Fujitsu AJYA90LALH, AJY144LALH, AJY108LALH, AJY126LALH, AJHA72LALH Installation Manual

...
Page 1
AJYA72LALH
TM
INSTALLATION MANUAL
OUTDOOR UNIT
For authorized service personnel only.
INSTALLATIONSANLEITUNG
AUßENGERÄT
Nur für autorisiertes Fachpersonal.
MANUEL D’INSTALLATION
UNITÉ EXTÉRIEURE
Pour le personnel agréé uniquement.
English
Deutsch
FrançaisEspañol
AJYA90LALH AJY108LALH AJY126LALH AJY144LALH
AJHA72LALH AJHA90LALH AJH108LALH AJH126LALH AJH144LALH
MANUAL DE INSTALACIÓN
Únicamente para personal de servicio autorizado.
MANUALE DI INSTALLAZIONE
UNITÀ ESTERNA
A uso esclusivo del personale tecnico autorizzato.
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
ΕΞΩΤΕΡΙΚΉ ΜΟΝΆΔΑ
Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό.
MANUAL DE INSTALAÇÃO
UNIDADE EXTERIOR
Apenas para técnicos autorizados.
РУКОВОДСТВО ПО УСТАНОВКЕ
ВНЕШНИЙ МОДУЛЬ
Только для авторизованного обслуживающего персонала.
Italiano
ΕλληνικάPortuguês
РусскийTürkçe
MONTAJ KILAVUZU
DIŞ ÜNİTE
Yalnızca yetkili servis personeli için.
安装说明书
室外机
仅针对授权的专业维修人员。
PART NO. 9378945104
中 文
Page 2
INSTALLATION MANUAL
PART NO. 9378945104 VRF system outdoor unit
CONTENTS
1. SAFETY PRECAUTIONS ........................................................................................ 1
2. ABOUT THE UNIT ...................................................................................................2
2. 1. Precautions for using the R410A refrigerant .................................................2
2. 2. Special tools for R410A .................................................................................2
2. 3. Accessories ..................................................................................................2
2. 4. Combinations ................................................................................................ 2
2. 5. Optional parts................................................................................................3
3. INSTALLATION WORK ............................................................................................ 3
3. 1. Selecting an installation location ................................................................... 3
3. 2. Drain processing ........................................................................................... 3
3. 3. Installation dimensions .................................................................................. 3
3. 4. Transportation the outdoor unit .....................................................................5
3. 5. Installation the unit ........................................................................................ 6
4. SYSTEM CONFIGURATION ...................................................................................6
4. 1. System confi guration .................................................................................... 6
4. 2. Pipe selection................................................................................................7
4. 3. Protection of pipes ........................................................................................ 8
5. PIPE INSTALLATION ............................................................................................... 8
5. 1. Brazing .......................................................................................................... 8
5. 2. Indoor unit pipe connections ......................................................................... 8
5. 3. Piping method ............................................................................................... 8
5. 4. Multiple connections .....................................................................................9
6. ELECTRICAL WIRING ........................................................................................... 11
6. 1. The precautions of electrical wiring ............................................................. 11
6. 2. Wiring method ............................................................................................. 11
6. 3. Knockout hole ............................................................................................. 11
6. 4. Selecting power supply cable and breaker ................................................. 12
6. 5. Transmission line ........................................................................................12
6. 6. Wiring procedure......................................................................................... 13
6. 7. External input and external output .............................................................. 14
7. FIELD SETTING ....................................................................................................15
7. 1. Field setting switches .................................................................................. 15
7. 2. DIP switch setting ....................................................................................... 15
7. 3. Rotary switch setting ................................................................................... 16
7. 4. Push button setting ..................................................................................... 17
7. 5. Signal amplifi er address setting .................................................................. 19
7. 6. Indoor unit address setting .......................................................................... 19
7. 7. Resistance measurement of transmission cable
(Measure with breaker OFF) ....................................................................... 20
8. PIPE INSTALLATION II .......................................................................................... 20
8. 1. Sealing test ................................................................................................. 20
8. 2. Vacuum process .........................................................................................20
8. 3. Additional charging .....................................................................................21
8. 4. Installing insulation ...................................................................................... 22
9. TEST RUN .............................................................................................................22
9. 1. Pre-test run check items ............................................................................. 22
9. 2. Test operation method ................................................................................ 22
9. 3. Checklist ..................................................................................................... 23
10. LED Status ............................................................................................................. 23
10. 1. Normal operation mode .............................................................................. 23
10. 2. Error codes ................................................................................................. 23
11. INFORMATION ...................................................................................................... 24
SAFETY PRECAUTIONS1.
Be sure to read this Installation manual thoroughly before installation• The warnings and precautions indicated in this Installation manual contain impor-• tant information pertaining to your safety. Be sure to observe them. After installing the unit, perform a test run to make sure the unit operates normally. • Then, explain to the customer how to operate and maintain the unit. Please pass this Installation manual together with the Operating manual to the cus-• tomer. Please ask the customer to keep the Operating manual and Installation manual at hand for future reference during the moving or repair of the main unit.
This mark indicates procedures which, if improperly
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts. Using non-specifi ed parts will cause serious accidents such as falling unit, refriger- ant leakage, water leakage, electric shock, and fi re.
performed, might lead to the death or serious injury of the user.
.
To in st all a u nit th at us es the R410A refrigerant, use dedicated tools and piping materials that have been manufactured specifi cally for R410A use. Because the pressure of the R410A refrigerant is approximately 1.6 times higher than the R22, failure to use dedicated piping material or improper installation can cause rupture or injury. It will also cause serious accidents such as refrigerant leakage, water leakage, electric shock, and fi re.
Do not use this equipment with air or any other unspecifi ed refrigerant in the refrig- erant lines. Excess pressure can cause a rupture.
Be sure to install the unit as prescribed, so that it can withstand earthquakes and typhoons or other strong winds. Improper installation can cause the unit to topple or fall, or other accidents
Ensure that the outdoor unit is securely installed at a place that can withstand the weight of the unit. Improper installation will cause injuries caused by falling unit.
If there is a refrigerant leakage, make sure that it does not exceed the concentra­tion limit. If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as oxygen starvation.
If a refrigerant leakage occurs during operation, immediately vacate the premises and thoroughly ventilate the area. If the refrigerant is exposed to fi re, it will create a hazardous gas.
Electrical work must be performed in accordance with this Installation manual by a person certifi ed under the national or regional regulations. Be sure to use a dedi- cated circuit for the unit. An insuffi cient power supply circuit or improperly performed electrical work can cause serious accidents such as electric shock or fi re.
For wiring, use the prescribed type of cables, connect them securely, making sure that there are no external forces of the cables applied to the terminal connections. Improperly connected or secured cables can cause serious accidents such as overheating the terminals, electric shock, or fi re.
Do not turn ON the power until all work has been completed. Turning ON the power before the work is completed can cause serious accidents such as electric shock or fi re.
After the installation, make sure there is no refrigerant leakage. If the refrigerant leaks into the room and becomes exposed to a source of fi re such as a fan heater, stove, or burner, it will create a hazardous gas.
Use a wall hole pipe. Otherwise, it may cause a short circuit.
Do not place the outdoor unit near the handrail of the balcony. Children may climb onto the outdoor unit, lean over the handrail and fall over.
Use only a specifi ed power cable. Poor connection, poor insulation, and exceeding the allowable current will lead to electric shock and fi re
Attach the connecting cables securely to the terminal. Or secure it fi rmly with a "wir- ing suppressor". Loose connection will lead to malfunction, electric shock, and fi re.
Install a breaker to cut off all AC main current at the same time. If you do not install a breaker, it may cause electric shock and fi re.
During installation, make sure that the refrigerant pipe is attached fi rmly before you run the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnormal pres­sure in the refrigeration cycle that leads to rupture and even injury.
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping. Do not remove the connection pipe while the compressor is in operation with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
If there is a possibility of touching the fan during maintenance, make sure to turn OFF the power before implementing the maintenance. Even if operations are suspended, the fan of outdoor unit sometimes rotates, so if the fan rotates suddenly while in contact with you may cause serious injury.
This mark indicates procedures which, if improperly
CAUTION
This unit must be installed by qualifi ed personnel with a capacity certifi cate for handling refrigerant fl uids. Refer to regulation and laws in use on installation place.
The installation must be carried out in compliance with regulations in force in the place of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or with non-authorized by the manufacturer.
This unit contains no user-serviceable parts. Always consult authorized service personnel to repairs.
When moving, consult authorized service personnel for disconnection and installa­tion of the unit.
Obtain the distribution network operator's agreement about the power capacity • of the power supply system, specifi cation of the cable and the harmonic current, and etc. when you connect the outdoor unit with the power supply. This unit must be connected to a power supply with impedance of 0.33 ohm and • below. If the power supply does not satisfy this requirement, please consult the power supplier. This product is intended for professional use.• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
performed, might possibly result in personal harm to the user, or damage to property.
.
.
En-1
Page 3
Do not install the unit in the following areas:
Area with high salt content, such as at the seaside. • It will deteriorate metal parts, causing the parts to fall or the unit to leak water. Area fi lled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to fall or the unit to leak water. Area that generates substances that adversely affect the equipment, such as • sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage. Area containing equipment that generates electromagnetic interference. • It will cause the control system to malfunction, preventing the unit from oper­ating normally. Area that can cause combustible gas to leak, contains suspended carbon bers or fl ammable dust, or volatile infl ammables such as paint thinner or gasoline. If gas leaks and settles around the unit, it can cause a fi re. Avoid installing the unit at places where it will come into contact with animals’ • urine or ammonia.
The units are not explosion proof and therefore should not be installed in explosive atmosphere.
Do not use the unit for special purposes, such as storing food, raising animals, growing plants, or preserving precision devices or art objects. It can degrade the quality of the preserved or stored objects.
Ground the unit. Do not connect the ground wire to a gas pipe, water pipe, lightning rod, or a telephone ground wire. Improper grounding may cause electric shock.
Perform draining for the unit according to the Installation manual. Check that the water is properly drained. If the drain processing is improperly installed, water may drip down from the unit, wetting the furniture.
Do not touch the fi ns with bare hands.
Be sure not to start or stop the operation of air conditioning with power breaker. Otherwise, it may cause malfunction or water leakage.
When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave, be sure to take measures against noise. Otherwise, it may cause malfunction or failure.
When energizing to the crankcase heater, please turn on the power 12 hours or earlier before operation begins. When the energizing time is short, it may cause failure. Besides, please do not turn off power during the busy season.
Children should be monitored to ensure they do not play with the device.
This product is not intended to be used by people (including children) with physical, sensory or mental disability, or persons lacking experience or knowledge unless they have been given by the through a person responsible for their safety, supervi­sion or instruction concerning the use of the device.
Tool name Contents of change for R22 tool
A conventional (R22) vacuum pump can be used by install­ing a vacuum pump adapter.
Vac uu m p um p
Gas leakage detec­tor
A conventional vacuum pump can be used by installing a • vacuum pump adapter. Be sure that the pump oil does not back fl ow into the sys- tem. Use one capable for vacuum suction of -100.7kPa (5 Ton, -755mmHg).
Special gas leakage detector for HFC refrigerant R410A.
Accessories2. 3.
Use connecting parts as required. Do not throw away the connecting parts until the installation has been complete.
Name and shape Q’ty Application
Specifi cations manual
Installation manual
Joint pipe A
Joint pipe B
Cable tie
1
(This book)
1
For connecting gas pipe (Straight type)
1
For connecting gas pipe (L type)
1
For binding power cable and transmis­sion cable
4
ABOUT THE UNIT2.
Precautions for using the R410A refrigerant2. 1.
Pay careful attention to the following points :
Since the working pressure is 1.6 times higher than that of R22 models, some of the piping and installation and service tools are special. (See the table in the SPECIAL TOOLS FOR R410A section.) Especially, when replacing a conventional refrigerant (other than R410A) model with a new refrigerant R410A model, always replace the conventional piping and are nuts with the R410A piping and fl are nuts.
Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with R22, R407C and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
Be more careful than the installation of the refrigerant (other than R410A) models, not to enter foreign matters (oil, water, etc.) and other refrigerant into the piping. Also, when storing the piping, securely seal the openings by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composi­tion of the gas and liquid phases, and always charge from the liquid phase side whose composition is stable.
Special tools for R410A2. 2.
Tool name Contents of change for R22 tool
Pressure is huge and cannot be measured with a conven­tional (R22) gauge. To prevent erroneous mixing of other
Gauge manifold
Charging hose
refrigerants, the diameter of each port has been changed. It is recommended to use a gauge manifold with a high pressure display range -0.1 to 5.3 MPa and a low pressure display range -0.1 to 3.8 MPa.
To increase pressure resistance, the hose material and base size were changed.
Combinations2. 4.
A maximum of 3 outdoor units can be connected to 1 refrigerant system. The combination of outdoor units per refrigerant system and the number of indoor units that can be connected are as follows:
Outdoor Unit
Model Name Nominal System Capacity (HP)
A72LALH 8
AJ AJ
A90LALH 10
AJ
108LALH 12
AJ
126LALH 14 144LALH 16
AJ
Installation space combination
Combination (HP) 8 10121416182022242628
Outdoor Unit 1 (HP) 8 10121416101212121416 Outdoor Unit 2 (HP) –––––8810121212
Outdoor Unit 3 (HP) –––––––––––
Maximum Connectable Indoor Unit
Combination (HP) 30 32 34 36 38 40 42 44 46 48
Outdoor Unit 1 (HP) 16 16 12 12 14 16 16 16 16 16 Outdoor Unit 2 (HP) 14 16 12 12 12 12 14 16 16 16
Outdoor Unit 3 (HP) – 10 12 12 12 12 12 14 16
Maximum Connectable Indoor Unit
When connecting outdoor units, install the outdoor unit with the largest nominal system capac­ity nearest to the refrigerant pipe and indoor unit, followed by those with lesser nominal system capacities. (Outdoor unit 1 Outdoor unit 2 Outdoor unit 3)
15 16 17 21 24 32 32 32 35 39 42
45 48 48 48 48 48 48 48 48 48
En-2
Page 4
Energy-saving combination
Combination (HP) 8 10121416182022242628
Outdoor Unit 1 (HP) ––––8––1481012 Outdoor Unit 2 (HP) ––––8––8888
Outdoor Unit 3 (HP) ––––––––888
Maximum Connectable Indoor Unit
Combination (HP) 30 32 34 36 38 40 42 44 46 48
Outdoor Unit 1 (HP) 14 12 14 14 – 14 14 16 – Outdoor Unit 2 (HP) 8 12 12 14 – 14 14 14 –
Outdoor Unit 3 (HP) 8888–121414––
Maximum Connectable Indoor Unit
* Means that the energy-saving combination is unavailable. When connecting outdoor units, install the outdoor unit with the largest nominal system capac­ity nearest to the refrigerant pipe and indoor unit, followed by those with lesser nominal system capacities. (Outdoor unit 1 Outdoor unit 2 Outdoor unit 3)
* * * * 30 * * 33 36 39 42
45 48 48 48 * 48 48 48 * *
Optional parts2. 5.
CAUTION
The following parts are optional parts specifi c to R410A refrigerant. Do not use parts other than those listed below.
Outdoor unit branch kit2. 5. 1.
Model Total cooling capacity of indoor unit (kW)
UTP-CX567A, UTR-CP567X ALL
CAUTION
Install the unit in an area that has no heat sources, vapors, or the risk of the leakage of fl ammable gas in the vicinity.
Install the unit in an area that is away from the exhaust or vent ports that discharge vapor, soot, dust, or debris.
Install the indoor unit, outdoor unit, power supply cable, transmission cable and remote control cable at least 1 meter away from a television or radio. The purpose of this is to prevent TV reception interference or radio noise. (Even if they are installed more than 1 meter apart, you could still receive noise under some signal conditions.)
Keep the length of the piping of the indoor and outdoor units within the allowable range.
For maintenance purposes, do not bury the piping.
Drain processing3. 2.
The drain water is discharged from the bottom of the equipment. Construct a drain • ditch around the base and discharge the drain water properly. When installing on a roof, perform fl oor waterproofi ng properly.
Drain processing:
The drain water from the base of the outdoor unit may generate during operations.
Perform drain processing, as necessary.
When you want to prevent the drain water from leaking at the perimeter, construct • a ditch for the drain water as shown in the fi gure.
Provide a central drain pan, as necessary.
Outdoor unit
50mm or more
Separation tube2. 5. 2.
Model Total cooling capacity of indoor unit (kW) UTP-AX090A , UTR-BP090X 28.0 or less UTP-AX180A , UTR-BP180X 28.1 to 56.0 UTP-AX567A , UTR-BP567X 56.1 or more
Header2. 5. 3.
3-6 branches 3-8 branches Total cooling capacity of indoor unit (kW) UTR-H0906L UTR-H0908L 28.0 or less UTR-H1806L UTR-H1808L 28.1 to 56.0
INSTALLATION WORK3.
Please obtain the approval of the customer when selecting the location of installation and installing the main unit.
Selecting an installation location3. 1.
WARNING
Install the unit in a location that can withstand its weight, and where it will not topple or fall.
Calculate the proper refrigerant concentration if you will be installing it in an en­closed location.
Total amount of replenished refrigerant in refrigerant facility (kg)
Capacity of smallest room where unit is installed (m3) If the results of the calculation exceed the concentration limit, increase the room surface area or install a ventilation duct.
Refrigerant concentration (kg/m3) (0.3kg/m3)
CAUTION
Select an installation location by observing the following precautions:
Install the unit level. (Within 3 degrees)
Install this unit in a location with good ventilation.
If the unit must be installed in an area within easy reach of the general public, install as necessary a protective fence or the like to prevent their access.
Install the unit in an area that would not inconvenience your neighbors, as they could be affected by the airfl ow coming out from the outlet, noise, or vibration. If it must be installed in proximity to your neighbors, be sure to obtain their approval.
If the unit is installed in a cold region that is affected by snow accumulation, snow fall, or freezing, take appropriate measures to protect it from those elements. To ensure a stable operation, install inlet and outlet ducts.
Install the unit in an area that would not cause problems even if the drain water is discharged from the unit. Otherwise, provide drainage that would not affect people or objects.
10mm or more
Installation dimensions3. 3.
CAUTION
When installing the outdoor unit, pay attention to the following items.
Provide suffi cient installation space, such as transportation route, maintenance space, ventilation space, refrigerant piping space, and passageways.
Pay attention to the specifi cations of the installation space as shown in the fi gure. If the unit is not installed according to specifi cations, it may cause short circuit or poor performance. The unit may be prone to lapse into non-operation due to high pressure protection.
Do not place obstructions in the air fl ow outlet direction. If there is an obstruction in the outlet direction, install an outlet duct.
When there is a wall in front of the unit, provide a space of 500mm or more as maintenance space. When there is a wall at the left side of the unit, provide a space of 30mm or more as maintenance space.
An outdoor temperature of 35 degrees in air-conditioned operation is assumed for the installation space in this item. If the outdoor temperature exceeds 35 degrees and the outdoor unit is operating at a load exceeding its rated ability, provide a larger inlet space.
If you are installing more outdoor units than indicated here, please ensure suffi cient space or consult your distributing agent as it may affect the performance due to short circuit and other problems.
When install near by limited height wall3. 3. 1.
Single and multiple installations(1)
There are no restrictions on the height of the side wall.• Provide installation spaces L1 and L2 in accordance with the table below according • to the wall height (front side, rear side) conditions. Provide installation spaces other than L1 and L2 in accordance with the conditions • shown in the fi gure below. Ventilation resistance can be ignorable when the distance from a wall or product, • etc. is larger than 2m.
Wall height condition Necessary installation space
When H1 is 1500 (mm) or less L1 500 (mm)
When H1 is 1500 (mm) or more L1 500+h1÷2 (mm)
When H2 is 500 (mm) or less L2 100 (mm)
When H2 is 500 (mm) or more L2 100+h2÷2 (mm)
En-3
Page 5
1Fig.
<Front> <Rear>
<Side view>
J
6 Fig.
<Top view>
L4
*

Wall
2 Single installationFig.
<Front>
3 Multiple installationsFig.
<Rear>
<Front>
30mm or more
Concentrated installation(2) Provide installation spaces L3, L4, and L5 in accordance with the table below ac-• cording to the wall height (front side, rear side) conditions. Provide installation spaces other than L3, L4, and L5 in accordance with the condi-• tions shown in the fi gure below. Ventilation resistance can be ignorable when the distance from a wall or product, • etc. is larger than 2m.
Wall height condition Necessary installation space
When H3 is 1500 (mm) or less L3 500 (mm)
When H3 is 1500 (mm) or more L3 500+h3÷2 (mm)
When H4 is 500 (mm) or less L4 200 (mm)
When H4 is 500 (mm) or more L4 200+h4÷2 (mm)
When H5 is 500 (mm) or less L5 200 (mm)
When H5 is 500 (mm) or more L5 200+h5÷2 (mm)
4Fig.
<Front>
.
<Top view>
<Rear>
30mm or more 10mm or more
.
.
<Top view>
20mm or more
<Side view>
.
.
.
20mm or more
J

Wall
<Rear>
*
10mm or more
J
*

.
Wall
5 Fig.
<Front view>
J
*

.
Wall
800mm or more
800mm or more
L3
20mm or more
7 Fig.
20mm or
L5
more
20mm or more
<Top view>
20mm or more
L5L5
L4
500mm or more
1000mm or more
L3
L5
When install near unlimited height wall3. 3. 2.
Single and multiple installations(1)
There are no restrictions on the height of the wall.• The wall (without height restrictions) must not exist on the both sides (left / right) • of outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor unit. Provide installation spaces other than L6 in accordance with the conditions • shown in the fi gure below. Ventilation resistance can be ignorable when the distance from a wall or prod-• uct, etc. is larger than 2 m.
When installing with the REAR of the outdoor unit facing the wall side
Condition Necessary installation space
When B 400 (mm) L6 200 (mm)
When 20 B < 400 (mm) L6 200 + (400-B) ×3 (mm)
8 Single installationFig.
<Rear>
<Front>
9 MFig. ultiple installations
<Rear>
200mm or more
<Top view>
<Top view>
100mm or more
L6
h5
H5
500
Wall Wall
L5
L5
h5
500
<Front>
H5
200mm or more
B
B
En-4
Page 6
800mm or more
200mm or more
When installing with the FRONT of the outdoor unit facing the wall side
10 Fig.
11 Fig.
Wall
200mm or more
Concentrated Installation(2) The wall (without height restrictions) must not exist on the both sides (left / right) of • outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor unit. Ventilation resistance can be ignorable when the distance from a wall or product, • etc. is larger than 2m.
12 Fig.
200mm 200mm
Example : When B is made 200mm L6 200+(400-200)×3=800mm
<Top view>
Wall
200mm or more
20mm or more
<Top view>
<Top view>
20mm or more
Wall
500mm or more
Wall
500mm or more
400mm or more
800mm or more
When there are obstacles above the product3. 3. 3.
When there are obstacles above the product, keep the minimum installation height as shown in the fi gure and install the outlet duct. When installing the outlet duct, you must set the high static pressure mode with the push-button switch. (Similar when installing anti-snow hood)
Setting high static pressure mode
Follow the instructions in the table below to set the high static pressure mode.
Condition
Static Pressure (SP) *1 : 0 SP 30 (Pa)
Static Pressure (SP) 30 < SP 80 (Pa)
Static pressure is the air fl ow resistance that includes *1. the discharge duct resistance & the other additional resistance like discharge grill and so on. Refer to the section on Push Switch Setting in “Chapter 7 Field Setting”.*2.
High static pressure mode
setting
Set to Mode 1
*1
:
Set to Mode 2
*2
Outlet duct
Transportation the outdoor unit3. 4.
Product mass (kg)
A72LALH 220
AJ
A90LALH 220
AJ
AJ
108LALH 275
AJ
126LALH 303
AJ
144LALH 303
Hoisting method
When hanging the outdoor unit and conveying it to installation location, hang the • unit with rope by passing through the 4 opening holes on bottom of front and rear side as shown in fi gure. Use 2 ropes at least 8m long. If used shorter length, it may cause to damage to the • unit
. Use the suffi ciently strong rope to bear the unit’s weight. Place the protective board or fi ller cloth at the place where the cabinet may come into contact with rope to prevent from damages. Without using them, cabinet may cause to damage or deform. During the hanging unit, make sure to keep the unit level to prevent from falling.• To prevent an unit swing accident or falling down of the unit, do not apply any • impact to the unit when it is hanging.
500mm or more
1000mm or more
13Fig.
1000mm or more
400mm or more
400mm or more
400mm or more
<Top view>
400mm or more
800mm or more
400mm or more
500mm or more
1000mm or more
protective boards
opening space
Lifting by forklift
When using the forklift to lift the unit, pass the forklift arms through the opening • space as shown in below.
Front : Bottom of the wooden delivery pallet. Side : Space between pallet and cabinet. (Enable to remove the pallet from cabinet.)
Be careful not to damaged.
Lifting by forklift (Manual forklift: hand-fork)
When using the manual forklift to lift the unit, pass the forklift arms through to the • opening space between pallet and cabinet from side.
En-5
Page 7
SYSTEM CONFIGURATION4.
System confi guration4. 1.
<Front>
Fork (Forklift)
Delivery pallet
<Side>
Fork (Forklift) or Fork (Manual forklift)
Installation the unit3. 5.
Install the unit level. (within 3 degrees).• Install 4 or more anchor bolts at the 8 locations indicated by arrows (Fig. A).• Place the left and right anchor bolts at a distance further away than the dimensions • of A in the Table A. (Excluding the case where anchor bolts are installed at 8 places.)
AFig.
Hole: 12 × 17 (8 places)
80
Table.A
Model name A B
AJ
A72LALH 610 930
A90LALH 610 930
AJ
108LALH 610 930
AJ
126LALH 920 1240
AJ
144LALH 920 1240
AJ
To minimize vibration, do not install the outdoor unit directly on the ground.• Instead, install it on top of a fi rm platform (such as concrete block). (Fig. B) The foundation base should be able to support the product and the foot width of • the product should be more than 46.5mm. Depending on the installation condition, vibration during the operation of the unit • may cause noise and vibration. Install vibration-proofi ng materials (such as rubber pads). Consider the removal space of the connection piping when installing the founda-• tion. Secure the equipment fi rmly with anchor bolts, washers, and nuts.
BFig.
GOODPROHIBITED GOOD
B A
Bottom view
(Unit: mm)
160160
732
80
Bolt (M10)
765
CAUTION
When connecting multiple outdoor units, set the nearest outdoor unit to the indoor • unit on the refrigerant pipe as the master unit. When connecting multiple outdoor units, install the outdoor unit with the largest • nominal system capacity nearest to the indoor unit on the refrigerant pipe, fol­lowed by those with less nominal system capacities.
[Capacity: Master Slave]
Always keep to the limit on the total amount of refrigerant. Exceeding the limit • on the total amount of refrigerant when charging will lead to malfunction.
In case of 1 outdoor unit connected A)
A Fig.
f
I.U.
I.U. I.U. I.U.
Allowable pip length (actual pipe length)
Between master outdoor unit and the farthest indoor unit
Between the fi rst separation tube and the farthest indoor unit
Total pipe length 700 m or less Total
Allowable height difference
Between outdoor unit and indoor unit (When indoor unit is installed below)
Between outdoor unit and indoor unit (When outdoor unit is installed below)
Between indoor units 15 m or less H2, H3
Total refrigerant amount : 31.5 kg or less
In case of 2 outdoor units connected B)
B Fig.
O.U.-1
(Master)
e
I.U.
O.U.
(Master)
O.U. :Outdoor unit
f
O.U.-2
(Slave)
p
I.U. :Indoor unit
H3
O.U. :Outdoor unit I.U. :Indoor unit
b
I.U.
I.U. I.U.
150 m or less
60 m or less f, p
50 m or less
40 m or less
a
I.U. I.U. I.U. I.U.
H4
a
I.U.
H1
H2
I.U.
a+p
H1
a+f
H1
*Do not use a four-corner support foundation.
CFig.
When installing pip­ing from the bottom of the outdoor units, the required space under the outdoor unit 200mm. * Install the branch
kit horizontally.
More than 200mm
I.U.
H2
a+e+f
a+e+p
I.U.
I.U.
I.U.
H3
Allowable pip length (actual pipe length)
Between master outdoor unit and the farthest indoor unit
Between the fi rst separation tube and the farthest indoor unit
Total pipe length 1000 m or less Total
Between outdoor unit and outdoor unit branch kit
150 m or less
60 m or less f, p
3 m or less a, b
En-6
Page 8
Allowable height difference
Between outdoor unit and indoor unit (When indoor unit is installed below)
Between outdoor unit and indoor unit (When outdoor unit is installed below)
50 m or less
40 m or less
Between indoor units 15 m or less H2, H3
Between outdoor units 0.5 m or less H4
Total refrigerant amount : 63 kg or less• Outdoor unit capacity : Master Slave
In the case of 3 outdoor units connected C)
CFig.
O.U.-3
O.U.-1
(Master)
O.U.-2
(Slave1)
a
d
e
H4
b
c
(Slave2)
f
O.U. :Outdoor unit I.U. :Indoor unit
H1
p
H2
H3
Allowable pip length (actual pipe length)
Between master outdoor unit and the farthest indoor unit
Between the fi rst separation tube and the farthest indoor unit
150 m or less
60 m or less f, p
a+e+f
a+e+p
Total pipe length 1000 m or less Total
Between outdoor unit and outdoor unit branch kit
Between the farthest outdoor unit and the rst outdoor unit branch kit
3 m or less a, b, c
12 m or less
b+d c+d
Allowable height difference
Between outdoor unit and indoor unit (When indoor unit is installed below)
Between outdoor unit and indoor unit (When outdoor unit is installed below)
50 m or less
40 m or less
Between indoor units 15 m or less H2, H3
Between outdoor units 0.5 m or less H4
Total refrigerant amount : 94.5 kg or less• Outdoor unit capacity : Master Slave 1 Slave 2
If the outdoor temperature during cooling operation is expected to be –5 °C
NOTE) or less, do not install the outdoor unit lower than the indoor unit
• Please refer to “8.3.2. Checking total amount of refrigerant and calculat­ing the amount of refrigerant charge to be added” for the total amount of refrigerant.
.
(Wall thickness and pipe material for each diameter)
Outside Diameter mm 6.35 9.52 12.70 15.88 19.05 22.22 28.58 34.92 41.27
H1
Wall Thick ness*3mm 0.8 0.8 0.8 1.0 1.2 1.0 1.0 1.2 1.43
Material
Allowable tensile stress 33 (N/mm*1. Allowable tensile stress 61 (N/mm*2. Endurance pressure of the pipes 4.2MPa*3.
Please select the pipe size in accordance with local rules.
JIS H3300 C1220T-O or equiva-
COPPER
lent
2
)
2
)
*1
JIS H3300 C1220T-H or
COPPER
equivalent
*2
A (Between outdoor unit and outdoor unit branch kit)Tab le.
Outdoor unit cooling
HP
capacity (kW)
8 10 12 14 16
22.4 12.70 (1/2") 22.22 (7/8")
28.0 12.70 (1/2") 22.22 (7/8")
33.5 12.70 (1/2") 28.58 (1-1/8")
40.0 12.70 (1/2") 28.58 (1-1/8")
45.0 12.70 (1/2") 28.58 (1-1/8")
Outside diameter (mm)
Liquid pipe Gas pipe
*4
Branch kit
UTP-DX567A, UTR-CP567X
For the installation method, refer to “5.4. Multiple connections”.*4.
B (Between outdoor unit branch kits or outdoor unit branch kit and Table.
rst separation tube)
Tot al co oling ca pa ci ty
of outdoor unit (kW)
Outside diameter (mm)
Liquid pipe Gas pipe
22.4 to 28.0 12.70 (1/2") 22.22 (7/8")
28.1 to 45.0 12.70 (1/2") 28.58 (1-1/8")
45.1 to 56.0 15.88 (5/8") 28.58 (1-1/8")
56.1 to 80.0 15.88 (5/8") 34.92 (1-3/8")
80.1 to 96.0 19.05 (3/4") 34.92 (1-3/8")
96.1 or more 19.05 (3/4") 41.27 (1-5/8")
C (Between separation tubes)Tab le.
Total cooling capacity
of indoor unit (kW)
Outside diameter (mm)
Liquid pipe Gas pipe
4.4 to 11.1 9.52 (3/8") 15.88 (5/8")
11.2 to 13.9 9.52 (3/8") 19.05 (3/4")
14.0 to 28.0 12.70 (1/2") 22.22 (7/8")
H1
28.1 to 44.7 12.70 (1/2") 28.58 (1-1/8")
44.8 to 56.0 15.88 (5/8") 28.58 (1-1/8")
56.1 to 80.0 15.88 (5/8") 34.92 (1-3/8")
80.1 to 95.0 19.05 (3/4") 34.92 (1-3/8")
95.1 or more 19.05 (3/4") 41.27 (1-5/8")
* If the selected pipe diameter between separation tubes (based on table "C") becomes
larger than the pipe diameter between outdoor unit branch kit and the fi rst separation tube (based on table "B"), please select the pipe whose diameter is equal to the one between outdoor unit branch kit and the fi rst separation tube.
(If pipe diameter C > B, select pipe size from table B)
* Total cooling capacity of indoor unit" is the total value for the cooling capacity of indoor
unit connected downstream.
Pipe selection4. 2.
CAUTION
This unit is designed specifi cally for use with the R410A refrigerant. Pipes for R407C or R22 may not be used with this unit. Do not use existing pipes. Improper pipe selection will degrade performance.
unit
Slave
unit1
Indoor
unit
Slave
unit2
Separation tube (optional)
Indoor
unit
Indoor
unit
Master
First separation tube (optional)
Indoor
Indoor
unit
unit
unit
Outdoor unit branch kit (optional)
Indoor
En-7
Pipe size (table A)
Pipe size (table B)
Pipe size (table C)
Pipe size (table D)
D (Between separation tube to indoor unitTab le.
Model code
Cooling capacity of
indoor unit (kW)
)
Outside diameter mm (in)
Liquid pipe Gas pipe
07, 09, 12, 14 2.2, 2.8, 3.6, 4.0, 4.5 6.35 (1/4") 12.70 (1/2")
18, 24, 30 5.6, 7.1, 8.0, 9.0 9.52 (3/8") 15.88 (5/8")
36, 45, 54, 60 11.2, 12.5, 14.0, 18.0 9.52 (3/8") 19.05 (3/4")
72, 90 22.4, 25.0 12.70 (1/2") 22.22 (7/8")
Use a standard separation tube for pipe branching. Do not use a T tube as it does not separate the refrigerant evenly.
E (Separation tube / Header)Tabl e.
Separation tube
Total cooling capacity of indoor unit (kW) Separation tube
*5
28.0 or less UTP-AX090A or UTR-BP090X
28.1 to 56.0 UTP-AX180A or UTR-BP180X
56.1 or more UTP-AX567A or UTR-BP567X
Page 9
Header
*5
Total cooling capacity of indoor unit (kW)
Header
3-6 Branches 3-8 Branches
28.0 or less UTR-H0906L UTR-H0908L
28.1 to 56.0 UTR-H1806L UTR-H1808L
For the installation method, refer to the section on "Indoor unit pipe connections" *5. below.
Protection of pipes4. 3.
Protect the pipes to prevent the entry of moisture and dust.• Especially pay attention when passing the pipes through a hole or connecting the • end of a pipe to the outdoor unit.
Location Working period
Outdoor
Indoor
1 month or more Pinch pipes
Less than 1 month Pinch or tape pipes
Protection method
Pinch or tape pipes
PIPE INSTALLATION5.
Brazing5. 1.
CAUTION
If air or different type of refrigerant enters the refrigeration cycle, the internal pres­sure in the refrigeration cycle will become abnormally high and prevent the unit from exerting its full performance.
Apply nitrogen gas while brazing the pipes. Nitrogen gas pressure: 0.02 MPa (= suf­ cient pressure to be felt on the back of your hand or more)
If a pipe is brazed without applying nitrogen gas, it will create an oxidation fi lm. This can degrade performance or damage the parts in the unit (such as the com­pressor or valves).
Do not use fl ux to braze pipes. If the fl ux is the chlorine type, it will cause the pipes to corrode. In addition, if the fl ux contains fl uoride, it will affect the refrigerant piping system due to deterioration of refrigerant oil.
For brazing material, use phosphor copper that does not require fl ux.
Fig.
Pressure regulating valve Cap
Nitrogen gas
Brazing area
Header
Gas pipe
Outdoor unit side
Liquid pipe Outdoor
unit side
H
= 0 to 10 mm
1
(α1: 0° to 1°) β1: -10° to 10°
= 0 to 10 mm
H
2
(α2: 0° to 1°) β2: -10° to 10°
C
D
Horizontal line
A
1
H
1
Vertical line
2
GOOD
Horizontal line
A
2
H
PROHIBITED PROHIBITED
CAUTION
Do not connect a separation tube after a header.
Leave the distance 0.5 m or more for straight part to branch tube and header.
Main pipe
Main pipe
0.5 m or more
0.5 m or more
To in do or u ni t
0.5 m or more
To in do or u ni t
0.5 m or more
Separation tube
or
Header
To in do or u ni t
Separation tube
or
Header
To in do or unit
B
1
VIEW C
B2
VIEW D
To in do or unit
Horizontal line
Indoor unit pipe connections5. 2.
CAUTION
For details, refer to the Installation Instruction Sheet of each part.
Separation tube
Horizontal
A
± 15°
B
Horizontal line
GOOD
A : Outdoor unit or Refrigerant branch kit B : Indoor unit or Refrigerant branch kit
PROHIBITED
A
Vertic al
B
To in do or u ni t
Piping method5. 3.
Opening the knockout hole5. 3. 1.
B
Be careful to prevent panel deformation or damaged while opening the knockout hole.
or
A
To prevent cutting of the wiring after the knockout hole was opened, remove the burrs along the edge.
In addition, to prevent rusting, painting the edge with rust preventive paint is recom-
mended.
The piping can be connected from 2 directions; the front or the bottom. (Knockout holes are provided so that the piping can be connected from 2 different directions.) Use the front knockout hole, as required.
A Knockout positionFig.
CAUTION
En-8
Page 10
B Detail of knockout position (bottom)Fig.
(Unit: mm)
Knockout hole
After all the gas is vented, melt the brazing fi ller metal on connecting part using a 3) torch and remove the pinch pipe.
C Detail of knockout position (front)Fig.
95
75
10
100
(Unit: mm)
Knockout hole
125
4373199
Removing the pinch pipe5. 3. 2.
WARNING
Remove the pinch pipe only when the internal gas is completely drained as shown on the below instructions. If gas still remains inside, the piping may crack if you melt the brazing fi ller metal of the junction area with a burner.
Before connecting the piping, remove the pinch pipe in accordance with the following instructions:
Verify that the liquid side and gas side 3-way valves are closed. 1)
3-way valve
Pinch pipe
Pipe connection5. 3. 3.
CAUTION
Seal the pipe route hole with putty (fi eld supply) such that there are no gaps. Small insects or animals that are trapped in the outdoor unit may cause a short circuit in the electrical component box.
To prevent pipe damage; do not make sharp bends. Bend the pipe at a radius of 70mm or greater.
Do not bent pipe many times at same part to prevent break.
After completing all the pipe connection by brazing, perform the indoor unit pipe con­nection with a fl are joint.
When removing the pinch pipe or brazing the joint pipe, carry out the work while cooling down the 3-way valve suffi ciently.
Braze the joint pipe onto the 3-way valves at the liquid and gas side.• Install the joint pipe appropriately so that it can be connected easily with the main pipe. Braze the joint pipe at the liquid and gas side with the main pipe.• * Be sure to supply nitrogen when brazing.
AFig.
Joint pipe (Accessory)
Joint pipe (Field supply)
Liquid pipe
(Field supply)
BFig.
Knockout hole
Gas pipe (Field supply)
To in do or u ni t
Cut the end of the liquid side and gas side pinch pipe and vent the gas inside the 2) pinch pipe.
End of pinch pipe
En-9
Joint pipe
(Field supply)
Multiple connections5. 4.
CAUTION
When connecting multiple (maximum 3) units, be sure to install the unit with the
largest capacity nearest to the indoor unit.
For example) AJ
When connecting multiple units, set the unit with the largest capacity as the master
unit, and the rest as the slave units.
(Refer to 7. Field Setting)
When connecting multiple units, use the optional outdoor unit branch kit.
126LALH (Outdoor Unit1) + AJ 126LALH (Outdoor Unit2) +
AJ
A90LALH (Outdoor Unit3)
Joint pipe (Accessory)
Knockout hole
Page 11
To in do or u ni t
Outdoor unit 1
(Master unit)
Outdoor Capacity 2 Units : Unit 1 Unit 2 3 Units : Unit 1 Unit 2 Unit 3
Outdoor unit 2
(Slave unit 1)
Outdoor unit 3
(Slave unit 2)
CAUTION
To prevent the oil from settling in the stopped unit, install the pipes between the outdoor units so that they are level or are tilted upward to the outdoor units.
Examples of multiple unit installation are shown below.(1) Installable patterns a)
GOOD
Master
unit
Slave unit 1
Slave
unit 2
Outdoor unit branch kit (Optional)
To in do or u ni t (To main pipe)
To ou td oor un it
To ou td oor un it
Branch kit restriction when install
Be sure following restriction.
Installation angle 1)
Outdoor unit branch kit
Horizontal
A
To in do or u ni t
PROHIBITED
GOOD:
0° to -10°
PROHIBITED
Vert ical
PROHIBITED PROHIBITED PROHIBITED
Install the outdoor unit branch kit horizontally level, within 0° to -10°, so that the • refrigerant separates evenly. Do not install the outdoor unit branch kit vertically.
Straight pipe length 2)
To in do or u ni t (To main pipe)
To indoor unit (To main pipe)
Leave the distance 0.5 m or more for straight part to outdoor unit branch kit.
For details, refer to the Installation Instruction Sheet of the outdoor unit branch kit. 3)
Examples of multiple unit installationFig.
(Example 1)
Master unit Slave unit1 Slave unit2
(Example 2)
Master unit Slave unit1 Slave unit2
A
0.5 m or more
0.5 m or more
Liquid pipe (Field supply)
C
To ou td oor un it
To ou td oor un it
B
To outdoor unit or
C
next branch kit
C
B
To ou td oor un it
(Example 3)
Master unit
Slave unit1
Slave unit2
Joint pipe (Accessory)
Gas pipe (Field supply)
PROHIBITED
GOOD:
0° to -10°
PROHIBITED
To ou td oor un it
To ou td oor un it
To ou td oor unit
To in do or u ni t
GOOD
To in do or u ni t
GOOD
To in do or u ni t
Non-installable patterns b)
PROHIBITED
To in do or u ni t
PROHIBITED
To in do or u ni t
PROHIBITED
To in do or u ni t
If the pipe length between outdoor unit branch kit and outdoor unit branch kit (2) (or slave unit) is longer than 2 m, or a lower pipe line exists between outdoor units, rise for gas pipe should be arranged to eliminate oil from entering into and remaining at pipes and the stopped outdoor unit. However, there is no need to provide a rise on the pipe connecting between the master unit and the indoor unit even if the length exceeds 2m.
To in do or u ni t
To in do or u ni t
To in do or u ni t
Master
unit
Master
unit
Master
unit
Master
unit
Master
unit
Master
unit
Master
unit
Master
unit
Slave unit 1
2 m or less 2 m or less
2 m or more 2 m or more
Slave unit 1
Slave unit 1
Slave unit 1
2 m or less2 m or less
Slave unit1
Slave
unit 1
Slave unit 1
Slave
unit1
Rise
lower pipe
Slave unit 2
Slave unit 2
Slave unit 2
Slave unit 2
Slave unit 2
Slave unit 2
Gas pipe
Rise
(200 mm or more)
Slave
unit2
500 mm or less
Gas pipe
Slave
unit2
Gas pipe
En-10
Page 12
ELECTRICAL WIRING6.
The precautions of electrical wiring6. 1.
WARNING
Wiring connections must be performed by a qualifi ed person in accordance with specifi cations. The rated supply of this product is 50Hz, 400V of 3-phase, 4-wire. Use a voltage within the range of 342-456V.
Make sure to perform earthing (grounding) work. Improper earthing (grounding) work can cause electric shocks.
Before connecting the cables, make sure the power supply is OFF.
Be sure to install an earth (ground) leakage breaker. Otherwise, it will cause electric shock or fi re.
Be sure to install a breaker of the specifi ed capacity. When selecting breaker, please comply with the laws and the regulations of each country. One breaker must be installed on the power supply of the outdoor unit. Wrong selection and setup of the breaker will cause electric shock or fi re.
Do not connect AC power supply to the transmission line terminal board. Improper wiring can damage the entire system.
Connect the connector cord securely to the terminal. Faulty installation can cause a fi re.
Do not modify power cable, use extension cable or branch wiring. Improper use may cause electric shock or fi re by poor connection, insuffi cient insulation or over current.
Make sure to secure the insulation portion of the connector cable with the cord clamp. A damaged insulation can cause a short circuit.
Never install a power factor improvement condenser. Instead of improving the power factor, the condenser may overheat.
Before servicing the unit, turn the power supply switch OFF. Then, do not touch elec­tric parts for 10 minutes due to the risk of electric shock.
Always use a separate power supply line protected by a circuit breaker operating on all cables with a distance between contact of 3 mm for this unit.
Use crimp-type terminals and tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating may be produced and possibly cause serious dam­age inside the unit.
Securely install the electrical box cover on the unit. An improperly installed service panel can cause serious accidents such as electric shock or fi re through exposure to dust or water.
If the supply cable is damaged, it must be replaced by the manufacturer, its service agent or similarly qualifi ed persons in order to avoid a hazard.
CAUTION
The primary power supply capacity is for the air conditioner itself, and does not include the concurrent use of other devices.
Connect the power cables in positive phase sequence. If they are connected in negative phase sequence, an error will be displayed. If there is a missing phase con­nection, the unit will not operate normally. Do not connect a N phase (neutral phase) cable to other phases (misconnection). Wrong wiring will lead to parts damage.
Do not use crossover power supply wiring for the outdoor unit.
If the electrical power is inadequate, contact your electric power company.
Install a breaker (Included with earth leakage circuit breaker) in a location that is not exposed to high temperatures. If the temperature surrounding the breaker is too high, the amperage at which the breaker cuts out may decrease.
Use a breaker (Included with earth leakage circuit breaker) that is capable of handling high frequencies. Because the outdoor unit is inverter controlled, a high-frequency breaker is necessary to prevent a malfunction of the breaker itself.
When the electrical switchboard is installed outdoors, place it under lock and key so that it is not easily accessible.
Never bundle the power supply cable and transmission cable, remote control cable together. Separate these cable by 50 mm or more. Bundling these cables together will cause miss operation or breakdown.
Always keep to the maximum length of the transmission cable. Exceeding the maxi­mum length may lead to erroneous operation.
The static electricity that is charged to the human body can damage the control PC board when handling the control PC board for address setting, etc. Please keep caution to the following points. Provide the earthing (grounding) of Indoor unit, Outdoor unit and Option equipment. Cut off the power supply (breaker). Touch the metal section (such as the unpainted control box section) of the indoor or outdoor unit for more than 10 seconds. Discharge the static electricity in your body. Never touch the component terminal or pattern on the PC board.
Wiring method6. 2.
The wiring example for outdoor units and indoor units is shown in the fi gure.
To other refrigerant cricuit outdoor unit
Power supply
400V 3Ø 50Hz
Outdoor unit 1 (Master unit)
Transmission Transmission Transmission
Power supply
*1
Breaker Breaker Breaker
Power supply 230V 1Ø 50Hz
*1: The number of power supply terminals is different depending on the indoor unit
model. For the wiring, refer to the indoor unit installation manual.
*2: Earth (Ground) the remote controller if it has an earth (ground) cable.
There are two types of remote controller: the 2-wire type and the 3-wire type. For • details, see the relevant remote controller installation manual. (When connecting the 2-wire type remote controller, Y3 is not used.)
Remote control Remote control Remote control
*2 *2 *2
Remote
controller
Power supply
400V 3Ø 50Hz
Power supplyPower supply
Outdoor unit 2 (Slave unit 1)
Power supply Power supply
*1 *1
Remote
Power supply 230V 1Ø 50Hz
controller
Power supply
400V 3Ø 50Hz
Breaker Breaker Breaker
Power supply
Outdoor unit 3
(Slave unit 1)
TransmissionTransmissionTransmission
Indoor unitIndoor unitIndoor unit
Power supply 230V 1Ø 50Hz
Remote
controller
Knockout hole6. 3.
CAUTION
Seal the wiring route hole with putty (fi eld supply) such that there are no gaps. Small insects or animals that are trapped in the outdoor unit may cause a short circuit in the electrical component box.
Be careful not to deform or scratch the panel while opening the knockout holes.
After opening the knockout hole, remove the burr on the edges to prevent snapping of cables. It is recommended to apply rust proof paint on the edges to prevent rust.
Electric wires can be connected from the front or from the left. (Knockout holes are prepared so that wiring can be made from 2 different directions.) Use the knockout holes on the front and the left separately when necessary.
En-11
Page 13
In case of connected 3 outdoor unitFig.
GOOD
Sub
Main breaker
400 V 3ø 50 Hz
breaker
< Left view >
Ø 50
Ø 34.5
Ø 43.7
Ø 22.2
< Front view >
Ø 50
Ø 34.5
Ø 22.2
Ø 43.7
(Unit: mm)
Selecting power supply cable and breaker6. 4.
CAUTION
Obtain the distribution network operator's agreement about the power capacity of the power supply system, specifi cation of the cable and the harmonic current, and etc. when you connect the outdoor unit with the power supply.
Regulation of wire size and circuit breaker differs from each locality, please refer in accordance with local rules.
Refer to the table for the wiring and breaker specifi cations of each installation condition
Selecting power supply cable and breaker when connecting 1 outdoor unit(1)
MODEL
AJ
A72LALH 30
A90LALH 30
AJ AJ
108LALH 50 126LALH 50
AJ
144LALH 50
AJ
MODEL
A72LALH 4 4 30
AJ AJ
A90LALH 4 4 30
108LALH 10 6 42
AJ
126LALH 10 6 42
AJ
144LALH 10 6 42
AJ
These values are recommended data. 1) Specifi cation: Use conformed cord with Type 60245 IEC66 2) Max. wire length: Set a length so that the voltage drop is less than 2%. Increase 3) the wire diameter when the wire length is long.
In case of connected outdoor unitFig.
Transmission cable
GOOD
400 V 3ø 50 Hz
Breaker
Outdoor unit Power supply cable
Selecting main breaker and main power supply cable when connecting multiple (2) outdoor units
Main breaker: Main breaker Total Sub breaker sub breaker capacity)
Breaker (Time delay fuse or circuit capacity)
Fuse capacity (A) Leakage current
100mA
0.1sec or less
Outdoor unit power supply cable
Power supply
cable (mm
Ground wire (mm2)
2
)
230 V 1ø 50 Hz
(Refer to the table in item (1) for the
Critical wiring
Indoor unit Power supply cable
Breaker
Remote controller cable
length (m)
Outdoor unit power supply cable
Example of bad breaker wiring(3)
PROHIBITED
400 V 3ø 50 Hz
Outdoor unit Breaker PROHIBITED: install a breaker for each outdoor unit
Power supply cable
PROHIBITED: crossover
power supply wiring prohibited
Transmission line6. 5.
CAUTION
Caution when wiring cable
.
When stripping off the coating of lead wire, always use the exclusive tool such as a wire stripper. If there is no exclusive tool available necessarily, carefully strip the coating by a cutter etc. so that the conductive wire is not damaged. If it is damaged, it may lead to an open circuit and a communication error.
Pay attention to the following points while attaching wires on the terminal board.• Do not attach 2 wires on one side. Do not twist wires. Do not cross the wires. Do not shorted at edge at root.
2pcs at one side
PROHIBITED
Shorted at edge
PROHIBITED PROHIBITED
Wires twisted
PROHIBITED
Shorted at root
Transmission wiring specifi cations6. 5. 1.
Follow the specifi cations below for the transmission cable.
Use Size Wire type Remarks
Transmission
cable
0.33mm
22AWG LEVEL 4 (NEMA)
2
non-polar 2core, twisted pair
solid core diameter 0.65mm
Wiring rules6. 5. 2.
(1) Total length of transmission cable
Total transmission line length : Max. 3,600 m
EF + EG + GH + HJ + HK + KL < 3,600 m (Fig.2)
In the following cases , Signal Amplifi er is required.
When the total length of the transmission line exceeded 500 m.
①
AB + BC + BD > 500 m (Fig.1)
When the total number of units* is over 64.
②
Transmission line length between each unit*
③
(2) Length of transmission cable between 1 network segment (NS)
EF + EG + GH + HJ + HK 500 m (Fig.2) KL 400 m (Fig.2)
(3) Length of transmission cable between outdoor units in a refrigerant system
MN 18 m NP 18 m
400m
1 wire
GOOD
2 wires
GOOD
LONWORKS
patible cable
®
com-
En-12
Page 14
1Fig.
Terminal resistor
2Fig.
Outdoor unit
B
A
Indoor unit
When AB + BC + BD > 500 m : Signal Amplifi er is required.
Outdoor unit
E
Terminal resistor
M
N
Transmission line
Indoor unit
F
Wiring procedure6. 6.
System
Controller
C
D
Tou c h Panel
Controller
NS 1
P
• Remove the cover of the electrical compartment and follow the terminal plate to con­nect the electric cables to the terminal.
• After connecting the cables, secure them with the cable ties.
• Connect the cables without applying excessive tension.
Cable routing
Secure with a binder as shown in the fi gure below.
Connecting the power supply cable
Connecting the transmission cable
G
Transmission line
H
K
Signal Amplifi er
NOTE)
Unit* means indoor unit, outdoor unit, Touch Panel Controller and System Controller, Signal Amplifi er, single split adaptor, Network Convertor etc..
Do not use loop wiring. This may lead to parts damage and erroneous operation.
Terminal resistor
J
NS 2
Tou c h Panel Controller
System
L
Controller
Enabling/Disabling automatic address setting6. 5. 3.
You can enable/disable automatic address setting for the indoor unit and the signal amplifi er. To enable automatic address setting for the indoor unit, connect the indoor unit to outdoor units under the same refrigerant system.(Fig.4)
Example : Disable Automatic Address setting
Refrigerant system 1
Refrigerant system 2
Refrigerant system 3
Example : Enable Automatic Address setting
Refrigerant system 1
Transmission line
Transmission line
Transmission line
Transmission line
Cable tie (Accessory)
Cable guide
Cable clip
Cable tie * (Accessory)
Power supply cable routing
* Tighten the cable tie fi rmly so that pulling force does not propagate to the terminal connection even if force of 100N is applied to the cable.
Transmission cable routing
Connecting cables to the terminals
WARNING
Use ring terminals and tighten the terminal screws to the specifi ed torques, other- wise, abnormal overheating may be produced and possibly cause heavy damage inside the unit.
Be sure fi ll the holes of power supply cable and transmission cable with putty (fi eld supply). If small animals such as insects enter the electrical component box, a short circuit may be caused.
Tight ening to rque
M3 screw 0.5 to 0.6 N·m (5 to 6 kgf·cm)
M8 screw 5.0 to 7.0 N·m (50 to 70 kgf·cm)
Refrigerant system 2
Refrigerant system 3
En-13
Transmission line
Transmission line
Page 15
(1) Connecting the power supply cable
Caution when wiring cable
1) Use crimp-type terminals with insulating sleeves as shown in the fi gure to con- nect to the terminal block.
2) Securely clamp the crimp-type terminals to the cables using an appropriate tool so that the cables do not come loose.
3) Use the specifi ed cables, connect them securely, and fasten them so that there is no stress placed on the terminals.
4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screwdriver that is too small, otherwise, the screw heads may be damaged and prevent the screws from being properly tightened.
5) Do not tighten the terminal screws too much, otherwise, the screws may break.
6) See the table for the terminal screw tightening torques.
Strip 10 mm
Ring terminal
Sleeve
Cable
Screw with special washer
Ring terminal
Screw with special washer
Ring terminal
Terminal block
Cable
External input and external output6. 7.
Terminal position6. 7. 1.
Base heater (CN115: Black)
Output 1 (CN136: Black)
Output 2 (CN137: Blue)
Input 4 (CN134: Red)
Input 3 (CN133: White)
Input 2 (CN132: Green)
Input 1 (CN131: Yellow)
Input 5 (CN135: Orange)
Ring terminal: M8
Earth (Ground) cable
Cable clamp
90 to 100 mm
70 to 80 mm
Use a ring terminal to connect the electric cables to the power supply terminal * board.
(2) Connecting the transmission cable
Sealing transmission cable
Connect both ends of the sealed wires of the transmission cable to the earth terminal of the equipment or to the earth screw near the terminal. Be very careful that the screws are not overly tightened as the wires may snap and the terminal may be damaged.
Wind with insulation tape to prevent short circuit
Use one side of the twisted-pair cable
Be sure to use one side of a twisted-pair cable when using transmission cable with 2 sets of twisted-pair cables.
8 to 10 mm
Connect both ends of sealed cable to earth.
IN
RB
Outdoor unit PC board
CAUTION
Do not bundle the cable for base heater with other cables.
(Example) In case of Outdoor unit
Insert the connector to CN136 (Black) and CN137 (Blue) of control PC board. (1) Fix it to the wire with the attached cable tie.(2)
CN136 (Black)
CN115 (Black)
Clamp
Wire
Do not clamp the base heater cable.
External input terminal6. 7. 2.
Service parts: EXTERNAL INPUT WIRE A (9368777005)
Setting to low noise mode, outdoor unit operation peak control setting, emergency/• batch stop and electricity meter pulse are possible from the outside. Except for wattmeter pulse reception (CN135) among external input terminals, only • the Master unit is effective.
Clamp
CN137 (Blue)
Cable tie (Accessory)
40 mm or more
Cable clip
Cable tie (Accessory)
Wiring method and specifi cations
A twisted pair cable (0.33 mm* cable is 150 m. Use an external input and output cable with appropriate external dimension, de-* pending on the number of cables to be installed For each input, pin No.1 is of positive polarity and pin No.2 is of ground level.*
2
(22AWG)) should be used. Maximum length of
En-14
Page 16
Input 1 CN131
(Yellow)
P. C .B
connected unit connected unit
Operation behavior
Each input terminal works as follows.
Connector Input signal Status
Input 1 CN131 (Yellow)
Input 2 CN132 (Green) *1
Input 3 CN133 (White)
Input 4 CN134 (Red)
Input 5 CN135 (Orange) *4
Slave unit can connect only input5 (CN135).
The operations of each input terminal and the selection of function are set with the push button on the PC board of outdoor unit. About the setting, please refer to 7.4. Push button setting.
Note : *1: The "external input priority mode" must be set by pressing push button on PC
board of outdoor unit.
*2: Batch stop or Emergency stop pattern can be selected by outdoor unit PC
board push button.
*3: The emergency stop function mounted in the V-II does not guarantee the
regulations of each country. For this reason, suffi cient checking is necessary regarding use. Especially, since the fact that the equipment may not be emergency-stopped in the case of breaking of the wiring to the external input terminals and com­munication line, communication error due to noise, VRF external input circuit trouble, etc. must be considered, the provision of double measures that add direct interruption of the power supply by switch, etc. is recommended as a precaution.
*4: Pulse input to CN135 must be width 50ms or more, and must be interval 50ms
or more.
CN132 (Green)
OFF Normal operation
ON Low noise mode operation
OFF Cooling priority
ON Heating priority
OFF Normal operation
ON
OFF Normal operation
ON
No pulse
Pulse
Input 3Input 2
CN133 (White)
connected unit connected unit connected unit
Outdoor unit operation peak control
Batch stop or Emergency stop operation *2, *3
No information from electricity meter
Power usage information from electricity meter
Input 4 CN134
(Red)
Input 5
CN135 (Orange)
Outdoor unit
Master Slave
O
O
O
O
OO
External output terminal6. 7. 3.
Service parts : EXTERNAL INPUT WIRE A (9368777005)
You can detect the operation condition of outdoor unit and the abnormal situation • of both indoor and outdoor unit. The external output terminal is only valid for Master Unit.
Wiring method and specifi cations
Error status (Master unit only)
This output indicates the outdoor unit and connected indoor unit's "Normal" or "Error" status.
Operation status (Master unit only)
This output indicates the outdoor unit's "Operation" status.
Connector Output voltage Status
CN136 (Black)
CN137 (Blue)
0 V Normal DC 12 to 24 V Error 0 V Stop DC 12 to 24 V Operation
P. C .B
CN136 (Black) or CN137 (Blue)
5: Provide a DC12 to 24 V power supply. *
Select a power supply capacity with an ample surplus for the connected load.
6: The allowable current is 30 mA or less. *
Provide a load resistance such that the current becomes 30 mA or less.
7: Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.*
Do not impress a voltage exceeding 24 V across pins 1-2.
A twisted pair cable (0.33 mm* cable is 150 m. Use an external input and output cable with appropriate external dimension, de-* pending on the number of cables to be installed.
+
1
2
*7
DC power supply (External) 12 to 24 V
+ -
Connected load (Operation Indicator or Error Indicator)
2
(AWG22)) should be used. Maximum length of
*5
*6
connected unit
Base heater terminal6. 7. 4.
Service parts : WIRE WITH CONNECTOR (9708642000)
This is the output signal for base heater. Output signal ON, when the outdoor tem-
perature goes down below 2°C, and signal OFF at the outdoor temperature 4°C.
P. C .B
1
CN115 (Black) *8
8: Connect to pin 1 and pin 3. No connection pin 2 and pin 4.* 9: The allowable current is 1 A or less.*
AC240 V
2
(For rated 415 V power supply)
3
(0.82 mm
Cable
4
2
(18AWG))
Base heater *9
FIELD SETTING7.
CAUTION
Discharge the static electricity from your body before setting up the DIP switches. Never touch the terminals or the patterns on the parts that are mounted on the board.
Field setting switches7. 1.
Remove the service panel of the outdoor unit and the cover of the electrical compo­nent box to access the PC board of the outdoor unit. PC board switches for various settings and LED indicators are shown in the fi gure.
DIP switch setting7. 2.
List of Settings7. 2. 1.
SET3 and SET5 must be set for the DIP switch. Confi gure the settings before turning on the power. Settings for SET1, SET2, and SET4 DIP switches are factory default ones. Do not change them.
DIP Switch Function
SET1 1-4 Forbidden
SET2 1-4 Forbidden
1
SET3
SET4 1-4 Forbidden
SET5
2
3
4
1-2 Number of outdoor units installed
3 Forbidden
4 Terminal resistor setting
Outdoor unit address setting
Setting for number of slave units
En-15
Page 17
LED lamp
7 Segment LED indicator
Rotary switch
X 10 X 1
Confi gure the setting (DIP switch SET5) of the terminal resistor of the outdoor units as shown below from conditions 1 to 3.
SET5
4
OFF Disable (Factory setting)
ON Enable -
Terminal resistor Remarks
Push button
Outdoor unit PC board
DIP switch
5'6
Settings to be confi gured locally7. 2. 2.
Outdoor unit address setting(1) When 2 or 3 outdoor units are installed to 1 refrigerant system, set the address for each outdoor unit. Set the address for all outdoor units.
SET3
12
OFF OFF 0 Master unit (Factory setting) OFF ON 1 Slave unit 1
ON OFF 2 Slave unit 2 ON ON - Forbidden
Nu(2) mber of slave units setting for outdoor unit Set the number of slave units connected to 1 refrigerant system. Set only the master unit.
SET3
34 OFF OFF 0 Master unit only (Factory setting) OFF ON 1 1 slave unit connected
ON OFF 2 2 slave unit connected ON ON - Forbidden
Number o(3) f outdoor units installed The number of outdoor units installed in 1 refrigerant system must be set. Set for all outdoor units.
SET5
12 OFF OFF 1 (Factory setting) OFF ON 2 -
ON OFF 3 ­ON ON - Forbidden
Outdoor unit address Remarks
Number of connectable
outdoor units
Number of outdoor units Remarks
Remarks
Terminal resistor setting7. 2. 3.
CAUTION
Be sure to set the terminal resistor according to specifi cations. Set the terminal resistor for every network segment (NS).
If terminal resistor is set in multiple devices, the overall communication system may be damaged. If terminal resistor is not set in a device, abnormal communication may occur.
Figure: Terminal resistor setting
Master unit
Master unit
Master unit
NS2 (Network segment 2)
About the setting of terminal resistor
Outdoor unit (Master unit)
:on
:off
Signal amplifi er
Install
Do not install
NS1 (Network segment 1) (Set terminal resistor at outdoor units)
Terminal resistor: on
Refrigerant system1
Terminal resistor: off
Refrigerant system2
Refrigerant system3
NS3 (Network segment 3)
Terminal resister: on
NS4 (Network segment 4)
Rotary switch setting7. 3.
The rotary switch (REF AD) sets the refrigerant circuit address of the outdoor unit. Confi gure the settings only on the master unit of a refrigerant system. If multiple refrigerant systems are connected, set the rotary switch (REF AD) as shown in the table below.
Rotary Switch Setting
Refrigerant circuit address
000 101 202 303 404
・・・ ・・
97 9 7 98 9 8 99 9 9
REF AD
×10 ×1
Be sure to set 1 terminal resistor in a network segment. You can set the terminal resistor at the outdoor unit or signal amplifi er. When settin g the terminal resistor of a signal amplifi er, refer to the installation manual of the signal amplifi er.
When settin• g multiple terminal resistors, take note of the following items.
How many network segments are there in a VRF system?
Where will you set the terminal resistors in a network segment? (Condition for 1
segment: Total number of outdoor and indoor units and signal amplifi ers is less than 64, or the total length of the transmission cable is less than 500m)
How many outdoor units are connected to 1 refrigerant system?
Setting Setting range Type of switch
Refrigerant circuit
address
Rotary Switch (REF AD×1): Factory setting "0" Rotary Switch (REF AD×10): Factory setting "0"
0–99
Setting
example
63
REF AD × 10 REF AD × 1
En-16
Page 18
Push button setting7. 4.
Various functions can be set when necessary. Perform settings after all indoor units have stopped operation.
A: List of SettingsTab le.
No Setting Item
Standard (40 to 65 m)
Short (less than 40 m) 0 1
Pipe length set­ting *1
00
Pipe length means the length between master outdoor unit and the nearest indoor unit.
Sequential start shift *1
10
The start-up timing of outdoor unit (compressor) can be set up so that it can delay several seconds. This feature is useful when multiple number of outdoor units are installed and turned on at the same time to limit the starting current.
Cooling capacity shift *1
11
Set this item when necessary.
Heating capacity shift *1
12
Set this item when necessary. (Forbidden) 1 3 0 0
13
Switching between batch stop or emergency stop
This mode selects the pattern of the stop function to be operated by the external input terminal (CN134).
• Batch stop: The stop of all indoor units connected to same refrigerant system
20
due to input signal coming from CN134.
• Emergency stop: When emergency stop is actuated, the indoor unit does not accept the operation command from the remote controller. On the other hand, when the emergency stop is released (no input from CN134), the air condi­tioner does not return to the original operation until the indoor unit is turned on by the remote controller.
Operation mode selecting method *1
21
Select the priority setting of the operation mode.
• Priority given to the fi rst command: Priority is given to the operation mode which is set fi rst.
• Priority given to external input of outdoor unit: Priority is given to the operation mode which is set by the external input terminal (CN132).
• Priority given to administrative indoor unit: Priority is given to the operation mode of the administrative indoor unit which is set by the wired remote control­ler.
Snow falling protection fan mode *1
22
This mode operates the fans of outdoor units in order to prevent the units from stop­ping operation when they are covered by snow.
Interval setting for snow falling protection fan
23
mode *1
When the snow falling protection fan mode is set, the operation interval of the fans of outdoor units can be selected.
Medium (65 to 90 m) 0 2
Long 1 (90 to 120 m) 0 3
Long 2 (120 to 150 m) 0 4
Normal 21 sec. Delay 0 1 42 sec. Delay 0 2 63 sec. Delay 0 3
Normal mode Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 (Forbidden) 0 4
Normal mode Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3
Batch stop
Emergency stop 0 1
*1
Priority given to the fi rst command
Priority given to external input of outdoor unit
Priority given to adminis­trative indoor unit
Normal mode Snow falling protection fan
mode
Standard (30 minutes) Short 1 (5 minutes) 0 1 Short 2 (10 minutes) 0 2 Short 3 (20 minutes) 0 3
7 segment LED indicator
First 2
Last 2 digits
digits
00
00
00
10
00
11
00
12
20
21
22
23
00
00
01
02
00
01
00
Factory
setting
Standard
High static pressure 1 High static pressure mode
24
When installing a duct to the blow-off outlet of an outdoor unit, set the high static pressure mode according to the static pressure of the duct to be installed. Furthermore, use this setting if the air blow of an outdoor unit is poor, such as when installed in a place with a low ceiling.
(Forbidden) 2 5 0 0
25
(Forbidden) 2 6 0 0
26
(Forbidden) 2 7 0 0
27
(Forbidden) 2 8 0 0
28
(Forbidden) 2 9 0 0
29
Energy saving level setting *1
30
The capacity limit can be selected by the external input terminal (CN133) when operating with the “Energy Saving Peak Cut function”. The lower the level, the more the effect of energy saving, but the cooling/heating performance will also drop.
Capacity priority setting (in low noise mode) *1
40
If the cooling/heating performance becomes insuffi cient when the low noise mode is set, it is possible to set “capacity priority” that automatically cancels the low noise mode (once performance is restored, the mode will automatically return to the low noise mode).
Low noise mode setting *1
41
Low noise mode operation level
42
*1
setting The noise level when operating in the low noise mode can be set.
Back up operation 1
60
*1
Electricity meter No. setting 1 *2
70
Set the ones digit and tens digit of the No. of the electricity meter connected to CN135.
Electricity meter No. setting 2 *2
71
Set the hundreds digit of the No. of the electricity meter connected to CN135.
Electricity meter pulse setting 1 *3
72
Set the ones digit and tens digit of the No. of the electricity meter pulse setting connected to CN135.
(equivalent to 30Pa)
High static pressure 2
(equivalent to 80Pa)
(Forbidden) 0 3
Level 1 (stop) Level 2 (operated at 40%
capacity) Level 3 (operated at 60%
capacity) Level 4 (operated at 80%
capacity) Level 5 (operated at 100%
capacity)
Off (quiet priority)
On (capacity priority) 0 1
Off (Normal) On (Low noise mode) 0 1
Level 1 (55 dB)
Level 2 (50 dB) 0 1
On Off 0 1 Setting number (x00) Setting number (x01) 0 1
······ ··· ··· Setting number (x98) 9 8 Setting number (x99) 9 9
Setting number (0xx) Setting number (1xx) 0 1 Setting number (2xx) 0 2
Setting number (xx00) Setting number (xx01) 0 1
······ ··· ··· Setting number (xx98) 9 8 Setting number (xx99) 9 9
24
30
40
41
42
60
70
71
72
00
01
02
00
01
02
03
04
00
00
00
00
00
00
00
En-17
Page 19
Electricity meter pulse setting 2 *3
73
Setting number (00xx) Setting number (01xx) 0 1
······ ··· ···
73
Setting number (98xx) 9 8
00
Setting number (99xx) 9 9
Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135.
(Forbidden) 9 0 0 0
90
*1: Do not set this for outdoor units with Slave setting. *2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to CN135
become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
(1) Turn on the power of the outdoor unit and enter standby mode.
When system is normal
POWER/MODE lamp lights up. (ERROR lamp is off.)
POWER/MODE lamp: ON
7 segment LED indicator: OFF
MODE/EXIT button
When system is abnormal• Check the settings as there is an error in the settings for outdoor unit address (DIP switch SET3-1, 2) or number of connected slave units (DIP switch SET3-3, 4).
7 segment LED indicator: "-" display
(2) Setting method
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons to confi gure settings accord-
ing to the procedures below. (If no setting is made, the factory default setting will be displayed.)
MODE/EXIT
SELECT
ENTER
ENTER
POWER/MODE lamp: ON
: Press the “MODE/EXIT” button.
: Press the “SELECT” button.
: Press the “ENTER” button.
: Press the “ENTER” button for more than 3 seconds.
SELECT button
ERROR lamp: OFF
ENTER button
ERROR lamp: Blinking
1: FUNCTION Setting
First 2 digits
Every press of the “SELECT” button will change the setting number for the fi rst 2 digits.
Last 2 digits
MODE/EXIT
SELECT
ENTER
2: Setting the
rst 2 digits
SELECT
7 segment LED indicator (LED105, LED104)
(Flashing)
(When [F3] to [F9] are displayed, continue to press the “SELECT” button until [F2] is displayed.)
3: Setting the last 2 digits
Continue to press the “SELECT” button until the desired number appears at the
ENTER
MODE/EXIT
last 2 digits.
SELECT
SELECT
SELECT
SELECT
SELECT
ENTER
Setting is complete when the lamp lights up
Press “ENTER” button to return to “2. Setting the first 2 digits” (If there is no operation for 5 seconds after the setting, the indicator will return to “2: Setting the first 2 digits”.)
ENTER
MODE/EXIT
SELECT
MODE/EXIT
SELECT
(Continue to press the “SELECT” button until the desired number appears at the last 2 digits.)
ENTER
Setting is complete when the lamp lights up
Press “ENTER” button to return to “2. Setting the rst 2 digits” (If there is no operation for 5 seconds after the setting, the indicator will return to “2: Setting the fi rst 2 digits”.)
EXIT: Press the “MODE/EXIT” button to cancel the setting mode.
SELECT
En-18
Page 20
Signalamplifieraddresssetting7.5.
Signal amplifi er address setting7. 5. 1.
When using signal amplifi ers, the address for signal amplifi ers must be set. The address for signal amplifi ers can be set automatically from 1 outdoor unit (master unit) on the network. Refer to the next section “Fig. Wiring example for automatic address setting” for the wiring example. (For manual setting of address, refer to the signal amplifi er installation manual.)
Procedures to enable automatic address setting 7. 5. 2. on signal amplifi er
When setting the address of the signal amplifi er, please use the factory setting. (See the installation manual of the signal amplifi er)
When the system is normal, nothing will be displayed on the 7 segment indicator.
When ERROR is displayed, inspect the units. Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit PC board to confi gure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits
Last 2 digits
MODE/EXIT
(The indicator when the main power is turned on)
Wiring example for automatic address settingFig.
(1) Signal amplifi er wiring example (2)(3)(4) Indoor unit wiring example
(Connect the indoor and outdoor units of the same refrigerant system as shown below.)
Refrigerant system1
Master unit
Refrigerant system2
Master unit
Refrigerant system3
Master unit
NOTE)
The automatic address function can be used for a maximum of 48 indoor units • installed to the same refrigerant system. When network is connected to other refrigerant systems, the automatic address function cannot be used. The addresses of indoor units that have been confi gured automatically cannot be assigned in the order when they are installed. (Refer to the indoor unit installation manual for the procedures to check the addresses.)
2 12 8 21 4 1 26 3
314256 8171128
(1) Signal amplifi er
12 18 1 10 23 4 22 8 9
(1) Signal amplifi er
(2)
(3)
(4)
SELECT
SELECT
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
ENTER
Automatic address setting for signal amplifiers
SELECT
ENTER
ENTER
MODE/EXIT
End
Press the “SELECT” button until “10” is displayed.
Press the “ENTER” button for more than 3 seconds.
Setting is complete when the number of units is displayed
Indoor unit address setting7. 6.
Indoor unit address setting7. 6. 1.
Address must be set for the indoor unit. Manual setting • When setting with the switch inside the indoor unit, refer to
When setting with a remote controller, refer to the remote
Automatic setting • Check that the wiring is as shown in the fi gure below.
the indoor unit installation manual.
controller installation manual.
Operate using the master outdoor unit of each refrigerant system.
Procedures to enable automatic address setting 7. 6. 2. on indoor units
Check that the rotary switch IU AD on the indoor unit PC board is set to “00”.If it is not set to “00”, it means the address of that device is not set. (Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed on the 7 segment LED indi­cator.
When ERROR is displayed, inspect the units. Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit PC board to confi gure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits
Last 2 digits
MODE/EXIT
SELECT
SELECT
ENTER
Automatic address setting for indoor units
SELECT
ENTER
ENTER
(The indicator when the main power is turned on)
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
Press the SELECT button until “11” is displayed.
Press the “ENTER” button for more than 3 seconds.
The number of indoor units with normal set­tings will be displayed at the fi rst 2 digits of the 7 segment LED indicator. The number of indoor units with error will be displayed at the last 2 digits.
NOTE) After the “ENTER” button is pressed, the end processing will occur for about 30 seconds. During this period, the 7 segment will blink.
En-19
End
Page 21
7. 7.
Resistance measurement of transmission cable (Measure with breaker OFF)
CAUTION
Do not turn on the power if the resistance between the terminals of the transmis­sion cable is abnormal. Otherwise, the circuit board may be damaged.
Measure the resistance between 2 terminals of a transmission cable.
Transmission cable connecting indoor units, outdoor units, and signal (1) amplifi ers
Measure the resistance of the signal amplifi er terminal and the terminal of the indoor and outdoor units connected farthest away from the device where terminal resistor is measured. A value from the table is displayed, depending on the distance from the signal amplifi er and the device where the terminal resistor is set. This value is an estimate.
Transmission cable connecting outdoor units in a refrigerant system(2)
The resistance between the terminals of the transmission cable is 45-60Ω. This value is an estimate.
Fig. B
Val ve
Open
Close
Cap
ATable.
Valv e t ype Sp indle Ca p Chargin g cap
Liquid
Gas
9.0 to 12.0 N·m (90 to 120 kgf·cm)
27.0 to 33.0 N·m (270 to 330 kgf·cm)
Charging cap
Spindle
Open
Close
20.0 to 24.0 N·m (200 to 240 kgf·cm)
25.0 to 30.0 N·m (250 to 300 kgf·cm)
Hexagon wrench
12.5 to 16.0 N·m (125 to 160 kgf·cm)
12.5 to 16.0 N·m (125 to 160 kgf·cm)
Distance from termination resistor (m)
0 ~100 ~ 200 ~ 300 ~400 ~500
A short circuit somewhere or 2 or more termination
0 ~ 50
resistors are connected 50 60 70 80 90
100 110 120 130 140 150 160 170 180
190 ~ Faulty contact or wiring length over 500 m
Approximate resistance (Ω)
1K ~ Faulty contact, open circuit, or no termination resistor
PIPE INSTALLATION II8.
A Connection systemFig.
In case of connecting 1 outdoor unit A)
Outdoor unit
Pressure gauge
Pressure regulating valve
Nitrogen
Sealing test8. 1.
CAUTION
Use only nitrogen gas.• Never use refrigerant gas, oxygen, in fl ammable gas or poisonous gas to pressur- ize the system. (If oxygen is used. There is danger of an explosion.)
Do not shock during sealing test.• It can rupture the pipes and cause serious injury.
Do not turn on the power unless all operations are complete.
Do not block the walls and the ceiling until the sealing test and charging of the • refrigerant gas have been completed.
After connecting the pipes, perform a sealing test. Recheck that the spindle of the 3-way valve are closed before performing a sealing test. (Fig. B) Pour nitrogen gas through both the liquid pipe and the gas pipe. Pressurize nitrogen gas to 4.2 MPa to perform the sealing test.
Check all fl are connection areas and brazed areas. Then, check that the pressure has not decreased. Compare the pressures after pressurizing and letting it stand for 24 hours, and check that the pressure did not decreased.
When the outdoor temperature changes 5 °C, the test pressure changes 0.05 * MPa. If the pressure has dropped, the pipe joints may be leaking.
If a leakage is found, immediately repair it and perform a sealing test again.
* Decrease the pressure of nitrogen gas before brazing After completing the sealing test, release the nitrogen gas from both valves. Release the nitrogen gas slowly.
Vacuum process8. 2.
Indoor
Indoor
unit
In case of connecting multiple outdoor units B)
Outdoor unit Outdoor unit
unit
Indoor unit
Vac cum pump
Indoor unit
Scale
Pressure regulating valve
Pressure gauge
Vac cum
Scale
pump
Nitrogen
CAUTION
Do not turn on the power unless all operations are complete.
If the system is not evacuated properly, its performance will drop.
If moisture enter the piping, follow below. (i.e., if doing work during the rainy
season, if the actual work takes long enough that condensation may form on the
inside of the pipes, if rain might enter the pipes during work, etc.)
After operating the vacuum pump for 2 hours, pressurize to 0.05 MPa (i.e.,
vacuum breakdown) with nitrogen gas, then depressurize down to -100.7kPa
(-755mmHg) for an hour using the vacuum pump (vacuum process).
If the pressure does not reach -100.7kPa (-755mmHg) even after depressurizing
for at least 2 hours, repeat the vacuum breakdown - vacuum process.
After vacuum process, maintain the vacuum for an hour and make sure the pres­sure does not rise by monitoring with a vacuum gauge.
Evacuation procedure
Remove the caps of the gas pipe and liquid pipe and check that the valves are 1) closed. Remove the charging cap. 2) Connect a vacuum pump and a pressure gauge to a charging hose and connect 3) it to the charging port. Activate the vacuum pump and vacuum the indoor unit and connection piping 4) until the pressure gauge becomes -100.7kPa (-755mmHg). Evacuate from both the gas pipe and the liquid pipe. Continue evacuating the system for 1 hour after the pressure gauge reads 5)
-100.7kPa (-755mmHg). Remove the charging hose and reinstall the charging cap. 6)
En-20
Page 22
Additional charging8. 3.
CAUTION
Do not turn on the power unless all operations are complete.
After evacuating the system, add refrigerant.
Do not charge the system with a refrigerant other than R410A. Always keep to the limit on the total amount of refrigerant. Exceeding the limit on
the total amount of refrigerant will lead to malfunction during charging of refrigerant. Do not reuse recovered refrigerant. Use an electronic scale to measure the charging amount of refrigerant.
Adding more refrigerant than the specifi ed amount will cause a malfunction. Charge refrigerant using the liquid pipe.
Adding refrigerant through the gas pipe will cause a malfunction. Add refrigerant by charging the system with the refrigerant in the liquid state. If
the refrigerant cylinder is equipped with a siphon, it is not necessary to place the cylinder upright.
Procedure for charging the system with refrigerant8. 3. 1.
Remove the charging cap from the liquid pipe. Use standard refrigeration prac- 1) tices when charging refrigerant. Attach a charging hose to the refrigerant cylinder, and connect it to the charging 2) port. Add refrigerant by calculating the additional refrigerant volume in accordance with 3) the calculation formula indicated below. Remove the charging cap and install the charging hose. 4) Remove the body caps (gas pipe and liquid pipe), and open the valves. 5) Close the body caps. 6) After adding refrigerant, indicate the added charging volume on the unit. 7)
Tighten the body caps and charging caps to the torque values specifi ed in the * Tabl e A .
To open and close the valves, Use an M4 hexagon wrench for liquid pipe. Use an M10 hexagon wrench for gas pipe.
If you can not charge the specifi ed amount of refrigerant with the above
**
method, be sure to charge the refrigerant through the gas pipe while operat­ing in cooling mode. In order to prevent liquid back-fl ow, carefully operate the refrigerant cylinder valve so that the refrigerant will fl ow in certain part at a time.
Checking total amount of refrigerant and calculat-8. 3. 2. ing the amount of refrigerant charge to be added
The amount of refrigerant charge to be added is the total value of the basic refrig-• erant charge amount and the value calculated from the length of the liquid pipe. Round up the value to 2 dec• imal places.
Model HPdFactory charged amount
A72LALH
AJ
A90LALH
AJ
108LALH
AJ
126LALH
AJ
144LALH
AJ
Diameter of liquid pipe (mm)
Calculation of additional amount for outdoor unit(1)
Outdoor unit1 additional
A =
amount for outdoor unit
Outdoor unit3 additional amount for outdoor unit
Calculation of additional amount for pipe length(2)
8HP 11.20 0 10HP 11.20 0 12HP 11.80 1.20 14HP 11.80 3.30 16HP 11.80 3.30
Ø6.35 0.021
Ø9.52 0.058 Ø12.70 0.114 Ø15.88 0.178 Ø19.05 0.268
a
a
Outdoor unit2 additional
+
amount for outdoor unit
kg
Total
=
kg
(kg)
Additional amount for pipe length (kg/m)
a
+
kg
kg
a
Additional amount for
outdoor unit (kg)
b
Total length of
ø12.70 mm liquid
Total length of ø6.35 mm liquid pipe
Calculation of additional charge refrigerant(3)
C=A+B =
pipe
b × 0.114
m
× 0.021 (kg/
m
(kg/m)
b
m)
Total length of ø9.52 mm liquid pipe
+
kg
b × 0.058
m
Tot al
=
kg
(Round up C to 2 decimal place)
kg
(kg/m)
+
kg
kg
Calculation of factory charged amount(4)
d
Outdoor unit1
D =
factory charged amount
d
Outdoor unit3
factory charged amount
Total refrigerant amount check(5)
E=C+D=
Note : Check the total refrigerant amount under the following conditions
For 1 outdoor unit per refrigerant system : Total amount of refrigerant 31.5kg
For 2 outdoor units per refrigerant system : Total amount of refrigerant 63kg
For 3 outdoor units per refrigerant system : Total amount of refrigerant 94.5kg
+
kg
Total
=
kg
kg
Condition Computational formula
d
Outdoor unit2
factory charged amount
kg
+
kg
E 31.5kg
E 63kg
E 94.5kg
<Calculation>
When there are 3 outdoor units (AJ 144LALH, AJ 126LALH, AJ 108LALH) connected to 1 system
Calculation of additional amount for outdoor unit(1)
A = 3.30 (kg) + 3.30 (kg) + 1.20 (kg) = 7.80 (kg)
Calculation of additional amount for pipe length(2)
If liquid pipe piping length is the following
ø
19.05 : 50m, ø15.88 : 25m, ø12.70 : 0m, ø9.52 : 20m, ø6.53 : 15m
Additional charge volume B = 50 (m) × 0.268 (kg/m) + 25 (m) × 0.178 (kg/m)
= 19.325kg
Calculation of additional charge refrigerant(3)
C = A + B = 7.80 (kg) + 19.33 (kg) = 27.13 (kg)
Calculation of factory charged amount(4)
D = 11.8 (kg) + 11.8 (kg) + 11.8 (kg) = 35.4 (kg)
Check the total amount of refrigerant(5)
When 3 outdoor units are connected to 1 system, the following condition must be satisfi ed. Condition: E = C + D 94.5 (kg) Calculation: 27.13 (kg) + 35.4 (kg) = 62.53 (kg) < 94.5 (kg)
No problem if the above condition is satisfi ed.
+ 0 (m) × 0.114 (kg/m) + 20 (m) × 0.058 (kg/m) + 15 (m) × 0.021 (kg/m)
B =
Total length of ø19.05 mm liquid pipe
m
b × 0.268
(kg/m)
+
kg
Total length of
ø15.88 mm liquid
pipe
m
En-21
b × 0.178
(kg/m)
+
kg
Page 23
Installing insulation8. 4.
Install insulation material after conducting the “8.1 Sealing Test”.
To prevent condensation and water droplets, install insulation material on the refriger-
ant pipe.
Refer to the table to determine the thickness of the insulation material.
If the outdoor unit is installed at a level that is higher than the indoor unit, the water
that has condensed in the 3-way valve of the outdoor unit could travel to the indoor
unit.
Therefore, use putty in the space between the pipe and the insulation to prevent the
entry of water.
Perform test operation for each refrigerant system. You can set “cooling test run" or “heating test run” with the push button on the outdoor unit PC board.
Test operation setting method
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit PC board to confi gure settings according to the procedures below.
FUNCTION settings
First 2 digits
Last 2 digits
MODE/EXIT
Insulation
Putty
Selection of insulationTa ble .
(for using an insulation material with equal heat transmission rate or below
0.040W/(m·k))
Insulation material
Minimum thickness (mm)
Relative humidity 70% 75% 80% 85%
Pipe diameter (mm)
When an ambient temperature and relative humidity exceed 32 °C, please strength-* en heat insulation of refrigerant pipe.
6.35 8 10 13 17
9.52 9 11 14 18
12.70 10 12 15 19
15.88 10 12 16 20
19.0510131621
22.22 11 13 17 22
28.58 11 14 18 23
34.92 11 14 18 24
41.27 12 15 19 25
TEST RUN9.
SELECT
SELECT
(When [F4] to [F9] are displayed, continue to press the SELECT button until [F3] is displayed.)
ENTER
SELECT
ENTER
Press the “ENTER” button for more than 3 seconds.
This will be displayed when the cooling test operation is complete.
This will be displayed after 5 seconds.
ENTER
SELECT SELECT
or
For heating operation, press the “SELECT” button until “01” is displayed.
ENTER
Press the “ENTER” button for more than 3 seconds.
Settings for starting test run operation
This will be displayed when the heating test operation is complete.
This will be displayed after 5 seconds.
ENTER
or
Settings for stopping test run operation
Pre-test run check items9. 1.
Before the test operation, check the following items.
Is there a gas leakage? (At pipe connections {fl ange connections and brazed
areas}) Is the system charged with the specifi ed volume of refrigerant?
Is the refrigerant circuit address correct?
Is a breaker installed at the power supply cable of every outdoor unit?
Are the cables connected to the terminals without looseness, and in accordance with
the specifi cations? Are the initial settings of the switches of the outdoor unit correctly confi gured?
Is the 3-way valve of the outdoor unit open? (gas pipe and liquid pipe)
Is power supplied to the crank case heater for more than 12 hours? Electricity
current in short period of time may result in compressor damage. Are all the indoor units within the same coolant system connected to the power?
Operating indoor units which are not connected to the power may result in mal­functions.
After checking that the above items are all in order, refer to “9.2 Test
operation method” to test operation of the unit.
If there are problems, adjust immediately and recheck.
Test operation method9. 2.
Be sure to confi gure test run settings only when the outdoor unit has stopped operating.
Depending on the communication status between the indoor and outdoor units, • it may take several minutes for the system to start operating after settings for the test run are complete. After the test run settings are complete, all the outdoor units and the connected • indoor units will start operating. Room temperature control will not activate during test operation (continuous operation). If a knocking sound can be heard in the liquid compression of the compressor, • stop the unit immediately and then energize the crank case heater for a suffi cient length of time (more than 12 hours) before restarting the operation.
ENTER ENTER
Press the “ENTER” button for more than 3 seconds.
This will be dis­played when the cooling operation mode is canceled.
This will be displayed after 5 seconds.
ENTER
MODE/EXIT
EXIT
After the test operation is complete, turn off the power. Attach the cover of the electrical compartment box and the front panel of the outdoor unit.
Note
Check that the indoor and outdoor units connected to the same refrigerant system • are operating normally. When indoor or outdoor units are not operating, or when the indoor and outdoor • units of other refrigerant systems are operating, the indoor/outdoor unit address or DIP switch for the number of connected slave units are not confi gured correctly. The system will not operate normally with an incorrect DIP switch setting.• Stop the system immediately and recheck the DIP switch setting.
or
Press the “ENTER” button for more than 3 seconds.
This will be dis­played when the heating operation mode is canceled.
This will be displayed after 5 seconds.
En-22
Page 24
Checklist9. 3.
Check description Check method Criteria
High and low pressure
1
values are normal.
Drain water is dis-
2
charged smoothly through the drain hose.
Indoor and outdoor unit
3
fans are operating. Compressor operates after
4
the indoor unit operates. Difference between inlet
5
and outlet temperatures is normal.
6 Error is not displayed
Check it with a pressure gauge.
Check it by pour­ing water.
Check them visu­ally.
Check the operat­ing sound.
Measure the inlet and outlet temper­atures.
Check the 7 segment LED indicator
Cooling: low pressure ap­prox. 0.8 MPa Heating: high pressure ap­prox. 3.0 MPa
Temperature difference 10 degrees
Error blinking or no error code display
LED Status10.
You can determine the operating status by the lighting up and blinking of the 7 seg­ment LED indicator. Check the status using the table below.
Normal operation mode10. 1.
Mode Code Description
Operation
CL Cooling Ht Heating
o r During oil recovery operation d F During defrosting operation P C During peak cut operation L n During low noise operation S n During setting of snowfall mode
E 9 2. 1 Outdoor unit compressor 2 error E 9 2. 2 Outdoor unit compressor 2 current value error E 9 3. 1 Outdoor unit inverter compressor start up error
Outdoor unit actuator error
Refrigerant system error
E 9 4. 1 Outdoor unit trip detection E95.5 E 9 7. 1 Outdoor unit fan motor 1 lock error E 9 7. 4 Outdoor unit fan motor 1 undervoltage error
E97.5
E 9 U. 2 Outdoor slave unit error
EA1.1
EA2.1
EA3.1Outdoor unit compressor 1 temperature error E A 3. 2 Outdoor unit compressor 2 temperature error E A 4. 1 Outdoor unit high pressure error E A 4. 2 Outdoor unit high pressure protective action 1 E A 4. 3 Outdoor unit high pressure protective action 2 E A 5. 1 Outdoor unit low pressure error E A C. 4 Outdoor unit heat sink temperature error
7 segment LED indicator:
㪘㪑
㪚㪑
㪃㪃
㪡㪑
㪃㪃㪃㪃
㫉㪑
㪃㪃㪃㪃㪃
㪍㪑
㪎㪑
Outdoor unit compressor motor loss of synchronization
Outdoor unit fan motor 1 temperature error (protective action)
Outdoor unit discharge temperature 1 error (perma­nent stop) Outdoor unit discharge temperature 2 error (perma­nent stop)
㪻㪑
㪣㪑㪟 㪪㪑
㪜㪑
㫅㪑
㫋㪑
㪊㪑㪈㪑 㪉㪑
㪋㪑
㪐㪑㪏㪑
㪝㪑
㪃㪃
㪃㪃
㪬㪑
㪌㪑
㪇㪑
Error codes10. 2.
Mode Code Description
Communication error
Function setting error
Indoor unit actuator error E 5 U. 1 Indoor unit miscellaneous error
Outdoor unit PCB/Elec­trical component/ Switch error
Outdoor unit sensor error
E 1 3. 1 Communication error between outdoor units E 1 4. 1 Outdoor unit network communication 1 error E 1 4. 2 Outdoor unit network communication 2 error E 1 4. 5 The number of indoor unit shortage E 2 8. 1 Auto address setting error E 2 8. 4 Signal amplifi er auto address error
E61.5Outdoor unit reverse/missing phase & wiring error E62.3Outdoor unit EEPROM access error E 6 2. 6 Outdoor unit inverters communication error E 6 2. 8 Outdoor unit EEPROM data corruption error E 6 3. 1 Outdoor unit inverter error
E67.2
E 6 8. 1 Outdoor unit magnetic relay error
E68.2
E69.1
E 7 1. 1 Outdoor unit discharge temp. thermistor 1 error E 7 1. 2 Outdoor unit discharge temp. thermistor 2 error E 7 2. 1 Outdoor unit compressor temp. thermistor 1 error E 7 2. 2 Outdoor unit compressor temp. thermistor 2 error E 7 3. 3 Outdoor unit heat ex. liquid temp. thermistor error E 7 4. 1 Outside air temp. thermistor error E 7 5. 1 Outdoor unit suction gas temp. thermistor error E 7 7. 1 Outdoor unit heat sink temp. thermistor error
E82.1
E82.2
E 8 3. 1 Outdoor unit liquid pipe temp. thermistor 1 error E 8 3. 2 Outdoor unit liquid pipe temp. thermistor 2 error E 8 4. 1 Outdoor unit current sensor 1 error (permanent stop) E 8 6. 1 Outdoor unit discharge pressure sensor error E 8 6. 3 Outdoor unit suction pressure sensor error E 8 6. 4 Outdoor unit high pressure switch 1 error E 8 6. 5 Outdoor unit high pressure switch 2 error
Outdoor unit inverter PCB power short interruption error
Outdoor unit rush current limiting resister temp. rise error (protective operation) Outdoor unit transmission PCB parallel communication error
Outdoor unit sub-cool heat ex. gas inlet temp. therm­istor error Outdoor unit sub-cool heat ex. gas outlet temp. thermistor error
En-23
Page 25
INFORMATION11.
Main contents of label
Item Detail
Model name 1. Model name
Serial number 2. Serial number
Electric characteristics 3. Phase, rated voltage, and frequency
Weight 4. Product weight
Capacity 5.
Current 6.
Input power 7.
Max. Current 8.
Air circulation 9. Air circulation
Noise level10. Noise level
Refrigerant11.
Max. pressure (HP/LP)12.
Protection13. Protection level against dust and water
Working temperature14. Working temperature
Condition of cooling/heating15.
Condition of max. cooling16.
Manufacture year17. Manufacture year
Origin18. Origin country
Manufacturer19.
Cooling/heating capacity under cooling/ heating condition (refer to item 15)
Electric current during cooling/heating operation under cooling/heating condi­tion (refer to item 15)
Input during cooling/heating operation under cooling/heating condition (refer to item 15)
Maximum electric current (temperature condition is max. cooling condition [refer to item 16])
Refrigerant type and initial charging amount
Means pressure of High Pressure side/ Low Pressure side
Dry-bulb temperature and wet-bulb temperature under standard cooling/ heating condition
Dry-bulb temperature and wet-bulb temperature at maximum electric cur­rent and input
Manufacturer FUJITSU GENERAL LIMITED Address : 1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan
Label
En-24
Loading...