• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) /67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) /59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) /43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play store or on App Store. For details, refer to the setting manual.
Wall mounted
Inverter heat pump
Cooling
Heating
Cooling
Heating
Cooling
Heating3.34.75.2
Cooling
Heating879396
Cooling
Heating11.911.914.9
Cooling
Airflow rate
Heating
Type × Q'tyCross flow fan × 1
Motor outputW61
Cooling
Heating
Dimensions (H × W × D)in (mm)
Fin pitchFPIMain: 21, Sub 1 and Sub 2: 18
Rows × StagesMain: 3 × 24, Sub 1: 1 × 4, Sub 2: 1 × 6
Pipe typeCopper tube
Fin typeAluminum
MaterialPolystyrene
Color
Net
Gross
Net
Gross37 (17)
Size
MethodFlare
MaterialPP+LLDPF
Sizein (mm)
Cooling
Heating°F (°C)60 to 88 (16 to 30)
Remote controllerWireless (Wired [option])
Mobile application *3FGL new mobile app
By installing mobile app on a smart device, several functions can be controlled from outside the
house.
WALL MOUNTED
ASU9-15RLS3Y
2-1. System requirement
Before using this function, prepare the following items:
• Wireless router:
Wireless LAN standardIEEE802.11b/g/n
Frequency bands*
Network security standard
• U.S.A., Canada: 2.4 GHz (1ch—11ch)
• Other countries: 2.4 GHz (1ch—13ch)
• Open
• WEP
• WPA (PSK)
• WPA2 Personal (PSK)
• WPS for same-LAN registration
*: Usable only in the country or region where you purchased the product.
To check whether your wireless router complies with the network security standards listed above,
refer to the operation manual.
WALL MOUNTED
ASU9-15RLS3Y
• Smartphone or Tablet PC:
App-compliant operating
system
®
iOS
Android
™
Version 8.0 or later
Version 4.1 or later
• (mobile application):
Mobile app is available on Google Play™ store or on App Store®.
After installation of mobile app, user registration is required. For user registration and setup infor-
mation, refer to Setting Manual attached with the product.
For the latest version of the Wireless LAN (WLAN) control manuals, refer to the following web site.
https://www.fujitsu-general.com/global/support/
2-1. System requirement2. Wireless LAN control
- 3 -
Page 8
2-2. Wireless LAN function list
NOTE: To use Wireless LAN control, user registration in advance and access to the wireless home
Human sensor setting○*○*
Outdoor unit low noise operation setting○*○*
ItemMobile app
Louver position adjustment
(vertical/horizontal)
○○
Swing (vertical/horizontal)○○
Off timer—○
On timer—○
Sleep timer—○
On/off program timer—○
Weekly timer○○
Attached
wireless
remote
controller
WALL MOUNTED
ASU9-15RLS3Y
*: Not operable when wired remote controller is connected.
2-2. Wireless LAN function list2. Wireless LAN control
- 4 -
Page 9
3. Dimensions
Unit: in (mm)
14-3/4 (375)
for pipe inlet Ø 2-9/16 (65)
for pipe inlet Ø 2-9/16 (65)
15-1/4 (387)
Outline of unit
18-1/2 (470)18-1/2 (470)
10-5/8 (270)
1-11/16 (43)
11-5/8 (295)
11-5/8 (295)
37 (940)
37 (940)
15-1/4 (387)
3-1/4
(83)
3-1/16
(77)
15-7/16 (393)
1-9/16 (40)
3/8 (9)
1-11/16 (43)
WALL MOUNTED
3-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y
ASU9-15RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
3-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y3. Dimensions
- 5 -
Page 10
¢
Outline of unit
Unit: in (mm)
2 (50) or more
5 (127) or more
2 (50) or more
6 (133) or more
60 (1,500) or more
2 (50) or more
4 (84) or more
71 (1,800) or more
Provide sufficient installation space for product safety.
WALL MOUNTED
ASU9-15RLS3Y
Installation space requirement
WALL MOUNTED
ASU9-15RLS3Y
3-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y3. Dimensions
- 6 -
Page 11
4. Wiring diagrams
WALL MOUNTED
4-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y
ASU9-15RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
4-1. Models: ASU9RLS3Y, ASU12RLS3Y, and ASU15RLS3Y4. Wiring diagrams
- 7 -
Page 12
5. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
WALL MOUNTED
ASU9-15RLS3Y
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)
Circuit protectionCurrent fuse (PCB*)250 V, 3.15 A
Fan motor protection
*PCB: Printed Circuit Board
Type of protectionProtection form
Thermal protector
program
Activate
Reset
Model
ASU9RLS3YASU12RLS3YASU15RLS3Y
302±27 °F (150±15 °C)
Fan motor speed down
248±27 °F (120±15 °C)
Fan motor speed recover
WALL MOUNTED
ASU9-15RLS3Y
- 20 -
8. Safety devices
Page 25
9. External input and output
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
WALL MOUNTED
ASU9-15RLS3Y
9-1. External input
With using external input function, some functions on this product can be controlled from an external
device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
• The wire connection should be separate from the power cable line.
¢
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial on/off
switch to a connector on the external control PCB and turning it on.
ConnectorInputOutputRemarks
CNA01Control input—
CNB01—Operation status output
CNB02—Error status output
See external input/output
settings for details.
Control input (Operation/Stop or Forced stop)
WALL MOUNTED
ASU9-15RLS3Y
Unit operationInitial setting after power is onStarting mode other than initial setting
Operation modeAuto changeoverMode at previous operation
Set temperature75 °F (24 °C)Temperature at previous operation
Airflow modeAUTOMode at previous operation
Air direction (swing)Standard air direction (swing: off)Air direction at previous operation
9-1. External input9. External input and output
- 21 -
Page 26
• Circuit diagram example
Signal
Locally purchased
Indoor unit
control PCB
Communication kit
Optional parts
Connector
1
3
33 ft (10 m)*
Connected unit
Example: Switch
Operation
Stop
On
Off
Input signal
Indoor unit
Remote controller
OnOnOn
Input signal
Indoor unit
Command
Remote control
operation invalidity
On
Off
Operation
Stop
Forced stop
Normal
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
OnOnOff
WALL MOUNTED
ASU9-15RLS3Y
– When function setting is “Operation/Stop” mode
– When function setting is “Forced stop” mode
• Contact capacity: DC 24 V or more,
10 mA or more.
• *: Make the distance from the PCB to
the connected unit within 33 ft (10
m).
• Use non-polar relays and switches.
WALL MOUNTED
ASU9-15RLS3Y
– When function setting is "Operation/Stop" mode 2
9-1. External input9. External input and output
NOTE:
When "Operation/Stop" mode 2 function is used with forming a remote controller
group, connect the same equipment to each indoor unit within the group.
- 22 -
Page 27
• Optional part
WALL MOUNTED
ASU9-15RLS3Y
Part nameModel nameExterior
External input wire
External connect kitUTY-XWZXZ5
Communication kitUTY-TWBXF1
* For operating the external function, the wall mounted type requires the communication kit in addition to the wire (UTY-XWZXZ5).
WALL MOUNTED
ASU9-15RLS3Y
9-1. External input9. External input and output
- 23 -
Page 28
9-2. External output
Locally purchasedOptional parts
Example: Display
Indoor unit
control PCB
Communication kitConnected unit
Example: Relay unit
1
2
Signal
Relay
power supply
V
Connector
33 ft (10 m)*
DC 24 V
On
Off
Operation
Stop
Indoor unit
Output signal
With using external output function, operating status of this product can be transmitted to the external device, and also, this product can be inter-connected with the external device.
WALL MOUNTED
ASU9-15RLS3Y
¢
Circuit diagram example
Operation status output
WALL MOUNTED
ASU9-15RLS3Y
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
Optional part
Part nameModel nameExterior
External connect kitUTY-XWZXZ5
Communication kitUTY-TWBXF1
External output wire
* For operating the external function, the wall mounted type requires the communication kit in
addition to the wire (UTY-XWZXZ5).
9-2. External output9. External input and output
- 24 -
Page 29
¢
Locally purchasedOptional parts
Example: Display
Indoor unit
control PCB
Communication kitConnected unit
Example: Relay unit
1
2
Signal
Relay
power supply
V
Connector
33 ft (10 m)*
DC 24 V
On
Off
Error
Normal
Error status
Output signal
Circuit diagram example
WALL MOUNTED
ASU9-15RLS3Y
Error status output
• *: Make the distance from the PCB to the connected unit within 33 ft (10 m).
• Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.
WALL MOUNTED
ASU9-15RLS3Y
Optional part
Part nameModel nameExterior
External connect kitUTY-XWZXZ5
Communication kitUTY-TWBXF1
* For operating the external function, the wall mounted type requires the communication kit in
addition to the wire (UTY-XWZXZ5).
External output wire
9-2. External output9. External input and output
- 25 -
Page 30
10. Remote controller
Signal
transmitter
MIN. HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
OUTDOOR UNIT
LOW NOISE button
SWING button
SET button
WEEKLY button
ON/OFF button
SLEEP button
MODE button
SENSOR button
FAN button
TEST RUN
button
RESET
button
CLOCK ADJUST
button
ECONOMY button
Mode indicator
ENERGY SAVING mode
indicator
LOW NOISE mode
indicator
Turns on when
the SENSOR button is operated.
Clock and Timer indicator
SEND indicator
Temperature indicator
Fan speed indicator
Swing indicator
Transmit indicator
WALL MOUNTED
10-1. Wireless remote controller
ASU9-15RLS3Y
¢
Overview
WALL MOUNTED
ASU9-15RLS3Y
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators;
in actual operation, however, the display will only show those indicators appropriate to the current operation.
To adjust the functions of this product according to the installation environment, various types of
function settings are available.
WALL MOUNTED
ASU9-15RLS3Y
NOTE:
11-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting procedure and the content of each function setting, select appropriate functions for your installation environment.
¢
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller,
and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Cover for the electrical enclosure on the outdoor unit is in place.
• There is no wiring mistake.
• Piping air tight test and vacuuming have been performed firmly.
• All the necessary wiring work for outdoor unit has been finished.
Incorrect settings can cause a product malfunction.
Setting procedure by using wireless remote controller
WALL MOUNTED
ASU9-15RLS3Y
After reconfirming the items listed above, connect the power supply of the indoor unit.
NOTES:
• Settings will not be changed if invalid numbers or setting values are selected.
• When optional wired remote controller is used, refer to the installation manual enclosed with the
remote controller.
Entering function setting mode:
While pressing the POWERFUL button and TEMP. () button simultaneously, press the RESET button to enter the function setting mode.
Selecting the function number and setting value:
1. Press the TEMP. () () buttons to select the function number. To
switch between the left and right digits, press the MIN. HEAT button.
2. Press the POWERFUL button to proceed to value setting. To return
the function number selection, press the POWERFUL button again.
3. Press the TEMP. () () buttons to select the setting value. To
switch between the left and right digits, press the MIN. HEAT button.
4. Press the MODE button once to send the function setting information. Confirm that you hear the beep sound.
5. Press the START/STOP button to fix the function setting. Confirm
that you hear the beep sound.
6. Press the RESET button to end the function setting mode.
7. After completing the function setting, be sure to disconnect the power supply and then reconnect it.
CAUTION
After disconnecting the power supply, wait 30 seconds or more before reconnecting it. The function
setting will not become active unless the power supply is disconnected and then reconnected.
11-1. Function settings by using remote controller11. Function settings
- 28 -
Page 33
¢
Each function setting listed in this section is adjustable in accordance with the installation environment.
WALL MOUNTED
ASU9-15RLS3Y
NOTE:
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Contents of function setting
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.Functions
1)11Filter sign
2)30/31Room temperature control for indoor unit sensor
3)35/36Room temperature control for wired remote controller sensor
4)40Auto restart
5)42Room temperature sensor switching
6)44Remote controller custom code
7)46External input control
8)48Room temperature sensor switching (Aux.)
9)49Indoor unit fan control for energy saving for cooling
11-1. Function settings by using remote controller11. Function settings
- 29 -
Page 34
2) Room temperature control for indoor unit sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-
WALL MOUNTED
ASU9-15RLS3Y
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
*When Function 95-01 (High insulation) is set, the Standard setting "00" will be the same as "No cor-
11-1. Function settings by using remote controller11. Function settings
- 30 -
Page 35
3) Room temperature control for wired remote controller sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the wire remote temperature sensor may be
WALL MOUNTED
ASU9-15RLS3Y
required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Enables or disables automatic restart after a power interruption.
Function numberSetting valueSetting descriptionFactory setting
40
00Enable♦
01Disable
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external device.
5) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function numberSetting valueSetting descriptionFactory setting
42
00Indoor unit♦
01Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
11-1. Function settings by using remote controller11. Function settings
- 31 -
Page 36
6) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
WALL MOUNTED
ASU9-15RLS3Y
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
8) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting 30 and 31 too.
Function numberSetting valueSetting descriptionFactory setting
00A♦
44
Function numberSetting valueSetting descriptionFactory setting
Function numberSetting valueSetting descriptionFactory setting
48
00Both♦
01Wired remote controller
9) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function numberSetting valueSetting descriptionFactory setting
00Disable
49
01Enable
02Remote controller♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially invalidated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for energy saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each remote
controller.
11-1. Function settings by using remote controller11. Function settings
Heat insulation conditions differ according to the installed environment.
"Standard insulation" (00) allows system to rapidly respond to the cooling or heating load changes.
"High insulation" (01) is when the heat insulation structure of the building is high and does not re-
WALL MOUNTED
ASU9-15RLS3Y
quire system to rapidly respond to cooling or heating load changes.
When "High insulation" (01) is selected:
• Overheating (overcooling) is prevented at the start-up.
• All room-temperature control settings (Function 30, 31, 35, and 36) will reset to "No correction
NOTE: When changing Function 95, perform this setting before other room-temperature control
0.0 °F (0.0 °C)".
Function numberSetting valueSetting descriptionFactory setting
95
00Standard insulation♦
01High insulation
settings (Function 30, 31, 35, and 36). If Function 95 is not set first, room-temperature control settings (Function 30, 31, 35, and 36) will be reset and you must re-do them again.
WALL MOUNTED
ASU9-15RLS3Y
11-1. Function settings by using remote controller11. Function settings
- 33 -
Page 38
11-2. Custom code setting for wireless remote controller
To interconnect the air conditioner and the wireless remote controller, assignment of the custom
code for the wireless remote controller is required.
WALL MOUNTED
ASU9-15RLS3Y
NOTE:
When 2 or more air conditioners are installed in a room, and the remote controller is operating an air
conditioner other than the one you wish to set, change the custom code of the remote controller to
operate only the air conditioner you wish to set. (4 selections possible.)
Confirm the setting of the remote controller custom code and the function setting. If these do not
match, the remote controller cannot be used to operate for the air conditioner.
Air conditioner cannot receive a signal if the air conditioner has not been set for the custom
code.
1. Press the START/STOP button until only the clock is displayed on
the remote controller display.
2. Press the MODE button for at least 5 seconds to display the current
custom code. (Initially set to
.)
3. Press the TEMP. () () buttons to change the custom code between → → → . Match the code on the display to the air conditioner custom code. (Initially set to .)
WALL MOUNTED
ASU9-15RLS3Y
4. Press the MODE button again to return to the clock display. The
custom code will be changed.
NOTES:
• If no button is pressed within 30 seconds after the custom code is displayed, the system returns
to the original clock indicator. In this case, start again from step 1.
The air conditioner custom code is set to prior to shipment. To change the custom code, con-
•
tact your retailer.
If you do not know the assigned code for the air conditioner, try each of the custom code (
•
→
→ → ) until you find the code which operates the air conditioner.
11-2. Custom code setting for wireless remote controller11. Function settings
- 34 -
Page 39
11-3. Switching the temperature unit of remote controller
Displayed temperature unit on the remote controller LCD can be switched between °F (Fahrenheit)
and °C (Celsius).
WALL MOUNTED
ASU9-15RLS3Y
To change temperature unit, do as follows:
1.Press the TEMP. (Up) button () for at least 5 seconds to display the current temperature unit.
2.Press the TEMP. () () buttons to switch the temperature unit between °F and °C.
3.With either of pressing the START/STOP button or no additional button operation for 30 sec-
(Factory setting: °F)
onds in step 2., the temperature unit currently selected will be set.
WALL MOUNTED
ASU9-15RLS3Y
11-3. Switching the temperature unit of remote controller11. Function settings
- 35 -
Page 40
12. Accessories
WALL MOUNTED
ASU9-15RLS3Y
Operating manual1
Setting manual
(for Wireless LAN
control)
Installation manual1Tapping screw (large)1
Wall hook bracket1Tapping screw (small)5
Remote controller1Air cleaning filter2
Part nameExteriorQ’tyPart nameExteriorQ’ty
Wireless LAN label
(Attached to the indoor unit beside the wireless
1
LAN indicator)
1Cloth tape1
WALL MOUNTED
ASU9-15RLS3Y
Battery2Filter holder2
Remote controller
holder
Seal A
1
(for 15 model)
1
- 36 -
12. Accessories
Page 41
13. Optional parts
Mode
Menu
Cool
Monitor
Set temp.
Fan
High
°
F
80
Mo
10:00
AM
Icon check:
WALL MOUNTED
13-1. Controllers
ASU9-15RLS3Y
ExteriorPart nameModel nameSummary
Large and full-dot liquid crystal screen,
wide and large keys easy to press,
user-intuitive arrow key.
Wired remote
controller
UTY-RVNUM
Wire type: Polar 3-wire
Optional communication kit is
necessary for installation.
Room temperature can be controlled
by detecting the temperature
accurately with built-in thermo sensor.
Wired remote
controller
UTY-RNNUM
Wire type: Polar 3-wire
Optional communication kit is
necessary for installation.
Compact remote controller
concentrates on the basic functions
such as Start/Stop, fan control,
temperature setting, and operation
Simple remote
controller
UTY-RSNUM
mode.
Wire type: Polar 3-wire
Optional communication kit is
necessary for installation.
WALL MOUNTED
ASU9-15RLS3Y
NOTES:
• Available functions may differ by the remote controller. For details, refer to the operation manual.
• In this product, group controlling system of the wired remote controller is prohibited.
13-2. Others
ExteriorPart nameModel nameSummary
Required when external device is
External
connect kit
Communication
kit
UTY-XWZXZ5
UTY-TWBXF1
connected.
Optional communication kit is
necessary for installation.
Use to connect with optional devices
and air conditioner PCB.
13-1. Controllers13. Optional parts
- 37 -
Page 42
WALL MOUNTED
ASU9-15RLS3Y
WALL MOUNTED
ASU9-15RLS3Y
13-2. Others13. Optional parts
- 38 -
Page 43
Part 2. OUTDOOR UNIT
SINGLE TYPE:
AOU9RLS3H
AOU12RLS3H
AOU15RLS3H
Page 44
1. Specifications
TypeInverter heat pump
Model nameAOU9RLS3HAOU12RLS3HAOU15RLS3H
Power supply208/230 V ~ 60 Hz
Available voltage range188—253 V
Starting currentA3.34.75.2
Fan
Sound pressure level *1
OUTDOOR UNIT
AOU9-15RLS3H
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions
(H × W × D)
Weight
Connection pipe
Operation range
Drain hose
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
– Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Cooling
Heating4750
Dimensions
(H × W × D)
Fin pitchFPI20
Rows × Stages2 × 28
Pipe typeCopper
Fin type
TypeR410A
Charge
TypeFREOL (ɑ68SZ)
Amount
MaterialSteel sheet
Color
Liquid
GasØ 3/8 (Ø 9.52)Ø 1/2 (Ø 12.7)
Cooling
Heating-15 to 75 (-26 to 24)
MaterialLDPE
Sizein (mm)
CFM (m3/h)
dB (A)
in23-1/8 × 34-11/16 × 1-7/16
mm588 × 881 × 36.4
Type (Material)Corrugate (Aluminum)
Surface treatmentCorrosion resistance (Blue fin)
lb oz2 lb 14 oz3 lb 1 oz
g1,3001,400
in3 (cm3)
in24-1/2 × 31-1/8 × 11-7/16
mm620 × 790 × 290
in28-1/16 × 37-3/16 × 15-9/16
mm713 × 945 × 395
lb (kg)
in (mm)
ft (m)
°F (°C)
424349
989 (1,680)1,206 (2,050)
12.5 (205)
Beige
Approximate color of Munsell 10YR 7.5/1.0
86 (39)88 (40)
Ø 1/4 (Ø 6.35)
49 (15)
14 to 115 (-10 to 46)
Ø 9/16 (Ø 13.8) [I. D.]
Ø5/8 to Ø11/16 (Ø 15.8 to Ø 16.7) [O. D.]
OUTDOOR UNIT
AOU9-15RLS3H
- 40 -
1. Specifications
Page 45
2. Dimensions
Unit: in (mm)
Top view
Front view
Bottom view
Side view
31-1/8 (790)
24-7/16 (620)
13/16 (20)
3/8 (9)
3/4 (19)2-5/8 (67)
11-5/16 (288)
11/16 (18)7/8 (23)
13-7/8 (352)
4-5/16
(110)
8-1/4 (209)
6-7/8 (175)
12-5/8 (320)
4-ø7/16 (11.3) hole
21-1/4 (540)
Airflow
ø13/16 (20) hole
1 (25)
2-3/16
(55)
3/8(10)
hole
1(25)
3/8 (10)
3/8 (10)
hole
4 (102)
2-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
2-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H2. Dimensions
- 41 -
Page 46
3. Installation space
4 (100) or more
10 (250) or more
4 (100) or more
4 (100) or more
24 (600) or more
24 (600) or more
4 (100) or more
4 (100) or more
Max. 7 (200)
24 (600)
or more
24 (600)
or more
4 (100) or more
10 (250) or more
4 (100) or more
Max. 7 (200)
3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H
¢
Provide sufficient installation space for product safety.
Single outdoor unit installation
OUTDOOR UNIT
AOU9-15RLS3H
Space requirement
• When the upper space is open:
When there are obstacles at the rear only.When there are obstacles at the rear and
sides.
Unit: in (mm)
OUTDOOR UNIT
AOU9-15RLS3H
When there are obstacles at the front only.When there are obstacles at the front and
rear.
• When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and
above.
When there are obstacles at the rear, sides,
and above.
3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H3. Installation space
- 42 -
Page 47
Multiple outdoor unit installation
8 (200)
or more
40 (1,000)
or more
8 (200) or more
40 (1,000) or more
60 (1,500)
or more
8 (200) or more
Max. 11 (300)
OUTDOOR UNIT
AOU9-15RLS3H
• When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only.When there are obstacles at the front only.
When there are obstacles at the front and
rear.
OUTDOOR UNIT
AOU9-15RLS3H
• When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H3. Installation space
- 43 -
Page 48
Outdoor unit installation in multi-row
4 (100)
or more
8 (200) or more
20 (500) or more
40 (1,000)
or more
8 (200) or more
16 (400) or more
40 (1,000) or more
80 (2,000) or more
8 (200) or more
OUTDOOR UNIT
AOU9-15RLS3H
Single parallel unit arrangementMultiple parallel unit arrangement
Unit: in (mm)
OUTDOOR UNIT
AOU9-15RLS3H
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 2 in (50 mm) or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the
drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 32 °F (0 °C) or less, do not use the accessory drain pipe and
drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in
extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it
might become difficult to get warm, and it is likely to cause product malfunction. Construct a
canopy and a pedestal, or place the unit on a high stand that is locally installed.
3-1. Models: AOU9RLS3H, AOU12RLS3H, and AOU15RLS3H3. Installation space
- 44 -
Page 49
4. Refrigerant circuit
2-way
valve
Strainer
Strainer
3-way
valve
MufflerMuffler
Acccumlator
4-way valve
Expansion valve
Heat exchanger
( INDOOR )
Heat exchanger
( OUTDOOR )
Compressor
Cooling
Heating
Th
D
Th
R
Th
PI
Th
HO
Th
O
Th
R
Th
PI
Th
D
Th
O
Th
HO
:Thermistor (Room temp.)
:Thermistor (Pipe temp.)
:Thermistor (Discharge temp.)
:Thermistor (Outdoor temp.)
:Thermistor (Heat exchanger out temp.)
4-1. Models: AOU9RLS3H and AOU12RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
4-1. Models: AOU9RLS3H and AOU12RLS3H4. Refrigerant circuit
- 45 -
Page 50
4-2. Model: AOU15RLS3H
Th
R
Th
PI
Th
R
Th
PI
Th
D
Th
D
Th
O
Th
HO
: Thermistor (Room temp.)
: Thermistor (Pipe temp.)
: Thermistor (Discharge temp.)
: Thermistor (Outdoor temp.)
: Thermistor (Heat exchanger out temp.)
Th
O
Th
HO
Compressor
Muffler
Muffler
Heat exchanger
(INDOOR)
Heat exchanger
(OUTDOOR)
3-Way
valve
2-Way
valve
Cooling
Heating
Receiver
Strainer
Strainer
Expansion valve
OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
4-2. Model: AOU15RLS3H4. Refrigerant circuit
- 46 -
Page 51
5. Wiring diagrams
5-1. Models: AOU9RLS3H and AOU12RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
5-1. Models: AOU9RLS3H and AOU12RLS3H5. Wiring diagrams
- 47 -
Page 52
5-2. Model: AOU15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
OUTDOOR UNIT
AOU9-15RLS3H
5-2. Model: AOU15RLS3H5. Wiring diagrams
- 48 -
Page 53
6. Capacity compensation rate for pipe length and height
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
difference
OUTDOOR UNIT
AOU9-15RLS3H
6-1. Models: AOU9RLS3H and AOU12RLS3H
NOTE: Values mentioned in the table are calculated based on the maximum capacity.