IF, DURING THE WARRANTY PERIOD, THE CUSTOMER USES A PART FOR THIS
MANITOWOC FOOD SERVICE EQUIPMENT OTHER THAN AN UNMODIFIED NEW OR
RECYCLED PART PURCHASED DIRECTLY FROM FRYMASTER OR ANY OF ITS FACTORY
AUTHORIZED SERVICERS, AND/OR THE PART BEING USED IS MODIFIED FROM ITS
ORIGINAL CONFIGURATION, THIS WARRANTY WILL BE VOID. FURTHER, FRYMASTER
DEAN AND ITS AFFILIATES WILL NOT BE LIABLE FOR ANY CLAIMS, DAMAGES OR
EXPENSES INCURRED BY THE CUSTOMER WHICH ARISE DIRECTLY OR INDIRECTLY, IN
WHOLE OR IN PART, DUE TO THE INSTALLATION OF ANY MODIFIED PART AND/OR PART
RECEIVED FROM AN UNAUTHORIZED SERVICE CENTER.
DANGER
Copper wire suitable for at least 167°F (75°C) must be used for power connections.
DANGER
The electrical power supply for this appliance must be the same as indicated on the rating
and serial number plate located on the inside of the fryer door.
DANGER
This appliance must be connected to the voltage and phase as specified on the rating and
serial number plate located on the inside of the fryer door.
DANGER
All wiring connections for this appliance must be made in accordance with the wiring
diagrams furnished with the equipment. Wiring diagrams are located on the inside of the
fryer door.
DANGER
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or
any other appliance.
WARNING
Do not attach accessories to this fryer unless fryer is secured from tipping. Personal injury
may result.
WARNING
Frymaster fryers equipped with legs are for permanent installations. Fryers fitted with legs
must be lifted during movement to avoid damage and possible bodily injury. For a moveable
or portable installation, Frymaster optional equipment casters must be used.
Questions? Call 1-800-551-8633 or email at service@frymaster.com.
WARNING
Do not use water jets to clean this equipment.
WARNING
This equipment is intended for indoor use only. Do not install or operate this equipment in
outdoor areas.
DANGER
Adequate means must be provided to limit the movement of this appliance without
depending on or transmitting stress to the electrical conduit. A restraint kit is provided with
the fryer. If the restraint kit is missing contact your local KES.
DANGER
Prior to movement, testing, maintenance and any repair on your Frymaster fryer, disconnect
all electrical power from the fryer.
BIGL30 SERIES GAS FRYERS
TABLE OF CONTENTS
WARRANTY ....................................................................................................................................... i
1.14.3 Service Required Errors ................................................................................. 1-30
MANUAL LOV™ GAS WARRANTY STATEMENT
Frymaster, L.L.C. makes the following limited warranties to the original purchaser only for this
equipment and replacement parts:
A. WARRANTY PROVISIONS - FRYERS
1. Frymaster L.L.C. warrants all components against defects in material and workmanship for a
period of two years.
2. All parts, with the exception of the frypot, O-rings and fuses, are warranted for two years after
installation date of fryer.
3. If any parts, except fuses and filter O-rings, become defective during the first two years after
installation date, Frymaster will also pay straight-time labor costs up to two hours to replace the
part, plus up to 100 miles/160 km of travel (50 miles/80 km each way).
B. WARRANTY PROVISIONS - FRYPOTS
1. Frymaster warrants the frypot assembly for fifteen (15) years. First ten (10) years parts and
labor. Years eleven (11) through fifteen (15) frypot only. Components attached to the frypot,
such as the high-limit, probe, gaskets, seals, ignitors and related fasteners, are also covered by
the fifteen year warranty if replacement is necessitated by the frypot replacement. Components
that are not part of the frypot assembly, such as the blower, gas valve, micro switches, doors and
cabinetry are not covered by the frypot warranty. Leaks due to abuse or from threaded fittings
such as probes, sensors, high-limits, drain valves or return piping are not included. If the frypot
is found to be defective, Frymaster will replace the frypot, allowing up to the maximum time per
the Frymaster time allowance chart hours of straight-time labor plus up to 100 miles/160 km of
travel (50 miles/80 km each way) to change the frypot.
2. This warranty is limited to fryers operating on natural or propane (LP) gas. Fryers that operate
on manufactured gas (also known as town gas or high-hydrogen gas) have a lifetime frypot
warranty, parts only.
C. WARRANTY PROVISIONS – COMBUSTION CHAMBERS
1. Frymaster L.L.C. warrants the combustion chambers against defective material or workmanship
for a period of ten years from the original installation date, parts and labor.
2. The combustion chamber consists of the infrared burners and the structural components to
mount the burners. This warranty does not cover ancillary components, including the igniter,
blower, high-limit thermostat, and temperature probe.
3. This warranty is limited to fryers operating on natural or propane (LP) gas.
E. PARTS RETURN
All defective in-warranty parts must be returned to a Frymaster Authorized Factory Servicer within
60 days for credit. After 60 days, no credit will be allowed.
F. WARRANTY EXCLUSIONS
This warranty does not cover equipment that has been damaged due to misuse, abuse, alteration, or
accident such as:
improper or unauthorized repair (including any frypot which is welded in the field);
failure to follow proper installation instructions and/or scheduled maintenance procedures as
prescribed in your MRC cards. Proof of scheduled maintenance is required to maintain the
warranty;
improper maintenance;
damage in shipment;
abnormal use;
removal, alteration, or obliteration of either the rating plate or the date code on the heating elements;
operating the frypot without shortening or other liquid in the frypot;
no fryer will be warranted under the ten-year program for which a proper start-up form has not been
received.
This warranty also does not cover:
transportation or travel over 100 miles/160 km (50 miles/80 km each way), or travel over two
hours;
overtime or holiday charges;
consequential damages (the cost of repairing or replacing other property which is damaged), loss of
time, profits, use or any other incidental damages of any kind.
There are no implied warranties of merchantability or fitness for any particular use or purpose.
This warranty is applicable at the time of this printing and is subject to change.
BIGL30 SERIES GAS FRYER
CHAPTER 1: SERVICE PROCEDURES
1.1 Functional Description
BIGL30 series gas fryers contain a welded stainless steel frypot that is directly heated by a high efficiency
infrared burner system, requiring approximately 43% less energy than conventional burners to cook the same
volume.
Self-contained combustion chambers (referred to as “burners”) are fitted into rails attached to the sides of the
frypot, one on each side. Each combustion chamber is fitted with special ceramic tiles that are heated by the
burning of a forced air/gas mixture. The tiles transfer heat to the frypot by means of infrared radiation,
providing much more constant and uniform heat dispersion over the surface of the frypot than conventional
burners. Because less heat is lost to the atmosphere in the process, compared to “open-burner” designs, less
fuel is required to achieve and maintain a given frypot temperature.
In full-vat units, gas flow to both of the burners is regulated by one electromechanical gas valve. All fryers in
this series are equipped with 24 VAC gas valve systems, and all are configured with electronic ignition.
1.2 The Electronic Ignition System
An ignition module mounted below the component box (located behind the control panel) is connected to an
ignitor assembly at the burner. The ignition module performs five important functions: it provides fuse
protection for the 24-volt circuit, provides an ignition spark, supplies voltage to the gas valve, provides the
alarm circuit (24V) to the controller and proofs the burner flame. The module contains a four second time
delay circuit and a coil that activates the gas valve.
The ignitor assembly consists of a spark plug, an enrichment tube, and a flame sensor.
At start-up, the power switch is placed in the ON position,
supplying approximately 12-volts DC to the heat-control circuitry
in the controller and to one side of the heat relay coils on the
interface board. If resistance in the temperature probe indicates the
temperature in the frypot is below 180ºF (82ºC), the current flows
through a melt cycle circuit where a timer switch alternately closes
for six seconds and opens for 24 seconds. If the temperature is
180ºF (82ºC) or above, the current flows through a heat circuit,
bypassing the timer switch. In either case, ground is supplied to
the other leg of the heat relay coils, which closes electronic
switches in the 24 VAC circuit to provide current to the ignition
module. Circuitry in the ignition module sends 24 VAC to the gas
valve via a normally closed high-limit switch. Simultaneously,
the module causes the ignitor to spark for four seconds to light the
burner. A flame sensor verifies the burner ignition by measuring
the flow of microamps through the flame. If the burner does not
light (or is extinguished), current to the ignition module is cut, the gas valve closes, and the ignition module
“locks out” until the power switch is turned off and then back on. A normally closed drain switch is attached
to the rear of the controller. If the drain is opened, the heat circuit is opened and all heating is discontinued. A
probe monitors the temperature in the frypot. When the programmed setpoint temperature is reached,
resistance in the probe causes the heat cycle circuitry in the controller to cut off current flow through the heat
relay. This in turn cuts off the 24 VAC to the ignition module, causing the gas valve to close.
.
1-1
1.3 Interface Board
All fryers in this series have an interface board located in the component box behind the control panel. The
interface board provides a link between the controller and the fryer’s individual components without requiring
excessive wiring, and allows the controller to execute commands from one central point.
K2 and K3 are double-pole-double throw (DPDT) relays that supply 24VAC to the ignition and gas valve
circuits, as well as 120VAC to the blower motor. The relays on this board plug into sockets. If a relay fails,
that relay can be replaced.
LEDs (labeled D1 through D7) are arrayed around the board to assist in troubleshooting.
INTERFACE BOARD
LED DIAGNOSTIC LIGHTS
D1 24 VAC to left gas valve (dual vat only)
D2 24 VAC to left ignition module (dual vat only)
D3 24 VAC from transformer
D4 24 VAC to right ignition module
D5 24 VAC to gas valve (right valve if dual vat)
D6 12 VAC from transformer
D7 CE and Japanese units only: air switch closed
NOTE: In full-vat fryers, the relay for the left side (K2) may not be present.
The chart on the following page illustrates current flow through the board, and the table at the top of page 1-4
identifies frequently used test points.
1-2
1-3
FREQUENTLY USED TEST POINTS FOR INTERFACE BOARD
TEST
12VAC Power to Controller 50VAC Scale 1 and 3 on J3 or J2 12-18
24VAC Power to Right Module 50VAC Scale 8 on J3 and GROUND 22-28
120 VAC Power 250VAC Scale 11 on J3 and GROUND 110-125
120 VAC Power to Blowers 250VAC Scale 12 on J3 and GROUND 110-125
24VAC Power to Full or Right vat High-Limit 50VAC Scale 9 on J3 and GROUND 22-28
24VAC Power to Left High-Limit (if present) 50VAC Scale 9 on J1 and GROUND 22-28
Probe Resistance (Full or Right Vat) * R x 1000 OHMS 2 and 6 on J3 or 13 and 14 on J2 **
Probe Resistance (Left - if present) * R x 1000 OHMS 2 and 6 on J1 or 14 and 15 on J2 **
Probe Isolation R x 1000 OHMS 6 on J1 or J3 and GROUND ***
High-Limit Continuity (Full or Right Vat) R x 1 OHM 9 on J3 and Wire 13C on Gas Valve 0
High-Limit Continuity (Left - if present) R x 1 OHM 9 on J1 and Wire 12C on Gas Valve 0
* Disconnect 15-pin harness from controller before testing probe circuit.
** See Probe Resistance Chart on page 1-28.
*** 5 mega-Ohms or greater.
METER
SETTING
PINS RESULTS
1.4 Thermostats
BIGL30 series gas fryers have temperature probes located on the front centerline of each frypot. In this type of
thermostat, the probe resistance varies directly with the temperature. That is, as the temperature rises, so does
resistance, at a rate of approximately 2 ohms for every 1º F. Circuitry in the controller monitors the probe resistance
and controls burner firing when the resistance exceeds or falls below programmed temperatures (setpoints).
BIGL30 series gas fryers are also equipped with a high-limit thermostat. In the event that the fryer fails to properly
control the oil temperature, the high-limit thermostat prevents the fryer from overheating to the flash point. The highlimit thermostat acts as a normally closed power switch that opens when exposed to temperatures above 425ºF to
450ºF (218ºC to 232ºC). The different types of thermostats have different part numbers for CE and Non-CE models,
and are not interchangeable.
1.5 Accessing Fryers for Servicing
DANGER
Moving a fryer filled with oil may cause spilling or splattering of the hot liquid. Follow the
draining instructions in Chapter 5 of the BIGL30 Series Gas Fryer Installation and
Operation Manual before attempting to relocate a fryer for servicing.
1. Shut off the gas supply to the unit. Unplug the power cords. Disconnect the unit from the gas supply.
2. Remove any attached restraining devices and relocate the fryer for service accessibility.
3. After servicing is complete, reconnect the unit to the gas supply, reattach restraining devices, and plug in the
electrical cords.
1-4
1.6 Cleaning the Gas Valve Vent Tube
1. Set the fryer power switch and the gas valve to the OFF position.
2. Carefully unscrew the vent tube from the gas valve. NOTE: The vent tube may be straightened for ease of
removal.
3. Pass a piece of ordinary binding wire (.052 inch diameter) through the tube to remove any obstruction.
4. Remove the wire and blow through the tube to ensure it is clear.
5. Reinstall the tube and bend it so that the opening is pointing downward.
1.7 Checking the Burner Manifold Gas Pressure
1. On non-CE fryersonly ensure that the gas valve knob is in the OFF position.
Honeywell
ON
OFF
2.Remove the pressure tap plug from the gas valve assembly.
Pressure Tap Plug
Typical Non-CE
Valve Assembly
Typical CE Valve
Assembly
3. Insert the fitting for a gas pressure-measuring device into the pressure tap hole.
4. On non-CE fryers only , place the gas valve in the ON position.
5. Place the fryer power switch in the ON position. When the burner has lit and burned steadily for at least one
minute, compare the gas pressure reading to the pressure for the corresponding gas in the appropriate table on the
following page. The tables list the burner manifold gas pressures for each of the gas types that can be used with
this equipment.
1-5
CE Standard
Burner Manifold Gas Pressures
Pressure
(mb a r )
Single
Gas
Natural Gas Lacq
(G20) under 20 mbar
Natural Gas Gronique
(G25) under 25 mbar
Natural Gas Gronique
(G25) under 20 mbar
Butane/Propane
(G30) at 28/30 or 50 mbar
Propane
(G31) under 37 or 50 mbar
* Belgian G25 = 7,0 mbar
*
Vat
7
10
10
17
20
Non-CE Standard
Bur ner Ma nifold G as Pr e ssures
GasPressure
Natural
Propane
3" W.C.
0.73 kPa
8.25" W.C.
2.5 kPa
6.To adjust the burner gas pressure, remove the cap from the gas valve regulator and adjust to the correct pressure.
Non-CE
Valve
CE
Valve
GAS VALVE REGULATOR CAP
7. Place the fry er power switch (and the gas valve in non-CE fryers) in the OFF position. Remove the fitting from
the pressure tap hole and reinstall the pressure tap plug.
1.8 Measuring Flame Current
When the burner flame is properly adjusted, it will produce a current between 2.5 A and 3.5 A. Flame current is
measured by placing a microamp (not milliamp) meter in series with the sensing wire on the ignitor. This is
accomplished as follows:
1. Place the fryer power switch in the OFF position.
1-6
r
2. Disconnect the sensing wire from one of the burner ignitors and connect it to the positive lead of the meter.
Connect the negative lead of the meter to the terminal from which the sensing wire was removed.
Flame Sensor Wire
3. Place the fryer power switch in the ON position to light the burners. After the frypot temperature reaches 200F
(93C), wait at least one minute before checking the reading. NOTE: The closer the unit is to normal operating
temperature, the more accurate the reading will be.
1.9 Replacing Fryer Components
1.9.1 Replacing the Controller or the Controller Wiring Harnesses
1. Disconnect the fryer from the electrical power supply.
2. Open the control panel by removing the screws on the bottom of the bezel. Carefully lower the bezel.
3. Remove the two screws from the upper corners of the controller. The controller is hinged at the bottom and will
swing open from the top.
4. Unplug the wiring harnesses from the connectors on the back of the controller marking their position for
reassembly and disconnect the grounding wires from the terminals. Remove the controller by lifting it from the
hinged slots in the control panel frame.
Ground Wire Terminal
Communication Wires
Drain Switch
Manual M3000 controller.
Ground Wire Terminal
20-Pin Connecto
Locator Wire
5. Install the replacement controller. Reverse steps 1 thru 4.
6. Setup the manual M3000 controller following the instructions in the Installation and Operation manual. Setup
MUST be performed after replacement.
7. Once setup is complete on all replaced controllers, reset all control power following the instructions in section
1.13.6 to readdress the new controller. Check software version and if necessary update the software. If a
software update was necessary, follow the instructions to update the software in section 1.15 on page 1-34.
1.9.2 Replacing the Temperature Probe, High-Limit Thermostat
1. Disconnect the fryer from the electrical supply.
2. Drain cooking oil below the level of the probe or thermostat.
3. Remove the screws on the bottom of the bezel. Carefully lower the bezel.
4. Remove the top two screws in the upper corners of the controller.
5. Swing the controller out from the top and allow it to rest on its hinge tabs.
6. Disconnect the controller wiring harness(es) and ground wire from the back of the controller and remove the
controller by lifting it from the hinge slots in the control panel frame.
7. Disconnect the ignition cables from the ignitors by grasping the boots and gently pulling toward you.
8. Disconnect the flame sensor wires from the flame sensors.
9. Disconnect the sound device lead from the interface board.
1-7
10. If working on the left frypot, cut the wire tie on the wiring bundle and disconnect the main wiring harness 15-pin
connector.
11. Remove the spark module boxes.
12. Remove the component box mounting screws.
13. Lower the component box far enough to expose the probes and carefully disconnect the wiring harness plug from
the back of the box. This will leave one set of wires, enclosed in spiral wrap, connected to the component box.
14. Unscrew the probe or thermostat from the frypot.
15. Apply Loctite
®
PST56765 pipe thread sealant or equivalent to the replacement part threads and screw the
replacement part into the frypot, torquing to 180 inch-pounds.
16. Connect the wires from the new component as follows:
a. If replacing the temperature probe, use a pin pusher to disconnect (one at a time) the red and white leads from
the connector and insert the corresponding leads from the new probe into the plug..
b. If replacing the high-limit thermostat, use a pin pusher to disconnect the lead running to the connector and
insert the corresponding lead from the new thermostat.
c. Disconnect the other lead from the drain safety switch and connect the remaining lead from the new
thermostat.
17. Reverse steps 1 through 13 to complete the procedure.
1.9.3 Replacing the Interface Board
1. Perform steps 1 through 4 from section 1.9.1.
2. Disconnect the wires attached to the interface board, marking or making a note of the wires and terminals to
facilitate reconnection.
3. Remove the nuts at each corner of the interface board and carefully pull it from the studs far enough to allow the
connector on the back of the board to be disconnected, then remove the board from the box. When removing the
board, be careful not to lose the spacers that fit over the studs behind the board.
4. Recover the relay(s) from the failed interface board and install on the replacement board.
5. Reverse the procedure to install the replacement board, being sure that the spacers behind the board are in place
and the computer locator ground wire is attached to a stud.
1.9.4 Replacing an Ignition Module
1. Disconnect the fryer from the electrical supply.
2. Remove the screws on the bottom of the bezel. Carefully lower the bezel.
3. Remove the top two screws in the upper corners of the controller.
4. Swing the controller out from the top and allow it to rest on its hinge tabs.
5. Loosen the nuts attached to the screws of the module. Slide the module towards the rear of the component box
until the nuts drop through the keyholes.
6. Carefully rotate the module and pull forward. On some units it may be necessary to remove the blower.
7. Disconnect the wires from the ignition module, marking or making a note of the wires and terminals to facilitate
reconnection.
8. Remove the screws from the module.
9. Move the screws and spacers to the new module.
10. Reverse the procedure to install the replacement module.
1.9.5 Replacing an Ignitor Assembly
DANGER
Drain the frypot or remove the handle from the drain valve before proceeding further.
1. Disconnect the fryer from the electrical supply.
2. Disconnect the flame sensor wire by carefully pulling its push-on terminal from the terminal strip on the ignitor.
Disconnect the gas enrichment tube at the ignitor-end compression fitting. Disconnect the ignition cable from the
ignitor by grasping its boot and gently pulling toward you. (See photo below)
1-8
Flame Sensor Wire
Gas Enrichment Tube
Ignition Cable
3. Remove the sheet metal screws securing the ignitor to the mounting plate and pull the ignitor from the fryer.
4. Reverse the procedure to install the replacement ignitor.
1.9.6 Replacing or Cleaning a Combustion Air Blower
1.
Disconnect the blower wiring harness, remove the blower assembly mounting nuts, and remove the blower
assembly from the fryer. If cleaning the motor, continue with Step 2; otherwise, install the replacement blower,
reconnect the wiring harness, and then go to Step 6.
Blower assembly
mounting nuts
Wiring connection
2. Remove the blower motor shield and separate the blower motor from the housing as shown in the illustration
below.
Remove these screws to
remove the shield from the
blower assembly.
Remove these nuts to
separate the blower
motor from the housing.
3. Wrap the motor with plastic wrap to prevent water from entering it. Spray degreaser or detergent on the blower
wheel and the blower housing. Allow it to soak for five minutes. Rinse the wheel and housing with hot tap water,
then dry with a clean cloth.
NOTICE- Australia Only
The air pressure switch on the combustion blower should read: Full Vat units-122pa (0.5
inches W.C.) and for Split Vat units-180pa (0.72 inches W.C.).
1-9
Wrap the motor and wires
with plastic wrap or a
plastic bag.
Blower Housing
Blower Wheel
4. Remove the plastic wrap from the blower motor assembly. Reassemble the blower motor assembly and blower
housing. Reinstall the blower shield.
5. Reinstall the blower assembly in the fryer and reconnect the wiring disconnected in Step 1.
6. Light the fry er in accordance with the procedure described in Chapter 3, Section 3.2.2 of the BIGL30 Series Gas
Fryer Installation and Operation Manual.
7. After the burners have been lit for at least 90 seconds, observe the flames through the burner viewing ports
located on each side of the combustion air blower.
Right
Viewing Port is
behind motor.
Left Viewing
Port.
The air/gas mixture is properly adjusted when the burner manifold pressure is in accordance with the applicable
table on page 1-6 and the burners display a bright orange-red glow. If a blue flame is observed or if there are dark
spots on a burner face, the air/gas mixture requires adjustment.
result in whistling. It should not be more than 1/3 open.
NOTE: Opening the air shutter too much may
1.9.7 Adjusting the Air/Gas Mixture
On the side of the blower housing opposite the motor is a shutter plate with a locking nut. Loosen the nut enough to
allow the shutter to be moved, then adjust the position of the shutter to open or close the air intake opening until a
bright orange-red glow is obtained. Carefully hold the shutter in position and tighten the locking nut (see illustration
on the following page).
1-10
On non-CE blowers,
loosen this nut and rotate
shutter to open or close
air intake.
On CE blowers, loosen
both wing nuts and slide
the shutter to adjust the
air intake.
1.9.8 Replacing a Gas Valve
1. Disconnect fryer from electrical and gas supplies.
2. Disconnect the drain safety and high-limit thermostat wires from the gas valve. Mark each wire to facilitate
reconnection.
3. Remove the vent tube (on non-CE fryers) and the enrichment tube fitting from the valve. Disconnect the flexible
gas line(s).
If replacing the left-most valve on any configuration, or the right valve on a two-fryer battery, follow the
instructions below. If replacing valves in other positions, skip to “ALL OTHER VALVES.”
A. Remove the filter pan from the unit. Remove the door adjacent to the valve being replaced.
B. Remove the screws that attach the pan rails adjacent to the valve being replaced.
C. Uncouple the pipe union and remove the gas valve and associated piping from the unit.
D. Remove the fittings and associated piping from the failed valve and install them on the replacement valve using
Loctite
E. Reconnect the gas valve assembly to the fryer using Loctite
reattach the flexible gas line(s), enrichment tube(s), and the vent tube (on non-CE units). Reconnect the highlimit thermostat wires and drain safety wires to the valve.
F. Reconnect the fryer to the gas supply and open the cut off valve. Apply a thick soapy solution of water around
each connection to check for gas leaks and ensure there are no bubbles. Eliminate any that are found. There
should be no smell of gas.
G. Position the pan rail assembly beneath the fryer and rest the rear end of the rail on the cabinet frame. Install the
two nuts and bolts behind the front face of the rail, but do not tighten them. Install the nut and bolt at the rear end
of the filter rail and tighten securely.
H. Reattach the screws for the pan rails. Install the filter pan in the unit to make sure that all components are properly
aligned.
I. Reconnect the fryer to the electrical power supply and check for proper operation. When proper operation has
been verified, reinstall the door removed in Step A.
ALL OTHER VALVES
4. Carefully unscrew the valve from the manifold. NOTE: Some models may have the valve attached to the
manifold by means of a pipe union. In such cases, remove the valve by uncoupling the union.
5. Remove all fittings from the old gas valve and install them on the replacement valve, using Loctite
equivalent pipe thread sealant.
6. Reconnect the gas valve assembly to the fry er using Loctite
reattach the flexible gas line(s), enrichment tube(s), and the vent tube (on non-CE units). Reconnect the highlimit thermostat wires and drain safety wires to the valve.
7. Reconnect the fryer to the gas supply and open the cut off valve. Apply a thick soapy solution of water around
each connection to check for gas leaks and ensure there are no bubbles. Eliminate any that are found. There
should be no smell of gas.
8. Reconnect the fryer to the electrical power supply and check for proper operation.
®
PST56765 or equivalent pipe thread sealant.
®
PST56765 or equivalent pipe thread sealant, and
®
PST56765 or
®
PST56765 or equivalent pipe thread sealant, and
1-11
1.9.9 Replacing a Burner Assembly
1. Disconnect the unit from the electrical and gas supplies.
2. Remove the gas line and enrichment tube using a 7/16” and 5/8” wrench from the front of the burner.
3. Remove the elbow and tee off the bottom of the burner to ensure easier
removal of the burner.
4. Remove the fryer back.
5. Remove the screws attaching the flue cap to the brace.
6. Remove the top cross brace in the back.
7. Remove the flue by removing the two screws in the rear and one screw in
the front of the flue.
Figure 1
8. Remove all the screws on the flue collector and bend back the tabs and remove the
collector.
9. Remove four screws on the collector insulation plate (see Figure 1).
10. Remove the four nuts and cover of the lower insulation retaining cover (see Figure
2).
11. Carefully remove the insulation.
12. Grasp the burner firmly and slide the burner out the rear of the fryer. Pull it toward
you until it clears the burner channels, taking care not to damage the ceramic tiles in
the process.
Figure 2
13. Slide the burner out the rear of the fryer.
14. Clean all debris from the burner channels and combustion area.
15. Inspect the upper and lower burner rails for cracked or burned out welds.
a. If the welds in the lower rail are cracked or burned out, the frypot must be
replaced. Refer to Section 1.9.11 for procedure.
b. If the welds in the upper rail are cracked or burned out, the upper rail must be
replaced. Refer to Section 1.9.12 for procedure.
16. Wrap a new insulating strip along the edges of the burner. NOTE: Use P/N 8260931 for full-vat frypots and P/N 826-0932 for dual-vat frypots.
17. Carefully slide the replacement burner into the rails starting at the top and lifting
slightly up on the bottom (see Figure 3). Ensure that the insulation is not torn or
damaged.
Figure 3
18. In reverse order, reassemble insulation and holding plates.
19. Install flue collector.
20. Install the flue.
21. Install the cross brace, ensuring the flue cap is secured to the brace.
22. Replace the fryer back.
23. Reattach the elbow, gas line and enrichment tubes to the front of the burner.
24. Fill the frypot with oil. Turn the fryer on; turn off or bypass the melt cycle and operate the unit for at least 10
minutes.
25. Examine the burner flame. The color and intensity on both sides should be the same.
Use an inspection mirror to check for leaks in areas that cannot be directly
26.
observed.
27. If a leak is detected, tighten all the lower insulation retainer nuts, allow the frypot to heat for five additional
minutes, and repeat steps 25 and 26.
28. If a leak persists, use a rubber hammer and a small block of wood to tap the corners of the lower combustion
chamber insulation retainers. Repeat steps 25 through 27. Repeat this step until no leakage is detected.
1-12
1.9.10 Replacing the Filter Motor, Filter Pump, or Filter Pump Solenoid Valve
1. Disconnect the unit from the electrical power supply.
2. Remove the filter pan from the unit.
3. Position a container beneath the oil return fitting at the front of the cabinet. Disconnect the flexible oil lines from
the fittings, allowing any residual oil to drain into the container.
4. At the rear of the fryer, unplug the left connector (as viewed from the rear of the fryer) from the transformer box.
5. Remove the four nuts and bolts attaching the motor mount to the rear motor mount support.
6. At the front of the fryer, remove the cover plate from the front of the motor and disconnect the motor wires.
7. Place a 1-foot (30.5-cm) length of wood (or similar support) beneath the motor mount near the front of the unit
and remove the two remaining nuts and bolts attaching the motor mount to the front cabinet cross-brace.
8. Carefully remove the support and lower the motor mount to the floor, allowing the rear of the mount to slide
forward and off the rear motor mount support.
9. Disconnect the return flexline from the pump. The motor and pump assembly can now be pulled from beneath the
fryer and the failed component can be removed and replaced.
10. Position the replacement motor and pump assembly beneath the fryer and reconnect the oil return flexline to the
pump. Lift the rear of the motor mount up and onto the rear motor mount support.
11. Lift the front of the motor mount up and support it with a 1-foot (30.5-cm) piece of wood or a similar support.
Install but do not tighten the two nuts and bolts that attach the motor mount to the front cabinet cross-brace.
12. Install and tighten the four nuts and bolts that secure the motor mount to the rear motor mount support.
13. At the front of the fryer, tighten the two nuts and bolts at the front of the motor mount. Reconnect the motor
power wires and reinstall the wiring cover plate.
14. Reconnect the oil return flexline and reinstall the filter pan.
15. Reconnect the unit to the electrical power supply, fill the frypots with oil and check for proper operation.
1.9.11 Replacing the Frypot
1. Disconnect the fryer from the electrical and gas supplies.
2. Remove the filter pan from the unit and drain one frypot at a time into a Shortening Disposal Unit (SDU) or other
appropriate metal container.
DANGER
DO NOT attempt to drain more than one full frypot into the SDU at one time.
3. Open the control panel by removing the two screws on the bottom of the bezel. Carefully lower the bezel.
4. Remove the top screws in the upper corners of the controller.
5. Grasp the upper edge of each controller and swing the controller downward. Unplug the controller wiring harness
and grounding wire from the back of each controller.
6. Remove the controllers by lifting them from the hinge slots in the control panel frame.
7. Disconnect the sound device wire from the interface board.
8. Disconnect the flame sensor wires by carefully pulling the push-on terminals from the terminal strips on the
ignitors. Disconnect the gas enrichment tube at the ignitor-end compression fitting. Disconnect the ignition
cables from the ignitors by grasping the boots and gently pulling toward you.
9. Dismount the topcap by removing the screws on the bottom of each front corner and lifting the topcap straight up.
10. Remove the two mounting screws on each side of the component box and rotate the top of the box out of the
frame. Carefully pull it out enough to disconnect the wiring harness connector from the back of the box. Cut any
ties that prevent the box from being pulled out of the control panel frame.
11. Carefully pull the box clear of the frame and rest it on top of the fryer.
12. Using a pin pusher, remove the temperature probe, high-limit thermostat wires and RTD probe wires from the
plugs or terminals, marking each wire to facilitate re-assembly.
13. Remove the cover from the safety drain switch. Disconnect the wires from the switch.
14. Disconnect any auto top-off sensors if equipped and wiring.
15. Remove the section(s) of drain from the drain valve(s) of the frypot to be removed.
1-13
16. Disconnect the gas lines from the burner orifices and ignitor assemblies.
17. Remove the frypot hold down bracket.
18. Remove the screws in the back panel and inside the flue cap at each end that secure the flue cap to the fryer and
lift it clear of the fryer.
19. Disconnect the oil return line(s) from the frypot to be removed.
20. Carefully lift the frypot from the fryer cabinet.
21. Remove the drain valve(s), temperature probe(s), high-limit thermostat(s), RTD probes and igniter assemblies.
Inspect each of these components carefully and install them in the replacement frypot if they are in serviceable
condition. Use Loctite
®
PST56765 sealant or equivalent on component threads.
NOTE: Some servicers, based upon their experience, recommend that probes and thermostats be replaced
whenever a frypot is replaced; however, this remains the customer’s decision.
20. Reverse steps 1-19 to reassemble fryer.
NOTE: Care should be taken not to over-torque nuts on frypots made of 400-series stainless steel, as this could
tear the material. One turn past hand-tight is sufficient torque.
21. Perform steps 14 through 18 of Section 1.9.9 to ensure that there are no leaks in the burner insulation.
CAUTION
Before installing temperature probe, high-limit thermostat, RTD probe and drain valve on
replacement frypot, clean the threads and apply Loctite® PST56765 thread sealant or
equivalent.
NOTE: Replacing the burner rails requires completely tearing down the frypot and installing new frypot insulation.
Refer to the frypot exploded view (on next page) for component identification.
1. Remove the frypot per Section 1.9.11.
2. Remove the burner assemblies (1).
3. Remove insulation retainers and blanket insulation (2).
4. Remove the upper oil zone insulation bracket and upper oil zone insulation (3).
5. Remove the plenum (4).
6. Remove the front lower combustion chamber insulation retainer and insulation (5) and the front lower combustion
chamber inner insulation retainer and insulation (6). NOTE: Full-vat units have two-piece insulation retainer and
insulation components. Dual-vat units have one-piece components.
7. Remove the upper combustion chamber insulation retainer and insulation (7).
8. Remove the inner upper combustion chamber insulation retainer and insulation (8).
9. Remove the rear lower combustion chamber retainers, back, and insulation (9). NOTE: Full-vat units have two-
piece backs and four retainers. Dual-vat units have one-piece backs and two retainers.
10. Remove the flue assembly (10).
1-14
10
Spacer
2
9
3
Spacer
s
8
11
1
4
7
6
5
Disassembling A Frypot
(Full Vat Illustrated)
See page 1-17 for reassembly illustration.
11. Remove the upper burner rails (11). NOTE: For the following steps, refer to the frypot exploded view on page 1-
15 for component identification.
12. Remove any residual insulation, sealant, and/or oil from the exterior of the frypot.
13. Place the “L” shaped pieces of the combustion chamber insulation (1) in the front and rear corners of both upper
rail-retaining slots. (See page 1-17).
14. Using a mallet and short piece of wood, tap the corner tabs of the combustion chamber over the insulation to
ensure a solid seal of the burner.
15. Install the upper burner rails (2) with the heat deflectors slanting toward the rear of the frypot. The rails will
cover the “L” shaped pieces of combustion chamber insulation previously installed.
16. Place the upper inner combustion chamber insulation and insulation retainers (3) on the top two studs on each side
of the front of the frypot and secure with ¼”-20 washer-nuts. It is normal for the retainers to slice off the overhanging insulation.
17. Place the lower rear combustion chamber insulation (4) on the lower four studs at the rear of the frypot.
18. Place one 1.625-inch tubular spacer (5) on each of the flue assembly (upper) studs at the rear of the frypot.
NOTE: There are three different sizes of spacers. Verify the size to ensure the correct spacers are installed.
19. Press the flue assembly (6) over the burner rails. It may be necessary to use a rubber mallet or screwdriver to
align the components. Use four ¼”-20 washer nuts to secure the flue assembly. Do not tighten the retainer nuts at this point. They should be finger-tight only. NOTE: The flue edge will cover one to two inches of the
lower insulation.
20. Install the lower rear combustion chamber back(s) and retainer(s) (7) with the flanged edge(s) against the flue.
Secure with ¼”-20 washer nuts. NOTE: Full-vat units have two-piece backs and four retainers. Dual-vat units
come with one-piece backs and only two retainers.
1-15
21. Insert the burners (9) into the rails to ensure the rail spacing and alignments are correct. The burner should slide
freely into and out of the rails. The upper rail can be bent slightly to increase or decrease tension on the burner
and the edges of the slot can be closed or opened slightly to best fit the burner frame.
22. Carefully wrap a strip of burner insulation (8) tightly around the rear and sides of the burner frame (9), with the
glass-tape side of the strip on the outside. Do not use duct tape or adhesive to secure the strip to the burner frame.
23. Align the burner to the burner rails while maintaining tension on the insulation strip. Insert the burner at a slight
angle and begin pushing the burner slowly into the rails until it contacts the rear combustion chamber. The fit
should be snug, but not excessively tight.
24. Verify that the burners are flush with the front edge of the burner rails. Remove the excess burner insulation by
cutting with a knife or diagonal pliers. Do not try to tear the insulation!
25. Insert the upper front insulation (10) into its retainer (11), making sure that the holes in each piece are aligned
with one another. Install the assembly with the insulation side toward the frypot and secure with ¼”-20 washernuts. Do not over tighten.
26. Place a washer on each of the four lower studs on the front of the frypot. Install the lower inner front insulation
(12) with the rectangular openings toward the drain valve nipple. Install the lower inner front insulation
retainer(s) (13). NOTE: Full-vat units have a two-piece insulation retainer. Dual-vat units have a one-piece
retainer.
27. If necessary, replace the sight-glasses and insulation (14).
28. Place one washer and one 1.888-inch spacer (15) on each stud. NOTE: There are three different sizes of spacers.
Verify the size to ensure the correct spacers are installed.
29. Insert the front lower insulation (16) into the front lower insulation retainer(s) (17) and install assembly on
frypot. Secure with ¼”-20 washer-nuts. If frypot uses two retainers, connect them together with two ¼” selftapping screws. NOTE: Full-vat units have a two-piece insulation retainer and two pieces of insulation. Dual-vat
units have one-piece components.
30. Return to the rear of the frypot and fully tighten all washer-nuts.
31. Remove and replace the plenum gaskets (18).
32. Place a 0.938-inch spacer (19) on the plenum-mounting studs, and mount the plenum (20). Ensure the gaskets
are clear of the burner tubes by pulling the plenum back slightly. Place a washer on each stud and secure plenum
with ¼”-20 lock-nuts.
33. Install the upper oil-zone insulation (21) by pressing it under the upper combustion chamber metalwork. Secure
the insulation with the bracket (22) and ¼” self-tapping screws.
34. Install the upper burner rail blanket insulation (23). Position any excess insulation toward the top of the frypot.
Avoid overhang past the bottom of the upper burner rail. Overhang in this area will make future burner
replacement more difficult.
35. Cover the insulation with the insulation retainer (24), and secure with ¼” self-tapping screws.
36. Reinstall probes, drain valves, high-limit thermostats, and other pipe fittings using Loctite® PST56765 sealant or
equivalent on the threads.
1-16
6
5
24
4
23
21
22
1
2
7
8
1
9
17
16
15
3
10
20
19
12
11
13
14
18
Re-assembling A Frypot
(Full-Vat Illustrated)
1.10 Troubleshooting and Problem Isolation
Because it is not feasible to attempt to include in this manual every conceivable problem or trouble condition that
might be encountered, this section is intended to provide technicians with a general knowledge of the broad problem
categories associated with this equipment, and the probable causes of each. With this knowledge, the technician
should be able to isolate and correct any problem encountered.
Problems you are likely to encounter can be grouped into six categories:
1. Ignition failure
2. Improper burner function
3. Improper temperature control
4. Controller malfunctions
5. Filtration malfunctions
6. Leakage
The probable causes of each category are discussed in the following sections. A series of Troubleshooting Guides is
also included at the end of the chapter to assist in solving some of the more common problems.
1-17
1.10.1 Heating (Ignition) Failure
Heating (ignition) failure occurs when the ignition module fails to sense a flame within the 4-second time delay period
and locks out. When this happens, the module sends 24 VAC through the interface board alarm circuit to the
controller.
M3000 controllers display “HEATING FAILURE.”
The three primary reasons for ignition failure, listed in order of probability, are problems related to:
1. Gas and/or electrical power supplies
2. Electronic circuits
3. Gas valve.
PROBLEMS RELATED TO THE GAS AND/OR ELECTRICAL POWER SUPPLIES
The main indicators of this are that an entire battery of fryers fails to light and/or there are no indicator lights
illuminated on the fryer experiencing ignition failure. Verify that the quick disconnect fitting is properly connected,
the fryer is plugged in with connector twisted and locked, the main gas supply valve is open, and the circuit breaker
for the fryer electrical supply is not tripped.
PROBLEMS RELATED TO THE ELECTRONIC CIRCUITS
If gas and electrical power are being supplied to the fryer, the next most likely cause of ignition failure is a problem in
the 24 VAC circuit. Verify that the drain valve is fully closed. The valve is attached to a microswitch that must be
closed for power to reach the gas valve (often, although the valve handle appears to be in the closed position, the
microswitch is still open). If the valve is fully closed, refer to Section 1.11.1, TROUBLESHOOTING THE 24 VAC
CIRCUIT.
Some typical causes of heating failure in this category include a defective sensing wire in the ignitor assembly, a
defective module, a defective ignition wire, and a defective ignitor.
Occasionally, a heating failure occurs in which all components appear to be serviceable and the microamp reading is
within specification, but the unit nevertheless goes into ignition failure. The probable cause in this case is an
intermittent failure of an ignition module. When the unit is opened up for troubleshooting, the module cools down
enough to operate correctly; however, when the unit is again closed up and placed back into service the module heats
up and fails.
PROBLEMS RELATED TO THE GAS VALVE
If the problem is not in the 24 VAC circuit, it is most likely in the gas valve, itself. Before replacing the gas valve,
refer to Section 1.11.2
1.10.2 Improper Burner Function
TROUBLESHOOTING THE GAS VALVE.
With problems in this category, the burner ignites but exhibits abnormal characteristics such as “popping,” dark spots
on the burner ceramics, fluctuating flame intensity, and flames shooting out of the flue.
“Popping” indicates delayed ignition. In this condition, the main gas valve is opening but the burner is not
immediately lighting. When ignition does take place, the excess gas “explodes” into flame, rather than smoothly
igniting.
The primary causes of popping are:
Incorrect or fluctuating gas pressure
Defective or incorrectly adjusted
combustion air blower
Inadequate make-up air
Heat-damaged computer or ignition module
1-18
Cracked ignitor or broken ignition wire
Defective ignition module
Cracked burner tile (typically causes a very
loud pop).
If popping occurs only during peak operating hours, the problem may be incorrect or fluctuating gas pressure.
Verify that the incoming gas pressure (pressure to the gas valve) is in accordance with the appropriate CE or
Non-CE Standard found in Section 2.3 page 2-4 of the BIGL30 Series Gas Fryer Installation and Operation
Manual, and that the pressure remains constant throughout all hours of usage. Refer to Section 1.7, Checking the Burner Manifold Gas Pressure in this manual for the procedure for checking the pressure of gas
supplied to the burner.
If popping is consistent during all hours of operation, the most likely cause is an insufficient air supply.
Check for “negative pressure” conditions in the kitchen area. If air is flowing into the kitchen area, this
indicates that more air is being exhausted than is being replenished and the burners may be starved for air.
If the fryer’s gas and air supplies are correct, the problem is most likely with one of the electrical components.
Examine the ignition module and controller for signs of melting, distortion, and/or discoloration due to
excessive heat build-up in the fryer (this condition usually indicates improper flue performance). A melted or
distorted ignition module is automatically suspect and should be replaced; however, unless the condition
causing excessive heat is corrected, the problem is likely to recur.
Verify that the ignition wire is tightly connected at both ends and free of obvious signs of damage. Again, if
damage is due to excessive heat in the fryer, that problem must also be corrected. Check for proper operation
by disconnecting the wire from the ignitor (spark plug), inserting the tip of a screw driver into the terminal.
With the insulated handle of the screwdriver, hold the shaft near the frame of the fryer as the power switch is
placed in the ON position. A strong, blue spark should be generated for at least four seconds.
DANGER
Make sure you are holding the insulated handle of the screwdriver and not the blade.
The sparking charge is approximately 25,000 volts.
Examine the ignitor (spark plug) for any signs of cracking. A cracked ignitor must be replaced.
If all other causes have been ruled out, examine the burner tiles for any signs of cracking. If cracking is
found, the burner must be replaced.
Fluctuating flame intensity is normally caused by either improper or fluctuating incoming gas pressure, but
may also be the result of variations in the kitchen atmosphere. Verify incoming gas pressure in the same way
as for “popping,” discussed in the preceding paragraphs. Variations in the kitchen atmosphere are usually
caused by air conditioning and/or ventilation units starting and stopping during the day. As they start and
stop, the pressure in the kitchen may change from positive or neutral to negative, or vice versa. They may
also cause changes in airflow patterns that may affect flame intensity.
Dark spots on the burner tiles are the result of an improper air/gas mixture. Adjust the combustion air
blower to reduce the amount of air in the mixture to correct this problem
Flames shooting out of the flue are usually an indication of negative pressure in the kitchen. Air is being
sucked out of the burner enclosure and the flames are literally following the air. If negative pressure is not the
cause, check for high burner manifold gas pressure in accordance with the procedures in Section 1.7.
An excessively noisy burner, especially with flames visible above the flue opening, may indicate that the gas
pressure is too high, or it may simply be that the gas valve vent tube is blocked. If the incoming gas pressure
is correct and the vent tube is unobstructed, the gas valve regulator is probably defective.
Occasionally a burner may apparently be operating correctly, but nevertheless the fryer has a slow recovery rate (the length of time required for the fryer to increase the oil temperature from 250ºF to 300ºF (121ºC to
149ºC)). The primary causes of this include an over-filled frypot, a dirty or out-of-adjustment combustion air
blower, low burner manifold pressure, and/or damaged burner tiles. Adding oil to the frypot during the
recovery process will also cause a slow recovery rate.
If these causes are ruled out, the probable cause is a misadjusted gas valve regulator. Refer to Section 1.7,
Checking the Burner Manifold Gas Pressure, for the gas valve adjustment procedure.
1-19
1.10.3 Improper Temperature Control
Temperature control, including the melt cycle, is a function of several interrelated components, each of which
must operate correctly. The principle component is the temperature probe. Other components include the
interface board, the controller itself, and the ignition module.
Improper temperature control problems can be categorized into melt cycle problems and failure to control at
setpoint problems.
MELT CYCLE PROBLEMS
Initiation of the melt cycle with manual M3000 controllers is automatic. Problems may originate from the
controller itself, the temperature probe, or a malfunctioning heat relay on the interface board.
FAILURE TO CONTROL AT SETPOINT
Problems in this category may be caused by the temperature probe, the interface board, or the controller.
1.10.4 Controller Malfunctions
RECOVERY TIME
Recovery time – is a method of measuring a fryer’s performance. Put simply, it is the time required for the
fryer to increase the oil temperature from 250ºF to 300ºF (121ºC to 149ºC). This range is used as a standard
since ambient kitchen temperatures can affect the test if lower ranges are used.
The controller performs the recovery test each time the fryer warms up. An operator can view the results of
the test any time the fryer is above the 325ºF (163ºC) point by pressing the INFO button once when the fryer
is on. The test results will be displayed in the controller’s LED panel in minutes and seconds. The maximum
acceptable recovery time for BIGL30 series gas fryers is two minutes and twenty-five seconds (2:25).
1.10.5 Filtration Malfunctions
The majority of filtration problems arise from operator error. One of the most common errors is placing the
filter pad on the bottom of the filter pan rather than over the filter screen.
Whenever the complaint is “the pump is running, but no oil is being filtered,” check the installation of the
filter pad, including that the correct size is being used. While you are checking the filter paper/pad, verify
that the O-rings on the filter pan suction tube are present and in good condition. Missing or worn O-rings will
allow the pump to suck air and decrease its efficiency.
If the pump motor overheats, its thermal overload will
trip and the motor will not start until it is reset. If the
pump motor does not start, press the red reset switch
located on the front of the motor. If the pump then
starts, something caused the motor to overheat. It may
be that several frypots in a large battery of fryers were
being filtered one after the other and the pump became
hot. Letting the pump cool down for at least a halfhour is all that is required in this case. More often, the
pump overheated for one of the following reasons:
Shortening that remained in the pan, after
previous filtering, solidified in the suction
tube recess in the bottom of the pan or the
suction tube, itself. Adding hot oil to the pan and waiting a few minutes will usually correct this
problem. A flexible wire can be used to clean out the suction tube and the recess in the bottom of the
pan. NEVER use compressed air to blow solidified shortening out of the suction tube!
FLOW
FREEING A SEIZED PUM P
Sediment Particle
Up fo r re v e rse
Down for forward
1-20
Room temperature oil was filtered. Cold oil is thicker and causes the pump motor to work harder and
overheat.
If the motor hums but the pump does not rotate, there is a blockage in the pump. Incorrectly sized or installed
paper will allow food particles and sediment to pass through the filter pan and into the pump. When sediment
enters the pump, the gears can bind up and cause the motor to overload, tripping the thermal overload.
Solidified shortening in the pump will also cause it to seize, with similar results.
A pump seized by debris or hard shortening can usually be freed by manually moving the gears with a
screwdriver or other instrument as illustrated on the previous page. Make sure power to the pump motor is
off before trying this.
1. Disconnect power to the filter system.
2. Remove the input plumbing from the pump.
3. Use a screwdriver to manually turn the gears.
Turning the pump gears backwards will release a hard particle and allow its removal.
Turning the pump gears forward will push softer objects and solid shortening through the pump and
allow free movement of the gears.
Filter paper/pads that are installed incorrectly will also allow food particles and sediment to pass through and
clog the suction tube recess on the bottom of the filter pan or the suction tube, itself. Particles large enough to
block the suction tube recess or the suction tube may indicate that the crumb tray is not being used.
1.10.6 Leakage
Leakage of the frypot is usually due to improperly sealed high-limit thermostats, RTD’s, temperature probes,
and drain fittings. When installed or replaced, each of these components must be sealed with Loctite
®
PST56765 sealant or equivalent to prevent leakage. In very rare cases, a leak may develop along one of the
welded edges of the frypot. When this occurs, the frypot must be replaced.
If the sides or ends of the frypot are coated with oil, the most likely cause is spillage over the top of the frypot
rather than leakage.
The clamps on the rubber boots that hold the drain tube sections together may loosen over time as the tubes
expand and contract with heating and cooling during use. Also, the boot itself may be damaged. If the
section of drain tube connected to the drain valve is removed for any reason, ensure that its rubber and clamps
are in good condition and properly fitted around the drain tube when it is reinstalled. Also, check to ensure
that the drain tube runs downward from the drain along its whole length and has no low points where oil may
accumulate.
1.11 Troubleshooting Guides
The troubleshooting guides on the following pages are intended to assist service technicians in isolating the
probable causes of equipment malfunctions by following a logical, systematic process. An additional set of
operator troubleshooting guides are contained in Chapter 7 of the BIGL30 Series Installation and Operation
Manual. It is suggested that service technicians thoroughly familiarize themselves with both sets.
1-21
1.11.1 Troubleshooting the 24 VAC Circuit
Prior to checking for problems associated with the 24 VAC circuit, ensure that the unit is connected to a
power supply, the drain valve is fully closed, and the controller is on and is calling for heat (green dot appears
under heat indicator and display toggles between LOWTEMP).
NOTE: All voltage measurements must be made within 4 seconds of the unit calling for heat. If unit does not
fire within 4 seconds, ignition modules will lock out and controller must be turned off, then on to reset.
The following processes will assist you in troubleshooting the 24 VAC circuit and ruling it out as a probable
cause:
24 VAC is not present on the interface board J3 pin 9 (LED 5 (GV)).
1. If LED 3 is not continually lit, the probable causes are a failed 24 VAC transformer or failed wiring
between the transformer and interface board.
2. If LED 3 is continually lit, check the right PWR terminal (LED 4) for 24 VAC.
check the left PWR terminal (LED 2) for 24 VAC.
Verify that the F2 fuse is not blown.
a. If 24 VAC is not present, the probable cause is a failed interface board, blown fuse or a defective
heat relay.
b. If 24 VAC is present, check for 24 VAC on V1S
(or V1D and V2D, if dual unit)..
i. If 24 VAC is not present, check the fuses. If they are good, the probable causes are failed
ignition module(s) or a failed interface board. Replace the questionable ignition module with
one known to be good to isolate the cause.
ii. If 24 VAC is present, the probable cause is a failed interface board.
24 VAC is present on interface board J3 pin 9 (LED 5 (GV))
(GV)).
and, on dual units, on J1 pin 9 (LED 1
1. If 24 VAC is not present across the gas valve main coil (MV terminals), probable causes are an open
high-limit thermostat or a failed wire between the interface board and gas valve. Be sure to check
both valves on dual units.
Check continuity of high-limit thermostat. If reading is zero, problem is in wiring.
2. If 24 VAC is present across the gas valve main coil (MV terminals), the 24 VAC circuit is working
and the problem may be with the gas valve. Be sure to check both valves on dual vat units.
Ensure drain valve is closed and that it has continuity. If reading is zero, problem is in wiring.
On dual units, also
1-22
1-23
1.11.2 Troubleshooting the Gas Valve
Prior to checking for problems associated with the gas valve, ensure that the unit is calling for heat. Also, for
non-CE units, verify that the gas valve is in the ON position.
The following processes will assist you in troubleshooting the gas valve and ruling it out as a probable cause:
If 24 VAC is not present across gas valve main coil, the probable cause is the 24 VAC circuit. Refer to
the 24 VAC circuit troubleshooting guide.
If 24 VAC is present across gas valve main coil, check the incoming gas pressure and compare to the
tables on page 2-4 of the Installation and Operation manual.
1-24
1. If incoming gas pressure is not correct, the probable cause is the gas supply to fryer.
2. If incoming gas pressure is correct, check the burner manifold gas pressure and compare it to the
tables on page 2-7 of the Installation and Operation manual.
a. If burner manifold gas pressure isnot correct, the probable cause is an improperly adjusted or
failed gas valve. Adjust the valve by following the procedure “Check Burner Manifold Pressure”
in Section 1.7 of this manual. If the valve cannot be adjusted, replace it.
b. If outgoing gas pressure is correct, the gas valve is okay.
1.11.3 Troubleshooting the Temperature Probe
CAUTION
Disconnect the controller before testing temperature probe resistances to avoid
invalid readings
Prior to checking for problems associated with the temperature probe, inspect the probe body for damage
while it is still in the frypot. Remove and replace the probe if it is bent, dented, or cracked. Also, inspect leads
for fraying, burning, breaks, and/or kinks. If found, replace the probe.
The following processes will assist you in troubleshooting the temperature probe and ruling it out as a
probable cause:
Before testing the probe, determine the temperature of the cooking oil using another thermometer or
pyrometer placed at the tip of the questionable probe.
If resistance through J3 pins 2 and 6 (J1 pins 2 and 6 for left side of dual unit) is not approximately
equal to that given in the Probe Resistance Chart for the corresponding temperature, the probe has
failed and must be replaced.
If resistance through J3 pins 2 and 6 (J1 pins 2 and 6 for left side of dual unit) is approximately
equal to that given in the Probe Resistance Chart for the corresponding temperature, measure the
resistance through each of the previously tested pins to ground.
1. If resistance is not 5 mega-Ohms or greater in each pin, the probe has failed and must be replaced.
2. If resistance is 5 mega-Ohms or greater in each pin, the probe is okay.
1.11.4 Replacing the Transformer, Reset Switch or Filter Relay
Disconnect the fryer from the electrical power supply. Remove the cover from the transformer box in the rear
of the fryer to expose the interior of the transformer box. Replace the transformer or filter relay marking the
wires to ease reassembly. Once replaced, reconnect the power. When replacing a filter relay in the
transformer, ensure the 24VAC relay (8070012) is used.
1-25
1.12 Probe Resistance Chart
Probe Resistance Chart
For use with BIGL30 Series fryers manufactured with Minco Thermistor probes only.
The control power reset switch, is a momentary rocker switch located
below the left control box (see Figures 6), that resets all power to all the
controllers and boards in the fryer. It is necessary to reset all power after
replacing any controller or board. Press and hold the switch for at least
ten seconds when resetting the control power to ensure power has
sufficiently drained from boards.
Figure 6
1-26
1.14 Controller Service Procedures
1.14.1 Controller Troubleshooting
Problem Probable Causes Corrective Action
A. No power to the fryer.
B. Power switch turned off.
C. Loose fuse holder.
No Display on
Controller.
M3000 display shows
filter busy.
D. Controller has failed.
E. Damaged controller wiring harness.
F. Power supply component or interface
board has failed.
A. Another filtration cycle is still in
process.
A. Verify controller power cord is
plugged in and that circuit breaker
is not tripped.
B. Some fryers have a rocker power
switch inside the cabinet below the
controller. Ensure the switch is
turned on.
C. Ensure fuse holder is screwed in
properly.
D. Swap the controller with a
controller known to be good. If
controller functions, replace the
controller.
E. Swap with a harness known to be
good. If controller functions,
replace the harness.
F. If any component in the power
supply system (including the
transformer and interface board)
fail, power will not be supplied to
the controller and it will not
function.
A. Wait until the previous filtration
cycle ends to start another filtration
cycle. This may take up to one
minute. If filter busy is still
displayed with no activity, remove
and restore ALL power to the fryer.
M3000 display shows
RECOVERY
FAULT.
M3000 display is in
wrong temperature
scale (Fahrenheit or
Celsius).
Recovery time exceeded maximum time
limit for two or more cycles.
Incorrect display option programmed.
Silence the alarm by pressing the
button. Check that fryer is heating
properly. Maximum recovery for
electric is 1:40.
Fryers using the M3000 controller can
toggle between F° to C° by pressing and
holding the
and simultaneously
for TEN seconds; three chirps sound.
The computer displays TECH MODE.
displays OFF. Turn the controller on
to check temperature. If the desired
scale is not displayed, repeat.
Enter 1658. The controller
1-27
Problem Probable Causes Corrective Action
M3000 displays
SERVICE
REQUIRED followed
by the error.
M3000 display shows
hot-hi-1.
M3000 display shows
HI-LIMIT.
Controller displays
LOw temp with an
alarm.
M3000 display shows
low temp,
indicator cycles on and
off normally but fryer
M3000 display shows
TEMP PROBE
M3000 display shows
PROBE FAILURE
with alarm sounding.
Controller will not go
into program mode or
some buttons do not
M3000 display shows
M3000 display shows
FAILURE with
alarm sounding.
Heating indicator is
on, but fryer is not
heating
does not heat.
FAILURE.
actuate.
HI 2 BAD.
HEATING
heating.
Press YES to silence alarm. The error
is displayed three times. See list of
issues in section 1.14.3. Fix issue. The
computer displays SYSTEM
An error has occurred.
Frypot temperature is more than 410ºF
(210ºC) or, in CE countries, 395ºF
(202ºC).
Controller in high-limit test mode.
Frypot temperature has dropped more than
40°F (17°C) for M3000 controllers below
setpoint in idle mode or 45°F (25°C) in
cook mode.
A. Failed controller.
B. Damaged controller wiring harness.
Problem with the temperature measuring
circuitry including the probe.
Damaged controller wiring harness or
connector.
Failed controller. Replace controller
ERROR FIXED? YES/NO.
Press YES. Computer displays
ENTER CODE. Enter 1111 to clear
error code. Pressing NO will allow the
fryer to cook but the error will be
redisplayed every 15 minutes.
This in an indication of a malfunction in
the temperature control circuitry,
including a failure of the high-limit
thermostat.
This is displayed only during a test of
the high-limit circuit and indicates that
the high-limit has opened properly.
This display is normal for a short while
if a large batch of frozen product is
added to the frypot or if the fryer is not
heating properly.
A. Replace controller.
B. Replace controller wiring harness.
This indicates a problem within the
temperature probe circuitry. Check
resistance of probe, if faulty replace
probe.
Swap the controller wiring harness with
one known to be good. If problem is
corrected replace harness.
This is displayed only during a test of
Controller in high-limit test mode.
Failed controller, failed interface board,
open high limit thermostat, gas valve or
gas is turned off.
the high-limit circuit and indicates that
the high-limit has failed.
Check high limit thermostat, interface
board, controller, gas valve. Ensure the
gas valve is on.
1-28
Problem Probable Causes Corrective Action
M3000 display shows
HEATING
FAILURE and alarm
sounds, but fryer
operates normally
(false alarm).
M3000 display shows
CLOSE DRAIN
VALVE.
M3000 display shows
ERROR RM
SDCRD
M3000 display shows
CALL TECH
Failed controller.
Drain valve is open or switch is out of
adjustment or failed.
Defective SD Card. Shown only during
software updates.
Typically shown during software update.
Also may be that parameter data has been
corrupted or lost.
Replace controller.
Ensure all drain valves are completely
closed and that microswitches are
adjusted and working.
Replace card with another card.
Press the FILTER button to bypass and
continue.
1-29
1.14.2 M3000 Controller Useful Codes
To enter any of the following codes: Press and hold and simultaneously for TEN seconds; three chirps
sound. The computer displays TECH MODE. Enter the codes below to perform the function.
1658 – Change from F° to C° The computer displays off. Turn the computer on and check
temperature to see the temperature scale. If the desired scale is not displayed, repeat.
3322 – Reset Factory Menu The computer displays COMPLETE and then off. (NOTE:
This will delete any hand-entered menu items).
1650 – Enter Tech Mode. See page 1-36 to reset passwords and change filter pad time.
1212 – Switch between Domestic Menu and International Menu. The computer displays
COMPLETE and then off. (NOTE: This will delete any hand-entered menu items).
9988. Computer display switches to off. Remove and then restore power to the computer
using the 20-pin plug.
The following codes are entered when prompted to do so or from an energy misconfigured exception error.
1111 – Reset SERVICE REQUIREDMessage – Enter when the issue is fixed and
prompted to enter.
1234 – Enter SETUP MODE (This usually can be done without pressing the filter buttons if an
error is displayed.)
PASSWORDS
To enter level one, level two passwords: Press and hold the TEMP and INFO buttons simultaneously until
level 1 or level 2 is displayed. Release the buttons and ENTER Code appears.
1234 – Fryer Setup, Level One and Level Two
4321 – Usage Password (resets usage statistics).
1.14.3 Service Required Errors
A SERVICE REQUIRED error alternating with YES displays on the computer. After YES is pressed the
alarm is silenced. The computer displays an error message from the list below three times with the
location of the error. Then the computer displays SYSTEM ERROR FIXED? YES/NO. If yes is chosen,
enter code 1111. If NO is chosen the system returns to cook mode for 15 minutes then redisplays
error until issue is fixed.
1-30
1.14.4 Error Log Codes
Code ERROR MESSAGE
E03 ERROR TEMP PROBE FAILURE TEMP Probe reading out of range
E04 HI 2 BAD High limit reading is out of range.
E05 HOT HI 1
E06 HEATING FAILURE A component has failed in the high limit circuit
E08 ERROR ATO BOARD ATO board connection lost; ATO board failure
E17 ERROR ATO PROBE ATO RTD reading out of range
E20 INVALID CODE LOCATION SD card removed during update
E21 FILTER PAPER PROCEDURE ERROR
(Change Filter Paper)
E22 OIL IN PAN ERROR Oil may be present in the filter pan.
E25 RECOVERY FAULT Recovery time exceeded maximum time limit.
E27 LOW TEMP ALARM Oil temperature has dropped 40°F (17°C) below
High limit temperature is past 410°F (210°C), or
in CE countries, 395°F (202°C)
such as controller, interface board, contactor,
gas valve, failure to light, open-high limit or gas
is off.
25-hour or customer-set timer has expired and
the user has pressed “NO” twice at the
“CHANGE FILTER PAPER” prompt.
Recovery time should not exceed 1:40 for
electric.
setpoint temperature in idle mode or 45°F (25°C)
in cook mode. (This message may appear if a
product is dropped and the start cook button is
not pressed immediately or if too large of cook
loads are dropped.)
EXPLANATION
1-31
1.14.5 M3000 Controller Menu Summary Tree
Reflected below are the major programming sections in the M3000 and the order in which
submenu headings will be found under the sections in the Installation and Operation Manual.
Adding New Product Menu Items See section 2.10.2 in the M3000 Controller manual
1-32
1.14.6 M3000 Controller Pin Positions and Harnesses
Updating the software takes approximately 30 minutes. The software only needs to be loaded in ONE controller,
typically the far left controller in a battery and it will replicate to all the controllers and boards in the system. Press the
TEMP button to check current M3000 software version. Remove the bezel by removing the screws under the bottom of
the bezel. Remove the two screws securing the controller allow it to swing down. Remove the two screws on the left
side cover plate of the M3000 controller or far left controller in a battery.
To update the software, follow these steps carefully:
Left Display Right Display Action
OFF OFF
UPGRADE IN
WAIT
PROGRESS
CC
UPDATING
BOOT
PERCENTAGE
COMPLETE
BLANK
CALL TECH
UPGRADE IN
WAIT
PROGRESS
IF_COOK
HEXand
PERCENTAGE
COMPLETE
IF_aTO HEX
REMOVE SD
100
CARD
CYCLE
BLANK Cycle the control power using the hidden reset switch under the far left control
POWER.
BOARD ID
Zero or a number
from 1-4
System
BIGL30
type
System
BIGL30 Press . Ensure correct fryer type is displayed.
type
TYPE
TYPE
GL30 Press the or to select proper fryer model. One of several fryer models may
GL30 Once proper fryer model is displayed, press .
With the controller folded down, insert the SD card, with the contacts facing
down and the notch on the bottom right (see Figure 7 and 8), into the slot on the
left side of the M3000 controller. ENSURE THE CARD IS FULLY
INSERTED INTO THE SD CARD SLOT.
None required.
None required.
None required.
If this message is displayed, press the FILTER button and the software load will
continue.
None required.
None required.
Remove the SD card using the fingernail slot on the top of the SD card.
box. ENSURE THE SWITCH IS HELD FOR 10 SECONDS.
Press the IO (Power) button.
Press the or to choose correct fryer type. BIGL30 (Frymaster)
be displayed.
EXIT EXIT
OFF OFF
Press the
With the controller displaying OFF, VERIFY software update by pressing
the TEMP button to check updated M3000 version on each controller.
M3000 should display software version shown on SD card on all controllers .
OFF OFF
Once the software has been updated and the versions are correct, replace the
cover and screws covering the SD card slot. Replace the screws attaching the
controller and replace the bezel and screws.
OFF OFF
Using the menu on page 1-31, perform fryer setup under Level 1.
(check) button.
Figure 7 Figure 8
1-34
1.16 Principal Wiring Connections
1-35
1.17 Wiring Diagrams
1.17.1 BIGL230/430 Wiring
1-36
1.17.2 BIGL330 Wiring
1-37
1.17.3 BIGL430 Extra Transformer Box Wiring
1-38
1.18 Simplified Wiring Diagrams
1.18.1 BIGL30 Series Full Vat Single Spark Module
TD
HV
Y
D
A
O
L
O
E
H
R
LINE
VOLTAGE
RIGHT IGNITION
MODULE
GND
25V+
M
ALAR
J3
TEMP
PROBE
BLOWER
GV
24V
12V
621291185431
HIGH
LIMIT
AIR
SWITCH
OPTIONAL
LED 5
R-GV
F2
FUSE
12V
LED 3
LED 6
24V
R
PWR
R-
HEAT
LED 4
F1
K3
VALVE
BNR
GND
V1S
ALARM
HEAT
RELAY
AIR
L
HEAT
LED 2
L
ALARM
PWR
V2S
IGNITOR
RIGHT
SD
11
4
13
14
10
1K
47K
1/50
A
5
3
1
2
LINE VOLTAGE
J2
11
4
HEAT
13
14
10
5
3
1
2
12 VDC
POWER
24 VAC
12 VAC
PROBE CIRCUIT
SOUND DEVICE CIRCUIT
T
M
TROUBLE
ON/
OFF
BIGL30 SERIES – FULL-VAT – SINGLE SPARK MODULES
AIR SWITCH ONLY ON CE
AND SOME EXPORT UNITS
LEFT IGNITION
MODULE
ALARM
25V+
VALVE
GND
T
GND
BNR
HV
D
IGNITOR
LEFT
1-39
1.18.2 BIGL30 Series Dual Vat Single Spark Module
N
O
I
T
T
A
V
L
A
U
D
–
S
E
I
R
I
N
G
E
I
L
T
U
H
D
G
I
R
d
t
o
e
t
r
o
6
u
n
e
9
t
l
/
c
e
b
6
a
s
a
f
e
c
u
s
u
r
i
l
r
F
n
o
p
e
f
a
1
y
p
e
r
m
a
b
F
f
3
E
B
P
O
M
R
E
P
T
R
E
W
O
L
B
L
A
H
N
C
R
O
T
I
I
I
A
T
W
P
S
O
V
G
J
6
R
2
E
S
1
U
F
F
2
1
1
1
4
E
2
S
V
F
U
8
V
4
2
T
H
I
G
M
I
I
H
L
9
V
3
2
1
1
5
4
F
2
V
G
R
+
O
V
M
5
R
M
2
A
L
A
R
R
W
P
T
4
A
D
E
E
H
L
3
R
I
D
A
E
L
5
D
E
L
V
2
1
t
o
n
D
E
L
R
I
A
6
D
E
L
D
T
H
V
D
E
D
N
G
Y
T
A
2
A
L
K
E
E
H
R
e
r
s
o
r
f
e
e
y
b
r
f
d
o
e
t
r
u
e
t
l
c
b
a
a
f
c
u
i
l
n
6
p
a
9
p
/
m
a
6
R
N
V
N
G
L
B
A
V
M
D
R
1
V
A
L
A
0
K
5
7
/
4
1
E
S
0
3
L
G
Y
D
I
A
O
L
O
E
H
B
R
E
G
A
T
E
L
N
O
I
V
L
T
9
H
V
I
G
G
M
I
I
H
L
8
4
E
B
P
O
M
R
E
P
T
Y
E
L
M
N
O
O
S
H
D
C
N
T
I
A
W
E
S
C
R
N
I
O
A
6
2
1
J
S
T
I
N
U
T
R
O
P
X
E
1
V
D
G
E
L
L
0
K
5
7
/
4
1
Y
T
A
A
L
E
1
E
H
K
R
2
T
-
D
A
L
E
E
L
H
R
L
W
P
M
R
A
L
N
O
I
T
I
N
G
I
T
F
E
L
+
A
E
L
U
D
O
M
D
V
N
5
2
G
D
2
V
E
V
R
D
L
N
N
A
B
G
V
V
H
D
T
R
O
T
T
H
I
N
G
I
G
R
I
D
S
2
J
1
1
1
1
3
3
1
1
4
4
1
1
4
A
K
1
A
K
1
M
R
A
L
A
4
0
0
1
1
5
5
3
3
1
1
2
2
2
2
1
1
6
6
4
4
1
1
5
5
1
1
R
O
T
T
I
F
N
E
G
L
I
T
I
U
C
E
R
I
G
C
A
C
T
E
D
L
C
4
I
V
O
V
E
N
I
L
T
A
E
H
2
V
2
E
1
D
D
N
U
O
S
T
T
I
U
C
R
I
C
C
2
C
A
A
1
E
V
V
B
O
R
P
M
‘
E
L
B
U
O
R
T
R
E
W
O
P
R
E
W
O
P
T
A
E
H
F
F
O
/
N
O
F
F
O
/
N
O
E
L
B
U
O
R
T
M
T
1-40
1.18.3 BIGL30 Series Data Network Flowchart
J7
Left M3000
120 O Pins 2 & 3
NOTE: Pins 2 & 3 can
be tested on any plug
throughout the system
and should read 120O.
Unplug one end of the
harness and meter for
120O.
The data network plugs
on the boards can be
swapped. (ie. J6 and
J7 on the M3000)
Right M3000
J6
3-wire harness
J7
Middle
M3000
J6
3-wire harness
J7
J6
3-wire harness
J203
3-wire harness
Turn each computer to OFF. Press the TEMP
button on each computer and verify ALL software
versions are present (M3000 and optional LON). A
missing version may indicate an open connection.
Harness
Function
Pin#
1GroundBlack
2CAN LoRed
3CAN HiWhite
4
5
6
Voltage
NOT USED
WireColor
LON Board
(Optional)
120 O Pins 2 & 3
J202
1-41
1.18.3 BIGL30 Series Data Network Flowchart without LON
1-42
MANUAL LOV SERIES GAS FRYERS
CHAPTER 2: PARTS LIST
2.1 Accessories
ITEM PART # COMPONENT
1 810-2793Hanger, Basket
* 809-0171Thumbscrew, ¼-20 X 1⅜-inch Universal Hood (use 809-0921 for Spacer)
Cover, Full-Vat Frypot (use 106-8931 for Dual-Vat Cover)
Rack, Full-Vat Basket Support (use 803-0372 for Dual-Vat Basket Support)
2.2 Doors, Sides, Flue Caps, Top Caps and Casters
2-1
2.2 Doors, Sides, Flue Caps, Top Caps and Casters cont.
ITEM PART # COMPONENT
1 2317908Side, Standard Cabinet Left SS
2 2327908Side, Standard Cabinet Right SS
3 8101105Magnet, Door (vertical) (use 8102346 for horizontal over filter pan)
4 1064397
5 2304960Handle, Eurolook Door
6 1064067 Pin Assy, Door
* 8100275 Spring, Door Pin
* 2307192Hinge, Door Lower
* 2108288 Panel, Universal Door
* 2206097 Holder, Manual
7 8100327Caster 4” without Brake
8 8100944Caster 3” with Brake
9
8237659 Two Station Fryer
8237660 Three Station Fryer
8237661 Four Station Fryer
8238101 Five Station Fryer
* Not illustrated.
Door, Left or Right (Left shown – move handle to bottom for right) (use 1080915 for Door w/ Manual Holder)
Flue Cap-Stainless Steel (Use Aluminized steel with Cap-N-Splash)
Two Station (8236666 for Alz Steel)(2302635 for Hood Strip)
Two Station (8236666 for Alz Steel)(2302635 for Hood Strip)
Three Station (8236681 for Alz Steel) (2302405 for Hood Strip)
Three Station (8239032 for Alz Steel)(Use 2302405 for Hood Strip) after 06/2014
Four Station (8236680 for Alz Steel) (Use 2302636 for Hood Strip) prior to 07/2014
Four Station (8239033 for Alz Steel)(Use 2302636 for Hood Strip) after 06/2014
Five Station (8238100 for Alz Steel) (Use 2302637 for Hood Strip) prior to 07/2014
Five Station(8239034 for Alz Steel)(Use 2302637 for Hood Strip) after 06/2014
Two Station Fryer prior to 07/2014
Two Station Fryer after 06/2014
Three Station Fryer prior to 07/2014
Three Station Fryer after 06/2014
Four Station Fryer prior to 07/2014
Four Station Fryer after 06/2014
Five Station Fryer prior to 07/2014
Five Station Fryer after 06/2014
prior to 07/2014
after 06/2014
2-2
2.3 Drain System Components
2.3.1 Drain Valves and Associated Parts
ITEM PART # COMPONENT
108-2509 Valve, Assy Drain FV or DV Left
108-2510 Valve, Assy Drain DV Right
1 809-0540Nut, ½-13 2-Way Hex Lock
2 900-2936Retainer, Nut Drain Valve
3 230-9433Handle, Drain Valve FV or DV Left
230-9434 Handle, Drain Valve DV Right
4 814-0047Cap, Vinyl Red
5 901-2348Cover, Safety Switch
6 807-4936Switch, Micro Gold Plated
7 816-0220Insulation, RF Switch
8 200-6496Support, Drain Tube
9 108-2506Bracket Assy, Drain Switch FV and DV Left
108-2537 Bracket Assy, Drain Switch DV Right
10 816-0135PKO-Ring, Round Drain Seal
11 810-1018Valve, 1¼-inch Drain with Filter
* 807-5159
* 807-5160
Harness, Drain FV (connects from drain switch to rear of M3000 controller only)
Harness, Drain DV(connects from drain switch to rear of M3000 controller only)
2-3
2.3.2 Drain Tube Sections and Associated Parts
2-4
2.3.2 Drain Tube Sections and Associated Parts cont.
ITEM PART # COMPONENT
1 823-8135Drain Tube, Dump Full-Vat Left Closed/Right End Open
2 823-8136 Drain Tube, Dump Dual-Vat Left Closed/Right End Open
3 823-8137 Drain Tube, Dump Full-Vat Left Closed Both Ends
4 823-8138 Drain Tube, Dump Dual-Vat Left Closed Both Ends
5 823-8139 Drain Tube, Dump Full-Vat Left Closed Both Ends
* 823-8130Drain Tube, Dump Full-Vat Left Closed/Right End Open
6 823-7943 Drain Tube, Dump Dual-Vat Left Closed Both Ends
* 823-8131 Drain Tube, Dump Dual-Vat Left Closed/Right End Open
7 823-4643Drain Tube, Full-Vat, Short, Open Both Ends
8 823-7905 Drain Tube, Dual-Vat, Short, Open Both Ends
9 810-3550 Drain Tube, Short, Open Both Ends
10 810-3551 Drain Tube, Long, Open Both Ends
11 823-4625Drain Tube, Short Full-Vat Left Open/Right End Closed
12 823-7906Drain Tube, Short Dual-Vat Left Open/Right End Closed
13 823-4639Drain Tube, Long Full-Vat Left Open/Right End Closed
14 823-7908Drain Tube, Long Dual-Vat Left Open/Right End Closed
15 823-4641Drain Tube, Long Full-Vat Open Both Ends
16 823-7907 Drain Tube, Long Dual-Vat Open Both Ends
17 816-0772 Sleeve
18 809-0969 Clamp
* 816-0630 Vinyl Cap
* 811-1071Tubing, ¼-inch OD Teflon Vent (sold by the foot)
19 823-7915 Guard, Filter Lid Splash
* Not illustrated.
2.4 Electronics and Electrical Components
2.4.1 Controllers and Associated Components
ITEM PART # COMPONENT
√ 1 108-5589Replacement Manual LOV M3000 Controller Gas
807-4403 Speaker SMT
√ Recommended parts.
2-5
2.4.2 Control Box
2-6
2.4.2 Control Box cont.
ITEM PART # COMPONENT
1 810-1164Block, One-Piece Screwless Terminal
2 816-0217Insulation, Terminal Block Paper
√ 3 807-3843Fuse 3A 250V
√ 4 807-5008Cable, Ignition 19” (CE)
5 807-4199Cable, 20-pin Computer to 15-pin Interface Board - SMT
6 806-6085SP Wire Assembly, Ignitor
7 108-2353 Wire Assembly, Ignition Module CE FV
* 108-1260 Wire Assembly, Ignition Module CE DV
√ 8 807-1006Ignition Module, CE
9 106-0531SP Fuse Assembly, Inline (not used on all models)
10 108-1094 Plate, Ignition Module
11 824-2091Cover, Ignition Module CE
√ 12 807-0833Relay, DPDT 5A 12VDC Latch
13 810-2243Spring, Relay Retaining
* 807-2659 Switch, Momentary (Control Power Reset, only used in far left component box)
807-1973 Terminal, Post
807-0070Terminal, Ground Lug
208/222/230/240V -12V (20VA) / 24V (50VA) Control Box
2-8
ITEM PART # COMPONENT
20
21
22
23
*
*
*
*
* Not illustrated.
√ Recommended parts.
220-3191 Cover, Large Transformer Box
823-6324Box, Large Transformer/Filter
823-7638 Box, Transformer/Filter GL30 4-Battery
220-6514 Cover, GL30 Small Transformer Box
WIR 0100 Wire Assembly, 430 (used in Items C)
WIR 0799 Wire Assembly, GL230 Transformer/Filter Box (used in Item A)
WIR 0798 Wire Assembly, GL330 Transformer/Filter Box (used in Item B)
WIR 0957 Wire Assembly, GL230/430 (used in Items A and B)
See page 2-3 for Drain Valve
Assemblies and page 2-11
through 2-14 for Frypot Assemblies
ITEM PART # COMPONENT
1
√
2
√
√ Recommended parts.
826-2900Probe, Temperature Cooking
826-1177
Thermostat, High-Limit 425F/218C
2-15
2.7 Gas Valves, Supply and Combustion System Components
2
3
21
1
1
4
5
15
17
16
14
4
13
17
19
18
20
12
6
11
BIGL30 Full Vat Gas Manifold
13
The example illustrated is typical of
15
16
(Typical)
BIGL Series Fryer Gas Manifolds.
Each manifold is assembled from
9
standard 1/2-, 3/4-, and 1-inch NPT
black iron pipe nipples, elbows,
tees, plugs, and unions, which may
be locally acquired.
Non-CE Gas Valve Assembly
(Typical)
NOTE: The gas tube and enrichment tube fittings are assembled in varying configurations depending
upon the location of the valve and whether the associated frypot is a full- or dual-vat pot.
ITEM PART # COMPONENT
√ 1 Ignitor
826-3053Natural Gas (G20, G25) (includes gasket 816-0059)
826-2994
Propane (G30, G31) (includes gasket 816-0981)
√ 2 Blower Assembly, Combustion Air (includes harness and Item 3)
108-1960 230V 50HZ RH CE (Dual Vat)
108-1959 230V 50HZ RH CE (Full Vat)
3 816-0554Cover, Blower Motor (component of all blowers listed above)
* 807-1067Harness Assembly, Blower Motor
14
13
2-16
2.7 Gas Valves, Supply and Combustion System Components cont.
ITEM PART # COMPONENT
4 Orifice, Burner
810-3861 3.26 mm Natural Gas (G20, G25) (0-4999 Ft, 0-1524 M)
810-38651.95 mm Propane/Butane (G30, G31) (0-4999 Ft, 0-1524 M)
√ 5 108-3346 Switch, Air Pressure Assembly Full Vat (812-2226 switch alone)
108-1455 Switch, Air Pressure Assembly Dual Vat (812-2141 switch alone)
√ 6 Valve, Non-CE Gas
826-1122Natural Gas (G20, G25)
826-1120Kit Natural Gas w/ flexlines and hardware
826-1123Propane Gas (G30, G31)
826-1121Kit, Propane Gas w/ flexlines and hardware
9 810-0691Tube, ⅛-inch Vent
10 806-9678SPPlug Assy, CE Gas Valve
11 813-0304Bushing, ½-inch NPT to ¼-inch NPT Flush Reducing
12 813-0700 Nipple, ¼-inch NPT x 3-inch
13 813-0302Elbow, ¼-inch Male NPT to ⅜-inch Tube 90° (used on DV valve)
14 813-0449Tee, ¼ -inch NPT Brass
15 810-3147Bushing, ¾-inch OD x ½ -inch ID NPT Flush
16 813-0340Adapter, ⅛-inch NPT to ⅛-inch Tube
17 810-3807Tube, ⅛-inch OD X 6.5-inch Enrichment
18 813-0301Tee, ¼-inch Male NPT to ⅜-inch Tube
19 810-1353Gas Line, ⅜-inch OD X 9-inch SS Flexible (Used on some split pots)
20 810-1355Gas Line, ⅜-inch OD X 15-inch SS Flexible
21 810-3435Burner, HE30, Universal
* 826-2965Conversion Kit, Natural Gas FV (G20, G25) to Propane/Butane(G30,G31)
* 826-2966Conversion Kit, Natural Gas DV (G20, G25) to Propane/Butane(G30,G31)
* 826-2967Conversion Kit, Propane/Butane FV(G30, G31) to Natural Gas (G20,G25)
* 826-2968Conversion Kit, Propane/Butane DV(G30, G31) to Natural Gas (G20,G25)
* 826-2969Conversion Kit, Natural Gas FV (G20, G25) to Prop/Butane(G30,G31) Aust /CE
* 826-2970Conversion Kit, Natural Gas DV (G20, G25) to Prop/Butane(G30,G31) Aust/CE
* 826-2971Conversion Kit, Prop/Butane FV(G30, G31) to Natural Gas (G20,G25) Aust /CE
* 826-2972Conversion Kit, Prop/Butane DV(G30, G31) to Natural Gas (G20,G25) Aust/CE
* Not illustrated.
√ Recommended parts.
2-17
2.8 Filtration System Components
2
3
1
4
5
10
6
8
9
ITEM PART # COMPONENT
1 823-8028Lid, Filter Pan
2 810-3276 Crumb Tray
3 810-3268Hold-Down Ring 11.20 x 19.10,
4 812-2025Sana Grid Filter Screen
5 108-3999 Pan, Filter
813-0568 Plug, ⅛-inch Socket Head Pipe (used with Item 5; two required)
2-Pin Female
6-Pin Female
9-Pin Female
12-Pin Female
15-Pin Female
2-Pin Male
6-Pin Male
9-Pin Male
12-Pin Male
15-Pin Male
Terminal, Female Split Pin (Pkg of 25)
Terminal, Male Split Pin (Pkg of 25)
Plug, Mate-N-Lock (Dummy Pin)
Extract Tool Pin Pusher
Pin Pusher Screwdriver Assy
SMT Pin Extractor
2-22
2.13 Fasteners
ITEM PART # COMPONENT
* 809-0429Bolt, ¼-inch – 20 x 2.00-inch Hex Head ZP Tap
* 809-0131 Bolt, ¼-inch -20 x ¾-inch Hex
* 809-0953Bolt, ¼-20 x ¾-inch Hex Head
* 807-1926Bushing, .875-inch Split
* 809-0514Capscrew, 5/16-inch-18 NC Hex
* 809-0448 Clip, Tinnerman
* 826-1351Nut Retainer, ¼-20 (Pkg. of 10 – for basket hanger thumbscrew) Std. Fluecap
* 809-0171Thumbscrew, ¼-20 x 1⅜-inch (for use on Standard Fluecap)
* 826-1366Nut, 4-40 Keps Hex (Pkg. of 25) (809-0237)
* 826-1358Nut, 6-32 Keps Hex (Pkg. of 25) (809-0049)
* 809-0247Nut, 8-32 Keps Hex
* 809-0052 Nut, 10-24 Hex
* 826-1376Nut, 10-32 Keps Hex (Pkg. of 10) (809-0256)
* 809-0766Nut, 10-32 Keps Hex SS
* 809-0581Nut, ½ NPT Locking
* 809-0020Nut Cap 10-24 NP
* 826-1372Nut Grip ¼-inch ¼-20 Hex NP (Pkg. of 10) (809-0059)
* 809-0417Nut Flange ¼-inch ¼-20 Serr
* 809-0535Nut, "T" ¼-inch-20 x 7/16 SS
* 809-0495Nut, ¼-inch - 20 Press
809-0804Nut, ¼- inch - 20 Keps Hex
* 826-1362Nut, ¼-20 Hex (Pkg. of 10) (809-0071)
* 809-0540Nut, Lock ½-inch-13 Hex 2-Way ZP
* 809-0656 Screw, 4-40 X 3/8-inch Slotted Round Head
* 826-1359Screw, 4-40 x ¾-inch Slotted Round Head (Pkg. of 25) (809-0354)
* 826-1365Screw, 6-32 x ⅜-inch Slot Head (Pkg. of 25) (809-0095)
* 809-0098 Screw, 6-32 x 1¼-inch Slotted Round Head
* 809-0357Screw, 6 x ⅜-inch Phillips Head NP
* 809-0359Screw, 8 x ¼-inch Hex Washer Head
* 809-0360Screw, 8 x ⅜-inch Hex Washer Slot Head
* 826-1371Screw, 8 x ½-inch Hex Head ZP (Pkg. of 25) (809-0361)
* 809-0364Screw, 8 x ⅝-inch Hex Washer Head ZP
* 809-0441Screw, 8 x 1½-inch Hex Washer Head
* 809-0362Screw, 8 x 1¼-inch Hex Washer Head Drill Point
* 809-0518Screw, 8-32 x ⅜-inch Hex Washer Slotted Head SS
* 809-0104Screw, 8-32 x ½-inch Slotted Head ZP
* 826-1363Screw, 8-32 x ½-inch NP (Pkg. of 25) (809-0103)
* 826-1360Screw, 10-24 x 5/16-inch Round Slot Head ZP (Pkg. of 25) (809-0024)
* 809-0123Screw, 10-24 x 3/4-inch Slotted Truss Head
* 826-1330Screw, 10-32 x ⅜-inch Slot Head SS (Pkg. of 25) (809-0117)
* 809-1003Screw, 10-32 x ⅜-inch Hex Trim Head SS
* 809-0938Screw, 10-32 x ⅝-inch Philips Truss Head
* 826-1375Screw, 10-32 x ¾-inch Hex Trim Head SS (Pkg. of 5) (809-0401)
* 809-1000 Screw, 10-32 x 1¼-inch Hex Sck C/S
* 826-1374Screw, 10 x ½-inch Hex Head (Pkg. of 25) (809-0412)
* 809-0266Screw, 10 x ½-inch Phillips Head ZP
continued on the following page
2-23
2.13 Fasteners cont.
ITEM PART # COMPONENT
* 809-0500Screw, 10 x ½-inch Hex Washer Head 410 SS
*
* 809-0123Screw, 10 x ¾-inch Slot Head
* 826-1389Screw, ¼-20 x ¾-inch Hex Head ZP (Pkg. of 10) (809-0131)
* 826-1346 Spacer, Ignition Module (Pkg. of 10)
* 810-2763Spacer, Interface Board
* 826-1340Spacer, .25-inch x 1.187-inch (Pkg. of 10)
* 810-0500Spacer, .25-inch x .9375-inch
810-2023 Spacer, .25-inch x .110-inch (Used on drain valves.)
* 200-6721 Plate, Strain Relief
* 826-1337Tab, ¼-inch Terminal (Pkg. of 5)
* 807-0070Terminal, Ground Lug
* 807-1948 Ty-Wrap
* 807-1359 Mount, Ty-Wrap
* 826-1383Washer, ¾-inch O.D. x ¼-inch I.D. ZP (Pkg. of 5) (809-0435)
* 809-0582Washer ½ NPT Locking
*
*
*
*
*
* 809-0196
* 810-1165
809-0434 Screw, 10 x ⅜-inch Hex Washer Head NP
809-0184Washer, #10 LK ZP
809-0190Washer, .625 X .275 X 40 Flat SS
809-0191Washer, Lock ¼ Spring ZP
809-0193Washer, Flat ¼ Nylon
809-0194Washer, Flat 5/16 ZP
Washer, ⅜-inch Flat
Washer, ⅜-inch Teflon
2-24
THIS PAGE INTENTIONALLY LEFT BLANK
Frymaster, L.L.C., 8700 Line Avenue, Shreveport, Louisiana 71106
TEL 1-318-865-1711 FAX (Tech Support) 1-318-219-7135
PRINTED IN THE UNITED STATES
SERVICE HOTLINE
1-800-551-8633
8196968
03/2016
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.