Fujitsu ASU15RLQ/AOU15RLQ, ASU18RLQ/AOU18RLQ Installation Manual

Page 1
SPLIT TYPE ROOM AIR CONDITIONER
INSTALLATION MANUAL
(P/N 9314989063-01) ENGLISH
(MODEL: ASU15RLQ/AOU15RLQ; ASU18RLQ/AOU18RLQ)
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all danger, warning, and caution notices given in
this manual.
WARNING:
CAUTION:
Hazel alerting symbols
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury and the potential for product or property damage.
Electrical
Connect all wiring tightly. Loose wiring may cause overheating at con­nection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing...
...In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
...In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
...In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnor­mal vibration.
...In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
Safety / alert
If Necessary, Get Help
These instructions are all you need for most installation sites and mainte­nance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
...In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Keep all tubing runs as short as possible.
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the flare and
union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either nar­row or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “small” or “large” rather than as “liquid” or “gas”.
When Servicing
Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check that no metal
scraps or bits of wiring have been left inside the unit being serviced.
After installation, explain correct operation to the customer, using the operating manual.
Page 2
This air conditioner uses new refrigerant HFC (R410A).
5 cm or over
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant(R22) mod-
els, some of the piping and installation and service tools are special.(See the table below.)
Especially, when replacing a conventional refrigerant(R22) model with a new refrigerant R410A model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent
erroneous charging with conventional refrigerant(R22) and for safety. Therefore, check beforehand.[The charging port thread diameter for R410A is 1/2 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant(R22) models. Also, when storing the piping ,securely seal the opening by pinching, taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the gas
and liquid phases, and always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Tool name
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the ex­pansion value or capillary tube may become blocked with con­taminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table1.Never use copper pipes thinner than 0.8mm even when it is available on the market.
(1) Do not use the existing (for R22) piping and flare nuts.
• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc.(Use the special R410A materials.)
mixing of other refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Contents of change
Table 1 Thicknesses of Annealed Copper Pipes
WARNING
Nominal
diameter
1/4
1/2
Outer diameter
(mm)
6.35
12.7
Thickness (mm)
R410A
0.80
0.80
[ref.] R22
0.80
0.80
(2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A)
to enter the refrigerant cycle.
• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause breakage, injury, etc.
When installing pipes shorter than 3m, sound of the outdoor unit will be transferred to the indoor unit, which will cause large operating sound or some abnormal sound.
CAUTION
Page 3
GENERAL
This INSTALLATION MANUAL briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1.
TYPE OF COPPER PIPE AND INSULATION MATERIAL
Copper tubing for connectin the outdoor unit to the indoor unit and insulation material is available for purchase locally. When you purchase them, please specify the following.
A.
Deoxidized annealed copper pipe for refrigerant piping as:
Table 3
Small pipe Large pipe
Outer diameter Thickness Outer diameter Thickness
1/4”(6.35 mm) 1/32”(0.8 mm) 1/2”(12.7 mm) 1/32”(0.8 mm)
Cut each pipe to the appropriate length +12” (30 cm) to16” (40 cm) to dampen vibration between units.
B. Foamed polyethylene insulation for copper pipes as
required to precise length of piping. Wall thickness of the insulation should not be less than 5/16” (8 mm).
C. Use insulated copper wire for field wiring.
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Wall hook bracket
Remote control unit
Battery (penlight)
Remote control unit holder
Q’ty
1
1
2
1
Name and Shape
Cloth tape
Tapping screw (big)
Tapping screw (small)
Air-cleaning and Deodorizing filter
Q’ty
1
8
2
1
2. ADDITIONAL MATERIALS REQUIRED FOR INSTALLATION
A. Refrigeration (armored) tape B. Insulated staples or clamps for connecting wire
(See your local electrical codes.) C. Putty D. Refrigeration lubricant E. Clamps or saddles to secure refrigerant piping
3. OPERATING RANGE
Table 4
Cooling/Dry Mode
Outdoor temperature
Indoor temperature
Indoor humidity
About 14 to 115 °F
About 64 to 90 °F
About 80% or less
ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 49 ft (15 m) is charged in the outdoor unit at the factory. When the piping is longer than 49 ft (15 m), additional charging is necessary. For the additional amount, see the table below.
Table 5
Pipe length
Additional
refrigerant
Between 49 ft (15 m) and 66 ft (20 m), when using a connection pipe other than that in the table, charge additional refrigerant with 0.2 oz/ ft (20g/1 m) as the criteria.
(1) When adding refrigerant, add the refrigerant from
the charging port at the completion of work.
(2) The maximum length of the piping is 66 ft (20 m).
If the units are further apart than this, correct operation can not be guaranteed.
49 ft (15 m)
None
66 ft (20 m)
3.5 oz (100 g)
CAUTION
Heating Mode
About 5 to 75 °F
88 °F or less
Seal A
1
The following items are necessary to install this air conditioner. (The items are not included with the air conditioner and must be purchased separately.)
Name
Connection pipe assembly
Connection cord (3-conductor)
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
Q’ty
1
1
1
1
1
1
1 set
1
1 set
1
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch cir­cuit and provide a special switch and receptacle. Do not extend the power cord.
CAUTION
MINIMUM CIRCUIT AMPACITY 16 A
MAXIMUM OVERCURRENT PROTECTION (TIME DELAY FUSE OR HACR TYPE CIRCUIT BREAKER)
20 A
Page 4
SELECTING THE MOUNTING
INSTALLATION DIAGRAM OF
POSITION
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject
to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room. (3) Install the unit near an electric outlet or special branch circuit. (4) Do not install the unit where it will be exposed to direct sunlight. (5) Install the unit where connection to the outdoor unit is easy. (6) Install the unit where the drain pipe can be easily installed. (7) Take servicing, etc. into consideration and leave the spaces shown
in (Fig. 7). Also install the unit where the filter can be removed.
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to di-
rect sunlight. (If necessary, install a blind that does not interfere
with the air flow.) (2) Do not install the unit where a strong wind blows or where it is
very dusty. (3) Do not install the unit where people pass. (4) Take your neighbors into consideration so that they are not dis-
turbed by air blowing into their windows or by noise. (5) Provide the space shown in Fig. 7 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four direc-
tions front, rear, and both sides.
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
CAUTION
(1) Do not install where there is the danger of com-
bustible gas leakage. (2) Do not install near heat sources. (3) If children under 10 years old may approach the
unit, take preventive measures so that they can-
not reach the unit.
INDOOR AND OUTDOOR UNITS
Fig. 7
[INDOOR UNIT]
2-2/5”(6 cm) or over
60”(150 cm) or over
Dust collection unit
Air-cleaning and Deodorizing filter
Air filter
Remote control unit
Connection Cord
14AWG
[OUTDOOR UNIT]
4”(10 cm) or over
12”(30 cm) or over
2”(5 cm) or over
95” (240 cm) or over
24”(60 cm) or over
Wall hook bracket
3- 3/5”(9 cm) or over
(Wall cap)
Remote control unit holder
Tapping screw (small)
4”(10 cm) or over
12”(30 cm) or over
[Indoor unit piping direction]
The piping can be connected in the 6 directions indicated in (Fig. 6). When the piping is connected in direction 2, 3, 4 or 5, cut along the piping groove in the side of the front cover with a hacksaw.
Fig. 6
2 Right outlet
3 Bottom outlet
Fig. 8
21-1/4” (54 cm)
(Rear)
1 Rear outlet
4 Left bottom
outlet
5 Left outlet
6 Left rear outlet
12-9/16” (32 cm)
Mounting Support (Prepared On-site)
2”(5 cm) or over
[Reverse cycle only]
Outdoor unit bottom
Drain hose
NOTE:
In places where the outdoor temperature drops to 32°F or lower, the drain water may freeze and may stop up the drain or cause other outdoor unit trouble. Therefore take measures so that the drain water will not freeze and clog the drain.
Page 5
INDOOR UNIT
1. CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING
(1) Cut a 3-2/16’’(80 mm) diameter hole in the wall at the position shown
in (Fig.1).
(2) When cutting the wall hole at the inside of the wall hook bracket,
cut the hole within the range of the left and right center marks 3/8’’(10 mm) below the installation frame.
When cutting the wall hole at the outside of the wall hook bracket,
cut the hole at least 3/8’’(10 mm) below less.
(3) Cut the hole so that the outside end is lower 3/16’’ to 3/8’’ (5 to 10 mm)
than the inside end.
(4) Always align the center of the wall hole. If misaligned, water leak-
age will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall
cap, fasten the cap with vinyl tape, and stick the pipe through the hole. (The connection pipe is supplied in the installation set.) (Fig.1)
(6) For left piping and right piping, cut the hole a little lower so that
drain water will flow freely. (Fig.1)
Fig. 1
Fasten with vinyl tape
(Wall cap)
Lower
3/8’’(10 mm) or over
(Wall pipe)
(Inside)
3-2/16’’(80 mm) dia. hole
Wall
Center mark
3/16’’ to 3/8’’ (5 to 10 mm) low
(Outside)
Lower
3/8’’(10 mm) or over
3-2/16’’(80 mm) dia. hole (A 2-9/16’’(65mm) diameter hole is possible for the right­hand side.)
2. INSTALLING THE WALL HOOK BRACKET
(1) Install the wall hook bracket so that it is correctly positioned hori-
zontally and vertically. If the wall hook bracket is titled, water will drip to the floor.
(2) Install the wall hook bracket so that it is strong enough to with-
stand the weight of an adult.
Fasten the wall hook bracket to the wall with 6 or more screws
through the holes near the outer edge of the bracket.
Check that there is no rattle at the wall hook bracket.
WARNING
If the wall pipe is not used, the cord interconnecting the indoor and outdoor units may touch metal and cause electric leakage.
3. FORMING THE DRAIN HOSE AND PIPE
[Rear piping, Right piping, Bottom piping]
Install the indoor unit piping in the direction of the wall hole and
bind the drain hose and pipe together with vinyl tape. (Fig. 3)
Install the piping so that the drain hose is at the bottom.
Wrap the pipes of the indoor unit that are visible from the outside
with decorative tape.
[For Left rear piping, Left piping]
Interchange the drain cap and the drain hose.
CAUTION
(1) In order to align the drain hose and drain cap, be
sure to insert securely and vertically. Incline in­sertion will cause water leakage.
When inserting, be sure not to attach any mate-
(2)
rial besides water. If any other material is attached, it will cause deterioration and water leakage.
(3) After removing drain hose, be sure not to forget
mounting drain cap.
Be sure to fix the drain hose with tape to the bot-
(4)
tom of piping.
Prevent drain water frozen under low tempera-
(5)
ture environment.
When installing indoor unit's drain hose outdoors, necessary measure for frost protection should be taken to prevent drain water frozen.
Under low temperature environment (when out-
door temperature under 32 °F), after cooling op­eration is executed, water in the drain hose could be frozen. Once drain water is frozen, the drain hose will be blocked and water leakage may be resulted for indoor unit.
Wall hook bracket
Center notch
Fig. 2
Hook
Tapping screw
Wall hook bracket
Counter weight
String
CAUTION
Install the wall hook bracket horizontally and perpen­dicularly.
Fig. 3
Right piping
Bottom
piping
Indoor unit drain hose
Removal method of drain hose
Remove the screw at the left of
drain hose and pull out drain hose.
Screw
Drain fixture (blue)
Be sure to install around the drain hose connector.
As the screw is inside, be sure to use screwdriver treated with magnet.
Drain hose
Bind with vinyl tape
Pipe (top) Rear piping
Indoor unit drain hose (bottom)
For left outlet piping, cut off the piping outlet cutting groove with a hacksaw.
Remove the drain cap by pulling
Drain cap
at the projection at the end of the cap with pliers, etc.
Installation method of drain hose
Vertically insert the drain hose
toward the inside, so that the drain fixture (blue) can accu­rately align with the screw hole around the drain cock. After inserting and before re­placing, please reinstall and fix the removed screws.
Drain fixture (blue)
Screw hole
Screw
Drain hose
Drain cock
Page 6
For left piping and left rear piping, align the marks on the wall
hook bracket and shape the connection pipe.
Bend the connection piping at a bend radius of 2- 3/4’’(70 mm) or
more and install no more than 1- 3/8’’(35 mm) from the wall.
After passing the indoor piping and drain hose through the wall
hole, hang the indoor unit on the hooks at the top and bottom of the wall hook bracket.
[Installing the indoor unit]
Hang the indoor unit from the hooks at the top of the wall hook
bracket.
Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.
Indoor unit
Fig. 4
Bend 2-3/4’’(R70) with a pipe bender
Align the marks.
Connection pipe (1/2’’(12.7 mm) dia.)
Connection pipe (1/4” (6.35 mm) dia.)
Top hooks
(Spacer)
Wall hook bracket
4. CONNECTING THE PIPING
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional in-
stallation set or procured at the site) to the wall pipe. (2) Connect the outdoor unit and indoor unit piping. (3) After matching the center of the flare surface and tightening the
nut hand tight, tighten the nut to the specified tightening torque
with a torque wrench. (Tighten the flare nut of the outdoor unit
3-way valve after air purging.)
FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter. (2) Hold the pipe downward so that cuttings will not enter the pipe
and remove the burrs. (3) Insert the flare nut onto the pipe and flare the pipe with a flaring
tool.
Check if [L] is flared uniformly and is not cracked or scratched.
L dimension
Thin pipe 1/4” (6.35 mm)dia. ...... 1/16” (1.4 to 1.7 mm)
Thick pipe 1/2” (12.7 mm)dia. ...... 5/64” (1.9 to 2.2 mm)
Indoor unit
After hooking the indoor unit to the top hook, hook the fittings of the indoor unit to the two bottom hooks while lowering the unit and pushing it against the wall.
(Fitting)
Bottom hooks
Fig. 5
Tighten with two wrenches.
Wrench (fixed)
Torque wrench
Indoor unit pipe
Flare nut
Connection pipe
To prevent gas leakage, coat the flare surface with refrigerator oil.
Table 2 Flare nut tightening torque
Flare nut
1/4” (6.35 mm)dia.
1/2” (12.7 mm)dia.
Tightening torque
11.57 to 13.02 ft•lbs (160 to 180 kgf•cm)
36.17 to 39.78 ft•lbs
(500 to 550 kgf•cm)
Wall hook bracket
BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
OK NO
Do not bend the pipes in an angle more than 90°. When pipes are repeatedly bent or stretched, the material will harden, making it difficult to bend or stretch them any more. Do not bend or stretch the pipes more than three times.
Extend the pipe by unwinding it.
CAUTION
(1) Fasten a flare nut with a torque wrench as instructed in this manual. If
fastened too tight, the flare nut may be broken after a long period of time and cause a leakage of refrigerant.
(2) During installation, make sure that the refrigerant pipe is attached firmly
before you run the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
Page 7
OUTDOOR UNIT
L
O
H
I
OUTDOOR UNIT INSTALLATION
Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trouble.
Connector cover removal
Remove the mounting screw.
Installing the connector cover
(1) After inserting the three front hooks, then insert the rear hook. (2) Tighten the mounting screw.
WARNING
(1) Install the unit where it will not be tilted by more
than 5°.
(2) When installing the outdoor unit where it may ex-
posed to strong wind, fasten it securely.
AIR PURGE
Always use a vacuum pump to purge the air. Refrigerant for purging the air is not charged in the outdoor unit at the factory.
Close the high pressure side valve of the gauge manifold fully and do not operate it during the following work.
Fig. 9
Tapping screw
Front hooks
Rear hooks
Connector cover
1. Check if the piping connections are secure.
2. Check that the stems of 2-way valve and 3-way valve are closed fully.
3. Connect the gauge manifold charge hose to the charging port
of the 3-way valve (side with the projection for pushing in the valve core).
4. Open the low pressure side valve of the gauge manifold fully.
5. Operate the vacuum pump and start pump down.
6. Slowly loosen the flare nut of the 3-way valve and check if air enters, then retighten the flare nut. (When the flare nut is loosened the operating sound of the vacuum pump changes and the reading of the compound pressure gauge goes from minus to zero.)
7. Pump down the system for at least 15 minutes, then check if the compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).
8. At the end of pump down, close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump.
9. Slowly loosen the valve stem of the 3-way valve. When the compound pressure gauge reading reaches 0.1-0.2 MPa, retighten the valve stem and disconnect the charge hose from the 3-way valve charging port. (If the stem of the 3-way valve is opened fully before the charge hose is disconnected, it may be difficult to disconnect the charge hose.)
10. Fully open the valve stems of the 2-way valve and 3-way valve using a hexagon wrench. (After the valve stem begins to turn, turn it with a torque of less than 2.17ft •lbs (30 kgf•cm) until it stops turning.)
11. Firmly tighten the 2-way valve and 3-way valve blank cap and the charging port cap.
Fig. 10
Gauge manifold
-0.1 MPa (-76 cmHg
-1 bar)
Low pressure side valve
Pressure gauge
High pressure side valve (closed)
Charge hose
Vacuum pump
3-way valve
Charging port cap
2-way valve
Compound pressure gauge
Flare nut
Valve stem
Blank cap
Charge hose
Charging port
Table 6
Tightening torque
Blank cap (2-way valve) 14.47 to 18.08 ft•lbs (200 to 250 kgf•cm)
Blank cap (3-way valve) 20.25 to 23.15 ft•lbs (280 to 320 kgf•cm)
Charging port cap 9.04 to 11.57 ft•lbs (125 to 160 kgf•cm)
CAUTION
(1) Refrigerant must not be discharged into atmos-
phere.
(2) After connecting the piping , check the joints for
gas leakage with gas leak detector.
Page 8
ELECTRICAL WIRING (OUTDOOR UNIT)
G
1
G
3
2
1
2
3
208/230V
208/230V
208/230V
5
(L)
(N)
4
1. Remove the screws, then remove the control box cover.
2. Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut.
3. Connect inter-unit wire harness and power supply to the terminal. Refer to the wiring diagram
4. Use the screws to install the control box cover.
WARNING
Be sure to comply with local codes while run­ning the wire from the indoor unit to the out­door unit (size of wire and wiring method, etc. ).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant tubing, the compressor or any moving part.
Loose wiring may cause the terminal to over­heat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
Connect wires to the matching numbers of terminals.
Fig. 11
Indoor unit
Terminal
G
Grounding line
Outdoor unit
Terminal
G
NOTE:
Connector trade size for this unit is 1/2” (12.7 mm). The connec-
tor can be bought at a hardware store. Refer to How to connect wiring to the terminals for instructions on connecting depend­ing on the wire type you are using.
The fuse located in the outdoor unit provides power supply pro­tection and may blow when power is applied if the system has been incorrectly wired.
Lock nut
Cord Clamp
3
2
1
Earth screw
DISCONNECT SWITCH (FIELD SUPPLY)
Indoor unit terminal block
12
G
Control line
(Inter Unit) Power line
4
3
208/230V
208/230V
208/230V
Disconnect switch
(N)
(L)
5
4
3
2
1
POWER SUPPLY
1 phase, 208/230V
Outdoor unit terminal block
12
3
45
Earth screw
Conduit connector
Power supply Inter-unit wire harness
G
Power supply line
Page 9
ELECTRICAL WIRING (INDOOR UNIT)
HOW TO THE INSTALL THE INTER-UNIT WIRE HARNESS
1. Remove the screws, then remove the conduit holder.
2. Fasten the inter-unit wire harness to the conduit holder using the lock nut. IMPORTANT: Refer to Fig. 19 about the length of inter-unit wire harness.
3. Use the screws to install the conduit holder with which Inter-unit wire har­ness is included.
4. Remove the screws, then remove the cord clamp.
5. Connect inter-unit wire harness to the terminal. Refer to the wiring diagram.
6. Use the screws to install the cord clamp.
Fig. 13
Cord clamp
Fig. 12
Lock nut
Conduit Holder
Conduit Connector
Screw
Cord clamp
Screw
Connection cord
Connection cord
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 15/16" (25 mm) to expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using pliers, bend the solid wire to form a loop suitable for the termi-
nal screw.
(4) Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 3/8" (10 mm) to expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using a round terminal fastener or pliers, securely clamp a round
terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the termi-
nal screw using a screwdriver.
Fig. 14
A. Solid wire
Insulation
Strip 15/16" (25 mm)
Wire
Screw
Loop
Screw with special washer
Round terminal
Terminal board
Terminal block
Wire
B. Strand wire
Strip 3/8" (10 mm)
Screw with special washer
Round terminal
Round terminal
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the elec-
tric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
CAUTION
(3) Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.) (4) Securely earth the power cord plug. (5) Do not use the earth screw for an external connector.
Only use for interconnection between two units.
Page 10
FINISHING
(1) Insulate between pipes.
For rear, right, and bottom piping, overlap the connection pipe
heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
For left and left rear piping, butt the connection pipe heat insula-
tion and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap.
For left and left rear piping, wrap the area which accommodates
the rear piping housing section with cloth tape.
For left and left rear piping, bind the connection cord to the top
of the pipe with vinyl tape.
For left and left rear piping, bundle the piping and drain hose
together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
(2) Temporarily fasten the connection cord along the connection pipe
with vinyl tape. (Wrap to about 1/3 the width of the tape from the
bottom of the pipe so that water does not enter.) (3) Fasten the connection pipe to the outside wall with a saddle, etc. (4) Fill the gap between the outside wall pipe hole and the pipe with
sealer so that rain water and wind cannot blow in. (5) Fasten the drain hose to the outside wall, etc.
Fig. 15
Indoor unit pipe (heat insulation)
Connection pipe (heat insulation)
Pipe
Drain hose
Cloth tape
Connection cord
For connection from the left rear
Wall pipe
Vinyl tape
Wrap with cloth tape
Left piping
Pipe
Seal A
Butt connection pipe (heat insulation) against the indoor unit pipe (heat insulation) and wrap with seal A so that there is no gap.
Drain hose
Connection cord
Fig. 16
(Saddle)
Pipe
Wall
FRONT PANEL REMOVAL AND INSTALLATION
AIR CLEANING UNIT REMOVAL
(1) Open the intake grille, and then remove the right air filter.
(2) Pull the air cleaning unit grip in the direction of the arrow and remove the unit.
AIR CLEANING UNIT INSTALLATION
(1) Open the intake grille, and then insert the dust collection unit into the indoor unit. (2) Install the right air filter, and then close the intake grille.
THE INTAKE GRILLE REMOVAL
(1) Open the intake grille. (2) Pull down the knob. (3) Lift the intake grille upward, until the axle at the top of the intake
grille is removed.
THE INTAKE GRILLE INSTALLATION
(1) The fixing axle of the intake grille is installed on the Panel. (2) Lay down the intake grille.
THE FRONT PANEL REMOVAL
(1) Remove intake grille (Reference the intake grille removal.) (2) Remove four screws. (3) The thumb is hung on the lower part as shown in the figure, and it
pulls to the front, pushing [ tion) is removed from wall hook bracket.
(4) The front panel bottom is pulled to the front, and bottom hooks is
removed indoor unit.
(5) The front panel is pulled to the front, raising the upper surface,
and a front panel is removed.
THE FRONT PANEL INSTALLATION
(1) Firstly, fit the lower part of the front panel, and insert top and bot-
tom hooks. (Three top sides, six bottom sides) (2) Four screws is attached. (3) The intake grille is attached.
] mark , and bottom hooks (two posi-
(Outside wall cap)
(Sealer putty)
(Outdoors)
Check the following:
GOOD
Drain hose
Saddle
Fig. 17
Screws (4 position)
Top hole (center)
Indoor unit
INSERT
Intake grille
Mounting shaft
Bearing Front panel
[ ] mark
Push
Top holes (two sides)
Bottom hole (six position)
Drain hose
View from indoors
BAD
Lifted up
PULL
Push
Front panel
BAD BAD
Grip
Bottom hooks (six position)
Connection pipe
Wave
Front panel
Wall hook bracket
Top hook (two sides)
Top hook (center)
End in water
Intake grille
Knob
Front panel
Page 11
WIRED REMOTE CONTROL UNIT (OPTIONAL)
BEFORE INSTALL WIRED REMOTE CONTROL UNIT
The wired remote control unit is an option. It isn't included in main body of air-conditioner.
When you use wired remote control unit, some functions may not be used.
please use the recommended wired remote control unit.
(Before installing, Please read the FEATURES AND FUNCTIONS section of OPERATING MANUAL to confirm the concerned contents.)
CAUTION
(1) Before installing, be sure to disconnect all power supply. (2) Don't touch the heat exchanger. (3) During installing or removing operation, be sure not to have wire catched by parts or draw it hard. Or it
may result troubles to the air-conditioner. (4) Avoid place in direct sunlight. (5) Select place that will not be affected by the heat from a stove, etc. (6) Insure the length of wire is not over the recommended maxuim length. (7) Before setting up the wired remote control unit, please confirm whether air-conditioner can receive the
signal.
1. FRONT PANEL AND CONTROL UNIT REMOVAL
(1) Refer to " FRONT PANEL REMOBAL AND INSTALLATION " to remove the front panel. (2) Remove screws of the heat exchanger, ang then remove grounding wire. (3) Remove 2 thermistor. (4) Remove screw, then remove the connector cover and connector. (5) Remove screw, then remove the control unit.
THERMISTOR
SCREW
THERMISTOR
CONNECTOR
EARTH WIRE
CONTROL UNIT
SCREW
CONNECTOR
SCREW
CONNECTOR COVER
SCREW
Page 12
2. Connecting to control unit of wire
(1) Connect the wire of wired remote control unit to the board of Control unit. (2) Use wire clamper and screws to fasten wire. (3) Cut off part of the control unit and thread wire through.
CONNECTOR
CIRCUIT BOARD
SCREW
TO RENOTE CONNTROL UNIT
CLAMPER
3. FRONT PANEL AND CONTROL UNIT INSTALLATION
Install Front panel and Control unit by the reverse procedures as stated in "1. FRONT PANEL AND CONTROL UNIT REMOVAL".
CUT
Page 13
TEST RUNNING
Perform test operation and check items 1 and 2 below.
For the test operation method, refer to the operating manual.
The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit
while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run button with the tip of a ball-point pen, etc.)
To end test operation, press the remote control unit START/STOP button. (When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously flash slowly.)
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal? (2) Does each lamp light normally? (3) Do the air flow-direction louver operate normally? (4) Is the drain normal?
Transmitter section
Fig. 18
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation? (2) Will noise, wind, or drain water from the unit disturb the neighbors? (3) Is there any gas leakage?
Test run button
POWER
WARNING
(1) The rated voltage of this product is 208/230 V AC
60 Hz.
(2) Before turning on the power, check if the voltage
is within the 208 V-10% to 230V+10% range.
(3) Always use a special branch circuit and install a
special receptacle to supply power to the room air conditioner.
(4) Use a circuit breaker and receptacle matched to
(1) The power source capacity must be the sum of
the air conditioner current and the current of other electrical appliances. When the current contracted capacity is insufficient, change the contracted ca­pacity.
(2) When the voltage is low and the air conditioner is
difficult to start, contact the power company the voltage raised.
CAUTION
the capacity of the air conditioner. (5) Do not extend the power cord. (6) Perform wiring work in accordance with stand-
ards so that the air conditioner can be operated
safely and positively. (7) Install a leakage circuit breaker in accordance with
the related laws and regulations and electric com-
pany standards.
CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operat­ing manual: (1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow switching, and other remote control unit
operations. (2) Air filter removal and cleaning, and how to use the air louvers. (3) Give the operating and installation manuals to the customer.
PUMP DOWN OPERATION (FORCED COOLING OPERATION)
To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced cooling operation.)
(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening the
low-pressure valve slightly. (2) Close the valve stem of 2 way valve completely. (3) Start the cooling operation or following forced cooling operation.
When using the remote control unit
Press the TEST RUN button after starting the cooling operation by the remote control unit.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.) (4) Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm (5) Stop the operation.
• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side.
(It is not necessary to press on keeping for more than 10 seconds.)
2
).
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.
CAUTION
Page 14
The method of adjusting inter-unit wire harness
To connect inter-unit wire harness to the terminal correctly, please
refer to Fig. 19 to adjust the length of the part of Inter-unit Wire
harness ahead from conduit holder.
Fig. 19
14AWG
(1:1)
EARTH WIRE
15/16" (25mm)
5-1/2" (140mm) 15/16" (25mm)
4-3/16" (105mm)
CONDUIT PLATE
CONDUIT CONNECTOR
Page 15
REMOTE CONTROL UNIT INSTALLATION
CAUTION
(1) Check that the indoor unit correctly receives the
signal from the remote control unit, then install the remote control unit holder.
(2) Select the remote control unit holder selection
site by paying careful attention to the following: Avoid places in direct sunlight. Select a place that will not be affected by the heat from a stove, etc.
1. REMOTE CONTROL UNIT HOLDER INSTALLATION
Install the remote control unit with a distance of 23 ft(7
m) between the remote control unit and the photocell as the criteria. However, when installing the remote con­trol unit, check that it operates positively.
Install the remote control unit holder to a wall, pillar,
etc. with the tapping screw (Fig.20).
Fig. 20
Remote control unit holder fixing
Remote control unit holder
Tapping screw (small)
Remote control unit mounting
1 Set
2 Push
Remote control unit
Loading...