Fuji Electric PXR3 Operating Manual

SV C1 C2 AL1 AL2
Micro-contr oller X
SEL
Model: PXR3
Operation Manual
TN5A2704-E

Table of Contents

1 Part Names and Functions .................................................................................................... 5
2 Operations ............................................................................................................................. 6
2-1 Parameter list............................................................................................................ 6
2-2 Basic operations ....................................................................................................... 11
2-3 Parameter functions and method of settings ............................................................ 12
First block parameters ............................................................................................... 13
Standby setting .......................................................................................................... 13
Ramp-soak control..................................................................................................... 14
Canceling the alarm latch .......................................................................................... 15
Auto-tuning function................................................................................................... 16
Displaying ON-delay alarm or the remaining time of timers ...................................... 17
Setting alarm 1 and 2 ................................................................................................ 18
Upper limit of alarm 1 and 2 ...................................................................................... 18
Lower limit of alarm 1 and 2....................................................................................... 18
Key lock ..................................................................................................................... 19
Second block parameters .......................................................................................... 20
Proportional band ...................................................................................................... 20
Integral time ............................................................................................................... 21
Derivative time ........................................................................................................... 22
Hysteresis range for ON/OFF control ........................................................................ 23
Cooling-side proportional band coefficient ................................................................ 24
Cooling-side proportional band shift (Dead band/Overlap band) .............................. 25
Output offset value..................................................................................................... 26
Anti-reset windup ....................................................................................................... 26
Control algorithm ....................................................................................................... 27
PV (Measured value) stable range ............................................................................ 31
HYS (Hysteresis) mode at ON/OFF control............................................................... 32
Cycle time of control output 1 .................................................................................... 33
Cycle time of control output 2 (cooling-side).............................................................. 34
Input signal code........................................................................................................ 35
Setting lower limit of the measuring range................................................................. 36
Setting upper limit of the measuring range ................................................................ 36
Decimal point position................................................................................................ 38
PV offset .................................................................................................................... 39
SV offset .................................................................................................................... 40
Time constant of input filter........................................................................................ 41
Alarm types................................................................................................................ 42
Selecting ramp-soak patterns .................................................................................... 45
Ramp-soak status display.......................................................................................... 46
1st to 8th target SV.................................................................................................... 46
1st to 8th ramp segment time .................................................................................... 46
1st to 8th soak segment time..................................................................................... 46
Ramp-soak modes..................................................................................................... 46
Third block parameters .............................................................................................. 49
Specifying control system and action, and output direction at input burn-out............ 49
SV (Setting value) lower limiter.................................................................................. 50
SV (Setting value) upper limiter ................................................................................. 50
The time of ON-delay alarm or timer function............................................................ 51
Hysteresis alarm 1 and 2 ........................................................................................... 53
Options of alarm 1 and 2 ........................................................................................... 54
Upper and lower limits for control output 1 ................................................................ 56
Upper and lower limits for control output 2 ................................................................ 56
Output limit types ....................................................................................................... 57
Output value display .................................................................................................. 58
RCJ (Cold junction compensation) ............................................................................ 59
Adjusting the PV (Measured value) display (0%)....................................................... 60
Adjusting the PV (Measured value) display (100%)................................................... 60
DI operation ............................................................................................................... 61
Station No. for communication ................................................................................... 64
Parity for communication ........................................................................................... 65
Input type for PYP...................................................................................................... 66
Retransmisson output type setting ............................................................................ 67
Retransmisson base scale......................................................................................... 68
Retransmisson span scale......................................................................................... 68
Parameter display mask ............................................................................................ 69
3 T roub leshooting...................................................................................................................... 70
Index ......................................................................................................................................... 72
digit
<Size of front H x W>
4
24 × 48 mm
<Input signal>
5
Thermocouple °C
Specification Note
Thermocouple °F RTD Pt100 3-wire type °C RTD Pt100 3-wire type °F 1 to 5V DC 4 to 20mA DC
<Control output 1>
6
Relay contact output SSR/SSC driving output 4 to 20mA DC output
<Control output 2>
7
None Relay contact output SSR/SSC driving output 4 to 20mA DC output
<Revision code>
8
<Optional specifications 1>
9
None Alarm 1 point 8 ramps/soaks Alarm 1 point + 8 ramps/soaks Alarm 2 point Alarm 2 point + 8 ramps/soaks
<Instruction Manual>
10
None 100 to 240V AC
<Power supply voltage>
Japanese 100 to 240V AC English 100 to 240V AC None 24V AC/24V DC Japanese 24V AC/24V DC English 24V AC/24V DC
<Optional specifications 2>
11
None
12
RS-485 Modbus interface
13
RS-485 Z-ASCLL interface Retransmission + Digital input 1 point Retransmission Digital input 2 points RS-485 Modbus interface + Digital input 1 point RS-485 Z-ASCLL interface + Digital input 1 point
<Non-standard specification>
14
Non-standard parameter setting
PXR
Note 1 Note 1 Note 1
Note 2 Note 2
Note 3 Note 3
45678 9
3
T R N S A B
A C E
Y A C E
1 2
10 11 12 13 14
0 1 4 5 F
G
N Y V C A B
0
0
M
0
N
0
Q
0
R
0
T
0
V
0
W
0
Model Specifications
Note 1
Process alarm (2 points) (the codes “ F and G ” in the 9th digit) cannot be specified.
Note 2
Control output 2 (the codes “ A, C, and E ” in the 7th digit) cannot be specified.
Note 3
Control output 2, communication digital input (2 points), alarm (2 points), and 24V power supply (the codes “ A, C and E ” in the 7th digit, “ F and G ” in the 9th digit, and “ A, B, and C ” in the 10th digit) cannot be specified.
The default settings of input signals, measured ranges, and setting values are shown below.
Thermocouple specified : Thermocouple K, Measured range: 0 to 400°C,
Resistance bulb specified : Pt, Measured range: 0 to 150°C, Setting value:
Voltage, Current specified : Scaling: 0 to 100%, Setting value: 0%
0 0 0 0 0 0 0 0
In any case other than the description above, specify input signals and measured range.
The input signals for the thermocouple and the resistance bulb can be switched with the front panel keys.
The default settings of control action is reverse for control output 1 and direct for control output 2. The reverse and direct actions can be switched with keys on the face panel.
F
Setting value: 0°C
0°C
1
This chapter explains the part names and functions on the face panel. The face panel has the PV and SV displays, the status indicating lamp, and the setting keys, etc. Those functions are explained below. Please read and understand them before using the PXR. For details about the setting of parameters, see Chapter 2.

Part Names and Functions

Lampforcontroloutput1①
Lampforcontroloutput2②
Lampforalarmoutput1③
Lampforalarmoutput2④
SV C1 C2 AL1 AL2
⑥  key
Type:PXR3
q Lamp for control output 1
Lights up while control output 1 stays ON.
w Lamp for control output 2
Lights up while control output 2 stays ON.
e Lamp for alarm output 1 (option)
Lights up when alarm output 1 is actuated. Flickers un­der ON-delay operation.
SEL
SEL
⑤Display⑨SVlamp
⑦   key
y
SEL
Used to switch the PV display to/from the SV display and select a parameter block and a parameter, and regis­ter a set value.
u keys
Used to change the SV, call parameters, and change pa­rameter values.
⑧Auto-tuning/self-tuninglamp
key
r Lamp for alarm output 2 (option)
Lights up when alarm output 2 is actuated. Flickers un­der ON-delay operation.
t Display
Displays the PV (process value) or SV (set value). When setting a parameter, its name or its value appears.
i Auto-tuning/self-tuning lamp
Flickers under an auto-tuning or self-tuning operation.
o SV lamp
Displays the PV (process value) in normal condition (while the lamp stays out). Press the up the SV lamp and display the SV (set value). Note that the lamp stays out while parameters and data are dis­played. Flickers while the display shows the PV (process value) in standby state.
SEL
key to light
2

Operations

This chapter explains how to set the SV (Setting value) and the parameters for the PXR.

2-1 Parameter list

Parameters for the PXR are classified under three blocks according to the frequency of use. The parameters of the second and third blocks are used at initialization or when they are of absolute necessity. Some parameters may not be displayed at the time of delivery depending on the type of the instrument.
Parameters of the first block
Parameter
display symbol
Parameter name
AT
AL1
AL2
Standby setting
Ramp-soak control
Alarm latch cancel
Auto-tuning
Timer 1 display Timer 2 display Set value of
alarm 1
Lower limit value of alarm 1
Upper limit value of alarm 1
Set value of alarm 2
Lower limit value of alarm 2
Upper limit value of alarm 2
Key lock
Stby
ProG
LACH
TM-1 TM-2
A1-L
A1-H
A2-L
A2-H
LoC
Description
Switches between RUN and Standby for control.
Switches between Start, Stop, and Hold for ramp-soak control
Cancels the alarm latch.
Used for setting the constants for , , and by auto-tuning.
Displays the remaining time of timer 1. Displays the remaining time of timer 2.
Sets the value at which alarm 1 is detected.
Sets the lower limit value at which alarm 1 is detected.
Sets the upper limit value at which alarm 1 is detected.
Sets the value during which alarm 2 is detected.
Sets the lower limit value at which alarm 2 is detected.
Sets the upper limit value at which alarm 2 is detected.
Specifies whether or not to allow the change of parameters.
is displayed when alarm type 1 is 0 to 15, or 32 to 34, and or is displayed when alarm type 1 is 16 to 31.
is displayed when alarm type 2 is 0 to 15 or 32 to 34, and or is displayed when alarm type 2 is 16 to 31.
Setting range and
factory default setting (*)
oN: Control standby
(Output: OFF, Alarm: OFF)
oFF: Control RUN* oFF: Stop*
rUn: Start HLd: Hold
0: Keeps the alarm latch.* 1: Opens up the alarm latch.
0: OFF (Resets the auto-tuning or does
not use it.)*
1: ON (Performs the auto-tuning in the
SV standard type.)
2: ON (Performs the auto-tuning in
low PV type (SV value-10%FS).)
- (Unit: seconds)
- (Unit: seconds)
When the alarm type is absolute value: 0 to 100%FS (*:10)
When the alarm type is deviation:
-100 to 100%FS (*:10)
When the alarm type is absolute value: 0 to 100%FS (*:10)
When the alarm type is deviation:
-100 to 100%FS (*:10)
0: All settings are changeable both from
the face panel and via communication.*
1: All settings are unchangeable from the
face panel, but changeable via communication.
2: Only the SV is changeable from the
face panel, and all settings are changeable via communication.
3: All settings are changeable from the
face panel, but unchangeable via communication.
4:
All settings are unchangeable from the face
panel or
via
5:
Only the SV is changeable from the face
panel, but all settings are unchangeable
via
communication.
communication.
User’s
set value
Parameter mask DSP
dSP1-1
dSP1-2
dSP1-4
dSP1-8
dSP1-16 dSP1-32
dSP1-128
dSP2-1
dSP2-2
dSP2-4
dSP2-8
dSP2-16
dSP3-1
Reference
page
13
14
15
16
17 17
18 18 18 18 18 18
19
*
*
*
*
*
*
Note: The parameters for which * is marked with the page number in Reference page are related to Remedies
of “4” on page 70.
Parameters of the second block
Parameter display symbol
User’s
set value
Reference
page
Description
Sets the types of alarm operations. Sets the types of alarm operations.
Selects ramp-soak patterns.
Sets the 1st target SV of ramp-soak operation. / Selected at switching­SV function for DI1
Sets the first ramp segment time.
Setting range and factory
default setting (*)
0.0 to 999.9% (*: 5.0)
0 to 3200 seconds (*: 240)
0.0 to 999.9 seconds (*: 60.0) 0 to 50%FS (*: equivalent of 1.0°C)
0.0 to 100.0 (*: 1.0)
-50.0 to +50.0 (*: 0.0)
-100 to 100% (*: single 0.0, dual 50.0)
0 to 100%FS (*: 100%FS)
PID: Runs normal PID control.* FUZY: Runs PID control with fuzzy logic. SELF: Runs PID control with self-running.
0 to 100%FS (*: 2%FS)
oFF: Starts the two-position control at the
values of SV+HYS/2 and SV-HYS/2.
on:
Starts the two-position control at the values of SV and SV+HYS, or SV and SV-HYS.
*
RLY, SSR: 1 to 150 seconds
(*: Contact output = 30, SSR/SSC-driven output = 2)
RLY, SSR: 1 to 150 seconds (*: Contact output = 30, SSR/SSC-driven output = 2)
1 to 16 (*: specified by customer while ordering)
Note 1
-1999 to 9999 (*: specified by customer while ordering)
Note 1
-1999 to 9999 (*: specified by customer while ordering)
Note 1
0 to 2 (*: specified by customer while ordering)
Note 1
°C / °F
-10 to 10%FS (*: 0)
-50 to 50%FS (*: 0)
0.0 to 900.0 seconds (*: 5.0)
0 to 34 (*: 0/5) 0 to 34 (*: 0/9)
- (*: OFF)
1: Performs 1st to 4th segments.* 2: Performs 5th to 8th segments. 3: Performs 1st to 8th segments.
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
Parameter
mask DSP
dSP3-2
dSP3-4 dSP3-8 dSP3-16
dSP3-32
dSP3-64
dSP3-128
dSP4-1
dSP4-2
dSP4-4
dSP4-8
dSP4-16
dSP4-32
dSP4-64
dSP4-128
dSP5-1
dSP5-2
dSP5-4
dSP5-8
dSP5-16 dSP5-32
dSP5-64 dSP5-128 dSP6-2
dSP6-4
dSP6-8
dSP6-16
Selects the control algorithm.
Sets the PV stable range for the self­tuning operation.
Selects the hysteresis operation at ON/OFF control.
Not shown at 4-20mA DC output
Set this parameter when changing the types of temperature sensors.
Set to 0.0 to select the ON/OFF control (Two-position control).
20 21
22 23
24
25 26
26
27
31
32
33
34
35
36 36 38
36
39 40
41 42
42 46
45
46
46
Sets the hysteresis for ON/OFF control.
*
*
*
*
*
*
P
I
D
HYS
CooL
db
bAL
Ar
CTrL
SLFb
onoF
TC
TC2
P-n2
P-SL
P-SU
P-dP
P-dF
PTn
Sv-1
TM1r
Parameter name
ALM1
ALM2
STAT
P-F
PVOF
SVOF
Proportional band
Integral time Derivative time
Hysteresis range for ON/OFF control
Cooling-side proportional band coefficient
Cooling-side proportional band shift
Output convergence value
Anti-reset windup
Control algorithm
PV (Measured value) stable range
Setting HYS (Hysteresis) mode
Cycle time of control output 1
Cycle time of control output 2 (cooling-side)
Input signal code
Lower limit of measuring range
Upper limit of measuring range
Setting the deci­mal point position
Time constant of input filter
Selecting ramp-soak execute type
1st target value
/Switching-SV value
First ramp segment time
Alarm type 1 Alarm type 2 Status display
of ramp-soak
°C / °F selection
PV (Measured value) offset
SV (Setting value) offset
Shift the display of the PV. Shift the SV. But the SV display
is not changed.
Note: The pa rameters for which * is marked with the page number in
Reference page are related to Remedies of “4” on page 70.
Parameter display symbol
Parameter name Description
TM1S
Sv-2
TM2r
TM2S
Sv-3
TM3r
TM3S
Sv-4
TM4r
TM4S
Sv-5
TM5r
TM5S
Sv-6
TM6r
TM6S
Sv-7
TM7r
TM7S
Sv-8
TM8r
TM8S
Mod
1st soak segment time
2nd target SV
2nd ramp segment time
2nd soak segment time
3rd target SV
3rd ramp segment time
3rd soak segment time
4th target SV
4th ramp segment time
4th soak segment time
5th target SV
5th ramp segment time
5th soak segment time
6th target SV
6th ramp segment time
6th soak segment time
7th target SV
7th ramp segment time
7th soak segment time
8th target SV
8th ramp segment time
8th soak segment time
Ramp-soak mode
Sets the 1st soak segment time.
Sets the 2nd target SV of ramp-soak operation.
Sets the 2nd ramp segment time.
Sets the 2nd soak segment time.
Sets the 3rd target SV of ramp-soak operation.
Sets the 3rd ramp segment time.
Sets the 3rd soak segment time.
Sets the 4th target SV of ramp-soak operation.
Sets the 4th ramp segment time.
Sets the 4th soak segment time.
Sets the 5th target SV of ramp-soak operation.
Sets the 5th ramp segment time.
Sets the 5th soak segment time.
Sets the 6th target SV of ramp-soak operation.
Sets the 6th ramp segment time.
Sets the 6th soak segment time.
Sets the 7th target SV of ramp-soak operation.
Sets the 7th ramp segment time.
Sets the 7th soak segment time.
Sets the 8th target SV of ramp-soak operation.
Sets the 8th ramp segment time.
Sets the 8th soak segment time.
Selects the power-on start, repeat, and standby functions for ramp­soak operations.
Setting range and factory
default setting (*)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
0 to 15 (*: 0)
User’s
set value
Parameter
mask DSP
dSP6-32
dSP6-64
dSP6-128
dSP7-1
dSP7-2
dSP7-4
dSP7-8
dSP7-16
dSP7-32
dSP7-64
dSP7-128
dSP8-1
dSP8-2
dSP8-4
dSP8-8
dSP8-16
dSP8-32
dSP8-64
dSP8-128
dSP9-1
dSP9-2
dSP9-4
dSP9-8
Reference
page
46
*
46 46 46
*
46 46 46
*
46 46 46
*
46 46 46
*
46 46 46
*
46 46 46
*
46 46 46
46
Note 1:When a customer does not specify the settings while ordering, the follo wing settings are selected as f actory defaults.
Thermocouple input: Thermocouple K Measured range: 0 to 400°C Resistance bulb input: Measured range: 0 to 150°C Voltage/Current input: Scaling: 0 to 100%
Parameters of the third block
Parameter display symbol
Parameter name Description
P-n1
Sv-L
Sv-H
dLY1
dLY2
A1hy
A2hy
A1oP
A2oP
PLC1
PHC1
PLC2
PHC2
PCUT
oUT1
oUT2
GAin
AdJ0
AdJS
STno
CoM
PYP
Ao-T
Control action
SV (Setting value) lower limiter
SV (Setting value) upper limiter
Delay time 1 Delay time 2
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 1 options
Alarm 2 options
Lower limit for output 1 Upper limit for output 1 Lower limit for output 2 Upper limit for output 2
Output limit types
Output value (MV) display
Output value (MV) display
RCJ (Cold junction compensation)
rCJ
setting
PV gradient User-definable zero
adjustment User-definable span
adjustment DI1 (Digital input 1)
di-1
operation DI2 (Digital input 2)
di-2
operation Station No.
Parity setting
Input type for PYP (Color Touch­Operation Unit)
Retransmission output type
Note: The parameters for which * is marked with the page number in
Specifies control action and output at the input burn-out.
Sets the lower limit of the SV.
Sets the upper limit of the SV.
Delay time or timer value for alarm 1 relay. Delay time or timer value for alarm 2 relay.
Sets the hysteresis range of ON and OFF of alarm 1.
Sets the hysteresis range of ON and OFF of alarm 2.
Sets the optional functions of alarms 1 and 2.
Alarm latch (1: use, 0: not use)
Alarm of error status (1: use, 0: not use)
De-energized output (1: use, 0: not use)
Sets the lower limit for output 1. Sets the upper limit for output 1. Sets the lower limit for output 2. Sets the upper limit for output 2.
Sets the limit types of outputs 1 and 2 (breaking the limit, or maintained within the limit).
Displays the value of output 1.
Displays the value of output 2.
Sets the cold junction compensation function to ON/OFF.
Shifts the zero point of input value.
Shifts the span of input value.
Sets the DI1 operations.
Sets the DI2 operations.
Sets the station No. for communication.
Sets the parity for communication. (The baud rate is fixed at 9600bps.
Sets the input type for communicating with PYP.
Selecting retransmission output type.
0 to 19 (*: specified by customer while ordering)
0 to 100%FS (*: 0%FS)
0 to 100%FS (*: 100%FS)
0 to 9999 seconds (*: 0) 0 to 9999 seconds (*: 0)
0 to 50%FS (*: 1)
0 to 50%FS (*: 1)
000 to 111 (*: 000)
000 to 111 (*: 000)
-3.0 to 103.0% (*: -3.0)
-3.0 to 103.0% (*: 103.0)
-3.0 to 103.0% (*: -3.0)
-3.0 to 103.0% (*: 103.0)
0 to 15 (*: 0)
-
-
ON: Performs the RCJ compensation).* OFF: Does not perform the RCJ (Cold junction compensation).
0.001 to 2.000 (*: 1.000)
-50 to 50%FS (*: 0)
-50 to 50%FS (*: 0)
0 to 12 (*: 0=OFF)
0 to 12 (*: 0=OFF)
0 to 255 (Setting to does not start the communications function.) (*: 1)
0: Odd parity* 1: Even parity 2: No parity
0 to 255 (*: 34)
0: PV/ 1: Set point/ 2: Output/ 3: Error (* : 0)
Reference page are related to Remedies of “4” on page 70.
Setting range and factory
default setting (*)
Note 2
(Cold junction
User’s
set value
Parameter mask DSP
dSP9-16
dSP9-32
dSP9-64
dSP9-128 dSP10-1
dSP10-16
dSP10-32
dSP10-128
dSP11-1
dSP11-4 dSP11-8
dSP11-16 dSP11-32
dSP11-64
dSP11-128
dSP12-1
dSP12-2
dSP12-4 dSP12-8
dSP12-16
dSP12-32
dSP12-64
dSP12-128
dSP13-1
dSP13-2
dSP13-4
Reference
page
49 50 50
51 51
53 53 54
54 56
56 56 56
57
58 58
59
60
60 61 61
64
65
66
67
*
*
*
*
*
*
Ao-L
Ao-H
Retransmission base scale
Retransmission span scale
Setting retransmission base scale.
Setting retransmission span scale.
(Setting range: -100.0 to 100.0%) (* : 0.0%)
(Setting range: -100.0 to 100.0%) (* : 100.0%)
Note 2:The following settings are selected as factory defaults depending on the model you order.
Seventh digit = Y model: 0 Seventh digit = A, C, E model: 4
dSP13-8
dSP13-16
68
68
Parameter display symbol
Parameter name Description
Setting range and factory
default setting (*)
User’s
set value
Parameter
mask DSP
Reference
page
to
to
to
dSP9
dSP10
to
Parameter mask
Sets whether or not to display each parameter.
0 to 255 (*: specified by customer while ordering)
69
dSP13
dSP1
10

2-2 Basic operations

Just after power-on:
The PV (process value) is displayed just after power-on.
SV C1 C2 AL1 AL2
SEL
How to switch parameters:
The figure below shows the basic operations for the PXR3.
Exp.) In case when the PV (process value)
Basic operations for the PXR3
is 149.9.
SV C1 C2 AL1 AL2
SEL
Indication switching PV (process value) to / from SV (set value)
OFF
SV lamp
……indicatingPV
Lit, flickers
……indicatingSV
Press the key to
SEL
switch PV to / from SV.
How to set values:
key: One press increases the value by 1.
Press and hold this key to increase the value.
key: One press decreases the value by 1.
Display state just after power-on
(PV indication)(SV indication)
Parameter setting
Flickers when the set value is changed by pressing the
SEL
SV C1 C2 AL1 AL2
SEL
or key. Stop flickering when the SV is registered by pressing the key.
SEL
Set data indication
SEL
(apporox. 1 second)
SEL
(apporox. 3 second)
SEL
(apporox. 5 second)
SEL
SEL
Set data registration
Parameters of the first block
Parameters of the second block
Parameters of the third block
Pressing and holding the keys makes the value increase or decrease fast.
If it has not been operated for 30 seconds, the display returns to the PV display. Pressing the key for 2 second after setting parameters, the indication
SEL
shifts to the SV indication state.
Press and hold this key to decrease the value.
How to register the set data:
By pressing the Note that the SV (SV0) will be registered in 3 seconds without any operation. (Refer to P.12) When changed the parameters “P-n2”, “ALM1” or “ALM2”, turn the power OFF and ON.
key, the displayed values are registered.
SEL
11

2-3 Parameter functions and method of settings

Method of setting the SV (Setting value) [Description]
•The SV is a target value for control.
•Any SV that is outside of the range set in the parameters of (lower limit) and (upper limit) of the third block cannot be set. (See page 50.)
[Setting example] Changing the SV from 250.0°C to 348.7°C
Display Operating procedure
Related parameters: (page 50)
(page 50)
PV indication SV indication
Press the key to display the SV. (SV lamp is lit.)
1.
Press the or keys to display .
2.
will be registered in the SV (front SV) in three seconds. After that, the controller will
3.
operate with the SV being .
SEL
12
q First block parameters
Standby setting (Settings: oFF/on)
[Description]
•This parameter switches the control between RUN and Standby.
• During standby, the control output and the alarm output stay OFF, like the standby for ramp-soak operation. Retransmission output is kept operated. (However, if the type of retransmission output is set to the MV, it becomes 4mA or lower.)
• While the alarm with a hold is selected, the hold function takes effect after changing the Standby setting from ON to OFF.
is displayed during the standby for ramp-soak operations or the controller changes to the standby state in case of the occurrence of errors.
• The other operations are the same as those of the ramp­soak standby.
•The setting of ON/OFF for standby is saved after po wer ­off.
•When the standby is set to ON during the auto-tuning, self-tuning, and ramp-soak operations, those operations will stop. (The PID constant will not be renewed.) Even through it is set to OFF later, the auto-tuning, self-tuning, and ramp-soak operations will not be re-started.
• During standby, the ON-delay timer is reset. When returning to RUN from the standby state, the timer will start from the beginning.
•The SV lamp flickers only when standby state.
[Setting example] Starting the control
Display Operating procedure
PV indication
SV indication
PV indication
Press and hold the key for one second.
1.
will be displayed.
Press the key once.
2.
The current setting ( ) will be displayed.
Press the or keys to flicker and to display .
3.
Press the key once. The standby state for control is selected. (control output and all the alarm
4.
outputs: OFF) (Repeat the procedure from 2 to 4 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds. The value
5.
on the SV display will flash, indicating the standby status.
If unoperated state continues, the PV will be displayed.
SEL
SEL
SEL
SEL
13
Ramp-soak control (Settings: oFF/rUn/hLd) (Option)
[Description]
• This function automatically changes the SV (Setting value) according to the program pattern set in advance as shown in the right line graph. Up to eight pairs of ramp­soak operation can be programmed.
•The first ramp starts at the PV (Measured value) that is the one just before running the program.
•The program can also automatically run at power-on (Power-on starting function). Refer to the parameter of
(page 46).
Related parameters:
(page 46) to (page 46)
to (page 46)
to (page 46) (page 46) (page 45)
Up to SV-8
SV-3 SV-2 SV-1
SV-4
PV
First ramp
TM1r
Ramp: the section in which the SV changes toward the target value. Soak: the section in which the SV is the target value, and remains unchanged.
First soak
TM1S
Second soak
Second ramp
TM2S
TM2r
Third soak
Third ramp
Fourth ramp
TM3S
TM3r TM4r
Fourth soak
TM4S
Up to TM8r
Up to TM8s
[Setting example] Starting the ramp-soak operation
Display Operating procedure
PV indication
SV indication
PV indication
Press and hold the key for one second.
1.
will be displayed.
Press the key to display .
2.
Press the key once.
3.
SEL
The current setting ( ) is displayed.
Pressing the or keys, the display flickers and is displayed.
4.
Press the key once. Then, the program will start according to the ramp-soak pattern that is
5.
SEL
set in advance.
(Repeat the procedure from 3 to 5 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds.
6.
The SV is displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
*1
SEL
14
*1) When the program was not set, it is turned to .
Canceling the alarm latch (Setting range: 0/1) (Option)
[Description]
•This parameter cancels the alarm latch when it is latching.
Related parameters:
[Setting example] Opening up the alarm latch
Display Operating procedure
to (page 54)
PV indication
SV indication
PV indication
Press and hold the key for one second.
1.
will be displayed.
Press the key to display .
2.
Press the key once.
3.
The current setting ( ) is displayed.
Pressing the or keys to flicker and to display .
4.
Press the key once.
5.
(Repeat the procedure from 3 to 5 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds.
6.
The SV is displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
SEL
SEL
SEL
15
Auto-tuning function (Settings: 0/1/2)
[Description]
[Note]
If the controller is powered off during auto-tuning, this makes the auto-tuning ineffectiv e with each parameter of , , and unchanged. To start the auto-tuning operation, set to “1” or “2” again.
•To suspend the auto-tuning, set to “0”. This makes the auto-tuning cancel with each parameter of , , and
unchanged.
• Once the parameters of , , and are set automatically by the auto-tuning, those parameters are stored in the controller even after it is powered off. Therefore, it is not necessary to execute the auto-tuning again.
• By setting to “1” or “2” , the auto-tuning operation starts, and at the end of the tuning, will be displayed automatically to .
• After the auto-tuning operation, the controller starts to operate at the automatically set values of , , and .
•A decimal point at the right end of the SV display flashes during auto-tuning.
•There are two codes for AT: Setting code [1]: SV standard type
Performs the auto-tuning based on the SV.
Setting code [2]: Low PV type
Performs the auto-tuning based on the SV-10%FS.
[Note]
Since ON/OFF control is performed during auto-tun­ing, overshoot against the SV may occur. To reduce the overshoot, execute the auto-tuning operation with the setting code [2] (Low PV) selected.
•The auto-tuning can be executed both just after power-on and in a control or stable status.
Related parameters:
(page 20) (page 21) (page 22)
(page 26)
(page 24)
[Setting example] Setting the auto-tuning operation to 1
Display Operating procedure
PV indication
PV indication
SV indication
Press and hold the key for one second.
1.
will be displayed.
Press the key to display .
2.
Press the key once.
3.
The current setting ( ) is displayed.
Press the or keys to flicker the display and to display .
4.
Press the key once. is displayed and the auto-tuning will start. During auto-tuning,
5.
a decimal point at the first digit from the right end of the display flickers.
(Repeat the procedure from 3 to 5 to check the set value.)
When the auto-tuning finishes properly, a decimal point stops flashing, and the set values of , ,
6.
and parameters change. When the auto-tuning finishes abnormally, a decimal point stops flash­ing, but the set values of , , and parameters remain unchanged.
If you want to display the operation status, press and hold the key for two seconds.
7.
The SV is displayed on the display area.
SEL
SEL
SEL
SEL
16
PV indication
If unoperated state continues, the PV will be displayed.
,
Displaying ON-dela y alarm or the remaining time of timers (unit: seconds) (Option)
[Description]
•These parameters display the remaining time of T imers 1 and 2.
• The remaining time of the ON/OFF-delay timer is counted down. When the counter shows , the alarm relay is closed.
• During count-down, if the PV changes to the value of the temperature at which the alarm is set to OFF, or if “DI” for the timer is set to OFF, the counter is reset, and the alarm relay is opened.
,   display parameter
SEL SEL
[Setting example] Displa ying ON-delay alarm or the remaining time of timers
Display Operating procedure
PV indication
SV indication
PV indication
Press and hold the key for one second.
1.
will be displayed.
Press the key to display . By pressing the key,
2.
the remaining time (10 seconds) of the timer 1 will be displayed. Pressing the key again, it returns to display.
Press the key to display . By pressing the key, the remaining time (8 seconds)
3.
of the timer 2 will be displayed. Pressing the key again, it returns to display.
If you want to display the operation status, press and hold the key for two seconds.
4.
The SV is displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
SEL
SEL
SEL
SEL
SEL
17
[Description]
Setting alarm 1 and 2 Upper limit of alarm 1
and 2 Lower limit of alarm 1
and 2
(Setting range:
Absolute value alarm: 0 to 100%FS Deviation value alarm: -100 to 100%FS )
}
(Option)
• These parameters are used to for settings of alarm 1 and 2.
• When the alarm type ( or alarms 1 and 2 ( and ) can be set.
•When the alarm type ( or ) is set to any value other than 0 to 15, the upper and lower limits of alarm 1 and 2 ( , , , ) can be set.
[Setting example] Setting the operation value of alarm 2 to -10°C
Display Operating procedure
PV indication
Press and hold the key for one second.
1.
will be displayed.
Press the key to display .
2.
Press the key once.
3.
The current setting ( ) will be displayed.
Press the or keys to flicker and to display .
4.
SEL
) is set to 0 to 15,
SEL
[Note]
Setting codes (12 to 15) cannot be selected in alarm type 1 ( ).
Related parameters: ,
, , ,
(page 42) (page 53) (page 51) (page 54)
SV indication
PV indication
Press the key once. will be displayed and the operation value -10°C will be registered
5.
for . After that, the controller will operate with the operation value of = -10°C.
(Repeat the procedure from 3 to 5 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds.
6.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
SEL
18
Key lock (Setting range: 0−5)
[Description]
• This parameter makes the set values of parameters unchangeable. However, the parameter name and the set values can be displayed.
•To reset the key lock, change to .
• Even when the key lock is set, control and alarm functions can operate properly.
• There are six levels of the key lock:
[Setting example] Setting the key lock to “2”
Display Operating procedure
: Unlocked (reset) : All settings are unchangeable from the controller, but
changeable via communication.
: Only the SV is changeable from the controller, and all
settings are changeable via communication.
: All settings are changeable from the controller, but
unchangeable via communication.
:
All settings are unchangeable from the controller or via communication.
: Only the SV is changeable from the controller, but all
settings are unchangeable via communication.
PV indication
SV indication
PV indication
Press and hold the key for one second.
1.
will be displayed.
Press the key to display .
2.
Press the key once.
3.
The current setting ( ) will be displayed.
Press the or keys to flicker and to display .
4.
Press the key once. will be displayed and "2" will be registered for . After that,
5.
any setting other than the SV cannot be changed from the front panel.
(Repeat the procedure from 3 to 5 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds.
6.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
SEL
SEL
SEL
19
w Second block parameters
Proportional band (Setting range: 0.0 to 999.9% of the measured range)
[Description]
•To select the ON/OFF control (two-position control), set to 0.0. It is not necessary to set and .
can be automatically set by the auto-tuning operation.
• When is too small, control will be unstable, and when is too large, the response will be delayed.
[Setting example] Changing the proportional band from 5.0% to 15.0%
Display Operating procedure
• Set the hysteresis of the ON/OFF control (two-position control) in the parameter
• If auto-tuning is run after the ON/OFF control is selected, the ON/OFF control changes to the PID control. To keep the ON/OFF control selected, do not execute the auto­tuning.
Related parameters: (page 23)
.
(page 32)
PV indication
SV indication
PV indication
Press and hold the key for three seconds.
1.
will be displayed.
Press the key once.
2.
The current setting ( ) will be displayed.
Press the or keys to flicker and to display .
3.
Press the key once. will be displayed and the 15.0% will be registered for . After that,
4.
the controller will operate with being 15.0%. (Repeat the procedure from 2 to 4 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds.
5.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
SEL
SEL
SEL
20
Integral time (Setting range: 0 to 3200 seconds)
[Description]
can be set automatically by the auto-tuning operation.
can also be set manually.
•When is set to 0, the integral operation does not start.
•When is set to 0.0, this makes the setting of ineffec­tive.
[Setting example] Changing the integral time from 240 seconds to 600 seconds
Display Operating procedure
PV indication
SV indication
PV indication
Press and hold the key for three seconds.
1.
will be displayed.
Press the key to display .
2.
Press the key once.
3.
The current setting ( ) will be displayed.
Press the or keys to flicker and to display .
4.
Press the key once. will stop flashing and will be registered for . After that, the
5.
controller will operate with being seconds.
(Repeat the procedure from 3 to 5 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds.
6.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
SEL
SEL
SEL
21
Derivative time (Setting range: 0.0 to 999.9 seconds)
[Description]
can be set automatically by the auto-tuning operation.
• can also be set manually.
•When is set to 0, the differential operation does not start.
•When is set to 0.0, this makes the setting of ineffective.
[Setting example] Changing the diff erential time from 60.0 seconds to 50.0 seconds
Display Operating procedure
PV indication
SV indication
PV indication
Press and hold the key for three seconds.
1.
will be displayed.
Press the key to display .
2.
Press the key once.
3.
The current setting ( ) will be displayed.
Press the or keys to flicker and to display .
4.
Press the key once. will be displayed and 50.0 seconds will be registered for . After that,
5.
the controller will operate with being 50.0 seconds.
(Repeat the procedure from 3 to 5 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds.
6.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
SEL
SEL
SEL
22
Hysteresis range for ON/OFF control (Setting range: 0 to 50%FS)
[Description]
•To select the ON/OFF control (two-position control), set to 0.0. It is not necessary to set and .
• When the hysteresis range (Range of ON/OFF control) is
too small, the output may switch the ON/OFF frequently. (This may affect the life of the device to be controlled, especially when contact output is selected.)
• The unit of the set value of this parameter is ºC or ºF
(engineering unit). The setting range varies according to the measured range of input.
[Ex] Input Thermocouple K :At measured range of 0
Resistance bulb :At measured range of 0
Related parameters:
[Setting example] Changing the hysteresis range from 1˚C to 35˚C
Display Operating procedure
to 400 ºC, the setting range is 0 to 200 ºC.
to 150 ºC, the setting range is 0 to 75 ºC.
(page 20)
(page 32)
PV indication
SV indication
PV indication
Press and hold the key for three seconds.
1.
will be displayed.
Press the key to display .
2.
Press the key once.
3.
The current setting ( ) will be displayed.
Press the or keys to flicker and to display .
4.
Press the key once. will be displayed and 35˚C will be registered for . After that,
5.
the controller will operate with the being 35˚C.
(Repeat the procedure from 3 to 5 to check the set value.)
If you want to display the operation status, press and hold the key for two seconds.
6.
The SV will be displayed on the display area.
If unoperated state continues, the PV will be displayed.
SEL
SEL
SEL
SEL
23
Loading...
+ 51 hidden pages