Pipe length:24ft.(7.5m),Height difference:0ft. (0m) (Outdoor unit-Indoor unit)
●The protective function might work when using it in environment out of the temperature range mentioned above.
*: The maximum current is the ma ximum value when operated within the operation range.
CNA01Control input-
CNB01-Operation status output
CNB02-Error status output
See external
input/output settings
for details.
WALL MOUNTED TYPE
ASU9-12RLF1
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operationInitial setting after power is ONStarting mode other than initial setting
Operation modeAuto changeoverMode at previous operation
Set temperature75°F (24°C)Temperature at previous operation
Air ow modeAUTOMode at previous operation
Up-down air direction (swing)Standard air direction (swing OFF)Air direction at previous operation
Circuit diagram example
z
When function setting is in "Operation/Stop" mode
z
* Make the distance from the PC board to the connected unit within 33ft. (10m).
Contact capacity: DC 24 V or more, 10 mA or more.
Use non-polar relays and switches.
- (01 - 17) -
Page 21
WALL MOUNTED TYPE
Remote controller
ONONON
Input signal
ON
OFF
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control
operation invalidity
ASU9-12RLF1
When function setting is in "Forced stop" mode
z
Parts (Optional)
z
WALL MOUNTED TYPE
ASU9-12RLF1
Parts name
Model name
External connect kitUTY-X WZ X Z5
Communication kitUT Y-XCBX Z2
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(U T Y-XWZX Z5).
Wire (External input) : UTY-XWZXZ5
- (01 - 18) -
Page 22
EXTERNAL OUTPUT11-2.
Ex.)Display
Indoor unit
control PC boardCommunication kitConnected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
*33ft.
(10m)
24V DC
Optional partsField supply
ON
OFF
Operation
Stop
Indoor unit
Output signal
WALL MOUNTED TYPE
ASU9-12RLF1
OPERATION STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
z
*: Make the distance from the PC board to the connected unit within 33ft. (10m)
Relay spec.: Max. DC 24 V, 10 mA to less than 500 mA.
WALL MOUNTED TYPE
ASU9-12RLF1
Parts (Optional)
z
Parts name
Model name
External connect kitUTY-X WZ X Z5
Communication kitUT Y-XCBX Z2
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(U T Y-XWZX Z5).
Wire (External output) : UTY-XWZXZ5
- (01 - 19) -
Page 23
WALL MOUNTED TYPE
Ex.)Display
Indoor unit
control PC boardCommunication kitConnected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
*33ft.
(10m)
24V DC
Optional partsField supply
ON
OFF
Error
Normal
Error status
Output signal
ASU9-12RLF1
ERROR STATUS OUTPUT
WALL MOUNTED TYPE
ASU9-12RLF1
An air conditioner error status signal can be output.
Circuit diagram example
z
*: Make the distance from the PC board to the connected unit within 33ft. (10m)
Relay spec.: Max. DC 24 V, 10 mA to less than 500 mA.
Parts (Optional)
z
Parts name
Model name
External connect kitUTY-X WZ X Z5
Communication kitUT Y-XCBX Z2
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(U T Y-XWZX Z5).
Wire (External output) : UTY-XWZXZ5
- (01 - 20) -
Page 24
FUNCTION SETTINGS12.
Function number
Setting
value
INDOOR UNIT (Setting by remote controller)12-1.
WALL MOUNTED TYPE
ASU9-12RLF1
The function settings of the control of the indoor unit can be changed by this procedure according •
to the installation conditions. Incorrect settings can cause the indoor unit to malfunction.
After the power is turned on, perform the Function Setting according to the installation conditions •
using the remote controller.
The settings may be selected between the following two: Function Number and Setting Value. •
Settings will not be changed if invalid numbers or setting values are selected. •
PREPARATION
• Before turning on the power of the indoor unit:
- Conrm whether the piping air-tight test and vacuuming have been conducted.
- Reconrm whether there is no miswiring.
• Turn on the power of the indoor units.
FUNCTION SETTING METHOD (for Wireless remote controller)
Entering the Function Setting Mode
While pressing the POWERFUL button and SET TEMP. (
•
function setting mode.
STEP 1
Setting the Remote controller Custom code
Use the following steps to select the custom code of the remote controller. (Note
that the air conditioner cannot receive a custom code if the air conditioner has not
been set for the custom code.) The custom codes that are set through this process
are applicable only during the Function Setting process. For details on how to set
the custom codes through the normal process, refer to "REMOTE CONTROLLER
CUSTOM CODE SETTING".
Press the SET TEMP. (1. ) ( ) button to change the custom code between →
→ → .
Match the code on the display to the air conditioner custom code. (initially set to )
(If the custom code does not need to be selected, press the MIN. HEAT button and
proceed to
Press the MODE button and check that the indoor unit can receive signals at the 2.
displayed custom code.
Press the MIN. HEAT button to accept the custom code, and proceed to 3.
STEP 2
.)
) simultaneously, press the RESET button to enter the
STEP 2
.
WALL MOUNTED TYPE
ASU9-12RLF1
The air conditioner custom code is set to "A" prior to shipment.
The remote controller resets to custom code A when the batteries in the remote controller are replaced. If you use a
custom code other than custom code A, reset the custom code after replacing the batteries.
If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until
you nd the code which operates the air conditioner.
STEP 2
Selecting the Function Number and Setting Value
After turning off the power, wait 30 seconds or more before turning on it again.
The Function Setting will not become active unless the power is turned off then on again.
Press the SET TEMP. (1. ) ( ) buttons to select the function number.
(Press the MIN. HEAT button to switch between the left and right
digits.)
Press the POWERFUL button to proceed to setting the value. 2.
(Press the POWERFUL button again to return to the function number
selection.)
Press the SET TEMP. (3. ) ( ) buttons to select the setting value.
(Press the MIN. HEAT button to switch between the left and right
digits.)
Press the MODE button, then the START/STOP button in order to x 4.
the settings.
Press the RESET button to end the function setting mode.5.
After completing the Function Setting, be sure to turn off the power 6.
and turn it on again.
CAUTION
- (01 - 21) -
Page 25
WALL MOUNTED TYPE
ASU9-12RLF1
FUNCTION DETAILS
Functions
1) Filter sign
2) Room temperature control for cooling
3) Room temperature control for heating
4) Auto restart
5) Room temperature sensor switching
6) Remote controller custom code
7) External input control
8) Room temperature sensor switching (Aux.)
9) Indoor unit fan control for energy saving for cooling
WALL MOUNTED TYPE
ASU9-12RLF1
1) Filter sign
Select appropriate intervals for displaying the lter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard (400 hours)
Long interval (1000 hours)01
Short interval (200 hours)02
No indication03
11
00
2) Room temperature control for cooling
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard
Slightly lower control01
Lower control02
Higher control03
30
00
3) Room temperature control for heating
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
(... Factory setting)
Setting descriptionFunction numberSetting value
Standard
Lower control01
Slightly higher control02
Higher control03
31
00
- (01 - 22) -
Page 26
WALL MOUNTED TYPE
ASU9-12RLF1
4) Auto restart
WALL MOUNTED TYPE
ASU9-12RLF1
Enable or disable automatic restart after a power interruption.
(... Factory setting)
Setting descriptionFunction numberSetting value
Enable
Disable01
40
00
* Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external
input device.
5) Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperture sensor, change the setting to "Both" (01).
(... Factory setting)
Setting descriptionFunction numberSetting value
Indoor unit
Both01
42
00
* 00: Sensor on the indoor unit is active.
*01: Sensors on both indoor unit and wired remote controller is active.
*Remote controller sensor must be turned on by using the remote controller.
6) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
(... Factory setting)
Setting descriptionFunction numberSetting value
A
B01
C02
D03
44
00
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(... Factory setting)
Setting descriptionFunction numberSetting value
Operation/Stop mode
(Setting prohibited)01
Forced stop mode02
46
00
8) Room temperature sensor switching (Aux.)
To use the sensor on the wired remote controller only, change the setting to "Wired remote
controller" (01). This function will only work if the function setting 42 is set at "Both" (01)
(... Factory setting)
Setting descriptionFunction numberSetting value
Wired remote controller01
Both
48
00
- (01 - 23) -
Page 27
WALL MOUNTED TYPE
ASU9-12RLF1
9) Indoor unit fan control for energy saving for cooling
WALL MOUNTED TYPE
ASU9-12RLF1
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
(... Factory setting)
Setting descriptionFunction numberSetting value
Disable
Enable01
49
00
*00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller..
*01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
- (01 - 24) -
Page 28
WALL MOUNTED TYPE
ASU9-12RLF1
REMOTE CONTROLLER CUSTOM CODE SETTING
Use the following steps to select the custom code of the remote controller.
(Note that the air conditioner cannot receive a signal if the right custom code has not
been set.)
Press the START/STOP button until only the clock is displayed on the remote 1.
controller display.
Press the MODE button for at least ve seconds to display the current custom 2.
code (initially set to ).
Press the SET TEMP. (3. ) ( ) button to change the custom code between →
→ → .
Match the code on the display to the air conditioner custom code.
Press the MODE button again to return to the clock display. The custom code will 4.
be changed.
If no buttons are pressed within 30 seconds after the custom code is displayed, the system returns to the original
clock display. In this case, start again from step 1.
The air conditioner custom code is set to A prior to shipment.
The remote controller resets to custom code A when the batteries in the remote controller are replaced. If you use a
custom code other than custom code A, reset the custom code after replacing the batteries. If you do not know the
air conditioner custom code setting, try each of the custom codes ( → → → ) until you nd the code which
operates the air conditioner.
WALL MOUNTED TYPE
ASU9-12RLF1
REMOTE CONTROLLER TEMPERATURE UNIT
To change the temperature unit:
• Press the °C / °F switching button to select the preferred temperature unit. (Factory setting is °F.)
- (01 - 25) -
Page 29
OPTIONAL PARTS13.
Mode
Menu
Cool
Monitor
Set temp.
Fan
High
°
F
80
Mo
10:00
AM
Icon check:
CONTROLLERS13-1.
WALL MOUNTED TYPE
ASU9-12RLF1
ExteriorParts nameModel No.Summary
Large and full-dot liquid crystal
screen, wide and large keys
Wired remote
controller
UTY- RVNUM
easy to press, user-intuitive
arrow key.
*Optional communication kit
is necessary for installation.
The room temperature can
be controlled by detecting the
Wired remote
controller
UTY-RNNUM
temperature accurately with
built-in thermo sensor.
*Optional communication kit
is necessary for installation.
Compact remote controller
concentrates on the basic
Simple remote
controller
UTY- RSNUM
functions such as Start/Stop,
Fan Control, Temperature
Setting and Operation mode.
*Optional communication kit
is necessary for installation.
WALL MOUNTED TYPE
ASU9-12RLF1
OTHERS13-2.
ExteriorParts nameModel No.Summary
Use to connect with optional
devices and air conditioner
PC board.
TypeINVERTER HEAT PUMP
Model nameAOU9RLFW1AOU12RLFW1
Power sourse208/230V~60HZ
Available voltage range187-253V~60HZ
Starting currentA4.25.9
Airow rate
Fan
OUTDOOR UNIT
AOU9-12RLFW1
Sound pressure level
Heat exchanger type
Compressor
Refrigerant
Refrigerant oilTypeRB68VG74
Enclosure
Dimensions
(H×W×D)
Weight
Connenction
pipe
Operation range
Type×Q'tyPropeller fan×1
Motor outputW2337
Type×Q'tyRotary×1
Motor outputW500750
Net
Gross
Net
Gross67(30)86(39)
Size
MethodFlare
Pre - charge length
Min. length9(3)
Max.length66(20)
Max.height difference49(15)
Cooling
Heating906(1540)889(1510)
Cooling
Heating4849
Dimensions
(H×W×D)
Fin pitchFPI18
Rows×Stages2×24
Pipe typeCopper
Fin TypeAluminum
TypeR410A
Charge
MaterialSteel
Color
Liquid
GasØ3/8(Ø9.52)
Cooling
Heating5 to 75(-15to 24)
CFM
(m3/h)
dB(A)
in.19-13/16×25-1/4×1-7/1619-13/16×35-1/4×1-7/16
mm504×642×36.4504×896×36.4
lb.oz.1lb.14oz.2lb.5oz.
kg0.85 1.05
mm540×660×290540×790×290
in. 21-1/4×26×11-7/16 21-1/4×31-1/8×11-7/16
mm611×797×401648×934×400
in. 24-1/16×31-3/8×15-13/1625-1/2×36-3/4×15-3/4
lb.(kg)
in.
(mm)
ft.
(m)
°F
(°C)
995(1690)1036(1760)
4849
Beige
Approximate color of MUNSELL 10YR7.5/1.0
60(27)80(36)
Ø1/4(Ø6.35)
49(15)
14to115(-10 to 46)
OUTDOOR UNIT
AOU9-12RLFW1
Note:
Specications are based on the following conditions.
Cooling:Indoor temperature of 80°F(26.67°C)DB/67°F(19.44°C)WB,and outdoor temperature of 95°F(35°C)DB/75°F(23.9°C)WB.
Heating:Indoor temperature of 70°F(21.11°C)DB/59°F(15°C)WB,and outdoor temperature of 47°F(8.33°C)DB/43°F(6.11°C)WB.
Pipe length:24ft.(7.5m),Height difference:0ft. (0m)(Outdoor unit-Indoor unit)
- (02 - 01) -
Page 33
DIMENSIONS2.
24 (600)
or more
10 (250)
or more
10 (250)
or more
12 (300)
or more
24 (600)
or more
4 (100)
or more
12 (300)
or more
4 (100)
or more
10 (250) or more
(Service space)
MODEL : AOU9RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
13/16 (20)
21-1/4 (540)
12-1/2 (318)
26 (660)
13-16 (20)
3/8 (9)
17-7/8 (454)
2-11/16 (68)11/16 (18)3/8 (10)11-7/16 (290)
13-7/8 (352)
6-7/8 (175)
5-5/16 (135)
INSTALLATION PLACE
When there are obstacles at the
back or front sides.
When there are obstacles at the
back, side(s), and top.
4-5/16 (110)
Unit : in.(mm)
When there are obstacles at the
back, side with the installation of
more than one unit.
- (02 - 02) -
Page 34
MODEL : AOU12RLFW1
24 (600)
or more
10 (250)
or more
10 (250)
or more
12 (300)
or more
24 (600)
or more
4 (100)
or more
12 (300)
or more
4 (100)
or more
10 (250) or more
(Service space)
OUTDOOR UNIT
AOU9-12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
13/16 (20)
21-1/4 (540)
12-1/2 (318)
31-1/8 (790)
13-16 (20)
3/8 (9)
21-1/4 (540)
2-11/16 (68)11/16 (18)3/8 (10)11-7/16 (290)
13-7/8 (352)
6-7/8 (175)
8-1/4 (209)
4-5/16 (110)
INSTALLATION PLACE
When there are obstacles at the
back or front sides.
When there are obstacles at the
back, side(s), and top.
Unit : in.(mm)
When there are obstacles at the
back, side with the installation of
more than one unit.
- (02 - 03) -
Page 35
REFRIGERANT CIRCUIT3.
MODEL : AOU9RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
- (02 - 04) -
Page 36
MODEL : AOU12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
- (02 - 05) -
Page 37
WIRING DIAGRAMS4.
MODEL : AOU9RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
- (02 - 06) -
Page 38
MODEL : AOU12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
- (02 - 07) -
Page 39
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 5.
AND HEIGHT DIFFERENCE
MODEL : AOU9RLFW1
Pipe length
COOLING
Ú
OUTDOOR UNIT
AOU9-12RLFW1
Indoor unit is higher
than outdoor unit.
Height
difference H
Indoor unit is lower
than outdoor unit
Indoor unit is higher
than outdoor unit.
Height
difference H
Indoor unit is lower
than outdoor unit
1
Ú
2
HEATING
Ú
1
Ú
2
15m49ft.---0.872 0.910
10m33ft.--0.961 0.886 0.925
7.5m25ft.-0.979 0.965 0.890 0.929
5m16ft.0.9920.983 0.969 0.893 0.933
0m0ft.1.000 0.991 0.976 0.901 0.940
-5m-16ft.1.000 0.991 0.976 0.901 0.940
-7.5m-25ft.-0.991 0.976 0.901 0.940
-10m-33ft.--0.976 0.901 0.940
-15m-49ft.---0.901 0.940
15m49ft.---0.832 0.822
10m33ft.--0.917 0.832 0.822
7.5m25ft.-0.961 0.917 0.832 0.822
5m16ft.1.000 0.961 0.917 0.832 0.822
0m0ft.1.000 0.961 0.917 0.832 0.822
-5m-16ft.0.995 0.956 0.912 0.828 0.818
-7.5m-25ft.-0.954 0.910 0.826 0.816
-10m-33ft.--0.908 0.824 0.814
-15m-49ft.---0.815 0.805
5m7.5m10m15m20m
16ft.25ft.33ft.49ft.66ft.
Pipe length
5m7.5m10m15m20m
16ft.25ft.33ft.49ft.66ft.
OUTDOOR UNIT
AOU9-12RLFW1
Height difference H
Indoor unit
HH
Outdoor unit
Connection pipe
1 Indoor unit is higher than outdoor unit.
Outdoor unit
Indoor unit
Connection pipe
2 Indoor unit is lower than outdoor unit.
- (02 - 08) -
Page 40
MODEL : AOU12RLFW1
Pipe length
COOLING
Ú
OUTDOOR UNIT
AOU9-12RLFW1
Indoor unit is higher
than outdoor unit.
Height
difference H
Indoor unit is lower
than outdoor unit
Indoor unit is higher
than outdoor unit.
Height
difference H
Indoor unit is lower
than outdoor unit
1
Ú
2
HEATING
Ú
1
Ú
2
15m49ft.---0.858 0.868
10m33ft.--0.929 0.872 0.882
7.5m25ft.-0.960 0.933 0.876 0.885
5m16ft.0.9920.964 0.937 0.879 0.889
0m0ft.1.000 0.972 0.944 0.887 0.896
-5m-16ft.1.000 0.972 0.944 0.887 0.896
-7.5m-25ft.-0.972 0.944 0.887 0.896
-10m-33ft.--0.944 0.887 0.896
-15m-49ft.---0.887 0.896
15m49ft.---0.896 0.879
10m33ft.--0.968 0.890 0.879
7.5m25ft.-0.994 0.968 0.896 0.879
5m16ft.1.000 0.994 0.968 0.896 0.879
0m0ft.1.000 0.994 0.968 0.896 0.879
-5m-16ft.0.995 0.989 0.963 0.891 0.875
-7.5m-25ft.-0.987 0.961 0.889 0.873
-10m-33ft.--0.959 0.887 0.871
-15m-49ft.---0.878 0.862
5m7.5m10m15m20m
16ft.25ft.33ft.49ft.66ft.
Pipe length
5m7.5m10m15m20m
16ft.25ft.33ft.49ft.66ft.
OUTDOOR UNIT
AOU9-12RLFW1
Height difference H
Indoor unit
HH
Outdoor unit
Connection pipe
1 Indoor unit is higher than outdoor unit.
Outdoor unit
Indoor unit
Connection pipe
2 Indoor unit is lower than outdoor unit.
- (02 - 09) -
Page 41
ADDITIONAL CHARGE CALCULATION6.
MODEL : AOU9RLFW1
Refrigerant typeR410A
Refrigerant amount
REFRIGERANT CHARGE
OUTDOOR UNIT
AOU9-12RLFW1
z
Pipe length
Additional charge
lb. oz.1lb.14oz.
g850
ft.49 or less66 (MAX)
m15 or less20 (MAX)
oz.03.5
g0+100
0.22oz./ft.
(20g /m)
OUTDOOR UNIT
AOU9-12RLFW1
MODEL : AOU12RLFW1
Refrigerant typeR410A
Refrigerant amount
REFRIGERANT CHARGE
z
lb. oz.2lb.5oz.
g1050
Pipe length
Additional charge
ft.49 or less66 (MAX)
m15 or less20 (MAX)
oz.03.5
g0+100
0.22oz./ft.
(20g /m)
- (02 - 10) -
Page 42
AIR FLOW7.
MODEL : AOU9RLFW1
Cooling
z
Number of
rotations
(r.p.m.)
1690m
Air ow
3
/h
OUTDOOR UNIT
AOU9-12RLFW1
780
Heating
z
Number of
rotations
(r.p.m.)
720
469 l/s
995 CFM
Air ow
1540m
428 l/s
906 CFM
OUTDOOR UNIT
AOU9-12RLFW1
3
/h
MODEL : AOU12RLFW1
Cooling
z
Number of
rotations
(r.p.m.)
1760m
Air ow
3
/h
780
Heating
z
Number of
rotations
(r.p.m.)
680
489 l/s
1036 CFM
Air ow
1510m
419 l/s
889 CFM
3
/h
- (02 - 11) -
Page 43
OPERATION NOISE8.
NOISE LEVEL CURVE (SOUND PRESSURE)8-1.
MODEL : AOU9RLFW1
Cooling
z
80
70
OUTDOOR UNIT
AOU9-12RLFW1
60
50
40
30
20
Octave band sound pressure level, dB:(0 dB= 0.0002µbar)
10
0
63 125 250 500 1,000 2 ,000 4,000 8,0 00
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0 dB= 0.0002µbar)
10
0
63 125 250 500 1,000 2 ,000 4,000 8,0 00
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
OUTDOOR UNIT
AOU9-12RLFW1
MODEL : AOU12RLFW1
Cooling
z
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0 dB= 0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
Heating
z
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0 dB= 0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC -15
0
63 125 250 500 1,000 2 ,000 4,000 8,0 00
Octave band center frequency,Hz
- (02 - 12) -
0
63 125 250 500 1,000 2 ,000 4,000 8,0 00
Octave band center frequency,Hz
Page 44
SOUND LEVEL CHECK POINT8-2.
40 in. (1m)
OUTDOOR UNIT
AOU9-12RLFW1
OUTDOOR UNIT
AOU9-12RLFW1
- (02 - 13) -
Page 45
ELECTRIC CHARACTERISTICS9.
Model NameAOU9RLFW1AOU12RLFW1
Power Supply
MCAA1012
Starting CurrentA4.25.9
*1) Wiring Spec.
OUTDOOR UNIT
AOU9-12RLFW1
*1) Wiring Spec.
Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E00005)
MCA: Min Circuit Amp(Calculation based on UL1995)
MAX. CKT. BKR: Maximum Circuit Breaker
VoltageV208 / 230~
FrequencyHz60
MAX. CKT. BKR A1520
Power CableAWG14
OUTDOOR UNIT
AOU9-12RLFW1
- (02 - 14) -
Page 46
SAFETY DEVICES10.
Model
Protection form
AOU9RLFW1AOU12RLFW1
Current fuse
(IN THE INVERTER CASE)
Circuit protection
OUTDOOR UNIT
AOU9-12RLFW1
Fan motor protection Terminal protection program
Compressor
protection
Current fuse
(MAIN PRINTED
CIRCUIT BOARD)
Terminal protection program
COMPRESSOR TEMP.
─
OFF: 212±27°F (100±15°C)
ON: 203±18°F (95±10°C)
250V 20A
250V 5A
OFF: 302±27°F (150±15°C)
ON: 230±18°F (120±15°C)
OFF:230°F (110°C)
ON:After 7 minutes
250V 15A
250V 3.15A
OUTDOOR UNIT
AOU9-12RLFW1
- (02 - 15) -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.