15. Optional parts ........................................................................................85
Page 5
Part 1. INDOOR UNIT
WALL MOUNTED TYPE:
ASU30RLE
Page 6
WALL MOUNTED
1. Product features
Implemented core technology provides easy-to-use product operations that realize a comfortable
ASU30RLE
space.
1-1. Model lineup
ASU30RLEAOU30RLXEH
1-2. Features
High energy performance
Seasonal Energy Efficiency Ratio (SEER)
Heating Seasonal Performance Factor (HSPF)11.8
Coefficient Of Performance (COP)11.7
Energy Efficiency Ratio (EER)12.5
MODEL
ASU30RLE
18.7
Btu/hW
*Measurement conditions: ANSI/ASHRAE Standard 37-1988
Powerful heating operation and high performance heating
These systems can deliver 100% of rated heating capacity at 5°F (-15°C) and operate down to
-15°F (-26°C), so stay more comfortable at low ambient temperature than previous.
(%)
Rated heating
capacity
Temperature
Keep
100% operation
5°F (-15°C) -15°F (-26°C) (°F (°C))
75°F (24°C)
5°F (-15°C)
0°F (-18°C)
-15°F (-26°C)
Previous
18model
Previous
24model
New
30 model
Base heater
• Equipped with a base heater that provides powerful heating even at extra low outdoor
temperature. (Prevents the exhaust water from freezing.)
• The cultivated base design discharges the melted water out of many water discharge holes.
Base freezing prevention
Base heater
Drain hole
base heater
- 2 -
Without
With
base heater
Page 7
Set temperature control by 1 °F possible
Temperature setting by 1 degree in Fahrenheit or by 0.5 degree in Celsius possible.
Energy saving control by using human sensor
Implemented human sensor detects the presence or absence of human in a room by sensing
movement of occupants, and suppress both of the air conditioner operation and energy consumption.
Human sensor
Corresponding to server room air conditioning
Cooling operation can be performed even in the low outdoor temperature and low humidity environment. In addition, the following interlock operation is possible by connecting 2 indoor units
with a cable.
WALL MOUNTED
ASU30RLE
Output error
• Alternative operation: 2 units operate alternately.
• Backup operation: In case one unit breaks down, the
other unit starts operation automatically.
• Supporting operation: Both units operate simultaneously
when the loaded capacity is not enough with one unit.
• Server room control can be set at site.
- 3 -
Page 8
WALL MOUNTED
On
Primary unit
Secondary unit
Off
On
Off
Off timer expired
On timer expired
1-3. Details of server room control
By activating server room control using function setting 96, this product maintains a room at constant
ASU30RLE
temperature.
Available operations
When server room control is activated by changing the setting on function setting 96, this product
maintains the room temperature constant by performing 3 types of operations automatically according to the room temperature conditions.
While this function is activated, contents of operation is fixed as follows:
Operation modeSet temperatureAirflow mode
COOL76°F (24°C)*HIGH
*: Set temperature correction (±8°F [4°C]) is possible by switching the setting value on function setting 30. For the setting details, refer to “Room temperature control for indoor unit sensor” in “Con-
tents of function setting” on page 48.
• Alternative operation
Controls the units operations by using the weekly timer of the primary unit.
When the weekly timer is activated and the primary unit operation is turned off, the secondary unit
starts operation simultaneously.
Also, when the weekly timer is activated and the primary unit operation is turned on, the secondary unit stops operation simultaneously.
• Backup operation
Regardless of the primary-secondary relation of the unit, if an error occurred on one unit, operation start indication is issued to another unit and the unit starts backup operation.
Error occurred
On
Indoor unit A
Off
On
Indoor unit B
Off
- 4 -
Page 9
• Supporting operation
On
Indoor unit A
Indoor unit B
Off
On
Off
Set point non-attainment
*: Operaion is started even when the unit is stopped by the weekly timer.
When the room temperature does not reach to the set point after a certain period of time, regardless of the primary-secondary relation of the unit, operation start indication is issued to another
unit and both indoor units perform air conditioning simultaneously.
Supporting operation: On
Ts + 5°F (2.5 °C)
Ts + 1°F (0.5 °C)
Supporting operation: Off
WALL MOUNTED
ASU30RLE
NOTE: While performing this function, following functions cannot be used:
• Operation modes other than cooling
• Airflow modes other than HIGH
• Temperature setting other than 76°F (24°C)
• POWERFUL mode
• MIN. HEAT operation
• ECONOMY operation
• On/off timer, program timer, and SLEEP timer
• Weekly timer on secondary unit
• Human sensor function
• Shutdown operation
• Starting operation on secondary unit
To stop the operation, shutdown the power supply.
- 5 -
Page 10
WALL MOUNTED
!
CAUTION
1
2
3
4
5
6
ASU30RLE
Precautions on unit installation
• Do not place any other electrical products or household belongings under the product. Condensation dripping from the product might get them wet, and may cause damage or malfunction to
the property.
• In units installation facing each other, the vertical airflow direction louver on each indoor unit
should be set at a position from 3 to 6.
• Do not connect any wired remote controller.
To perform server room control, mind the followings:
• Additional cable connecting between 2 indoor units needs to be purchased locally.
• DIP switch on the indoor unit main PC board needs to be switched to “3WIRE”.
• Setting of function setting 30 “Room temperature control for indoor unit sensor” on each indoor
unit needs to be same. For contents of the function setting 30, refer to “Room temperature control
for indoor unit sensor” in “Contents of function setting” on page 48.
• Setting change on function setting 96 required. For contents of the function setting 96, refer to
“Server room control” in “Contents of function setting” on page 48.
- 6 -
Page 11
Initial setup for server room control
Function setting procedure
Before activating server room control, assignment of primary unit and secondary unit is required.
Change the setting of function setting 96 as follows:
1. Turn on the power source of 2 indoor units.
2. Set one of the indoor unit as “Primary unit” (Setting value: 01) by function setting 96. (For
contents of function setting 96, refer to “Server room control” in “Contents of function setting”
on page 48.)
When performing the setting, operate the remote controller close to the signal receiver on the
primary unit as possible so that the signal transmission is firmly received by the primary unit
only.
3. Set the other unit as “Secondary unit” (Setting value: 02) by function setting 96.
When performing the setting, operate the remote controller close to the signal receiver on the
secondary unit as possible so that the signal transmission is firmly received by the secondary
unit only.
4. Turn off the power supply of the 2 indoor units.
Starting units operation
After the setting change on function setting 96 is completed, do as follows:
1. After 30 seconds or more since the power source is turned off, turn of the power source of the
secondary unit.
2. Turn on the power source of the primary unit.
3. Press the MANUAL AUTO button on the primary unit for more than 3 seconds.
You will hear a short beep, and the primary unit starts operation.
WALL MOUNTED
ASU30RLE
NOTE: While performing these steps, error indications will be lit on the unit. Nevertheless,
continue the procedure.
Starting server room control
Set the weekly timer on the primary unit.
Server room control is activated, and the unit will start the alternative operation.
NOTE: If the alternative operation does not start or error indications on the unit are still lit, reconfirm whether the settings on function setting 96 are set correctly, and perform the setup procedures from the beginning.
As for the display pattern of the error indications of the indoor unit, refer to the installation manual.
- 7 -
Page 12
WALL MOUNTED
30 min
60 min
90 min
Timer setting
2°F (1°C)
4°F (2°C)
6°F (3°C)
8°F (4°C)
2. Remote controller
ASU30RLE
2-1. Wireless remote controller
Features
• Temperature setting by 1 °F or by 0.5 °C possible.
NOTE: When performing server room control, only the weekly timer
is effective.
• Easy operation.
• Easy to change custom code (max. 4 custom code).
• Can be used jointly with wired remote controllers.
NOTE: When performing server room control, wired remote controller cannot be connected.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Weekly timer
Weekly timer can be easily set by wireless remote controller.
On and off can be set up to 4 times in a day, and up to 28 times in a week.
Program timer
The program timer operates the on and off timer once within a 24-hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to
the time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/Dry operation
When the sleep timer is set, the set temperature
automatically rises 2 °F (1 °C) every hour. The
set temperature can rise up to a maximum of 4 °F
(2 °C).
Timer setting
60 min
Heating operation
When the sleep timer is set, the set temperature
automatically drops 2 °F (1 °C) every 30 minutes.
The set temperature can drop to a maximum of 8
°F (4 °C).
2 °F (1 °C)
4 °F (2 °C)
- 8 -
Page 13
Switching remote controller custom code
Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.)
After code change
Mixed-up
I.U. I.U. I.U. I.U.
AB CD
I.U. I.U. I.U. I.U.
ABCD
* I.U.: Indoor unit
Temperature unit switchable
Easy to change the temperature unit between °F and °C by button operation.
WALL MOUNTED
ASU30RLE
- 9 -
Page 14
WALL MOUNTED
Signal
transmitter
MIN. HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
OUTDOOR UNIT
LOW NOISE button
SWING button
SET button
WEEKLY button
ON/OFF button
SLEEP button
MODE button
SENSOR button
FAN button
TEST RUN
button
RESET
button
CLOCK ADJUST
button
ECONOMY button
Mode indicator
ENERGY SAVING mode
indicator
LOW NOISE mode
indicator
Turns on when
the SENSOR button is operated.
Clock and Timer indicator
SEND indicator
Temperature indicator
Fan speed indicator
Swing indicator
Transmit indicator
Overview
ASU30RLE
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in
actual operation, however, the display will only show those indicators appropriate to the current operation.
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) /67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) /59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) /43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Wall mounted
Inverter heat pump
WALL MOUNTED
ASU30RLE
- 13 -
Page 18
WALL MOUNTED
Unit: in (mm)
Outline of unit
20-1/2 (520)
3-9/16 (90)
13/16 (21)
2-1/2 (64)
18-7/8 (479)2-6/16 (61)
4-1/4
(108)19-6/8 (502)
20-1/2 (520)
1-15/16
(50)
7/16 (11)
13-6/16 (340)
ø80
ø80
13-6/16
(340)
11 (280)
10/16
(16)
45-1/4 (1150)
24 (609)
26-7/16 (672)
28-9/16 (725)
45-1/4 (1150)
4. Dimensions
ASU30RLE
4-1. Model: ASU30RLE
- 14 -
Page 19
Installation space requirement
2-1/2 (63)
or more
3-8/1 (80)
or more
1-15/16 (50)
or more
1-15/16 (49)
or more
2-6/16 (60)
or more
Outline of unit
5-1/8 (130)
or more
59-1/16 (1,500) or more
70-7/8 (1,800) or more
Unit: in (mm)
Provide sufficient installation space for product safety.
WALL MOUNTED
ASU30RLE
- 15 -
Page 20
WALL MOUNTED
5. Wiring diagrams
ASU30RLE
5-1. Model: ASU30RLE
- 16 -
Page 21
6. Capacity table
Outdoor temperature
Outdoor temperature
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)
With using external input function, some functions on this product can be controlled from an external
device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
• The wire connection should be separate from the power cable line.
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit connectors.
Connected unit
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
PCB
Connector
(CN2)
- 25 -
Page 30
WALL MOUNTED
1
2
3
Input 1
PCB
Connected unit
*
+
-
1
2
3
Input 2
*
+
-
Connector
(CN313)
Connector
(CN314)
1
2
3
Input 1
Power supply
PCB
Connected unit
*
*
*2
+-
1
2
3
Input 2
Connector
(CN313)
Connector
(CN314)
ASU30RLE
External input and output PCB
The indoor unit Operation/Stop can be set by using the input connector on the PCB.
Input select
Use either one of these types of connectors according to the application. (Both types of connectors cannot be used simultaneously.)
•Dry contact
In case of internal power supply, set the slide switch of SW301 to "NON VOL" side.
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
• Apply voltage
In case of external power supply, set the slide switch of SW301 to "VOL" side.
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
*2: Make the power supply DC 12 to 24 V, 10 mA or more.
- 26 -
Page 31
10-2. External output
1
2
Connector
(CN3)
LED
PCB
Resistor
Connected unit
+
-
1
2
Connected device
Connector
(CN3)
PCBConnected unitRelay
(Operation status)
-
+
Use an external output cable with appropriate external dimension, depending on the number of cables to be installed.
Indoor unit
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m).
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 29.
When indicator or other components are connected directly
Example: Function setting 60 is set to "00"
WALL MOUNTED
ASU30RLE
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
- 27 -
Page 32
WALL MOUNTED
1
2
Connector
(CN310)
LED 1
(Operation status)
PCB
Resistor
Connected unit
+
-
1
2
Connector
(CN311)
LED 2
(Error status)
Resistor
+
-
1
2
Connector
(CN312)
LED 3
(Indoor unit fan
operation status)
Resistor
+
-
1
2
Connected device 1
Connector
(CN310)
PCBConnected unitRelay
(Operation status)
-
+
1
2
Connected device 2
Connector
(CN311)
(Error status)
-
+
1
2
Connected device 3
Connector
(CN312)
(Indoor unit fan
operation status)
-
+
ASU30RLE
External input and output PCB
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m).
• Output voltage: High DC 12 V±2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to Chapter 10. "Combination of external input and output" on page 29.
When indicator or other components are connected directly
Example: Function setting 60 is set to "00".
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00".
- 28 -
Page 33
10-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External input
and output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
External input
Mode
0-160—001
0-260-002
160-013
260-024
360-035
460-046
560-057
660-068
760-079
860-08A
960-09B
1060-10C
116 0 - 11D
1260-12D
Function
setting
Rotary
SW
Indoor unitExternal input and output PCB
CN2
Operation/Stop
(Function setting 46-00)
or
Emergency stop
(Function setting 46-01)
or
Forced stop
(Function setting 46-02)
Forced thermostat
Mechanical cooling
Forced thermostat
Mechanical cooling
Mechanical cooling
Forced thermostat
Forced thermostat
Mechanical cooling
Forced thermostat
Forced thermostat
Forced thermostat
Forced thermostat
Forced thermostat
1
CN313
Operation/StopNot available
OperationStop
Off
Off
Off
On
On
Off
Off
Off
Off
Off
Off
Off
Off
2
CN314
Not available
WALL MOUNTED
ASU30RLE
External output
Mode
0-160-001Operation/StopOperation/StopError status
0-260-002Operation/StopError status
160-013
260-024
360-035
460-046
560-057
660-068Operation/StopError status
760-079
Function
setting
Rotary
SW
Indoor unitExternal input and output PCB
CN3
Cooling
thermostat On
Cooling
thermostat On
Cooling
thermostat On
Cooling
thermostat On
Heating
thermostat On
Cooling
thermostat On
1
CN310
Error status
Error status
Cooling high/low
output
Error status
Error status
Error status
operation status
operation status
controller output
controller output
controller output
operation status
operation status
2
CN311
Indoor unit fan
Indoor unit fan
Remote
Remote
Remote
Indoor unit fan
Indoor unit fan
Heating
thermostat On
3
CN312
Indoor unit fan
operation status
External heater
output
External heater
output
External heater
output
External heater
output
Cooling high/low
output
External heater
output
Heating
thermostat On
External heater
output
- 29 -
Page 34
WALL MOUNTED
Edge
ASU30RLE
External output
Mode
860-08A
960-09BError statusOperation/Stop
1060-10C
116 0 - 11D
1260-12D
Function
setting
Rotary
SW
Indoor unitExternal input and output PCB
CN3
Cooling
thermostat On
Indoor unit fan
operation status
External heater
output
Set point
attainment
status
1
CN310
Heating
thermostat On
Operation/StopError status
Operation/Stop
Operation/Stop
controller output
operation status
operation status
operation status
2
CN311
Remote
Indoor unit fan
Indoor unit fan
Indoor unit fan
NOTE: Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (R.C. enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (R.C. disabled)
3
CN312
External heater
output
External heater
output
External heater
output
Error status
Error status
Input signal type
• Indoor unit
Input signal type is only "Edge".
• External input and output PCB
The input signal type can be selected.
Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and
output PCB.
Edge
The width of pulse must be longer than 200 msec.
Pulse
- 30 -
Page 35
10-4. Details of function
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
CN313
CN314
Control input function
When function setting is "Operation/Stop" mode 1
• In the case of "Edge" input
Rotary SW on
External input and
output PCB
-Input of indoor unitCN2
60-00 / 1
On
Off
Operation
Stop
External input and
External inputInput signal Command
output PCB
CN313
On
Mode
0-146-00
Function
setting /
CN313
Indoor unit
Remote controller
Off → OnOperation
On → OffStop
Off → OnOperation
On → OffStop
WALL MOUNTED
ASU30RLE
• In the case of "Pulse" input
Mode
0-146-0060-00 / 1
Function
setting /
Rotary SW on
External input and
output PCB
External inputInput signal Command
External input and
output PCB
CN313PulseOperation
CN314PulseStop
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
• This function is invalid when function setting 96 is set to “02” (Secondary unit).
- 31 -
Page 36
WALL MOUNTED
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
CN313
CN314
OnOnOn
Indoorunit
ASU30RLE
When function setting is "Forced stop" mode
• In the case of "Edge" input
Rotary SW on
External input and
External inputInput signal Command
output PCB
-Input of indoor unitCN2
60-00 / 1
External input and
output PCB
CN313
Mode
0-146-02
Function
setting /
Off → On
Forced
stop
On → OffNormal
Off → On
Forced
stop
On → OffNormal
CN313
Forced stop
Indoor unit
Remote controller
• In the case of "Pulse" input
Mode
Function
setting /
0-146-0260-00 / 1
Rotary SW on
External input and
output PCB
On
Off
Normal
Operation
Stop
On
External inputInput signal Command
External input and
output PCB
OnOn
CN313Pulse
Forced
stop
CN314PulseNormal
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the remote
• When forced stop function is used with forming a remote controller group, connect the same
• This function is invalid when function setting 96 is set to “02” (Secondary unit).
controller is restricted.
equipment to each indoor unit within the group.
- 32 -
Page 37
When function setting is "Operation/Stop" mode 2
On
CN313
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote contoller
OnOnOff
• In the case of "Edge" input
Rotary SW on
External input and
External inputInput signal Command
output PCB
-Input of indoor unitCN2
60-00 / 1
External input and
output PCB
CN313
Off → OnOperation
On → Off
Off → OnOperation
On → Off
Mode
0-146-03
Function
setting /
Stop (R.C.
disabled)
Stop (R.C.
disabled)
WALL MOUNTED
ASU30RLE
• In the case of "Pulse" input
Mode
Function
setting /
0-146-0360-00 / 1
CN313
CN314
Indoor unit
Remote controller
Operation
(R.C. disabled)
Rotary SW on
External input and
output PCB
On
Off
On
Off
Stop
External inputInput signal Command
External input and
output PCB
CN313PulseOperation
CN314Pulse
On
Off
Stop (R.C.
disabled)
On
NOTES:
• When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect
the same equipment to each indoor unit within the group.
• This function is invalid when function setting 96 is set to “02” (Secondary unit).
- 33 -
Page 38
Forced thermostat off function
On
Off
On
Off
Compressor
Room temp.
Set temp.
Input
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
82˚F
(28˚C)
75˚F
(24˚C)
82˚F
(28˚C)
88˚F
(31˚C)
Cooling operation
(Thermostat on)
Fan sto p
(Thermostat off)
Indoor
temperature
Outdoor
temperature
Outdoor
temperature
Direct digital
controller
Thermistor
Thermistor
Ventilat or
Indoor
temperature
WALL MOUNTED
ASU30RLE
Rotary SW on
External input and
output PCB
60-00 / 2
60-09 / B
60-10 / C
External input
External input and
output PCB
CN313
Input
signal
Off → On
On → Off
Command
Thermostat
off
Normal
operation
Mode
0-1
9
10
Function
setting /
• Example of individual connection
Forced thermostat off is one of the function to save energy. For example, case of using ventilator
at condition with outdoor temperature is lower than indoor temperature, indoor unit of air conditioner stop based upon receiving signal from external controller. (Cooling only)
- 34 -
Page 39
• System figure example
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
82˚F
(28˚C)
88˚F
(31˚C)
External input wire
Except indoor unit
and external wire,
all other items are
locally purchased.
Relay
Indoor unit
External controller
Ventilator
Outdoor
thermistor
Indoor
thermistor
Indoor
temperature
Outdoor
temperature
Outdoor temp. < Indoor temp. : On
Outdoor temp. > Indoor temp. : Off
Normal
Forced thermostat off
On
Off
Signal detected by
external controller
Command from
external controller
Indoor
unit
WALL MOUNTED
ASU30RLE
• Operation status
Normal means that indoor unit continues to operate until “Forced thermostat Off” signal received,
at condition which are set by central and individual controller or detected by thermo sensors of
indoor unit.
Indoor unit continues to operate until “Forced thermostat Off” signal received, at condition which
are set by central and individual controller or detected by thermo sensors of indoor unit. Once
“Forced thermostat Off” signal received, indoor unit stop operation.
- 35 -
Page 40
WALL MOUNTED
Operation
Stop
High
Low
CN3
On
Off
CN310
Indoor unit
Error
Normal
High
Low
CN3
On
Off
CN310―312
Indoor unit
ASU30RLE
Control output function
Operation/Stop status
Mode
Function
setting /
0-1
0-2
0-160-00 / 1
The output is low when the unit is stopped.
Rotary SW on
External input and
output PCB
60-00 / 1, 2Output of indoor unitCN3
External output
External input and
output PCB
CN310
Output
signal
Command
Low → HighOperation
High → LowStop
Off → OnOperation
On → OffStop
Error status
Mode
Function
setting /
960-09 / BOutput of indoor unitCN3
0-160-00 / 1
The output is ON when an error is generated for the indoor unit.
Rotary SW on
External input and
output PCB
External output
External input and
output PCB
CN311
Output
signal
Command
Low → HighError
High → LowNormal
Off → OnError
On → OffNormal
- 36 -
Page 41
Indoor unit fan operation status
Fan run
Fan stop
High
Low
CN3
On
Off
CN311―312
Indoor unit
Rotary SW on
External input and
output PCB
External output
Mode
Function
setting /
1060-10 / COutput of indoor unitCN3
0-160-00 / 1
External input and
output PCB
CN312
Output signalCondition
On
Low → High
The indoor unit fan is operating.
OffThe fan is stopped or during cold air prevention.
High → LowDuring thermostat off when in dry mode operation.
Output
signal
Command
Low → HighFan run
High → LowFan stop
Off → OnFan run
On → OffFan stop
WALL MOUNTED
ASU30RLE
- 37 -
Page 42
WALL MOUNTED
Tr > Tsα + 5°F (2.5°C)
Output: On
Output: Off
Tr ≤ Tsα + 1°F (0.5°C)
When starting operation*
*: When starting operation or resetting, judges the zone to descending direction.
ASU30RLE
Set point attainment status
NOTE: This function is valid only when function setting 96 is set to “01” (Primary unit) or “02”
(Secondary unit).
When the room temperature does not reach the set point at a room due to the lower cooling performance caused by external factor such as the outdoor temperature change, signal is output to tell
the attainment status of set point.
Mode
1260-12 / DOutput of indoor unitCN3
Output signalCondition
Function
setting /
OffReached the set point. (Tr ≤ Ts α +1°F [0.5°C])
On
Rotary SW on
External input and
output PCB
Unreached the set point. (Tr > Tsα +5°F [2.5°C])
However, even if the set point unreached, the signal will not be output for 7 minutes
after power is turned on.
External output
Output
signal
On → OffNormal
Off → On
Command
Set point
attainment
When performing the server room control, both of the primary unit and secondary unit output the set
point attainment status if any of the unit is outputting alternative operation command.
- 38 -
Page 43
Fresh air conditioner (for external control module*) input func-
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
83˚F
(27.5˚C)
84˚F
(28˚C)
89˚F
(31˚C)
Direct digital
controller
Thermistor
Thermistor
Ventilator
Indoor
temperature
Set
temperature
Outdoor
temperature
Output: Cooling thermostat On
Output: Off (Cooling thermostat Off)
Input:
Input: On
(Mechanical cooling Off)
84˚F
(28˚C)
84˚F
(28˚C)
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
85˚F
(28.5˚C)
88˚F
(30˚C)
85˚F
(28.5C)
82˚F
(27˚C)
Output: On (Cooling thermostat On)
Output: On (Cooling thermostat On)
Input: On
(Mechanical cooling Off)
Input: Off
(Mechanical cooling On)
Mechanical cooling
control
Indoor
temperature
Outdoor
temperature
Set
temperature
Indoor
temperature
Outdoor
temperature
Set
temperature
tion (mode 1 or 7)
* Module that reduces or stops the cooling operating ratio of the air conditioner by intaking fresh air
such as Direct digital controller.
1
7
Function
setting
60-01
60-07
External inputExternal outputInput signal*Command
CNA03 or CNA04
(EXT. IN2)
Mechanical cooling Off
CNB01 (Pin: 1-2)
Cooling thermostat On
Off → On
On → OffNormal operation
Mechanical
cooling Off
Mode
* Edge input only.
• With using “Fresh air conditioner” input and “Cooling thermostat On” output, external control
module controls the cooling operation by the air conditioner.
• When “Fresh air conditioner On” is input during cooling thermostat on, fresh air conditioning is
performed with stopping the cooling operation by the air conditioner.
NOTE: During operations other than cooling such as heating or dry, “Fresh air conditioner On” input
is disabled.
• Example of individual connection
WALL MOUNTED
ASU30RLE
- 39 -
Page 44
WALL MOUNTED
Outdoor temp. < Indoor temp. : On
Set temp. + 0.9°F (+ 0.5°C)
Set temp. - 0.9°F (- 0.5°C)
Outdoor temp. > Indoor temp. : Off
Off
Off
Off
On
On
On
Signal detected by
external controller
[Mechanical cooling Off]
(EXT.IN2)
Cooling thermostat On
(EXT.OUT)
Mechanical cooling
Fan (49-01)
Indoor
unit
Indoor
temp.
*
• Operation status
ASU30RLE
*: This status follows the configuration on function setting 49.
•0: Setting airflow (When comp. on)
•1: Intermittent S-Lo (On: 1 minute and off: 3 minutes)
•2: Remote controller setting (Either of 0 or 1)
- 40 -
Page 45
External heater output
!
WARNING
Indoor unit
External
heater
Indoor unit
Supply airReturn air
Function setting
Indoor unitWired R. C.
ControlPrimary heaterAuxiliary heater
Auxiliary heater
control 1
Auxiliary heater
control 2
Heat pump
prohibition control
Heater selection
control by outdoor
temperature 1
Heater selection
control by outdoor
temperature 2
RAC heat pump
RAC heat pump
External device
(Hot water electrical
heater, etc.)
RAC heat pump
External device
(Hot water electrical
heater, etc.)
External device
(Hot water electrical
heater, etc.)
External device
(Hot water electrical
heater, etc.)
None61-02On (Enabled)*
External device
(Hot water electrical
heater, etc.)
RAC heat pump61-04On (Enabled)*
NOTES:
• After turning off the heater, 3 minutes of standby time is required by next power-on of the heater.
• For items marked “—” in the table, any of validate or invalidate of the setting are acceptable.
• *: setting change from the factory setting is required.
• *: Indoor unit fan setting will be on for safety reason without sensor activation of wired remote
controller.
Control switching
external heaters
Sensor activation
No. 61
61-00—
61-01—
61-03On (Enabled)*
(UTY-RNRUZ1)
WALL MOUNTED
ASU30RLE
Installation configuration of individual connection
External heating device is installed individually. (No use of indoor unit fan)
ON / OFF
Example of heating device:
- Floor heating device
• When auxiliary heater is installed, always set “indoor unit fan setting for external heater”.
• Design and install external heater appropriately with considering its protection.
• Inappropriate designing and installation of external heater may cause a fire by emitted heat from
the external heater.
• Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external
heating device.
- 41 -
Page 46
WALL MOUNTED
Off
On
Tr-Ts ≥ -1.8 °F
(-1°C)
Tr-Ts
Tr-Ts (=Thon) < -5.4°F (-3°C)
Tr-Ts ≥ -18° F
(-10°C
)
Tr-Ts < -21.6°F (-12°C)
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts ≥ -1.8°F
(-1°C)
Tr-Ts
Tr-Ts (=Thon) < -5.4°F (-3°C)
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
ASU30RLE
Auxiliary heater control 1
OperationCondition
Heater onHeater is on as shown in following diagram of heating temperature.
• Heater is off as shown in following diagram of heating temperature.
• Other than heating mode
Heater off
• Temperature of heater on (Thon): Adjustable by function setting no. 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
Example: When set temperature (Ts) is 72°F (22°C) (Factory setting),
• and room temperature (Tr) increases above 53.6°F (12°C), signal output is on.
• and room temperature (Tr) increases above 69.8°F (21°C), signal output is off.
• and room temperature (Tr) decreases below 66.2°F (19°C), signal output is on.
• and room temperature (Tr) decreases below 50°F (10°C), signal output is off.
• Error occurred
• Forced thermostat off
• Fan stop protection
Off
Auxiliary heater control 2
OperationCondition
Heater onHeater is on as shown in following diagram of heating temperature.
• Heater is off as shown in following diagram of heating temperature.
• Other than heating mode
Heater off
• Temperature of heater on (Thon): Adjustable by function setting no. 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
• Error occurred
• Forced thermostat off
• Fan stop protection
- 42 -
Page 47
Heat pump prohibition control
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts ≥ 0.9°F
(0.5°C)
Tr-Ts
Tr-Ts (=Thon) ≤ -0.9°F
(
-0.5°C)
On
0.9°F (0.5°C)
-0.9°F (-0.5°C)
On
12 V
On
Off
Off
0 V
Off
Heating operation
Heater
Fan
Air conditioner
Room temperature
Set temp.
3 min or more
OperationCondition
Heater onHeater is on as shown in following diagram of heating temperature.
• Heater is off as shown in following diagram of heating temperature.
Heater off
• Temperature of heater on (Thon): Adjustable by function setting no. 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
Operation status
• Other than heating mode
• Error occurred
• Forced thermostat off
WALL MOUNTED
ASU30RLE
NOTE: In following operations, compressor will be on.
• Other than heating
• Test run
- 43 -
Page 48
WALL MOUNTED
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts ≥ 0.9°F
(0.5°C)
Tr-Ts
Tr-Ts (=Thon) ≤ -0.9°F
(
-0.5°C)
ASU30RLE
Heater selection control by outdoor temperature 1
OperationCondition
Heater onHeater is on as shown in following diagram of heating temperature.
• Heater is off as shown in following diagram of heating temperature.
• Other than heating mode
Heater off
• Temperature of heater on (Thon): Adjustable by function setting no. 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
• Outdoor temperature zone boundary A and B: Adjustable individually by function setting no. 36
and 37 for outdoor unit.
• External heater output
• Error occurred
• Forced thermostat off
• Heat pump only zone
• Outdoor temperature zone
Outdoor temp.
B + 3.6°F (2°C): 46.4°F (8°C)
A + 3.6°F ( 2°C): -0.4°F (-18°C)
• Operation status
46.4°F (8°C)
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
Comp. On/Off
42.8°F (6°C)
-0.4°F (-18°C)
-4°F (-20°C)
On
Off
*B: 42.8°F (6°C)
*A: -4°F (-20°C)
*Adjustable by function setting no. 66 and 67
Heat pump only zone
(Heat pump)
Combination zone
(Heat pump + Heater)
Heat pump prohibition zone
(Heater)
Heat pump
prohibition
zone
Combination zone
Heat pump
only zone
12 V
Heater
Fan
0 V
On
Off
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
NOTE: In following operations, compressor will be on in heat pump prohibition zone.
• Other than heating
• Test run
- 44 -
Page 49
Heater selection control by outdoor temperature 2
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts ≥ 0.9°F
(0.5°C)
Tr-Ts
Tr-Ts (=Thon) ≤ -0.9°F
(
-0.5°C)
On
On
12 V
Off
Off
0 V
Heater
Fan
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
Heat pump
prohibition
zone
Combination zone
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.4°F (-18°C)
-4°F (-20°C)
OperationCondition
Heater onHeater is on as shown in following diagram of heating temperature.
• Heater is off as shown in following diagram of heating temperature.
Heater off
• Temperature of heater on (Thon): Adjustable by function setting no. 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
• Outdoor temperature zone boundary A and B: Adjustable by function setting no. 36 for outdoor
unit.
• External heater output
• Other than heating mode
• Error occurred
• Forced thermostat off
WALL MOUNTED
ASU30RLE
• Outdoor temperature zone
A + 3.6°F ( 2°C): -0.4°F (-18°C)
• Operation status
Outdoor temp.
*A: -4°F (-20°C)
Combination zone
(Heat pump + Heater)
Heat pump prohibition zone
(Heater)
*Adjustable by function setting no. 66.
NOTE: In following operations, compressor will be on in heat pump prohibition zone.
• Other than heating
• Test run
- 45 -
Page 50
WALL MOUNTED
Heating operation
Heating thermostat
On output
External heater
output On / Off
Comp. On / Off
On
On
On
On
On
Off
Off
Off
Off
Off
Fan
Cool air prevention
ASU30RLE
Heating thermostat on for humidifier
Indoor unit
Function
Situation
Mode
560-057CN2
Example of
individual
connection
660-068CN312
760-079CN311
860-08ACN310
• Example of individual connection
External output: Heating thermostat on
setting
Heating
thermostat on
no. 60
Rotary SW
thermostat on
Humidifier
External output
Heating
Indoor unit fan
operation
status
Not used
• Operation status
The heating thermostat output for CNB01 (1-2 or 1-3 or 1- or 1-5) will be on when comp. on or
external heater on.
The heating thermostat output will be off when comp off and external heater off.
- 46 -
Page 51
11. Function settings
!
CAUTION
Function number
Setting value
To adjust the functions of this product according to the installation environment, various types of
function settings are available.
NOTE: Incorrect settings can cause a product malfunction.
11-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting procedure and the content of each function setting, select appropriate functions for your installation environment.
Setting procedure by using wireless remote controller
The function number and the associated setting value are displayed on the LCD of the remote
controller. Follow the instructions written in the local setup procedure supplied with the remote
controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Cover for the electrical enclosure on the outdoor unit is in place.
• There is no wiring mistake.
• Piping air tight test and vacuuming have been performed firmly.
• All the necessary wiring work for outdoor unit has been finished.
After reconfirming the items listed above, connect the power supply of the indoor unit.
WALL MOUNTED
ASU30RLE
NOTES:
• Settings will not be changed if invalid numbers or setting values are selected.
• When optional wired remote controller is used, refer to the installation manual enclosed with the
remote controller.
Entering function setting mode:
While pressing the POWERFUL button and TEMP. () button
simultaneously, press the RESET button to enter the function setting mode.
Selecting the function number and setting value:
1. Press the TEMP. () () buttons to select the function number. To switch
between the left and right digits, press the MIN. HEAT button.
2. Press the POWERFUL button to proceed to value setting. To return the function number selection, press the POWERFUL button again.
3. Press the TEMP. () () buttons to select the setting value. To switch
between the left and right digits, press the MIN. HEAT button.
4. Press the MODE button once to send the function setting information.
Confirm that you hear the beep sound.
5. Press the START/STOP button to fix the function setting. Confirm that you
hear the beep sound.
6. Press the RESET button to end the function setting mode.
7. After completing the function setting, be sure to disconnect the power supply
and then reconnect it.
After disconnecting the power supply, wait 30 seconds or more before reconnecting it. The function setting will not become active unless the power supply is disconnected and then reconnected.
- 47 -
Page 52
WALL MOUNTED
ASU30RLE
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.Functions
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
13)
14)
15)
00
11
30/31
35/36
40
42
44
46
48
49
60
66
67
94
96
Remote controller address setting
Filter sign
Room temperature control for indoor unit sensor
Room temperature control for wired remote controller sensor
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
Switching functions for external output terminal
Outdoor temperature zone boundary temperature A
Outdoor temperature zone boundary temperature B
Fixed operation mode switching
Server room control
1) Remote controller address setting
NOTE: Because this setting is normally done automatically when 2-wire-type wired remote
controller is installed, setting is unnecessary.
Multiple indoor units can be operated by using one wired remote controller.
Set the unit number of each indoor unit.
Function numberSetting valueSetting descriptionFactory setting
• When connecting Polar 3-core wired remote controller, set the remote controller address in the
order of 0, 1, 2, ....., and 15.
• When different type of indoor units (such as wall-mounted type and cassette type, cassette type
and duct type, or other combinations) are connected using group control system, some functions
may no longer be available.
- 48 -
Page 53
2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function numberSetting valueSetting descriptionFactory setting
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufacturer’s recommended value).
4) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be
required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is pos-
sible by setting function setting 30 and 31 too.
WALL MOUNTED
ASU30RLE
Function numberSetting valueSetting descriptionFactory setting
48
00Both♦
01Wired remote controller
10) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function numberSetting valueSetting descriptionFactory setting
00Disable
49
01Enable
02Remote controller♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially .
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for energy
saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each remote
controller.
- 51 -
Page 56
11) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
WALL MOUNTED
ASU30RLE
Function numberSetting valueSetting descriptionFactory setting
00Operation status♦
60
09Error status
10Indoor unit fan operation status
12Set point attainment status
12) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is required when heater selection control using outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to “External input and output”.
Function numberSetting valueSetting descriptionFactory setting
13) Outdoor temperature zone boundary temperature B
Setting required if changing of the outdoor temperature setting for heat pump only zone is required
when heater selection control using outdoor temperature 1 is performed on the indoor unit. For details, refer to “External input and output”.
Function numberSetting valueSetting descriptionFactory setting
Sets the operation mode to heat pump, heating only, or cooling only.
Function numberSetting valueSetting descriptionFactory setting
00Heat pump♦
94
01Heating only
02Cooling only
- 52 -
Page 57
15) Server room control
Switches between normal control and server room control.
NOTE: To use this function, address setting of the primary unit and secondary unit needs to be
done.
Function numberSetting valueSetting descriptionFactory setting
00Normal control♦
96
01Server room control (Primary unit)
02Server room control (Secondary unit)
When performing server room control, mind the followings:
• Set to “01” on one of the 2 indoor units, and set to “02” on the other indoor unit.
• As for the function details and setup procedure, refer to “Details of server room control” on page 4.
WALL MOUNTED
ASU30RLE
- 53 -
Page 58
WALL MOUNTED
11-2. Custom code setting for wireless remote controller
To interconnect the air conditioner and the wireless remote controller, assignment of the custom
ASU30RLE
code for the wireless remote controller is required.
NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom
code.
When 2 or more air conditioners are installed in a room, and the remote controller is operating an
air conditioner other than the one you wish to set, change the custom code of the remote controller
to operate only the air conditioner you wish to set. (4 selections possible.)
Confirm the setting of the remote controller custom code and the function setting. If these do not
match, the remote controller cannot be used to operate for the air conditioner.
1. Press the START/STOP button until only the clock is displayed on the
remote controller display.
2. Press the MODE button for at least 5 seconds to display the current custom
code. (Initially set to .)
3. Press the TEMP. () () buttons to change the custom code between
→ → → . Match the code on the display to the air conditioner custom
code. (Initially set to .)
4. Press the MODE button again to return to the clock display. The custom code
will be changed.
NOTES:
• If no button is pressed within 30 seconds after the custom code is displayed, the system returns
to the original clock indicator. In this case, start again from step 1.
• The air conditioner custom code is set to prior to shipment. To change the custom code, contact
your retailer.
• If you do not know the assigned code for the air conditioner, try each of the custom code ( → → → ) until you find the code which operates the air conditioner.
- 54 -
Page 59
12. Accessories
Part nameExteriorQ’tyPart nameExteriorQ’ty
Operating manual1Drain hose insulation1
Installation manual1Cloth tape1
WALL MOUNTED
ASU30RLE
Wall hook bracket1
Remote controller1
Battery2Air cleaning filter2
Remote controller
holder
Tapping screw (large),
M4 × 25 mm
Tapping screw (small),
M3 × 12 mm
1Air cleaning filter frame2
8
2
- 55 -
Page 60
WALL MOUNTED
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
13. Optional parts
ASU30RLE
13-1. Controllers
ExteriorPart nameModel nameSummary
Wired remote
controller
Easy finger touch operation with LCD
panel. Backlit LCD enables easy
operation in a dark room.
Wire type: Non-polar 2-wire
NOTE: When this remote controller is
connected, wireless remote
controller cannot be used.
UTY-RNRUZ1
Monitor
10:00
Mo
Set temp.
80
Icon check:
AM
Fan
°
F
High
Wired remote
controller
UTY-RVNUM
Mode
Cool
Menu
Large and full-dot liquid crystal
screen, wide and large keys easy to
press, user-intuitive arrow key.
Wire type: Polar 3-wire
Room temperature can be controlled
Wired remote
controller
UTY-RNNUM
by detecting the temperature
accurately with built-in thermo
sensor.
Wire type: Polar 3-wire
Compact remote controller
concentrates on the basic functions
Simple remote
controller
UTY-RSNUM
such as Start/Stop, fan control,
temperature setting, and operation
mode.
Wire type: Polar 3-wire
NOTE: Available functions may differ by the remote controller. For details, refer to the operation
manual.
- 56 -
Page 61
13-2. Others
ExteriorPart nameModel nameSummary
WALL MOUNTED
ASU30RLE
External
connect kit
External input
and output PCB
External input
and output PCB
box
UTY-XWZX
UTY-XCSXZ1
UTZ-GXXB
Use to connect with various
peripheral devices and air conditioner
PCB.
Use to connect with external devices
and air conditioner PCB.
For installing the External input and
output PCB.
- 57 -
Page 62
WALL MOUNTED
ASU30RLE
- 58 -
Page 63
Part 2. OUTDOOR UNIT
SINGLE TYPE:
AOU30RLXEH
Page 64
OUTDOOR UNIT
AOU30RLXEH
1. Specifications
Typ eInverter heat pump
Model name
Power supply208/230 V ~ 60 Hz
Available voltage range187—253 V
Starting currentA18.7
Fan
Sound pressure level *1
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions
(H × W × D)
Weight
Connection pipe
Operation range
Drain hose
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Airflow rate
Type × Q'tyPropeller fan × 2
Motor outputW100 × 2
Type × Q'tyTwin rotary × 1
Motor outputW3,750
Net
Gross
Net
Gross227 (103)
Size
MethodFlare
Pre-charge length
Max. length246 (75)
Max. height difference98 (30)
Cooling
Heating4,032 (6,850)
Cooling
Heating54
Dimensions
(H × W × D)
Fin pitchFPI1.3
Rows × Stages2 × 60
Pipe typeCopper
Fin type
TypeR410A
Charge
TypePOE (VG74)
Amount
MaterialSteel sheet
Color
Liquid
GasØ 5/8 (Ø 15.88)
Cooling
Heating-15 to 75 (-26 to 24)
MaterialLDPE
SizemmØ 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
CFM (m3/h)
dB (A)
in49-10/16 × 35-7/16 × 1-7/16
mm1,260 × 900 × 36.4
Type (Material)Corrugate (Aluminum)
Surface
treatment
lb oz6 lb 12 oz
g3,050
in3 (cm3)
in50-13/16 × 35-7/16 × 13
mm1,290 × 900 × 330
in57-1/2 × 41-5/16 × 17-1/2
mm1,460 × 1,050 × 445
lb (kg)
in (mm)
ft (m)
°F (°C)
Hydrophilic coating (Blue fin)
Approximate color of MUNSELL 10YR7.5/1.0
AOU30RLXEH
4,032 (6,850)
53
94.5 (1,550)
Beige
205 (93)
Ø 3/8 (Ø 9.52)
65 (20)
-5 to 115 (-20 to 46)
- 60 -
Page 65
2. Dimensions
13 (330)
1-1/4
(31)
25-9/16 (650)
4-11/16
(119)
5-3/16
(132)
14-9/16 (
370
)
1-1/2 (38)
(Liquid)
1-3/4 (45)
2-5/8 (66)
1-13/16 (46)
(
Gas
)
50-13/16 (1290)
35-7/16 (900)
13/16 (21)
3/8 (9)
3-1/2
(89)
13/16
(21)
13/16
(21)
13/16
(21)
3-3/4 (95)
1 (25)
1-15/16
(50)
1-15/16
(50)
1-15/16
(50)
21-3/8 (543)
(
Gas valve
)
21-1/4 (540)
(Liquid valve)
39-1/16 (992)
13 (330)
1-1/4
(31)
1/2
(12)
2-3/16
(55)
4-3/4
(120)
3-3/4
(95)
6-9/16 (167)
6-1/8
(156)
4-7/16
(112)
2-5/8
(67)
7-3/8 (188)
10-7/16 (265)
11-7/8 (302)
15-3/4 (400)
2 (51.5)
17-5/16 (440)
24-5/8 (625)
Ø28 (Ø1-1/8)
x 2
(Cable port)
Ø28 (Ø1-1/8) x 2
(Cable port)
Ø28 (Ø1-1/8) x 2(Cable port)
Pipe port
Pipe port
Pipe port
Top view
Front view
Bottom view
Side view
Detail A
Rear view
1-9/16 (40)
3-way valve
(
Gas
)
3-way valve
(Liquid)
Terminal blocks
9/16
(14)
13/16
(46)
5/8
(16)
2-1/8
(54)
3-7/16 (87)
5-3/16 (131)
Pipe and cable port
Unit: in (mm)
A
2-1. Model: AOU30RLXEH
OUTDOOR UNIT
AOU30RLXEH
- 61 -
Page 66
OUTDOOR UNIT
6 (150) or more
8 (200) or more
8 (200) or more
12 (300) or more
40 (1,000) or more
12 (300) or more
Max. 19 (500)
40 (1,000)
or more
AOU30RLXEH
3. Installation space
3-1. Model: AOU30RLXEH
Space requirement
Provide sufficient installation space for product safety.
Single outdoor unit installation
• When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only.When there are obstacles at the rear and sides.
When there are obstacles at the front only.When there are obstacles at the front and rear.
6 (150) or more
40 (1,000) or more
• When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and
above.
When there are obstacles at the rear, sides, and
above.
60 (1,500)
or more
- 62 -
10 (250)
or more
10 (250) or more
20 (500)
or more
Max. 19 (500)
Page 67
Multiple outdoor unit installation
60 (1,500)
or more
• When the upper space is open:
When there are obstacles at the rear only.When there are obstacles at the front only.
12 (300) or more
When there are obstacles at the front and rear.
Unit: in (mm)
OUTDOOR UNIT
AOU30RLXEH
20 (500)
or more
60 (1,500)
or more
• When there is an obstruction in the upper space:
When there are obstacles at the rear and above.
Max. 11 (300)
60 (1,500) or more
Unit: in (mm)
60 (1,500)
or more
20 (500) or more
- 63 -
Page 68
OUTDOOR UNIT
!
CAUTION
AOU30RLXEH
Outdoor unit installation in multi-row
Unit: in (mm)
Single parallel unit arrangementMultiple parallel unit arrangement
6 (150)
or more
79 (2,000)
or more
24 (600) or more
40 (1,000) or more
24 (600) or more
60 (1,500) or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no
obstacle.
• Height above the floor level should be 2 in (50 mm) or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
20 (500)
or more
119 (3,000)
or more
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the
drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 32 °F (0 °C) or less, do not use the accessory drain pipe and
drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in
extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might
become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and
a pedestal, or place the unit on a high stand that is locally installed.
- 64 -
Page 69
4. Refrigerant circuit
SUB
ACM
FAN
4WV
CMP
AC
OUTER
HEX
INNER
HEX
FAN
STRAINER
3WV
3WV
STRAINER
MUFFULER
EEV
SERVICE
PORT
PRESSURE
SENSOR
FUSIBLE
PLUG
STRAINER
4-1. Model: AOU30RLXEH
OUTDOOR UNIT
AOU30RLXEH
- 65 -
Page 70
OUTDOOR UNIT
AOU30RLXEH
5. Wiring diagrams
5-1. Model: AOU30RLXEH
- 66 -
Page 71
6. Capacity compensation rate for pipe length and height
Height difference H
Height difference H
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
difference
6-1. Model: AOU30RLXEH
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
0
63125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
80
70
60
50
40
30
20
10
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
0
63125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
- 70 -
Page 75
9-2. Sound level check point
Airflow
MicrophoneMicrophone
Rear
Rear viewSide view
39-3/8 in (1 m)
NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated
above.
OUTDOOR UNIT
AOU30RLXEH
- 71 -
Page 76
OUTDOOR UNIT
AOU30RLXEH
10. Electrical characteristics
Model nameASU30RLE
Power supplyVoltageV208/230
FrequencyHz60
MCA *1A25.6
Starting currentA18.7
MAX. CKT. BKR *3A30
Wiring spec. *2
*1: Minimum Circuit Ampacity (Calculation based on UL1995)
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
*3: Maximum Circuit Breaker
*4: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
Power cableAWG10
Connection cable *4AWG14
Limited wiring lengthft (m)249 (76)
- 72 -
Page 77
11. Safety devices
Type of
protection
Circuit protection
Fan motor
protection
Compressor
protection
High pressure
protection
High pressure
protection
Low pressure
protection
Protection form
Model
AOU30RLXEH
Current fuse (Near the terminal)250 V, 25 A
Current fuse (Filter PCB)
250 V, 10 A
250 V, 5 A
Current fuse (Main PCB)250 V, 3.15 A
Current fuse (Out of PCB)250 V, 5 A
Activate
Thermistor protection
Reset
122±9 °C
Fan motor stop
+10
116
°C
-9
Fan motor restart
Terminal protection
program
(Compressor temp.)
Thermal protection
program
(Discharge temp.)
Pressure switch
Pressure switch
Pressure sensor
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
108 °C
Compressor stop
After 40 minutes
Compressor restart
110°C
Compressor stop
After 7 minutes
Compressor restart
4.2±0.1 MPa
Compressor stop
3.2±0.15 MPa
Compressor restart
4.2±0.1 MPa
Compressor stop
3.2±0.15 MPa
Compressor restart
4.2±0.1 MPa
Compressor stop
3.2±0.15 MPa
Compressor restart
OUTDOOR UNIT
AOU30RLXEH
- 73 -
Page 78
OUTDOOR UNIT
Outdoor unit
control PCB
Connected unit
Example: Switch
Connector
1
2
Signal
Locally purchased
33 ft. (10 m)*
On
Off
On
Off
Input signal
Low noise mode
AOU30RLXEH
12. External input and output
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
ConnectorInputOutputRemarks
CN10Low noise mode—
CN11Peak cut mode—
CN12—Error status
CN13—Compressor status
See external input/output
settings for details.
12-1. External input
With using external input function, on/off status of “Low noise mode” and “Peak cut mode” can be
specified by the external signal.
Low noise mode
In following condition, the operating noise of the outdoor unit reduces comparing from the one in
normal operating condition:
The air conditioner is set to the “Low noise mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit
NOTE: Product performance may drop depending on some conditions such as the outdoor
temperature.
Circuit diagram example
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit
within 33 ft (10 m).
• Construct a circuit as shown in this figure with using
optional parts mentioned below.
• Input signal: On in “Low noise mode”
• Input signal: Off in normal operation
• To set the level of “Low noise mode”, refer to “Low noise
mode” on page 80.
Optional part
Part nameModel nameExterior
External connect kitUTY-XWZXZ3
- 74 -
Page 79
Peak cut mode
On
Off
On
Off
Input signal
Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
Circuit diagram example
Outdoor unit
control PCB
Connector
1
2
Optional part
Connected unit
Example: Switch
33 ft. (10 m)*
Signal
Locally purchased
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit
within 33 ft (10 m).
• Construct a circuit as shown in this figure with using
optional parts mentioned below.
• Input signal: On in “Peak cut mode”
• Input signal: Off in normal operation
• To set the level of “Peak cut mode”, refer to “Peak cut
mode” on page 82.
OUTDOOR UNIT
AOU30RLXEH
Part nameModel nameExterior
External connect kitUTY-XWZXZ3
- 75 -
Page 80
12-2. External output
Signal
Outdoor unit
control PCB
Connected unit
Connector
1
2
Locally purchased
*33 ft (10) m
Vcc
+
+
-
Load
Vcc
Power
supply
Error
Normal
On
Off
Error status
Output signal
With using external output function, some status signals are transmitted to the control PCB, and the
related LED lamp indicates the status of this product.
Error status output
Circuit diagram example
OUTDOOR UNIT
AOU30RLXEH
• 1: Power supply
Voltage (Vcc): DC 24 V or less
• 2: Load
DC 500 mA or less
• *: Make the distance from the PCB to the
connected unit within 33 ft (10 m).
Optional part
Part nameModel nameExterior
External connect kitUTY-XWZXZ3
- 76 -
Page 81
Compressor status output
Signal
Outdoor unit
control PCB
Connected unit
Connector
1
2
Locally purchased
*33 ft (10) m
Vcc
+
+
-
Load
Vcc
Power
supply
Operation
Stop
On
Off
Compressor
status
Output signal
Circuit diagram example
• 1: Power supply
Voltage (Vcc): DC 24 V or less
• 2: Load
DC 500 mA or less
• *: Make the distance from the PCB to the
connected unit within 33 ft (10 m).
OUTDOOR UNIT
AOU30RLXEH
Optional part
Part nameModel nameExterior
External connect kitUTY-XWZXZ3
- 77 -
Page 82
OUTDOOR UNIT
!
CAUTION
AOU30RLXEH
13. Function settings
Perform appropriate function setting locally according to the installation environment.
NOTE: Incorrect settings can cause a product malfunction.
• Before setting up the switch buttons, discharge the static electricity from your body.
• Never touch the terminals or the patterns on the parts that are mounted on the PCB.
13-1. Local setting switch buttons
Control PCB and switch buttons location
Control PCB of the outdoor unit is located as shown in the following figure.
LED lamps
Switch buttons
Terminal block
- 78 -
Page 83
Switch buttons and the functions
SW1
SW2
SW3SW4SW5
(1)(2)(3)(4)(5)
LED lamps
Switch buttons
LED lampFunction or operation method
(1) POWER/MODEGreen
(2) ERRORRedBlinks during error operation.
(3) PUMP DOWN (L1)Orange Lights on during pump down operation.
LOW NOISE MODE
(4)
(L2 and L3)
PEAK CUT MODE
(5)
(L4, L5, and L6)
Orange
Orange
Lights on while power on.
Local setting in outdoor unit or error code is displayed with blink.
Lights on during “Low noise mode” when local setting is activated.
(Lighting pattern of L2 and L3 indicates low noise level.)
Lights on during “Peak cut mode” when local setting is activated.
(Lighting pattern of L4, L5, and L6 indicates peak cut level.)
OUTDOOR UNIT
AOU30RLXEH
Switch buttonFunction or operation method
SW1MODESwitches between “Local setting” and “Error code display”.
SW2SELECT
SW3ENTER
Switches between the individual “Local settings” and the “Error code
displays”.
Switches between the individual “Local settings” and the “Error code
displays”.
SW4EXITReturns to “Operation status display”.
SW5PUMP DOWNStarts the pump down operation.
- 79 -
Page 84
OUTDOOR UNIT
SW1
SW2
SW3SW4SW5
(1)(2)(3)(4)(5)
LED lamps
Switch buttons
POWER
MODE
ERROR
(L1)(L2)(L3)(L4)(L5)(L6)
PUMP
DOWN
LOW NOISEPEAK CUT
Blinks
(9 times
)
Sign “ ”: Lights off
(L2)(L3)
LOW NOISE
LOW NOISE
MOD
E
Sign “ ”: Lights on
AOU30RLXEH
13-2. Local setting procedure
NOTE: Before performing the function setting, be sure to stop the operation of the air conditioner.
Low noise mode
1.Press the MODE switch button (SW1) for 3 seconds or more to switch to “Local setting mode”.
2.After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch
button (SW3).
3.Press the SELECT switch button (SW2), and adjust the LED lamp as shown below. Then the
LED lamp indicates the current setting.
LOW NOISE
(L3)
(L2)
LOW NOISE
MODE
Blink
4.Press the ENTER switch button (SW3).
5.Press the SELECT switch button (SW2), and adjust the LED lamps as shown below.
MODE 1
MODE 2
PEAK CUT
(L4)(L5)(L6)
Blink
Blink
- 80 -
Page 85
6.Press the ENTER switch button (SW3) and fix it.
PEAK CUT
(L4)(L5)(L6)
MODE 1
MODE 2
7.To return to “Operating status display (Normal operation)”, press the EXIT switch button
(SW4).
In case of missing how many times you pressed the SELECT and ENTER switch buttons:
1. To return to “Operation status display (Normal operation)”, press the EXIT switch button once.
2. Restart from the beginning of setting procedure.
NOTE: In case of missing how many times you pressed the SELECT and ENTER switch buttons,
you must redo the setting procedure. Return to “Operation status display (Normal operation)” by pressing the EXIT switch button once, and restart from the beginning of the setting
procedure.
OUTDOOR UNIT
AOU30RLXEH
- 81 -
Page 86
OUTDOOR UNIT
SW1
SW2
SW3SW4SW5
(1)(2)(3)(4)(5)
LED lamps
Switch buttons
POWER
MODE
ERROR
(L1)(L2)(L3)(L4)(L5)(L6)
PUMP
DOWN
LOW NOISEPEAK CUT
Blinks
(9 times
)
Sign “ ”: Lights off
(L2)(L3)
LOW NOISE
PEAK CUT
MODE
Sign “ ”: Lights on
100 % of rated input ratio
75 % of rated input ratio
50 % of rated input ratio
0 % of rated input ratio
Blink
Blink Blink
Blink
Blink
PEAK CUT
(L4)(L5)(L6)
AOU30RLXEH
Peak cut mode
1.Press the MODE switch button (SW1) for 3 seconds or more to switch to “Local setting mode”.
2.After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch
button (SW3).
3.Press the SELECT switch button (SW2), and adjust the LED lamp as shown below. Then the
LED lamp indicates the current setting.
4.Press the ENTER switch button (SW3).
5.Press the SELECT switch button (SW2), and adjust the LED lamps as shown below.
PEAK CUT
E
MOD
LOW NOISE
(L2)
(L3)
Blink
- 82 -
Page 87
6.Press the ENTER switch button (SW3) and fix it.
100 % of rated input ratio
75 % of rated input ratio
50 % of rated input ratio
0 % of rated input ratio
PEAK CUT
(L4)(L5)(L6)
7.To return to “Operating status display (Normal operation)”, press the EXIT switch button
(SW4).
NOTE: When pressed number is lost during setting, you must redo the setting procedure. Return to
“Operation status display (Normal operation)” by pressing the EXIT switch button once, and
restart from the beginning of the setting procedure.
OUTDOOR UNIT
AOU30RLXEH
- 83 -
Page 88
OUTDOOR UNIT
AOU30RLXEH
14. Accessories
Part nameExteriorQ’tyPart nameExteriorQ’ty
Installation manual1Conduit plate1
- 84 -
Page 89
15. Optional parts
ExteriorPart nameModel nameSummary
External
connect kit
UTY-XWZXZ3
Use to operate the external input and
output functions of outdoor unit.
OUTDOOR UNIT
AOU30RLXEH
- 85 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.