Fuji Electric PXG9, Micro Controller X PXG5, Micro Controller X PXG9 Instruction Manual

– 1 –
Thank you for purchasing the Fuji Digital temperature Controller.
Once you have confirmed that this is the product you ordered, please use it in accordance with the following instructions.
For detailed information on operating this equipment, please refer to the separate operations manual.
In addition, please keep this instruction manual within easy reach of the actual person using this equipment.
CAUTION
The contents of this manual are subject to change without notice.
This manual is complied with possible care for the purpose of accuracy, however, Fuji Electric
Systems shall not be held liable for any damages, including indirect damage,
caused by typographical errors, absence of information or use of information in this manual.
Please Read First (Safety Warnings)
Please read this section thoroughly before using and observe the mentioned safety warnings fully. Safety warnings are categorized as “Warning” or “Caution”.
1
Warning
1-1
Limitations in Use
This product was developed, designed and manufactured on the premise that it would be used for general machinery. In particular, if this product is to be used for applications that require the utmost safety as described below, please take into consideration of the safety of the entire system and the machine by adopting such means as a fail-safe design, a redundancy design as well as the conducting of periodical inspections.
Safety devices for the purpose of protecting the human body
Direct control of transportation equipment
Airplanes
Space equipment
Atomic equipment, etc
Please do not use this product for applications which directly involve human lives.
1-2
Installation and Wiring
This equipment is intended to be used under the following conditions.
Between the temperature sensor and the location where the voltage reaches or generates the values described below, secure clearance space and creepage distance as shown in the table below. If such space cannot be secured, the EN61010 safety compliance may become invalid.
For the above, if voltage exceeds 50Vdc (called danger voltage), grounding and basic insulation for all terminals of the equipment, and auxiliary insulation for digital outputs 1 to 3 is required, Note that the insulation class for this equipment is as follows. Before installing, Please confirm that the insulation class for equipment meets usage requirements.
Basic insulation (1500VAC) Functional insulation (500VAC) No insulation
In cases where damage or problems with this equipment may lead to serious accidents, install appropriate external protective circuits.
As this equipment does not have a power switch or fuses, install them separately as nec­essary. Fuse should be wired between main power switch and this equipment. (Main power switch: Bipolar breaker, fuse rating: 250V 1A)
For power supply wiring, use wire equal to 600V vinyl insulated wire or above.
To prevent damage and failure of the equipment, provide the rated power voltage.
T o pre v ent shock and equipment failure, do not turn the power ON until all wiring is complete.
Before turning on power, confirm that clearance space has been secured to prevent shock or fire.
Do not touch the terminal while the machine is on. Doing so risks shock or equipment errors.
Never disassemble, convert, modify or repair this equipment. Doing so risks abnormal operation, shock or fire.
Output relay is the part has a limited life. When output relay contact comes to the end of its life, it might remain on-state, or off-state. For safety, use a protective circuit outside.
1-3
Maintenance
When installing or removing the equipment, turn the power OFF. Otherwise, shock, oper­ational errors or failures may be caused.
Periodic maintenance is recommended for continuous and safe use of this equipment.
Some parts installed on this equipment have a limited life and/or may deteriorate with age.
The warranty period for this unit (including accessories) is one year, if the product is used properly.
2
Caution
2-1
Cautions when Installing
Please avoid installing in the following locations.
Locations in which the ambient temperature falls outside the range of –10 to 50°C when equipment is in use. (If the power supply is 200V AC, the recommended maximum ambi­ent temperature is 45°C.)
Locations in which the ambient humidity falls outside the range of 45 to 90% RH when equipment is in use.
Locations with rapid temperature changes, leading to dew condensation
Locations with corrosive gases (especially sulfide gas, ammonia, etc.) or flammable gases.
Locations with vibration or shock directly.
Locations in contact with water, oil, chemicals, steam or hot water. (If the equipment gets wet, there is a risk of electric shock or fire, so have it inspected by Fuji distributor.)
Locations with high concentrations of atmospheric dust, salt or iron particles.
Locations with large inductive interference, resulting in static electricity, magnetic fields or noise
Locations in direct sunlight.
Locations that build up heat from radiant heat sources, etc.
Warning Mishandling may lead to death or serious injury. Caution Mishandling may cause injury to the user or property damage.
Fuji Electric Co., Ltd.
International Sales Div Sales Group Gate City Ohsaki, East Tower 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan http://www.fujielectric.com Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425 http://www.fujielectric.com/products/instruments/
INP-TN1PXG5/9e-E
Confirming Specifications and Accessories
Before using the product, confirm that it matches the type ordered. (For model code, please refer to page 19.) Confirm that all of the following accessories are included.
Temperature Controller 1 unit Instruction Manual 1 copy Mounting Fixture 2 pcs I/V Unit (250Ω Resistor) 1 pc Waterproof packing 1 pc Unit nameplate 1 pc
Option
Name Order No. Terminal cover ZZPPXR1-B230 PC loader
communication cable
ZZPPXH1*TK4H4563
Related Information
Refer to the following reference materials for details about the items described in this manual.
The latest materials can also be downloaded at the following URL: http://www.fic-net.jp/eng
Document
Reference No.
Catalog
ECNO:1125
Micro Controller (Model: PXG) Operation Manual
ECNO:1411
Micro Controller (Model: PXG) Communication Functions Manual (MODBUS)
INP­TN514450-E
Ambient temperature -10 °C to 50 °C Ambient humidity 90% RH or below (with no condensation) Installation category
II
by IEC 1010-1
Pollution level 2
Voltage used or generated by any assemblies
Clearance Space (mm) Creepage Space (mm)
Up to 50 Vrms or Vdc 0.2 1.2 Up to 100 Vrms or Vdc 0.2 1.4 Up to 150 Vrms or Vdc 0.5 1.6 Up to 300 Vrms or Vdc 1.5 3.0 Above 300 Vrms or Vdc Please consult our distributor
Power
Internal circuit
Measurement input
Control output 1 (Relay contact)
or
Motorized valve OPEN output
Valve opening feedback input
Auxiliary analog input (remote SV)
Heater current detector input
Control output 1 (SSR drive, current, voltage)
Control output 2 (Relay contact)
or
Motorized valve CLOSE output
Control output 2 (SSR drive, current, voltage)
or Auxiliary analog output (Re-transmission output)
or Transmitter power supply
Digital input 1 to 5Digital output 1 (Relay contact) Digital output 1 to 3
(Relay contact)
Digital output 4, 5
Digital output 2 (Relay contact) (Transistor output)
Communication (RS-485)
When the ninth digit in the model code is J
When the ninth digit in the model code is not J
(Do1,2 are independent common) (Do1 to 3 shared common)
Instruction Manual
Micro Controller X
Model: PXG5/9
hazardous voltage
– 2 –
2-2
Cautions when Attaching to the Panels
Please attach the PXG5/PXG9 with the included fixtures (2 pieces) to the top and bottom, and tighten with a screwdriver.
The clamp torque is approximately 0.15 N/m (1.5 kg/cm) It is designed such that overtightening will cause left/right cracking to the central area of the Fixtures and hence reduce the torque. Cracking to the central area will not cause any problems in terms of usability of the equip­ment. (However, do exercise caution in not applying too much torque because the casing is made of plastic.)
The front of this equipment is waterproof in compliance with NEMA-4X standards (IP66­equivalent). To effect waterproof, the included packing is shall be attached between the controller and the panel according to the guidelines below. (Incorrect attachment may cause the equip­ment to lose its waterproof capabilities.) (1) As shown in Fig. 1, insert to the panel after attaching the packing to the equipment
case.
(2) As shown in Fig. 2, tighten the fixture screws so that no gaps can remain between the
equipment face, the packing and the panels. Once finished, confirm that there are no changes in shape such as displaced or improperly-fitted packing, etc. as shown in Fig. 3.
If the panel does not have enough strength, gaps may develop between the packing and the panel to lose waterproofing capabilities.
2-3
Cautions for Wiring
For thermocouple input, use the designated compensation lead; for resistance bulb input, use wires with small lead wire resistance and without any resistance difference among the three wires.
To avoid noise conductor effects, input signal wires should be separated from electric power lines or load lines.
Input signal wire and output signal wire should be separated each other. And both should be shield wire.
If there is a lot of noise from the power source, adding an insulation transducer and using a noise filter is recommended.
(Example: ZMB22R5-11, noise filter Maker: TDK) Always attach a noise filter to a panel that is grounded securely, and keep the wiring between the noise filter output side and the measuring equipment power terminal wiring to a minimum length.
Please do not attach fuses and switches, etc. to the noise filter output wiring, otherwise the filter’s effectiveness will be decreased.
Twisting the power wires is effective when connecting the wires. (The shorter the pitch of the twist, the more effective the connection is against noise.)
If there is a function of heater current detection, heater wires and power wires should be connected with same power line.
Operation preparation time is required for the contact output when power is turned on. If using it as a signal to an external interlock circuit, please couple it with a delayed relay.
Concerning the output relay, connecting the maximum rated load will shorten the prod­uct’s life; so please attach an auxiliary relay. If the output operation frequency is high, selecting a SSR/SSC drive output type is recommended.
[Proportionate cycles] Relay output: 30 seconds or more, SSR/SSC drive output: 1
second or more
When inductive loads such as magnetic opening/closing equip­ment, etc. as relay output equipment are connected, use of “Z-trap,” manufactured by Fuji Electric Device Technology Co., Ltd., is recommended in order to protect the contacts against opening/closing surges and to ensure long-term use.
Model names : ENC241D-07A
(For 100V power voltage) ENC471D-07A (For 200V power voltage)
Attachment position : Please connect between the relay
control output contacts. (Refer to Fig. 4.)
2-4
Key Operation Caution/Error Operation
The alarm function does not work properly when an error takes place unless the settings are made correctly. Always verify its setting before operation.
If the input wiring breaks, the display will read “
UUUU
”. When replacing the sensor, always
turn the power OFF.
2-5
Others
Please do not wipe the equipment with organic solvents such as alcohol or benzene, etc. If wiping is necessary, use a neutral cleaning agent.
Do not use mobile phones near this equipment (within 50 cm). Otherwise a malfunction may result.
Trouble may occur if the equipment is used near a radio, TV, or wireless device.
For Proper Usage
Caution
In order to aid heat dissipation, do not block the sides of the equipment.
Do not block the air vents on the upper part of the terminal.
For the PXG9, please attach the fixtures to the attachment holes in the center of the main unit.
Fig. 3
Packing
Packing
Case
Case
(Bad)
(Good)
Unit
Fig. 1 Fig. 2
Front
Panel
Screw
Screw
Panel
Packing
Mounting fixture
Mounting fixture
α = 0 to 30°
Standard: vertical attachment (horizontal position attachment) If attached at an angle, the maximum gradient is a 30° downslope.
12
11
10
9
8
7
36
35
34
33
32
31
6
5
4
3
2
1
25 26 27 28 29 30
Fig.4 Attachment posi-
tion of Z-Trap
(Example)
Caution
Wait 30 minutes for the controller to stabilized thermally. Operations such as measurements should be taken after the equipment has been on for 30 min­utes or more.
Confirmation of model code
Please confirm that the model delivered matches your order.
"12 Model Specifications" (page 19)
2
Wiring Connection
Terminal connections diagram
"4 Wiring" (page 4)
3 Display and Operations 4 Parameter List 5 Functions of the Temperature Controller
Changing set value
Basic Operation Methods
Parameter List
Input/Output/Control
"5 Display and Operations" (page 5)
"5 Display and Operations" (page 5)
"6 Parameter List" (page 6)
"7 Functions" (page 10)
Turn Power On
6 Advanced Usage Setting of input sensor and input range
Selecting control method
Controlling through auto-tuning
Automatic setting parameters
"8-1 Input Setting" (page 17)
"8-3 Control Setting" (page 18)
"7-6 Auto-tuning" (page 11)
"7-3 Fuzzy PID Control", "7-4 Self-tuning Control" (page 10)
7 Error Indications
Display during equipment error
"9 Error Indications" (page 18)
Operation
1 Installation and Mounting
External dimensions
• Panel cut dimensions
• Mounting the panel
"3 Installation and Mounting" (page 3)
– 3 –
3
Installation and Mounting
3-1
External/Panel Cut Dimensions
Caution
Panel cut dimensions should also meet the above dimensions after the panel is coated. Cautions when Close Fit Mounting:
When the power supply is AC 200V, keep the maximum ambient temperature at 45°C. For vertical close-fit mounting, use a power source of AC 100V. (In both cases, a fan is recommended as a measure against radiation.)
When there is an instrument larger than 70 mm or a wall to the right of the controller, move it as least 30 mm away.
Cautions when wiring:
Start by wiring from the left-hand terminals (terminals 1 to 12).
Use a screw that is the right size on terminals and tighten them with a torque of about 0.8 N/m.
Do not attach anything to unused terminals. (Do not use relay terminals.)
PC loader interface
PXG9
TOP
TOP
13-2437-48 61-7249-60
1-12
25-36
waterproof packing
panel
terminal screw M3
96
96
79.510
2
91.5
115.5 MAX
t
6.2
31 32 33 34 35 36
7 8 9
1 2 3 4 5 6
10 11 12
mounting fixture (fastening torque 0.15 N•m)
25 26 27 28 29 30
Panel thickness 1 to 8 mm
PC loader interface
25-36
1-12
13-24
Waterproof packing
panel
terminal screw M3
48
96
Mounting fixture (fastening torque 0.15 N•m)
PXG5
7810
2
91.5
115.5 MAX
t
Panel thickness 1 to 8 mm
6.2
12
11
10
36
35
34
33
32
31
9
8
7
6
5
4
3
2
1
25 26 27 28 29 30
Installing multiple controllers
Installing multiple controllers horizontally (In this installing, the waterproof of PXG is lost.)
50 MIN.
45
92
+0.6 0
116 MIN.
+0.8
0
(48 × n–3)
+0.8 0
+0.8
0
92
Installing multiple controllers
92
+0.8 0
92
+0.8
0
116 MIN.
100 MIN.
– 4 –
4
Wiring
4-1
Terminal Connection Diagram (100 to 240V AC, 24V AC/DC)
Standard T ype
Motorized Valv e Type
Note 1: Check the power supply voltage before making the connections. Note 2: When inputting current, connect the additional I/V unit (250
resistor) between the terminals number 33 and 36.
Note 3: Transmitter power output is an option only for PXG9.
1 2 3 4 5 6 7 8
9 10 11 12
25 26 27 28 29 30 31 32
33 34 35 36
1 2
DI–COM
DI1
1 2
3
4
CT1 input
Digital input
1 2
DI–COM
DI1
Digital input
RSV1 input
Digital input
343
4
++
No communication function
Relay output
5 6
Current output
SSR drive
XPS output
125
6
++ –
125 6
++
Voltage output
Digital input
Control output 2/Re–transmission
1 2
DI–COM
DI1
3
4
DI2
1 2 3
4
DI2
RSV1 input
5 6
++
7 8 9
10
DO1
DO–COM
DO2
DO3
7 8 9
10
DO1
DO1–COM
DO2
DO2–COM
11
4
12
++
50/60Hz
11
4
12
DIgital output
Digital output
AC100 to 240V
AD/DC 24V
1
2
DI–COM
DI1
3
4
DI2
No connection
No connection
1
2
3
4
DI2
Relay output
31 32
Current output
31 32
++
SSR drive
125
6
++ –
3 4
+
32
31
Voltage output
Control output 1
33 34 35 36
+ –
Thermocouple input
33 34 35 36
A B B
Resistance bulb input
33 34 35 36
+
Current/voltage input
Voltage (mV) input
33 34 35 36
+
Measurement value input
29
30
++
29 30
RSV2 input
CT2 input
25 26 27 28
DIO–COM
DI3
DI5
DI4
Digital input
25 26 27 28
DIO–COM
DI3
DI5
DI4
Digital input
25
26
27
28
29 30
DIO–COM
DI3
DI5
DI4
DO4 DO5
Digital input/output
5
6
+
Power supply
(Note 3)
(Note 1)
(Note 2)
50/60Hz
++
31 32
+
DI–COM
DI1
3 4
3 4
3 4
+
5 6
1 2
+
DI–COM
DI1
3
4
1 2
+
RS485 communicator
RS485 communicator
Communication function included
Digital input Digital inputRSV1 input
RSV1 input
CT input
1 2 3 4 5 6 7 8
9 10 11 12
25 26 27 28 29 30 31 32
33 34 35 36
Digital input
RS485 communicator
RSV1 input
5
6
+
DI–COM
DI1
3
4
1 2
+
7 8 9
10
DO1
DO–COM
DO2
DO3
7 8 9
10
DO1
DO1–COM
DO2
DO2–COM
11
4
12
++
50/60Hz
11
4
12
Digital output Digital output
AC100 to 240V
AD/DC 24V
AUX DO
31 32
Control output 1
33 34 35 36
+
Thermocouple input
33 34 35 36
A B B
Resistance bulb input
33 34 35 36
+
Current/voltage input
Voltage (mV) input
33 34
35 36
+
Measurement value input
Power supply
(Note 1)
(Note 2)
50/60Hz
Communication function included
Digital input
1 2
DI–COM
DI1
3
DI2
3 4
DI1
5
6
DI3
1 2
DI–COM
DI1
3
DI2
1 2
3 4
DI3
Digital input
RSV1 input
5 6
––
++
No communication function
28 29 30
I + I 0 I –
25 26 27
PFB input
CLOSE
COM OPEN
Valve control output
++
31 32
XPS output
(Note 3)
– 5 –
5
Display and Operations
5-1
Part names and functions
Operation Parts
USER Key
Pressing this key in monitoring mode display or setup mode display returns you to the PV/SV display. Pressing this key on the PV/SV display allows you to set the function for "
UkEY
" under the system menu
("
SYS Ch 7
"). (The factory set function for this key is switching between auto and manual.)
SEL Key
Switches the PV/SV display to the monitoring mode display or setup mode display.
Switches to setup mode when parameter display , and this k e y functions as the select ke y when changing parameters. Holding this key down in channel display or parameter display returns you to the PV/SV display.
Pressing this key at PV/SV display in manual mode, manual output value is shown in the lower display.
Key
Pressing once will increase the setting value by one. Holding down the button will continue to increase the value. It changes SV on the PV/SV display. It is also used to move between items in channel screen display and parameter screen display.
Key
Pressing once will decrease the setting value by one. Holding down the button will continue to decrease the value. It changes SV on the PV/SV display. It is also used to move between items in channel screen display and parameter screen display.
Display
C1/C2 Lamp
Displays the condition of the control output. Lights ON at 100% output and goes out at 0% out­put. For values between 0% and 100%, the output is indicated by the length of time the lamp flickers.When acting as a valve control, the C1 lamp will light with OPEN output, and the C2 lamp will flickers with CLOSE output.
DO1/2/3 Lamp
Lights ON when there is digital output is on state (DO1, DO2, DO3). The lamp flickers when delay behavior is on.
PV Display
Displays the measurement value (PV). Displays the name of the parameter when setting parameters.
SV Display
Displays the setting value (SV). Also can display the output value during manual mode. Dis­plays the parameter setting value when setting parameters. Displays "
rEM" during remote SV
operation, and "
SoFT" and set value alternately during soft start.
SV Lamp
Lights when displaying the setting value (SV). Goes out when displaying the manual output value. The lamp flickers while performing ramp soak or lamp SV operations.
MAN/AT/SELF Lamp
Normally lights up during manual mode and blinks during auto-tuning or self-tuning.
5-2 Monitor Display and Status Display
In monitor mode, the PV display shows item names, while the SV display shows the input/output values.
For more details on “
PASS” (PASS), see “5-6 Key Lock and Password” (page 6).
For more details on (Note) in the Remarks column, see “6 Parameter List” (page 6).
5-3 Basic Operations
Pressing the key or the key switches between modes. Pressing in monitor mode or setup mode allows you to choose menu items.
Changing SV (set values)
Changing MV (control output values)
5-4 Operations
For the following modes, the PV display will show the PV input value.
Operation Mode
SV display shows the SV setting value.
Manual Mode
An LED light decimal point lights ON in the lowest digit place in the SV display. An “o” appears in the highest decimal place during MV display. Pressing the keys sets the MV (%).
DO1 Lamp
DO2 Lamp
DO3 Lamp
PV Display
SV Display
Key Key
C2 Lamp
C1 Lamp
SV Lamp
USER Key
SEL Key
MAN/AT/SELF Lamp
PFB input value display (%)
RSV terminal input value display
Password entry
hold down
MV1 (%)Error source
display
MV2 (%)
monitor mode
operation mode
Parameter display symbol
Parameter name Function Setting range
Remarks
"
FALT
"
(FALT)
Error source display
Displays the source of an error
"
Mv1
" (Mv1) MV1 Displa ys the output
value of the control output (OUT1)
-3.0 to 103.0%
"
Mv2
" (Mv2) MV2 Displays the output
value of the control output (OUT2) (during dual control)
-3.0 to 103.0% (Note4)
"
PFb
" (PFb) Displays the PFB
input value
Displays the input value of the position feedback
-3.0 to 103.0% (Note8)
"
rSv
" (rSv) RSV input value
display
Displays the input value of the RSV
-5 to 105% FS (initial value) (Note1)
1
Change the display to PV/SV display (shown when you turn on the power and the SV lamp is lit).
2
Change the SV with the keys.
3
Press the key to save the values.
(The value will be automatically saved after 3 seconds even if a key is not pressed.)
1
Switch to manual mode.
2
Change the display to PV/MV display (MAN/AT/SELF lamp is lit).
(Pressing the key in manual mode toggles between PV/SV display and PV/MV display.)
3
Change the MV with the keys.
(Changes are reflected to the MV as it is changed.)
Refer to
See “7-9 Manual Output” (page 12) for more about changing to manual mode.
fixed at 0 8bit : PV input underflow 9bit : PV input overflow 10bit: underrange 11bit: overrange 12bit: RSV underrange 13bit: RSV overrange 14bit: range setting error 15bit: EEPROM error
0bit: PFB input underflow 1bit: PFB input overflow
initial display
(PV/SV display)
observation
value display
channel menu
parameter
menu
parameter
setting
manual output
(PV/MV display)
hold down
(change mode)
operation mode
monitor mode
manual mode
setup mode
hold down
hold down
hold down
only during manual mode
manual lamp ON
(change display only)
channel display
: Press several times
parameter display
– 6 –
5-5
Setting Parameters
The following explains how to set the parameters.
No matter where you are in monitor or setup mode, pressing the key returns you to operation mode. When setting the parameters in manual mode, pressing the key holds manual mode and returns you to operation mode.
5-6
Key Lock and Password
Setting Key Lock
When key lock is activated, parameters cannot be changed but can displayed. Use the follow­ing steps to set key lock.
Saving and entering a password
Use the following steps to save a password.
The authority of the passwords grows from "
PAS1
" to "
PAS2
" to "
PAS3
". The higher the author-
ity, the greater number of channels for display and settings.
Use the following steps to enter a password.
6
Parameter List
The following explains each channel parameter. The list also shows the operational range of set values for parameters that are limited.
When the PV input lower limit (Pvb), PV input upper limit (PvF), or decimal place position (Pvd) is changed, reconfigure all the initial parameter setting values.
When the parameter that has
on its Remarks column is changed, turn off the power
once, and then re-start the controller.
6-1
Operation (Ch1)
The following is a menu to oper ate the controller. Switchover between auto and manual control output, switchover between RUN and standby, and other such functions.
6-2
PID (Ch2)
Sets parameters for controls such as PID.
1
Press and hold the key in operation mode, or manual mode.
This switches you to the monitor mode Mv1.
2
Press and hold the key in monitor mode
This switches you to the channel menu of setup mode.
3
Choose the channel with the keys, then press and hold the key.
This switches you to the parameter menu.
4
Choose the parameter with the keys, then press the key.
The set value flickers.
5
Choose the parameter with the keys, then press the key.
The set value is fixed.
1
Display the operation menu ("oPE Ch 1").
2
Display key lock ("LoC") and press the key.
3
Set the value.
0 : No lock (all parameters can be changed. Initial value.) 1 : All lock (no parameters can be changed.) 2 : All lock without SV (only the SV can be changed.)
4
Press the key to set the value.
1
Display the password menu ("PAS Ch11").
2
Display password 1 ("PAS1") and press the key.
3
Set the password.
You can enter the hexadecimal value 0000 through FFFF.
4
Press the key to set the value.
"
PAS2" and "PAS3" can be saved in the same way.
1
In monitoring mode, display ("PASS") and press the key.
2
Enter a saved password and press the key.
You will be able to operate the equipment depending on the authority of your password.
Point
Each parameter channel and the authority of passwords 1 to 3
Note: When “
FEFE” (FEFE) is entered as “PASS” (PASS), all of the channels “OPE ch” to
“DSP ch” can be displayed and set. This “super password” function is useful when you forget the set passwords.
oPE ch
PAS1 permissions <"PASS" = "PAS1">
PAS2 permissions <"PASS" = "PAS2">
PAS3 permissions <"PASS" = "PAS3">
Pid ch PLT ch PrG ch Mon ch SET ch SyS ch ALM ch CoM ch PFb ch PAS ch dSP ch
Password level
Parameter display symbol
Parameter name Function Setting range
Initial value
Remarks
"
man" (MAn) Switchover
between auto and manual mode
Switchover between auto and manual modes
oFF (auto) / on (manual)
oFF
"
STbY" (STby) Switchover
between RUN and standby
Switchover the operation mode between RUN and standby
oFF (RUN) / on (standby)
oFF
"
rEm" (rEM) Switchover
between local and remote SV operation
Switchover between local and remote SV operation
LoCL (local) / rEM (remote)
LoCL
(Note1)
"PrG" (PrG) Ramp soak
control command
Changes ramp soak run states
oFF (stop) rUn (run) hLd (hold)
oFF
Displays End (when ending) or GS (during guaranty soak).
"At" (AT) Auto-tuning run
command
Runs auto-tuning. oFF (stop/finish)
on (normal type) Lo (low PV type)
oFF
"
LA[h"
(LACh)
DO output latch release command
Cancels the DO latch state
oFF / rST (latch resets)
oFF (Note2)
"
Svn" (Svn) Currently
selected SV No.
Choose the SV No. used for control
Sv0 Sv1 Sv2 Sv3 Sv4 Sv5 Sv6 Sv7 di (chooses SV according to di)
Sv0
(Note20)
"PLn1" (PLn1) Currently
selected PID No.
Choose the PID group No. used for control
Pid 0 (PID ch) P
id
1 (PID group No. 1) P
id
2 (PID group No. 2) P
id
3 (PID group No. 3) P
id
4 (PID group No. 4) P
id
5 (PID group No. 5) P
id
6 (PID group No. 6) P
id
7 (PID group No. 7) di (chooses PID group according to di)
Pid0
"
AL1
" (AL1)
"
AL1L
" (AL1L)
"
AL1h
" (AL1h)
"
AL5
" (AL5)
"
AL5L
" (AL5L)
"
AL5h
" (AL5h)
AL1 set value AL1L set value AL1h set value
AL5 set value AL5L set value AL5h set value
Set the alarm value.
0 to 100% FS (absolute value alarm)
-100 to 100% FS (deviation alarm)
10°C
(Note3)
"
LoC
" (LoC) Key lock Sets the key lock to
prevent wrong operation
0 (no lock) 1 (all lock)
2
(All but SV locked)
0
Parameter display symbol
Parameter name Function Setting range
Initial value
Remarks
" P
" (P) Proportional band Sets the
proportional band of the PID parameter. Setting "0.0" will turn it to an ON/OFF control.
0.0 to 999.9% 5.0%
"
i
" (i) Integration time
Sets the integration time of the PID parameter. Setting "0" will turn off integration.
0 to 3200 sec 240 sec
"
d
" (d) Differential time
Sets the differential time of the PID parameter. Setting "0.0" will turn off derivation.
0.0 to 999.9 sec 60.0 sec
"
hyS
" (hyS) ON/OFF control
hysteresis
Sets the hysteresis width for the ON/ OFF control.
0 to 50% FS 1°C
"
[oL
" (CoL) Cooling
proportional band coefficient
Sets the cooling proportional band coefficient. Setting "0.0" will turn the cooling into an ON/ OFF control.
0.0 to 100.0 1.0
(Note4)
RST
– 7 –
6-3
PID Palette (Ch3)
Saves the palette values of PV and PID. Up to seven sets can be saved.
6-4
Ramp soak (Ch4)
Create a pattern of temperatures using ramp soak combinations. You can create a temperature pattern with up to 16 steps.
"
db" (db) Dead band Shifts the cooling
proportional band from the set value
-50 to 50% 0%
(Note4)
"bAL" (bAL) Output
convergence value
Offset value which is added to the MV output value
-100 to 100% 0/50 (single/ dual)
"
Ar" (Ar) Anti-reset
windup
Sets the range of integration control
0 to 100% FS 100%FS
"
rEv" (rEv) Sets normal/
reverse operations
Sets the control action
rv-- (heat (reverse)
/cool (none))
no-- (heat (normal)
/cool (none))
rvno (heat (reverse)
/cool (normal))
norv (heat (normal)
/cool (reverse))
rvrv (heat (reverse)
/cool (reverse))
nono (heat (normal)
/cool (normal))
rv--/rvno (single/ dual)
"
SvL" (SvL) SV limit
(lower limit)
Sets the lower limit of SV
0 to 100% FS 0% FS
(Note5)
"Svh" (Svh) SV limit
(upper limit)
Sets the upper limit of SV
0 to 100% FS 100% FS
(Note5)
"t[1" (TC1) OUT1 proportion
cycle
Sets the proportion cycle of the control output (OUT1) (contacts, SSR drive)
1 to 150 sec 30:
Contact 2: SSR drive
(Note7)
"t[2" (TC2) OUT2 proportion
cycle
Sets the proportion cycle of the control output (OUT2) (contacts, SSR drive)
1 to 150 sec 30:
Contact 2: SSR drive
(Note4)
"Plc1" (PLC1)
OUT1 lower limit
Sets the lower limit of the control output (OUT1)
-3.0 to 103.0% -3.0%
"
Ph[1" (PhC1)
OUT1 upper limit
Sets the upper limit of the control output (OUT1)
-3.0 to 103.0% 103.0%
"
PL[2" (PLC2)
OUT2 lower limit
Sets the lower limit of the control output (OUT2)
-3.0 to 103.0% -3.0%
(Note4)
"Ph[2" (PhC2)
OUT2 upper limit
Sets the upper limit of the control output (OUT2)
-3.0 to 103.0% 103.0%
(Note4)
"P[UT" (PCUT) Selects the type of
output limiter
Sets the type of output limiter
0 to 15 0
Parameter display symbol
Parameter name Function Setting range
Initial value.
Remarks
"Sv1" (Sv1) SV 1 Sets the SV set
value
SV limit (lower) (SVL) to SV limit (upper) (SVH) %FS
0%FS
(Note5)
"P1" (P1) Proportional band 1 Sets the
proportional band
0.0 to 999.9% 5.0%
"
i1" (i1) Integration time 1 Sets the
integration time
0 to 3200 sec 240 sec
"
d1" (d1) Differential time 1 Sets the
differential time.
0.0 to 999.9 sec
60.0 sec
"hyS1" (hyS1) ON/OFF control
hysteresis 1
Sets the hysteresis when using the ON/OFF control.
0 to 50% FS 1 °C
"
[oL1" (CoL1) Cooling proportional
band 1
Sets the cooling proportional band
0.0 to 100.0 1.0
(Note4)
"db1" (db1) Dead band 1 Sets the dead
band
-50.0 to 50.0% 0%
(Note4)
"bAL1" (bAL1)
Output convergence value 1
Offset value which is added to the control output
-100.0 to 100.0% 0/50
(single/ dual)
"
Ar1" (Ar1) Anti-reset windup 1 Sets the anti-reset
windup
0 to 100% FS
100%FS
"rEv1" (rEv1) Sets normal/
reverse 1
Sets the control action
rv-- (heat (reverse)/
cool (none))
no-- (heat (normal)/
cool (none))
rvno (heat (reverse)/
cool (normal))
norv (heat (normal)/
cool (reverse))
rvrv (heat (reverse)/
cool (reverse))
nono (heat (normal)/
cool (normal))
rv--/rvno (single/ dual)
(Note6)
"Sv7" (Sv7) SV 7 Sets the SV set
value
SV limit (lower) (SVL) to SV limit (upper) (SVH) %FS
0%FS
(Note5)
"P7" (P7)
Proportional band 7
Sets the proportional band
0.0 to 999.9% 5.0%
"
i7" (i7) Integration time 7 Sets the
integration time
0 to 3200 sec 240 sec
"
d7" (d7) Differential time 7 Sets the
differential time.
0.0 to 999.9 sec
60.0 sec
"hyS7" (hyS7) ON/OFF control
hysteresis 7
Sets the hysteresis when using the ON/OFF control.
0 to 50% FS 1 °C
"
[oL7" (CoL7)
Cooling proportional band 7
Sets the cooling proportional band
0.0 to 100.0 1.0
(Note4)
Parameter display symbol
Parameter name Function Setting range
Initial value
Remarks
RST
RST
"db7" (db7) Dead band 7 Sets the dead
band
-50.0 to 50.0% 0%
(Note4)
"bAL7" (bAL7)
Output convergence value 7
Offset value which is added to the control output
-100.0 to 100.0% 0/50 (single/ dual)
"
Ar7" (Ar7)
Anti-reset windup 7
Sets the anti-reset windup
0 to 100% FS
100% FS
"rEv7" (rEv7) Sets normal/reverse 7Sets the control
action
rv-- (heat (reverse)
/cool (none))
no--(heat (normal)
/cool (none))
rvno (heat (reverse)
/cool (normal))
norv (heat (normal)
/cool (reverse))
rvrv (heat (reverse)
/cool (reverse))
nono (heat (normal)
/cool (normal))
rv--/rvno (single/ dual)
(Note6)
"SvMX" (SvMX) Sets the Max SV
selection number
Choosing SV with the user key sets it to the maximum possible number.
Sv0 Sv1 Sv2 Sv3 Sv4 Sv5 Sv6 Sv7 di
Sv7
"
PL1m" (PL1M) Set the Max PID
selection number
Choosing PID with the user key sets it to the maximum possible number.
Pid0 Pid1 Pid2 Pid3 Pid4 Pid5 Pid6 Pid7 di
P
id
7
Parameter display symbol
Parameter name Function Setting range
Initial value
Remarks
"
Ptn
" (PTn) Ramp soak
operation pattern (Step No.)
Sets which steps to use in the ramp soak operation pattern
0 (uses steps 1 to 4) 1 (uses steps 5 to 8) 2 (uses steps 1 to 8) 3 (uses steps 9 to 12) 4 (uses steps 13 to 16) 5 (uses steps 9 to 16) 6 (uses steps 1 to 16) di (according to di)
6
(Note 21)
"
TiMU
" (TiMU) Ramp soak time
units
Sets the units of the ramp soak time
hh.MM (hour:min) MM.SS (min:sec)
hh.MM
"
Sv-1
"
(Sv-1)
Ramp soak 1 seg/ SV
Sets the SV
0 to 100% FS 0%FS
"
tm1r
" (TM1r) Ramp soak 1 seg
ramp time
Sets the ramp time
00.00 to 99.59 (hour:min/ min:sec)
00:00 (hour:min)
"
tm1S
" (TM1S) Ramp soak 1 seg
soak time
Sets the soak time
00.00 to 99.59 (hour:min/ min:sec)
00:00 (hour:min)
"
Sv16
"
(Sv16)
Ramp soak 16 seg/ SV
Sets the SV
0 to 100% FS 0%FS
"
t16r"
(T16r")
Ramp soak 16 seg ramp time
Sets the ramp time
00.00 to 99.59 (hour:min/ min:sec)
00:00 (hour:min)
"t16S" (T16S) Ramp soak 16
seg soak time
Sets the soak time
00.00 to 99.59 (hour:min/ min:sec)
00:00 (hour:min)
"mod" (Mod)
Ramp soak mode
Sets the program operation method
0 to 15 0
"
Gsok" (Gsok) Guaranty soak
ON/OFF
Sets the guaranty soak ON or OFF
oFF (guaranty soak off) on (guaranty soak on)
oFF
"
GS-L"(GS-L) Guaranty soak
band (lower)
Sets the lower limit of guaranty soak
0 to 50% FS 5°C
"
GS-h"(GS-h) Guaranty soak
band (upper)
Sets the upper limit of guaranty soak
0 to 50% FS 5°C
"PvST"( PvST) PV start Sets whether or
not to start ramp soak with PV.
oFF (PV start OFF) on (PV start ON)
oFF
" ConT "(ConT) Restore mode Sets how to
restart when the controller is restored after a power loss.
rES (Reset) Con (Continue) ini (Restart)
rES
(Note 20)
"
PTnM
" (PTnM) Sets the Max
pattern selection
Choosing pattern with the user key sets it to the maximum possible number.
0 to 6,di 6
" PMin "(PMin) Sets the Min
pattern selection
Choosing pattern with the user key sets it to the minimum possible number.
0 to 6, di 0
Parameter display symbol
Parameter name Function Setting range
Initial value.
Remarks
RST
RST
– 8 –
6-5
Monitor (Ch5)
You can check the ramp soak progress, control output, heater current, remaining time, and other status functions.
6-6
Setup (Ch6)
Sets up the input range, output range, and other items for the equipment.
6-7
System (Ch7)
Assigns the functions of the DI/DO, LED lamp, and other controls.
Parameter display symbol
Parameter name Function Setting range
Remarks
"
StAt
" (STAT) Ramp soak
progress
Displays the progress of the ramp soak
oFF (ramp soak stopped) 1-rP (ramp in step 1) 1-Sk (soak in step 1)
16rP (ramp in step 16) 16Sk (soak in step 16) End (ramp soak finished)
"
Mv1
" (Mv1) MV1 Displa ys the output
value of the control output (OUT1)
-3.0 to 103.0%
"
Mv2
" (Mv2) MV2 Displays the output
value of the control output (OUT2)(during dual control)
-3.0 to 103.0% (Note4)
"
PFb
" (PFb) Displays the PFB
input value
Displays the input value of the position feedback
-3.0 to 103.0% (Note8)
"
rSv
" (rSv) RSV input value
display
Displays the input value of the RSV
-5 to 105% FS (Note1)
"
[t1
"
(CT1)
Heater current 1
Displays the current through the CT
0, 0.4 to 50.0A
(Note10) (Note13)
"
LC1
" (LC1)
Leak current value 1
Displays the leak current value of CT.
0, 0.4 to 50.0A
(Note 10) (Note 13)
"
tm1
"
(TM1)
Remaining time on timer 1
Displays the remaining time on timer 1
0 to 9999 sec/ 0 to 9999min (Note3)
"
tm5
"
(TM5)
Remaining time on timer 5
Displays the remaining time on timer 5
0 to 9999 sec/ 0 to 9999min
"
FALT
"
(FALT)
Error source display
Displays the source of an error
" PLno "( PLno) Current palette No. Displays the PID
palette No. currently selected.
0 to 7
" PTno "( PTno) Current pattern
No.
Displays the pattern No. of the ramp soak currently selected.
0 to 6
Parameter display symbol
Parameter name Function Setting range
Initial value
Remarks
"
PvT
" (PvT) PV input type Sets the type
of input sensor
0 (no function) 1 (PT 100
) 2 (J) 3 (K) 4 (R) 5 (B) 6 (S) 7 (T) 8 (E) 9 (no function) 10(no function) 11 (no function) 12 (N) 13 (PL-
2
) 14 (no function) 15 (0 to 5V / 0 to 20mA) 16 (1 to 5V / 4 to 20mA) 17 (0 to 10V) 18 (2 to 10V) 19 (0 to 100mV)
3 (K)
"
Pvb
" (Pvb) PV input lower
limit
Sets the lower limit of PV input
-1999 to 9999 0
°
C
"
PvF
" (PvF) PVinput upper
limit
Sets the upper limit of PV input
-1999 to 9999 400
°
C
"
Pvd
" (Pvd) Decimal point
position
Sets the number of decimal point positions for the PV/SV
0 (No digit after decimal point) 1 (1 digit after decimal point) 2 (2 digit after decimal point)
0
"
PvoF
" (PvoF) PV input shift
Sets the amount of shift for PV input
-10 to 10% FS
0%FS
"
tF
" (TF) PV input filter
Sets the time constant for the PV input filter
0.0 to 120.0 sec 5.0 sec
"
rEm0
" (rEM0) RSV Zero
adjustment
Adjusts the zero RSV input
-50 to 50% FS
0%FS (Note1)
"
rEmS
" (rEMS) RSV Span
adjustment
Adjusts the span RSV input
-50 to 50% FS
0%FS (Note1)
"
rEmr
" (rEMr) RSV input
range
Sets the range for RSV input
0-5 (0 to 5V) 1-5 (1 to 5V)
1-5
(Note1)
"
rtF
" (rTF) RSV input
filter
Sets the time constant for the RSV input filter
0.0 to 120.0 sec 0.0 sec
(Note1)
fixed at 0 8bit : PV input underflow 9bit : PV input overflow 10bit: underrange 11bit: overrange 12bit: RSV underrange 13bit: RSV overrange 14bit: range setting error 15bit: EEPROM error
0bit: PFB input underflow 1bit: PFB input overflow
RST
RST
RST
RST
"
[1r
" (C1r) OUT1 range Sets the range
of the control output (OUT1)
0-5 (0 to 5V) 1-5 (1 to 5V) 0-10 (0 to 10V) 2-10 (2 to 10V) 0-20 (0 to 20mA) 4-20 (4 to 20mA)
0-10 (voltage ) 4-20 (current)
(Note9) (Note14)
"
[2r
" (C2r) OUT2 range
Sets the range of the control output (OUT2) (Also sets for the re-transmission output)
0-5 (0 to 5V) 1-5 (1 to 5V) 0-10 (0 to 10V) 2-10 (2 to 10V) 0-20 (0 to 20mA) 4-20 (4 to 20mA)
0-10 (voltage )
4-20
(current)
(Note12) (Note14) (Note18)
"
FLo1
" (FLo1) Output 1 set
value during FALT
Sets the output value for the control output (OUT1) during FALT
-3.0 to 103.0% -3.0%
"
Flo2
" (FLo2) Output 2 set
value during FALT
Sets the output value for the control output (OUT2) during FALT
-3.0 to 103.0%
-3.0% (Note4)
"
SFo1
" (SFo1) Soft Start
output 1 set value
Sets the output value for the control output (OUT1) during soft start
-3.0 to 103.0%
103.0%
"
SFtm
" (SFTM) Soft Start set
time
Sets the time from startup to the finish of soft start
00:00 to 99:59 (hour:min) 0.00
(hour: min)
Be sure to set
0.00 during dual control.
"
Sbo1
" (Sbo1) OUT1 output
set value during standby
Sets the output value for the control output (OUT1) during standby
-3.0 to 103.0% -3.0%
"
Sbo2
"
(
Sbo2)
OUT2 output set value during standby
Sets the output value for the control output (OUT2) during standby
-3.0 to 103.0% -3.0% (Note4)
"
Sbmd
" (SbMd) Standby mode
setting
Sets the alarm output, re­transmission output, and PV/SV display during standby
0
(Note15)
"
Aot
" (AoT) Types of AO
output
Displays the types of re­transmission output
PV SV MV DV
Pv
(Note12)
"
AoL
" (AoL) AO lower limit
scaling
Sets the lower limit of AO
-100 to 100% 0%
(Note12)
"
Aoh
" (Aoh) AO upper limit
scaling
Sets the upper limit of AO
-100 to 100% 100%
(Note12)
Parameter display symbol
Parameter name
Function Setting range
Initial value
Remarks
"
UkEy
" (UkEy) Assigns the
USER key
Sets the function of the [USER] key
0 (no function) 1 (Switchover between STBY ON/OFF) 2 (Switch
over
between Auto/Manual) 3 (Switchover between Local/Remote) 4 (no function) 5 (Starts AT (standard)) 6 (Starts AT (low PV)) 7 (Ramp SV on/off) 8 (Ramp SV HOLD) 9 (Ramp soak OFF) 10 (Ramp soak RUN/HOLD) 11 (no function) 12 (Latch release (all)) 13 (Latch release (DO1)) 14 (Latch release (DO2)) 15 (Latch release (DO3)) 16 (Latch release (DO4)) 17 (Latch release (DO5)) 18 (Start timer (DO1)) 19 (Start timer (DO2)) 20 (Start timer (DO3)) 21 (Start timer (DO4)) 22 (Start timer (DO5)) 23 (SV No. + 1 (send)) 24 (PID No. + 1 (send)) 25 (no function) 26 (Ra
mp soak
pattern No. + 1 (send)) 27 (SV No. + 1, PID No. + 1 (send))
2
Parameter display symbol
Parameter name
Function
Setting range
Initial value
Remarks
ALM display/ output
Ao outpu t
PV/SV displa y
0 OFF ON ON
1ON ON ON 2 OFF OFF ON
3ON OFF ON 4 OFF ON OFF
5ON ON OFF 6 OFF OFF OFF
7ON OFF OFF
RST
RST
– 9 –
6-8
Alarm (Ch8)
Sets the detect conditions for each type of alarm.
6-9
Communication (Ch9)
Sets the communication conditions towards the host computer.
6-10
PFB (Ch10)
Changes settings to use valve control.
"
di1
" (di1) DI-1 function
selection
Sets the function of DI-1
0 (No function) 1 (Switchover between STBY ON/OFF) 2 (Switch
over
between Auto/Manual) 3 (Switchover between Local/Remote) 4 (No function) 5 (No function) 6 (Start AT (standard)) 7 (Start AT (low PV)) 8 (No function) 9 (No function) 10 (Ramp SV ON/OFF) 11 (Ramp SV HOLD) 12 (Ramp soak OFF) 13 (Ramp soak RUN/HOLD) 14 (No function) 15 (Latch release (all)) 16 (Latch release (DO1)) 17 (Latch release (DO2)) 18 (Latch release (DO3)) 19 (Latch release (DO4)) 20 (Latch release (DO5)) 21 (Start timer (DO1)) 22 (Start timer (DO2)) 23 (Start timer (DO3)) 24 (Start timer (DO4)) 25 (Start timer (DO5)) 26 (SV No. + 1) 27 (SV No. + 2) 28 (SV No. + 4) 29 (PID No. + 1) 30 (PID No. + 2) 31 (PID No. + 4) 32 (No function) 33 (No function) 34 (No function) 35 (SV No.+1, PID No.+1) 36 (SV No.+2, PID No.+2) 37 (SV No.+4, PID No.+4) 38 (Pattern No.+1) 39 (Pattern No.+2) 40 (Pattern No.+4) 41 (Soft start) 42 (Ramp soak RUN) 43 (Ramp soak HOLD) 44
(Ramp soak RUN at DO1 startup) 45 (Ramp soak RUN at DO2 startup) 46
(Ramp soak RUN at DO3 startup) 47
(Ramp soak RUN at DO4 startup) 48 (Ramp soak RUN at DO5 startup)
0
(Note11)
"
di5" (di5) DI-5 function
selection
Sets the function of DI-5
0 to 48 0
"
do1t" (do1T) Sets the DO1
output event type
Sets the function of DO1
0 to 102 0
"
doP1" (doP1) Sets DO1
option function
Assigns the four types of option functions in bit units
0000 to 1111 0000
(Note3)
"do5t" (do5T) Sets the DO5
output event type
Sets the function of DO5
0 to 102 0
"
doP5" (doP5) Sets DO5
option function
Assigns the four types of option functions in bit units
0000 to 1111 0000
"
rmP" (rMP) ramp SV
ON/OFF
Sets the ramp SV ON/OFF
oFF (ramp SV OFF) on (ramp SV ON)
on
"
rmPL" (rMPL) Ramp SV-
Decline
Sets the slope for a falling SV during ramp SV operations
0 to 100% FS 0°C
"rmPh" (rMPH) Ramp SV-
Incline
Sets the slope for a rising SV during ramp SV operations
0 to 100% FS 0°C
"rmPU" (rMPU) Ramp SV-
slope units of time
Sets the unit of time for the slope during ramp SV operations
hoUr (slope temperature/hour) Min (slope temperature/min)
hoUr
"Svt" (SvT) Ramp SV - SV
display mode selection
Displays the SV during ramp operations or the SV goal value on the SV display
rMP (SV during ramp) TrG (target SV)
rMP
"
[trL" (CTrL) Control
methods
Allows you to select the control method.
Pid (PID control) FUZY (Fuzzy PID control) SELF (Self-tuning control) Pid2 (PID2 control)
Pid
Sections 5-1 to 5-8 (Note19)
Parameter display symbol
Parameter name
Function Setting range
Initial value
Remarks
RST
bit0 : output latch function bit1 : error alarm function bit2 : non-excitation output
alarm function
bit3 : hold reset function
□□□□
RST
□□□□
bit0 : output latch function bit1 : error alarm function bit2 : non-excitation
output alarm function
bit3 : hold reset function
RST
"PrCS" (PrCS) Control target Allows you to
select the control target.
SRV1 (Servo control 1) SRV2 (Servo control 2) PFB (Position feedback control)
PFb/ Srv1 (with PFB/ without PFB)
(Note16)
"Stmd" (STMd) Start mode Sets the
operation mode when starting up
Auto (auto mode startup) Man (manual mode startup) Rem
(remote mode startup)
STby
(standby make startup)
AUTo
Parameter display symbol
Parameter name Function Setting range
Initial value
Remarks
"A1hY" (A1hy) ALM1 hysteresis Sets the hysteresis
for alarm output 1 ON/OFF
0 to 50% FS 1°C
(Note3)
"dLY1" (dLY1) ALM1 delay Sets the delay
before detecting alarm output 1
0 to 9999 [sec/min] 0(sec/
min)
"
dL1U" (dL1U) ALM1 delay time
units
Sets the delay time units for alarm output 1
sec (second) Min (minute)
sec
"
A5hY" (A5hy) ALM5 hysteresis Sets the hysteresis
for alarm output 3 ON/OFF
0 to 50% FS 1°C
"
dLY5" (dLY5) ALM5 delay Sets the delay
detecting for alarm output 3
0 to 9999 [sec/min]
0(sec/ min)
"
dL5U" (dL5U) ALM5 delay time
units
Sets the delay time units for alarm output 3
sec (second) Min (minute)
sec
"
hb1" (hb1) HB alarm set value
for CT
Sets the heater burnout alarm detection value for CT
0.0 to 50.0A 0.0A
(Note10) (Note13)
"hb1h" (hb1h) HB alarm
hysteresis for CT
Sets the heater burnout alarm ON/ OFF hysteresis for CT
0.0 to 50.0A 0,5A
(Note10) (Note13)
"hS1" Load short-circuit
alarm setting value for CT
Sets the heater load short-circuit alarm setting value for CT.
0.0 to 50.0A 0.0A
(Note10) (Note13)
"hS1h" Load short-circuit
alarm hysteresis for CT
Sets the heater load short-circuit alarm ON/OFF hysteresis for CT.
0.0 to 50.0A 0.5A
(Note10) (Note13)
"lbTm" (LbTM) Loop break
detection time
Sets the time before detecting a broken loop
0 to 9999 sec 0 sec
"
LbAb" (LbAb) Loop break
detection range (°C)
Sets the temperature range before detecting a broken loop
0 to 100% FS 10°C
Parameter display symbol
Parameter name
Function Setting range
Initial value
Remarks
"Stno" (Stno) ST No. setting Sets the station
number.
0 to 255 (0: unresponsive communication)
1
(Note17)
"CoM" (CoM) baud rate/parity
setting
Sets the baud rate and parity check
96od (9600 bps/odd) 96Ev (9600 bps/even) 96no (9600 bps/none) 19od (19200 bps/odd) 19Ev (19200 bps/even) 19no (19200 bps/none)
96od
(Note17)
"S[[" (SCC) Communication
permissions
Sets whether or not overwriting is possible from the master side (PC, etc.)
r (read only permission) rW (read and overwrite permission)
rW
(Note17)
Parameter display symbol
Parameter name Function Setting range
Initial value
Remarks
"PGAP" (PGAP)
PFB dead band Sets the PFB dead
band
0.0 to 100.0% 5%
(Note16)
"trvL" (TrvL) Valve stroke time Sets the full stroke
time for the valve
5 to 180 sec 30 sec
(Note16)
"[AL" (CAL) PFB input
adjustment command
Adjusts the zero/ span for PFB input
0 (none/forcibly termination) 1 (zero adjustment) 2 (span adjustment) 3 (automatic adjustment)
-
(Note8)
Parameter display symbol
Parameter name
Function Setting range
Initial value
Remarks
RST
RST
– 10 –
6-11
Password Setup (Ch11)
Sets the password. Passwords can be set at three levels.
6-12
Display (Ch12)
Sets the parameter mask function Optional parameters can be set not to display. For details on the parameter mask function, refer to the "Operation Manual".
Note 1: Displayed when the seventh digit of the model code is H, K, F, 2 or E, or the eleventh
digit is D.
Note 2: Displayed when the ninth digit of the model code is not 0, or the
eleventh digit is C. Note 3: Display changes according to the DO number and the selected alarm type. Note 4: Displayed when the fifth digit of the model code is not V or S and the sixth digit is A,
C, E or P. Note 5: “
SvL” and “Svh” must be set so that SvL < Svh.
When the setting values of “
SvL” and “Svh” are changed, check SV setting value 1
(“
Sv1 Ch3”) through SV setting value 7 (“Sv7 Ch3”).
Note 6: Set the same value as the one for the Normal/Reverse setting (“
rEv Ch2”).
Note 7: Displayed when the fifth digit of the model code is A or C. Note 8: Displayed when the fifth digit of the model code is V. Note 9: Displayed when the fifth digit of the model code is E or P. Note 10: Displayed when the seventh digit of the model code is G or J, or when the eleventh
digit is A.
Note 11: The number of parameters to be displayed varies depending on the number of DIs
that PXG has.
For more details on “41: DI soft start”, refer to the “Operation Manual”. Note 12: Displayed when the sixth digit of the model code is R or S. Note 13: The parameter uses this even if the terminal uses CT2 input. Note 14: Select the proper setup range for the output type. Note 15: Do not set 4 to 7. Note 16: Displayed when the fifth digit of the model code is V or S. Note 17: Displayed when the seventh digit of the model code is M, V, K, J, F or U. Note 18: Displayed when the sixth digit of the model code is E or P. Note 19: When the fifth digit of the model code is S or V, be sure to select PID control. Options
other than PID control cannot be used. Note 20: When changing the SV with the front key, do not change the “
Svn” parameter via
communication.Otherwise, the changed SV may not be stored correctly. Note 21: Do not change this parameter during the ramp soak operation.
Be sure to set “
PrG” = “oFF” before changing the parameter.
7 Functions
This controller has five types of temperature control functions and three types of valve control functions. Select according to type and use.
Temperature Control Functions
Valve Control Functions
7-1 ON/OFF (2-position) Control
Acts as an ON/OFF control when the PID parameter is set to "P" = 0.0 ("Pid Ch 2").
ON/OFF control switches the control output to ON (100%) or OFF (0%) according to the size rela­tionship of PV and SV.The output hysteresis can be set under the parameter "
hYS
" ("
Pid Ch 2
").
Reverse Operation (heat control)
Method used to control the electrical heating furnace."Set the hYS" to an appropriate value according to the control target.
Normal Operation (cooling control)
Method used to control the cooling machine.
7-2 PID Controls
PID controls run as long as the parameter is set to "P" 0.0 ("Pid Ch 2") and "CTrL" = PID ("SYS
CH 7
"). The PID controls calculate PID based on the set values for parameters "P", "i", "d", and
"
Ar", and output the calculated result (-3% to 103%).
Each parameter can be set either by manually tuning the values or by running auto-tuning (AT) to automatically set the values.
Setting PID Control
7-3 Fuzzy PID Control
Related to normal PID controls, fuzzy PID control acts with small overshoot. You will need to run auto-tuning to set the PID parameter when using fuzzy control.
Setting fuzzy PID control
Display Parameter name Function Setting range
Initial value
Remarks
"PAS1" (PAS1) Password1 setup Sets password 1. 0000 to FFFF 0000 "PAS2" (PAS2) Password2 setup Sets password 2. 0000 to FFFF 0000 "PAS3" (PAS3) Password3 setup Sets password 3. 0000 to FFFF 0000
Display Parameter name Function Setting range
Initial value
Remarks
"dP01" (dP01) Parameter mask of
each parameter
Sets the parameters to be displayed/not displayed.
0000 to FFFF
Value different depending on the model code
"dP30" (dP30) Parameter mask of
each parameter
Sets the parameters to be displayed/not displayed.
0000 to FFFF
Value different depending on the model code
Caution
The ramp soak function ( page 12), remote SV function ( page 15), and SV selection function ( page 16) cannot be combined.
ON/OFF (2-position) control
Turns the control output ON/OFF according to the size relationship of PV and SV Can build a control system out of simple elements such as SSR. Suitable when accuracy is not requested.
7-1
(page 10)
PID Controls PID calculation and controls proceed according to the
previously set PID parameters. PID parameters can be set manually or through auto­tuning (AT). It is the most basic control in this equipment.
7-2
(page 10)
Fuzzy PID Control PID control with function that reduces the amount of
overshoot during control. It is effective when you want to suppress overshoot when SV is changed, even if you may take a long time to reach the target value.
7-3
(page 10)
Self-tuning Control Automatically calculating PID control according to the
control target or SV change. It is effective when the control conditions change frequently.
7-4
(page 11)
PID2 Control In case which the power supply of the control target
goes ON OFF ON, this PID2 control can suppress the amount of overshoot during control target turns OFF ON.
7-5
(page 11)
Servo Control 1 (Servo 1)
Regulates the valve position according to [OPEN] and [CLOSE] of the contact output.
7-7
(page 11)
Servo Control 2 (Servo 2)
Regulates the valve position according to [OPEN] and [CLOSE] of the contact output.It can also display the valve ís degree of openness according to the position position signal from the valve. However, it cannot be used to calculate the control output.
7-7
(page 11)
Position Feedback (PFB Control)
Controls the valve according to a calculation performed on the opening signal.Regulates the valve position according to [OPEN] and [CLOSE] of the contact output. It can be used when there is an opening signal coming from the valve.
7-8
(page 12)
Parameter Set Value "P" 0.0 "rEv rv-­"hYS" arbitary (factory
setting: 1 °C)
Parameter Set Value "P" 0.0 "rEv no-­"hYS" arbitary (factory
setting: 1 °C)
Point
During ON/OFF control, the I and D settings do not affect control. The manual operation during ON/OFF control will become MV=100% when the key is pressed, and MV=0% when the key is pressed. If the hysteresis width is narrow, and PV and SV are nearly equal, the output may frequently switch ON and OFF. Note that it may affect the operation life of the contact output.
Refer to
For more details on auto-tuning, see "7-6 Auto-tuning" (page 11)
1
Display the system menu ("SYS Ch 7").
2
Display the control parameter ("CTrL") and choose PID controls ("Pid").
3
Press the key to set the value.
1
Display the system menu ("SYS [h 7").
2
Display the controller parameter ("[trL") and choose fuzzy ("FUZY").
3
Press the key to set the value.
Refer to
For more details on auto-tuning, see "7-6 Auto-tuning" (page 11)
PV
ON
OFF
control output
t
SV
process value
PV<SV
PV>SV
HYS
PV<SV
PV>SV
PV
ON
OFF
control output
t
SV
process value
HYS
– 11 –
7-4 Self-tuning Control
Self-tuning Control is a control which automatically calculate the value of PID, under the condi­tion that the control target or set value (SV) changes. Self-tuning is especially effective for situations when a high level of control is not needed, but auto-tuning cannot be run due to frequent changes in the control target conditions.
Conditions where self-tuning can be used
Self-tuning is used in the following situations:
When temperature rises when the power is turned on
When temperature rises when SV changes (or when the controller decides it is necessary)
When the controller decides it is necessary because the controls have become unstable
Conditions where self-tuning cannot be used
Self-tuning cannot be used in the following situations:
During control standby
During ON/OFF (2-position) control
During auto-tuning
During ramp soak progress
When there is error input
When set for dual output
When any of the P, I, D, Ar parameters are set to manual
During manual mode
During soft start progress
Conditions to halt self-tuning
Halt self-tuning in the following situations:
When there is a change in SV (This includes the case where SV changes because of the
ramp soak function, remote SV function, or ramp SV.)
When self-tuning has not finished after running for nine or more hours
Setting self-tuning
7-5 PID2 Control
In case which the power supply of the control target goes ON → OFF → ON, this PID2 control can suppress the amount of overshoot. This control introduces an algorithm to prevent the calculated PID result from becoming a mis­calculation, even when the control loop is open. You will need to run auto-tuning to set the Pid parameter when using Pid2 control.
Features of PID2 Control
Setting PID2 control
7-6 Auto-tuning
Run auto-tuning to set the PID parameter automatically.
Normal type Low PV type
Running auto-tuning
7-7 Valve Control (Servo Control 1 / Serve Control 2)
Valve controls adjust and control the valve position according to [OPEN] and [CLOSE] of the contact signal. Turn on the contact outputs in man ual mode, so that pressing the key means "OPEN", and pressing the key means "CLOSE" Servo control 1 and servo control 2 have the following differences.
Servo Control 1: No valve position display
Servo Control 2: Has valve position display
Neither control can be used to control the valve position itself.
Setting Servo Control 1 or Servo Control 2
Point
When a high level of control is required, choose PID control, fuzzy PID control, or PID2 control.
1
Turn on power of the controller and set the SV.
2
Display the system menu ("SYS [h 7").
3
Display the controller parameter ("[trL") and choose self-tuning ("SELF").
4
Press the key to set the value.
5
Turn off power of the controller.
6
Turn on power of the control target equipment and the controller. Turn on power of the control equipment first.
Self-tuning will begin.
Point
The equipment will not tune correctly if power of the controller is
turned on first.
To reset self-tuning, set the control method to PID ("PiD") once
before changing back to self-tuning.
1
Display the system menu ("SYS Ch 7").
2
Display the control parameter ("CTrL") and choose PID2 ("Pid2").
3
Press the key to set the value.
dead time
t
process value
tuning
SV
lag time
suppress overshoot
ON
OFF
control equipment power
t
SV
process value
control loop
close
close
open
PV
"At" set value Behavior Function "oFF" Stop/Finish Stops or finishes auto-tuning. "on" Normal type The standard auto-tuning for SV reference. Choose this
auto-tuning in most situations.
"
Lo"Low PV type Auto-tuning for SV-10% reference. Choose this when you
want to suppress the overshoot when tuning.
Point
Set the following parameters before running auto-tuning.
PV input type / PV input upper limit / PV input lower limit / Decimal
position / PV input filter in the setup channel menu ("
SET Ch 6")
OUT1 proportion cycle (OUT2 proportion cycle) in the PID channel
menu ("
Pid Ch 2").
1
Display the operation menu ("oPE [h 1").
2
Display auto-tuning ("At") and choose the tuning type.
Choose the standard type ("
on") or low PV type ("Lo") according to the control target.
3
Press the key to start auto-tuning.
A decimal point will blink at the bottom of the display during auto-tuning. When auto-tuning has successfully competed, blinking decimal point will turn off and overwrites the PID.
Point
PID parameter which is set after auto tuning has finished normally
will be maintained even when the power is turned off. However, the PID value will not be changed if the power is turned off during auto­tuning. In this case, rerun auto-tuning.
The equipment will use ON/OFF (2 position) control during auto-
tuning, so there may be a large change in PV according to the pro­cess. Do not use auto-tuning for processes that do not permit a large change in PV. Do not use auto-tuning for processes such as pressure control and flow control that have a fast response.
Auto-tuning is not behaving normally if it has not finished after four
or more hours have passed. In these cases, recheck parameters such as input/output wiring, control output behavior (normal/ reverse), and input sensor type.
Rerun auto-tuning if there is a large change in SV, a change in the
PV input type, or a change in the control target conditions that reduces the effectiveness of the controls.
You can run auto-tuning when the control type is set to "fuzzy" or "PID2".
You cannot run auto-tuning in manual mode.
When using the PID selection function, the auto-tuning result for
the selected PID group is stored.
Auto tuning is forcibly terminated when SV changes because of
the ramp soak function, remote SV function, or ramp SV.
1
Display the system menu ("SYS Ch 7").
2
Display the control parameter ("PrCS") and choose servo control 1 ("Srv1").
This chooses "Servo Control 1".
3
Press the key to set the value.
Point
Adjustments must be made to display the valve opening position.
"7-8 Position Feedback Control (PFB Control) (page 12)
An interlock function is built in.
Caution
Chattering may occur if the dead band ("PGAP") in the PFB menu ("PFB Ch10") is set too small.
PV
t
process value
AT start
AT calculating
PID control
SV
PV
t
process value
AT s tart
AT calculating
PID control
SV
SV-10%FS
Valve
OPEN contact output CLOSE contact output
Valve opening (servo 2/PFB)
set value input (temperature)
boiler
Valve motor (servo 1)
– 12 –
Setting the valve stroke time
The valve stroke time must be set to use servo control 1 or servo control 2.
7-8
Position Feedback Control (PFB Control)
PFB control uses the opening position signal from the valve in its MV output calculation for the controller, but is otherwise a similar function to "7-7 Valve Controls (Servo Control 1 / Servo Control 2)". Unlike the servo controls, which use estimated controls for the valve position, PFB controls allow detailed control.
Setting position feedback control
Adjusting the valve opening position
7-9
Manual Output
Allows the control output to be manually set at an arbitrary value.
Manual Mode Display A decimal point will light up at the bottom right of the display during manual mode. The same decimal point appears on the parameter setting display.
Switchover between Auto and Manual Modes can be changed by four methods: the front key (user key), DI function, communica­tion function, or the parameter "
MAn
" ("
oPE Ch 1
").
MV output flow diagram (MV output priority processing)
7-10
Ramp Soak Function
Automatically runs after setting the times for the SV changes. You can choose up to sixteen steps for the SV setting and seven types of ramp soak operation patterns.
Creating a ramp soak operation pattern
Set the following items to create a pattern.
The following steps will explain how to run the specified pattern 0 in SV-1 to SV-4.
Running ramp soak
The following steps explain how to run ramp soak.
Guaranty soak
This function guarantees the soak time. Only soak time within the specified range of tempera­ture for SV is counted towards soak time. As seen in the figure below, only the sum of the shaded areas is counted as soak time. The operation moves onto the next step when the total soak time equals the specified soak time.
1
Display the PFB menu ("
PFB [h10
").
2
Display the valve stroke time parameter ("
trvL
") and set the stroke time for the
valve in use.
3
Press the key to set the value.
Point
Auto valve adjustment sets valve stroke time automatically. For more details on the operation, refer to “7-8 Position Feedback Control (PFB Control)” (page 12).
1
Display the system menu ("
SYS Ch 7
").
2
Display the control parameter ("
PrCS
") and choose position feedback controls
("
PFb
").
3
Press the key to set the value.
1
Display the PFB menu ("
PFB Ch 10
").
2
Switch to manual control output and fully close the valve.
3
Display "1 (zero adjustment)" in the PFB input adjustment parameter ("
[aL
")
and press the key.
4
Press the key to enter the current input value as "zero".
5
Fully open the valve using manual control.
6
Display "2 (span adjustment)" in the PFB input adjustment parameter ("
[aL
").
7
Press the key to enter the current input value as "span".
Point
To automatically adjust the valve opening, set "
CAL
" to 3 in step 3 above. This setting will automatically open and close the valve to adjust it auto­matically.
Caution
To manually adjust the valve, carry out step 1 through step 7 as written above.
If the valve is not connected or connected incorrectly, it can still be adjusted, but will not achieve accurate results.
There is no open-circuit judgment function for the valve opening feed­back signal.
Caution
MV limit does not apply to the MV output during manual operation, FALT, or standby. (Take extra caution when MV performs flash protection during combus­tion control by using the overlimit function.)
MV
MV1
MV2
MV1 MV2
MV limit
PID calculation
output setting during FALT
Soft start limit
Specify standby MV output
manual MV output
parameter “MAN”
Dual calculation
OFF
ON
Caution
When using the system in the restore mode ("
ConT
") = continue ("
Con
") in
the ramp/soak menu ("
PrG Ch4
"), do not set the ramp/soak control com-
mand ("
PrG
") of the operation menu ("
oPE Ch1
") to hold ("
hLd
") during the
ramp period at the beginning of the pattern.
When PV start ("
PVST
") of the ramp/soak menu ("
PrG Ch4
") is on ("on"), set
the pattern parameter ("
PTn
") of ramp/soak ("
PrG Ch4
") to "
PTn
" = 0, 2, 6
(setting that starts with 1 seg ramp).
Do not set the Startup mode ("
STMd
") = standby mode ("
STbY
") of the sys-
tem menu ("
SYS Ch7
") and the restore mode ("
ConT
") = continue ("
Con
") of
the ramp/soak menu ("
PrG Ch4
") at the same time.
Pattern Sets which steps to use from the following seven types.
Steps 1 to 4 / Steps 5 to 8 / Steps 9 to 12 / Steps 13 to 16 / Steps 1 to 8 / Steps 9
to 16 / Steps 1 to 16 Target SV Sets the controlled temperature. Ramp time Sets the time to reach the target SV from the current SV. Soak time Sets the time to maintain the specified SV.
1
Display the ramp soak menu ("
PrG [h4
").
2
Display pattern parameter ("
PTn
") and choose pattern 0 ("0").
Run SV-1 through SV-4.
3
Display the time parameter ("
timU
") and choose minute:second ("
MM.SS
").
Sets the units of time.Besides minute:second ("
MM.SS
"), you can also choose
hour:minute ("
hh.MM
").
4
Display the target value ("
Sv-1
") and set the target temperature.
5
Display the ramp time parameter ("
tm1r
") and set the ramp time.
6
Display the soak time parameter ("
tm1r
") and set the soak time.
7
Repeat steps 4 through 7 and set the remaining parameters.
1
Display the operation menu ("
oPe [h 1
").
2
Display program parameter ("
PrG
") and choose RUN ("
rUn
").
3
Ramp soak starts running from the current PV.
Point
To interrupt the ramp soak operation, choose HOLD ("hLD") in step 2. To
cancel the interruption, choose RUN ("rUn") again.
"End" will display when ramp soak has completed.
SV-1
SV-2
SV-3
SV-4
SV-5
SV-7
SV-8
time
TM1r
PV
TM1s
TM5r
TM5s
TM16r
TM16s
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
step1 to 4: pattern0
SV-9
SV-10
SV-12
SV-13
SV-14
SV-15
SV-16
SV-11
SV-6
• • • •
step5 to 8: pattern1
step9 to 12: pattern3
step13 to 16: pattern4
step1 to 8: pattern2
step9 to 12: pattern5
step1 to 16: pattern6
SV
step1
step2
step3
PV
SV
process value
soak time=T1+T2+T3
guaranty soak range upper limit
guaranty soak range lower limit
t
T3T2T1
– 13 –
The following steps will explain how to set an example guaranty soak range with an upper limit of 5°C and a lower limit of 3°C.
Mode setting
Sets how you want to run ramp soak.
The following items can be set.
You can choose from the following 16 types of modes according to the combination of run method options.
Delay start
Ramp soak can be automatically started (RUN) after a certain period of time has elapsed since the power of the controller is turned on. This function is enabled by setting the digital input function (DI n) and the digital output function (DonT), and setting the delay time to set dLYn.
The following steps will explain how to assign the delay start to DI 1, Do1 and to set the delay time to five minutes.
PV start
When the ramp soak starts (RUN), this function searches the first point where the measure­ment value (PV) and the program pattern match, and starts operation at that pooint.
If the measurement value does not match the pattern as with PV=, the normal operation starts.
7-11
Digital Input Function
Each of the digital inputs (DI1 to DI5) can be assigned the following functions. The specified function will run when an external DI signal enters the input.
1
Display the ramp soak menu ("PrG [h4").
2
Display guaranty ON/OFF parameter ("GSoK") and choose on ("on").
3
Display the guaranty soak lower limit parameter ("GS-L") and set the lower limit (in this example, set it to 3°C).
4
Display the guaranty soak upper limit parameter ("GS-h") and set the upper limit (in this example, set it to 5°C).
5
Press the key to set the value.
Power On Start Ramp soak starts running from the current PV. Ending Output Shows the ending output after ramp soak has been completed. OFF Output Shows the output during OFF after ramp soak has been completed. Repeat Behavior
After finishing the last step in ramp soak, the process starts again from 1st step.
Setting
Power On Start Ending Output OFF Output Repeat Behavior “0 Off Continuous control Continuous control Off “1 Off Continuous control Continuous control On “2 Off Continuous control Standby Off “3 Off Continuous control Standby On “4 Off Standby Continuous control Off “5 Off Standby Continuous control On “6 Off Standby Standby Off “7 Off Standby Standby On “8”On Continuous control Continuous control Off “9”On Continuous control Continuous control On “10”On Continuous control Standby Off “11”On Continuous control Standby On “12”On Standby Continuous control Off “13”On Standby Continuous control On “14”On Standby Standby Off “15”On Standby Standby On
1
Display the system menu (Sys Ch7).
2
Display the Di1 function selection ("di1"), and set 44 ("44").
3
Display the DO1 output event type setting ("do1T"), and set 35 ("35").
4
Display the Alarm menu (ALM Ch8).
5
Display the ALM1 delay time ("dLY1"), and set 5 ("5").
6
Display the ALM1 delay time unit ("dL1U"), and set the minute ("Min").
PV
SV-1
SV-2
SV-3
SV-4
1st ramp
power on start
repeats
TM1r
TM1S TM2r TM2S TM3r TM3S TM4r TM4S
2nd ramp
4th ramp
3rd ramp
2nd soak
3rd soak
4th soak
1st soak
DLYn
TM1S
TM1r
TM2S
TM2r
TM3r
TM3S
TM4r
TM4S
1st ramp
SV-1
2nd ramp
3rd ramp
4th ramp
SV-2
SV-3
SV-4
Dis play
Function Name Behavior ON OFF
Jud gment conditio n
" 0
" No function Nothing happen
"
1
"
Switchover between standby ON/OFF
Switches between standby on and off
Standby
Standby Cancel
Edge
"
2
"
Switchover between auto/manual
Switches between auto and manual control output
Manual
Auto Edge
"
3
"
Switchover between local/remote
Switches between local and remote SV
Remote
Local Edge
"4" No function Do not set
–––
"5" No function Do not set "6"
Auto-tuning (standard) Start
Starts standard auto-tuning Start Finish Edge
"7"
Auto-tuning (low PV) Start
Starts low PV auto-tuning Start Finish Edge
"8" No function Do not set
–––
"9" No function Do not set "10" Ramp SV on/off. Enables or disables ramp SV.
Disable Enable
Edge
"11" Ramp SV HOLD
Switches between ramp SV HOLD and HOLD cancel
HOLD
HOLD cancel
Edge
"12"
Ramp Soak OFF
Tur ns ramp soap off OFF Edge
"13"
Ramp Soak RUN/ HOLD
Switches between RUN and HOLD. RUN HOLD Edge "14" No function Do not set – "15" Latch release (all)
Cancels all of the sources currently acting as
latches.
––Edge
"16"
Latch release (DO1)
Cancels the source currently acting as a latch on
DO1.
Cancel
Edge
"17"
Latch release (DO2)
Cancels the source currently acting as a latch on
DO2. "18"
Latch release (DO3)
Cancels the source currently acting as a latch on
DO3. "19"
Latch release (DO4)
Cancels the source currently acting as a latch on
DO4. "20"
Latch release (DO5)
Cancels the source currently acting as a latch on
DO5. "21" Start timer (DO1) Starts the specified timer for DO1.
Timer ONTimer
OFF
Level
"22" Start timer (DO2) Starts the specified timer for DO2. "23" Start timer (DO3) Starts the specified timer for DO3. "24" Start timer (DO4) Starts the specified timer for DO4. "25" Start timer (DO5) Starts the specified timer for DO5. "26" SV No. + 1 When selecting SV No., increases the SV No. by 1. +1 Level "27" SV No. + 2 When selecting SV No., increases the SV No. by 2. +2 Level "28" SV No. + 4 When selecting SV No., increases the SV No. by 4. +4 Level
"29" PID No. + 1
When selecting PID No., increases the PID No. by
1.
+1 Level
"30" PID No. + 2
When selecting PID No., increases the PID No. by
2.
+2 Level
"31" PID No. + 4
When selecting PID No., increases the PID No. by
4.
+4 Level
"32" No function Do not set
–––"33" No function Do not set
"34" No function Do not set "35"
SV No.+1, PID No.+1
When selecting SV No. and PID No., increases the
SV No. and PID No. by 1.
+1 Level
"36"
SV No.+2, PID No.+2
When selecting SV No. and PID No., increases the
SV No. and PID No. by 2.
+2 Level
"37"
SV No.+4, PID No.+4
When selecting SV No. and PID No., increases the
SV No. and PID No. by 4.
+4 Level
"38"Pattern No.+1
When selecting pattern No., increases the Pattern
No. by +1
+1 - Level
"39"Pattern No.+2
When selecting pattern No., increases the Pattern
No. by +2
+2 - Level
"40"Pattern No.+4
When selecting pattern No., increases the Pattern
No. by +4
+4 - Level
"41" Soft start Starts the soft start
Soft start ON- Edge
"42" Ramp soak RUN Sets the ramp soak to RUN. RUN - Edge "43" Ramp soak HOLD Sets the ramp soak to HOLD. HOLD - Edge
"44" Delay start(DO1) Enables delay start with the delay time = dLY1.
Delay start enable
-
"45" Delay start(DO2) Enables delay start with the delay time = dLY2.
Delay start enable
-
"46" Delay start(DO3) Enables delay start with the delay time = dLY3.
Delay start enable
-
Start of
PV=
PV=
PV=
Start of
Start of
SV
– 14 –
The following steps will explain an example of how to set DI1 to switchover between standby ON/OFF.
7-12
Digital Output
Each of DO1 to DO5 can be assigned the following functions (events). The functions are divided into two categories for when they behave as alarms and when they behave as events.
1. DO event settings
Events are divided into those related to alarms and those not related. For more about the events related to alarms, see "11. Alarm Action Type Codes" (page 18). Use the following steps events other than alarms.
Ramp soak delay start
Wire burnout circuit alarm
Conditional outputs
Use the following steps to set DO.
2. Setting DO option functions
Allows you to set not just even settings, but option functions for each DO. The DO events are set by each digit.
3. Setting the alarm menu
Hysteresis Function
The hysteresis band is preserved during alarm output.
Delay Function
When events (including alarms) occur, the DO does not begin outputting immediately. Instead, the event continues for a specified period of time before outputting DO.
"47" Delay start(DO4) Enables delay start with the delay time = dLY4.
Delay start enable
-
"48" Delay start(DO5) Enables delay start with the delay time = dLY5.
Delay start enable
-
1
Display the system menu ("SYS [h 7").
2
Display the DI1 parameter ("di1") and choose 1 ("1").
This chooses to switchover between standby ON and OFF.
3
Press the key to set the value.
Caution
When “Switchover between local and remote” (DI setting v alue =3) is used f or the digital input function, the operation before turning off the power of the main unit affects the DI operation when the power turns on again.
(For the DI operation when the power turns on under each state, see the table below.)
No .
Operation before turning off power of the main unit
DI status while the power of the main unit is on
DI behavior while the power of the main unit is on
Operation
Operation status
1 DI On when rEM parameter = LoCL
Remote SV operation
DI On
Remote SV operation
DI Off
Local SV operation
2 Switches to rEM parameter = rEM by
key operation
DI On
Remote SV operation
DI Off
Remote SV operation
3 Switches desired parameter setting
value via communication during rEM parameter = rEM
DI On
Remote SV operation
DI Off
Remote SV operation
4 DI Off when rEM parameter = rEM
Local SV operation
DI On
Remote SV operation
DI Off
Remote SV operation
5 Switches to rEM parameter = LoCL by
key operation
DI On
Remote SV operation
DI Off
Local SV operation
6 Switches desired parameter setting
value via communication during rEM parameter = LoCL
DI On
Remote SV operation
DI Off
Local SV operation
Type
Setting (DO1 to DO3)
Function
Ramp soak delay start 35 Delay start enable
Type
Setting (DO1 to DO5)
Function
Wire burnout circuit alarm 41 Loop break alarm 1
44 Heater burnout alarm 1
Wire break/short circuit alarm
47 Load short-circuit alarm
Dis play
Function Name Behavior ON OFF
J udgmen t conditio n
Settings complete
Using them as alarms (1 to 31) Using them as events (35 to 102)
or timers (32 to 34)
1. Setting the System Menu
2. Setting the Alarm Menu 3. Setting the alarm menu (page 14)
Delay
Hysteresis
Settings complete
1. Set events for DO1 to DO5 1. DO event settings (page 14)
2. Set DO options 2. Setting DO option functions (page 14)
Latch function
Input error
Non-excitation output
Hold reset
3. Setting the Operation Menu 4. Setting the operation menu (page 15)
Alarm set value
Type
Setting (DO1 to DO5) Function
Conditional outputs 51 During auto-tuning
52 Normal 53 During standby 54 During manual mode 55 During remote SV operation 56 During ramp SV
Ramp soak Event Output 60 OFF state
61 RUN state 62 HOLD state 63 GS (Guaranty Soak) State 65 END state
Time Signal 71 Time signal (1st segment)
72 Time signal (2nd segment) 73 Time signal (3rd segment) 74 Time signal (4th segment) 75 Time signal (5th segment) 76 Time signal (6th segment) 77 Time signal (7th segment) 78 Time signal (8th segment) 79 Time signal (9th segment) 80 Time signal (10th segment) 81 Time signal (11th segment) 82 Time signal (12th segment) 83 Time signal (13th segment) 84 Time signal (14th segment) 85 Time signal (15th segment) 86 Time signal (16th segment) 87 Time signal (17th segment) 88 Time signal (18th segment) 89 Time signal (19th segment) 90 Time signal (20th segment) 91 Time signal (21st segment) 92 Time signal (22nd segment) 93 Time signal (23rd segment) 94 Time signal (24th segment) 95 Time signal (25th segment) 96 Time signal (26th segment) 97 Time signal (27th segment) 98 Time signal (28th segment) 99 Time signal (29th segment) 100 Time signal (30th segment) 101 Time signal (31st segment) 102 Time signal (32nd segment)
1
Display the system menu ("
SYS Ch 7
").
2
Set the event you want to specify under the DO1 output event setting type ("
do1T
").
3
Set the option function under the DO1 option function parameter ("
doP1
").
For the contents of this setting, see "2. Setting DO option functions" below.
4
Set DO2 to DO5 as necessary.
5
Press the key to set the value.
bit
Function Description bit0 Event output latch function Latches (maintains) the DO when the event starts bit1 Error alarm function Outputs when the unit receives an input error
(“
UUUU
” or “
LLLL
” is displayed).
Set DO event to “0” when using this function.
bit2 Non-excitation output alarm
function
Reverses the output signal and outputs it through the DO terminal when the event starts
bit3 Hold reset function When using an alarm with hold, the hold function
will reset when any of the following operations occur: SV change / Alarm type change / Alarm set value change /Standby cancel / Power reset
bit0 (1 : ON, 0 : OFF)
bit1 (1 : ON, 0 : OFF) bit2 (1 : ON, 0 : OFF) bit3 (1 : ON, 0 : OFF)
– 15 –
This is called a delay function because there is a delay between the event and outputting to DO.
Use the following steps to set an alarm delay and hysteresis.
4. Setting the operation menu
Sets the alarm value so that DO is used as the alarm output. Use the following steps to set this function.
7-13
Communication Functions
Set the following to communicate with the host.
Setting communication functions
7-14
Re-transmission Output Function
The re-transmission output function delivers an analog output signal from the controller. The following values can be output: PV, SV, MV, DV (PV-SV), PFB Depending on the type of output, you can choose the voltage type or current type. The re-transmission output also contains a scaling function. The following example shows a re-transmission output of 100% when PV=960°C (80% FS) and a re-transmission output of 0% when PV=240°C (0% FS) for a PV range of 0 to 1200°C.
Setting re-transmission output function
7-15
Remote SV Function
The remote SV function controls the analog input signal coming into the controller as SV. The input terminal becomes RSV1 or RSV2. The remote SV function contains a zero/span adjustment function, as well as an input filter function. The setup menu ("
SET [h 6
") must be set in the following manner before using the remote SV
function.
Switching to remote SV operation
7-16
Heater Break Alarm Functions
The heater wiring passes through the CT, allowing the current value to be monitored and detect errors in the heater line. Heater break are detected by drops in the heater current. Setting the detection values acti­vates this function.
Related parameters: “
hb1
”, “
hb1h
” (“
ALM Ch 8
”), “
Ct1
”,“
LC1
” (“
Mon Ch 5
”)
7-17
Loop Break Alarm
Detects when the control loop is open (break) without using the CT, but instead observing the control output and PV.
Related parameters: “
LbTM
”, “
TbAb
” (“
ALM Ch8
”)
7-18
Load Short-circuit Alarm
The heater wiring passes through the CT, allowing the current value to be monitored and detect errors in the heater line. The load short-circuit is detected by drops in the heater current. Setting the detection values activates this function.
Related parameters: "
hS1
", "
hS1h
" ("
ALM Ch8
")
7-19
Other Functions
1. Soft start function
When turning on the equipment (including the temperature controller), the soft start function suppresses the MV to become maximum output. It places an upper limit on MV output for a specified amount of time after power is turned on. This function is useful for effects such as suppressing the heater output during equipment star­tup, and makes load lightened. After the specified time has passed after switching on the equipment (or if SFTM = 0), the soft start function ends and normal controls begin.
1
Display the alarm menu ("
ALM Ch 8
").
2
Display hysteresis 1 ("
A1hY") and set the hysteresis.
3
Display delay time 1 ("dLY1") and set the delay.
4
Display delay time units 1 ("dL1U") and set the units to minutes or seconds.
5
Set the values for alarm 2 to alarm 5 as necessary.
6
Press the key to set the value.
1
Display the operation menu ("oPE Ch1").
2
Set the alarm 1 set value ("AL1") or "AL1L" and "AL1H".
The parameters displayed will vary according to the type of alarm.
3
Set up to alarm 5 as necessary.
4
Press the key to set the value.
Display Parameter Function "STno" ST No. setting Sets the station number. "[oM"Parity/baud rate setting Choose the configuration of parity and baud rate "S[[" Setting communication
permissions
Set whether or not the host has permission to overwrite.
1
Display the communication menu ("[oM [h 9").
2
Display ST No. setting parameter ("Stno") and choose 1, and then display Par- ity/baud rate setting parameter (“
CoM”) and choose 9600 bps, even ("96ev").
This sets the baud rate to 9600 bps and the parity to "even".
3
Display communication permissions ("S[[") and choose to allow read and over­write permissions ("
rw").
This sets the host to be allowed to read and overwrite the controller.
4
Press the key to set the value.
5
Turn the controller off and on again.
Caution
The communication function settings will not be active until the power for the controller is turned OFF/ON.
ON
OFF
ON
OFF
ON
OFF
ON delay set time
alarm
normal alarm relay
relay with ON delay
cancel
no relay output (alarm during delay is invalid)
(Ex.) Alarm On Delay
Function
20% (AoL)
re-transmission output
calculation value
actual re-transmission output
100°C
0%
80% (AoH)
upper/lower limit
scaling range
100%
0%
1
Display the setup menu ("SET [h 6").
2
Display the AO output function parameter ("Aot") and choose the PV.
This selects PV as the re-transmission output.
3
Display AO lower limit scaling ("AoL") and set the lower limit scaling (in this example, set it to 20%).
4
Display AO upper limit scaling ("AoH") and set the upper limit scaling (in this example, set it to 80%).
5
Press the key to set the value.
Display Parameter Function "rEMO" (rEMO) RSV Zero adjustment Adjusts the zero of the RSV input "rEMS" (rEMS) RSV Span adjustment Adjusts the span of the RSV input "rEMr" (rEMr) RSV input range Sets the range for RSV input "rTF" (rTF) RSV input filter Sets the time constant for the RSV input filter
1
Display the operation menu ("oPE [h 1").
2
Display the switching to remote SV parameter ("rEm") and choose remote ("
rEM").
3
Press the key to set the value.
Caution
Soft start is not displayed during the remote SV operation.
Do not use remote SV and the SV selection function at the same time.
Refer to
For details on the heater break alarm, refer to the "Operation Manual".
Refer to
For details on the loop break alarm, refer to the "Operation Manual".
Refer to
For more details on the load short-circuit alarm, refer to the "Operation Manual"..
PV
PID
calculation
local SV
remote SV
(DC0 to 5/1 to 5V)
control output
Switch to remote SV parameter rEM
– 16 –
Use the following steps to set soft start output set value and set time.
2. Error output function
When the error output specification function has concluded that the equipment has an error, it halts the temperature controls and maintains the control output at a previously specified value. There is an error in PV if any of the following conditions occur: burnout upper limit / burnout lower limit / underage (PV< -5% FS) / overage (105% <PV)
Use the following steps to set this function.
3. Standby output function
Sets the control output value, alarm output, re-transmission output (ON/OFF), and PV/SV dis­play for standby mode.
Use the following steps to set this function.
4. Ramp SV function
The ramp SV function suppresses a sudden change in SV (step change) when changing SV.It allows SV to change smoothly according to the set slope of temperature per unit of time.This smooth SV change allows you to minimize the effect of the change on controls. You can set both inclining temperature and declining temperature slopes, and choose from "minutes" or "hours" for the time units. You can also choose for the SV display to show the current value or the target value during ramp SV.
The SV lamp will blink while ramp SV is running.(When not displaying parameters or Ch.)
When you turn on the power while ramp SV is in effect, ramp SV will begin using the starting value of PV (PV start).
Use the following steps to set ramp SV.
5. SV selection function
The SV selection function can record and switch up to eight sets of SV infor mation to the pal­ette menu settings. It is effective when the SV used during a process are numerous and the set values have been previously decided.
Use the following steps to save SV information.
The following four methods can switch SV.
parameter “SvN” / press the user key / DI function / overwrite parameter “SvN” via the
communication function
Switch Using Parameter "Svn"
Switch Using the User Key
Switch Using DI Function
Switch Using Parameter “Svn” via the Communication Function
Display Parameter Function "SFo1" (SFo1) MV1 soft start
output set value
Places a limit on MV1 output after power is turned on for a time period set in SFTM.
"
SFTM" (SFTM) Soft start set time Sets the time for soft start to function after turning power
on. Setting "0" will turn off soft start.
Caution
The soft start function cannot be used simultaneously with the valve control functions, and cannot be used simultaneously with the dual control.
Point
During manual mode, the manual output value has priority, but soft start will continue to keep track of the set time period.
1
Display the setup menu ("SET [h 6").
2
Display soft start output 1 ("SFo1") and set the output value.
3
Display soft start set time ("SFTM") and set the time.
4
Press the key to set the value.
5
Turn off the power once, and then re-start the controller to begin soft start. (When the soft start function is turned on, the lo wer display will alternate show­ing SoFT and SV.)
Note: Do not use auto-tuning at the same time.
1
Display the setup menu ("SET [h 6").
2
Display FALT output 1 set value ("FLo1") and set the output value.
For dual control, set "
FLo2" the same way.
3
Press the key to set the value.
1
Display the setup menu ("SEt [h 6").
2
Display the standby mode setting ("Sbmd") and set the alarm output, re-trans­mission output, and PV/SV display for standby mode.
Refer to
For the possible ON/OFF combinations for each output, see "6-6 Setup (Ch 6)" (page 8).
3
Display the standby control output 1 set value ("Sbo1") and set the output value. For dual control, set "
Sbo2" the same way.
4
Press the key to set the value.
t
control output (MV)
soft start set time
soft start output set value
MV when not using soft start
MV when using soft start (limited)
power on
0
t
SV during ramp SV behavior (rMPL/rMPH)
SV
changing SV with the front key
set value after change
set value before change
1
Display the system menu ("SYS Ch 7").
2
Set both ramp SV decline ("rMPL") and incline ("rMPH").
3
Set the unit of time for the slope ("rMPU") during ramp SV.
4
Press the key to set the value.
Point
Ramp SV can be used with remote SV or SV selection functions.
Ramp SV cannot be used at the same time with ramp soak.
Coming out of a standby state will begin PV start.
Make sure to check the controller’s parameters after changing PV
scale.
Caution
If the power is turned on during the input error, or released standby, the ramp SV operates differently from the normal PV start.
1
Display the palette menu ("PLt [h 3").
2
Display SV setting 1 ("SV1") and set SV1.
3
Set SV setting 2 through SV setting 7 in the same way as necessary.
4
Press the key to set the value.
1
Display the operation menu ("oPE [h 1").
2
Display the selected SV number ("Svn") and choose the SV No.
3
Press the key to set the value.
1
Display the palette menu ("PLT Ch 3").
2
Display max selected SV number ("SvMX") and set the SV number by choosing it with the user key.
3
Display the user key function setting ("UKEy") and set it to SV selection function.
4
On the PV/SV display, pressing the user key will switch you from the currently selected SV to the next SV.
1
Display the operation menu ("oPE Ch 1").
2
Display the selected SV number ("Svn") and choose "di".
3
Display the DI function setting ("di1" to "di5") and set the SV selection function.
1
In the communication, overwrite the set value to the selected SV number ("
Svn").
t
PV
power ON
SV
SV
behavior when power rises
t
Sv switches to Sv-1 with DI input
SV
SV
Sv
Sv-1
behavior when SV changes with DI
State at PV start Operation Standby PV tracking (Maintains the state where SV=PV. The SV ramp
function does not operate.)
Auto or manual Starts the ramp SV from the current SV (PV start is off)
– 17 –
6. PID selection function
The SV selection function can record and switch up to eight sets of PID parameters from the palette menu settings. It is effective when the control equipment changes the target often and must frequently change the PID parameters. Use the following steps to save PID information.
The PID parameter selection (P, i, d, normal and reverse settings) can be changed by the same four methods as the SV selection function.
Switch Using Parameter
"
PLn1
"
Switch Using the User Key
Switch Using DI Function
Switch Using Parameter "
PLn1
" via the Communication Channel
7. Startup mode function
The startup mode specification function sets the controller to start up in either auto mode , manual mode , remote mode or standby mode. It is used when you want to start up in manual mode.
Use the following steps to set this function.
8. User function key
Pressing the key in the monitor screen display, channel screen display, or parameter screen display will immediately return you to the PV/SV display, regardless of assigned function.
Holding the key down for about a second in PV/SV display or PV/MV display (only during manual mode) will run the assigned function.The standard factory default for the key is switchover between auto and manual modes.
Use the following steps to set this function.
9. bAL and Ar functions
The anti-reset windup function ("
Ar
") cuts integration that falls outside of the Ar set range that is centered around SV. Running auto-tuning will set the optimum values for P, i, and d parameters, as well as Ar.
The output convergence value function ("
bAL
") outputs to PV and SV a calculated result of the PID computed MV plus the bAL offset. (The factory setting of bAL is 0% for single output, 50% for dual output.)
10. MV limit function
The MV limit function allows you to choose whether to limit the MV or let it pass through maxi­mum and minimum MV.
8
Setting the Temperature Controller
8-1
Input Setting
Set the type and the range for input sensor. Input can be set in the setup menu ("
SET [h6
"). For more on input types, input scaling, decimal point location, and input codes, see "10 Input Range and Codes (standard renge)". (page 18)
Point
When switching the normal and reverse operation by using the PID selec­tion function, be sure to turn off the system power beforehand for safety reasons (Do not switch normal and reverse operation during control).
1
Display the palette menu ("
PLT Ch 3
").
2
Display proportional bandwidth setting 1 ("
P1
") and set P1.
3
Set "i1" and "d1" in the same way.
Set the following parameters as necessary: ON/OFF control hysteresis ("
hyS1
"), cool-
ing proportional band ("
CoL1
"), dead band ("
db1
"), balance ("
bAL1
"), anti-reset windup
("
Ar1
"), and normal/reverse setting ("
rEv1
").
4
Press the key to set the value.
1
Display the operation menu ("
oPE Ch1
").
2
Display the selected PID number ("
PLn1
") and choose the PID No.
3
Press the key to set the value.
1
Display the palette menu ("
PLT Ch 3
").
2
Display max selected PID number ("
PL1M
") and set the PID number by choosing
it with the user key.
3
Display the user key function setting ("
UKEy
") and set it to PID selection
function.
4
On the PV/SV display, pressing the user key will switch you from the currently selected PID to the next PID.
Point
When the user key function code is 27 (SV No.+1, PID No.+1 (send)) and the initial PID No. and SV No. are different, the first time you press the user key, PID No. will become the same as SV No. Also the SVMX parameter value becomes the maximum selectable number for PID No. and SV No.
1
Display the operation menu ("
oPE Ch 1
").
2
Display the selected PID number ("
PLn1
") and choose "di".
3
Display the DI function setting ("
di1
" to "
di5
") and set the PID selection
function.
1
In the communication, overwrite the set value for the selected PID number ("
PLn1
").
1
Display the system menu ("
SYS [h 7
").
2
Display the startup mode ("
Stmd
") and choose the operational mode.
Choose from auto or manual.
3
Press the key to set the value.
After changing the above setting, restarting the controller will start it in the selected mode.
Point
When starting up in manual, the MV becomes 0%.
Refer to
For functions that can be assigned, see "6-7 System (Ch7)" (page 8).
1
Display the system menu ("
SYS [h 7
").
2
Display the assign user key specification ("
UtEy
") and choose the function.
3
Press the key to set the value.
Point
Ar1 to Ar7 and bAL1 to bAL7 have the same function as in each PID group.
Point
PV scaling and decimal point location can be used with the factory settings.
PV
SV
}
}
}
cuts integration
includes integration
cuts integration
PV
AR value AR value
proportional bandwidth
MV
bAL=40%
50%
PV
SV
40%
bAL=0
100%
PHC
PLC
103%
output value (before limit)
PHC
PLC
limit
pass
limit
pass
—3%
output value (after limit)
PCUT
MV1 MV2
PHC1 PLC1 PHC2 PLC2
"0" "1" "2" "3"
103% 103% limit limit
-3% limit
-3% limit
103% 103% 103% 103%
-3%
-3%
-3%
-3%
"4" "5" "6" "7"
103% 103% limit limit
-3% limit
-3% limit
103% 103% 103% 103%
limit limit limit limit
"8" "9" "10" "11"
103% 103% limit limit
-3% limit
-3% limit
limit limit limit limit
-3%
-3%
-3%
-3%
"12" "13" "14" "15"
103% 103% limit limit
-3% limit
-3% limit
limit limit limit limit
limit limit limit limit
1. Choose an input type ("PVt")
Check the type of the thermocouple or resistance bulb which is used.
2. Set the PV scaling (input range) ("PVb"/"PvF")
Set Pvb to the lower limit of the temperature range and PvF to the upper limit. It is recom­mended to set the values at the standard range, even though they can be set at values beyond of it. There is no standard range for DC voltage or DC current input. (-1999 to 9999, lower limit<upper limit)
3. Set the decimal point location ("Pvd")
Sets whether or not to display digits after the decimal point. Two digits can also be dis­played after the decimal point when using 1 to 5V DC, and 4 to 20mA DC.
– 18 –
8-2
Output Setting
Sets the control output. (Only when the output is current or voltage.)
8-3
Controls Setting
Sets controls to normal operation or reverse operation.
Reverse operation: As the process value (PV) rises, the control output (MV) becomes smaller. Used to heat the control object.
Normal operation: As the process value (PV) rises, the control output (MV) becomes larger. Used to cool the control object.
9
Error Indications
9-1
Display During Equipment Error
This controller has a display function to indicate several types of error code shown below. If any of the error code is displayed, please eliminate the cause of error immediately. After the cause is eliminated, turn off the power once, and then re-start the controller.
Note : The error display does not appear even when it must appear depending on the setting
of parameter SbMd (“
SET Ch6
”).
10
Input Range and Codes (standard range)
Note 1 : For DC current input, attach a 250Ω resistance to convert the range to 1 to 5V or 0 to
5V DC.
Note 2 : Input accuracy is ±0.3% FS ± 1 digit ± 1°C or 2°C whichever greater.
Except, B thermocouple 0 to 400°C: ±5% FS ± 1 digit ± 1°C
R thermocouple 0 to 500°C: ±1% FS ± 1 digit ± 1°C T thermocouple -200 to -150°C: ±0.5% FS ± 1 digit ± 1°C
Note 3 : Input accuracy cannot be ensured when using an input smaller than the minimum
range.
11
Alarm Action Type Codes
Display
Possible cause Control output
"
UUUU
"
q
Thermocouple burnout.
w
Resistance bulb sensor (A) burnout.
e
PV exceeds upper limit of the range by 5%FS.
Output as setting value when an error occurs (set in parameter Flo1 or Flo2)
"
LLLL
"
q
Resistance bulb sensor B or C wire burnout.
w
Resistance bulb sensor (between A & B or A & C) short.
e
PV is below lower limit of the range by 5%FS.
r
Burnout or short in the voltage input.
"
LLLL
"
q
PV < -199.9
"
Err
"
(SV flickers)
Incorrect setting (Pvb/PvF)
PV is not displayed
q
H’4000 is added into the dP30 set value
w
SbMd set value is set at 4 to 7, and STbY is ON
Normal control * The controller does not
have to be restarted
SV is not displayed
q
H’2000 is added into the dP30 set value
w
SbMd set value is set at 4 to 7, and STbY is ON
Normal control * The controller does not
have to be restarted
Parameters may not be displayed
q
Check the settings of dP01 to dP30
w
Check the password function
Normal control * The controller does not
have to be restarted
Input type
Measurement range [°C]
Measurement range [°F]
Smallest input increment °C
Input code
Resistance bulb JIS (IEC)
Pt 100
0 to 150 32 to 302 0.1 "
1
" 0 to 300 32 to 572 0.1 0 to 500 32 to 932 0.1 0 to 600 32 to 1112 1
-50 to 100 -58 to 212 0.1
-100 to 200 -148 to 392 0.1
-150 to 600 -238 to 1112 1
-200 to 850 -328 to 1562 1
Thermocouple J 0 to 400 32 to 752 0.1 "2"
0 to 1000 32 to 1832 1
K0 to 400 32 to 752 0.1 "3"
0 to 800 32 to 1472 0.1 0 to 1200 32 to 2192 1
R0 to 1600 32 to 2912 1 "4" B0 to 1800 32 to 3272 1 "5" S0 to 1600 32 to 2912 1 "6" T -200 to 200 -328 to 392 0.1 "7"
-200 to 400 -328 to 752 0.1
E0 to 800 32 to 1472 0.1 "8"
-200 to 800 -328 to 1472 1
N0 to 1300 32 to 2372 1 "12" PL-
2
0 to 1300 32 to 2372 1 "13"
1. Sets the range of the control output (OUT1/OUT2) ("C1r"/"C2r")
Choose any of 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V, 0 to 20mA or 4 to 20mA DC.
1. Set the normal or reverse operation ("rEV") Choose any of the following combinations of heat and cool to suit your system.
rEv
Control output 1
Control
output 2 rv-- Reverse – no-- Normal – rvno Reverse Normal norv Normal Reverse rvrv Reverse Reverse nono Normal Normal
DC voltage 0 to 5V DC -1999 to 9999 (Range where scaling is allowed) "15"
1 to 5V DC "16" 0 to 10V DC "17" 2 to 10V DC "18" 0 to 100mV DC
"19"
DC current
0 to 20mA DC
"15"
4 to 20mA DC
"16"
Type DO1 to DO5 Alarm T ype Action diagram
0 No alarm
Absolute value alarm
1 High alarm
2Low alarm
3 High alarm (with hold)
4Low alarm (with hold)
Deviation alarm 5 High alarm
6Low alarm
7 High/Low alarm
8 High alarm (with hold)
9Low alarm (with hold)
10 High/Low alarm (with hold)
Zone alarm 11 High/Low deviation alarm
12 (Note1)
High/Low absolute alarm
13 (Note1)
High/Low deviation alarm
14 (Note1)
High absolute/Low deviation alarm
15 (Note1)
High deviation/Low absolute alarm
Input type
Measurement range [°C]
Measurement range [°F]
Smallest input increment °C
Input code
PV
t
ALn
PV
t
ALn
PV
t
ALn
PV
t
ALn
SV
PV
t
ALn
SV
PV
t
ALn
SV
PV
ALn
SV
PV
t
ALn
SV
PV
t
ALn
SV
PV
ALn
SV
PV
t
ALn
PV
t
AL1 AL2
SV
PV
t
AL1 AL2
SV
PV
t
AL2
AL1
SV
PV
AL2
AL1
– 19 –
Dual Set Value Alarm Codes
Timer Code
(Note1) Available only for DO2 * Other than the alarm setting, each of the event output functions can be assigned to
DO1 to 5. For more details on each of the event output functions, refer to “7-12. Digital output” - “1. DO event setting” (page 14).
12
Model Specifications
12-1
PXG5/9 Standard Model List
Note 1: For outer dimensions of 48 x 96, the transmitter power supply output cannot be specified.
(5 in the fourth digit and T in the sixth digit cannot be specified.)
Note 2: If output 1 was for current or voltage output, option cannot be assigned to CT1 nor CT2.
(If 7th digit was assigned to G or J, or 11th digit to A, 5th digit cannot be assigned to E nor P.)
Note 3: RSV1 in option 1 and RSV2 in option 2 cannot be assigned simultaneously.
(If 7th digit was assigned to H or K, 11th digit cannot be assigned to D.)
Note 4: In case, in option 1, of DI 2 points + RSV1 or RS485 + DI 1 + RSV1, output 2 cannot be
assigned. (If 7th digit was assigned to F or 2, 6th digit cannot be assigned to A, C, E, P, R nor S.)
Note 5: In case of CT1 in option 1, or CT2 in option 2, digit output cannot be assigned to None.
(If 7th digit was assigned to G or J, or 11th digit to A, 9th digit cannot be assigned to 0.)
Note 6: CT1 in option 1 and CT2 in option 2 cannot be assigned simultaneously.
(If 7th digit was assigned to G or J, 11th digit cannot be assigned to A.)
Type DO1 to DO5 Alarm T ype Action diagram High/Low limit
alarm
16 High/Low absolute alarm
17 High/Low deviation alarm
18 High absolute/Low
deviation alarm
19 High deviation/Low
absolute alarm
20 High/Low absolute alarm
(with hold)
21 High/Low deviation alarm
(with hold)
22 High absolute/Low
deviation alarm (with hold)
23 High deviation/Low
absolute alarm (with hold)
Zone alarm 24 High/Low absolute alarm
25 High/Low deviation alarm
26 High absolute/Low
deviation alarm
27 High deviation/Low
absolute alarm
28 High/Low absolute alarm
(with hold)
29 High/Low deviation alarm
(with hold)
30 High absolute/Low
deviation alarm (with hold)
31 High deviation/Low
absolute alarm (with hold)
Type DO1 to DO5 Alarm T ype Action diagram Timer 32 ON delay timer
33 OFF delay timer
34 ON/OFF delay timer
Point
What is alarm with hold? The alarm will not turn ON immediately when the process value gets into the alarm band and enters again. If without hold, alarm ma y turn ON when starting up.
Caution
When alarm action code is changed, alarm set value may also become dif-
ferent from previous settings.
When alarm action type code is changed, turn off the power once, and
then re-start the controller, before starting control.
Aln: AL1 to AL5 show the alarm set values
ALnh: AL1h to AL5h show the alarm set values
ALnL: AL1L to AL5L show the alarm set values
dLYn: dLY1 to dLY5 show the alarm delay on set values
PV
t
ALnh ALnL
SV
PV
t
ALnh ALnL
SV
PV
t
ALnh ALnL
SV
PV
t
ALnh ALnL
PV
t
ALnL
ALnL
SV
PV
t
ALnh ALnL
SV
PV
t
ALnh ALnL
SV
PV
t
ALnh
ALnL
PV
t
ALnh ALnL
SV
PV
t
ALnh ALnL
SV
PV
t
ALnL
ALnh
SV
PV
t
ALnL
ALnh
PV
t
ALnh ALnL
SV
PV
t
ALnh ALnL
SV
PV
t
ALnL
ALnh
SV
PV
t
ALnL
ALnh
DI ALM
dLYn
DI ALM
dLYn
DI ALM
dLYn
dLYn
PV (process value)
power on
lower limit alarm lower limit alarm
(with hold)
power on
power off
Lower limit alarm output area
off off off
on on
off off
on
Digit
Specifications 1 2 3 4 5 6 7 8 - 9
10 11 12 13-14
Notes
4 <Size of front WxH>
48 x 96 mm P X G 5
Note 1
96 x 96 mm P X G 9
5 <Output 1>
Relay contacts A SSR drive C Current (0 to 20mA DC / 4 to 20mA DC)
E
Note 2
Voltage (0 to 5V DC / 1 to 5V DC / 0 to 10V DC / 2 to 10V DC)
P
Note 2
6 <Output 2>
None Y Relay contacts A
Note 4
SSR drive C
Note 4
Current (0 to 20mA DC / 4 to 20mA DC)
E
Note 4
Voltage (0 to 5V DC / 1 to 5V DC / 0 to 10V DC / 2 to 10V DC)
P
Note 4
Re-transmission output current (0 to 20mA DC/ 4 to 20mA DC)
R
Note 4
Re-transmission output voltage (0 to 5V DC / 1 to 5V DC / 0 to 10V DC / 2 to 10V DC)
S
Note 4
Transmitter power supply T
Note 1,4
7 <Option 1>
None Y RS 485 M Digital input (No. 1) + digital input
(No. 2)
T
Digital input (No. 1) + RSV1 H
Note 3
Digital input (No. 1) + CT1 G
Note
2,5,6 RS 485 + digital input (No. 1) V RS 485 + RSV1 K
Note 3
RS 485 + CT1 J
Note
2,5,6 RS 485 + digital input (No. 1)+RSV1
F
Note 4
Digital input (No. 1) + RSV1 +Digital input (No. 2)
2
Note 4
8 <Revision symbols> 1 9 <Digital Output>
(Relay contact output) None 0
Note 5 Digital output 1 point (No.1) 1 Digital output 2 points (No.1, 2) F Digital output 3 points (No.1, 2, 3) M Digital output 2 points
[independent common] (No.1, 2)
J
10
<Power Supply> <Instruction Manual> 100V/240V AC no instruction
manual
N
100V/240V AC English instruction manual
V
24V AC/DC no instruction manual C 24V AC/DC English instruction
manual
B
11 <Option 2>
None Y Digital input (No. 3, 4, 5) + CT2 A
Note
2,5,6 Digital input (No. 3, 4, 5) B Digital input (No. 3, 4, 5)
+ digital outputs (No. 4, 5) [transistor output]
C
Digital input (No. 3, 4, 5) + RSV2 D
Note 3 12 0 13 0
– 20 –
12-2
PXG5/9 Motorized Valve Control Model List
Note 1: If front panel size 48 × 96, the transmitter power supply output is not available.
13
Specifications
Digit
Specifications 1 2 3 4 5 6 7 8 - 9
10 11 12 13-14
Notes
4 <Size of front WxH>
48 x 96 mm P X G 5
Note 1
96 x 96 mm P X G 9
5 <Output 1>
Motor valve control output (no PFB input)
S
Motor valve control output (PFB input)
V
6 <Output 2>
None Y Auxual DO output A Transmitter power supply T
Note 1
7 <Option 1>
None Y Digital input (No. 1, 2, 3) + RSV1 E RS 485 + digital input (No. 1, 2, 3) U RS 485 + digital input
(No. 1) + RSV1
F
8 <Revision symbols> 1 9
<Digital Output> (Relay contact output) None 0 Digital output 1 point (No.1) 1 Digital output 2 points (No.1, 2) F Digital output 3 points (No.1, 2, 3) M Digital output 2 points
[independent common] (No.1, 2)
J
10
<Power Supply> <Instruction Manual> 100V/240V AC no instruction manual
N
100V/240V AC English instruction manual
V 24V AC/DC no instruction manual C 24V AC/DC English instruction manual
B
11 <Option 2>
None Y
12 0 13 0
Power Supply 100 (-15%) to 240V AC (+10%), 50/60dHz, 24V DC/AC (±10%) Power Consumption 12VA or less
Control Output
Relay contact output
•1a contact 220V AC / 30V DC , 3A (resistance load) SSR/SSC drive output (voltage pulse output)
•ON 20V DC (18 to 24V DC)
•OFF 0.5V DC or less
•Max Current 20mA DC or less (both OUT1 and OUT2)
•Load resistance 850 or more Current Output
•0 to 20mA DC / 4 to 20mA DC
•Acceptable load resistance 600 or less
•Accuracy: ±5%FS Voltage output
•0 to 5V DC / 1 to 5V DC / 0 to 10V DC / 2 to 10V DC
•Resistance load 10k or more
•Accuracy: ±5%FS
Process value input
Input accuracy
Thermocouple input: greatest one among ±0.3%FS, ±1 digit, and ±1°C or 2°C
Resistance bulb input: greatest one among ±0.3%FS, ±1
digit, and ±0.5°C
mV input, voltage input, current input : ±0.3%FS±1digit Indication resolution: ±0.3%FS or less
Digital Output
Relay contact output
(DO1 to DO3)
•1a contact 220V AC / 30V DC , 3A (resistance load) Transistor Output (DO4, DO5)
•Open collector 30V DC, 100mA, max 2 contacts
•Judged ON 1V DC or less
Digital input
Contact or Transistor type Max 5 inputs 30V DC, 3mA (1 input)
•Judged ON 1k or less (contact), or 5V DC or less (transistor)
•Judged OFF
100kor more (contact), or 18V DC or more (transistor)
Re-transmission output
0 to 20mA DC / 4 to 20mA DC / 0 to 5V DC / 1 to 5V DC / 0 to 10V DC / 2 to 10V DC Re-transmission data: PV, SV, DV, MV Accuracy: ±0.2%FS Resistance load : 600 or less (Current), 10k or more (voltage)
Remote SV Input
1 to 5V DC /0 to 5V DC, 0 to 20mA DC / 4 to 20mA DC (use an external 250 resistor)
Heater break detector (CT) input
Single-phase type CT 1 input, 1 to 30A / 20 to 50A
Valve feedback signal (potentiometer) input
Resistance range: 100 to 2.5k
(three line type)
Resolution: 0.5% FS Input accuracy: ±1.0% FS Corresponding full stroke time: 30 sec to 180 sec
Motorized valve control output
1a contact x 2, 220V AC / 30V DC , 3A (resistance load)
Transmitter supply power input
24V DC (19.5 to 24V DC), max current 21.6mA (with short-circuit protection) Max load resistance: 400
Communication Functions
RS-485 interface Communication method: Half-duplex bit serial asynchronous cycle Communication rate: 9600bps, 19200 bps Protocol: Modbus RTU compatible Communication distance: Max 500m (total connection length) Connectable units: 31 units
Loader Interface
RS-232C interface Connection method: ø2.5 mini-plug/jack (use the included cable at the bottom of the case) Communication method: Full-duplex bit serial asynchronous cycle Communication speed: 9600bps parity/none Protocol: Modbus RTU compatible
Operation and storage conditions
Range of usable temperatures: -10 to 50°C, ambient humidity 90% RH or less (non condensing)
-20 to 60 °C (storage temperature)
Loading...