Fujitsu AB*F18LAT, AB*F14LAT, AB*F24LAT, AR* 9LUAB, AR*12LUAD Service Instruction

...
Models Indoor unit Outdoor unit
AB*14LBAJ AB*18LBAJ AB*24LBAJ AB*F14LAT AB*F18LAT AB*F24LAT
AR* 9LUAB AR*12LUAD AR*14LUAD AR*18LUAD AR*22LUAD AR*F09LALU AR*F12LALU AR*F14LALU AR*F18LALU AR*F22LALU
AO*18LMAK2 AO*24LMAM2 AO*30LMAW4
SERVICE
INSTRUCTION
R410A
AU*12LBAB AU*14LBAB AU*18LBAB AU*F09LAL AU*F12LAL AU*F14LAL AU*F18LAL
AS*18LBAJ AS*24LBAJ AS* 7LMACW AS* 9LMACW AS*12LMACW AS*A07LACM AS*A09LACM AS*A12LACM AS*A14LACM AS*A18LACM
AG*F09LAC AG*F12LAC AG*F14LAC
SPLIT TYPE ROOM AIR CONDITIONER
INVERTER MULTI
Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type
CONTENTS
1. DESCRIPTION OF EACH CONTROL OPERATION
1. CAPACITY CONTROL................................................................................................
3. INDOOR FAN CONTROL...........................................................................................
2. AUTO CHANGEOVER OPERATION..........................................................................
5. LOUVER CONTROL...................................................................................................
4. OUTDOOR FAN CONTROL.......................................................................................
7. TIMER OPERATION CONTROL................................................................................
6. COMPRESSOR CONTROL........................................................................................
9. TEST OPERATION CONTROL..................................................................................
8. ELECTRONIC EXPANSION VALVE CONTROL........................................................
11. 4-WAY VALVE EXTENSION SELECT.......................................................................
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )................................
13. MANUAL AUTO OPERATION...................................................................................
12. AUTO RESTART........................................................................................................
15. FRESH AIR CONTROL..............................................................................................
14. COMPRESSOR PREHEATING..................................................................................
18. DEFROST OPERATION CONTROL..........................................................................
16. EXTERNAL ELECTRICAL HEATER CONTROL........................................................
19. DRAIN PUMP OPERATION.......................................................................................
21. VARIOUS PROTECTIONS.........................................................................................
20. ENERGY SAVE FUNCTION.......................................................................................
01-01 01-01 01-02 01-11 01-12 01-21 01-22 01-26 01-26 01-26 01-26
01-27 01-27 01-27
01-28
01-29
17. COIL DRY OPERATION CONTROL........................................................................... 01-28
01-32 01-32 01-33
01-27
2-1-2 OUTDOOR UNIT DISPLAY................................................................................
2-1-1 INDOOR UNIT DISPLAY....................................................................................
2-1 ERROR DISPLAY......................................................................................................
2. TROUBLE SHOOTING
2-2 TROUBLE SHOOTING WITH ERROR CODE..........................................................
2-3 TROUBLE SHOOTING WITH NO ERROR CODE....................................................
2-4 SERVICE PARTS INFORMATION............................................................................
02-01 02-01 02-06
2-1-3 WIRED REMOTE CONTROLLER DISPLAY......................................................
02-07
02-44
02-11
02-49
1-1-1 PARTS LAYOUT DRAWING...............................................................................
1-1-2 WIRING................................................................................................................
1-1-3 DISASSEMBLY PROCESS.................................................................................
1-1 For AO*18LMAK2/ 24LMAM2.................................................................................
1 REPLACEMENT PARTS ( For OUTDOOR UNIT ).......................................................
3. REPLACEMENT PARTS
03-01 03-01 03-01
03-04
03-03
1-2-1 PARTS LAYOUT DRAWING...............................................................................
1-2-2 WIRING................................................................................................................
1-2-3 DISASSEMBLY PROCESS.................................................................................
1-2-4 ASSEMBLY PROCESS of INVERTER UNIT......................................................
1-2 For AO*30LMAW4..................................................................................................
03-08 03-08
03-11
03-10
03-16
1 . DESCRIPTION OF EACH CONTROL OPERATION
R410A
INVERTER (MULTI )
Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type
2. AUTO CHANGEOVER OPERATION
01-01
1. CAPACITY CONTROL
1-1 COOLING, HEATING, DRY CAPACITY CONTROL
Compressor frequency decides by capacity of an indoor unit, operation number of an indoor unit, set temperature, room temperature and outside temperature.
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the HEATING, COOLING and MONITORING modes. During operation, the optimum mode is automatically swiched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1 degC steps.
When operation starts, only the indoor fan is operated for 1 minute. (Air flow mode: S- Lo) After 1 minute, depends on the room temperature and outdoor unit's operarion mode, the operation mode is selected in accordance with the table below.
( Table 1-1 : Operation mode selection table )
1
Room temperature :TR
Operation mode
TR > Ts +2 degC
Ts +2 degC > TR
=
=
Ts +2 degC > TR > Ts-2 degC
Cooling
Monitoring
Heating
Ts : Setting temperature TR: Room temperature
( Table 1-2 : Operation mode selection table for AS*18/ 24LBAJ )
Room temperature :TR
Operation mode
TR > Ts +2.5 degC
Ts +2.5 degC > TR
=
=
Ts +2.5 degC > TR > Ts-2.5 degC
Cooling
Monitoring
Heating
Ts : Setting temperature TR: Room temperature
When COOLING was selected at , the same operation as COOLING OPERATION is performed.
When HEATING was selected at , the same operation as HEATING OPERATION is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function after the COOLING or HEATING operation mode was selected at above, operation is switched to MONITORING and the operation mode is selected again.
1
2
3
1
4
1
3. INDOOR FAN CONTROL
1. Fan speed
( Table 2 : Indoor Fan Speed )
01-02
Operation mode Air flow mode Speed (rpm)
Hi 850
760 670
Me
Lo
Cooling
S-Lo
Heating
AB*14LBAJ
Operation mode Air flow mode Speed (rpm)
Hi 1030
890 770
250
Operation mode Air flow mode Speed (rpm)
Hi 1180
1040
900
Me
Lo
Cooling
S-Lo
Heating
AB*24LBAJ
300
250
Me
Lo
Cooling
S-Lo
Heating
Cooling Heating
Cooling Heating
Cooling Heating
Cooling Heating
AB*18LBAJ
Operation mode Air flow mode Speed (rpm)
Hi 955
870 800 650
Me
Lo
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 750
680 610 550
Me
Lo
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1000
860 720 570
Me
Lo
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1040
890 750 595
Me
Lo
S-Lo
AR*9LUAB
AR*14LUAD
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1270
1050
800 595
Me
Lo
S-Lo
AR*22LUAD
AR*12LUAD
AR*18LUAD
Cooling Heating
Cooling Heating
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 850
800 740 670 300
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1040
950 800 740 300
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1230
1040
900 780 300
Me
Lo
Quiet
S-Lo
AB*F14LAT
AB*F24LAT
AB*F18LAT
01-03
Cooling Heating
Cooling Heating
AU*12/ 14LBAB
--- ---
AU*18LBAB
AU*F09LAL AU*F12LAL
Operation mode Air flow mode Speed (rpm)
Hi 730
670 590
Me
Lo
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 800
700 600
Me
Lo
S-Lo
Cooling Heating
Cooling Heating
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1010
950 880 830 450
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 790
720 620 570 330
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 990
880 770 620 330
Me
Lo
Quiet
S-Lo
AR*F09LALU
AR*F14LALU
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1320
1100
980 780 450
Me
Lo
Quiet
S-Lo
AR*F22LALU
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1040
950 840 700 450
Me
Lo
Quiet
S-Lo
AR*F18LALU
AR*F12LALU
Operation mode Air flow mode
Speed (rpm)
Hi 660
580 520 460
Me
Lo
Dry Monitoring
Quiet
Hi
Me
Lo
Quiet
650
580
Me+
620
520 460 460 300
Auto S- Lo
Cooling Fan
Heating
Operation mode Air flow mode
Speed (rpm)
Hi 590
540 490 440
Me
Lo
Dry Monitoring
Quiet
Hi
Me
Lo
Quiet
590
540
Me+
570
490 440 460 300
Auto S- Lo
Cooling Fan
Heating
Operation mode Air flow mode
Speed (rpm)
Hi 730
630 540 460
Me
Lo
Dry Monitoring
Quiet
Hi
Me
Lo
Quiet
740
670
Me+
700
600 480 460 300
Auto S- Lo
Cooling Fan
Heating
AU*F14LAL
Operation mode Air flow mode
Speed (rpm)
Hi 790
660 570 460
Me
Lo
Dry Monitoring
Quiet
Hi
Me
Lo
Quiet
840
750
Me+
800
650 500 460 300
Auto S- Lo
Cooling Fan
Heating
AU*F18LAL
01-04
Cooling Heating
Cooling Heating
Operation mode Air flow mode Speed (rpm)
Hi 1160
1000
830 780 550
Me
Lo
Quiet
S-Lo
Operation mode Air flow mode Speed (rpm)
Hi 1290
1100
870 730 550
Me
Lo
Quiet
S-Lo
AS*18LBAJ AS*24LBAJ
Operation mode Air flow mode
Speed (rpm)
Louver position Louver position
Hi 1100
1050 1000
950
950 500
Me
Lo
Cooling Fan
Quiet
Quiet
Hi 1120
1070 1000
930 500
1100 1030
970
Me
Lo
Heating
AS*7LMACW
S- Lo
1
4
5
6
3
2
1
4
5
6
3
2
Operation mode Air flow mode
Speed (rpm)
Louver position Louver position
Hi 1200
1100 1000
940
940 500
Me
Lo
Cooling Fan
Quiet
Quiet
Hi 1200
1100 1000
900 500
1150 1050
960
Me
Lo
Heating
AS*9LMACW
S- Lo
1
4
5
6
3
2
Operation mode Air flow mode
Speed (rpm)
Louver position Louver position
Hi 1310
1260 1190 1100
970 500
Me
Lo
Cooling Fan
Quiet
Quiet
Hi 1310
1180 1030
970 500
1200 1100 1000
Me
Lo
Heating
AS*12LMACW
S- Lo
1
4
5
6
3
2
01-05
Operation mode Air flow mode
Speed (rpm)
Hi 1140
1000
880 700
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1140
1050
980 800 700 480
Auto S- Lo
Cooling Fan
Heating
AS*A07LACM
Operation mode Air flow mode
Speed (rpm)
Hi 1220
1060
900 720
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1220 1110 1040
830 720 480
Auto S- Lo
Cooling Fan
Heating
AS*A09LACM
Operation mode Air flow mode
Speed (rpm)
Hi 1280
1100
900 750
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1320 1180 1080
860 750 480
Auto S- Lo
Cooling Fan
Heating
AS*A12LACM
Operation mode Air flow mode
Speed (rpm)
Hi 1480
1250 1050
850
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1480 1250 1100
950 850 480
Auto S- Lo
Cooling Fan
Heating
AS*A14LACM
Operation mode Air flow mode
Speed (rpm)
Hi 1480
1250 1100
950
Me
Lo
Dry Monitoring
Quiet
Hi/ Me+
Me
Lo
Quiet
1480 1250 1100
950 950 480
Auto S- Lo
Cooling Fan
Heating
AS*A18LACM
01-06
AG*F09LAC
Operation mode
Air flow mode
Speed (rpm)
Hi 1120/ 950 1230/ ---
960/ 820 1070/ ---
660/ 560 680/ ---
820/ 700 910/ --­ 660/ 560 750/ --­ 570/ 480 --- / --­1120/ 950 1230/ --­1000/ 850 1090/ --­ 860/ 730 940/ --­ 660/ 560 750/ ---
660/ 560
680/ ---
Me
Lo
Heating
Quiet
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
S-Lo
Cooling Fan
Upper& Lower air flow mode
Upper air flow mode
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower) (Upper/ Lower)
AG*F12LAC
Operation mode
Air flow mode
Speed (rpm)
Hi 1240/ 1050 1300/ ---
1050/ 890 1120/ ---
660/ 560 680/ ---
860/ 730 930/ --­ 660/ 560 750/ --­ 570/ 480 --- / --­1240/ 1050 1300/ --­1080/ 920 1140/ --­ 910/ 770 980/ --­ 660/ 560 750/ ---
660/ 560
680/ ---
Me
Lo
Heating
Quiet
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
S-Lo
Cooling Fan
Upper& Lower air flow mode
Upper air flow mode
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower) (Upper/ Lower)
AG*F14LAC
Operation mode
Air flow mode
Speed (rpm)
Hi 1330/ 1120 1370/ ---
1100/ 930 1160/ ---
660/ 560 680/ ---
890/ 750 960/ --­ 660/ 560 750/ --­ 570/ 480 --- / --­1330/ 1120 1370/ --­1140/ 970 1180/ --­ 940/ 800 1020/ --­ 660/ 560 750/ ---
660/ 560
680/ ---
Me
Lo
Heating
Quiet
Hi
Me
Lo
Quiet
Cool air prevention
S-Lo
S-Lo
Cooling Fan
Upper& Lower air flow mode
Upper air flow mode
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower)
(Upper/ Lower) (Upper/ Lower)
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor fan only runs.
2-2. For AB*F14L/ 18L/ 24L AR*F09L/ 12L/ 14L/ 18L/ 22L AU*F09L/ 12L/ 14L/ 18L AS*7L/ 9L/ 12L/ 18L/ 24L AS*A07L/ 09L/ 12L/ 14L/ 18L AG*F09L/ 12L/ 14L
The airflow can be switched in 4 steps such as AUTO, LOW, MED, HIGH, while the indoor fan only runs.
2-1. For AB*14L/ 18L/ 24L AR* 9L/ 12L/ 14L/ 18L/ 22L AU*12L/ 14L/ 18L
3. COOLING OPERATION
(Fig.1)
airflow change - over ( Cooling: AUTO )
When the room temperature rises
Lo mode
When the room temperature lowers
01-07
Hi mode
Me mode
TR : Room temperature Ts : Setting temperature
TR-Ts > 2 degC
=
1 degC > TR-Ts
2 degC > TR-Ts > 1 degC
=
TR-Ts > 3 degC
*(TR-Ts > 2.5 degC)
=
=
2 degC > TR-Ts
*(2 degC > TR-Ts)
3 degC > TR-Ts > 2 degC
*(2.5 degC > TR-Ts > 1.5 degC)
= =
*1
*1 : Contains a condition to the following
When the operation mode is set to AUTO mode at the start of operation. When the setting temperature was changed. When the operation mode was changed to COOLING mode. When the airflow mode was changed to AUTO mode.
4. HEATING OPERATION
When the airflow is set to [AUTO], the indoor fan motor operates [MED] mode. Then the indoor fan motor will run according to a room temperature, as shown in Figure 2.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table 2.
47°C
41°C *(42°C)
Indoor heat exchanger temperature
( Fig.2 : Airflow change - over ( Heating : AUTO ) )
Hold
Go down one-step
Go up one-step
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 1. On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL] operation modes QUIET, LOW, MED, HIGH,as shown in Table 2.
*For AS*7/ 9/ 12LMACW
*For AS*A07/ 09/ 12/ 14/ 18LACM
*For AB*F/ AR*F/ AS*A/ AU*F/ AG*F Type
4-1. For AB/ AR/ AU/ AS Type
4-2. For AB*F/ AR*F/ AU*F/ AS*A/ AG*F Type
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature, as shown in Figure 3.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table 2.
( Fig.3 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > - 1.5 degC
=
- 2.5 degC > TR-Ts
- 1.5 degC > TR-Ts > - 2.5 degC =
TR-Ts > - 1 degC
=
- 2 degC > TR-Ts
- 1 degC > TR-Ts > - 2 degC =
When the room temperature rises
When the room temperature drops
TR : Room temperature Ts : Setting temperature
Lo mode
Me mode
Hi mode *(Me+ mode)
01-08
5. COOL AIR PREVENTION CONTROL (Heating mode)
Setting Fan mode
Lo mode
S-Lo mode
33°C
30°C
30°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
The maximum value of the indoor fan speed is set as shown in Figure 4, based on the detected temperature by the indoor heat exchanger sensor on heating mode.
( Fig.4 : Cool Air Prevention Control )
5-1. For AB/ AR/ AU Type
5-2. For AB*F/ AU*F Type
5-3. For AR*F Type
42°C
30°C
34°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 5, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.5 : Cool Air Prevention Control )
< [Hi] setting >
Hi
Me+
Lo
Cool air prevention
39°C
37°C
37°C
32°C
24°C
39°C
32°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
< The other of [Hi] setting >
< [Hi] setting >
< The other of [Hi] setting >
S-Lo
Lo (Qu)
Cool air prevention
37°C
30°C
34°C
24°C
Setting FAN mode
S-Lo
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 6, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.6 : Cool Air Prevention Control )
Setting Fan mode
Lo (Qu) mode
S-Lo mode
37°C
30°C
32°C
24°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
Hi mode
Lo mode
S-Lo mode
37°C
30°C
32°C
24°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
01-09
42°C
35°C
30°C
18°C
39°C
32°C
26°C
15°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
The maximum value of the indoor fan speed is set as shown in Figure 7-1,7-2, based on the fan speed mode and the detected temperature by the indoor heat exchanger sensor on heating mode.
( Fig.7-1 : Cool Air Prevention Control for AS*7/ 9/ 12LMACW )
5-4. For AS Type
E zone
D zone
C zone
B zone
A zone
AUTO HIGH MED LOW QUIET
E zone D zone C zone B zone A zone
Fan speed mode
ZONE
AUTO AUTO
S-Lo OFF OFF OFF OFF OFF
S-Lo S-Lo S-Lo S-Lo
Me
Lo Lo Lo
Setting Fan Speed
40°C
33°C
28°C
18°C
38°C
31°C
26°C
16°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
( Fig.7-2 : Cool Air Prevention Control for AS*18/ 24LBAJ )
E zone
D zone
C zone
B zone
A zone
AUTO HIGH MED LOW QUIET
E zone D zone C zone B zone A zone
Fan speed mode
ZONE
AUTO AUTO
S-Lo OFF OFF OFF OFF OFF
S-Lo S-Lo S-Lo S-Lo
Me
Lo Lo Lo
Setting Fan Speed
5-5. For AS*A Type
47°C
30°C
34°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.8 : Cool Air Prevention Control )
< [Hi] setting >
Hi
Me+
Lo
Cool air prevention
40°C
37°C
40°C
32°C
28°C
40°C
32°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
< The other of [Hi] setting >
S-Lo
Lo (Qu)
Cool air prevention
37°C
30°C
34°C
28°C
Setting FAN mode
S-Lo
[ AS*A07L: Cool air prevention 800rpm, S-Lo 480rpm ] [ AS*A09L: Cool air prevention 830rpm, S-Lo 480rpm ] [ AS*A12L: Cool air prevention 860rpm, S-Lo 480rpm ] [ AS*A14L/ 18L: Cool air prevention 850rpm, S-Lo 480rpm ]
01-10
5-6. For AG*F Type
42°C
30°C
31°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 9, based on the detected temperature by the indoor heat exchanger sensor on heating mode. When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.9 : Cool Air Prevention Control )
< [Hi] setting >
Hi
Me
Lo
Cool air prevention
39°C
37°C
34°C
29°C
24°C
39°C
29°C
Indoor heat exchanger temperature
Indoor heat exchanger temperature
< The other of [Hi] setting >
S-Lo
Lo (Qu)
Cool air prevention
37°C
30°C
31°C
24°C
Setting FAN mode
S-Lo
During the dry mode operation, the fan speed setting can not be changed. ( S-Lo )
6. DRY OPERATION
01-11
4. OUTDOOR FAN CONTROL
Following table shows the fan speed of the outdoor unit.
1. Outdoor Fan Motor
*
For AO*18LMAK2/ 24LMAM2 When the outdoor heat exchanger tenperature is lower than 2°C, the fan speed switches to 780rpm on heating mode.
For AO*30LMAW4 It runs at 500rpm for 20 seconds after starting up the outdoor fan. When the outdoor heat exchanger tenperature is lower than 2°C, the fan speed switches to 780rpm on heating mode.
*
( Table 3 : Fan speed of the outdoor unit )
780/ 420 rpm
820/ 780/ 400/ 300/ 200 rpm
850/ 780/ 400/ 300/ 200 rpm
780/ 420 rpm
Cooling
Heating
AO*18LMAK2
AO*30LMAW4
AO*24LMAM2
5. LOUVER CONTROL
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
(Swinging Range)
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-12
1
2
3
4
The indoor fan motor starts after the louver reaches to the setting position.
At the start of operation if the setting louver position is ,the setting position is set to after the louver moves from totally-enclosed position to . (Positioning Control)
( Stop mode means Operation stop.)
Airflow direction set Range of swing
to to to to
5-1 Compact Cassette (AU) type
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-13
The indoor fan motor starts after the louver reaches to the setting position.
At the start of operation if the setting louver position is or ,the setting position is set to or after the louver moves from totally-enclosed position to . (Positioning Control)
( Stop mode means Operation stop.)
1
4
5
6
7
3
2
1 2 3 4 5 6 7
1 2 3 4 5 6 7
1
2
1
3
1
2
3
6
4
5
3
4
5
6
7
1
7
1
1
2
2
3
(Swinging Range)
Airflow direction set
Range of swing
to to to to
1
4
5
7
7
7
to to to
5-2 Universal (AB) type
2. HORIZONTAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The horizontal airflow direction is set automatically on after initialization.
(Function Range)
(Air Direction Range)
(Operation Range)
2-1. SWING OPERATION
When the swing signal is received from the remote controller, the horizontal louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-14
( Stop mode means Operation stop.)
1 2 3 4 5
1 2 334 5
1
3
4
5
2
1
2
1
3
1
2
5
5
3
4
3
4
5
(Swinging Range)
Airflow direction set
Range of swing
to to to to
1 5
to
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
Cooling / Dry mode Heating mode
Use the air direction adjustments within the ranges shown above.
The remote control unit's display does not change.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
During AUTO mode operation, for the first minute after beginning operation, airflow will be horizontal ; the air direction cannot be adjusted during this period.
Cooling mode / Dry mode / Fan mode ( ) ) Heating mode / Fan mode (
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-15
5-3 Wall Mounted (AS*7/ 9/ 12L) type
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
Cooling / Dry mode Heating mode
Use the air direction adjustments within the ranges shown above.
The remote control unit's display does not change.
Direction Only the direction of the Moving Diffuser changes: the direction of the Air Direction Flaps does not change.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
During AUTO mode operation, for the first minute after beginning operation, airflow will be horizontal ; the air direction cannot be adjusted during this period.
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
01-16
5-4 Wall Mounted (AS*18/ 24L) type
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
1
2
1
3
1
1
4
5
4
4
3
4
5
6
(Swinging Range)
Airflow direction set
Range of swing
to to to to
4
1
6
6
to to
01-17
2. HORIZONTAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The horizontal airflow direction is set automatically on after initialization.
(Function Range)
(Air Direction Range)
(Operation Range)
2-1. SWING OPERATION
When the swing signal is received from the remote controller, the horizontal louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position. ( Stop mode means Operation stop.)
1 2 3 4 5
1 2 334 5
1
3
4
5
2
1
2
1
3
1
2
5
5
3
4
3
4
5
(Swinging Range)
Airflow direction set
Range of swing
to to to to
1 5
to
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follow:
Cooling / Dry mode Heating mode Fan mode
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During use of the Cooling and Dry modes, do not set the Air Flow Direction Louver in the Heating
range ( ) for long period of time, since water vapor many condense near the outlet louvers and drop of water may drip from the air conditioner. During the Cooling and Dry modes, if the Air Flow Direction Louvers are left in the hating range for more than 30 minutes, they will automatically return to position .
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically becomes , and it cannot be adjusted.
Cooling mode / Dry mode / Fan mode ( ) Heating mode / Fan mode ( )
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
01-18
5-5 Wall Mounted (AS*A) type
01-19
5-6 Compact Cassette (AU*F) type
1. VERTICAL LOUVER CONTROL
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry / Fan mode Horizontal flow Heating mode Downward flow
(Function Range)
(Air Direction Range)
(Operation Range)
1-2. SWING OPERATION
When the swing signal is received from the remote controller, the vertical louver starts to swing. The range of swing depends on the set airflow direction.
When the indoor fan is either at S-Lo or Stop mode, the swinging operation is interrupted and the louver stops at the memorized position.
1
2
3
4
( Stop mode means Operation stop.)
During Cooling/Dry mode/Fan mode : During Heating mode :
During AUTO mode operation, for the first minute after beginning operation, air-flow will be horizontal ; the air direction cannot be adjusted during this period.
(Swinging Range)
The type of operation
Cooling/Dry/Fan
Range of swing
to
Heating
to
01-20
5-7 Floor (AG*F) type
1. VERTICAL LOUVER CONTROL
1-2. SWING OPERATION
Each time the button is pressed, the air direction range will change as follows:
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
Cooling / Dry mode Horizontal flow Heating mode Downward flow
When the temperature of the air being blown out is low at the start of heating operation or during defrosting, the airflow direction temporarily becomes to prevent cold air being blown onto the body.
During Monitor operation in AUTO CHANGEOVER mode, the airflow direction automatically becomes , and it cannot be adjusted.
(Function and Operation Range)
(Air Direction Range)
When the swing signal is received from the remote controller, the vertical louver starts to swing.
(Swinging Range)
When the indoor fan is either at S-lo or Stop mode, the swinging operation is interrrupted and the louver stops at the memorized position.
01-21
6. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the table 4.
Cooling Heating
Min Max Min Max
AO*18LMAK2 15Hz 80Hz 15Hz 95Hz AO*24LMAM2 AO*30LMAW4
15Hz 80Hz 15Hz 95Hz 15Hz 90Hz 20Hz 95Hz
(Table 4 : Compressor Operation Frequency Range)
2. OPERATION FREQUENCY CONTROL AT START UP
2-1. For AO*18L/ 24L
The compressor frequency soon after the start-up is controlled as shown in Figure 10-1.
(Fig.10-1 : Compressor Control at Start-up)
56Hz
56Hz
40Hz
46sec 60sec 80sec 160sec
80Hz
Hold
2-2. For AO*30LMAW4
The compressor frequency soon after the start-up is controlled as shown in Figure 10-2.
(Fig.10-2 : Compressor Control at Start-up)
180sec
60sec
120sec
120sec
720sec
1
2
1 Discharge pipe temp. > 30°C 2 Discharge pipe temp. < 30°C
=
Hold
7. TIMER OPERATION CONTROL
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
2. PROGRAM TIMER
01-22
7-1 Wireless Remote Controller ( For AB/ AU/ AU*F/ AS/ AS*A/ AB*F/ AG*F type )
ON / TIMER OFF / TIMER
PROGRAM TIMER
SLEEP TIMER
The program timer allows the OFF timer and ON timer to be used in combination one time.
Operation mode
Operation will start from the timer setting (either OFF timer or ON timer) whichever is closest to the clock's current timer setting. The order of operations is indicated by the arrow in the remote control unit's display.
SLEEP timer operation cannot be combined with ON timer operation.
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
01-23
3. SLEEP TIMER
If the sleep timer is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON.
Set temperature rises
( Ts : Set temperature )
Stop of operation
Set temperature lowers ( Ts : Set temperature )
Ts
Stop of operation
In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1 degC. It increases the setting temperature another 1 degC after 1 hour. After that, the setting temperature is not changed and the operation is stopped at the time of timer setting.
Ts
+1degC
+2degC
-2degC
-1degC
-4degC
-3degC
Set
60min
In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1 degC. It decreases the setting temperature another 1 degC every 30 minutes. Upon lowering 4 degC, the setting temperature is not changed and the operation stops at the time of timer setting.
Set
30min
30min
30min
1. ON / OFF TIMER
OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
Operation mode
Stop mode
Set time of timer
ON timer : When the clock reaches the set time, the air conditioner will be turned on.
Operation mode
Stop mode
Set time of timer
The weekly timer allows up to two ON and OFF time to set up per day.
Use this timer function to set operating time for each day of the week.
Operation mode
The operating time can be set in 30 min increments only. The OFF time can be carried over to next day. The ON timer and the OFF timer functions cannot be set with using the weekly timer.
Both ON and OFF time must be set.
2. WEEKLY TIMER
2-1. WEEKLY TIMER
Stop mode
Stop mode
Stop mode
Operation mode
Operation mode
Set time
Set time Set time Set time
01-24
7-2 Wired Remote Controller ( For AR/ AR*F type )
ON / TIMER OFF / TIMER
WEEKLY TIMER
TEMPERATURE SET BACK TIMER
01-25
The DAY OFF setting is only available for days for which weekly settings already exist.
The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation.
The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower.
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
Normal
Next day setting
If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as shown below.
2-2. DAY OFF setting
3. TEMPERATURE SET BACK TIMER
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
Preceding day Next day
DAY OFF
Stop mode
Stop mode
Operation mode
Stop mode
Operation mode
DAY OFF
Setting day
Preceding day Next daySetting day
Case of SET BACK timer on the Cooling operation. ( Setting temperature :22°C, SET BACK temperature :26°C)
SET BACK setting
Operation temperature
Operation temperature
26°C
22°C
26°C
22°C
24°C
*1
ON OFF OFFON
*1: During the SET BACK function, the setting temperature is changed.
Chenge the setting temperature: 22°C 24°C
8. ELECTRONIC EXPANSION VALVE CONTROL
9. TEST OPERATION CONTROL
The compressor won't enter operation status for 3 minutes after the compressor is stopped, even if any operation is given.
10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
11. 4-WAY VALVE EXTENSION SELECT
01-26
The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 30 to 480 pulses.
At the time of supplying the power to the outdoor unit, the initialization of the electronic expansion valve is operated (1000 pulses are input to the closing direction).
At the time when the air conditioner is switched from the cooling mode to heating mode, the compressor is stopped, and the 4-way valve is switched in 3 minutes later after the compressor stopped.
Under the condition where the air conditioner runs, short two metal contacts under the battery compartment lid, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller
Under the condition where the air conditioner stops, press the MASTER CONTROL button and the FAN CONTROL button simultaneously for 5 seconds or more, and the test operation control mode will appear. During test running, " " will display on the remote controller display. Set the test operation mode, and the compressor will continue to run regardless of whatever the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wired Remote Controller ( without TEST RUN button )
Under the condition where the air conditioner runs, press the TEST RUN button, and the test operation control mode will appear. During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode, and the compressor will continue to run regardless of whether the room temperature sensor detects. The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller ( with TEST RUN button )
13. MANUAL AUTO OPERATION (Indoor unit body operation)
If MANUAL AUTO Button is set, the operation is controlled as shown in Table 5. If the remote control is lost or battery power dissipated, this function will work without the remote control.
(Table 5 : Manual auto operation)
14. COMPRESSOR PREHEATING
01-27
When the outdoor heat exchanger temperature is lower than Operation temperature (Refer to Table 6) and the heating operation has
been stopped for 3 hours, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to Release temperature or greater, preheating
is over.
(Table 6 : Preheating Operation / Release Temperature)
Before 24 hour After 24 hour
Operation temperature
Operation temperature
Release temperature
Release temperature
3°C 7°C 0°C 4°C
OPERATION MODE
Auto changeover
FAN CONT. MODE
Auto
TIMER MODE
Continuous (No timer setting available)
SETTING TEMP.
23°C or 24°C
SETTING LOUVER
Standard
SWING
OFF
The fan motor for Fresh Air is operated in synchronization with the indoor fan operation as shown in Figure 11.
15. FRESH AIR CONTROL (For AR type)
(Fig.11 : Fresh air control)
Operation
Stop
Operation
Stop
Fan motor (Indoor unit)
Fan motor (for Fresh Air)
12. AUTO RESTART
When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically resumed with the memorized operation contents. When the power is interrupted and recovered during timer operation, timer operation is canceled, but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode Set temperature
Set air flow
Timer mode and timer time Air flow Direction
Swing Thermistor detected position (For AU*F model wih wired remote controller)
10°C HEAT (For AG*F model)