IntroductionThank you for the trust you have placed in our company and congratulations on buying this
high-quality Fronius product. These instructions will help you familiarize yourself with the
product. Reading the instructions carefully will enable you to learn about the many different
features it has to offer. This will allow you to make full use of its advantages.
Please also note the safety rules to ensure greater safety when using the product. Careful
handling of the product will repay you with years of safe and reliable operation. These are
essential prerequisites for excellent results.
EN-US
1
Page 4
2
Page 5
IMPORTANT SAFETY
INSTRUCTIONS
SAVE THESE INSTRUCTIONS
GeneralThese operating instructions contain important instructions that must be followed during in-
stallation and maintenance of the inverter.
The inverter is designed and tested according to international safety requirements, but as
with all electrical and electronic equipment, certain precautions must be observed when installing and/or operating the inverter.
To reduce the risk of personal injury and to ensure the safe installation and operation of
the inverter, you must carefully read and follow all instructions and safety instructions in
these operating instructions.
EN-US
Safety instructions
Electrical installations
Failure to follow these instructions and other relevant safety procedures may result in voiding of the warranty and/or damage to the inverter or other property.
The following section "Safety instructions" contains various warnings. A Warning describes
a hazard to equipment or personnel. It calls attention to a procedure or practice, which, if
not correctly performed or adhered to, could result in damage to or destruction of part or
all of the inverter and/or other equipment connected to the inverter or personal injury.
All electrical installations must be carried out in accordance with the National Electrical
Code, ANSI/NFPA 70, and any other codes and regulations applicable to the installation
site.
For installations in Canada, the installations must be done in accordance with applicable
Canadian standards.
Standards and regulations ....................................................................................................................16
Declaration of conformity ......................................................................................................................16
The Fronius IG Unit in the PV System .......................................................................................................17
General .................................................................................................................................................17
Connection Options and Knockouts...........................................................................................................23
Connection Options and Knockouts......................................................................................................23
Choosing the Location ...............................................................................................................................25
Choosing the location in general...........................................................................................................25
Choosing a Location for Inside Installation ...........................................................................................25
Choosing a location for outdoor installation ..........................................................................................26
General ................................................................................................................................................27
Recommended screws for mounting plate assembly ...........................................................................27
Attaching the mounting plate - mounting height....................................................................................27
Connecting the Fronius IG to the Public Grid (AC) ....................................................................................29
General ................................................................................................................................................29
Inverter configuration for connection to grids without neutral ...............................................................29
Overview of available grids ...................................................................................................................30
Monitoring the Grid ...............................................................................................................................31
Systems with more than one inverter....................................................................................................31
AC-side terminals and grounding terminals ..........................................................................................32
Cross section of AC wires.....................................................................................................................33
DC terminals .........................................................................................................................................38
Solar module ground.............................................................................................................................38
Wire cross section of solar module strings ...........................................................................................39
5
Page 8
Connecting solar module strings...........................................................................................................39
Inserting and connecting option cards ..................................................................................................44
Data Communication and Solar Net ..........................................................................................................46
Solar Net and data interface .................................................................................................................46
Example ................................................................................................................................................46
Accessing the Menu Level ....................................................................................................................57
The Display Modes ....................................................................................................................................58
The Display Modes ...............................................................................................................................58
Selecting a Display Mode .....................................................................................................................58
Overview of Display Values ..................................................................................................................59
Display Values in "Now" Display Mode......................................................................................................60
Selecting the "Now" Display Mode........................................................................................................60
Display values in the ‘Now’ display mode .............................................................................................60
Display Values in "Day / Year / Total" Display Modes ...............................................................................62
General .................................................................................................................................................62
Selecting "Day / Year / Total" Display Mode.........................................................................................62
Display values in the ‘Day / Year / Total’ display modes ......................................................................63
The Setup Menu ........................................................................................................................................65
DAT COM .............................................................................................................................................69
TIME .....................................................................................................................................................69
STATE PS.............................................................................................................................................69
Setting and Displaying Menu Items ...........................................................................................................71
Setting Menu Items - General ...............................................................................................................71
Examples of Setting and Displaying Menu Items..................................................................................71
Setting the currency and rate................................................................................................................72
Displaying and Setting Parameters in the "DATCOM" Menu Item........................................................74
Setting Time and Date .........................................................................................................................75
Troubleshooting and Maintenance79
Status Diagnosis and Troubleshooting ......................................................................................................81
Displaying Status Codes.......................................................................................................................81
6
Page 9
Normal Operation Status Codes ...........................................................................................................81
Total Failure ..........................................................................................................................................81
Status Codes on Fronius IG with Several Power Stage Sets ...............................................................82
Class 1 Status Codes ...........................................................................................................................83
Class 2 Status Codes ...........................................................................................................................84
Class 3 status codes.............................................................................................................................85
Class 4 status codes.............................................................................................................................87
Class 5 status codes.............................................................................................................................90
Customer Service .................................................................................................................................92
Appendix93
Technical Data ...........................................................................................................................................95
Field adjustable trip points .................................................................................................................... 107
Relevant standards and directives........................................................................................................ 107
Warranty and Disposal............................................................................................................................... 108
DANGER! Indicates an immediate danger. Death or serious injury may result if
appropriate precautions are not taken.
WARNING! Indicates a possibly dangerous situation. Death or serious injury may
result if appropriate precautions are not taken.
CAUTION! Indicates a situation where damage or injury could occur. Minor injury
or damage to property may result if appropriate precautions are not taken.
NOTE! Indicates the possibility of flawed results and damage to the equipment.
IMPORTANT! Indicates tips for correct operation and other particularly useful information.
It does not indicate a potentially damaging or dangerous situation.
If you see any of the symbols depicted in the "Safety Rules," special care is required.
The device is manufactured using state-of-the-art technology and according
to recognized safety standards. If used incorrectly or misused, however, it can
cause
-injury or death to the operator or a third party,
-damage to the device and other material assets belonging to the operator,
-inefficient operation of the device
All persons involved in commissioning, maintaining and servicing the device
must
-be suitably qualified,
-have knowledge of and experience in dealing with electrical installations
and
-read and follow these operating instructions carefully
The operating instructions must always be at hand wherever the device is being used. In addition to the operating instructions, attention must also be paid
to any generally applicable and local regulations regarding accident prevention and environmental protection.
All safety and danger notices on the device
-must be kept in a legible state
-must not be damaged/marked
-must not be removed
-must not be covered, pasted or painted over
For the location of the safety and danger notices on the device, refer to the
section headed "General" in the operating instructions for the device.
Before switching on the device, remove any faults that could compromise
safety.
Your personal safety is at stake!
9
Page 12
Utilization in Accordance with
"Intended Purpose"
The device is to be used exclusively for its intended purpose.
Utilization for any other purpose, or in any other manner, shall be deemed to
be "not in accordance with the intended purpose." The manufacturer shall not
be liable for any damage resulting from such improper use.
Utilization in accordance with the "intended purpose" also includes
-carefully reading and obeying all the instructions and all the safety and
danger notices in the operating instructions
-performing all stipulated inspection and servicing work
-installation as specified in the operating instructions
The following guidelines should also be applied where relevant:
-Regulations of the utility regarding energy fed into the grid
-Instructions from the solar module manufacturer
Environmental
Conditions
Qualified Service
Engineers
Operation or storage of the device outside the stipulated area will be deemed
as "not in accordance with the intended purpose." The manufacturer is not responsible for any damages resulting from unintended use.
For exact information on permitted environmental conditions, please refer to
the "Technical data" in the operating instructions.
The servicing information contained in these operating instructions is intended
only for the use of qualified service engineers. An electric shock can be fatal.
Do not perform any actions other than those described in the documentation.
This also applies to those who may be qualified.
All cables and leads must be secured, undamaged, insulated and adequately
dimensioned. Loose connections, scorched, damaged or inadequately dimensioned cables and leads must be immediately repaired by authorized personnel.
Maintenance and repair work must only be carried out by authorized personnel.
It is impossible to guarantee that externally procured parts are designed and
manufactured to meet the demands made on them, or that they satisfy safety
requirements. Use only original replacement parts (also applies to standard
parts).
Do not carry out any modifications, alterations, etc. without the manufacturer's
consent.
Components that are not in perfect condition must be changed immediately.
Safety Measures
at the Installation
Location
10
When installing devices with openings for cooling air, ensure that the cooling air can enter
and exit unhindered through the vents. Only operate the device in accordance with the degree of protection shown on the rating plate.
Page 13
Data Regarding
Noise Emission
Values
The inverter generates a maximum sound power level of < 80 dB(A) (ref. 1
pW) when operating under full load in accordance with IEC 62109-1:2010.
The device is cooled as quietly as possible with the aid of an electronic temperature control system, and depends on the amount of converted power, the
ambient temperature, the level of soiling of the device, etc.
It is not possible to provide a workplace-related emission value for this device,
because the actual sound pressure level is heavily influenced by the installation situation, the power quality, the surrounding walls and the properties of
the room in general.
EN-US
EMC Device Classifications
EMC Measures
Grid Connection
Devices in emission class A:
-Are only designed for use in industrial settings
-Can cause line-bound and radiated interference in other areas
Devices in emission class B:
-Satisfy the emissions criteria for residential and industrial areas.
This is also true for residential areas in which the energy is supplied from the public low-voltage grid.
EMC device classification as per the rating plate or technical data.
In certain cases, even though a device complies with the standard limit values
for emissions, it may affect the application area for which it was designed (e.g.,
when there is sensitive equipment at the same location, or if the site where the
device is installed is close to either radio or television receivers). If this is the
case, then the operator is obliged to take appropriate action to rectify the situation.
High-performance devices (> 16 A) can affect the voltage quality of the grid
because of a high output current in the main supply.
This may affect a number of types of device in terms of:
-connection restrictions
-criteria with regard to maximum permissible mains impedance *)
-criteria with regard to minimum short-circuit power requirement *)
Electrical Installations
*) at the interface with the public grid
see Technical Data
In this case, the operator or the person using the device should check whether
or not the device is allowed to be connected, where appropriate through discussion with the power supply company.
Electrical installations must only be carried out according to relevant national
and local standards and regulations.
11
Page 14
Protective Measures against
ESD
Danger of damage to electrical components from electrical discharge. Suitable
measures should be taken to protect against ESD when replacing and installing components.
Safety measures
in normal operation
Safety Symbols
Disposal
Only operate the device when all safety devices are fully functional. If the safety devices are not fully functional, there is a risk of
-injury or death to the operator or a third party
-damage to the device and other material assets belonging to the operating company
-inefficient operation of the device
Safety equipment that is not fully functional must be repaired by an authorized
specialist before the device is turned on.
Never bypass or disable safety devices.
Devices with the CE marking satisfy the essential requirements of the low-voltage and electromagnetic compatibility directives. Further details can be found
in the appendix or the chapter entitled "Technical data" in your documentation.
Do not dispose of this device with normal domestic waste! To comply with the
European Directive 2002/96/EC on Waste Electrical and Electronic Equipment and its implementation as national law, electrical equipment that has
reached the end of its life must be collected separately and returned to an approved recycling facility. Any device that you no longer require must be returned to your dealer, or you must locate the approved collection and recycling
facilities in your area. Ignoring this European Directive may have potentially
adverse affects on the environment and your health!
Backup
Copyright
12
The user is responsible for backing up any changes made to the factory settings. The manufacturer accepts no liability for any deleted personal settings.
Copyright of these operating instructions remains with the manufacturer.
Text and illustrations are technically correct at the time of going to print. The
right to make modifications is reserved. The contents of the operating instructions shall not provide the basis for any claims whatsoever on the part of the
purchaser. If you have any suggestions for improvement, or can point out any
mistakes that you have found in the operating instructions, we will be most
grateful for your comments.
Page 15
General Information
Page 16
Page 17
Protection of Persons and Equipment
EN-US
Safety
Protection of Persons and Equipment
WARNING! An electric shock can be fatal. Danger from grid voltage and DC volt-
age from solar modules.
-The connection area should only be opened by a licensed electrician.
-The separate power stage set area should only be disconnected from the
connection area after first being disconnected from the grid power.
-The separate power stage set area should only be opened by Fronius-trained
service personnel.
Never work with live wires! Prior to all connection work, make sure that the AC
and DC wires are not charged.
WARNING! If the equipment is used or tasks are carried out incorrectly, serious
injury or damage may result. Only qualified personnel are authorized to install
your inverter and only within the scope of the respective technical regulations. It
is essential that you read the "Safety regulations" chapter before commissioning
the equipment or carrying out maintenance work.
The design and function of the inverter offer a maximum level of safety, both during installation as well as operation.
The inverter provides operator and equipment protection through:
a)galvanic isolation
b)monitoring the grid
Galvanic isolationThe inverter is equipped with a high frequency transformer that ensures galvanic isolation
between the DC side and the grid, thus ensuring the highest possible safety.
Monitoring the
Grid
Information on
"field adjustable
trip points"
FCC compliance
Whenever conditions in the electric grid are inconsistent with standard conditions (for example, grid switch-off, interruption), the inverter will immediately stop operating and interrupt the supply of power into the grid.
Grid monitoring is carried out using:
-Voltage monitoring
-Frequency monitoring
-Monitoring islanding conditions
The inverter is equipped with field adjustable trip points. For further information, please
contact Fronius technical support at the following e-mail address: pv-us-support@fronius.com.
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
15
Page 18
Ground fault detector / interrupter
The inverter is equipped with a ground fault detection and interruption (GFDI) circuit as required by UL 1741 and the National Electrical code.
Depending on the system configuration either the PV array’s negative or positive conductor
is connected to the grounding system in the inverter. If a ground fault occurs in the DC wiring, the inverter disconnects from the grid.
Standards and
regulations
Declaration of
conformity
Your inverter complies with the requirements for the following standards "Inverters, converters and controllers for use in independent power systems":
-UL1741
-IEEE 1547
The ground-fault detection and interruption is in compliance with NEC 690 building code
requirements.
Relevant declarations of conformity can be found in the appendix to these operating instructions.
16
Page 19
The Fronius IG Unit in the PV System
GeneralThe solar inverter is the highly complex link between the solar modules and the public grid.
Inverter
EN-US
PV array
TasksThe main tasks of the inverter include:
-Converting DC to AC current
-Fully automatic operational management
-Display function and data communication
Converting DC to
AC Current
The inverter transforms the direct current generated by the solar modules into alternating
current. This alternating current is fed into your home system or into the public grid and
synchronized with the voltage that is used there.
Main AC
Load
Center
Energymeter
Fully automatic
operation management
IMPORTANT! The inverter has been designed exclusively for use in grid-connected pho-
tovoltaic systems. It cannot generate electric power independently of the grid.
The inverter is fully automatic. Starting at sunrise, as soon as the solar modules generate
enough energy, the automatic control unit starts monitoring grid voltage and frequency. As
soon as there is a sufficient level of irradiance, your solar inverter starts feeding energy into
the grid.
The control system of the inverter ensures that the maximum possible power output is
drawn from the solar modules at all times.
This function is called MPPT (Maximum Power Point Tracking).
As dusk starts and there is no longer sufficient energy available to feed power into the grid,
the inverter shuts down the grid connection completely and stops operating. All settings
and recorded data are saved.
17
Page 20
Display function
and data communication
The display on the inverter is the interface between the inverter and the operator. The design of the display is geared towards simple operation and making system data available
as long as the inverter operates.
The inverter is equipped with a basic logging function to monitor minimum and maximum
data on a daily and a cumulative basis. These values are shown on the display.
A wide range of data communication products allows for many possibilities of recording
and viewing data.
Data Communications Components
Forced Ventilation
Power deratingShould there be insufficient heat dissipation in spite of the fan operating at maximum speed
The inverter is designed for various data communications components, e.g.:
-Data communications components that enable the inverter to communicate with external components as well as other inverters
-Datalogger and modem interface as well as an Ethernet/Internet connection (for using
a PC to record and manage data from your photovoltaic system)
-Various large-format displays
-Fronius Personal Display
-Actuators (e.g.: relays, alarms)
-Interface cards
Data communications components are available as plug-in cards.
The inverter's temperature-controlled, variable-speed fan with ball-bearing support provides:
-optimal inverter cooling
-efficiency increases
-cooler components, thus improving service life
-least possible energy consumption and lowest possible noise level
-weight reduction due to a reduction of the cooling element surface
(for example, inadequate heat transfer away from the heat sinks), the power will be derated
to protect the inverter when the ambient temperature reaches approx. 40 °C and above.
18
Derating the power reduces the output of the inverter for a short period sufficient to ensure
that the temperature will not exceed the permissible limit.
Your inverter will remain ready for operation as long as possible without any interruption.
Page 21
Installation and Startup
Page 22
Page 23
Fronius IG Installation and Connection
EN-US
Safety
Connection diagram
WARNING! An electric shock can be fatal. Danger from grid voltage and DC volt-
age from solar modules.
-The connection area should only be opened by a licensed electrician.
-The separate power stage set area should only be disconnected from the
connection area after first being disconnected from the grid power.
-The separate power stage set area should only be opened by Fronius-trained
service personnel.
Never work with live wires! Prior to all connection work, make sure that the AC
and DC wires are not charged.
WARNING! If the equipment is used or tasks are carried out incorrectly, serious
injury or damage may result. Only qualified personnel are authorized to install
your inverter and only within the scope of the respective technical regulations. It
is essential that you read the "Safety regulations" chapter before commissioning
the equipment or carrying out maintenance work.
DC +
Inverter
DC terminal block
String fuses
L3***
L2
L1
N**
DC disconnect
Grounding terminal
DC -
PV frame ground
N
L1
L2
L3
*may be required by local authorities
**may be required depending on grid configuration
***depending on inverter type
Grounding electrode terminal *
Energymeter
AC distribution
panel
Main grounding system
Lockable AC
disconnect
switch
21
Page 24
Overview‘Fronius IG installation and connection’ contains the following sections:
-Connection options and Knockouts
-Choosing the location
-Inverter installation
-Connecting the inverter to the public grid (AC)
-Connecting solar module strings
22
Page 25
Connection Options and Knockouts
Connection Options and Knockouts
(1)
(2)
EN-US
(13)
(3)(4)(6) (7)(8) (9)
ItemDescription
(1)Knockout for 1/2 in. / 3/4 in. conduit fitting (DC-cables)
(2)Knockout for 1/2 in. / 3/4 in. conduit fitting (DC-cables)
(3)Knockout for 1/2 in. / 3/4 in. conduit fitting (AC-cables)
(4)Knockout for 1/2 in. / 3/4 in. conduit fitting (AC-cables)
(5)Knockout for grounding electrode
(may be required by local authorities)
(6)Knockout for 1/2 in. / 3/4 in. conduit fitting (data communication cables)
(7)Display
(8)LED for operating status
(9)LED for GFDI status
(10)Knockout for 1/2 in. / 3/4 in. conduit fitting (data communication cables)
(11)Knockout for 1/2 in. / 3/4 in. conduit fitting (data communication cables)
(12)Air vents - Intake
(13)Air vents - Exhaust
(5)(10) (11)
(12)
23
Page 26
Connection area opened:
(14)
(15)
(16)(18)(17)(19)(20)
ItemDescription
(14)Connection area
(to be opened only by qualified electrical professionals)
(15)AC-disconnect
(16)DC-disconnect
(17)GFDI fuse
(18)Menu keysn
(19)LED for operating status
(20)LED for GFDI status
24
Page 27
Choosing the Location
EN-US
Choosing the location in general
Please note the following criteria when choosing a location for the inverter:
For use at altitudes above sea level: up to 6561 ft. (2000 m)
-Keep a minimum distance of 8 in. (20 cm) between each inverter or anything to the
right or left of the inverters such as walls or DC and AC disconnects.
For optimal airflow and cooling efficiency in locations with temperatures exceeding
104 °F (40 °C), the manufacturer recommends a distance of 10 - 12 in. (25 - 30 cm).
-When installing more than one inverter, keep a distance of 12 in. (30 cm) between
each inverter. In locations with temperatures exceeding 104 °F (40 °C), more than
12 inches is desirable..
The air flow direction within the inverter is from left to right (cold air intake on left, hot air
exit on right).
No objects are to be located within a distance of 6 in. around the air vents on both sides
of the inverter.
When installing the inverter in a switch panel cabinet (or similar closed environment), it is
necessary to make sure that the hot air that develops will be discharged by forced ventilation.
The inverter is designed for installation both indoors and outdoors..
Choosing a Location for Inside Installation
During certain operation phases the inverter may produce a slight noise. For this reason
it should not be installed in an occupied living area.
Do not install the inverter in:
-areas with large amounts of dust
-areas with large amounts of conducting dust particles (e.g., iron filings)
-areas with corrosive gases, acids or salts
-areas where there is an increased risk of accidents, e.g., from farm animals (horses,
cattle, sheep, pigs, etc.)
-stables or adjoining areas
-storage areas for hay, straw, chaff, animal feed, fertilizers, etc.
-storage or processing areas for fruit, vegetables or winegrowing products
-areas used in the preparation of grain, green fodder or animal feeds
-greenhouses
25
Page 28
Choosing a location for outdoor
installation
NEMA 3R protection means that the inverter is not susceptible to water spray from any
direction.
However, the manufacturer recommends, if possible, that the inverter not be exposed to
direct moisture or to a direct water jet (e.g., from sprinklers).
In order to protect the display, the inverter should not be exposed to direct sunlight. Ideally, the inverter should be installed in a protected location, e.g., near the solar modules
or under a roof overhang.
Do not install the inverter:
-where it can be exposed to ammonia, corrosive gasses, acids or salts (e.g., fertilizer
storage areas, vent openings of livestock stables, chemical plants, tanneries)
26
Page 29
Fronius IG Installation
EN-US
General
Recommended
screws for
mounting plate
assembly
Attaching the
mounting plate mounting height
IMPORTANT! Depending on the surface, different wall anchors and screws may be re-
quired for installing the wall bracket. These wall anchors and screws are not part of the
scope of delivery for the inverter. The installer is responsible for selecting the proper wall
anchors and screws.
NOTE! The inverter is designed only for a vertical installation position.
In most cases, you should use 1/4 in. or 5/16 in. stainless steel or aluminum screws capable of supporting:
-26 lbs. for Fronius IG 2000 / 3000 / 2500-LV
-42 lbs. for Fronius IG 4000 / 5000 / 4500-LV
IMPORTANT! Keep a minimum distance under the inverter corresponding to the ‘NEC
110.26 for code compliant disconnect location. If the DC disconnect is to be code compliant, it must be readily accessible (NEC 690.14 (B) (1)).
The DC disconnect is in the lower left part of the inverter. When choosing the inverter
mounting height, ensure a height that keeps the display slightly below eye level for best
possible readability of the display.
27
Page 30
Inverter Installation
As your inverter is delivered, the mounting plate is fixed to the inverter by two screws on
the bottom of the inverter.
CAUTION! Danger of injury by falling equipment. The inverter may become dislodged and fall from the mounting plate if the unit is not fixed to the mounting
plate.
Fix the inverter to the mounting plate using the two screws that were removed in
step 1.
Loosen the screws (1) on the bottom of
1
the inverter and remove the mounting
plate (2)
Triangulate the positions of the srews
2
on the mounting plate using the predrilled holes when possible
The three vertically aligned holes for
single stud mounting will suit most installations.
Fix the mounting plate (2) to the wall
3
using four suitable wall anchors (3) and
screws (4)
Attach the inverter to the bottom of the
4
mounting plate (2) by using the screws
(1), that were removed in step 1
(4)(3)
(4)
(4)(3)
(4)
(3)
(2)
(3)
(1)
NOTE! If you modify the inverter enclosure with custom openings you will be required to return the unit for repair in the event of a warranty-related issue rather
than doing an inverter exchange.
Knockouts for grounding electrode may be required by local authorities.
28
Page 31
Connecting the Fronius IG to the Public Grid (AC)
General Your inverter needs to be connected to the AC disconnect, to the DC disconnect and to the
equipment grounding according to the following steps.
AC and DC are switched separately.
EN-US
Inverter configuration for connection to grids
without neutral
The inverter comes from the factory pre-configured for grid connection with neutral.
For a connection to grids without neutral the inverter must be reconfigured by setting a
jumper in the connection area.
WARNING! An electric shock can be fatal. Danger from grid voltage and DC voltage from solar modules.
-The connection area should only be opened by a licensed electrician.
-Never work with live wires! Prior to all connection work, make sure that the
AC and DC wires are not charged.
Make sure, that the inverter is fixed
(2)
(2)(3)
(1)(2)
1
properly to the mounting plate
Open the connection area as shown in
2
the figure
Set the internal AC- and DC dis-
3
connects (1) to the "OFF" position
Remove the four screws (2) on the in-
4
verters faceplate (3)
NOTE! When removing the display faceplate covering the connection area do not pinch, bend or
strain the ribbon cable for the display.
Remove the display faceplate (3) co-
5
vering the connection area
29
Page 32
Jumper positions for neutral conductor in the grid:
(1)public grid with neutral conductor - factory setting
(Enable)
(2)public grid without neutral conductor
(Disable)
Set the jumper to the refered position
6
(2)
(1)
Overview of available grids
Inverters can be connected to the following grids:
208 V Delta : 120 V WYE240 V : 120 V Split Phase
021
208 V
(1)
208 V
120 V
V
120 V
(1)
120 V120 V
240 V
208 V
(1)
(1)
30
Page 33
240 V Delta : 120 V Stinger240 V Delta
(1)
240 V
120 V120 V
240 V
240 V
240 V
(2)
(2)
(2)
208 V DeltaJumper positions:
(1)
(2)
208 V
(2)
240 V
EN-US
240 V
(2)
(2)
Monitoring the
Grid
Systems with
more than one inverter
208 V
208 V
(2)
(2)
IMPORTANT! The resistance in the leads to the AC-side connection terminals must be as
low as possible for optimal functioning of grid monitoring.
For larger photovoltaic systems, it is possible to connect several inverters in parallel without any problems.
NOTE! The inverters Fronius IG 2500-LV and Fronius IG 4500-LV are designed
to be connected to three-phase systems. Utilities generally allow up to 6 kVA of
unbalance, but check with your utility and try to balance the installation. Try to balance the installation.
The connection to the grid should be done in the following way:
-Connect Fronius IG No. 1, No. 4, No. 7, ... to L1 and L2
-Connect Fronius IG No. 2, No. 5, No. 8, ... to L2 and L3
-Connect Fronius IG No. 3, No. 6, No. 9, ... to L1 and L3
31
Page 34
AC-side terminals
and grounding
terminals
(6)
(7)
N
(4)
(5)(1)(2)(3)
The white plastic divider that separates the AC from the DC connection area is not shown
in the figure.
(1)Grid grounding / Grounding conductor
The inverter must be connected via the grounding terminal to the AC grid grounding.
NOTE!
-Use copper wires for all grounding cables.
-Use only solid or stranded wire. Do not use fine stranded wire.
-See NEC section 250 for correct grounding.
(2)= Neutral conductor N
NOTE! The neutral conductor is not bonded to ground internally.
(3)AC disconnect
(4)Grounding of photovoltaic components (e.g., solar module frames)
The ground for photovoltaic components such as solar module frames must be
connected at the grounding terminals. The size of the wire usually corresponds to
the largest wire in the DC system.
(5)Grounding Electrode Terminal (GET)
A grounding electrode terminal may be required depending on local regulations
32
Page 35
(6)= Phase conductor L1
(7)= Phase conductor L2
EN-US
Cross section of
AC wires
SafetyOnly an authorized electrician is permitted to connect this inverter to the public grid.
WARNING! An electric shock can be fatal. Inadequately sized electrical compo-
nents can cause serious injuries to persons and damage to (or loss of) property.
-All electrical installations must be carried out in accordance with the National
Electrical Code, ANSI/NFPA 70, and any other codes and regulations applicable to the installation site.
-For installations in Canada, the installations must be done in accordance with
applicable Canadian standards.
-Use minimum AWG 12, min. 167 °F (75 °C), copper wire for the AC connection of the FRONIUS IG 2000, 3000 and 2500-LV.
-Use minimum AWG 10, min. 167 °F (75 °C), copper wire for the AC connection of the FRONIUS IG 4000, 5100 and 4500-LV.
-Use minimum AWG 14, min. 167 °F (75 °C), copper wire for all grounding
wires (see NEC table 250.122).
-Voltage drop and other considerations may dictate larger size wires be used.
-Use only solid or stranded wire. Do not use fine stranded wire.
WARNING! An electric shock can be fatal. Danger from grid voltage and DC voltage from solar modules.
The connection area should only be opened by a licensed electrician.
Never work with live wires! Prior to all connection work, make sure that the AC
and DC wires are not charged.
CAUTION! Danger of damaging the inverter due to an overload of the grid neutral
conductor.
-Do not connect 2-phase and 3-phase devices to one phase
-Never operate multiphase devices in one phase
CAUTION! Danger of damaging the inverter from improperly connected terminals. Improperly connected terminals can cause thermal damage to the inverter
and may cause a fire. When connecting the AC and DC cables, make sure that
all terminals are tightened securely using the proper torque.
33
Page 36
Removing knock-
(3)(2)(1)(4)
outs and mounting conduits
Available knockouts:
(1)Connecting plate
(2)Knockout 1/2 in. / 3/4 in. for DC cables
(3)Knockout 1/2 in. / 3/4 in. for AC cables
(4)Knockouts on inverter side 1/2 in. / 3/4 in. for AC or DC cables
CAUTION! Danger of short circuit by loose metal parts from knockouts. Loose
metal parts in the inverter may cause short circuits when the inverter is powered
up. When removing knockouts, make sure that
-no loose metal parts fall into the inverter,
-any metal pieces that do fall into the inverter are removed immediately.
1/2 in.
2
1
1/2 in.
1
Removing knockouts
Remove knockouts for AC and DC cables on the inverter side or on the inverter un-
1
1
2
3/4 in.
1
3/4 in.
derside according to the figure
34
NOTE! Procedure for removing knockouts for conduit fittings with a diameter exceeding 3/4 in.:
-Remove connecting plate (2)
-Remove knockouts
-Fix the connecting plate (2) again
NOTE! Use only water tight conduit fittings and conduits. Conduit fittings and conduits are not part of the scope of supply for the inverter.
Page 37
Connecting the
inverter to the
public grid (AC)
Insert a 1/2 or 3/4 in. conduit fitting in the knockouts labeled "AC" and fasten it
2
Insert a 1/2 or 3/4 in. conduit fitting in the knockout labeled "DC" and fasten it
3
(5)(1)(2)(3)
(4)
N
(6)
EN-US
(7)
Insert the AC cables and the grounding cables through the AC conduits into the invert-
1
er
Connect AC cables to the AC terminals L1 (6), L2 (7) and N (2)
2
Connect grounding cables to the ground terminal (4)
3
Tightening torque = 1.7 ft. lb.
NOTE! Form a min. 4 in. wire loop using all wires
Recommendation for the ACside overcurrent
protection
NOTE! To reduce the risk of fire, connect only to a circuit provided with branch
circuit overcurrent protection in accordance with the National Electrical Code,
ANSI / NFPA 70, at a MAXIMUM of:
-20A ... IG 2000 / 3000 / 2500-LV (15 A is permissible)
-30A ... IG 4000 / 5100 / 4500-LV (25 A is permissible with the IG 4000)
35
Page 38
Additional external AC and/or DC
disconnect
Depending on the installation, an additional external AC and/or DC disconnect may be required if the inverter is installed in a location not easily accessible to utility or fire personnel.
Contact your local authorities for additional information.
36
Page 39
Connecting Solar Module Strings to the Fronius IG
(DC)
EN-US
General information about solar
modules
Safety
In order to select suitable solar modules and get the most efficient use out of the inverter,
please note the following points:
-The open circuit voltage of the solar modules increases as the temperature decreases
(assuming constant irradiance). The open circuit voltage should never rise above 600
V regardless of temperature and an irradiance of 1000 W/m².
If the open circuit voltage exceeds 600 volts, the inverter may be damaged, and all
warranty rights will become null and void.
-More exact data for sizing the solar array for the particular location can be obtained
using calculation tools such as the Fronius Configuration Tool (available at http://
www.fronius-usa.com).
-See NEC table 690.7 for the appropriate code-related voltage adjustment factor for
crystalline silicon modules, or use the manufacturer’s specified voltage coefficient.
WARNING! An electric shock can be fatal. Danger due to grid voltage and DC
voltage from solar modules.
-The connection area should only be opened by a licensed electrician.
-Never work with live wires! Prior to all connection work, make sure that the
AC and DC wires are not charged.
CAUTION! Danger of damaging the inverter from improperly connected terminals. Improperly connected terminals can cause thermal damage to the inverter
and may cause a fire. When connecting the AC and DC cables, make sure that
all terminals are tightened securely using the proper torque.
37
Page 40
DC terminals
(1)
(2)
+++ -- -
Solar module
ground
DC+
The white plastic divider that separates the AC from the DC connection area is not shown
in the figure.
(1)DC disconnect
(2)DC terminal block
(3)GFDI fuse
The inverter is equipped with a ground-fault detection and interruption (GFDI) circuit as required by UL 1741 and the National Electrical code.
The array’s negative conductor is connected to the grounding system in the inverter.
WARNING! An electric shock can be fatal. Normally grounded conductors may
be ungrounded and energized when a ground fault is indicated. The ground fault
has to be repaired before operation is resumed
NOTE! Do not connect the ground to the negative DC line at any point! This is already done within the inverter. If negative DC lines are connected to the DC terminals or prior to this to the ground, this will circumvent the GFDI protection
system, preventing your inverter from properly detecting a fault current.
DC-
(3)
38
In addition, turning the DC disconnect to the OFF/open circuit condition will not
disconnect the array from ground, as it only disconnects the DC positive.
Page 41
Wire cross section of solar module strings
WARNING! An electric shock can be fatal. Inadequately sized electrical compo-
nents can cause serious injuries to persons and damage to (or loss of) property.
-All electrical installations must be carried out in accordance with the National
Electrical Code, ANSI/NFPA 70, and any other codes and regulations applicable to the installation site.
-For installations in Canada, the installations must be done in accordance with
applicable Canadian standards.
-Use minimum AWG 14, min. 167 °F (75 °C), copper wire for all grounding
wires (see NEC table 250.122).
-Use minimum AWG 14, min. 167 °F (75 °C), copper wire for the DC connection of the FRONIUS IG 2000, 3000 and 2500-LV.
-Use minimum AWG 14, min. 167 °F (75 °C), copper wire for the DC connection of the FRONIUS IG 4000, 5100 and 4500-LV
-Voltage drop and other considerations may dictate larger size wires be used.
-Use only solid or stranded wire. Do not use fine stranded wire.
NOTE! To ensure an effective strain relief device for solar module strings, only
use cable cross sections of the same size.
EN-US
Connecting solar
module strings
NOTE! Use only water tight conduit fittings and conduits. Conduit fittings and con-
duits are not part of the scope of supply for the inverter.
NOTE! Connecting the DC wiring
with the wrong polarity may cause
damage to the inverter. Check
both the polarity and the open circuit voltage.
The DC Voltage must not exceed 600 V, regardless of temperature.
39
Page 42
(1)
(2)
+++ -- -
DC+
To access the DC terminals, bend upward the white plastic divider.
It is possible to connect up to 3 PV-strings in parallel within the Fronius IG inverter.
Insert the DC cables and the grounding cables through the DC conduit into the inverter
1
Connect the DC cables to the DC terminal block:
2
-connect the positive (+) cables to the "DC+" terminals
-connect the negative (-) cables to the "DC-" terminals
Connect grounding cables to free grounding terminals
3
Tigtening torque = 1.7 ft. lb.
NOTE! Form a min. 4 in. wire loop using all wires.
DC-
(3)
40
Page 43
Commissioning
EN-US
Factory pre-set
configuration
CommissioningClose the connection area
The inverter has been pre-configured in the factory and is ready for operation.
To change your inverter settings, please see section ‘The setup menu’ in the chapter ‘Operation.’
1
If available, turn on an external AC disconnect
2
Switch AC disconnect on the inverter to the "ON" position
3
Switch DC disconnect on the inverter to the "ON" position
4
As soon as the photovoltaic modules produce sufficient power, the Operating Status LED
lights up orange.
The orange LED indicates that the feed-in mode of the inverter will begin shortly.
The screen displays the startup phase.
-Segmenttest
All display elements light up for about
one second.
-The inverter goes through a master
check list for several seconds.
The display shows ‘TEST’ and indicates the respective component that is
being tested (for example, ‘LED’).
-‘TEST COM’ is shown.
41
Page 44
-Synchronization with grid:
‘WAIT PS’ is displayed, the inverter
icon flashes: the inverter is waiting for
all power stage sets in the network to
be on stand-by. This procedure takes
place dependent on the DC voltage.
-Next, the display shows ‘SYNC AC,’
the grid icon flashes.
-Startup test:
Before the inverter starts feeding energy into the grid, the conditions of the
grid are tested in detail in accordance
with local regulations. The display
shows ‘START UP.’
-Operation of feeding energy into the
grid:
After selecting the grid and when the
tests are concluded, the inverter starts
feeding energy into the grid.
The display shows the present power
feeding into the grid.
The Operating Status LED lights up
green, and the inverter starts operating.
IMPORTANT! For more information about the startup phase, please see the chapter 'Operation', section 'Product description Fronius IG' (Startup Phase, Test Procedure).
42
Page 45
Inserting Option Cards
EN-US
Suitable option
cards
Safety
There are several options and system upgrades available for the inverter, e.g:
-Datalogger and modem interface, Ethernet/Internet connection (for using a PC to record and manage data from your photovoltaic system)
-Fronius Interface Card Easy (sends all relevant working parameters in a well defined
RS-232 protocol)
System upgrades are available as plug-in cards and as external boxes.
WARNING! An electric shock can be fatal. Danger from grid voltage and DC voltage from solar modules.
-The connection area should only be opened by a licensed electrician.
-Never work with live wires! Prior to all connection work, make sure that the
AC and DC wires are not charged.
-All electrical installations must be carried out in accordance with the National
Electrical Code, ANSI/NFPA 70, and any other codes and regulations applicable to the installation site.
-For installations in Canada, the installations must be done in accordance with
applicable Canadian standards.
WARNING! An electric shock can be fatal. Danger from residual voltage from capacitors.
You must wait until the capacitors have discharged. Discharge takes 5 minutes.
NOTE! Follow general ESD precautions when handling option cards.
43
Page 46
Inserting and
connecting option cards
When adding option cards to the inverter, please follow all inverter safety instructions and
information before opening the inverter.
Switch the AC and DC disconnect on the inverter to the OFF position
1
Open connection area
2
*
*Insert the Com Card in the left-most slot named "ENS"
**Insert any of the following cards in option slot 1 or 2:
Datalogger Card, Personal Display Card, Interface Card easy, Sensor Card
Insert option card (2) into a free slot
3
Tighten option card (2) with fastening screw (1)
4
CAUTION! Danger of short circuit by loose metal parts from knockouts. Loose
metal parts in the inverter may cause short circuits when the inverter is powered
up. When removing knockouts, make sure that
-no loose metal parts fall into the inverter,
-any metal pieces that do fall into the inverter are removed immediately.
(3)
**
(2)
(1)
(3)
44
Remove knockouts (3) for data communication cables
5
NOTE! Use only water tight conduit fittings and conduits. Conduit fittings and conduits are not part of the scope of supply for the inverter.
Insert a 1/2 or 3/4 in. conduit fitting in the knockout (3) labeled "DatCom" and fasten it
6
Page 47
Insert data communication cables through the DatCom conduit and connect them to
7
the sockets "IN" and "OUT"
IMPORTANT! When networking several DATCOM components, a termination plug must
be placed on each free IN and/or OUT connection of a DATCOM component.
Close the connection area
8
Switch the AC and DC disconnects on the inverter to the "ON" position
9
EN-US
45
Page 48
Data Communication and Solar Net
Solar Net and
data interface
Fronius developed Solar Net to make these add-on system components flexible and capable of being used in a wide variety of different applications. Solar Net is a data network
that enables several inverters to be linked with the data communications components.
Solar Net is a bus system. A single cable is all that is required for one or more inverters
to communicate with all system upgrade components.
The core of the Solar Net is the Fronius Datalogger. It coordinates data transmissions and
ensures that even large volumes of data are distributed quickly and securely.
The ‘Fronius Com Card’ is used to integrate the inverter into Solar Net.
Important Every inverter that is to be monitored using a Datalogger requires a ‘Fronius
Com Card.’ In this case, the ‘Fronius Com Card’ serves as a link between the internal network of the inverter and the Solar Net interface of the Datalogger.
Important Each inverter can have only one ‘Fronius Com Card.’ A network may only contain one Fronius Datalogger.
The first inverter with a ‘Fronius Com Card’ can be positioned up to 3280 ft. (1000 m)
away from the last inverter with a ‘Fronius Com Card.’
Different system upgrades are detected automatically by Solar Net.
In order to distinguish among several identical system upgrades, each one must be assigned a unique number.
In order to uniquely identify each inverter in Solar Net, each inverter must also be assigned an individual number.
You can assign individual numbers as per ‘The setup menu’ section in this manual.
More detailed information on the individual data communications components can be
found in the relevant operating instructions or on the Internet at http:\\www.froniususa.com.
ExampleLogging and archiving inverter and sensor data using a Fronius Datalogger and Fronius
Sensor Box:
Fronius
IG
IN
Com Card
OUT
123
Fronius
IG
PC
Com Card
Datalogger C.
OUT
RS 232
°C
Sensor Box
IN OUT
m/s
W/m²
Fronius
IG
IN
Com Card
OUT
IN
= Terminating plug
46
Page 49
Illustration explanation: Data network with 3 Fronius IG units and one Fronius Sensor Box:
-all Fronius IG units have one 'Fronius COM Card'
-one Fronius IG has a 'Fronius Datalogger Card' (no. 2)
-Fronius Datalogger has two RS-232 interfaces for connecting to a PC and a modem
Option cards communicate within the Fronius IG via its internal network. External communication (Solar Net) takes place via the 'Fronius Com Cards.' Each 'Fronius Com Card' is
equipped with two RS485 interfaces - an input and an output. RJ45 plug connectors are
used to connect to these cards.
EN-US
47
Page 50
48
Page 51
Operation
Page 52
Page 53
Product description
Controls and Indicators
EN-US
(1)
(6)
ItemFunction
(1)Display
for displaying values, settings and menus
(2)Operating Status LED
for displaying the operating status
(3)LED GFDI-Status
for displaying the GFDI status
(4)"Enter" key
for confirming a selection
(5)"Menu / Esc" key
for scrolling through menu options
for exiting the Setup menu
(5)
(2)
(4)(3)
(6)"Down/Right" key
depending on the selection:
for navigating down
for navigating right
(7)"Left/Up" key
depending on the selection:
for navigating left
for navigating up
51
Page 54
DisplayThe display unit's power is supplied via the safety-low voltage of the solar modules, which
means that the display unit can be used only in the daytime.
IMPORTANT! The inverter display is not a calibrated measuring instrument. A slight inaccuracy of a few percent is intrinsic to the system. A calibrated meter will be needed to make
calculations for the power supply company.
(1)(2)
(13)
(12)
(11)(10)
ItemFunction
(1)Icons for the "Now" display mode
(2)Icons for the "Day" display mode
(3)Icons for the "Year" display mode
(4)Icons for the "Total" display mode
(5)Icons for the "Setup" display mode
(6)Icons for operating conditions
(3)(4)(5)
(6)
(7)
(9)(8)
The value shown represents the maximum value within the period of
observation (depending on which display mode is selected).
The value shown represents the minimum value within the period of
observation (depending on which display mode is selected).
Important The minimum and maximum values displayed do not represent the absolute extreme values, because data are recorded only
at two-second intervals.
... appears when values are displayed which are directly associated
with the solar modules
... appears when values are displayed which are directly associated
with the public grid
... appears with data readings that are directly related to the inverter
... appears with data readings that are related to environmental conditions, like sunlight insolation and temperature (optional)
52
Page 55
ItemFunction
Operating Status
LED and GFDI
Status LED
... appears with data readings that are transmitted by the consumption
sensor (optional)
(7)Range for display unit
for displaying the applicable measuring unit
(8)Icon for the "Enter" key
(9)Icons for the "Menu/Esc" key
(10)Icons for the "Down/Right" key
(11)Icons for the "Left/Up" key
(12)Range for display value
for displaying the value
(13)Output bar (not active during setup)
indicates the output power fed into the grid at a given moment - regardless of the
display mode chosen. The screen displays % of the maximum possible output
power of your solar inverter
EN-US
Position of Operating Status LED (A) and
the GFDI Ststus LED (B) on the inverter
Depending on the operating status, the
Operating Status LED assumes different
colors:
(A)
(B)
Operating Status LED
(A)
Steady greenThe LED stays lit after the automatic startup phase of the invert-
Flashing greenThe photovoltaic system is working correctly, a status code is on
Steady orangeThe inverter enters an automatic startup phase as soon as the
Explanation
er as long as power is being fed into the grid.
It indicates problem-free operation of the photovoltaic system.
the display.
When a status code is shown, rectify the relevant condition by
going to the "Maintenance and Service" chapter, "Status Diagnosis and Troubleshooting" section. The status code can be acknowledged by pressing the "Enter" key.
solar modules are delivering sufficient power after sunrise.
53
Page 56
Operating Status LED
(A)
Flashes orangeA warning is shown on the display
Steady redGeneral status: the respective status code is shown on the
Remains darkThere is no connection to the solar modules,
Explanation
or
the inverter has been set to standby operation in the Setup
menu (= manual shutoff of operation).
The next day, operation will resume automatically.
During the time the LED flashes orange, operation can be resumed manually at any time (see section "The Setup Menu")
screen
no solar module power due to darkness.
GFDI Status LED
(B)
remains darkthere is no ground fault in the PV system;
lights up red-a ground fault is detected and the GFDI fuse is blown
A list of most status codes, the corresponding status information, their status causes and
repair measures can be found in the chapter "Troubleshooting and Maintenance," section
"Status Diagnosis and Troubleshooting."
Explanation
the system is working properly
-the inverter does not feed energy to the grid
-the ground fault needs to be removed and the GFDI fuse
needs to be changed
(see section "Ground fault indication" in the chapter "Status
Diagnosis and Troubleshooting")
54
Page 57
Startup Phase and Grid Feed-in Mode
Startup phaseThe inverter carries out a self test after being turned on automatically. Then a test of the
public grid is carried out. This test takes five minutes. During the startup sequence the illumination of the Operating Status LED is yellow.
Test procedure1.Segment test
All display elements light up for about one second
2.Self test of essential inverter components
-The inverter goes through a master check list for several seconds
-The display shows ‘TEST’ and indicates the respective component that is being
tested (for example, ‘LED’)
EN-US
3.Synchronization with grid:
-‘WAIT PS’ is displayed, the inverter icon flashes: The inverter is waiting for all
power stage sets in the network to be on stand-by. This procedure takes place
dependent on the DC voltage
-Next, the display shows ‘SYNC AC,’ the grid icon flashes.
4.Startup test
-Before the inverter starts feeding energy into the grid, the conditions of the grid
are tested in accordance with local regulations.
-The display shows ‘START UP.’
55
Page 58
The startup test takes five minutes. The time elapsed is indicated by a bar shrinking
from the top down.
Whenever two scale divisions stop flashing and disappear, 1/10 of the total duration
of the test is over.
Operation of
Feeding Energy
into the Grid
-Once the tests have been completed, the inverter starts feeding power into the grid.
-The display shows the present power feeding into the grid.
-The Operating Status LED lights up green, and the inverter starts operating.
56
Page 59
Navigation in the Menu Level
EN-US
Activating display
illumination
Accessing the
Menu Level
Press any key
1
The display illumination is activated.
If no key is pressed for 30 seconds, the display backlight goes out (provided that the
display illumination is set to automatic in the Setup menu).
The Setup menu also offers a choice between a permanently lit or permanently dark
display.
"Day" display mode...... Displays values for power fed into the grid during that day
"Year" display mode...... Displays values for the present calendar year - only avail-
able in combination with optional Fronius Datalogger
"Total" display mode...... Displays values for power fed into the grid since the in-
verter was started for the first time
Accessing the menu level
1
Use the "left" (7) or "right" (6) keys to
(1)(2) (3)(4)
2
select your preferred display mode (1)
- (4)
Press "Enter" (5)
3
(7)
(6)(5)
The selected display mode is shown, e.g.,
"Day" display mode.
IMPORTANT! The "Year" menu option is
supported only when the optional Fronius
Datalogger is connected. This system upgrade includes a real-time clock.
58
Page 61
Overview of Display Values
Display
mode
"Now"W-Output power
"Day"kWh / MWh-Energy fed into the grid
SymbolUnitOptionalDisplay value
V-Grid voltage
A-Output current
Hz-Grid frequency
V-Solar module voltage
A-Solar module current
°Fxsolar module temperature
--GFDI status
Wxenergy as read by consumption me-
ter
°Fxambient temperature
W/m²xirradiance
HH:MMxTime
EN-US
"Year"Currency-Return
"Total"kg / T-CO2 reduction
W-Max. output power
V-Maximum grid voltage
V-Minimum grid voltage
V-Maximum array voltage
kWh / MWhxoutput reading of consumption me-
ter
°Fxmax. solar module temperature
°Fxmin. solar module temperature
°Fxmax. ambient temperature
°Fxmin. ambient temperature
W/m²xmax. irradiance
HH:MM-Service hours completed by the in-
verter
xOptional
If the DatCom component for the required options is not available, the message
"N.A." (not available) is shown.
59
Page 62
Display Values in "Now" Display Mode
Selecting the
"Now" Display
Mode
Display values in
the ‘Now’ display
mode
(1)(2)
Select the "Now" display mode
1
The first display value in the "Now" display
mode appears
Use the "Down" (2) key to scroll to the
2
next display value
Scroll back using the "Up" key (1)
Output power
power supplied to grid at the particular
moment (Watts)
*) only for multi-phase inverters
AC grid voltage
(Volts)
*)
Output current
current supplied to the grid at the particular moment (Amperes)
*)
Grid frequency
(Hertz)
Solar module voltage
voltage of the solar array at the particular
moment (Volts)
60
Page 63
Solar module current
current supplied by solar array at the particular moment (Amperes)
Solar modul temperatur (optional Sensor Card/Box)
temperature at solar modules, temperature sensor No.1 (°F)
GFDI status
if there is no ground fault in the system
"GFDI OK" is displayed
Output reading of consumption meter
(optional Sensor Card/Box)
present power drawn from the grid (Watts)
Ambient temperature (optional Sensor
Card/Box)
Temperatur-Sensor No. 2 (°F)
EN-US
Irradiance (optional Sensor Card/Box)
the sunlight’s power per square meter
(W/m²)
GFDI status
If there is no ground fault in the system,
‘GFDI OK’ is displayed
Time (optional datalogger)
When the time on the inverter or on a datalogger is changed, this changes the time
on all devices connected via Solar Net.
OptionsIf the DatCom component for the required options is not available, the message "N.A." (not
available) is shown.
61
Page 64
Display Values in "Day / Year / Total" Display Modes
GeneralFor the inverter the day begins when it switches on. If the DC supply line is disconnected
and no Fronius Datalogger is connected, the following parameters within the display mode
‘Day’ will be reset after repeating the start-up:
-yield (currency can be selected)
-CO2 reduction (lbs.)
-maximum power supplied (Watts)
-maximum grid voltage (Volts)
-minimum grid voltage (Volts)
-energy as read by consumption meter
-operating hours for Fronius IG Plus unit
If an optional datalogger is available, the display values listed always apply for the whole
day.
Selecting "Day /
Year / Total" Display Mode
First Display Value in the "Day" Display
Mode:
(1)(2)(1)(2)
First Display Value in the "Total" Display
Mode:
First Display Value in the "Year" Display
Mode:
62
(1)(2)
Select the "Day" or
1
"Year" or
"Total" display mode
The first display value in the selected display mode appears.
Use the "Down" (2) key to scroll to the
2
next display value
Scroll back using the "Up" key (1)
Page 65
Display values in
the ‘Day / Year /
Total’ display
modes
Output energy
Energy supplied during the monitored period (kWh / MWh)
Due to the variety of different monitoring systems, there can be deviations between the
readings of other metering instruments as compared to the readings from the inverter. For
determining the energy supplied to the grid, only the readings of the calibrated meter supplied by the electric utility company are relevant.
Yield
Money earned during the monitored period (set currency and price per kWh in setup menu)
As was the case for the output energy, readings may differ from those of other instruments.
‘The Setup Menu’ section describes how to set the currency and rate for the energy supplied. The factory setting depends on the respective country-specific setting.
EN-US
CO2 reduction
CO2 emissions saved during the monitored period
(lb or T; pounds or tons)
The area for unit display switches between ‘lb’ or ‘T’ and ‘CO2.’
The CO2 meter gives an indication of CO2 emissions that would be released during the
generation of the same amount of electricity in a combustion power plant.
This factory setting for this is 1.3 lb/kWh.
Maximum output power
Highest output power during the observation period (watts)
Maximum grid voltage
Highest reading of grid voltage (V) during
the observation period
Minimum grid voltage
Lowest reading of grid voltage (V) during
the observation period
63
Page 66
Maximum solar module voltage
Highest reading of solar module voltage
(V) during the observation period
Energy consumption meter reading
(optional Sensor Card/Box and consumption sensor )
energy consumed during observation period (kWh / MWh)
Maximum solar module temperature
(optional Sensor Card/Box)
highest temperature reading at solar modules during observation period (°F)
temperature sensor No. 1
Minimum solar module temperature
(optional Sensor Card/Box)
lowest temperature reading at solar modules during observation period (°F)
temperature sensor No. 1
Maximum ambient temperature (optional Sensor Card/Box)
highest ambient temperature reading
during observation period (°F)
temperature sensor No. 2
Minimum ambient temperature (optional Sensor Card/Box)
lowest ambient temperature reading
during observation period (°F)
temperature sensor No. 2
Maximum irradiance (optional Sensor
Card/Box)
highest irradiance during observation period (W/m²)
Operating hours
Indicates how long the inverter has been
operating
(HH:MM)
Duration of operation is shown in hours and minutes up to 999 h and 59 min (display:
‘999:59’). After that only full hours are displayed.
Although the inverter does not operate during the night, all sensor data are recorded
around the clock.
OptionsIf the DatCom component for the required options is not available, the message "N.A." (not
available) is shown.
64
Page 67
The Setup Menu
PresettingThe inverter is pre-configured and ready to use. No manual control is necessary for feeding
the power it generates into the grid.
The setup menu allows easy readjustment of the inverter's preset parameters to your
needs.
EN-US
Accessing the
Setup Menu
(1)
(4)(3)(2)
Switch to the menu level (press the
1
"Menu" key)
Select the "Setup" (1) mode using the
2
"Left" (4) or "Right" (3) keys
Press "Enter" (2)
3
The Setup Menu’s first menu item "STANDBY" is shown.
65
Page 68
Scrolling through
Menu Items
Example: "STANDBY" menu itemExample: "CONTRAST" menu item
(1)(2)(1)(2)
Access the Setup menu
1
Scroll through the available menu items using the "Up" (1) and "Down" (2) keys
2
66
Page 69
Menu Items in the Setup Menu
EN-US
STANDBY
Manual activation / deactivation of Standby
operation using the "Enter" key
Unit-
Setting rangeEnter
Factory settingAutomatic operation of feeding energy into the grid (Standby
deactivated)
-The power electronics are switched off in standby mode. No power is fed into the grid.
-The Operating Status LED flashes orange.
-The orange flashing Operating Status LED stops at dusk.
-After the subsequent sunrise, the power supply operation into the grid is resumed automatically (after completion of the startup phase the LED is illuminated green).
-Grid supply operation can be resumed at any time whenever the LED is flashing orange (deactivate "STANDBY").
If the Standby mode is activated by pressing the "Enter" key, the display alternates between "STANDBY" and "Enter:"
CONTRAST
To maintain Standby operation:
-Press the "Esc" key
To end Standby operation:
-Press the "Enter" key
Contrast setting on LCD display
Unit-
Setting range0 - 7
Factory setting7
Since contrast depends on temperature, it may be necessary to adjust the "CONTRAST"
menu item when ambient conditions change.
67
Page 70
MENU MODE
‘MENU MODE‘ cannot be selected.
LIGHT MODE
Initial setting for display illumination.
Unit-
Setting rangeAUTO / ON / OFF
Factory settingAUTO
AUTO:The display illumination will stop 30 seconds after the last time
a key has been pressed.
ON:The display will remain illuminated whenever power is supplied
to the grid.
OFF:The display illumination will be permanently off.
IMPORTANT! The "LIGHT MODE" setting only relates to the display's background illumination. The LCD display will still remain on during operation. Its energy consumption is less
than one mW (1/1000 W).
CASH
IG no.
Setting of currency and rate for invoicing
the energy supplied
Unit-
Display areaCurrency / Charge rate/kWh
Factory settingUSD
Number setting (address) of the inverter in
a setup comprising multiple solar inverters
linked together
Unit-
Setting range01 - 99 (100th inverter = 00)
Factory setting1
68
Page 71
IMPORTANT! Each inverter must be assigned its own address when connecting several
inverters in a data communications system.
EN-US
DAT COM
TIME
Indicates status of data transmission, resets the Personal Display Card and Interface Card
Setting rangeDisplays OK COM or ERROR COM;
PDCD RST / IFCD RST
OK COM / ERROR COM
Displays data communication available via Solar Net or an error that occurred in data communication
PDCD RST
Resets the Fronius Personal Display Card option
IFCD RST
Resets the Fronius Interface Card option
Date and time setting
STATE PS
UnitDDMMYYYY, HH:MM
Setting rangeDate / Time
Factory setting-
IMPORTANT! The "TIME" menu item is only supported when the Fronius Datalogger option is installed.
Status display of power stage sets; the last
error that has occurred can be displayed
IMPORTANT! Due to the low level of irradiance early in the morning and in the evening,
the status codes 306 (power low) and 307 (DC low) are displayed routinely at these times
of day. These status messages do not indicate any kind of fault.
69
Page 72
VERSION
displays the version number and serial
number of the electronic components (e.g.
IG control unit and the power stage sets)
Unit-
Display areaMAIN CTRL / PS (PS00, PS01)
Factory setting-
MAINCTRLVersion information of the IG control unit (inverter controller)
PSVersion information of the power stage sets (PS00 - PS01)
70
Page 73
Setting and Displaying Menu Items
EN-US
Setting Menu
Items - General
Access the Setup menu
1
Use the "Up" or "Down" keys to select the desired menu item
2
Press the "Enter" key
3
The first digit of a value to be set flashes:
Use the "Up" and "Down" keys to se-
4
lect a value for the first digit
Press the "Enter" key
5
The second digit of the value flashes.
Repeat steps 4 and 5 until ...
6
the entire value flashes.
Press the "Enter" key
7
Repeat steps 4 - 6 for units or other
8
values to be set until the unit or value
flashes.
Press the "Enter" key to save and ap-
9
ply the changes.
The available settings are displayed:
Use the "Up" and "Down" keys to se-
4
lect the desired setting
Press the "Enter" key to save and ap-
5
ply the selection.
Press the "Esc" key to not save the
selection.
Examples of Setting and Displaying Menu Items
Press the "Esc" key to not save the
changes.
The currently selected menu item is displayed.
The following examples describe how to set and display menu items:
-Setting the Currency and Charge Rate
-Displaying and Setting Parameters in the "DATCOM" Menu Item
-Setting Time and Date
The currently selected menu item is displayed.
71
Page 74
Setting the currency and rate
Select the ‘CASH’ menu item
1
Press the ‘Enter’ key
2
The currency is display, factory setting =
‘USD’;
The first character flashes.
Use the ‘Up’ and ‘Down’ keys to select
3
a letter for the first character
Press the ‘Enter’ key
4
The second character flashes.
Use the ‘Up’ and ‘Down’ keys to select
5
a letter for the second character
Press the ‘Enter’ key
6
The third character flashes.
Use the ‘Up’ and ‘Down’ keys to select
7
a letter for the third character
Press the ‘Enter’ key
8
The set currency flashes.
Press the ‘Enter’ key
9
72
Page 75
The rate for energy supplied is now displayed in kWh / currency, factory setting = 0.14
USD / kWh;
The first digit flashes.
Use the ‘Up’ and ‘Down’ keys to select
10
a value for the first digit (e.g., 0)
Press the ‘Enter’ key
11
The second digit flashes.
Use the ‘Up’ and ‘Down’ keys to select
12
a value for the second digit (e.g., 0)
Press the ‘Enter’ key
13
EN-US
The first digit after the decimal point flashes.
Use the ‘Up’ and ‘Down’ keys to select
14
a value for the first digit after the decimal point (e.g., 4)
Press the ‘Enter’ key
15
The second digit after the decimal point
flashes.
Use the ‘Up’ and ‘Down’ keys to select
16
a value for the second digit after the
decimal point (e.g., 8)
The values that can be set range from
00.01 to 99.99.
Press the ‘Enter’ key
17
The set rate for energy supplied flashes.
Press the ‘Enter’ key
18
The currency and the rate for supplied
energy are now accepted.
Press the ‘Esc’ key to exit the ‘CASH’
19
menu item
73
Page 76
Displaying and
Setting Parameters in the "DATCOM" Menu Item
Available data connection
Select menu item ‘DATCOM’
1
Press the ‘Enter’ key
2
The following displays depend on
whether
-a data connection is available
-a data connection is faulty or an
option is not installed
If there is a data connection available, ‘OKCOM’ is shown.
Use the ‘Down’ key to select available
3
data:
e.g. Reset Personal Display Card (‘PDCDRST’) ...
... or Reset Interface Card (‘IFCDRST’)
Press the ‘Enter’ key
4
‘PDCD DONE‘...
...or...
‘IFCDDONE’ is shown
Press the ‘Esc’ key 2x to exit menu
5
item ‘DATCOM’
74
Page 77
Data connection faulty or an option is not installed
If there is a faulty data connection or options are not installed ‘ERRORCOM’ is
shown.
Press the ‘Esc’ key to exit menu item
3
‘DATCOM’
EN-US
Setting Time and
Date
Select the "TIME" menu item
1
Press the "Enter" key
2
The date is displayed (DD.MM.YYYY), the
first digit for the day flashes.
Use the "Up" and "Down" keys to
3
select a value for the first day digit
Press the "Enter" key
4
The second digit for the day flashes.
Use the "Up" and "Down" keys to
5
select a value for the second day digit
Press the "Enter" key
6
The first digit for the month flashes.
Use the "Up" and "Down" keys to
7
select a value for the first month digit
Press the "Enter" key
8
75
Page 78
The second digit for the month flashes.
Use the "Up" and "Down" keys to
9
select a value for the second month digit
Press the "Enter" key
10
The first digit for the year flashes.
Use the "Up" and "Down" keys to
11
select a value for the first year digit
Press the "Enter" key
12
The second digit for the year flashes.
Use the "Up" and "Down" keys to
13
select a value for the second year digit
Press the "Enter" key
14
The third digit for the year flashes.
Use the "Up" and "Down" keys to
15
select a value for the third year digit
Press the "Enter" key
16
The fourth digit for the year flashes.
Use the "Up" and "Down" keys to
17
select a value for the fourth year digit
Press the "Enter" key
18
76
The set date then flashes.
Press the "Enter" key
19
Page 79
The time is displayed (HH:MM), the first digit for the hour flashes.
Use the "Up" and "Down" keys to
20
select a value for the first hour digit
Press the "Enter" key
21
The second digit for the hour flashes.
Use the "Up" and "Down" keys to
22
select a value for the second hour digit
Press the "Enter" key
23
The first digit for the minutes flashes.
Use the "Up" and "Down" keys to
24
select a value for the first minutes digit
Press the "Enter" key
25
EN-US
The second digit for the minutes flashes.
Use the "Up" and "Down" keys to
26
select a value for the second minutes
digit
Press the "Enter" key
27
The set time flashes.
Press the "Enter" key to apply the time
28
Press the "Esc" key to exit the "TIME"
29
menu item
77
Page 80
78
Page 81
Troubleshooting and Maintenance
Page 82
Page 83
Status Diagnosis and Troubleshooting
EN-US
Displaying Status Codes
Normal Operation
Status Codes
Your inverter is equipped with a self diagnostic system that automatically identifies a large
number of possible operation issues by itself and displays them on the screen. This enables you to know immediately if there are any malfunctions in the inverter, the photovoltaic
system or any installation or operating errors.
Whenever the self diagnostic system has identified a particular issue, the respective status
code is shown on the screen.
IMPORTANT! Status codes may sometimes appear briefly as a result of the control response from the inverter. If it subsequently continues to operate normally, there has not
been a system error.
The open circuit voltage of the solar modules is too low.
As soon as the open circuit voltage exceeds 150 V, the inverter starts synchronizing with
the grid (display shows "SYNC AC").
The total power output of the solar modules is insufficient.
After a short time the inverter resumes grid synchronization (display shows "SYNC AC").
Total FailureIf the display remains dark for a long time after sunrise:
-Check the open circuit voltage of the solar modules at the connections of the inverter:
Open circuit voltage < 170 V ... error in the photovoltaic system
Open circuit voltage > 170 V ... may indicate a basic fault in the inverter. In this case,
notify a Fronius-trained service engineer.
81
Page 84
Ground fault indication
If a ground fault occurs in the DC cabling, the inverter disconnects from the grid.
The fault is indicated by the red ground-fault LED and the service code "434" is shown on
the display.
In this situation, the inverter is blocked from reconnection to the grid until the following actions are taken:
-Switch the AC and DC disconnect to position “OFF“ (open-circuit)
-Remove the ground fault in your photovoltaic system
-Test the GFDI fuse and replace if necessary
NOTE! When a defective fuse is changed, only replace it with a "Littlefuse KLKD
1 AMP 600V" fuse.
-Switch the AC and DC disconnect to position “ON“ (closed circuit)
Status Codes on
Fronius IG with
Several Power
Stage Sets
A special status diagnostic is run if an error occurs in an inverter with several power stage
sets.
It is also possible to call up status codes even if there is no actual error in existence. This
form of status polling may be found in the section "The Setup Menu."
Display during normal operation
When there is an error in one of the power
stage sets, the display flashes between
"STATE" and the corresponding status
code
(e.g., "STATE 515")
and
82
"ENTER"
-Press the "Enter" key twice
Page 85
-The status display of the power stage
sets "STATE PS" appears
-Press the "Enter" key
EN-US
Class 1 Status
Codes
Class 1 status codes are typically temporary. Their cause lies in the public grid.
The initial response of the inverter is to disconnect itself from the grid. The grid is subsequently checked for the stipulated monitoring period. If after the end of this period no further defect is identified, your inverter resumes operating and feeding power into the grid.
101
Grid voltage not within admissible range
BehaviorGrid voltage is thoroughly tested and as soon as it is again with-
in the permissible range, the inverter will resume feeding power
into the grid.
RemedyCheck grid connections and fuses
Should the status code persist, you should contact your system
installer
104
Grid frequency not within admissible range
BehaviorGrid frequency is thoroughly tested and as soon as it is again
within the permissible range, the inverter will resume feeding
power into the grid.
RemedyCheck grid connections, breakers and disconnect
Should the status code persist, you should contact your system
installer
107
No AC grid detected
BehaviorGrid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
RemedyCheck grid connections and fuses
Should the status code persist, you should contact your system
installer
83
Page 86
108
Islanding detected
BehaviorGrid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
RemedyShould the status code persist, you should contact your system
installer
Class 2 Status
Codes
Status codes of class 2 are typically temporary. Their cause lies in the grid.
The first reaction of the inverter is to disconnect from the grid. Subsequently, the grid will
be checked for the duration of the observation period stipulated. If after the end of this period no further defect is identified, the inverter resumes operating and feeding power into
the grid.
221
Grid voltage (L1/N) exceeds admissible limits
BehaviorAs soon as the grid voltage has returned to admissible range,
the inverter resumes feeding power into the grid.
RemedyCheck grid voltage; if the status code persists you should con-
tact your electrical contractor
222
Grid voltage (L1/N) below admissible limits
BehaviorAs soon as the grid voltage has returned to admissible range,
the inverter resumes feeding power into the grid.
RemedyCheck grid voltage; if the status code persists you should con-
tact your electrical contractor
223
Grid voltage (L2/N) exceeds admissible limits
BehaviorAs soon as the grid voltage has returned to admissible range,
the inverter resumes feeding power into the grid.
RemedyCheck grid voltage; if the status code persists you should con-
tact your electrical contractor
84
Page 87
224
Grid voltage (L2/N) below admissible limits
Class 3 status
codes
BehaviorAs soon as the grid voltage has returned to admissible range,
EN-US
the inverter resumes feeding power into the grid.
RemedyCheck grid voltage; if the status code persists you should con-
tact your electrical contractor
225
No grid voltage detected
BehaviorAs soon as the grid conditions have returned to admissible
range, the inverter resumes feeding power into the grid.
RemedyCheck grid connections and fuses; if the status code does not
disappear you should contact your electrical contractor
Class 3 comprises status codes that may
appear during feed-in operation and that do
not cause a permanent interruption of the
operation of feeding power into the grid.
After automatic disconnection from the grid and waiting for its conditions to return to those
stipulated, your inverter will try to resume feed-in operation.
301
Overcurrent (AC)
DescriptionShort interruption of power feeding into the grid due to overcur-
rent.
The inverter returns to the startup phase.
RemedyFault is rectified automatically
If this status code keeps recurring, contact your system installer
302
Overcurrent (DC)
DescriptionShort interruption of power feeding into the grid due to overcur-
rent.
The inverter returns to the startup phase.
RemedyFault is rectified automatically
If this status code keeps recurring, contact your system installer
85
Page 88
303 *
Over-temperature AC side
DescriptionShort interruption of power feeding into the grid due to over-
temperature.
The inverter returns to the startup phase.
RemedyFault is rectified automatically
If this status code keeps recurring, contact your system installer
304 *
Over-temperature DC side
DescriptionShort interruption of power feeding into the grid due to over-
temperature.
The inverter returns to the startup phase.
RemedyFault is rectified automatically
If this status code keeps recurring, contact your system installer
'POWER LOW' (306)
Intermediate circuit voltage has dropped below permissible threshold value for feed in.
This error is shown on the inverter in plain text.
DescriptionShort interruption of power feeding into the grid.
The inverter returns to the startup phase.
RemedyFault is rectified automatically
If this status code keeps recurring, contact your system installer
'DC LOW' (307)
DC input voltage is too low for feed in.
This error is shown on the inverter in plain text.
DescriptionShort interruption of power feeding into the grid.
The inverter returns to the startup phase.
RemedyFault is rectified automatically
If this status code keeps recurring, contact your system installer
*Service code 303 and 304 are shown briefly under certain circumstances. A brief
display of the service codes 303 and 304 does not mean there is a fault.
86
Page 89
Class 4 status
codes
Class 4 status codes may require the intervention of a trained Fronius service technician.
401
No internal communication with power stage set
DescriptionThe inverter will automatically attempt to connect again and, if
possible, resume feeding power into the grid
RemedyCheck grid connections and fuses
If status code persists: Contact a Fronius-trained service technician
402
Communication with EEPROM not possible
DescriptionThe inverter will automatically attempt to connect again and, if
possible, resume feeding power into the grid.
EN-US
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
403
EEPROM faulty
DescriptionThe inverter will automatically attempt to connect again and, if
possible, resume feeding power into the grid.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
406
One or both temperature sensors are defective
DescriptionThe inverter disconnects from the grid for safety reasons.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
407
Temperature sensor at cooling element defective
DescriptionThe inverter disconnects from the grid for safety reasons.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
87
Page 90
408
Direct current feed in
DescriptionThe inverter disconnects from the grid for safety reasons.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
409
No +15V supply available for the control electronics
DescriptionThe inverter does not connect to the grid.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
410
Service plug was not inserted in its original position
Description2-pole plug inserted in the wrong socket.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
412
The "fixed voltage" setting has been selected instead of MPP voltage operation and the
voltage is set to too low a value, or DC voltage exceeds allowable limits.
DescriptionFixed voltage lower than the current MPP voltage.
RemedyIf the status code persists, you should contact a Fronius-trained
service technician, or remove excess solar modules so DC voltage fits within inverter limits.
If status code persists: Contact a Fronius-trained service technician
413
Control problems
DescriptionThe inverter briefly disconnects from the grid, if AC voltage or
frequency are out of range.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
414
EEPROM faulty
DescriptionMemory deleted
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
88
Page 91
416
Communication with IG Brain not possible.
DescriptionThe Operating Status LED lights up orange, then the inverter at-
tempts a restart.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
417
Two power stage sets have the same PCB number
DescriptionThe inverter stops feeding power into the grid, the display
shows a critical error via a red Operating Status LED
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
419
Two or more power stage sets with an identical software serial number detected.
DescriptionThe inverter stops feeding power into the grid, the display
shows a critical error via a red Operating Status LED
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
421
PCB number has been set incorrectly
EN-US
DescriptionThe inverter stops feeding power into the grid, the display
shows a critical error via a red Operating Status LED.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
425
Communication with the power stage set is not possible
DescriptionThe Operating Status LED lights up orange, then the inverter at-
tempts a restart.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
434
Ground fault detected
DescriptionInverter is blocked from feeding energy into the grid.
RemedyRemove the ground fault in your photovoltaic system
Change GFDI fuse
89
Page 92
446
Internal communication error with the NL-MON plug-in card
DescriptionThe inverter will automatically attempt to connect again and, if
possible, resume feeding power into the grid
RemedyCheck grid connections and fuses;
If status code persists: Contact a Fronius-trained service technician
447
GFDI stopped grid monitoring
DescriptionIf it is possible, your inverter will resume the power feeding op-
eration after successfully completing another attempt to connect
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
448
The neutral conductor N is not connected
Class 5 status
codes
DescriptionThe inverter disconnects from the grid for safety reasons.
RemedyIf status code persists: Contact a Fronius-trained service tech-
nician
Class 5 status codes generally do not impair the operation of feeding power into the
grid. They will be displayed until the service
code is acknowledged by pressing a key
(the inverter, however, continues working
normally in the background).
-press any key
-error message disappears
501
One of the two fans is defective
DescriptionLow power generation because the temperature in the unit is
too high.
90
RemedyIf status code persists: Contact a Fronius-trained service tech-