Fujitsu ASTG12LVCC, ASTG18LVCC, ASTG09LVCC, AOTG09LVCC, AOTG12LVCC Design & Technical Manual

...
Page 1
AIR CONDITIONER
Wall Mounted type
INDOOR
OUTDOOR
ASTG09LVCC ASTG12LVCC ASTG18LVCC ASTG22LVCC
DESIGN & TECHNICAL MANUAL
AOTG09LVCC
AOTG22LVCC
Page 2
1. INDOOR UNIT
WALL MOUNTED TYPE :
ASTG09LVCC
ASTG12LVCC ASTG18LVCC
ASTG22LVCC
DTR_AS063E_03
2012.09.05
Page 3
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
CONTENTS
1. INDOOR UNIT
1. FEATURE
............................................................................................................ 01 - 01
2. WIRELESS REMOTE CONTROLLER
......................................... 01 - 03
3. SPECIFICATIONS
........................................................................................ 01 - 05
4. DIMENSIONS
................................................................................................... 01 - 06
5. WIRING DIAGRAMS
.................................................................................. 01 - 07
6. CAPACITY TABLE
....................................................................................... 01 - 08
6-1. COOLING CAPACITY
................................................................................ 01 - 08
6-2. HEATING CAPACITY
................................................................................. 01 - 09
7. FAN PERFORMANCE
.............................................................................. 01 - 10
7-1. AIR VELOCITY DISTRIBUTION
............................................................... 01 - 10
7-2. AIR FLOW
.................................................................................................... 01 - 13
8. OPERATION NOISE
................................................................................... 01 - 17
8-1. NOISE LEVEL CURVE
............................................................................... 01 - 17
8-2. SOUND LEVEL CHECK POINT
............................................................... 01 - 19
9. ELECTRIC CHARACTERISTICS
..................................................... 01 - 20
10. SAFETY DEVICES
....................................................................................... 01 - 21
11. EXTERNAL INPUT & OUTPUT
......................................................... 01 - 22
11-1. EXTERNAL INPUT
...................................................................................... 01 - 22
11-2. EXTERNAL OUTPUT
................................................................................. 01 - 23
12. FUNCTION SETTING
................................................................................ 01 - 24
12-1. INDOOR UNIT (Setting by remote controller)
..................................... 01 - 24
13. OPTIONAL PARTS
...................................................................................... 01 - 28
13-1. CONTROLLER
............................................................................................ 01 - 28
13-2. OTHERS
....................................................................................................... 01 - 28
Page 4
- (01 - 01) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
FEATURE1.
MODEL
ASTG09LVCC / AOTG09LVCC ASTG12LVCC / AOTG12LVCC ASTG18LVCC / AOTG18LVCC ASTG22LVCC / AOTG22LVCC
FEATURES
Energy Efficiency
MODEL
ASTG09LVCC ASTG12LVCC ASTG18LVCC ASTG22LVCC
STAR RATING
INDEX
Cooling 4.0 3.0 2.0 2.0 Heating 4.5 4.0 3.5 2.5
High efficiency & Compact
Significantly high efficiency is realized by using DC twin rotary compressor, DC inverter control and DC fan motor technologies. All models achieve new MEPS standard.
High density multiple path heat exchanger
Original technology supporting
energy saving and high power
Cross section of
copper pipes
1,
Copper pipe diameter
5 mm
High density technology
2,
Refrigerant branches
4*
Multiple path technology
*: For 22 type, refrigerant branches 6.
Smooth flow of the refrigerant
(Schematic)
ALL DC
DC fan motor
DC compressor
The two aspects that have evolved
Cooling
Heating
3.0 3.5
0
4.0
9000Btu
18000Btu
4.66 (COP)
3.0 3.5
0
4.0
12000Btu
22000Btu
4.32 (COP)
4.31 (EER)
3.80 (EER)
Cooling
Heating
3.0 3.5
0
4.0
4.03 (COP)
3.0 3.5
0
4.0
3.55 (COP)
3.27 (EER)
3.23 (EER)
790
mm
Compact stylish design
for all capacity range
AOTG09LVCC AOTG12LVCC AOTG18LVCC
AOTG22LVCC
Page 5
- (01 - 02) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
10°C HEAT Operation
The room temperature can be set to go no lower than 10°C, thus ensuring that the room does not get too cold when not occupied.
Caution)
When the room temperature is higher than 10°C, “10°C HE AT” operation does not start. Operation starts and maintains the room
temperature at 10°C when the temperature drops below 10°C.
“10°C HEAT” Button
ON
10
°C
20
°C
“10ºC HEAT” Button
ON
Indoor unit operation START
Super quiet
Air flow mode can be set in 4 steps and more detailed air flow setting is possible.
Fan speed Noise level
Quiet 21*
dB(A)
*: This value is for 9/12 type only.
Easy maintenance
Easy maintenance and always clean. Troublesome maintenance has been made easy.
Since the front panel is easy to remove, maintenance is also easy.
Low outdoor air temperature correspondence
Corresponds to cooling operation at 10°C outdoor air temperature Corresponds to heating operation at -15°C outdoor air temperature
Cooling Heating
10
°C
-15
°C
Corresponds to maximum 20m long piping
Air conditioner filter features
Clean automatic open panel • Air clean (Anti-bacteria) filter provides clean and comfort airflow
Blue fin heat exchanger
Corrosion-resistance of the heat exchanger even in coastal areas has been improved by blue fin treatment of the outdoor unit heat exchanger.
Open panel
Clean air
Dirty air
Air clean filter
Blue fin heat exchanger
Cobalt Blue protection
Standard chromate protection
Aluminium base material
Hydrophilic coating
Page 6
- (01 - 03) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
WIRELESS REMOTE CONTROLLER2.
FEATURES
Four kinds of timer setup
(ON/OFF/PROGRAM/SLEEP) are possible.
Four kinds of timers. Easy operation.
Easy to change transmission code (4 patterns) by button operation.
Built-in timers
Select from four different timer programs (ON/OFF/PROGRAM/SLEEP).
Program timer
The program timer operates the on and off timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the timer setting to prevent excessive cooling and heating while sleeping.
60min.
1 °C
2 °C
Timer setting
Set temp.
1 °C
30min.
60min.
90min.
2 °C
3 °C
4 °C
Set temp.
Timer setting
Cooling operation/dry operation
When the sleep timer is set, the set temperature automatically rises 1 °C every hour. The set temperature can rise up to a maximum of 2 °C.
Heating operation
When the sleep timer is set, the set temperature automatically drops 1 °C every 30 minutes. The set temperature can drop to a maximum of 4 °C.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Switching remote controller signal code
ABC D
ABCD
Mixed-up
I.U. I.U. I.U. I.U.
I.U. I.U. I.U. I.U.
After code change
Code selector switch eliminates unit
• being wrongly switched. (Up to 4 codes can be set.)
*I.U.=Indoor unit
Page 7
- (01 - 04) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
1
Signal transmitter
2
MODE button
3
10°C HEAT button
4
SET TEMP. button( / )
5
ECONOMY button
6
SLEEP button
7
TIMER MODE button
8
FAN but ton
9
START/STOP button
10
SET button (Vertical)
11
SWING button
12
TIMER SET (+ / -) button
13
CLOCK ADJUST button
14
TEST RUN button
•This button is used when installing the air conditioner, and should not be used under normal conditions, as it will c ause the indoor unit’s thermostat function to operate incorrectly.
•If this button is pressed during normal operation, the indoor unit will switch to test operation mode, and the Indoor Unit’s OPERATION Indic ator Lamp and TIMER Indicator Lamp will begin to flash simultaneously.
•To stop the test operation mode, press the SRART/STOP button to stop the air conditioner.
15
RESET button
16
Remote controller display
17
Transmit indicator
18
Fan speed display
19
Swing display
20
Timer mode display
21
Clock display
22
Temperature set display
23
Operation mode display
24
Sleep display
Functions will be different due to type of indoor unit. For details, please see operation manual.
FUNCTIONS
Display panel
16
23
24
19
17
22
18
20
21
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current operation.
SPECIFICATION
2
7
13
5
6
4
10
11
15
12
14
1
8
9
3
SIZE (H x W x D mm) 170 x 56 x 19
WEIGHT ( g ) 85 (w/o batteries)
ACCESSORY Holder
Page 8
- (01 - 05) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
SPECIFICATIONS3.
Typ e
WALL MOUNTED
INVERTER HEAT PUMP Model name ASTG09LVCC ASTG12LVCC ASTG18LVCC ASTG22LVCC Power source 240V ~ 50Hz Available voltage range 198V - 264V ~ 50Hz
STAR RATING INDEX 10 STAR standard
Cooling 4.0 3.0 2.0 2.0 Heating 4.5 4.0 3.5 2.5
Capacity
Cooling
Rated
kW 2.5 3.5 5.0 6.3
Btu/h 8,500 11,900 17,100 21,500
Min-Max
kW 0.50 - 3.3 0 0.90 - 4.00 0.90 - 5.80 0.90 - 7.30
Btu/h 1,700 - 11,300 3,100 - 13,600 3,100 - 19,800 3,100 - 24,900
Heating
Rated
kW 3.4 4.8 6.0 7.2
Btu/h 11,600 16,400 20,400 23,900
Min-Max
kW 0.50 - 4.0 0 0.90 - 5.60 1.05 - 8.10 1.05 - 8.70
Btu/h 1,700 - 13,600 3,100 - 19,100 3,600 - 27,600 3,600 - 29,700
Input power
Cooling
Rated
kW
0.58 0.92 1.53 1.95
Min- Max 0.25 - 1.24 0.25 - 1.42 0.18 - 2.03 0.18 - 2.75
Heating
Rated 0.73 1.11 1.49 2.03 Min-Max 0.25 - 1.56 0.25 - 2.0 0 0.17 - 3.19 0.17 - 4.18
Current
Cooling
Rated A
2.8 4.2 6. 5 8.2
Heating 3.5 5.0 6.3 8.5
EER Cooling
kW/kW
4.31 3.80 3.27 3.23 COP Heating 4.66 4.32 4.03 3.55 SENSIBLE CAPACITY Cooling kW 1.61 2.27 3.22 4.46
POWER FACTOR
Cooling
%
86 91 98 99
Heating 87 93 99 99 Moisture removal l/h (pints/h) 1.3 (2.3) 1.8 (3.2) 2.6 (4.6) 2.7 (4.8)
Maximum operating current *1
Cooling
A
6.0 6.5 9.5 11.5
Heating 7.5 9.0 13.5 17.5
Fan
Airflow rate
Cooling
High
I/s (m
3
/h)
219 (790) 225 (810) 267 (960) 267 (960) Med 183 (660) 189 (680) 214 (770) 217 (780) Low 144 (520) 144 (520) 183 (660) 181 (650)
Quiet 97 (35 0) 100 (360) 150 (540) 147 (530)
Heating
High 225 (810) 239 (860) 267 (960) 267 (960) Med 189 (680) 197 (710) 225 (810) 228 (820) Low 150 (540) 150 (540) 194 (700) 197 (710)
Quiet 100 (360) 100 (360) 144 (520) 147 (530) Type × Q'ty Cross flow fan×1 Motor output W 44
Sound pressure level
Cooling
High
dB (A)
41 42 46 48 Med 36 37 40 42 Low 30 30 35 37
Quiet 21 21 29 32
Heating
High 42 43 46 48 Med 37384242 Low 31 31 38 38
Quiet 22 22 30 32
Heat exchanger type
Dimensions (H × W × D)
mm
Main : 38 4×630×20
Sub : 126×630×13.3
Main : 38 4×630×20
Sub1 : 126×630×13.3
Sub2 : 84×630×13.3
Fin pitch Main : 1.1, Sub : 1.4
Rows × Stages Main : 2×24, Sub : 1×6
Main : 2×24,
Sub1 : 1×6,
Sub2 : 1×4
Pipe type Copper Fin type Aluminium
Enclosure
Material Polystyrene
Colour
WHITE
Approximate colour of MUNSELL N9.25/
Dimensions (H × W × D)
Net
mm
293×790×225
Gross 290×840×375
Weight
Net
kg
9.5 10.0
Gross 12.0
Connection pipe
Size
Liquid
mm
Ø6.35 (Ø1/4 in.)
Gas Ø9.52 (Ø3/8 in.) Ø12.70 (Ø1/2 in.) Ø15.88 (Ø5/8 in.)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote controller type Wireless
Drain hose
Material PP + LLDPE Size mm Ø13.8(I.D.), Ø15.8 to Ø16.7(O.D.)
International Protection rating IPX0
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB / 24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB / 6 °CWB. Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indo or unit) The protective function might work when using it outside the temperature range mentioned above. *1 : The maximum current is the maximum value when the operated wit hin the operation range.
Page 9
- (01 - 06) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
DIMENSIONS4.
MODEL  : ASTG09LV, ASTG12LV, ASTG18LV, ASTG22LV
(Unit : mm)
INSTALLATION PLACE
(Unit : mm)
52 or more
70 or more
48 or more
85 or more
63 or more
45 or more
1,500 or more
1,800 or more
Outline of unit
790
293
225
(Liquid pipe)
(Gas pipe)
Holes for piping (two) 65mm diameter
Outline of unit
ASTG09LV ASTG12LV ASTG18LV ASTG22LV
1
Refrigerant pipe flare
connection
Liquid ø 6.35 mm (ø 1/4 in.)
2
Gas
ø 9.52 mm
(ø 3/8 in.)
ø 12.70 mm
(ø 1/2 in.)
ø 15.88 mm
(ø 5/8 in.)
3
Drain hose connection Drain hose
I.D. ø 13.8 mm, O.D. ø 15.8 to ø 16.7 mm
Drain hose : L=420mm
Page 10
- (01 - 07) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
WIRING DIAGRAMS5.
MODEL  : ASTG09LV, ASTG12LV, ASTG18LV, ASTG22LV
Page 11
- (01 - 08) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
CAPACITY TABLE6.
COOLING CAPACITY6-1.
MODEL  :ASTG09LV
MODEL  :ASTG12LV
MODEL  : ASTG18LV
MODEL  : ASTG22LV
AFR : Air Fl ow Rate (m3/min) TC : Total Capaci ty (kW) SHC : Sens ible Heat Capac ity (kW) IP : Input Pow er (kW)
AFR 13.2
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 2.32 1.59 0.37 2.59 1.60 0.38 2.68 1.74 0.38 2.85 1.74 0.38 2.94 1.88 0.39 3.12 1.87 0.39 3.29 2.00 0.39
25 2.22 1.52 0.43 2.47 1.52 0.44 2.55 1.66 0.44 2.72 1.66 0.45 2.80 1.80 0.45 2.97 1.79 0.45 3.14 1.90 0.46
30 2.10 1.43 0.50 2.34 1.44 0.51 2.41 1.57 0.51 2.57 1.57 0.51 2.65 1.70 0.52 2.81 1.69 0.52 2.97 1.80 0.53
35 1.98 1.35 0.56 2.20 1.36 0.57 2.28 1.48 0.57 2.43 1.48 0.58 2.50 1.60 0.58 2.65 1.59 0.59 2.80 1.70 0.59
40 1.73 1.18 0.56 1.93 1.19 0.57 1.99 1.29 0.57 2.12 1.30 0.57 2.19 1.40 0.58 2.32 1.39 0.58 2.45 1.49 0.59
43 1.61 1.10 0.55 1.80 1.11 0.56 1.86 1.21 0.56 1.98 1.21 0.57 2.04 1.31 0.57 2.17 1.30 0.58 2.29 1.39 0.58
AFR 13.5
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 3.26 2.29 0.61 3.64 2.31 0.62 3.76 2.51 0.62 4.01 2.51 0.63 4.13 2.72 0.63 4.38 2.70 0.64 4.63 2.88 0.64
25 3.11 2.19 0.70 3.47 2.20 0.71 3.59 2.39 0.71 3.82 2.40 0.72 3.94 2.59 0.73 4.18 2.58 0.73 4.42 2.75 0.74
30 2.95 2.07 0.79 3.28 2.08 0.81 3.39 2.26 0.81 3.62 2.27 0.82 3.73 2.45 0.82 3.95 2.44 0.83 4.18 2.60 0.84
35 2.77 1.94 0.89 3.08 1.95 0.90 3.19 2.12 0.91 3.40 2.13 0.92 3.50 2.30 0.92 3.71 2.29 0.93 3.92 2.44 0.94
40 2.45 1.72 0.88 2.72 1.73 0.90 2.82 1.88 0.90 3.00 1.88 0.91 3.10 2.03 0.92 3.28 2.03 0.93 3.47 2.16 0.93
43 2.25 1.58 0.89 2.51 1.59 0.90 2.59 1.73 0.90 2.76 1.73 0.91 2.85 1.87 0.92 3.02 1.86 0.93 3.19 1.99 0.94
AFR 16.0
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 4.58 3.13 1.09 5.10 3.15 1.10 5.27 3.42 1.11 5.62 3.43 1.12 5.79 3.71 1.13 6.14 3.69 1.14 6.49 3.93 1.15
25 4.37 2.99 1.24 4.86 3.00 1.26 5.03 3.27 1.26 5.36 3.28 1.27 5.53 3.54 1.28 5.86 3.52 1.29 6.19 3.75 1.31
30 4.14 2.83 1.38 4.61 2.85 1.40 4.77 3.10 1.41 5.08 3.11 1.43 5.24 3.35 1.43 5.56 3.34 1.45 5.87 3.56 1.46
35 3.95 2.70 1.51 4.40 2.72 1.53 4.55 2.95 1.54 4.85 2.96 1.55 5.00 3.20 1.53 5.30 3.19 1.58 5.60 3.40 1.59
40 3.52 2.40 1.51 3.92 2.42 1.53 4.05 2.63 1.54 4.32 2.64 1.56 4.45 2.85 1.57 4.72 2.84 1.58 4.99 3.02 1.60
43 3.27 2.24 1.50 3.64 2.25 1.53 3.77 2.44 1.54 4.01 2.45 1.55 4.14 2.65 1.56 4.39 2.64 1.58 4.64 2.81 1.59
AFR 16.0
Indoor temperature
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
Outdoor temperature
°CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
20 5.79 4.38 1.35 6.45 4.41 1.37 6.67 4.79 1.38 7.11 4.81 1.39 7.33 5.19 1.40 7.77 5.17 1.40 8.21 5.51 1.40
25 5.53 4.18 1.53 6.16 4.21 1.55 6.37 4.57 1.56 6.79 4.59 1.57 7.00 4.95 1.58 7.42 4.93 1.58 7.84 5.26 1.58
30 5.26 3.98 1.70 5.86 4.00 1.73 6.06 4.35 1.74 6.46 4.37 1.76 6.66 4.72 1.76 7.06 4.70 1.76 7.46 5.00 1.76
35 4.98 3.76 1.88 5.54 3.79 1.91 5.73 4.12 1.92 6.11 4.13 1.94 6.30 4.46 1.95 6.68 4.44 1.95 7.06 4.73 1.95
40 4.67 3.53 2.07 5.20 3.55 2.10 5.38 3.86 2.11 5.74 3.88 2.13 5.91 4.19 2.14 6.27 4.17 2.14 6.62 4.44 2.14
43 4.48 3.39 2.18 4.99 3.41 2.21 5.16 3.71 2.22 5.50 3.72 2.25 5.67 4.01 2.26 6.01 4.00 2.26 6.35 4.26 2.26
Page 12
- (01 - 09) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
HEATING CAPACITY6-2.
MODEL  :ASTG09LV
MODEL  :ASTG12LV
MODEL  : ASTG18LV
MODEL  : ASTG22LV
AFR : Air Flow Ra te (m3/min) TC
: Total Capacit y (kW)
IP
: Input Power ( kW)
AFR 13.5
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 2.59 0.82 2.52 0.84 2.46 0.86 2.40 0.87 2.34 0.89
-10 -11 2.97 0. 88 2.90 0.89 2. 82 0.91 2.75 0. 93 2.68 0.95
-5 -7 3.32 0.91 3.24 0.93 3.16 0.95 3.08 0.97 3.00 0.98
0 -2 3.81 0.95 3.72 0.97 3.63 0.99 3.54 1.01 3.45 1.03
5 3 4.34 0.98 4.23 1.00 4.13 1.02 4. 03 1.04 3.92 1.06
7 6 4.64 1.01 4.53 1.03 4.42 1.05 4.31 1.07 4.20 1.09
10 8 4.84 1. 02 4.73 1.04 4 .61 1.06 4.49 1.0 9 4.38 1.11
15 10 5 .00 1.0 2 4.88 1. 05 4.7 6 1.07 4. 65 1.09 4.53 1.11
AFR 14.3
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 3.60 1.63 3.51 1.66 3.42 1.70 3.34 1.73 3.25 1.76
-10 -11 4.2 3 1.75 4.13 1.78 4.0 3 1.82 3.9 3 1.86 3.8 2 1.89
-5 -7 4.84 1.81 4.73 1.85 4.61 1.89 4.50 1.93 4.38 1.96
0 - 2 5 .62 1.8 1 5.49 1.85 5. 36 1.89 5 .22 1. 93 5.0 9 1.96
5 3 6.00 1.60 5. 86 1.63 5.71 1. 67 5.57 1.70 5. 43 1.73
7 6 6.43 1.61 6.2 7 1.64 6 .12 1. 67 5.97 1.71 5.8 1 1.74
10 8 6.69 1.61 6.53 1. 64 6.37 1.67 6.2 1 1.71 6.0 5 1.74
15 10 6.69 1.50 6.53 1.53 6.37 1.56 6.21 1.59 6.05 1.62
AFR 16.0
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 5.04 2.96 4.92 3.02 4.80 3.08 4.68 3.14 4.56 3.21
-10 -11 5.83 2.96 5.69 3.02 5.55 3.09 5.41 3.15 5.27 3.21
-5 -7 6.55 2.96 6.39 3.02 6.24 3.09 6.08 3.15 5.92 3.21
0 -2 6.80 2.41 6.64 2.46 6.47 2.51 6.31 2.56 6.15 2.61
5 3 7.98 2. 48 7.7 9 2. 54 7.6 0 2 .5 9 7. 41 2 .6 4 7. 22 2.6 9
7 6 8.66 2.51 8.46 2.56 8.25 2.61 8.04 2.67 7.84 2.72
10 8 9.05 2.50 8.84 2.56 8.62 2.61 8.40 2.66 8.19 2.71
15 10 8.56 2.05 8.35 2.09 8.15 2.14 7.95 2.18 7.74 2.2 2
AFR 16.0
Indoor temperature
°CDB 16 18 20 22 24
Outdoor temperature
°CDB °CWB TC IP TC IP TC IP TC IP TC IP
-15 -16 5.77 4.00 5.64 4.04 5.50 4.08 5.36 4.08 5.22 4.08
-10 -11 6.62 3.98 6.46 4.02 6.30 4.06 6.14 4.06 5.99 4.06
-5 -7 7.34 3.98 7.17 4.02 6.99 4.06 6.82 4.06 6.64 4.06
0 -2 8.29 3.97 8.10 4.01 7. 90 4.06 7.70 4.06 7.50 4.06
5 3 9.00 3.49 8.79 3.53 8.57 3.56 8.36 3.56 8.14 3.56
7 6 9.14 3.02 8.92 3.05 8.70 3.08 8.48 3.08 8.27 3.08
10 8 9.72 3.04 9.49 3.07 9.26 3.10 9.03 3.10 8.80 3.10
15 10 9.23 2.48 9.01 2.51 8.79 2.53 8.57 2.53 8.35 2.53
Page 13
- (01 - 10) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
FAN PERFORMANCE7.
AIR VELOCITY DISTRIBUTION7-1.
MODEL  :ASTG09LV, ASTG12LV
Note:
Fan speed : HIGH
Operation mode : FAN
3
2
1
0
(m)
(m)
SIDE VIEW VERTICAL FLAP : Downward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0.5
2
1
0
1
2
(m)
(m)
TOP VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0
.5
3
2
1
0
1
2
3
(m)
(m)
TOP VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Right & L eft
Unit : m/s
012345678
2.0
1.0
0.5
2.0
1.0
0.5
3
2
1
0
(m)
(m)
SIDE VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0.5
Page 14
- (01 - 11) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
MODEL  : ASTG18LV
3
2
1
0
(m)
(m)
SIDE VIEW VERTICAL FLAP : Downward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0.5
2
1
0
1
2
(m)
(m)
TOP VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0.5
3
2
1
0
(m)
(m)
SIDE VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0.5
(m)
(m)
TOP VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Right & L eft
Unit : m/s
012345678
2.0
1.0
0.5
2.0
1.0
0.5
3
2
1
0
1
2
3
Page 15
- (01 - 12) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
MODEL  : ASTG22LV
3
2
1
0
(m)
(m)
SIDE VIEW VERTICAL FLAP : Downward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0.5
2
1
0
1
2
(m)
(m)
TOP VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0.5
3
2
1
0
(m)
(m)
SIDE VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Cente r
Unit : m/s
012345678
2.0
1.0
0.5
(m)
(m)
TOP VIEW VERTICAL FLAP : Upward HORIZO NTAL FLAP : Right & L eft
Unit : m/s
012345678
2.0
1.0
0.5
2.0
1.0
0.5
3
2
1
0
1
2
3
Page 16
- (01 - 13) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
AIR FLOW7-2.
MODEL  :ASTG09LV
Cooling
Heating
Fan speed
Number of
rotations
(r.p.m.)
Air flow
HIGH
112 0
790
m3/h
219
l/s
465
CFM
MED
970
660 m3/h
183 l/s
388 CFM
LOW
800
520 m3/h
144 l/s
306 CFM
QUIET
610
350 m3/h
97 l/s
206 CFM
Fan speed
Number of
rotations
(r.p.m.)
Air flow
HIGH
115 0
810
m3/h
225
l/s
477
CFM
MED
990
680 m3/h
189 l/s
400 CFM
LOW
820
540 m3/h
150 l/s
318 CFM
QUIET
610
360 m3/h
100 l/s
212 CFM
Page 17
- (01 - 14) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
MODEL  :ASTG12LV
Cooling
Heating
Fan speed
Number of
rotations
(r.p.m.)
Air flow
HIGH
115 0
810
m3/h
225
l/s
477
CFM
MED
990
680 m3/h
189 l/s
400 CFM
LOW
800
520 m3/h
144 l/s
306 CFM
QUIET
610
360 m3/h
100 l/s
212 CFM
Fan speed
Number of
rotations
(r.p.m.)
Air flow
HIGH
1200
860
m3/h
239
l/s
506
CFM
MED
1020
710 m3/h
197 l/s
418 CFM
LOW
820
540 m3/h
150 l/s
318 CFM
QUIET
610
360 m3/h
100 l/s
212 CFM
Page 18
- (01 - 15) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
MODEL  : ASTG18LV
Cooling
Heating
Fan speed
Number of
rotations
(r.p.m.)
Air flow
HIGH
1320
960
m3/h
267
l/s
565
CFM
MED
110 0
770 m3/h
214 l/s
453 CFM
LOW
960
660 m3/h
183 l/s
389 CFM
QUIET
840
540 m3/h
150 l/s
318 CFM
Fan speed
Number of
rotations
(r.p.m.)
Air flow
HIGH
1320
960
m3/h
267
l/s
565
CFM
MED
115 0
810 m3/h
225 l/s
477 CFM
LOW
1010
700 m3/h
194 l/s
412 CFM
QUIET
810
520 m3/h
144 l/s
306 CFM
Page 19
- (01 - 16) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
MODEL  : ASTG22LV
Cooling
Heating
Fan speed
Number of
rotations
(r.p.m.)
Air flow
HIGH
1400
960
m3/h
267
l/s
565
CFM
MED
114 0
780 m3/h
217 l/s
459 CFM
LOW
1000
650 m3/h
181 l/s
383 CFM
QUIET
860
530 m3/h
147 l/s
312 CFM
Fan speed
Number of
rotations
(r.p.m.)
Air flow
HIGH
1400
960
m3/h
267
l/s
565
CFM
MED
1200
820 m3/h
228 l/s
483 CFM
LOW
1050
710 m3/h
197 l/s
418 CFM
QUIET
860
530 m3/h
147 l/s
312 CFM
Page 20
- (01 - 17) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
OPERATION NOISE8.
NOISE LEVEL CURVE8-1.
MODEL  :ASTG09LV
Cooling
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
㪟㫀㪾㪿
㪨㫌㫀㪼㫋
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
㪟㫀㪾㪿
㪨㫌㫀㪼㫋
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL  :ASTG12LV
Cooling
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
㪟㫀㪾㪿
㪨㫌㫀㪼㫋
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
㪟㫀㪾㪿
㪨㫌㫀㪼㫋
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Page 21
- (01 - 18) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
MODEL  : ASTG18LV
Cooling
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
㪟㫀㪾㪿
㪨㫌㫀㪼㫋
㪟㫀㪾㪿
㪨㫌㫀㪼㫋
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
MODEL  : ASTG22LV
Cooling
Heating
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
High
Quiet
High
Quiet
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Page 22
- (01 - 19) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
SOUND LEVEL CHECK POINT8-2.
Page 23
- (01 - 20) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
ELECTRIC CHARACTERISTICS9.
Model name ASTG09LV ASTG12LV ASTG18LV ASTG22LV
Power supply
Voltage V 240 ~
Frequency Hz 50
Max. operating current A 0.3
Wiring Spec.
Connection cable mm
2
1.5
Limited wiring length m 21
Note : Wiring Spec.
1. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
2. Limited wiring length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 2% or more.
3. Use conformed cable with Type 60245 IEC57.
Page 24
- (01 - 21) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
SAFETY DEVICES10.
Protection form
Model
ASTG09LV ASTG12LV ASTG18LV ASTG22LV
Circuit protection Current fuse (PCB) 250V 3.15A
Terminal protection Current (thermal) fuse 250V 3A
Fan motor protection Thermal protector program
OFF: 150 ± 15 °C
ON: 120 ± 15 °C
Page 25
- (01 - 22) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
EXTERNAL INPUT & OUTPUT11.
Connector INPUT OUTPUT REMARKS
CNA01 Control input -
See external
input/output settings for
details.
CNB01 - Operation status output
CNB02 - Error status output
EXTERNAL INPUT11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit. Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a connector on the external control PC board and turning it ON.
Unit operation Initial starting after turned power on Other than initial starting
Operation mode Auto changeover Mode at previous operation Set temperature 24°C Temperature at previous operation
Air flow mode AUTO Mode at previous operation Up-down air direction (swing) Standard air direction (swing OFF) Air direction at previous operation Left-right air direction (swing) Standard air direction (swing OFF) Air direction at previous operation
Circuit diagram example
indoor unit
control PC board Communication kit Connected unit
Ex.) Switch
Connector
1
3
Signal
Field supply
Optional parts
*10 m
* Make the distance from the PC board to the connected unit within 10m. Contact capacity : 24VDC or more, 10mA or more. Please use the non-polar relays and switches.
When function setting is "Operation/Stop" mode
Operation
Stop
ON
OFF
Input signal
Indoor unit
When function setting is "Forced stop" mode
Remote controller
ON ON ON
Input signal
ON OFF
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control operation invalidity
Parts (Optional)
Parts name Model name
External connect kit UTY-XWZXZ5
Communication kit UTY-TWBXF
* For operating the EXTERNAL function, the Compact wall mounted type requires the communication kit in addition to the wire (UTY-XWZX Z5).
Wire (External input) : UTY-XWZXZ5
Page 26
- (01 - 23) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
EXTERNAL OUTPUT11-2.
OPERATION STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
* Make the distance from the PC board to the connected unit within 10m. Relay spec. : Max.24VDC, 10mA to less than 500mA.
Field supplyOptional parts
Ex.)Display
indoor unit
control PC board Communication kit Connected unit
Ex.)Relay unit
1
2
Signal
Relay power supply
V
Connector
*10 m
24VDC
ON
OFF
Operation
Stop
Indoor unit
Output signal
Parts (Optional)
Parts name
Model name
External connect kit UTY-XWZXZ5
Communication kit UTY-TWBXF
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(UTY-XWZXZ5).
Wire (External output) : UTY-XWZXZ5
Page 27
- (01 - 24) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
ERROR STATUS OUTPUT
An air conditioner error status signal can be output.
Circuit diagram example
* Make the distance from the PC board to the connected unit within 10m. Relay spec. : Max.24VDC, 10mA to less than 500mA.
Field supplyOptional parts
Ex.)Display
indoor unit
control PC board Communication kit Connected unit
Ex.)Relay unit
1
2
Signal
Relay power supply
V
Connector
*10 m
24VDC
ON
OFF
Error
Normal
Error status
Output signal
Parts (Optional)
Parts name
Model name
External connect kit UTY-XWZXZ5
Communication kit UTY-TWBXF
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(UTY-XWZXZ5).
Wire (External output) : UTY-XWZXZ5
Page 28
- (01 - 25) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
FUNCTION SETTING12.
INDOOR UNIT (Setting by remote controller)12-1.
The function settings of the control of the indoor unit can be changed by this procedure according • to the installation conditions. Incorrect settings can cause the indoor unit malfunction.
After the power is turned on, perform the “FUNCTION SETTING” according to the installation • conditions using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value. • Settings will not be changed if invalid numbers or setting values are selected.
PREPARATION
Turn on the power
* By turning on the power indoor units, so make sure the piping air-tight test and vacuuming
have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the power.
FUNCTION SETTING METHOD (for Wireless remote controller)
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP. (
) simultaneously, press the RESET button to enter the function
setting mode.
STEP 1 Setting the remote controller signal code
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) The signal codes that are set through this process are applicable only to the signals in the FUNCTION SETTING. For details on how to set the signal codes through the normal process, refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE.
Press the SET TEMP. (1.
) ( ) button to change the signal code between →
→ Match the code on the display to the air conditioner signal code. (initially
set to
) (If the signal code does not need to be selected, press the MODE button and proceed to STEP 2.)
Press the TIMER MODE button and check that the indoor unit can receive signals 2. at the displayed signal code.
Press the MODE button to accept the signal code, and proceed to STEP 2.3.
The air conditioner signal code is set to A prior to shipment.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes (
→ → → ) until you
find the code which operates the air conditioner.
STEP 2 Selecting the function number and setting value
Press the SET TEMP. (1.
) ( ) buttons to select the function number. (Press the MODE button to switch between the left and right digits.)
Press the FAN button to proceed to setting the value. 2. Press the FAN button again to return to the function number selection.)
Press the SET TEMP. (3.
) ( ) buttons to select the setting value. (Press the MODE button to switch between the left and right digits.)
Press the TIMER MODE button, and START/STOP button, in 4. the order listed to confirm the settings.
Press the RESET button to cancel the function setting mode.5.
After completing the FUNCTION SETTING, be sure to turn 6. off the power and turn it on again.
Function number
Setting value
CAUTION
After turning off the power, wait 10 seconds or more before turning on it again. The FUNCTION SETTING doesn’t become effective if it doesn’t do so.
Page 29
- (01 - 26) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
CONTENTS OF FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in • accordance with the installed condition. After the power is turned on, perform the function setting on the remote control.
The settings may be selected between the following two: Function number or setting value. • Settings will not be changed if invalid numbers or setting values are selected.
Functions
1) Filter sign
2) Cooler room temperature correction
3) Heater room temperature correction
4) Auto restart
5) Indoor room temperature sensor switching function
6) Remote controller signal code
7) External input control
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room. If you do not wish the filter sign to be displayed, select the setting value for "No indication".
(... Factory setting)
Setting description Function number Setting value
Standard
11
00 Long interval 01 Short interval 02
No indication 03
Setting description Filter sign interval time
Standard 400 hours Long interval 1000 hours Short interval 200 hours
2) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.
(... Factory setting)
Setting description Function number Setting value
Standard
30
00
Slightly lower control 01
Lower control 02
Warmer control 03
3) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction. The settings may be changed as shown in the table below.
(... Factory setting)
Setting description Function number Setting value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
Page 30
- (01 - 27) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
4) Auto restart
Enable or disable automatic system restart after a power outage.
(... Factory setting)
Setting description Function number Setting value
Yes
40
00
No 01
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation. Be sure to operate by the control unit, or external input device.
5) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
(... Factory setting)
Setting description Function number Setting value
No
42
00
Yes 01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
6) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(... Factory setting)
Setting description Function number Setting value
A
44
00 B01 C02 D03
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(... Factory setting)
Setting description Function number Setting value
Operation/Stop mode
46
00
(Setting forbidden) 01
Forced stop mode 02
Page 31
- (01 - 28) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
REMOTE CONTROLLER SIGNAL CODE SETTING
Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has
not been set for the signal code.)
Press the START/STOP button until only the clock is displayed on the remote 1. controller display.
Press the MODE button for at least five seconds to display the current signal code 2. (initially set to
).
Press the SET TEMP. (3.
) ( ) button to change the signal code between →
→ .
Match the code on the display to the air conditioner signal code.
Press the MODE button again to return to the clock display. The signal code will 4. be changed.
If no buttons are pressed within 30 seconds after the signal code is displayed, the system returns to the original clock display. In this case, start again from step 1.
The air conditioner signal code is set to A prior to shipment. Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a signal code other than signal code A, reset the signal code after replacing the batteries. If you do not know the air conditioner signal code setting, try each of the signal codes (
→ → → ) until you find the code which
operates the air conditioner.
Page 32
- (01 - 29) -
WALL MOUNTED TYPE
ASTG09-22LV
WALL MOUNTED TYPE
ASTG09-22LV
OPTIONAL PARTS13.
CONTROLLER13-1.
OTHERS13-2.
Exterior Parts name Model No. Summary
Wired remote
controller
UTY-RNNYN
Unit control is performed by wired remote controller.
*Optional communication kit is
necessary for the installation.
Simple remote
controller
UTY-RSNYN
Unit control is performed by simple remote controller.
*Optional communication kit is
necessary for the installation.
Exterior Parts name Model No. Summary
Communication
kit
UTY-TWBXF
Use to connect with optional devices and air conditioner PC board.
( x 1 )
( x 2 )
External
connect kit
UTY-XWZXZ5
Required when external device is connected.
*Optional communication kit is
necessary for the installation.
Page 33
2. OUTDOOR UNIT
SINGLE TYPE :
AOTG09LVCC
AOTG12LVCC AOTG18LVCC
AOTG22LVCC
DTR_AO112E_02
2012.06.20
Page 34
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
CONTENTS
2. OUTDOOR UNIT
1. SPECIFICATIONS
........................................................................................ 02 - 01
2. DIMENSIONS
................................................................................................... 02 - 02
3. REFRIGERANT CIRCUIT
....................................................................... 02 - 06
4. WIRING DIAGRAMS
.................................................................................. 02 - 10
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
.............................................................. 02 - 13
6. ADDITIONAL CHARGE CALCULATION
................................... 02 - 17
7. AIR FLOW
.......................................................................................................... 02 - 18
8. OPERATION NOISE
................................................................................... 02 - 20
8-1. NOISE LEVEL CURVE
............................................................................... 02 - 20
8-2. SOUND LEVEL CHECK POINT
............................................................... 02 - 22
9. ELECTRIC CHARACTERISTICS
..................................................... 02 - 23
10. SAFETY DEVICES
....................................................................................... 02 - 24
11. OPTIONAL PARTS
...................................................................................... 02 - 25
Page 35
- (02 - 01) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
SPECIFICATIONS1.
Typ e INVERTER HEAT PUMP Model name AOTG09LVCC AOTG12LVCC AOTG18LVCC AOTG22LVCC Power source 240V ~ 50Hz Available voltage range 198V - 264V ~ 50Hz Starting current A 3.5 5.0 6.5 8.5
Fan
Airflow rate
Cooling
I/s
(m
3
/h)
475 (1,710) 539 (1,940) 654 (2,355) 683 (2,460)
Heating 461 (1,660) 472 (1,700) 654 (2,355) 650 (2,340) Type × Q'ty Propeller fan×1 Motor output W 23 50 115 115
Sound pressure level
Cooling
dB (A)
47 48 52 5 5
Heating 47 48 53 56
Sound power level 64 66 69 72
Heat exchanger type
Dimensions
(H × W × D)
mm
504×642×36.4 504×896×36.4 588×881×36.4
Main : 588×881×36.4
Sub : 546×580×18.2
Fin pitch 1.4 1.3 1.45
Rows × Stages 2×24 2×28
Main : 2×28
Sub : 1×26
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminum) Surface treatment Corrosion resistance (Blue fin)
Compressor
Type × Q'ty Rotary×1 Motor output W 500 750 1,000 1,000
Refrigerant
Typ e R410 A
Charge g 850 1,050 1,450 1,550
Refrigerant oil Type POE
Enclosure
Material Steel
Colour
BEIGE
Approximate colour of MUNSELL 10YR7.5/1.0
Dimensions (H × W × D)
Net
mm
540×660×290 540×790×290 620×790×290 620×790×290
Gross 610×807×395 633×945×395 713×945×395 713×945×395
Weight
Net
kg
25 34 37 40
Gross 28 37 41 43
Connection pipe
Size
Liquid
mm
Ø6.35
Gas Ø9.52 Ø12.70 Ø15.88 Method Flare Pre-charge length
m
15 Max. length 20 Max. height difference 15
Operation range
Cooling
°C
10 to 46
Heating -15 to 24
International Protection rating IPX4
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB / 24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB / 6 °CWB. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) * The protective function might work when using it outside the temperature range mentioned above.
Page 36
- (02 - 02) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
DIMENSIONS2.
MODEL  :AOTG09LV
(Unit : mm)
INSTALLATION PLACE
(Unit : mm)
135
110
175
454
352
20 660 68
10 290 18
20
9
540
320
Top view
Front view
Bottom view
Side view
Side view
Air flow
38
Drain port (Ø20)
330
If the space is larger that is stated, the condition will be the same as that are no obstacles.
• Height above the floor level should be 50 mm or over.
600 or more
100 or more
200 or more
100 or more
250 or more
(Service space)
Page 37
- (02 - 03) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  :AOTG12LV
(Unit : mm)
INSTALLATION PLACE
(Unit : mm)
790
290
352
6820
10 18
Top view
540
320
209
Side view
Side view
Front view
Air flow
175
110
9
20
540
4-ø11.3mm
hole
Bottom view
45.4
Drain port (Ø20)
395
If the space is larger that is stated, the condition will be the same as that are no obstacles.
• Height above the floor level should be 50 mm or over.
600 or more
100 or more
200 or more
100 or more
250 or more
(Service space)
Page 38
- (02 - 04) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  : AOTG18LV, AOTG22LV
(Unit : mm)
100
35
328
28
Drain port Ø20(Drain pipe)Drain port 3-Ø20(Drain cap)
28
Air flow
Bottom view
790
Top view
Front view
Bottom view
Air flow
Side viewSide view
23
62
290
18
20
2045.4
9
110
620
320
540
209
4-Ø11.3mm hole
Drain port Ø20
352
175
395
AOTG18LV
AOTG22LV
Page 39
- (02 - 05) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
INSTALLATION PLACE
(Unit : mm)
If the space is larger that is stated, the condition will be the same as that are no obstacles.
• Height above the floor level should be 50 mm or over.
600 or more
100 or more
200 or more
100 or more
250 or more
(Service space)
Page 40
- (02 - 06) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
REFRIGERANT CIRCUIT3.
MODEL  :AOTG09LV
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8" (9.52 mm)
Cooling Heating
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger Sub heat exchanger
( INDOOR )
Heat exchanger ( OUTDOOR )
Compressor
Page 41
- (02 - 07) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  :AOTG12LV
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8" (9.52 mm)
Cooling Heating
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger Sub heat exchanger
( INDOOR )
Heat exchanger ( OUTDOOR )
Compressor
Muffler
Page 42
- (02 - 08) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  : AOTG18LV
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 1/2" (12.70 mm)
Cooling Heating
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger Sub heat exchanger
( INDOOR )
Heat exchanger ( OUTDOOR )
Compressor
Muffler
Page 43
- (02 - 09) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  :AOTG22LV
Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 5/8" (15.88 mm)
Cooling Heating
2-Way
valve
Strainer
Strainer
3-Way
valve
Muffler
4-Way valve
Expansion valve
Heat exchanger
( INDOOR )
Sub heat exchanger
Heat exchanger
( OUTDOOR )
Compressor
Muffler
Sub heat exchanger
Page 44
- (02 - 10) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
WIRING DIAGRAMS4.
MODEL  :AOTG09LV
Page 45
- (02 - 11) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  :AOTG12LV
Page 46
- (02 - 12) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  : AOTG18LV, AOTG22LV
Page 47
- (02 - 13) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
CAPACITY COMPENSATION RATE FOR PIPE LENGTH 5.
AND HEIGHT DIFFERENCE
MODEL  : AOTG09LV
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
57.5101520
Height
difference H
(m)
1
Indoor unit is
upper than
outdoor unit.
15 - - - 0.888 0.873
10 - - 0.959 0.888 0.873
7.5 - 1.000 0.959 0.888 0.873
5 1.035 1.000 0.959 0.888 0.873
0 1.035 1.000 0.959 0.888 0.873
2
Indoor unit is
under than
outdoor unit.
-5 1.030 0.995 0.954 0.883 0.869
-7.5 - 0.993 0.952 0.881 0.866
-10 - - 0.950 0.879 0.864
-15 - - - 0.870 0.856
COOLING
Pipe length (m)
57.5101520
Height
difference H
(m)
1
Indoor unit is
upper than
outdoor unit.
15 - - - 0.902 0.910
10 - - 0.963 0.917 0.925
7.5 - 0.988 0.967 0.921 0.929
5 1.009 0.992 0.971 0.924 0.932
0 1.018 1.000 0.979 0.932 0.940
2
Indoor unit is
under than
outdoor unit.
-5 1.018 1.000 0.979 0.932 0.940
-7.5 - 1.000 0.979 0.932 0.940
-10 - - 0.979 0.932 0.940
-15 - - - 0.932 0.940
Page 48
- (02 - 14) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  :AOTG12LV
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
57.5101520
Height
difference H
(m)
1
Indoor unit is
upper than
outdoor unit.
15 - - - 0.955 0.934
10 - - 0.998 0.955 0.934
7.5 - 1.000 0.998 0.955 0.934
5 0.991 1.000 0.998 0.955 0.934
0 0.991 1.000 0.998 0.955 0.934
2
Indoor unit is
under than
outdoor unit.
-5 0.986 0.995 0.993 0.951 0.930
-7.5 - 0.993 0.991 0.948 0.927
-10 - - 0.988 0.946 0.925
-15 - - - 0.936 0.916
COOLING
Pipe length (m)
57.5101520
Height
difference H
(m)
1
Indoor unit is
upper than
outdoor unit.
15 - - - 0.894 0.895
10 - - 0.961 0.909 0.910
7.5 - 0.988 0.965 0.912 0.914
5 1.014 0.992 0.969 0.916 0.918
0 1.023 1.000 0.976 0.923 0.925
2
Indoor unit is
under than
outdoor unit.
-5 1.023 1.000 0.976 0.923 0.925
-7.5 - 1.000 0.976 0.923 0.925
-10 - - 0.976 0.923 0.925
-15 - - - 0.923 0.925
Page 49
- (02 - 15) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  : AOTG18LV
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
57.5101520
Height
difference H
(m)
1
Indoor unit is
upper than
outdoor unit.
15 - - - 0.994 0.979
10 - - 1.012 0.994 0.979
7.5 - 1.000 1.012 0.994 0.979
5 0.969 1.000 1.012 0.994 0.979
0 0.969 1.000 1.012 0.994 0.979
2
Indoor unit is
under than
outdoor unit.
-5 0.964 0.995 1.007 0.989 0.974
-7.5 - 0.993 1.004 0.986 0.972
-10 - - 1.002 0.984 0.969
-15 - - - 0.974 0.959
COOLING
Pipe length (m)
57.5101520
Height
difference H
(m)
1
Indoor unit is
upper than
outdoor unit.
15 - - - 0.951 0.950
10 - - 0.979 0.967 0.966
7.5 - 0.988 0.983 0.971 0.970
5 0.994 0.992 0.987 0.975 0.974
0 1.002 1.000 0.995 0.983 0.982
2
Indoor unit is
under than
outdoor unit.
-5 1.002 1.000 0.995 0.983 0.982
-7.5 - 1.000 0.995 0.983 0.982
-10 - - 0.995 0.983 0.982
-15 - - - 0.983 0.982
Page 50
- (02 - 16) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  :AOTG22LV
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
57.5101520
Height
difference H
(m)
1
Indoor unit is
upper than
outdoor unit.
15 - - - 0.974 0.955
10 - - 0.997 0.974 0.955
7.5 - 1.000 0.997 0.974 0.955
5 0.995 1.000 0.997 0.974 0.955
0 0.995 1.000 0.997 0.974 0.955
2
Indoor unit is
under than
outdoor unit.
-5 0.990 0.995 0.992 0.969 0.950
-7.5 - 0.993 0.990 0.966 0.948
-10 - - 0.987 0.964 0.945
-15 - - - 0.954 0.936
COOLING
Pipe length (m)
57.5101520
Height
difference H
(m)
1
Indoor unit is
upper than
outdoor unit.
15 - - - 0.946 0.953
10 - - 0.977 0.962 0.968
7.5 - 0.988 0.981 0.966 0.972
5 0.998 0.992 0.985 0.970 0.976
0 1.006 1.000 0.993 0.977 0.984
2
Indoor unit is
under than
outdoor unit.
-5 1.006 1.000 0.993 0.977 0.984
-7.5 - 1.000 0.993 0.977 0.984
-10 - - 0.993 0.977 0.984
-15 - - - 0.977 0.984
Page 51
- (02 - 17) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
ADDITIONAL CHARGE CALCULATION6.
MODEL  :AOTG09LV
Refrigerant charge
MODEL  :AOTG12LV
Refrigerant charge
MODEL  : AOTG18LV
Refrigerant charge
MODEL  :AOTG22LV
Refrigerant charge
Refrigerant type R410A
Refrigerant amount g 850
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 1050
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 1450
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 1550
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Page 52
- (02 - 18) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
AIR FLOW7.
MODEL  :AOTG09LV
Cooling
Heating
MODEL  :AOTG12LV
Cooling
Heating
Number of
rotations
(r.p.m.)
Air flow
780
1710 m
3
/h
475
l/s
1006
CFM
Number of
rotations
(r.p.m.)
Air flow
760
1660 m
3
/h
461 l/s
977 CFM
Number of
rotations
(r.p.m.)
Air flow
850
1940 m
3
/h
539 l/s
1142 C FM
Number of
rotations
(r.p.m.)
Air flow
750
170 0 m
3
/h
472 l/s
1001 CFM
Page 53
- (02 - 19) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  : AOTG18LV
Cooling
Heating
MODEL  :AOTG22LV
Cooling
Heating
Number of
rotations
(r.p.m.)
Air flow
1000
2355 m
3
/h
654
l/s
138 6
CFM
Number of
rotations
(r.p.m.)
Air flow
1000
2355 m
3
/h
654 l/s
138 6 CFM
Number of
rotations
(r.p.m.)
Air flow
110 0
2460 m
3
/h
683 l/s
1448 CFM
Number of
rotations
(r.p.m.)
Air flow
1050
2340 m
3
/h
650 l/s
1377 CFM
Page 54
- (02 - 20) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
OPERATION NOISE8.
NOISE LEVEL CURVE8-1.
MODEL  :AOTG09LV
Cooling
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
MODEL  :AOTG12LV
Cooling
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Page 55
- (02 - 21) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
MODEL  : AOTG18LV
Cooling
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Heating
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Octave ba nd sound press ure level, dB:(0d B=0.000 2μbar)
Octave band center frequency,Hz
80
70
60
50
40
30
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
MODEL  :AOTG22LV
Cooling
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
Page 56
- (02 - 22) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
SOUND LEVEL CHECK POINT8-2.
Page 57
- (02 - 23) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
ELECTRIC CHARACTERISTICS9.
Model name AOTG09LV AOTG12LV AOTG18LV AOTG22LV
Power supply
Voltage V 240 ~
Frequency Hz 50
*1) Max operating current A 7.5 9.0 13.5 17.5
Starting Current A 3.5 5.0 6.5 8.5
*2) Wiring spec.
Main Fuse (Circuit breaker) Current
A10 16 20
Power Cable mm
2
1.5 2.5 4.0
*3) Limited wiring length m 21 17 19 24
Use conformed cable with Type245 IEC57.
*1) The maximum current is the total current of indoor unit and outdoor unit.
*2)Wiring spec. : Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*3) Limited wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
Page 58
- (02 - 24) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
SAFETY DEVICES10.
Protection form
Model
AOTG09LV AOTG12LV AOTG18LV AOTG22LV
Circuit protection
Current fuse (NEAR THE TERMINAL)
-
Current fuse (MAIN PRINTED CIRCUIT BOARD)
250V 20A
250V 5A
Fan motor protection
Thermal protection program
OFF: 150 ± 20 °C
ON: 120 ± 20 °C
OFF: 100 ± 10 °C
ON: 95 ± 10 °C
Compressor protection
Thermal protection program (DISCHARGE TEMP.)
OFF : 110°C
ON : After 7 minutes
Page 59
- (02 - 25) -
OUTDOOR UNIT
AOTG09 -22LV
OUTDOOR UNIT
AOTG09 -22LV
OPTIONAL PARTS11.
Exterior Parts name Model No. Summary
Demand control
option PCB
UTY-XCZZ2
Cooling and heating operations of air conditioners are limited by the external input.