PRELIMINARY INSTRUCTIONS FOR INDICATION A TRIP OF THE
OVERVOLTAGE UNIT (SPD’S) ON THE FRONIUS TAURO
Publisher: Fronius International GmbH – TechSupport International
Version: 01_EN
Date: 03 / 2021
Note
In order to currently obtain information as to whether the integrated overvoltage contactors (SPDs for short) have
tripped, the display is done via a workaround. This can be done as follows.
Step 1
Connect via smartphone / tablet or laptop to the data communication board of your Fronius Tauro. You can find
out how to do this in your operating instructions.
Step 2
Go to the tab „Safety and Grid Regulations“
Step 3
Go to the tab „I/O Power Management“
03/2021 1/3

Step 4
Activate the active power function at a free rule (in the example rule 1 - IO control position 8). Depending on the
setting of the value, in this case it was set to 0% output power of the inverter, the inverter regulates its output
power.
Note to step 4
Please note that the signal line of the SPDs is connected to position 8 ex works. If you change the connection,
you must take this into account here accordingly.
In the example we reduce the active power to an output power of 0%. This ensures that you also see this behavior
very clearly in the Solar.web at Archive. Since this is a very drastic measure, you are of course free to adjust this
value for yourself.
Circuit diagram:
Example pictures: