Fujitsu ASU12RLS3Y, ASU15RLS3Y, ASU9RLS3Y, AOU12RLS3H, AOU15RLS3H Design & Technical Manual

...
Page 1
AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
For Extra Cold Climate Area
INDOOR
OUTDOOR
ASU9RLS3Y ASU12RLS3Y ASU15RLS3Y
AOU12RLS3H AOU15RLS3H
DR_AS013EF_02
2018.04.26
Page 2
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Trademarks
The following term and logo are trademarks of Fujitsu General Limited in the United States, other countries or both:
FGLair
Android™ and Google Play™ are trademarks of Google Inc.
App Store® is a service mark of Apple Inc., registered in the U.S. and other countries.
IOS® is a trademark or registered trademark of Cisco in the U.S. and other countries and is used under license.
Copyright © 2016, 2018 Fujitsu General Limited. All rights reserved.
Page 3
CONTENTS
Part 1. INDOOR UNIT...........................................................................1
1. Specifications................................................................................................2
2. Wireless LAN control....................................................................................3
2-1. System requirement.........................................................................................................3
2-2. Wireless LAN function list ................................................................................................4
3. Dimensions....................................................................................................5
3-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y ..............................................5
4. Wiring diagrams ............................................................................................7
4-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y ..............................................7
5. Capacity table................................................................................................8
5-1. Cooling capacity...............................................................................................................8
5-2. Heating capacity ............................................................................................................11
6. Fan performance .........................................................................................13
6-1. Air velocity distributions..................................................................................................13
6-2. Airflow............................................................................................................................15
7. Operation noise (sound pressure).............................................................17
7-1. Noise level curve............................................................................................................17
7-2. Sound level check point.................................................................................................19
8. Safety devices .............................................................................................20
9. External input and output...........................................................................21
9-1. External input.................................................................................................................21
9-2. External output...............................................................................................................24
10. Remote controller .......................................................................................26
10-1.Wireless remote controller ............................................................................................26
11. Function settings ........................................................................................28
11-1.Function settings by using remote controller................................................................. 28
11-2.Custom code setting for wireless remote controller.......................................................34
11-3.Switching the temperature unit of remote controller...................................................... 35
12. Accessories .................................................................................................36
13. Optional parts..............................................................................................37
13-1.Controllers ....................................................................................................................37
13-2.Others...........................................................................................................................37
Page 4
CONTENTS (continued)
Part 2. OUTDOOR UNIT.....................................................................39
1. Specifications..............................................................................................40
2. Dimensions..................................................................................................41
2-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H...........................................41
3. Installation space ........................................................................................42
3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H...........................................42
4. Refrigerant circuit .......................................................................................45
4-1. Models: AOU9RLS3H and AOU12RLS3H..................................................................... 45
4-2. Model: AOU15RLS3H.................................................................................................... 46
5. Wiring diagrams ..........................................................................................47
5-1. Models: AOU9RLS3H and AOU12RLS3H..................................................................... 47
5-2. Model: AOU15RLS3H.................................................................................................... 48
6. Capacity compensation rate for pipe length and height difference........49
6-1. Models: AOU9RLS3H and AOU12RLS3H..................................................................... 49
6-2. Model: AOU15RLS3H.................................................................................................... 50
7. Additional charge calculation ....................................................................51
7-1. Models: AOU9RLS3H and AOU12RLS3H..................................................................... 51
7-2. Model: AOU15RLS3H.................................................................................................... 51
8. Airflow..........................................................................................................52
8-1. Models: AOU9RLS3H and AOU12RLS3H..................................................................... 52
8-2. Model: AOU15RLS3H.................................................................................................... 52
9. Operation noise (sound pressure).............................................................53
9-1. Noise level curve............................................................................................................53
9-2. Sound level check point.................................................................................................55
10. Electrical characteristics ............................................................................56
11. Safety devices .............................................................................................57
12. Accessories .................................................................................................58
Page 5

Part 1. INDOOR UNIT

WALL MOUNTED TYPE:
ASU9RLS3Y ASU12RLS3Y ASU15RLS3Y
Page 6

1. Specifications

Type
WALL MOUNTED
Model name ASU9RLS3Y ASU12RLS3Y ASU15RLS3Y
ASU9-15RLS3Y
Power supply 208/230 V ~ 60 Hz Power supply intake Outdoor unit Available voltage range 188—253 V
Capacity
Input power
Current
EER Cooling
COP Heating
SEER Cooling Btu/hW 33.0 29.3 25.3 HSPF Heating Btu/hW 14.0 13.8 13.3
Power factor
Moisture removal pints/h (L/h) 2.6 (1.2) 2.7 (1.3) 4.0 (1.9)
Maximum operating current *1
Fan
Sound pressure level *2
Heat exchanger type
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Drain hose
Operation range
Remote control
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) /67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB). – Heating: Indoor temperature of 70 °FDB (21.11 °CDB) /59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) /43 °FWB (6.11 °CWB). – Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play store or on App Store. For details, refer to the setting manual.
Wall mounted
Inverter heat pump
Cooling
Heating
Cooling
Heating
Cooling Heating 3.3 4.7 5.2
Cooling Heating 87 93 96
Cooling Heating 11.9 11.9 14.9
Cooling
Airflow rate
Heating
Type × Q'ty Cross flow fan × 1 Motor output W 61
Cooling
Heating
Dimensions (H × W × D) in (mm)
Fin pitch FPI Main: 21, Sub 1 and Sub 2: 18 Rows × Stages Main: 3 × 24, Sub 1: 1 × 4, Sub 2: 1 × 6 Pipe type Copper tube Fin type Aluminum Material Polystyrene
Color
Net
Gross
Net Gross 37 (17)
Size
Method Flare Material PP+LLDPF
Size in (mm)
Cooling
Heating °F (°C) 60 to 88 (16 to 30) Remote controller Wireless (Wired [option]) Mobile application *3 FGL new mobile app
Rated
Min.—Max.
Rated
Min.—Max.
Rated Min.—Max. 0.20—0.85 0.20—0.99 0.18—1.56 Rated 0.66 1.01 1.15 Min.—Max. 0.20—1.93 0.20—1.94 0.17—2.19
Rated A
HIGH MED 400 (680) 459 (780) LOW 341 (580) 371 (630) QUIET 224 (380) 259 (440) HIGH 489 (830) 547 (930) MED 400 (680) 459 (780) LOW 341 (580) 371 (630) QUIET 224 (380) 294 (500)
HIGH MED 37 40 LOW 32 34 QUIET 23 26 HIGH 41 45 MED 35 39 LOW 31 33 QUIET 23 27
Liquid Gas Ø 3/8 (Ø 9.52) Ø 1/2 (Ø 12.7)
kW 2.64 3.52 4.25
Btu/h 9,000 12,000 14,500
kW 0.90—3.60 0.90—4.00 0.90—5.40
Btu/h 3,100—12,000 3,100—13,600 3,100—18,400
kW 3.52 4.69 5.28
Btu/h 12,000 16,000 18,000
kW 0.90—6.45 0.90—6.48 0.90—7.00
Btu/h 3,100—22,000 3,100—22,100 3,100—23,900
kW
kW/kW 5.28 4.46 4.09 Btu/hW 18.0 15.2 13.9 kW/kW 5.33 4.64 4.59 Btu/hW 18.2 15.8 15.7
%
A
CFM (m3/h)
dB (A)
in 11-5/8 × 37 × 10-5/8
mm 295 × 940 × 270
in 14-3/8 × 40-15/16 × 14
mm 365 × 1,040 × 355
lb (kg)
in (mm)
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less
0.50 0.79 1.04
2.5 3.8 4.8
87 90 94
9.4 9.4 9.9
489 (830) 547 (930)
42 45
Main: 15-1/8 × 28-3/8 × 1-3/16 (384 × 720 × 30)
Sub 1: 3-5/16 × 28-3/8 × 1/2 (84 × 720 × 13.3)
Sub 2: 4-15/16 × 28-3/8 × 1/2 (126 × 720 × 13.3)
Approximate color of Munsell 5PB 9.25/0.5
Ø 5/8 to Ø 11/16 (Ø 15.8 to Ø 16.7) (O.D.)
White
31 (14)
Ø 1/4 (Ø 6.35)
Ø 9/16 (Ø 13.8) (I.D.)
WALL MOUNTED
ASU9-15RLS3Y
- 2 -
1. Specifications
Page 7

2. Wireless LAN control

By installing mobile app on a smart device, several functions can be controlled from outside the house.
WALL MOUNTED
ASU9-15RLS3Y

2-1. System requirement

Before using this function, prepare the following items:
Wireless router:
Wireless LAN standard IEEE802.11b/g/n
Frequency bands*
Network security standard
• U.S.A., Canada: 2.4 GHz (1ch—11ch)
• Other countries: 2.4 GHz (1ch—13ch)
• Open
• WEP
• WPA (PSK)
• WPA2 Personal (PSK)
• WPS for same-LAN registration
*: Usable only in the country or region where you purchased the product. To check whether your wireless router complies with the network security standards listed above,
refer to the operation manual.
WALL MOUNTED
ASU9-15RLS3Y
Smartphone or Tablet PC:
App-compliant operating system
®
iOS
Android
Version 8.0 or later
Version 4.1 or later
(mobile application): Mobile app is available on Google Play™ store or on App Store®. After installation of mobile app, user registration is required. For user registration and setup infor-
mation, refer to Setting Manual attached with the product.
For the latest version of the Wireless LAN (WLAN) control manuals, refer to the following web site. https://www.fujitsu-general.com/global/support/
2-1. System requirement 2. Wireless LAN control
- 3 -
Page 8

2-2. Wireless LAN function list

NOTE: To use Wireless LAN control, user registration in advance and access to the wireless home
WALL MOUNTED
ASU9-15RLS3Y
Air conditioning control function
Additional function MIN. HEAT operation setting ○* ○*
App function Air conditioner error e-mail notification
network are required.
Operation on/off ○ Operation mode setting ○ Set temperature setting ○ Fan speed setting
Airflow direction setting
Timer setting
POWERFUL operation setting ○* ○* ECONOMY operation setting
Human sensor setting ○* ○* Outdoor unit low noise operation setting ○* ○*
Item Mobile app
Louver position adjustment (vertical/horizontal)
Swing (vertical/horizontal) ○ Off timer ○ On timer ○ Sleep timer ○ On/off program timer ○ Weekly timer
Attached
wireless
remote
controller
WALL MOUNTED
ASU9-15RLS3Y
*: Not operable when wired remote controller is connected.
2-2. Wireless LAN function list 2. Wireless LAN control
- 4 -
Page 9

3. Dimensions

Unit: in (mm)
14-3/4 (375)
for pipe inlet Ø 2-9/16 (65)
for pipe inlet Ø 2-9/16 (65)
15-1/4 (387)
Outline of unit
18-1/2 (470) 18-1/2 (470)
10-5/8 (270)
1-11/16 (43)
11-5/8 (295)
11-5/8 (295)
37 (940)
37 (940)
15-1/4 (387)
3-1/4 (83)
3-1/16 (77)
15-7/16 (393)
1-9/16 (40)
3/8 (9)
1-11/16 (43)
WALL MOUNTED

3-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y

ASU9-15RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
3-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y 3. Dimensions
- 5 -
Page 10
¢
Outline of unit
Unit: in (mm)
2 (50) or more
5 (127) or more
2 (50) or more
6 (133) or more
60 (1,500) or more
2 (50) or more
4 (84) or more
71 (1,800) or more
Provide sufficient installation space for product safety.
WALL MOUNTED
ASU9-15RLS3Y
Installation space requirement
WALL MOUNTED
ASU9-15RLS3Y
3-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y 3. Dimensions
- 6 -
Page 11

4. Wiring diagrams

WALL MOUNTED

4-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y

ASU9-15RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
4-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y 4. Wiring diagrams
- 7 -
Page 12

5. Capacity table

Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR):
WALL MOUNTED
ASU9-15RLS3Y
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP)

5-1. Cooling capacity

¢
AFR CFM 489
Model: ASU9RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
°FDB
Outdoor temperature
104 6.00 5.67 0.45 6.68 6.16 0.46 7.36 6.71 0.46 7.60 7.26 0.46 8.05 7.22 0.47 8.52 7.70 0.47 115 5.52 5.33 0.45 6.17 5.71 0.46 6.78 6.22 0.46 6.99 6.74 0.46 7.43 6.71 0.47 7.84 7.15 0.47
AFR
°CDB
-10.0 2.44 2.36 0.19 2.72 2.38 0.19 3.00 2.60 0.20 3.10 2.79 0.20 3.27 2.78 0.20 3.46 2.95 0.21
-5.0 2.39 2.31 0.22 2.67 2.32 0.22 2.94 2.53 0.23 3.03 2.73 0.22 3.21 2.72 0.22 3.39 2.90 0.23
0.0 2.34 2.25 0.22 2.61 2.27 0.23 2.88 2.48 0.24 2.97 2.68 0.23 3.14 2.67 0.23 3.32 2.84 0.24
5.0 2.29 2.22 0.24 2.55 2.23 0.24 2.81 2.43 0.25 2.90 2.63 0.24 3.07 2.61 0.24 3.25 2.79 0.25
10.0 2.24 2.16 0.22 2.49 2.17 0.22 2.75 2.37 0.24 2.84 2.57 0.23 3.00 2.55 0.23 3.17 2.71 0.24
15.0 2.19 2.12 0.27 2.44 2.13 0.27 2.69 2.32 0.28 2.77 2.51 0.28 2.93 2.49 0.28 3.10 2.66 0.28
19.4 2.47 2.39 0.34 2.75 2.40 0.35 3.03 2.62 0.36 3.13 2.82 0.36 3.31 2.81 0.36 3.50 2.98 0.37
25.0 2.35 2.27 0.39 2.62 2.28 0.39 2.89 2.49 0.40 2.98 2.68 0.40 3.15 2.67 0.41 3.33 2.85 0.41
Outdoor temperature
30.6 2.22 2.14 0.44 2.48 2.16 0.44 2.73 2.35 0.45 2.81 2.54 0.45 2.98 2.53 0.46 3.15 2.69 0.46
35.0 2.08 2.02 0.48 2.32 2.03 0.49 2.56 2.21 0.50 2.64 2.39 0.50 2.8 2.38 0.51 2.95 2.53 0.51
40.0 1.76 1.66 0.45 1.96 1.80 0.46 2.16 1.97 0.46 2.23 2.13 0.46 2.36 2.12 0.47 2.50 2.26 0.47
46.0 1.62 1.56 0.45 1.81 1.67 0.46 1.99 1.82 0.46 2.05 1.98 0.46 2.18 1.97 0.47 2.30 2.10 0.47
°FDB 64 70 75 80 85 90 °FWB 54 60 63 67 71 73
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW 15 8.33 8.06 0.19 9.29 8.11 0.19 10.25 8.87 0.20 10.57 9.53 0.20 11.17 9.50 0.20 11.81 10.07 0.21 23 8.16 7.88 0.22 9.09 7.91 0.22 10.03 8.65 0.23 10.35 9.31 0.22 10.94 9.28 0.22 11.56 9.91 0.23 32 7.99 7.69 0.22 8.90 7.75 0.23 9.81 8.45 0.24 10.13 9.16 0.23 10.70 9.09 0.23 11.32 9.68 0.24 41 7.81 7.58 0.24 8.71 7.61 0.24 9.60 8.28 0.25 9.90 8.97 0.24 10.47 8.90 0.24 11.07 9.50 0.25 50 7.64 7.36 0.22 8.51 7.41 0.22 9.38 8.07 0.24 9.68 8.76 0.23 10.24 8.70 0.23 10.83 9.26 0.24 59 7.47 7.24 0.27 8.32 7.27 0.27 9.16 7.91 0.28 9.46 8.57 0.28 10.01 8.51 0.28 10.58 9.08 0.28 67 8.42 8.15 0.34 9.38 8.18 0.35 10.33 8.94 0.36 10.67 9.63 0.36 11.28 9.59 0.36 11.93 10.18 0.37 77 8.01 7.74 0.39 8.93 7.77 0.39 9.85 8.49 0.40 10.16 9.15 0.40 10.74 9.11 0.41 11.35 9.73 0.41 87 7.57 7.29 0.44 8.45 7.36 0.44 9.31 8.01 0.45 9.58 8.67 0.45 10.16 8.63 0.46 10.74 9.18 0.46 95 7.09 6.88 0.48 7.91 6.91 0.49 8.73 7.53 0.50 9.00 8.15 0.50 9.55 8.12 0.51 10.06 8.63 0.51
m3/h
°CDB 17.8 21.1 23.9 26.7 29.4 32.2
°CWB 12.2 15.6 17.2 19.4 21.7 22.8
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW
Indoor temperature
830
Indoor temperature
5-1. Cooling capacity 5. Capacity table
- 8 -
Page 13
Model: ASU12RLS3Y
¢
AFR CFM 489
WALL MOUNTED
ASU9-15RLS3Y
AFR
°FDB 64 70 75 80 85 90
°FWB 54 60 63 67 71 73
°FDB
15 10.34 9.52 0.28 11.53 9.58 0.28 12.72 10.47 0.29 13.11 11.30 0.29 13.87 11.21 0.29 14.67 11.96 0.30 23 10.26 9.44 0.33 11.44 9.47 0.33 12.62 10.34 0.35 13.01 11.19 0.34 13.77 11.12 0.34 14.56 11.85 0.35 32 10.18 9.35 0.36 11.36 9.39 0.36 12.52 10.27 0.38 12.91 11.09 0.37 13.67 11.03 0.38 14.45 11.78 0.39 41 10.10 9.30 0.39 11.27 9.37 0.39 12.42 10.21 0.41 12.81 11.02 0.40 13.57 10.98 0.40 14.34 11.68 0.41 50 10.03 9.21 0.40 11.18 9.25 0.40 12.32 10.10 0.42 12.71 10.92 0.41 13.47 10.86 0.41 14.23 11.60 0.42 59 9.95 9.16 0.41 11.10 9.23 0.41 12.22 10.05 0.44 12.61 10.85 0.42 13.37 10.81 0.43 14.12 11.50 0.44 67 11.22 10.32 0.54 12.51 10.40 0.55 13.77 11.34 0.55 14.22 12.25 0.56 15.07 12.18 0.56 15.92 12.98 0.57
Outdoor temperature
Outdoor temperature
77 10.67 9.82 0.62 11.90 9.85 0.63 13.13 10.76 0.64 13.53 11.63 0.64 14.32 11.56 0.64 15.14 12.32 0.65 87 10.09 9.27 0.69 11.25 9.31 0.70 12.41 10.18 0.71 12.78 10.98 0.71 13.57 10.94 0.72 14.32 11.67 0.73 95 9.48 8.72 0.76 10.53 8.76 0.77 11.63 9.56 0.79 12.00 10.32 0.79 12.72 10.29 0.80 13.43 10.94 0.81
104 8.01 7.78 0.71 8.93 7.82 0.72 9.82 8.51 0.73 10.13 9.20 0.74 10.74 9.16 0.74 11.35 9.78 0.75 115 7.36 7.20 0.71 8.22 7.23 0.72 9.07 7.89 0.74 9.34 8.54 0.74 9.89 8.51 0.74 10.47 9.05 0.75
°CDB
-10.0 3.03 2.79 0.28 3.38 2.81 0.28 3.73 3.07 0.29 3.84 3.31 0.29 4.07 3.29 0.29 4.30 3.50 0.30
-5.0 3.01 2.77 0.33 3.35 2.78 0.33 3.70 3.03 0.35 3.81 3.28 0.34 4.04 3.26 0.34 4.27 3.47 0.35
0.0 2.98 2.74 0.36 3.33 2.75 0.36 3.67 3.01 0.38 3.78 3.25 0.37 4.01 3.23 0.38 4.23 3.45 0.39
5.0 2.96 2.73 0.39 3.30 2.75 0.39 3.64 2.99 0.41 3.75 3.23 0.40 3.98 3.22 0.40 4.20 3.42 0.41
10.0 2.94 2.70 0.40 3.28 2.71 0.40 3.61 2.96 0.42 3.73 3.20 0.41 3.95 3.18 0.41 4.17 3.40 0.42
15.0 2.92 2.68 0.41 3.25 2.71 0.41 3.58 2.94 0.44 3.70 3.18 0.42 3.92 3.17 0.43 4.14 3.37 0.44
19.4 3.29 3.03 0.54 3.67 3.05 0.55 4.04 3.32 0.55 4.17 3.59 0.56 4.42 3.57 0.56 4.67 3.80 0.57
25.0 3.13 2.88 0.62 3.49 2.89 0.63 3.85 3.15 0.64 3.97 3.41 0.64 4.20 3.39 0.64 4.44 3.61 0.65
30.6 2.96 2.72 0.69 3.30 2.73 0.70 3.64 2.98 0.71 3.75 3.22 0.71 3.98 3.21 0.72 4.20 3.42 0.73
35.0 2.78 2.56 0.76 3.09 2.57 0.77 3.41 2.80 0.79 3.52 3.03 0.79 3.73 3.02 0.80 3.94 3.21 0.81
40.0 2.35 2.28 0.71 2.62 2.29 0.72 2.88 2.49 0.73 2.97 2.70 0.74 3.15 2.68 0.74 3.33 2.87 0.75
46.0 2.16 2.11 0.71 2.41 2.12 0.72 2.66 2.31 0.74 2.74 2.50 0.74 2.90 2.49 0.74 3.07 2.65 0.75
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW
m3/h
°CDB 17.8 21.1 23.9 26.7 29.4 32.2 °CWB 12.2 15.6 17.2 19.4 21.7 22.8
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW
Indoor temperature
830
Indoor temperature
WALL MOUNTED
ASU9-15RLS3Y
5-1. Cooling capacity 5. Capacity table
- 9 -
Page 14
Model: ASU15RLS3Y
¢
AFR CFM 547
WALL MOUNTED
ASU9-15RLS3Y
AFR
°FDB 64 70 75 80 85 90
°FWB 54 60 63 67 71 73
°FDB
15 12.72 9.80 0.36 14.18 10.92 0.36 15.63 12.04 0.38 16.10 12.40 0.37 17.04 13.13 0.37 18.02 13.88 0.38 23 12.53 9.62 0.39 13.95 10.72 0.39 15.38 11.82 0.41 15.85 12.18 0.40 16.78 12.90 0.40 17.75 13.63 0.42 32 12.33 9.49 0.40 13.73 10.57 0.41 15.14 11.65 0.43 15.60 12.01 0.42 16.52 12.72 0.42 17.47 13.45 0.43 41 12.13 9.34 0.41 13.51 10.41 0.41 14.89 11.47 0.43 15.35 11.82 0.42 16.26 12.52 0.42 17.19 13.24 0.44 50 11.93 9.18 0.42 13.29 10.23 0.42 14.65 11.27 0.45 15.10 11.62 0.43 16.00 12.31 0.44 16.91 13.01 0.45 59 11.73 9.01 0.45 13.07 10.04 0.45 14.41 11.07 0.48 14.85 11.41 0.46 15.74 12.10 0.46 16.64 12.78 0.48 67 13.48 11.10 0.72 15.01 11.17 0.74 16.55 12.15 0.75 17.06 13.14 0.75 18.08 13.07 0.76 19.11 13.95 0.76
Outdoor temperature
Outdoor temperature
77 12.86 10.57 0.82 14.33 10.64 0.83 15.80 11.59 0.84 16.27 12.50 0.84 17.23 12.47 0.85 18.22 13.28 0.86 87 12.18 10.00 0.91 13.58 10.07 0.92 14.98 10.99 0.94 15.42 11.87 0.95 16.34 11.84 0.95 17.30 12.61 0.96 95 11.46 9.40 1.01 12.76 9.48 1.02 14.06 10.32 1.03 14.50 11.17 1.04 15.35 11.10 1.05 16.24 11.84 1.06
104 10.06 8.28 0.99 11.22 8.31 1.01 12.35 9.09 1.02 12.73 9.79 1.02 13.51 9.76 1.03 14.26 10.39 1.05 115 9.18 7.54 0.97 10.20 7.57 0.99 11.26 8.28 1.01 11.60 8.91 1.01 12.32 8.88 1.02 13.00 9.48 1.03
°CDB
-10.0 3.73 2.87 0.36 4.15 3.20 0.36 4.58 3.53 0.38 4.72 3.63 0.37 5.00 3.85 0.37 5.28 4.07 0.38
-5.0 3.67 2.82 0.39 4.09 3.14 0.39 4.51 3.46 0.41 4.65 3.57 0.40 4.92 3.78 0.40 5.20 4.00 0.42
0.0 3.61 2.78 0.40 4.02 3.10 0.41 4.44 3.42 0.43 4.57 3.52 0.42 4.84 3.73 0.42 5.12 3.94 0.43
5.0 3.56 2.74 0.41 3.96 3.05 0.41 4.37 3.36 0.43 4.50 3.46 0.42 4.77 3.67 0.42 5.04 3.88 0.44
10.0 3.50 2.69 0.42 3.90 3.00 0.42 4.29 3.30 0.45 4.43 3.41 0.43 4.69 3.61 0.44 4.96 3.81 0.45
15.0 3.44 2.64 0.45 3.83 2.94 0.45 4.22 3.24 0.48 4.35 3.34 0.46 4.61 3.54 0.46 4.88 3.75 0.48
19.4 3.95 3.25 0.72 4.40 3.27 0.74 4.85 3.56 0.75 5.00 3.85 0.75 5.30 3.83 0.76 5.60 4.09 0.76
25.0 3.77 3.10 0.82 4.20 3.12 0.83 4.63 3.40 0.84 4.77 3.66 0.84 5.05 3.65 0.85 5.34 3.89 0.86
30.6 3.57 2.93 0.91 3.98 2.95 0.92 4.39 3.22 0.94 4.52 3.48 0.95 4.79 3.47 0.95 5.07 3.70 0.96
35.0 3.36 2.76 1.01 3.74 2.78 1.02 4.12 3.02 1.03 4.25 3.27 1.04 4.50 3.25 1.05 4.76 3.47 1.06
40.0 2.95 2.43 0.99 3.29 2.44 1.01 3.62 2.66 1.02 3.73 2.87 1.02 3.96 2.86 1.03 4.18 3.05 1.05
46.0 2.69 2.21 0.97 2.99 2.22 0.99 3.30 2.43 1.01 3.40 2.61 1.01 3.61 2.60 1.02 3.81 2.78 1.03
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW kBtu kW
m3/h
°CDB 17.8 21.1 23.9 26.7 29.4 32.2 °CWB 12.2 15.6 17.2 19.4 21.7 22.8
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW
Indoor temperature
930
Indoor temperature
WALL MOUNTED
ASU9-15RLS3Y
5-1. Cooling capacity 5. Capacity table
- 10 -
Page 15

5-2. Heating capacity

¢
WALL MOUNTED
ASU9-15RLS3Y
AFR CFM 489
Model: ASU9RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
°FDB 60 65 70 75
°FDB °FWB
-15 -17 11.6 2.15 11.4 2.19 11.1 2.23 10.5 2.31
-5 -7 14.7 2.16 14.3 2.20 14.0 2.24 13.3 2.32
5 3 16.1 2.17 15.7 2.21 15.4 2.25 14.6 2.34 14 12 16.8 2.13 16.4 2.17 16.0 2.22 15.2 2.30 23 19 18.3 2.10 17.9 2.14 17.5 2.18 16.6 2.26 32 28 18.8 2.06 18.4 2.10 17.9 2.14 17.0 2.22 41 37 21.3 1.88 20.8 1.92 20.3 1.95 19.3 2.03
Outdoor temperature
47 43 23.1 1.85 22.6 1.89 22.0 1.93 20.9 2.01 50 47 25.5 1.84 24.9 1.88 24.3 1.91 23.1 1.99 59 50 26.5 1.63 25.8 1.67 25.2 1.70 23.9 1.77
AFR
°CDB °CWB
-26.1 -27.0 3.41 2.15 3.33 2.19 3.25 2.23 3.09 2.31
-20.6 -21.7 4.31 2.16 4.20 2.20 4.10 2.24 3.90 2.32
-15.0 -16.1 4.73 2.17 4.61 2.21 4.50 2.25 4.28 2.34
-10.0 -11.1 4.91 2.13 4.80 2.17 4.68 2.22 4.45 2.30
-5.0 -7.2 5.38 2.10 5.25 2.14 5.12 2.18 4.86 2.26
0.0 -2.2 5.52 2.06 5.39 2.10 5.26 2.14 5.00 2.22
5.0 2.8 6.25 1.88 6.10 1.92 5.95 1.95 5.65 2.03
Outdoor temperature
8.3 6.1 6.77 1.85 6.61 1.89 6.45 1.93 6.13 2.01
10.0 8.3 7.48 1.84 7.30 1.88 7.13 1.91 6.77 1.99
15.0 10.0 7.75 1.63 7.57 1.67 7.38 1.70 7.02 1.77
m3/h
°CDB 15.6 18.3 21.1 23.9
TC IP TC IP TC IP TC IP
kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW
TC IP TC IP TC IP TC IP
kW kW kW kW
Indoor temperature
830
Indoor temperature
Model: ASU12RLS3Y
¢
AFR CFM 489
°FDB 60 65 70 75
°FDB °FWB
-15 -17 12.4 2.15 12.1 2.19 11.8 2.23 11.2 2.31
-5 -7 15.8 2.16 15.4 2.20 15.0 2.24 14.3 2.32
5 3 17.4 2.17 17.0 2.21 16.6 2.25 15.8 2.34 14 12 18.3 2.13 17.8 2.18 17.4 2.22 16.5 2.30 23 19 20.0 2.10 19.5 2.14 19.0 2.18 18.1 2.26 32 28 20.6 2.07 20.1 2.11 19.6 2.15 18.6 2.23 41 37 22.5 1.88 21.9 1.92 21.4 1.96 20.3 2.04
Outdoor temperature
47 43 23.2 1.86 22.7 1.90 22.1 1.94 21.0 2.02 50 47 25.6 1.85 25.0 1.89 24.4 1.93 23.2 2.00 59 50 26.6 1.64 25.9 1.68 25.3 1.71 24.0 1.78
AFR
°CDB °CWB
-26.1 -27.0 3.62 2.15 3.54 2.19 3.45 2.23 3.28 2.31
-20.6 -21.7 4.63 2.16 4.52 2.20 4.41 2.24 4.19 2.32
-15.0 -16.1 5.11 2.17 4.99 2.21 4.86 2.25 4.62 2.34
-10.0 -11.1 5.36 2.13 5.23 2.18 5.10 2.22 4.85 2.30
-5.0 -7.2 5.86 2.10 5.72 2.14 5.58 2.18 5.30 2.26
0.0 -2.2 6.03 2.07 5.88 2.11 5.74 2.15 5.45 2.23
5.0 2.8 6.58 1.88 6.43 1.92 6.27 1.96 5.96 2.04
Outdoor temperature
8.3 6.1 6.80 1.86 6.64 1.90 6.48 1.94 6.15 2.02
10.0 8.3 7.52 1.85 7.34 1.89 7.16 1.93 6.80 2.00
15.0 10.0 7.79 1.64 7.60 1.68 7.42 1.71 7.05 1.78
m3/h
°CDB 15.6 18.3 21.1 23.9
TC IP TC IP TC IP TC IP
kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW
TC IP TC IP TC IP TC IP
kW kW kW kW
Indoor temperature
Indoor temperature
830
5-2. Heating capacity 5. Capacity table
- 11 -
Page 16
Model: ASU15RLS3Y
¢
AFR CFM 547
WALL MOUNTED
ASU9-15RLS3Y
AFR
°FDB 60 65 70 75
°FDB °FWB
-15 -17 17.1 2.77 16.7 2.82 16.3 2.88 15.5 2.98
-5 -7 19.6 2.78 19.1 2.84 18.6 2.89 17.7 3.00
5 3 22.0 2.79 21.5 2.85 21.0 2.90 19.9 3.01 14 12 22.7 2.68 22.2 2.73 21.6 2.78 20.5 2.89 23 19 23.3 2.56 22.8 2.61 22.2 2.66 21.1 2.76 32 28 24.0 2.45 23.4 2.49 22.9 2.54 21.7 2.64 41 37 24.7 2.18 24.1 2.22 23.5 2.27 22.3 2.36
Outdoor temperature
47 43 25.1 2.10 24.5 2.15 23.9 2.19 22.7 2.28 50 47 26.1 1.97 25.5 2.01 24.9 2.05 23.6 2.13 59 50 27.2 1.75 26.5 1.79 25.9 1.82 24.6 1.89
m3/h
°CDB 15.6 18.3 21.1 23.9
°CDB °CWB
-26.1 -27.0 5.01 2.77 4.89 2.82 4.77 2.88 4.53 2.98
-20.6 -21.7 5.73 2.78 5.60 2.84 5.46 2.89 5.19 3.00
-15.0 -16.1 6.46 2.79 6.31 2.85 6.15 2.90 5.84 3.01
-10.0 -11.1 6.65 2.68 6.49 2.73 6.33 2.78 6.02 2.89
-5.0 -7.2 6.84 2.56 6.68 2.61 6.52 2.66 6.19 2.76
0.0 -2.2 7.04 2.45 6.87 2.49 6.70 2.54 6.37 2.64
5.0 2.8 7.23 2.18 7.06 2.22 6.88 2.27 6.54 2.36
Outdoor temperature
8.3 6.1 7.35 2.10 7.18 2.15 7.00 2.19 6.65 2.28
10.0 8.3 7.66 1.97 7.47 2.01 7.29 2.05 6.93 2.13
15.0 10.0 7.97 1.75 7.78 1.79 7.59 1.82 7.21 1.89
TC IP TC IP TC IP TC IP
kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW
TC IP TC IP TC IP TC IP
kW kW kW kW
Indoor temperature
930
Indoor temperature
WALL MOUNTED
ASU9-15RLS3Y
5-2. Heating capacity 5. Capacity table
- 12 -
Page 17

6. Fan performance

2
1
0
1
2
Unit: ft/s (m/s)(m)
(m)
01234567
8
7
3
0
3
7
(ft)
(ft)
0371013162023
26
9
29
7 (2.0)
3 (1.0)
2 (0.5)
10
7
3
0
3
7
10
(ft)
(ft)
037101316202326
3
2
1
0
1
2
3
Unit: ft/s (m/s)
(m)
(m)
012345678
9
29
7 (2.0)
7 (2.0)
3 (1.0)
3 (1.0)
2 (0.5)
2 (0.5)
7 (2.0)
2 (0.5)
3 (1.0)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
037101316202326
9
29
7 (2.0)
2 (0.5)
3 (1.0)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 101316202326
9
29
WALL MOUNTED

6-1. Air velocity distributions

ASU9-15RLS3Y
¢
Measuring conditions
Models: ASU9RLS3Y and ASU12RLS3Y
Fan speed Operation mode
HIGH FAN
Top view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Center
WALL MOUNTED
ASU9-15RLS3Y
Top view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down
Horizontal airflow direction louver: Center
6-1. Air velocity distributions 6. Fan performance
- 13 -
Page 18
Model: ASU15RLS3Y
7 (2.0)
3 (1.0)
2 (0.5)
2
1
0
1
2
Unit: ft/s (m/s)(m)
(m)
01234567
8
7
3
0
3
7
(ft)
(ft)
0 3 7 10 13 16 20 23
26
9
29
10
7
3
0
3
7
10
(ft)
(ft)
0 3 7 10 13 16 20 23
26
3 (1.0)
3 (1.0)
7 (2.0)
2 (0.5)
2 (0.5)
7 (2.0)
3
2
1
0
1
2
3
Unit: ft/s (m/s)
(m)
(m)
01234567
8
9
29
3 (1.0)
7 (2.0)
2 (0.5)
2 (0.5)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
7 (2.0)
3 (1.0)
2 (0.5)
3
2
1
0
Unit: ft/s (m/s)
(m)
(m)
012345678
10
7
3
0
(ft)
(ft)
0 3 7 10 13 16 20 23 26
9
29
¢
Measuring conditions
WALL MOUNTED
ASU9-15RLS3Y
Top view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Center
Fan speed Operation mode
HIGH FAN
WALL MOUNTED
ASU9-15RLS3Y
Top view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Left & Right
Side view Vertical airflow direction louver: Up
Horizontal airflow direction louver: Center
Side view Vertical airflow direction louver: Down
Horizontal airflow direction louver: Center
6-1. Air velocity distributions 6. Fan performance
- 14 -
Page 19

6-2. Airflow

¢
WALL MOUNTED
ASU9-15RLS3Y
Cooling
Models: ASU9RLS3Y and ASU12RLS3Y
Fan speed Airflow
m3/h
HIGH
MED
LOW
QUIET
l/s 231
CFM 489
m3/h
l/s 189
CFM 400
m3/h
l/s 161
CFM 341
m3/h
l/s 106
CFM 224
830
680
580
380
WALL MOUNTED
ASU9-15RLS3Y
Heating
Fan speed Airflow
HIGH
MED
LOW
QUIET
m3/h
l/s 231
CFM 489
m3/h
l/s 189
CFM 400
m3/h
l/s 161
CFM 341
m3/h
l/s 106
CFM 224
830
680
580
380
6-2. Airflow 6. Fan performance
- 15 -
Page 20
¢
Cooling
WALL MOUNTED
ASU9-15RLS3Y
Heating
Model: ASU15RLS3Y
Fan speed Airflow
HIGH
MED
LOW
QUIET
m3/h
l/s 258
CFM 547
m3/h
l/s 217
CFM 459
m3/h
l/s 175
CFM 371
m3/h
l/s 122
CFM 259
930
780
630
440
WALL MOUNTED
ASU9-15RLS3Y
Fan speed Airflow
m3/h
HIGH
MED
LOW
QUIET
l/s 258
CFM 547
m3/h
l/s 217
CFM 459
m3/h
l/s 175
CFM 371
m3/h
l/s 139
CFM 294
930
780
630
500
6-2. Airflow 6. Fan performance
- 16 -
Page 21

7. Operation noise (sound pressure)

NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63
125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
WALL MOUNTED

7-1. Noise level curve

ASU9-15RLS3Y
¢
Cooling
Model: ASU9RLS3Y
Heating
WALL MOUNTED
ASU9-15RLS3Y
Model: ASU12RLS3Y
¢
Cooling
7-1. Noise level curve 7. Operation noise (sound pressure)
Heating
- 17 -
Page 22
Model: ASU15RLS3Y
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
㻴㼕㼓㼔
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
¢
Cooling
WALL MOUNTED
ASU9-15RLS3Y
Heating
WALL MOUNTED
ASU9-15RLS3Y
7-1. Noise level curve 7. Operation noise (sound pressure)
- 18 -
Page 23

7-2. Sound level check point

Microphone
Microphone
39-3/8 in (1 m)
31-1/2 in (0.8 m)
WALL MOUNTED
ASU9-15RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
7-2. Sound level check point 7. Operation noise (sound pressure)
- 19 -
Page 24

8. Safety devices

WALL MOUNTED
ASU9-15RLS3Y
Circuit protection Current fuse (PCB*) 250 V, 3.15 A
Fan motor protection
*PCB: Printed Circuit Board
Type of protection Protection form
Thermal protector program
Activate
Reset
Model
ASU9RLS3Y ASU12RLS3Y ASU15RLS3Y
302±27 °F (150±15 °C)
Fan motor speed down
248±27 °F (120±15 °C)
Fan motor speed recover
WALL MOUNTED
ASU9-15RLS3Y
- 20 -
8. Safety devices
Page 25

9. External input and output

With using external input and output functions, this product can be operated inter-connectedly with an external device.
WALL MOUNTED
ASU9-15RLS3Y

9-1. External input

With using external input function, some functions on this product can be controlled from an external device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
• The wire connection should be separate from the power cable line.
¢
The air conditioner can be remotely operated by means of the following on-site work. Unit operation is started at the following contents by adding the contact input of a commercial on/off
switch to a connector on the external control PCB and turning it on.
Connector Input Output Remarks
CNA01 Control input — CNB01 Operation status output CNB02 Error status output
See external input/output
settings for details.
Control input (Operation/Stop or Forced stop)
WALL MOUNTED
ASU9-15RLS3Y
Unit operation Initial setting after power is on Starting mode other than initial setting
Operation mode Auto changeover Mode at previous operation Set temperature 75 °F (24 °C) Temperature at previous operation
Airflow mode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing: off) Air direction at previous operation
9-1. External input 9. External input and output
- 21 -
Page 26
Circuit diagram example
Signal
Locally purchased
Indoor unit
control PCB
Communication kit
Optional parts
Connector
1
3
33 ft (10 m)*
Connected unit
Example: Switch
Operation
Stop
On
Off
Input signal
Indoor unit
Remote controller
On On On
Input signal
Indoor unit
Command
Remote control operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
On OnOff
WALL MOUNTED
ASU9-15RLS3Y
– When function setting is “Operation/Stop” mode
– When function setting is “Forced stop” mode
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Use non-polar relays and switches.
WALL MOUNTED
ASU9-15RLS3Y
– When function setting is "Operation/Stop" mode 2
9-1. External input 9. External input and output
NOTE:
When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
- 22 -
Page 27
Optional part
WALL MOUNTED
ASU9-15RLS3Y
Part name Model name Exterior
External input wire
External connect kit UTY-XWZXZ5
Communication kit UTY-TWBXF1
* For operating the external function, the wall mounted type requires the communication kit in addi­tion to the wire (UTY-XWZXZ5).
WALL MOUNTED
ASU9-15RLS3Y
9-1. External input 9. External input and output
- 23 -
Page 28

9-2. External output

Locally purchasedOptional parts
Example: Display
Indoor unit
control PCB
Communication kit Connected unit
Example: Relay unit
1
2
Signal
Relay power supply
V
Connector
33 ft (10 m)*
DC 24 V
On
Off
Operation
Stop
Indoor unit
Output signal
With using external output function, operating status of this product can be transmitted to the exter­nal device, and also, this product can be inter-connected with the external device.
WALL MOUNTED
ASU9-15RLS3Y
¢
Circuit diagram example
Operation status output
WALL MOUNTED
ASU9-15RLS3Y
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ5
Communication kit UTY-TWBXF1
External output wire
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
9-2. External output 9. External input and output
- 24 -
Page 29
¢
Locally purchasedOptional parts
Example: Display
Indoor unit
control PCB
Communication kit Connected unit
Example: Relay unit
1
2
Signal
Relay power supply
V
Connector
33 ft (10 m)*
DC 24 V
On
Off
Error
Normal
Error status
Output signal
Circuit diagram example
WALL MOUNTED
ASU9-15RLS3Y
Error status output
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
WALL MOUNTED
ASU9-15RLS3Y
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ5
Communication kit UTY-TWBXF1
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
External output wire
9-2. External output 9. External input and output
- 25 -
Page 30

10. Remote controller

Signal
transmitter
MIN. HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
OUTDOOR UNIT
LOW NOISE button
SWING button
SET button
WEEKLY button
ON/OFF button
SLEEP button
MODE button
SENSOR button
FAN button
TEST RUN button
RESET button
CLOCK ADJUST button
ECONOMY button
Mode indicator
ENERGY SAVING mode
indicator
LOW NOISE mode
indicator
Turns on when the SENSOR button is operated.
Clock and Timer indicator
SEND indicator
Temperature indicator
Fan speed indicator
Swing indicator
Transmit indicator
WALL MOUNTED

10-1. Wireless remote controller

ASU9-15RLS3Y
¢
Overview
WALL MOUNTED
ASU9-15RLS3Y
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current op­eration.
10-1. Wireless remote controller 10. Remote controller
- 26 -
Page 31
¢
Top view
Front view Side view
8-1/16 (205)
11/16 (17)
2-3/8
(61)
1-15/16 (48.5)
3/16 (5.5)
1-1/16
(26.2)
2-3/4 (69.3)
1/4 (6.5)
Front View Side View
Bottom View
Ø 1/8 (Ø3.5) (Hole)
5-7/8 (150)
4-3/16 (106.8)
Hole
(1/83.5)
2-R
Controller
WALL MOUNTED
ASU9-15RLS3Y
Specifications
Unit: in (mm)
WALL MOUNTED
ASU9-15RLS3Y
Size (H × W × D) in (mm) 8-1/16 × 2-3/8 × 11/16 (205 × 61 × 17) Weight oz (g) 4.3 (122) (without batteries)
Holder
Unit: in (mm)
Weight oz (g) 1 (27)
10-1. Wireless remote controller 10. Remote controller
- 27 -
Size (H × W × D) in (mm) 5-7/8 × 2-3/4 × 1-1/16 (150 × 69.3 × 26.2)
Page 32

11. Function settings

Function number
Setting value
To adjust the functions of this product according to the installation environment, various types of function settings are available.
WALL MOUNTED
ASU9-15RLS3Y
NOTE:

11-1. Function settings by using remote controller

Some function settings can be changed on the remote controller. After confirming the setting proce­dure and the content of each function setting, select appropriate functions for your installation envi­ronment.
¢
The function number and the associated setting value are displayed on the LCD of the remote con­troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Cover for the electrical enclosure on the outdoor unit is in place.
• There is no wiring mistake.
• Piping air tight test and vacuuming have been performed firmly.
• All the necessary wiring work for outdoor unit has been finished.
Incorrect settings can cause a product malfunction.
Setting procedure by using wireless remote controller
WALL MOUNTED
ASU9-15RLS3Y
After reconfirming the items listed above, connect the power supply of the indoor unit.
NOTES:
• Settings will not be changed if invalid numbers or setting values are selected.
• When optional wired remote controller is used, refer to the installation manual enclosed with the remote controller.
Entering function setting mode:
While pressing the POWERFUL button and TEMP. ( ) button simulta­neously, press the RESET button to enter the function setting mode.
Selecting the function number and setting value:
1. Press the TEMP. ( ) ( ) buttons to select the function number. To switch between the left and right digits, press the MIN. HEAT button.
2. Press the POWERFUL button to proceed to value setting. To return the function number selection, press the POWERFUL button again.
3. Press the TEMP. ( ) ( ) buttons to select the setting value. To switch between the left and right digits, press the MIN. HEAT button.
4. Press the MODE button once to send the function setting informa­tion. Confirm that you hear the beep sound.
5. Press the START/STOP button to fix the function setting. Confirm that you hear the beep sound.
6. Press the RESET button to end the function setting mode.
7. After completing the function setting, be sure to disconnect the pow­er supply and then reconnect it.
CAUTION
After disconnecting the power supply, wait 30 seconds or more before reconnecting it. The function setting will not become active unless the power supply is disconnected and then reconnected.
11-1. Function settings by using remote controller 11. Function settings
- 28 -
Page 33
¢
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
WALL MOUNTED
ASU9-15RLS3Y
NOTE:
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Contents of function setting
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no. Functions
1) 11 Filter sign
2) 30/31 Room temperature control for indoor unit sensor
3) 35/36 Room temperature control for wired remote controller sensor
4) 40 Auto restart
5) 42 Room temperature sensor switching
6) 44 Remote controller custom code
7) 46 External input control
8) 48 Room temperature sensor switching (Aux.)
9) 49 Indoor unit fan control for energy saving for cooling
10) 95 Heat insulation condition (building insulation)
WALL MOUNTED
ASU9-15RLS3Y
Function number Setting value Setting description Factory setting
00 Standard (400 hours)
11
01 Long interval (1,000 hours) 02 Short interval (200 hours) 03 No indication
11-1. Function settings by using remote controller 11. Function settings
- 29 -
Page 34
2) Room temperature control for indoor unit sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-
WALL MOUNTED
ASU9-15RLS3Y
quired. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value). *When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No cor-
rection 0.0 °F (0.0 °C)" (01).
WALL MOUNTED
ASU9-15RLS3Y
Function number Setting value Setting description
00 Standard setting* ♦ 01 No correction 0.0 °F (0.0 °C) 02 -1 °F (-0.5 °C) 03 -2 °F (-1.0 °C) 04 -3 °F (-1.5 °C) 05 -4 °F (-2.0 °C) 06 -5 °F (-2.5 °C) 07 -6 °F (-3.0 °C)
30
(For cooling)
31
(For heating)
08 -7 °F (-3.5 °C) 09 -8 °F (-4.0 °C) 10 +1 °F (+0.5 °C) 11 +2 °F (+1.0 °C) 12 +3 °F (+1.5 °C) 13 +4 °F (+2.0 °C) 14 +5 °F (+2.5 °C) 15 +6 °F (+3.0 °C) 16 +7 °F (+3.5 °C) 17 +8 °F (+4.0 °C)
Factory
setting
More cooling
Less heating
Less cooling
More heating
11-1. Function settings by using remote controller 11. Function settings
- 30 -
Page 35
3) Room temperature control for wired remote controller sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the wire remote temperature sensor may be
WALL MOUNTED
ASU9-15RLS3Y
required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
WALL MOUNTED
ASU9-15RLS3Y
Function number Setting value Setting description
00 Standard setting* ♦ 01 No correction 0.0 °F (0.0 °C) 02 -1 °F (-0.5 °C) 03 -2 °F (-1.0 °C) 04 -3 °F (-1.5 °C) 05 -4 °F (-2.0 °C) 06 -5 °F (-2.5 °C) 07 -6 °F (-3.0 °C)
35
(For cooling)
36
(For heating)
08 -7 °F (-3.5 °C) 09 -8 °F (-4.0 °C) 10 +1 °F (+0.5 °C) 11 +2 °F (+1.0 °C) 12 +3 °F (+1.5 °C) 13 +4 °F (+2.0 °C) 14 +5 °F (+2.5 °C) 15 +6 °F (+3.0 °C) 16 +7 °F (+3.5 °C) 17 +8 °F (+4.0 °C)
Factory
setting
More cooling
Less heating
Less cooling
More heating
4) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
40
00 Enable ♦ 01 Disable
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter­nal device.
5) Room temperature sensor switching
(Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number Setting value Setting description Factory setting
42
00 Indoor unit ♦ 01 Both
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
11-1. Function settings by using remote controller 11. Function settings
- 31 -
Page 36
6) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
WALL MOUNTED
ASU9-15RLS3Y
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
8) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired re­mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01). When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting 30 and 31 too.
Function number Setting value Setting description Factory setting
00 A
44
Function number Setting value Setting description Factory setting
46
01 B 02 C 03 D
00 Operation/Stop mode 1 ♦ 01 (Setting prohibited) 02 Forced stop mode 03 Operation/Stop mode 2
WALL MOUNTED
ASU9-15RLS3Y
Function number Setting value Setting description Factory setting
48
00 Both ♦ 01 Wired remote controller
9) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
00 Disable
49
01 Enable 02 Remote controller
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller. 01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed. 02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially invalidated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for ener­gy saving function or connecting a network converter. To confirm if the remote controller has this setting, refer to the operating manual of each remote controller.
11-1. Function settings by using remote controller 11. Function settings
- 32 -
Page 37
10) Heat insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment. "Standard insulation" (00) allows system to rapidly respond to the cooling or heating load changes. "High insulation" (01) is when the heat insulation structure of the building is high and does not re-
WALL MOUNTED
ASU9-15RLS3Y
quire system to rapidly respond to cooling or heating load changes. When "High insulation" (01) is selected:
• Overheating (overcooling) is prevented at the start-up.
• All room-temperature control settings (Function 30, 31, 35, and 36) will reset to "No correction
NOTE: When changing Function 95, perform this setting before other room-temperature control
0.0 °F (0.0 °C)".
Function number Setting value Setting description Factory setting
95
00 Standard insulation ♦ 01 High insulation
settings (Function 30, 31, 35, and 36). If Function 95 is not set first, room-temperature con­trol settings (Function 30, 31, 35, and 36) will be reset and you must re-do them again.
WALL MOUNTED
ASU9-15RLS3Y
11-1. Function settings by using remote controller 11. Function settings
- 33 -
Page 38

11-2. Custom code setting for wireless remote controller

To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required.
WALL MOUNTED
ASU9-15RLS3Y
NOTE:
When 2 or more air conditioners are installed in a room, and the remote controller is operating an air conditioner other than the one you wish to set, change the custom code of the remote controller to operate only the air conditioner you wish to set. (4 selections possible.)
Confirm the setting of the remote controller custom code and the function setting. If these do not match, the remote controller cannot be used to operate for the air conditioner.
Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
1. Press the START/STOP button until only the clock is displayed on the remote controller display.
2. Press the MODE button for at least 5 seconds to display the current custom code. (Initially set to
.)
3. Press the TEMP. ( ) ( ) buttons to change the custom code be­tween → → → . Match the code on the display to the air condi­tioner custom code. (Initially set to .)
WALL MOUNTED
ASU9-15RLS3Y
4. Press the MODE button again to return to the clock display. The custom code will be changed.
NOTES:
• If no button is pressed within 30 seconds after the custom code is displayed, the system returns to the original clock indicator. In this case, start again from step 1.
The air conditioner custom code is set to prior to shipment. To change the custom code, con-
• tact your retailer.
If you do not know the assigned code for the air conditioner, try each of the custom code (
→ → ) until you find the code which operates the air conditioner.
11-2. Custom code setting for wireless remote controller 11. Function settings
- 34 -
Page 39

11-3. Switching the temperature unit of remote controller

Displayed temperature unit on the remote controller LCD can be switched between °F (Fahrenheit) and °C (Celsius).
WALL MOUNTED
ASU9-15RLS3Y
To change temperature unit, do as follows:
1. Press the TEMP. (Up) button ( ) for at least 5 seconds to display the current temperature unit.
2. Press the TEMP. ( ) ( ) buttons to switch the temperature unit between °F and °C.
3. With either of pressing the START/STOP button or no additional button operation for 30 sec-
(Factory setting: °F)
onds in step 2., the temperature unit currently selected will be set.
WALL MOUNTED
ASU9-15RLS3Y
11-3. Switching the temperature unit of remote controller 11. Function settings
- 35 -
Page 40

12. Accessories

WALL MOUNTED
ASU9-15RLS3Y
Operating manual 1
Setting manual (for Wireless LAN control)
Installation manual 1 Tapping screw (large) 1
Wall hook bracket 1 Tapping screw (small) 5
Remote controller 1 Air cleaning filter 2
Part name Exterior Q’ty Part name Exterior Q’ty
Wireless LAN label (Attached to the indoor unit beside the wireless
1
LAN indicator)
1 Cloth tape 1
WALL MOUNTED
ASU9-15RLS3Y
Battery 2 Filter holder 2
Remote controller holder
Seal A
1
(for 15 model)
1
- 36 -
12. Accessories
Page 41

13. Optional parts

Mode
Menu
Cool
Monitor
Set temp.
Fan
High
°
F
80
Mo
10:00
AM
Icon check:
WALL MOUNTED

13-1. Controllers

ASU9-15RLS3Y
Exterior Part name Model name Summary
Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key.
Wired remote
controller
UTY-RVNUM
Wire type: Polar 3-wire Optional communication kit is
necessary for installation.
Room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor.
Wired remote
controller
UTY-RNNUM
Wire type: Polar 3-wire Optional communication kit is
necessary for installation.
Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation
Simple remote
controller
UTY-RSNUM
mode. Wire type: Polar 3-wire
Optional communication kit is necessary for installation.
WALL MOUNTED
ASU9-15RLS3Y
NOTES:
• Available functions may differ by the remote controller. For details, refer to the operation manu­al.
• In this product, group controlling system of the wired remote controller is prohibited.

13-2. Others

Exterior Part name Model name Summary
Required when external device is
External
connect kit
Communication
kit
UTY-XWZXZ5
UTY-TWBXF1
connected. Optional communication kit is
necessary for installation.
Use to connect with optional devices and air conditioner PCB.
13-1. Controllers 13. Optional parts
- 37 -
Page 42
WALL MOUNTED
ASU9-15RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
13-2. Others 13. Optional parts
- 38 -
Page 43

Part 2. OUTDOOR UNIT

SINGLE TYPE:
AOU9RLS3H AOU12RLS3H AOU15RLS3H
Page 44

1. Specifications

Type Inverter heat pump
Model name AOU9RLS3H AOU12RLS3H AOU15RLS3H
Power supply 208/230 V ~ 60 Hz Available voltage range 188—253 V Starting current A 3.3 4.7 5.2
Fan
Sound pressure level *1
OUTDOOR UNIT
AOU9-15RLS3H
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Operation range
Drain hose
NOTES:
• Specifications are based on the following conditions: – Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB). – Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB). – Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level – Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Airflow rate
Type × Q'ty Propeller fan × 1 Motor output W 49
Type × Q'ty Rotary × 1 Motor output W 850 1,000
Net
Gross
Net Gross 95 (43)
Size
Method Flare Pre-charge length Max. length 66 (20) Max. height difference 49 (15)
Cooling Heating 1,082 (1,840)
Cooling Heating 47 50 Dimensions (H × W × D) Fin pitch FPI 20 Rows × Stages 2 × 28 Pipe type Copper
Fin type
Type R410A
Charge
Type FREOL (ɑ68SZ) Amount Material Steel sheet
Color
Liquid Gas Ø 3/8 (Ø 9.52) Ø 1/2 (Ø 12.7)
Cooling Heating -15 to 75 (-26 to 24) Material LDPE
Size in (mm)
CFM (m3/h)
dB (A)
in 23-1/8 × 34-11/16 × 1-7/16
mm 588 × 881 × 36.4
Type (Material) Corrugate (Aluminum) Surface treatment Corrosion resistance (Blue fin)
lb oz 2 lb 14 oz 3 lb 1 oz
g 1,300 1,400
in3 (cm3)
in 24-1/2 × 31-1/8 × 11-7/16
mm 620 × 790 × 290
in 28-1/16 × 37-3/16 × 15-9/16
mm 713 × 945 × 395
lb (kg)
in (mm)
ft (m)
°F (°C)
42 43 49
989 (1,680) 1,206 (2,050)
12.5 (205)
Beige
Approximate color of Munsell 10YR 7.5/1.0
86 (39) 88 (40)
Ø 1/4 (Ø 6.35)
49 (15)
14 to 115 (-10 to 46)
Ø 9/16 (Ø 13.8) [I. D.]
Ø5/8 to Ø11/16 (Ø 15.8 to Ø 16.7) [O. D.]
OUTDOOR UNIT
AOU9-15RLS3H
- 40 -
1. Specifications
Page 45

2. Dimensions

Unit: in (mm)
Top view
Front view
Bottom view
Side view
31-1/8 (790)
24-7/16 (620)
13/16 (20)
3/8 (9)
3/4 (19) 2-5/8 (67)
11-5/16 (288)
11/16 (18) 7/8 (23)
13-7/8 (352)
4-5/16
(110)
8-1/4 (209)
6-7/8 (175)
12-5/8 (320)
4-ø7/16 (11.3) hole
21-1/4 (540)
Airflow
ø13/16 (20) hole
1 (25)
2-3/16
(55)
3/8(10)
hole
1(25)
3/8 (10)
3/8 (10)
hole
4 (102)

2-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H

OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
2-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H 2. Dimensions
- 41 -
Page 46

3. Installation space

4 (100) or more
10 (250) or more
4 (100) or more
4 (100) or more
24 (600) or more
24 (600) or more
4 (100) or more
4 (100) or more
Max. 7 (200)
24 (600) or more
24 (600) or more
4 (100) or more
10 (250) or more
4 (100) or more
Max. 7 (200)

3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H

¢
Provide sufficient installation space for product safety.
Single outdoor unit installation
OUTDOOR UNIT
AOU9-15RLS3H
Space requirement
When the upper space is open:
When there are obstacles at the rear only. When there are obstacles at the rear and
sides.
Unit: in (mm)
OUTDOOR UNIT
AOU9-15RLS3H
When there are obstacles at the front only. When there are obstacles at the front and
rear.
When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H 3. Installation space
- 42 -
Page 47
Multiple outdoor unit installation
8 (200) or more
40 (1,000) or more
8 (200) or more
40 (1,000) or more
60 (1,500) or more
8 (200) or more
Max. 11 (300)
OUTDOOR UNIT
AOU9-15RLS3H
When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only. When there are obstacles at the front only.
When there are obstacles at the front and rear.
OUTDOOR UNIT
AOU9-15RLS3H
When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H 3. Installation space
- 43 -
Page 48
Outdoor unit installation in multi-row
4 (100) or more
8 (200) or more
20 (500) or more
40 (1,000) or more
8 (200) or more
16 (400) or more
40 (1,000) or more
80 (2,000) or more
8 (200) or more
OUTDOOR UNIT
AOU9-15RLS3H
Single parallel unit arrangement Multiple parallel unit arrangement
Unit: in (mm)
OUTDOOR UNIT
AOU9-15RLS3H
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no ob­stacle.
• Height above the floor level should be 2 in (50 mm) or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 32 °F (0 °C) or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H 3. Installation space
- 44 -
Page 49

4. Refrigerant circuit

2-way
valve
Strainer
Strainer
3-way
valve
MufflerMuffler
Acccumlator
4-way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Compressor
Cooling
Heating
Th
D
Th
R
Th
PI
Th
HO
Th
O
Th
R
Th
PI
Th
D
Th
O
Th
HO
:Thermistor (Room temp.)
:Thermistor (Pipe temp.)
:Thermistor (Discharge temp.)
:Thermistor (Outdoor temp.)
:Thermistor (Heat exchanger out temp.)

4-1. Models: AOU9RLS3H and AOU12RLS3H

OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
4-1. Models: AOU9RLS3H and AOU12RLS3H 4. Refrigerant circuit
- 45 -
Page 50

4-2. Model: AOU15RLS3H

Th
R
Th
PI
Th
R
Th
PI
Th
D
Th
D
Th
O
Th
HO
: Thermistor (Room temp.)
: Thermistor (Pipe temp.)
: Thermistor (Discharge temp.)
: Thermistor (Outdoor temp.)
: Thermistor (Heat exchanger out temp.)
Th
O
Th
HO
Compressor
Muffler
Muffler
Heat exchanger
(INDOOR)
Heat exchanger
(OUTDOOR)
3-Way
valve
2-Way
valve
Cooling
Heating
Receiver
Strainer
Strainer
Expansion valve
OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
4-2. Model: AOU15RLS3H 4. Refrigerant circuit
- 46 -
Page 51

5. Wiring diagrams

5-1. Models: AOU9RLS3H and AOU12RLS3H

OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
5-1. Models: AOU9RLS3H and AOU12RLS3H 5. Wiring diagrams
- 47 -
Page 52

5-2. Model: AOU15RLS3H

OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
5-2. Model: AOU15RLS3H 5. Wiring diagrams
- 48 -
Page 53
6. Capacity compensation rate for pipe length and height
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
difference
OUTDOOR UNIT
AOU9-15RLS3H

6-1. Models: AOU9RLS3H and AOU12RLS3H

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
Height difference H
unit *2
Pipe length
m
5 7.5 10 15 20
ft 16 24 32 49 65 15 49 - - - 0.877 0.874 10 32 - - 0.956 0.891 0.888
7.5 24 - 0.988 0.960 0.895 0.892 5 16 1.017 0.992 0.964 0.899 0.895 0 0 1.025 1.000 0.971 0.906 0.902
-5 -16 1.025 1.000 0.971 0.906 0.902
-7.5 -24 - 1.000 0.971 0.906 0.902
-10 -32 - - 0.971 0.906 0.902
-15 -49 - - - 0.906 0.902
OUTDOOR UNIT
AOU9-15RLS3H
HEATING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
Height difference H
unit *2
Pipe length
m
5 7.5 10 15 20
ft 16 24 32 49 65 15 49 - - - 0.933 0.925 10 32 - - 0.981 0.933 0.925
7.5 24 - 1.000 0.981 0.933 0.925 5 16 1.017 1.000 0.981 0.933 0.925 0 0 1.017 1.000 0.981 0.933 0.925
-5 -16 1.012 0.995 0.976 0.928 0.920
-7.5 -24 - 0.993 0.974 0.926 0.918
-10 -32 - - 0.971 0.923 0.916
-15 -49 - - - 0.914 0.906

6-1. Models: AOU9RLS3H and AOU12RLS3H 6. Capacity compensation rate for pipe length and height difference

- 49 -
Page 54

6-2. Model: AOU15RLS3H

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
OUTDOOR UNIT
AOU9-15RLS3H
COOLING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
Height difference H
unit *2
HEATING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
Height difference H
unit *2
Pipe length
m
5 7.5 10 15 20
ft 16 24 32 49 65 15 49 - - - 0.951 0.950 10 32 - - 0.979 0.967 0.966
7.5 24 - 0.988 0.983 0.971 0.970 5 16 0.994 0.992 0.987 0.975 0.974 0 0 1.002 1.000 0.995 0.983 0.982
-5 -16 1.002 1.000 0.995 0.983 0.982
-7.5 -24 - 1.000 0.995 0.983 0.982
-10 -32 - - 0.995 0.983 0.982
-15 -49 - - - 0.983 0.982
Pipe length
m
5 7.5 10 15 20
ft 16 24 32 49 65 15 49 - - - 0.994 0.979 10 32 - - 1.012 0.994 0.979
7.5 24 - 1.000 1.012 0.994 0.979 5 16 0.969 1.000 1.012 0.994 0.979 0 0 0.969 1.000 1.012 0.994 0.979
-5 -16 0.964 0.995 1.007 0.989 0.974
-7.5 -24 - 0.993 1.004 0.986 0.972
-10 -32 - - 1.002 0.984 0.969
-15 -49 - - - 0.974 0.959
OUTDOOR UNIT
AOU9-15RLS3H
6-2. Model: AOU15RLS3H 6. Capacity compensation rate for pipe length and height difference
- 50 -
Page 55

7. Additional charge calculation

7-1. Models: AOU9RLS3H and AOU12RLS3H

Refrigerant type R410A
Refrigerant amount
lb oz 2 lb 14 oz
g 1,300
OUTDOOR UNIT
AOU9-15RLS3H

7-2. Model: AOU15RLS3H

¢ Refrigerant charge
¢ Refrigerant charge
Total pipe length
Additional charge
Refrigerant type R410A
Refrigerant amount
Total pipe length
Additional charge
lb oz 3 lb 1 oz
ft 49 or less 66 (Max.)
m 15 or less 20 (Max.)
oz 0 +3.5
g 0 +100
g 1,400
ft 49 or less 66 (Max.)
m 15 or less 20 (Max.)
oz 0 +3.5
g 0 +100
0.22 oz/ft (20 g/m)
0.22 oz/ft (20 g/m)
OUTDOOR UNIT
AOU9-15RLS3H
7-1. Models: AOU9RLS3H and AOU12RLS3H 7. Additional charge calculation
- 51 -
Page 56

8. Airflow

8-1. Models: AOU9RLS3H and AOU12RLS3H

Cooling
OUTDOOR UNIT
AOU9-15RLS3H
Heating

8-2. Model: AOU15RLS3H

Cooling
m3/h
l/s 467
CFM 989
m3/h
l/s 510
CFM 1,082
m3/h
l/s 569
CFM 1,206
1,680
1,840
2,050
OUTDOOR UNIT
AOU9-15RLS3H
Heating
m3/h
l/s 510
CFM 1,082
1,840
8-1. Models: AOU9RLS3H and AOU12RLS3H 8. Airflow
- 52 -
Page 57

9. Operation noise (sound pressure)

NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000

9-1. Noise level curve

Model: AOU9RLS3H
¢
Cooling
OUTDOOR UNIT
AOU9-15RLS3H
Heating
OUTDOOR UNIT
AOU9-15RLS3H
Model: AOU12RLS3H
¢
Cooling
9-1. Noise level curve 9. Operation noise (sound pressure)
Heating
- 53 -
Page 58
Model: AOU15RLS3H
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave band sound pressure level, dB: (0 dB=0.0002 µbar)
Octave band center frequency, Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
¢
Cooling
OUTDOOR UNIT
AOU9-15RLS3H
Heating
OUTDOOR UNIT
AOU9-15RLS3H
9-1. Noise level curve 9. Operation noise (sound pressure)
- 54 -
Page 59

9-2. Sound level check point

40 in (1 m)
MicrophoneMicrophone
Rear
A
irflow
Rear view
Side view
OUTDOOR UNIT
AOU9-15RLS3H
NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated
above.
OUTDOOR UNIT
AOU9-15RLS3H
9-2. Sound level check point 9. Operation noise (sound pressure)
- 55 -
Page 60

10. Electrical characteristics

OUTDOOR UNIT
AOU9-15RLS3H
*1: Minimum Circuit Ampacity (Calculation based on UL1995) *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de­vices complied to the regional standard.
*3: Maximum Circuit Breaker *4: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
Model name AOU9RLS3H AOU12RLS3H AOU15RLS3H Power
supply
Voltage V 208/230~
Frequency Hz 60 MCA *1 A 14.4 18.2 Starting current A 3.3 4.7 5.2
MAX. CKT. BKR *3 A 15 20
Wiring spec. *2
Power cable AWG 14 12
Connection
cable *4
Size AWG 14 Limited wiring
length
ft (m) 68 (21)
OUTDOOR UNIT
AOU9-15RLS3H
- 56 -
10. Electrical characteristics
Page 61

11. Safety devices

OUTDOOR UNIT
AOU9-15RLS3H
Type of
protection
Circuit protection
Fan motor protection
Compressor protection
Protection form
AOU9RLS3H AOU12RLS3H AOU15RLS3H
Current fuse (Near the terminal)
250 V, 20 A
250 V, 5 A
Current fuse (Filter PCB)
Current fuse (Main PCB)
Thermal protection program
Thermal protection
Activate
Reset
Activate
250 V, 15 A 250 V, 3.15 A
250 V, 3.15 A 250 V, 5 A
212±27 °F (110±15 °C)
203±18 °F (95±10 °C)
program (Discharge temp.)
Reset
Model
Fan motor stop
Fan motor restart
230 °F (110 °C)
Compressor stop
After 7 minutes
Compressor restart
250 V, 5 A
250 V, 25 A
250 V, 5 A
OUTDOOR UNIT
AOU9-15RLS3H
- 57 -
11. Safety devices
Page 62

12. Accessories

OUTDOOR UNIT
AOU9-15RLS3H
Part name Exterior Q’ty Part name Exterior Q’ty
Installation manual 1
OUTDOOR UNIT
AOU9-15RLS3H
- 58 -
12. Accessories
Loading...