Fujitsu ASTG30KMTA, ASTG34KMTA, AOTG34KMTA, AOTG30KMTA Design & Technical Manual

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
ASTG30KMTA ASTG34KMTA
AOTG30KMTA
AOTG34KMTA
2015.08.10
Notices:
• Product specifications and design are subject to change without notice for future improvement.
• For further details, please check with our authorized dealer.
Copyright © 2015 Fujitsu General Limited. All rights reserved.
CONTENTS
Part 1. INDOOR UNIT ........................................................................1
1. Product features ......................................................................................2
1-1. Model lineup ..............................................................................................................2
1-2. Features .....................................................................................................................2
2. Wireless remote controller ....................................................................4
2-1. Features .....................................................................................................................4
2-2. Overview ....................................................................................................................6
2-3. Specifications .............................................................................................................7
3. Specifications ..........................................................................................8
4. Dimensions ..............................................................................................9
4-1. Installation space requirement .................................................................................10
5. Wiring diagram .......................................................................................11
6. Capacity table ........................................................................................12
6-1. Cooling capacity ......................................................................................................12
6-2. Heating capacity ......................................................................................................13
7. Fan performance ....................................................................................14
7-1. Air velocity distributions ...........................................................................................14
7-2. Airflow ......................................................................................................................15
8. Operation noise (sound pressure) .......................................................16
8-1. Noise level curve .....................................................................................................16
8-2. Sound level check point ...........................................................................................17
9. Safety devices ........................................................................................18
10. External input and output .....................................................................19
10-1.External input ..........................................................................................................19
10-2.External output ........................................................................................................21
10-3.Combination of external input and output ...............................................................23
10-4.Details of function ...................................................................................................25
11. Function settings ...................................................................................30
11-1.Function settings on indoor unit ..............................................................................30
11-2.Function settings by using remote controller ..........................................................31
11-3.Custom code setting for wireless remote controller ................................................37
12. Optional parts ........................................................................................38
12-1.Controllers ...............................................................................................................38
12-2.Others .....................................................................................................................39
CONTENTS (continued)
Part 2. OUTDOOR UNIT ................................................................. 41
1. Specifications ........................................................................................42
1-1. Model: AOTG30KMTA ............................................................................................ 42
1-2. Model: AOTG34KMTA ............................................................................................ 43
2. Dimensions ............................................................................................44
2-1. Model: AOTG30KMTA ............................................................................................ 44
2-2. Model: AOTG34KMTA ............................................................................................ 45
2-3. Installation space requirement ................................................................................ 46
3. Refrigerant circuit ..................................................................................52
3-1. Model: AOTG30KMTA ............................................................................................ 52
3-2. Model: AOTG34KMTA ............................................................................................ 53
4. Wiring diagrams .....................................................................................54
4-1. Model: AOTG30KMTA ............................................................................................ 54
4-2. Model: AOTG34KMTA ............................................................................................ 55
5. Capacity compensation rate for pipe length and height difference .56
5-1. Model: AOTG30KMTA ............................................................................................ 56
5-2. Model: AOTG34KMTA ............................................................................................ 57
6. Additional charge calculation ...............................................................58
6-1. Model: AOTG30KMTA ............................................................................................ 58
6-2. Model: AOTG34KMTA ............................................................................................ 58
7. Airflow .....................................................................................................59
7-1. Model: AOTG30KMTA ............................................................................................ 59
7-2. Model: AOTG34KMTA ............................................................................................ 59
8. Operation noise (sound pressure) .......................................................60
8-1. Noise level curve ..................................................................................................... 60
8-2. Sound level check point .......................................................................................... 61
9. Electrical characteristics ......................................................................62
10. Safety devices ........................................................................................63
11. External input and output (for AOTG34KMTA) ...................................64
11-1.External input .......................................................................................................... 64
11-2.External output ....................................................................................................... 66
12. Function settings (for AOTG34KMTA) ................................................. 68
12-1.Local setting switch buttons .................................................................................... 68
12-2.Local setting procedure .......................................................................................... 70
13. Optional parts ........................................................................................73

Part 1. INDOOR UNIT

WALL MOUNTED TYPE:
ASTG30KMTA ASTG34KMTA
WALL MOUNTED
Large heat exchanger
37
%
Up!
Heat exchanger volume
: New model
: Previous model
34
3.29
3.38
30
3.31
3.45
31
EER
15
% Reduce!
Outdoor unit
volume
Human sensor

1. Product features

Implemented core technology provides easy-to-use product operations that realize a comfortable
ASTG30, 34KMTA
space.

1-1. Model lineup

ASTG30KMTA ASTG34KMTA

1-2. Features

Energy efficiency class
Star rating index
High energy saving
Top class EER by large heat exchanger and new refrigerant (R32).
AOTG30KMTA AOTG34KMTA
MODEL
ASTG30KMTA ASTG34KMTA
Cooling 2.0 2.0 Heating 3.0 2.5
.
Energy saving control by using human sensor
Implemented human sensor detects the presence or absence of human in a room by sensing movement of occupants, and suppress both of the air conditioner operation and energy con­sumption.
- 2 -
Powerful airflow
30
% Up!
Airflow
Current model
NEW model(+100 mm)
Demand Response flow
Energy provide
Energy save
* Restrict the operation of air conditioner base on the demand of energy provider in order to cut the peak load.
Smart Meter
Long-reach airflow 25 m by optimized airflow design. New models reach faster the setting temperature in the entire room than current models.
Corresponding to demand response program
WALL MOUNTED
ASTG30, 34KMTA
- 3 -
WALL MOUNTED
1 °C
2 °C
3 °C
4 °C
30 min
60 min
90 min
Timer setting

2. Wireless remote controller

ASTG30, 34KMTA

2-1. Features

• 5-mode timer setup (on, off, weekly, program, and sleep) available.
• Easy operation.
• Easy to change custom code (max. 4 custom code).
• Can be used jointly with wired remote controllers.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Built-in timers
Selectable from 4 different timer programs (on, off, program, and sleep).
Weekly timers
Weekly timer can be easily set by wireless remote controller. On and off can be set up to 4 times in a day, and up to 28 times in a week.
Program timer
The program timer operates the on and off timer once within a 24-hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/Dry operation
When the sleep timer is set, the set temperature automatically rises 1 °C every hour. The set temperature can rise up to a maximum of 2 °C.
Timer setting
Heating operation
When the sleep timer is set, the set temperature automatically drops 1 °C every 30 minutes. The set temperature can drop to a maximum of 4 °C.
60 min
1 °C
2 °C
- 4 -
Switching remote controller custom code
Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.)
After code change
AB CD
I.U. I.U. I.U. I.U.
ABCD
* I.U.: Indoor unit
Mixed-up
I.U. I.U. I.U. I.U.
WALL MOUNTED
ASTG30, 34KMTA
- 5 -
WALL MOUNTED
Signal
transmitter
10°C HEAT
button
TEMP.
button
POWERFUL
button
Start/Stop
button
TIMER SETTING button
SEND button
SELECT button
NEXT button
BACK button
OUTDOOR UNIT
LOW NOISE button
SWING button
SET button
WEEKLY button
ON/OFF button
SLEEP button
MODE button
SENSOR button
FAN button
RESET button
CLOCK ADJUST button
ECONOMY button
Mode indicator
ENERGY SAVING mode
indicator
LOW NOISE mode
indicator
Turns on when the SENSOR button is operated.
Clock & Timer indicator
SEND indicator
Transmit indicator
Temperature indicator
Fan speed indicator
Swing indicator

2-2. Overview

ASTG30, 34KMTA
NOTE: Functions may differ by type of the indoor unit. For details, refer to the operation manual.
Display panel
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current operation.
- 6 -

2-3. Specifications

Top view
Front view Side view
205
1761
48.5
5.5
26.2
69.3
6.5
Front View Side View
Bottom View
Ø 3.5 (Hole)
150
106.8
Hole
3.5
2-R
Controller
Unit: mm
WALL MOUNTED
ASTG30, 34KMTA
Size (H × W × D) mm 205 × 61 × 17 Weight g 122 (without batteries)
Holder
Unit: mm
Size (H × W × D) mm 150 × 69.3 × 26.2 Weight g 27
- 7 -

3. Specifications

WALL MOUNTED
ASTG30, 34KMTA
Typ e
Model name
Power supply 240 V ~ 50 Hz
Available voltage range 198—264 V
Star rating index 10-star standard
Cooling
Capacity
Heating
Cooling
Input power
Current
EER Cooling
COP Heating 3.84 3.63
Sensible capacity Cooling kW 6.00 6.95
Power factor
Moisture removal L/h (pints/h) 2.5 (4.4) 3.5 (6.16)
Maximum operating current *1
Fan
Sound pressure level *2
Heat exchanger type
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Drain hose
Operation range
Remote controller type Wireless (Wired [option])
International Protection rating IPX0
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.*1: Maximum current is maximum value when operated within the operation range.*2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Airflow rate
Type × Q'ty Cross flow fan × 1
Motor output W 80
Heating
Fan W 63 63
Cooling
Heating 10.1 12.9
Cooling
Heating 97 99
Cooling
Heating 17.0 20.5
Cooling
Heating
Cooling
Heating
Dimensions (H × W × D)
Fin pitch Main: 1.2, Sub: 1.4
Rows × Stages Main: 3 × 28, Sub1: 1 × 6, Sub2: 1 × 4
Pipe type Copper tube
Fin type Aluminum
Material Polystyrene
Color
Net
Gross 450 × 1,270 × 405
Net
Gross 24
Size
Method Flare
Material PVC
Size mm Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Cooling
Heating °C 16 to 30
Rated
Min.—Max.
Rated
Min.—Max.
Rated
Min.—Max. 0.58—3.85 0.59—4.03
Rated 2.34 2.84
Min.—Max. 0.50—4.01 0.60—4.24
Rated A
HIGH
MED 319 (1,150)
LOW 256 (920)
QUIET 200 (720)
HIGH 389 (1,400)
MED 319 (1,150)
LOW 256 (920)
QUIET 200 (720)
HIGH
MED 46 47
LOW 40 41
QUIET 33 34
HIGH 51 51
MED 44 44
LOW 39 38
QUIET 33 33
Liquid
Gas Ø 15.88 (Ø 5/8)
Cooling 2.0 2.0
Heating 3.0 2.5
kW 8.50 9.40
Btu/h 29,000 32,000
kW 2.9—10.5 2.9—11.2
Btu/h 9,900—35,800 9,900—38,200
kW 9.00 10.30
Btu/h 30,700 35,100
kW 2.2—11.2 2.7—11.7
Btu/h 7,500—38,200 9,200—39,900
kW
kW/kW
%
A
l/s (m3/h)
dB(A)
mm
mm
kg
mm (in)
°C 18 to 32
%RH 80 or less
ASTG30KMTA ASTG34KMTA
2.46 2.78
10.4 11.7
3.45 3.38
98.5 99
17.0 19.5
51 52
Wall mounted
Inverter heat pump
389 (1,400)
Main: 448 × 900 × 30
Sub1: 126 × 900 × 13.3
Sub2: 84 × 900 × 13.3
Approximate color of Munsell N 9.25/
White
340 × 1,150 × 280
18
Ø 9.52 (Ø 3/8)
- 8 -

4. Dimensions

Unit: mm
1150
Outline of unit
520
90
21
64
47961 108502
520
50
50
11
340
ø80
ø80
340
280
1150
609
672
725
WALL MOUNTED
ASTG30, 34KMTA
- 9 -
WALL MOUNTED
63 or more
80 or more
50 or more
49 or more
60 or more
Outline of unit
130 or more
1500 or more
1800 or more
Unit: mm

4-1. Installation space requirement

Provide sufficient installation space for product safety.
ASTG30, 34KMTA
- 10 -

5. Wiring diagram

WALL MOUNTED
ASTG30, 34KMTA
- 11 -
WALL MOUNTED

6. Capacity table

Capacity tables show each of following values calculated based on the outdoor temperature and the
ASTG30, 34KMTA
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)

6-1. Cooling capacity

Model: ASTG30KMTA
AFR
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
-10 6.25 5.14 0.75 6.96 5.17 0.76 7.20 5.62 0.76 7.67 5.64 0.77 7.91 6.09 0.77 8.39 6.07 0.78 8.86 6.46 0.79
0 6.16 5.09 0.80 6.86 5.12 0.81 7.10 5.56 0.82 7.57 5.58 0.83 7.80 6.03 0.83 8.27 6.00 0.84 8.74 6.40 0.85
5 6.13 5.05 0.85 6.83 5.08 0.87 7.07 5.53 0.87 7.53 5.55 0.88 7.77 5.99 0.88 8.23 5.96 0.89 8.70 6.35 0.90
10 6.11 5.02 0.90 6.80 5.05 0.92 7.04 5.49 0.92 7.50 5.51 0.93 7.73 5.95 0.94 8.20 5.93 0.95 8.66 6.31 0.96
15 6.65 5.27 1.25 7.41 5.31 1.27 7.67 5.77 1.28 8.17 5.79 1.29 8.42 6.25 1.30 8.93 6.22 1.31 9.43 6.63 1.32
20 7.20 5.53 1.60 8.02 5.56 1.62 8.30 6.05 1.63 8.84 6.07 1.65 9.12 6.55 1.65 9.66 6.52 1.67 10.21 6.95 1.69
25 6.95 5.41 1.79 7.74 5.45 1.82 8.00 5.92 1.83 8.53 5.94 1.85 8.80 6.41 1.86 9.32 6.39 1.88 9.85 6.81 1.90
30 6.63 5.20 2.08 7.39 5.23 2.12 7.64 5.68 2.13 8.14 5.70 2.15 8.40 6.16 2.16 8.90 6.13 2.18 9.40 6.53 2.20
35 6.72 5.29 2.37 7.48 5.32 2.41 7.74 5.79 2.42 8.25 5.81 2.45 8.50 6.27 2.46 9.01 6.24 2.48 9.52 6.65 2.51
40 5.56 4.77 2.08 6.20 4.80 2.11 6.41 5.22 2.12 6.83 5.23 2.14 7.04 5.65 2.15 7.46 5.63 2.18 7.89 6.00 2.20
46 4.74 4.47 2.11 5.28 4.50 2.15 5.46 4.89 2.16 5.82 4.91 2.18 6.00 5.30 2.19 6.36 5.28 2.21 6.72 5.62 2.23
m3/h
kW kW kW kW kW kW kW
1,400
Indoor temperature
Model: ASTG34KMTA
AFR
°CDB 18 21 23 25 27 29 32
°CWB 12 15 16 18 19 21 23
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
-10 8.76 5.57 1.13 9.76 5.61 1.15 10.09 6.10 1.16 10.76 6.12 1.17 11.09 6.61 1.18 11.76 6.58 1.19 12.42 7.01 1.20
0 8.68 5.55 1.20 9.67 5.58 1.21 10.00 6.07 1.22 10.66 6.09 1.23 10.99 6.57 1.24 11.65 6.55 1.25 12.31 6.97 1.26
5 8.63 5.59 1.27 9.61 5.62 1.29 9.94 6.11 1.30 10.59 6.13 1.31 10.92 6.62 1.32 11.58 6.60 1.33 12.23 7.03 1.35
10 8.60 5.66 1.37 9.57 5.69 1.40 9.90 6.19 1.40 10.55 6.21 1.42 10.88 6.71 1.42 11.53 6.68 1.44 12.19 7.11 1.45
15 8.55 5.65 1.54 9.52 5.68 1.56 9.85 6.17 1.57 10.50 6.19 1.58 10.82 6.69 1.59 11.47 6.66 1.61 12.12 7.10 1.62
20 8.77 5.40 1.89 9.77 5.43 1.92 10.10 5.90 1.93 10.77 5.92 1.95 11.10 6.40 1.96 11.77 6.37 1.98 12.43 6.79 2.00
25 8.90 5.50 2.24 9.91 5.54 2.27 10.25 6.02 2.28 10.92 6.04 2.31 11.26 6.52 2.32 11.94 6.50 2.34 12.61 6.92 2.37
30 9.17 5.62 2.65 10.22 5.65 2.70 10.57 6.14 2.71 11.26 6.16 2.74 11.61 6.66 2.75 12.31 6.63 2.78 13.00 7.06 2.81
35 7.43 5.53 2.68 8.27 5.56 2.72 8.55 6.05 2.74 9.12 6.07 2.77 9.40 6.55 2.78 9.96 6.52 2.81 10.53 6.95 2.84
40 8.01 5.21 3.04 8.92 5.24 3.09 9.23 5.69 3.10 9.84 5.71 3.14 10.14 6.17 3.15 10.75 6.14 3.18 11.36 6.55 3.21
46 6.79 4.75 3.07 7.57 4.77 3.12 7.83 5.19 3.14 8.34 5.21 3.17 8.60 5.62 3.18 9.12 5.60 3.21 9.63 5.97 3.25
m3/h
kW kW kW kW kW kW kW
1,400
Indoor temperature
- 12 -

6-2. Heating capacity

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
Model: ASTG30KMTA
WALL MOUNTED
ASTG30, 34KMTA
AFR
°CDB °CWB
-15 -16 7.65 3.91 7.47 3.99 7.29 4.08 7.10 4.16 6.92 4.24
-10 -11 8.32 3.92 8.12 4.00 7.92 4.08 7.72 4.17 7.52 4.25
-5 -7 8.98 3.93 8.77 4.01 8.55 4.09 8.34 4.17 8.12 4.26
0 -2 9.64 3.94 9.41 4.02 9.18 4.10 8.95 4.18 8.73 4.26
5 3 10.63 3.87 10.38 3.95 10.12 4.03 9.87 4.11 9.62 4.19
7 6 11.03 3.85 10.76 3.93 10.50 4.01 10.24 4.09 9.98 4.17
10 8 11.34 3.91 11.07 3.99 10.80 4.08 10.53 4.16 10.26 4.24
15 10 10.28 3.09 10.04 3.15 9.79 3.21 9.55 3.28 9.30 3.33
20 15 10.41 2.73 10.16 2.78 9.91 2.84 9.66 2.90 9.41 2.94
24 18 10.99 2.73 10.73 2.78 10.47 2.84 10.20 2.90 9.94 2.94
m3/h
16 18 20 22 24
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
Model: ASTG34KMTA
AFR
°CDB °CWB
-15 -16 8.87 3.70 8.66 3.77 8.45 3.85 8.24 3.93 8.03 4.01
-10 -11 8.94 3.87 8.73 3.95 8.51 4.03 8.30 4.12 8.09 4.20
-5 -7 9.85 4.07 9.61 4.15 9.38 4.24 9.14 4.32 8.91 4.41
0 -2 11.55 4.07 11.27 4.15 11.00 4.24 10.72 4.32 10.45 4.41
5 3 12.14 4.07 11.85 4.15 11.56 4.24 11.27 4.32 10.98 4.41
7 6 12.29 4.07 11.99 4.15 11.70 4.24 11.41 4.32 11.12 4.41
10 8 12.66 4.07 12.36 4.15 12.06 4.24 11.76 4.32 11.46 4.41
15 10 14.09 4.07 13.76 4.15 13.42 4.24 13.09 4.32 12.75 4.38
20 15 14.83 4.03 14.48 4.11 14.12 4.20 13.77 4.28 13.42 4.34
24 18 15.29 3.99 14.93 4.08 14.57 4.16 14.20 4.24 13.84 4.31
m3/h
16 18 20 22 24
TC IP TC IP TC IP TC IP TC IP
kW kW kW kW kW
1,400
Indoor temperature
1,400
Indoor temperature
- 13 -
WALL MOUNTED
1
2
3
4
0
1
2
3
4
(m)
(m)
Unit: m/s
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2.0 1.5 1.0
0.5
1
2
3
4
0
1
2
3
4
(m)
(m)
Unit: m/s
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0.5
0.5
1.0
1.0
2.0
1.5
1.5

7. Fan performance

ASTG30, 34KMTA

7-1. Air velocity distributions

Measuring conditions
Top v ie w Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
Fan speed Operation mode
HIGH FAN
Top v ie w Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right
(m)
3
Side view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center
2
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
(m)
Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center
3
2
2.0
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
1.5
1.0
- 14 -
2.0
1.5
Unit: m/s
0.5
1.0
(m)
Unit: m/s
0.5
(m)

7-2. Airflow

Models: ASTG30KMTA and ASTG34KMTA
Cooling
Fan speed Airflow
3
/h
m
HIGH
MED
LOW
QUIET
Heating
Fan speed Airflow
HIGH
MED
LOW
QUIET
l/s 389
CFM 824
3
m
/h
l/s 319
CFM 677
3
/h
m
l/s 256
CFM 542
3
m
/h
l/s 200
CFM 424
3
/h
m
l/s 389
CFM 824
3
m
/h
l/s 319
CFM 677
3
/h
m
l/s 256
CFM 542
3
m
/h
l/s 200
CFM 424
1,400
1,150
920
720
1,400
1,150
920
720
WALL MOUNTED
ASTG30, 34KMTA
- 15 -
WALL MOUNTED
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
80
70
60
50
40
30
20
10
0
Octave band center frequency, Hz
65 125 250 500 1,000 2,000 4,000 8,000
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
80
70
60
50
40
30
20
10
0
Octave band center frequency, Hz
65 125 250 500 1,000 2,000 4,000 8,000
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
HIGH
QUIET
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
80
70
60
50
40
30
20
10
0
Octave band center frequency, Hz
65 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
80
70
60
50
40
30
20
10
0
Octave band center frequency, Hz
65 125 250 500 1,000 2,000 4,000 8,000
HIGH
QUIET
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65

8. Operation noise (sound pressure)

ASTG30, 34KMTA

8-1. Noise level curve

Model: ASTG30KMTA
Cooling Heating
Model: ASTG34KMTA
Cooling Heating
- 16 -

8-2. Sound level check point

0.8 m
1 m
Microphone
Microphone
WALL MOUNTED
ASTG30, 34KMTA
- 17 -

9. Safety devices

WALL MOUNTED
ASTG30, 34KMTA
Type of
protection
Circuit protection Current fuse (PCB*) 250 V, 3.15 A
Thermistor protection
Fan motor protection
Power IC thermal shutdown protection
Protection form
Activate
Reset
Activate
Reset
ASTG30KMTA ASTG34KMTA
Fan motor speed down
Fan motor speed recover
Model
More than 85 °C
85 °C or less
150±15 °C
Fan motor stop
Less than 135 °C Fan motor restart
*PCB: Printed Circuit Board
- 18 -

10. External input and output

Rotary switchSW302
CN308
SW301
CN2 (Ext. in)
CN3 (Ext. out)
CN6 (Ext. in/out PCB)
External input and output PCBIndoor unit PCB
1
2
3
WALL MOUNTED
ASTG30, 34KMTA
PCB External input External output Connector Input select
Indoor unit
External input
and output
(UTY-XCSXZ1)
Operation/Stop Forced stop
Operation status
-
Operation/Stop Forced stop Forced thermostat off CN313 Edge
-
Error status Indoor unit fan
operation status
Operation status CN310 Error status CN311 Indoor unit fan
operation status
- CN2 Dry contact Edge
CN3 - -
CN313/
-
CN314
CN312
Dry contact/
Apply voltage
--
Edge/Pulse

10-1. External input

With using external input function, some functions on this product can be controlled from an external device.
Input
signal
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit connectors.
Connected unit

*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
- 19 -
PCB
Connector
(CN2)
WALL MOUNTED
1
2
3
Input 1
PCB
Connected unit
*
+
-
1
2
3
Input 2
*
+
-
Connector (CN313)
Connector (CN314)
1
2
3
Input 1
Power supply
PCB
Connected unit
*
*
*2
+-
1
2
3
Input 2
Connector
(CN313)
Connector
(CN314)
ASTG30, 34KMTA
External input and output PCB
The indoor unit Operation/Stop can be set by using the input connector on the PCB.
Input select
Use either one of these types of connectors according to the application. (Both types of connec­tors cannot be used simultaneously.)
•Dry contact In case of internal power supply, set the slide switch of SW301 to "NON VOL" side.
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
• Apply voltage In case of external power supply, set the slide switch of SW301 to "VOL" side.
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA. *2: Make the power supply DC 12 to 24 V, 10 mA or more.
- 20 -

10-2. External output

1
2
Connector (CN3)
LED
PCB
Resistor
Connected unit
+
-
1
2
Connected device
Connector (CN3)
PCBConnected unit Relay
(Operation status)
-
+
Use an external output cable with appropriate external dimension, depending on the number of ca­bles to be installed.
Indoor unit
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 23.
When indicator or other components are connected directly
Example: Function setting 60 is set to "00"
WALL MOUNTED
ASTG30, 34KMTA
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00"
- 21 -
WALL MOUNTED
1
2
Connector (CN310)
LED 1
(Operation status)
PCB
Resistor
Connected unit
+
-
1
2
Connector (CN311)
LED 2
(Error status)
Resistor
+
-
1
2
Connector (CN312)
LED 3
(Indoor unit fan
operation status)
Resistor
+
-
1
2
Connected device 1
Connector (CN310)
PCBConnected unit Relay
(Operation status)
-
+
1
2
Connected device 2
Connector (CN311)
(Error status)
-
+
1
2
Connected device 3
Connector (CN312)
(Indoor unit fan
operation status)
-
+
ASTG30, 34KMTA
External input and output PCB
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V±2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to Chapter 10-3. "Combination of external input and output" on page 23.
When indicator or other components are connected directly
Example: Function setting 60 is set to "00".
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00".
- 22 -

10-3. Combination of external input and output

By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
WALL MOUNTED
ASTG30, 34KMTA
External
Mode
1—8
Mode
1—8
Function
setting
0-1 60-00 1 Operation/Stop
0-2 60-00 2 Operation/Stop
60-01 to
60-08
9 60-09 B Operation/Stop
10 60-10 C Operation/Stop
Function
setting
0-1 60-00 1 Operation/Stop Operation/Stop Error status
0-2 60-00 2 Operation/Stop Not available
60-01 to
60-08
9 60-09 B Error status Not available
10 60-10 C
input and
output PCB
(Rotary SW)
3 - 9, A (Setting prohibited)
External
input and
output PCB
(Rotary SW)
3 - 9, A (Setting prohibited)
Indoor unit
Input
CN2 CN313 CN314 Signal type
Operation/Stop Not available Edge
Thermostat OFF
Thermostat OFF
Thermostat OFF
Indoor unit
Output
CN3 CN310 CN311 CN312
Indoor unit fan
operation status
External input
External input and output PCB
Operation Stop Pulse
Forced
Forced
Forced
External output
External input and output PCB
Not available Edge
Not available Edge
Not available Edge
Not available
Indoor unit fan
operation status
NOTE: Input of Operation/Stop depends on the setting of function setting 46. 00: Operation/Stop mode 1 (R.C. enabled) 01: (Setting prohibited) 02: Forced stop 03: Operation/Stop mode 2 (R.C. disabled)
- 23 -
WALL MOUNTED
Edge
Input signal type
Indoor unit Input signal type is only "Edge".
ASTG30, 34KMTA
External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW302) on the External input and output PCB.
Edge
The width of pulse must be longer than 200 msec.
Pulse
- 24 -

10-4. Details of function

On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
CN313
CN314
Control input function
When function setting is "Operation/Stop" mode 1
• In the case of "Edge" input
Function
setting /
46-00
Rotary SW on
External input and
output PCB
- Input of indoor unit CN2
60-00 / 1
CN313
Indoor unit
Remote controller
Operation
On
Off
Stop
External input Input signal Command
External input and
output PCB
CN313
On
Off On Operation On Off Stop Off On Operation On Off Stop
WALL MOUNTED
ASTG30, 34KMTA
• In the case of "Pulse" input
Function
setting /
46-00 60-00 / 1
Rotary SW on
External input and
output PCB
External input Input signal Command
External input and
output PCB
CN313 Pulse Operation CN314 Pulse Stop
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
- 25 -
WALL MOUNTED
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
CN313
CN314
On On On
Indoorunit
ASTG30, 34KMTA
When function setting is "Forced stop" mode
• In the case of "Edge" input
Function
setting /
46-02
Rotary SW on
External input and
External input Input signal Command
output PCB
- Input of indoor unit CN2
60-00 / 1
External input and
output PCB
CN313
Off On Forced stop On Off Normal Off On Forced stop On Off Normal
CN313
Forced stop
Indoor unit
Remote controller
Operation
• In the case of "Pulse" input
Function
setting /
46-02 60-00 / 1
Rotary SW on
External input and
output PCB
On
Off
Normal
Stop
External input Input signal Command
External input and
output PCB
On
On On
CN313 Pulse Forced stop CN314 Pulse Normal
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the remote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
- 26 -
When function setting is "Operation/Stop" mode 2
On
CN313
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote contoller
On OnOff
• In the case of "Edge" input
Function
setting /
46-03
Rotary SW on
External input and
External input Input signal Command
output PCB
- Input of indoor unit CN2
60-00 / 1
External input and
output PCB
CN313
Off On Operation
On Off
Off On Operation
On Off
Stop (R.C.
disabled)
Stop (R.C.
disabled)
WALL MOUNTED
ASTG30, 34KMTA
• In the case of "Pulse" input
Function
setting /
46-03 60-00 / 1
CN313
CN314
Indoor unit
(R.C. disabled)
Remote controller
Rotary SW on
External input and
output PCB
On
Off
On
Off
Operation
Stop
External input Input signal Command
External input and
output PCB
CN313 Pulse Operation
CN314 Pulse
On
Off
Stop (R.C.
disabled)
On
NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group
- 27 -
Forced thermostat off function
On Off
On
Off
Compressor
Room temp.
Set temp.
Input
Operation
Stop
High
Low
CN3
On
Off
CN310
Indoor unit
WALL MOUNTED
ASTG30, 34KMTA
Function
setting /
Rotary SW on
External input and
output PCB
60-00 / 2 60-09 / B
External input and output
60-10 / C
Control output function
Operation/Stop status
External input Input signal Command
Thermostat
off
Normal
operation
PCB
Off On
CN313
On Off
Function
setting /
Rotary SW on
External input and
output PCB
60-00 / 1, 2 Output of indoor unit CN3
60-00 / 1
External input and output
The output is low when the unit is stopped.
External output
PCB
CN310
Output
signal
Command
Low High Operation High Low Stop
Off On Operation On Off Stop
- 28 -
Error status
Error
Normal
High
Low
CN3
On
Off
CN310―312
Indoor unit
Fan run
Fan stop
High
Low
CN3
On
Off
CN311―312
Indoor unit
Function
setting /
Rotary SW on
External input and
output PCB
External output
60-09 / B Output of indoor unit CN3
60-00 / 1
External input and output
PCB
CN311
The output is ON when an error is generated for the indoor unit.
Indoor unit fan operation status
Function
setting /
Rotary SW on External
input and output PCB
External output
60-10 / C Output of indoor unit CN3
60-00 / 1
External input and output
PCB
CN312
Output
signal
Command
Low High Error High Low Normal
Off On Error On Off Normal
Output
signal
Command
Low High Fan run High Low Fan stop
Off On Fan run On Off Fan stop
WALL MOUNTED
ASTG30, 34KMTA
Output signal Condition
On
Low High
The indoor unit fan is operating.
Off The fan is stopped or during cold air prevention.
High Low During thermostat off when in dry mode operation.
- 29 -
WALL MOUNTED
(Factory setting)
2WIRE/3WIRE
2WIRE/3WIRE
Indoor unit main PC board
JM9
2WIRE/3WIRE
2WIRE/3WIRE

11. Function settings

To adjust the functions of this product according to the installation environment, various types of
ASTG30, 34KMTA
function settings are available.
NOTE: Incorrect settings can cause a product malfunction.

11-1. Function settings on indoor unit

Depending on the connected remote controller type, following setting is required:
Connected remote controller DIP switch Jumper (JM9)
2-wire-type wired remote controller is connected
JM9
(Disconnected)
JM9
3-wire-type wired remote controller is connected
(Connected)
Component location
Component on the indoor unit main PC board used for this setting is located as shown in the following figure.
(Factory setting)
- 30 -

11-2. Function settings by using remote controller

Function number
Setting value
Some function settings can be changed on the remote controller. After confirming the setting proce­dure and the content of each function setting, select appropriate functions for your installation envi­ronment.
NOTE: Incorrect settings can cause a product malfunction.
Setting procedure by using wireless remote controller
The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Before turning on the power of the indoor unit, reconfirm following items:
• Cover for the electrical enclosure on the outdoor unit is in place.
• There is no wiring mistake.
• Piping air tight test and vacuuming have been performed firmly.
• All the necessary wiring work for outdoor unit has been finished.
After reconfirming the items listed above, turn on the power of the indoor unit.
NOTES:
• Settings will not be changed if invalid numbers or setting values are selected.
• When optional wired remote controller is used, refer to the installation manual enclosed with the remote controller.
WALL MOUNTED
ASTG30, 34KMTA
Entering function setting mode
While pressing the POWERFUL button and TEMP. ( ) button simultaneously, press the RESET button to enter the function setting mode.
Selecting the function number and setting value
1. Press the TEMP. ( ) ( ) buttons to select the function number. To switch between the left and right digits, press the 10 °C HEAT button.
2. Press the POWERFUL button to proceed to value setting. To return the function number selection, press the POWERFUL button again.
3. Press the TEMP. ( ) ( ) buttons to select the setting value. To switch between the left and right digits, press the 10 °C HEAT button.
4. Press the MODE button once to send the function setting informa­tion. Confirm that you hear the beep sound.
5. Press the START/STOP button to fix the function setting. Confirm that you hear the beep sound.
6. Press the RESET button to end the function setting mode.
7. After completing the function setting, be sure to turn off the power and turn it on again.
- 31 -
WALL MOUNTED
!
CAUTION
After turning off the power, wait 30 seconds or more before turning on the power again. The function setting will not become active unless the power is turned off then on again.
ASTG30, 34KMTA
NOTES:
• The air conditioner custom code is set to prior to shipment.
• If you do not know the air conditioner custom code setting, try each of the custom codes ( ) until you find the code that operates the air conditioner.
- 32 -
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ­ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
Function no. Functions
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
00
11
30/31
35/36
40
42
44
46
48
49
60
1) Remote controller address setting
NOTE: Because this setting is normally done automatically when 2-wire-type wired remote
controller is installed, setting is unnecessary.
Multiple indoor units can be operated by using one wired remote controller. Set the unit number of each indoor unit.
Remote controller address setting
Filter sign
Room temperature control for indoor unit sensor
Room temperature control for wired remote controller sensor
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
Switching functions for external output terminal
WALL MOUNTED
ASTG30, 34KMTA
Function number Setting value Setting description Factory setting
00 Unit no. 0 01 Unit no. 1 02 Unit no. 2 03 Unit no. 3 04 Unit no. 4 05 Unit no. 5 06 Unit no. 6
00
07 Unit no. 7 08 Unit no. 8 09 Unit no. 9 10 Unit no. 10
11 Unit no. 11 12 Unit no. 12 13 Unit no. 13 14 Unit no. 14 15 Unit no. 15
NOTES:
• When connecting Polar 3-core wired remote controller, set the remote controller address in the
order of 0, 1, 2, ....., and 15.
• When different type of indoor units (such as wall-mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
- 33 -
WALL MOUNTED
ASTG30, 34KMTA
2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
00 Standard (400 hours)
11
01 Long interval (1,000 hours) 02 Short interval (200 hours) 03 No indication
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re­quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur­er’s recommended value).
Function number Setting value Setting description
00 Standard setting 01 No correction 0.0 °C 02 -0.5 °C 03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C
30
(For cooling)
31
(For heating)
08 -3.5 °C 09 -4.0 °C 10 +0.5 °C 11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
Factory
setting
More cooling Less heating
Less cooling
More heating
- 34 -
4) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
WALL MOUNTED
ASTG30, 34KMTA
Function number Setting value Setting description
00 No correction 01 No correction 0.0°C 02 -0.5 °C 03 -1.0 °C 04 -1.5 °C 05 -2.0 °C 06 -2.5 °C 07 -3.0 °C
35
(For cooling)
36
(For heating)
08 -3.5 °C 09 -4.0 °C 10 +0.5 °C
11 +1.0 °C 12 +1.5 °C 13 +2.0 °C 14 +2.5 °C 15 +3.0 °C 16 +3.5 °C 17 +4.0 °C
Factory
setting
More cooling Less heating
Less cooling
More heating
5) Auto restart
Enables or disables automatic restart after a power interruption.
Function number Setting value Setting description Factory setting
40
00 Enable 01 Disable
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external device.
6) Room temperature sensor switching
(Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number Setting value Setting description Factory setting
42
00 Indoor unit 01 Both
00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
- 35 -
WALL MOUNTED
ASTG30, 34KMTA
7) Remote controller custom code
(Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
00 A
44
01 B 02 C 03 D
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number Setting value Setting description Factory setting
00 Operation/Stop mode 1
46
01 (Setting prohibited) 02 Forced stop mode 03 Operation/Stop mode 2
9) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
Function number Setting value Setting description Factory setting
48
00 Both 01 Wired remote controller
10) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
00 Disable
49
01 Enable 02 Remote controller
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially invalidated.
• When connecting VRF system using network converter, this setting must be set to "00" or "01".
11) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and output”.
Function number Setting value Setting description Factory setting
00 Operation status
60
09 Error status 10 Indoor unit fan operation status
- 36 -

11-3. Custom code setting for wireless remote controller

To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required.
NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom
code.
When 2 or more air conditioners are installed in a room, and the remote controller is operating an air conditioner other than the one you wish to set, change the custom code of the remote controller to operate only the air conditioner you wish to set. (4 selections possible.)
Confirm the setting of the remote controller custom code and the function setting. If these do not match, the remote controller cannot be used to operate for the air conditioner.
1. Press the START/STOP button until only the clock is displayed on the remote controller display.
2. Press the MODE button for at least 5 seconds to display the current custom code. (Initially set to .)
3. Press the TEMP. ( ) ( ) buttons to change the custom code between → → → . Match the code on the display to the air conditioner custom code. (Initially set to .)
WALL MOUNTED
ASTG30, 34KMTA
4. Press the MODE button again to return to the clock display. The custom code will be changed.
Notes:
• If no button is pressed within 30 seconds after the custom code is displayed, the system returns to the original clock indicator. In this case, start again from step 1.
• The air conditioner custom code is set to prior to shipment. To change the custom code, contact your retailer.
• If you do not know the assigned code for the air conditioner, try each of the custom code ( ) until you find the code which operates the air conditioner.
- 37 -
WALL MOUNTED

12. Optional parts

ASTG30, 34KMTA

12-1. Controllers

Exterior Part name Model name Summary
Wired remote
controller
Wired remote
controller
Simple remote
controller
UTY-RNRYZ1
UTY-RVNYN
UTY-RSNYN
Easy finger touch operation with LCD panel. Backlight enables easy operation in a darkened room. Wire type: Non-polar 2-core Optional communication kit is necessary for installation.
Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wire type: Polar 3-core Optional communication kit is necessary for installation.
Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Polar 3-core Optional communication kit is necessary for installation.
- 38 -

12-2. Others

Exterior Part name Model name Summary
WALL MOUNTED
ASTG30, 34KMTA
External
connect kit
External input
and output PCB
External input
and output PCB
box
Communication
kit
Communication
kit
UTY-XWZX
UTY-XCSXZ1
UTZ-GXXB
UTY-TWRX
UTY-XWNX
Use to connect with various peripheral devices and air conditioner PCB.
Use to connect with external devices and air conditioner PCB.
For installing the External input and output PCB.
Use to connect Non-polar 2-core wired remote controller.
Use to connect Polar 3-core wired remote controller.
- 39 -
WALL MOUNTED
ASTG30, 34KMTA
- 40 -

Part 2. OUTDOOR UNIT

SINGLE TYPE: AOTG30KMTA AOTG34KMTA
OUTDOOR UNIT
AOTG30, 34KMTA

1. Specifications

1-1. Model: AOTG30KMTA

Typ e Inverter heat pump
Model name
Power supply 240 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A 10.4
Fan
Sound pressure level *1
Sound power level dB(A) 67
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Operation range
Drain hose
International protection rating IPX4
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 7.5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.*1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Airflow rate
Type × Q'ty Propeller fan × 1
Motor output W 100
Type × Q'ty Hermetic motor compressor × 1
Motor output W 2,200
Net
Gross 970 × 1,050 × 445
Net
Gross 67
Size
Method Flare
Pre-charge length
Max. length 50
Max. height difference 30
Cooling
Heating 945 (3,400)
Cooling
Heating 54
Dimensions (H × W × D)
Fin pitch 1.30
Rows × Stages 2 × 38
Pipe type Copper
Fin type
Typ e R32
Charge g 1,650
Typ e RmM68AF
Amount
Material Steel sheet
Color
Liquid
Gas Ø 15.88 (Ø 5/8)
Cooling
Heating -15 to 24
Material LDPE
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
l/s (m3/h)
dB(A)
mm
Type (Material) Corrugate (Aluminum)
Surface treatment Corrosion resistance (Blue fin)
3
cm
Approximate color of MUNSELL 10YR7.5/1.0
mm
kg
mm
m
°C
AOTG30KMTA
861 (3,100)
50
798 × 900 × 36.4
800
Beige
830 × 900 × 330
61
Ø 9.52 (Ø 3/8)
20
-10 to 46
- 42 -

1-2. Model: AOTG34KMTA

Typ e Inverter heat pump
Model name
Power supply 240 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A 12.9
Fan
Sound pressure level *1
Sound power level dB(A) 67
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions (H × W × D)
Weight
Connection pipe
Operation range
Drain hose
International protection rating IPX4
NOTES:
Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB. – Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB. – Pipe length: 7.5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.*1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber. – Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Airflow rate
Type × Q'ty Propeller fan × 1
Motor output W 111
Type × Q'ty Hermetic motor compressor × 1
Motor output W 2,200
Net
Gross 1,048 × 1,064 × 479
Net
Gross 82
Size
Method Flare
Pre-charge length
Max. length 50
Max. height difference 30
Cooling
Heating 1,139 ( 4,100)
Cooling
Heating 54
Dimensions (H × W × D)
Fin pitch 1.45
Rows × Stages Main: 2 × 42, Sub: 1 × 42
Pipe type Copper
Fin
Type R32
Charge g 2,000
Type RmM68AF
Amount
Material Steel sheet
Color
Liquid
Gas Ø 15.88 (Ø 5/8)
Cooling
Heating -15 to 24
Material LDPE
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
l/s (m3/h)
dB(A)
Main: 882 × 957 × 18.19 & 882 × 927 × 18.19
mm
Type (Material) Corrugate (Aluminum)
Surface
treatment
3
cm
mm
kg
mm (in)
m
°C
Sub: 882 × 580 × 18.19
Corrosion resistance (Blue fin)
Approximate color of Munsell 10YR7.5/1.0
AOTG34KMTA
1,139 (4,100)
50
800
Beige
914 × 970 × 370
75
Ø 9.52 (Ø 3/8)
30
-10 to 46
OUTDOOR UNIT
AOTG30, 34KMTA
- 43 -
OUTDOOR UNIT
900
650
830
370
99
196
21
9
77
31 330
400
170
147
12
Top view
Front view Side view
Bottom view
Airflow
4-Ø12 mm hole
Drain cap
mounting places
Drain pipe mounting place
Unit: mm
AOTG30, 34KMTA

2. Dimensions

2-1. Model: AOTG30KMTA

- 44 -

2-2. Model: AOTG34KMTA

37024
914
166
650
154
410
51: Gas
43:
Liquid
40
4
368
Unit : mm
OUTDOOR UNIT
AOTG30, 34KMTA
Top view
24
970
Terminal blocks
3-Way valve
(Liquid)
3-Way valve
(Gas)
Ø28
21
8
87
89
131
25
50
Pipe port
279
297
(Gas valve)
(Liquid valve)
95
661
120
50
21
55
12370
111
ø 28: Cable port
ø28: Cable port
Pipe port
155
142
65
ø28: Cable port ø28: Cable port Pipe port
50 70
21
341
305
50
227
Front view
438
622
Ø28
: Cable port
Bottom view
65 15
Detail A
Side view
14
50
Pipe & cable port
Rear view
- 45 -

2-3. Installation space requirement

100 or more
250 or more
300 or more
100 or more
600 or more
300 or more
Max. 500
600 or more
1,000 or more
100 or more
250 or more
500 or more
Max. 500
Provide sufficient installation space for product safety.
Model: AOTG30KMTA
Single outdoor unit installation
When the upper space is open:
OUTDOOR UNIT
AOTG30, 34KMTA
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the rear and sides.
When there are obstacles at the front only. When there are obstacles at the front and rear.
100 or more
600 or more
When there is an obstruction in the upper space:
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
Unit: mm
- 46 -
Multiple outdoor unit installation
300
250 or more
or more
500 or more
1,500 or more
250 or more
1,500 or more
500 or more
250 or more
250 or more
Max. 300
1,500 or more
When the upper space is open:
When there are obstacles at the rear only. When there are obstacles at the front only.
250 or more
1,500 or more
When there are obstacles at the front and rear.
Unit: mm
OUTDOOR UNIT
AOTG30, 34KMTA
When there is an obstruction in the upper space:
When there are obstacles at the rear and above.
Unit: mm
- 47 -
OUTDOOR UNIT
!
CAUTION
150 or more
600 or more
1,000 or more
2,000 or more
500 or more
600 or more
1,500 or more
250 or more
3,000 or more
250 or more
AOTG30, 34KMTA
Outdoor unit installation in multi-row
Unit: mm
Single parallel unit arrangement Multiple parallel unit arrangement
150
250 or more
1,500 or more
500 or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
- 48 -
Model: AOTG34KMTA
150 or more
1,000 or more
300 or more
Max. 500
1,000 or more
Single outdoor unit installation
When the upper space is open:
When there are obstacles at the rear only. When there are obstacles at the rear and sides.
Unit: mm
OUTDOOR UNIT
AOTG30, 34KMTA
150 or more
200
or more
200 or more
300 or more
When there are obstacles at the front only. When there are obstacles at the front and rear.
1,000 or more
When there is an obstruction in the upper space:
When there are obstacles at the rear and above.
When there are obstacles at the rear, sides, and above.
Max. 500
1,500 or more
Unit: mm
- 49 -
250 or more
500 or more
250 or more
OUTDOOR UNIT
300
or more
250 or more
1,500 or more
250 or more
AOTG30, 34KMTA
Multiple outdoor unit installation
When the upper space is open:
Unit: mm
When there are obstacles at the rear only. When there are obstacles at the front only.
When there are obstacles at the front and rear.
250 or more
500 or more
1,500 or more
When there is an obstruction in the upper space:
When there are obstacles at the rear and above.
Max. 300
250 or more
1,500 or more
1,500 or more
500 or more
Unit: mm
- 50 -
Outdoor unit installation in multi-row
!
CAUTION
500 or more
600 or more
1,500 or more
3,000 or more
500 or more
600 or more
1,500 or more
250 or more
3,500 or more
250 or more
150
1,500 or more
500 or more
250 or more
Single parallel unit arrangement Multiple parallel unit arrangement
Unit: mm
OUTDOOR UNIT
AOTG30, 34KMTA
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation efficiency.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and a pedestal, or place the unit on a high stand that is locally installed.
- 51 -
OUTDOOR UNIT
AOTG30, 34KMTA

3. Refrigerant circuit

3-1. Model: AOTG30KMTA

- 52 -

3-2. Model: AOTG34KMTA

OUTDOOR UNIT
AOTG30, 34KMTA
- 53 -
OUTDOOR UNIT
AOTG30, 34KMTA

4. Wiring diagrams

4-1. Model: AOTG30KMTA

- 54 -

4-2. Model: AOTG34KMTA

OUTDOOR UNIT
AOTG30, 34KMTA
- 55 -
OUTDOOR UNIT
Height difference H (m)
Height difference H (m)
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
AOTG30, 34KMTA

5. Capacity compensation rate for pipe length and height difference

5-1. Model: AOTG30KMTA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
5 7.5 10 20 30 40 50 30 - - - - 0.926 0.916 0.906 20 - - - 0.953 0.942 0.931 0.920 10 - - 0.979 0.968 0.958 0.946 0.936
7.5 - 0.988 0.983 0.972 0.961 0.951 0.939 5 0.992 0.992 0.987 0.976 0.965 0.954 0.943 0 1.000 1.000 0.995 0.984 0.973 0.962 0.951
-5 1.000 1.000 0.995 0.984 0.973 0.962 0.951
-7.5 - 1.000 0.995 0.984 0.973 0.962 0.951
-10 - - 0.995 0.984 0.973 0.962 0.951
-20 - - - 0.984 0.973 0.962 0.951
-30 - - - - 0.973 0.962 0.951
Pipe length (m)
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
Pipe length (m)
5 7.5 10 20 30 40 50 30 - - - - 0.931 0.914 0.899 20 - - - 0.954 0.931 0.914 0.899 10 - - 0.990 0.954 0.931 0.914 0.899
7.5 - 1.000 0.990 0.954 0.931 0.914 0.899 5 1.000 1.000 0.990 0.954 0.931 0.914 0.899 0 1.000 1.000 0.990 0.954 0.931 0.914 0.899
-5 0.995 0.995 0.986 0.949 0.926 0.909 0.895
-7.5 - 0.993 0.983 0.946 0.924 0.907 0.892
-10 - - 0.981 0.944 0.921 0.904 0.890
-20 - - - 0.935 0.912 0.895 0.881
-30 - - - - 0.903 0.886 0.872
- 56 -

5-2. Model: AOTG34KMTA

Height difference H (m)
Height difference H (m)
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
5 7.5 10 20 30 40 50 30 - - - - 0.902 0.882 0.862 20 - - - 0.938 0.917 0.897 0.876 10 - - 0.973 0.953 0.933 0.912 0.891
7.5 - 0.988 0.977 0.957 0.936 0.916 0.895 5 0.992 0.992 0.981 0.961 0.940 0.919 0.898 0 1.000 1.000 0.989 0.968 0.947 0.926 0.905
-5 1.000 1.000 0.989 0.968 0.947 0.926 0.905
-7.5 - 1.000 0.989 0.968 0.947 0.926 0.905
-10 - - 0.989 0.968 0.947 0.926 0.905
-20 - - - 0.968 0.947 0.926 0.905
-30 - - - - 0.947 0.926 0.905
Pipe length (m)
OUTDOOR UNIT
AOTG30, 34KMTA
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
Pipe length (m)
5 7.5 10 20 30 40 50 30 - - - - 0.978 0.968 0.958 20 - - - 0.988 0.978 0.968 0.958 10 - - 0.998 0.988 0.978 0.968 0.958
7.5 - 1.000 0.998 0.988 0.978 0.968 0.958 5 1.000 1.000 0.998 0.988 0.978 0.968 0.958 0 1.000 1.000 0.998 0.988 0.978 0.968 0.958
-5 0.998 0.995 0.993 0.983 0.973 0.963 0.953
-7.5 - 0.993 0.991 0.981 0.971 0.961 0.951
-10 - - 0.988 0.978 0.968 0.958 0.948
-20 - - - 0.968 0.958 0.959 0.939
-30 - - - - 0.949 0.949 0.929
- 57 -
OUTDOOR UNIT
AOTG30, 34KMTA

6. Additional charge calculation

6-1. Model: AOTG30KMTA

Refrigerant type R32 Refrigerant amount g 1,650
Refrigerant charge
Total pipe length m 20 or less 30 40 50 (Max.) Additional charge g 0 400 800 1,200

6-2. Model: AOTG34KMTA

Refrigerant type R32 Refrigerant amount g 2,000
Refrigerant charge
Total pipe length m 30 or less 40 50 (Max.) Additional charge g 0 450 900
40 g/m
45 g/m
- 58 -

7. Airflow

7-1. Model: AOTG30KMTA

Cooling
m3/h
l/s 861
CFM 1,825
Heating
3
/h
m
l/s 945
CFM 2,001

7-2. Model: AOTG34KMTA

Cooling
3
m
/h
l/s 1,139
CFM 2,413
3,100
3,400
4,100
OUTDOOR UNIT
AOTG30, 34KMTA
Heating
3
m
/h
l/s 1,139
CFM 2,413
4,100
- 59 -
OUTDOOR UNIT
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
80
70
60
50
40
30
20
10
0
Octave band center frequency, Hz
65 125 250 500 1,000 2,000 4,000 8,000
NC-20
NC-40
NC-50
NC-60
NC-15
NC-25
NC-45
NC-55
NC-65
NC-30
NC-35
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
80
70
60
50
40
30
20
10
0
Octave band center frequency, Hz
65 125 250 500 1,000 2,000 4,000 8,000
NC-20
NC-50
NC-60
NC-30
NC-15
NC-25
NC-45
NC-55
NC-65
NC-40
NC-35
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
80
70
60
50
40
30
20
10
0
Octave band center frequency, Hz
65 125 250 500 1,000 2,000 4,000 8,000
NC-20
NC-40
NC-50
NC-60
NC-15
NC-25
NC-45
NC-55
NC-65
NC-30
NC-35
Octave band sound pressure level, dB: (0 dB=0.0002 μbar)
80
70
60
50
40
30
20
10
0
Octave band center frequency, Hz
65 125 250 500 1,000 2,000 4,000 8,000
NC-20
NC-50
NC-60
NC-30
NC-15
NC-25
NC-45
NC-55
NC-65
NC-40
NC-35
AOTG30, 34KMTA

8. Operation noise (sound pressure)

8-1. Noise level curve

Model: AOTG30KMTA
Cooling Heating
Model: AOTG34KMTA
Cooling Heating
- 60 -

8-2. Sound level check point

1 m
1.5 m
Airflow
Center
MicrophoneMicrophone
Front
Front viewSide view
NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated
above.
OUTDOOR UNIT
AOTG30, 34KMTA
- 61 -

9. Electrical characteristics

OUTDOOR UNIT
AOTG30, 34KMTA
Model name
Power supply
Max operating current *1 A 17.0 19.5 Starting current A 10.4 12.9
Wiring spec. *2
Voltage V 240 ~ Frequency Hz 50
Circuit breaker current A 32 Power cable
Connection cable *3
Limited wiring length m 51
mm
mm
2
2
AOTG30KMTA AOTG34KMTA
2.5 4.0
1.5—2.5
*1: Maximum current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 62 -

10. Safety devices

Type of
protection
Circuit protection
Fan motor protection
Compressor protection
High pressure protection
Low pressure protection
Protection form
Current fuse (Near the terminal) 250 V, 25 A 250 V, 25 A Current fuse (Filter PCB) 250 V, 10 A 250 V, 10 A Current fuse (Main PCB) 250 V, 3.15 A 250 V, 3.15 A
Activate
Thermal protection
Reset
Activate
Thermistor protection
Reset
Terminal protection program (Compressor temp.)
Thermal protection program (Discharge temp.)
Pressure switch
Pressure sensor
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
AOTG30KMTA AOTG34KMTA
150±15 °C
Fan motor stop
120±15 °C
Fan motor restart
Model
More than 80 °C
Fan motor speed down
80 °C or less
Fan motor speed recover
120 °C
Compressor stop
80 °C
Compressor restart
110°C
Compressor stop
After 7 minutes
Compressor restart
4.2±0.1 MPa
Compressor stop
3.2±0.15 MPa
Compressor restart
0.12 MPa
Compressor stop
0.15 MPa
Compressor restart
OUTDOOR UNIT
AOTG30, 34KMTA
- 63 -
OUTDOOR UNIT
On
Off
On
Off
Input signal
Low noise mode
AOTG30, 34KMTA

11. External input and output (for AOTG34KMTA)

With using external input and output functions, this product can be operated inter-connectedly with an external device.
Connector Input Output Remarks
CN10 Low noise mode — CN11 Peak cut mode — CN12 Error status CN13 Compressor status
See external input/output
settings for details.

11-1. External input

With using external input function, on/off status of “Low noise mode” and “Peak cut mode” can be specified by the external signal.
Low noise mode
In following condition, the operating noise of the outdoor unit reduces comparing from the one in normal operating condition:
• The air conditioner is set to the “Low noise mode” when closing the contact input of a commercial timer or on/off switch to a connector on the control PCB of the outdoor unit.
NOTE: Product performance may drop depending on some conditions such as the outdoor
temperature.
Circuit diagram example
Outdoor unit control PCB
Connector
1
2
Connected unit
Example: Switch
*10 m
Signal
Locally purchased
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit within 10 m.
• Construct a circuit as shown in this figure with using optional parts mentioned below.
• Input signal: On in “Low noise mode”
• Input signal: Off in normal operation
• To set the level of “Low noise mode”, refer to “Low noise mode” on page 70.
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
- 64 -
Peak cut mode
Outdoor unit
control PCB
Connected unit
Example: Switch
Connector
1
2
Signal
Locally purchased
*10 m
On
Off
On
Off
Input signal
Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
• The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial timer or on/off switch to a connector on the control PCB of the outdoor unit.
Circuit diagram example
• Contact capacity: DC 24 V or more, 10 mA or more.
• *: Make the distance from the PCB to the connected unit within 10 m.
• Construct a circuit as shown in this figure with using optional parts mentioned below.
• Input signal: On in “Peak cut mode”
• Input signal: Off in normal operation
• To set the level of “Peak cut mode”, refer to “Peak cut mode” on page 71.
OUTDOOR UNIT
AOTG30, 34KMTA
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
- 65 -

11-2. External output

Signal
Outdoor unit
control PCB
Connected unit
Connector
1
2
Locally purchased
*10 m
Vcc
+
+
-
Load
Vcc
Power supply
Error
Normal
On
Off
Error status
Output signal
With using external output function, some status signals are transmitted to the control PCB, and the related LED lamp indicates the status of this product.
Error status output
Circuit diagram example
OUTDOOR UNIT
AOTG30, 34KMTA
• 1: Power supply Voltage (Vcc): DC 24 V or less
• 2: Load DC 500 mA or less
• *: Make the distance from the PCB to the connected unit within 10 m.
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
- 66 -
Compressor status output
Signal
Outdoor unit
control PCB
Connected unit
Connector
1
2
Locally purchased
*10 m
Vcc
+
+
-
Load
Vcc
Power supply
Operation
Stop
On
Off
Compressor status
Output signal
Circuit diagram example
• 1: Power supply Voltage (Vcc): DC 24 V or less
• 2: Load DC 500 mA or less
• *: Make the distance from the PCB to the connected unit within 10 m.
OUTDOOR UNIT
AOTG30, 34KMTA
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
- 67 -
OUTDOOR UNIT
!
CAUTION
AOTG30, 34KMTA

12. Function settings (for AOTG34KMTA)

Perform appropriate function setting locally according to the installation environment.
NOTE: Incorrect settings can cause a product malfunction.
• Before setting up the switch buttons, discharge the static electricity from your body.
• Never touch the terminals or the patterns on the parts that are mounted on the PCB.

12-1. Local setting switch buttons

Control PCB and switch buttons location
Control PCB of the outdoor unit is located as shown in the following figure.
LED lamps
Switch buttons
Terminal block
- 68 -
Switch buttons and the functions
SW1
SW2
SW3 SW4 SW5
(1) (2) (3) (4) (5)
LED lamps
Switch buttons
LED lamp Function or operation method
(1) POWER/MODE Green
(2) ERROR Red Blinks during error operation. (3) PUMP DOWN (L1) Orange Lights on during pump down operation.
LOW NOISE
(4)
MODE
Orange
(L2 and L3) PEAK CUT MODE
(5)
(L4, L5, and L6)
Orange
Lights on while power on. Local setting in outdoor unit or error code is displayed with blink.
Lights on during “Low noise mode” when local setting is activated. (Lighting pattern of L2 and L3 indicates low noise level.)
Lights on during “Peak cut mode” when local setting is activated. (Lighting pattern of L4, L5, and L6 indicates peak cut level.)
OUTDOOR UNIT
AOTG30, 34KMTA
Switch button Function or operation method
SW1 MODE Switches between “Local setting” and “Error code display”.
SW2 SELECT
SW3 ENTER
Switches between the individual “Local settings” and the “Error code displays”.
Switches between the individual “Local settings” and the “Error code
displays”. SW4 EXIT Returns to “Operation status display”. SW5 PUMP DOWN Starts the pump down operation.
- 69 -
OUTDOOR UNIT
SW1
SW2
SW3 SW4 SW5
(1) (2) (3) (4) (5)
LED lamps
Switch buttons
POWER
MODE
ERROR
(L1) (L2) (L3) (L4) (L5) (L6)
PUMP
DOWN
LOW NOISE PEAK CUT
Blinks
(9 times
)
Sign “ ”: Lights off
(L2) (L3)
LOW NOISE
LOW NOISE
MOD
E
Sign “ ”: Lights on
AOTG30, 34KMTA

12-2. Local setting procedure

NOTE: Before performing the function setting, be sure to stop the operation of the air conditioner.
Low noise mode
1. Press the MODE switch button (SW1) for 3 seconds or more to switch to “Local setting mode”.
2. After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch button (SW3).
3. Press the SELECT switch button (SW2), and adjust the LED lamp as shown below. Then the LED lamp indicates the current setting.
LOW NOISE
(L3)
(L2)
LOW NOISE
MODE
Blink
4. Press the ENTER switch button (SW3).
5. Press the SELECT switch button (SW2), and adjust the LED lamps as shown below.
MODE 1
MODE 2
PEAK CUT
(L4) (L5) (L6)
Blink
Blink
- 70 -
6. Press the ENTER switch button (SW3) and fix it.
SW1
SW2
SW3 SW4 SW5
(1) (2) (3) (4) (5)
LED lamps
Switch buttons
PEAK CUT
(L4) (L5) (L6)
MODE 1
MODE 2
7. To return to “Operating status display (Normal operation)”, press the EXIT switch button (SW4).
In case of missing how many times you pressed the SELECT and ENTER switch buttons:
1. To return to “Operation status display (Normal operation)”, press the EXIT switch button once.
2. Restart from the beginning of setting procedure.
NOTE: In case of missing how many times you pressed the SELECT and ENTER switch buttons,
you must redo the setting procedure. Return to “Operation status display (Normal opera­tion)” by pressing the EXIT switch button once, and restart from the beginning of the setting procedure.
Peak cut mode
OUTDOOR UNIT
AOTG30, 34KMTA
1. Press the MODE switch button (SW1) for 3 seconds or more to switch to “Local setting mode”.
2. After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch button (SW3).
3. Press the SELECT switch button (SW2), and adjust the LED lamp as shown below. Then the LED lamp indicates the current setting.
POWER
ERROR
MODE
PUMP
DOWN
(L1) (L2) (L3) (L4) (L5) (L6)
Blinks
(9 times
)
Sign “ ”: Lights off
PEAK CUT
LOW NOISE PEAK CUT
LOW NOISE
(L3)
MOD
(L2)
E
Blink
- 71 -
4. Press the ENTER switch button (SW3).
(L2) (L3)
LOW NOISE
PEAK CUT
MODE
Sign “ ”: Lights on
100 % of rated input ratio
75 % of rated input ratio
50 % of rated input ratio
0 % of rated input ratio
Blink
Blink Blink
Blink
Blink
PEAK CUT
(L4) (L5) (L6)
100 % of rated input ratio
75 % of rated input ratio
50 % of rated input ratio
0 % of rated input ratio
PEAK CUT
(L4) (L5) (L6)
OUTDOOR UNIT
AOTG30, 34KMTA
5. Press the SELECT switch button (SW2), and adjust the LED lamps as shown below.
6. Press the ENTER switch button (SW3) and fix it.
7. To return to “Operating status display (Normal operation)”, press the EXIT switch button (SW4).
NOTE: When pressed number is lost during setting, you must redo the setting procedure. Return to
“Operation status display (Normal operation)” by pressing the EXIT switch button once, and restart from the beginning of the setting procedure.
- 72 -

13. Optional parts

Exterior Part name Model name Summary
External
connect kit
UTY-XWZXZ3
Use to operate the external input and output functions of outdoor unit. (For 34 model)
OUTDOOR UNIT
AOTG30, 34KMTA
- 73 -
Loading...