Frigidaire FDH25J, FDD40J, FDH30J, FDD50J, FDD60J Service Manual

SERVICE MANUAL
DEHUMIDIFIER
MODELS:
1 Speed 2 Speeds
FDH25J FDD40J FDH30J FDD50J
FDD60J
P/N 5995334660 May 2000
TABLE OF CONTENTS
SAFE SERVICING PRACTICES - ALL APPLIANCES............ 3
INTRODUCTION
Uncrating ........................................................................................................................................... 4
Model & Serial Numbers .................................................................................................................. 4
Basic Operation and Initial Startup ................................................................................................. 4
Electrical Information ....................................................................................................................... 5
Compressor Information .................................................................................................................. 5
OPERATION & REPAIR INSTRUCTIONS
Bucket ................................................................................................................................................ 6
To Remove Bucket ..................................................................................................................... 6
To Remove Front Grille .................................................................................................................... 6
To Remove Top Cover ...................................................................................................................... 6
To Remove Wrapper ......................................................................................................................... 6
Control Assembly ............................................................................................................................. 7
To Remove Control Assembly................................................................................................... 7
To Remove Humidistat ............................................................................................................... 7
To Remove Full Bucket Pilot Light........................................................................................ 8
To Test Fan Speed Switch ......................................................................................................... 8
To Remove Fan Speed Switch .................................................................................................. 8
Bucket Switch ................................................................................................................................... 8
To Remove Float: ....................................................................................................................... 8
To Remove Bucket Switch ........................................................................................................ 8
To Test Bucket Switch ............................................................................................................... 9
Defrost Thermostat ........................................................................................................................... 9
To Remove Defrost Thermostat ................................................................................................ 9
To Test Defrost Thermostat ....................................................................................................... 9
Motor, Motor Bracket & Blower Wheel ........................................................................................... 9
To Remove Blower Assembly .............................................................................................. 9-10
To Test Motor ............................................................................................................................ 10
To Remove Casters......................................................................................................................... 10
Compressor ......................................................................................................................................11
Permanent Split Capacitor (PSC) Compressor ......................................................................11
Split Phase Compressor ...........................................................................................................11
To Test Compressor Motor .......................................................................................................11
Possible Causes of Compressor Overloading or Overheating ............................................ 11
Compressor Test Cord for PSC Compressor .........................................................................11
Compressor Test Cord for Split Phase Compressor ............................................................ 12
Running Capacitors ................................................................................................................. 12
To Test Capacitor...................................................................................................................... 12
Compressor Overload Protector ............................................................................................ 12
To Test Overload ...................................................................................................................... 12
To Test Relay (Split Phase Compressor)................................................................................ 12
To Replace Relay (Split Phase Compressor) ......................................................................... 12
REFRIGERANT SYSTEM SERVICE INSTRUCTIONS
Definitions ....................................................................................................................................... 13
Recovery ................................................................................................................................... 13
Recycling .................................................................................................................................. 13
Reclaim...................................................................................................................................... 13
Safety Warnings .............................................................................................................................. 13
Compressor Testing ................................................................................................................. 13
Charging Sealed Systems ....................................................................................................... 13
Soldering .................................................................................................................................... 13-14
Sealed System................................................................................................................................. 14
Sealed System Diagnosis
Undercharged System .............................................................................................................14
Overcharged System ............................................................................................................... 14
Pressure Equalizing (System Unloading) .............................................................................. 14
Refrigerant Leaks ................................................................................................................ 14-15
Component Replacement............................................................................................................... 15
Compressor Replacement ............................................................................................................. 15
To Flush The System ............................................................................................................... 15
To Use Refrigerant To Flush The System .............................................................................. 15
Installing a New Compressor ............................................................................................. 15-16
To Remove Evaporator or Capillary Tube .............................................................................. 16
To Remove Condenser ............................................................................................................ 16
Filter Dryer ................................................................................................................................ 16
Evacuating & Recharging .............................................................................................................. 16
Equipment Needed ................................................................................................................... 16
Installing Evacuation & Recharging Equipment ................................................................... 17
Evacuating System .................................................................................................................. 17
Charging The System .............................................................................................................. 17
Final Leak Test.......................................................................................................................... 17
WIRING DIAGRAMS - DATA SHEETS
Electrical Wiring Diagrams
Single Speed Fan - Models with Reciprocating Compressors ............................................ 18
Two Speed Fan - Models with Reciprocating Compressors ................................................ 19
Two Speed Fan - Models with Rotary Compressors............................................................. 20
Dehumidifier Rating Sheets
Models FDH25J & FDH30J....................................................................................................... 21
Model FDD40J........................................................................................................................... 22
Model FDD50J........................................................................................................................... 23
Model FDD60J........................................................................................................................... 24
SAFE SERVICING PRACTICES - ALL APPLIANCES
To avoid personal injury and/or property damage, it is important that Safe Servicing
Practices be observed. The following are some limited examples of safe practices:
1. DO NOT attempt a product repair if you have any doubts as to your ability to complete it in a safe and satisfactory manner.
2. Before servicing or moving an appliance:
Remove the power cord from the electrical outlet, trip the circuit breaker to the
OFF position, or remove the fuse  Turn off the gas supply  Turn off the water supply
3. Never interfere with the proper operation of any safety device.
4. USE ONLY REPLACEMENT PARTS CATALOGED FOR THIS APPLIANCE.
SUBSTITUTIONS MAY DEFEAT COMPLIANCE WITH SAFETY STANDARDS SET FOR HOME APPLIANCES.
5. GROUNDING: The standard color coding for safety ground wires is GREEN, or GREEN with YELLOW STRIPES. Ground leads are not to be used as current
carrying conductors. It is EXTREMELY important that the service technician reestablish all safety grounds prior to completion of service. Failure to do so will create a hazard.
6. Prior to returning the product to service, ensure that:
All electrical connections are correct and secure  All electrical leads are properly dressed and secured away from sharp edges,
high-temperature components, and moving parts
All non-insulated electrical terminals, connectors, heaters, etc. are adequately
spaced away from all metal parts and panels
All safety grounds (both internal and external) are correctly and securely
connected
All panels are properly and securely reassembled
WARNING
This service manual is intended for use by persons having electrical and mechnical training and a level of knowledge of these subjects generally considered acceptable in the appliance repair trade. Frigidaire cannot be responsible, nor assume any liability, for injury or damage of any kind arising from the use of this manual.
INTRODUCTION
This Service Manual may be used to service the following Dehumidifiers:
ledoMeziSlortnoCdeepSrosserpmoC
J52HDFtniP52deepS1gnitacorpiceResahPtilpS
J03HDFtniP03deepS1gnitacorpiceResahPtilpS
J04DDFtniP04oL-iH/deepS2gnitacorpiceResahPtilpS
J05DDFtniP05oL-iH/deepS2yratoRCSP *
J06DDFtniP06oL-iH/deepS2yratoRCSP *
* roticapaCtilpSyltnenamreP
Uncrating
Uncrating instructions are clearly printed on the shipping carton. See figures 4a and 4b to remove the unit from the carton.
Figure 4a
Figure 4b
Model & Serial Numbers
Model and Serial numbers are found on the Serial Plate located on the Front Panel directly behind the Bucket.
Figure 4c
rosserpmoC
rotoM
Basic Operation and Initial Startup
The Dehumidifier consists of a small refrigeration system and a fan. The fan moves the moisture-laden air over the evaporator and condenser. The moisture from the air condenses on the cold evaporator surface where it drips into a bucket. A drain hose can be connected to the bucket. The cool air then passes over the warm condenser, raising its temperature. Since this air contains less moisture and is warmer, its relative humidity is lower. This drier air is expelled through the side grille and mixes with the room air.
Place the Dehumidifier on a level surface with all four casters resting firmly on a solid floor. Since the dehumidifier draws in air through the front grille and exhausts out the left side louvers, the unit may be positioned against a wall, but care should be taken not to obstruct this air flow with furniture, walls, etc. Maintain at least 2 feet clearance at left side and front. Shut all doors and windows to the area to be dehumidified.
For the first operation, turn the Humidity Control to the MAX position. This aids moisture removal from furnishings as well as room air. When you feel a desired level of dryness has been reached, adjust the Humidity Control to your particular comfort level.
Prior to emptying the bucket, turn the Dehumidifier OFF and disconnect the power cord. This eliminates any possibility of electrical shock if you spill water, and there is a fault in the grounding system of the unit or your home wiring. Ensure the area, the Dehumidifier, and you are dry before reconnecting the power cord.
A light coating of frost on the coil is normal when the Dehumidifier is first turned "ON". Under normal conditions, it will disappear in 30 to 45 minutes. If it doesnt disappear, shut if off, and wait for it to defrost before running again.
Electrical Information
The Dehumidifier must be plugged into a 115 Volt, 60 Hz, AC only electrical outlet. The circuit should be protected by a 15 Amp circuit breaker or 15 amp time-delay type fuse.
CAUTION: If voltage varies by ±10% of 115 volts, performance of the Dehumidifier may be affected. Operating the Dehumidifier with insufficient power can damage the compressor.
The Dehumidifier power cord is equipped with a three prong grounding plug. It must be plugged directly into a properly grounded three prong receptacle. The receptacle must be installed in accordance with local codes and ordinances. A power cord about 6 feet long permits locating a unit suitably in most homes without the use of an extension cord. An extension cord can become a shock hazard if it rests on a damp floor or if water spills on it. Do not
use an extension cord or an adapter plug.
Compressor Information
There are two types of compressors used on Dehumidifiers:
gnitacorpiceRediS-woL
rosserpmoCnotsiP
roedis-wolhtiwsetareporosserpmocsihT
.llehsrosserpmocehtnihtiwerusserpnoitcus nwardsirotaropaveehtmorfropavtnaregirfeR erofebsgnidniwrotomehtloocotllehsehtotni siropaverusserphgiH.desserpmocgnieb
.resnednocehtotniyltceriddegrahcsid
:ETON gnitacorpicernahtssecorpnoitaregirferehttratsotregnolekatsrosserpmocyratoR
yratoRediS-hgiH
rosserpmoC
tnaregirfererusserpwolswardrosserpmocsihT ehtotniyltceridrotaropaveehtmorfropav siropaverusserphgiH.rebmahcnoisserpmoc
tierehwllehsrosserpmocehtotnidegrahcsid otnignissaperofebtaehrotomssecxepuskcip
.resnednoceht
ehtfoerutarepmetehtelihwtahtsinosaerehT.emitnwoddednetxenaretfasrosserpmoc
foepytrehtien,erutarepmettneibmaehtfonoitautculfehthtiwegnahcresnednocdnarotaropave
metsysehtnitnaregirferehtfollaecnis,dnA.ssamelbatserutarepmetaedivorpnacrosserpmoc
rosserpmocyrator"edis-hgih"eht,sdoirepeldidednetxegnirudllehsrosserpmocehtnisesnednoc pmupdnatnaregirferehteziropavotrosserpmocdnarotomehtybdetarenegtaehnopusdneped srewolylkciuqrosserpmocgnitacorpicer"edis-wol"eht,dnahrehtoehtnO.metsysehthguorhtti
.metsysehthguorhttipmupyletaidemmidnaretsafeziropavottignisuacdiuqilehtnoerusserpeht
CAUTION: Replacement compressors are charged with oil at the factory. Care should be exercized when replacing a compressor to avoid spilling any oil.
Rotary compressor hold down nuts must be torqued to 50 in/lbs to prevent loosening.
The motor for the Rotary compressor is a Permanent Split Capacitor (PSC ) motor with Start and Run windings. A capacitor is wired in series with the Start winding. When power is applied, the capacitor assists in bringing the compressor motor to optimum speed.
The motor for the Reciprocating compressor is a Split Phase. This compressor has a Start and Run winding, with a current activated relay or PTC (Positive Temperature Coefficient) relay. When power is applied to the Run winding (on models with current relay), the high starting current pulls the relay armature up, closing contacts, and completing the circuit to the Start winding. The motor starts and accelerates to a point where the current is reduced enough to allow the relay to drop out and disconnect the circuit to the Start winding. This point occurs at about 80% of full speed. The motor continues to accelerate to full speed on the Run winding alone. On models with PTC relay, current is applied to both windings at the same time. This starts the compressor. As current flows through the relay to the Start winding, the relay will increase in resistance . Within a fraction of a second, the resistance will climb high enough for the Start winding to drop out.
OPERATION & REPAIR INSTRUCTIONS
Bucket
The bucket is mounted to the front of the chassis and is located beneath the cooling coil to catch the condensate. A float mounted on the bucket is used to activate a switch to shut off the unit when the bucket is full of water.
If the unit is to be installed near a floor drain, a permanent drain hose may be attached to the threaded hose connection on the bucket. If you want water to flow directly into the drain, place the hose connection of the bucket directly over the drain. When using either method of draining, a plastic membrane in the hose connection of the bucket must be cut out in order to permit the water to flow into the hose or drain. To return to bucket collection, the hose connection may be closed with a standard threaded cap.
To Remove Bucket
1. Disconnect dehumidifier from electrical supply.
2. Pull bucket toward you, releasing actuator from float assembly. (See Figures 6a and 6b.)
3. Reverse procedure to complete repairs.
To Remove Front Grille
1. Disconnect dehumidifier from electrical supply.
2. Remove two screws at lower front of grille. (See Figure 6b.) Note: Bucket must be removed to gain access to these screws.
3. Remove two screws in upper holes in rear of cabinet flange. (See Figure 6d.)
4. Pull grille toward you so the two pins on each side of grille will pull free of holes in cabinet. (See Figure 6c and 6d.)
5. Pull grille down to release from top cover.
6. Reverse procedure to reassemble.
To Remove Top Cover
1. Disconnect dehumidifier from electrical supply.
2. Remove front grille.
3. Remove two screws on rear of dehumidifier holding top cover to cabinet. (See Figure 6d.)
4. Slide cover to rear to release tabs from flange.
NOTE: The Control Assembly is attached to the top cover. This must be removed before the top cover can be lifted up and off of the unit.
Figure 6a
Figure 6c
Figure 6b
Figure 6d
To Remove Wrapper
1. Disconnect dehumidifier from electrical supply.
2. Remove front grille and top cover.
3. Remove 14 screws from wrapper as shown in Figures 6e and 6f.
Figure 6e Figure 6f
4. Grasp wrapper on its left and right sides, pulling outward, then pull toward you and lift free of dehumidifier.
5. Reverse procedure to reassemble.
5. To release the Control Assembly from the top cover, press in on the four tabs, on the underside of the top cover. (See Figure 6g.) Electrical wires are still connected to assembly, so be careful.
6. Lift cover up and off.
6. Reverse procedure to reassemble.
Tabs
Tabs
Figure 6g
Control Assembly
The overlay of the Control Assembly for the two speed models displays an Humidity Control Switch, (humidification min. to max. range), Fan Speed Switch (HI and LO), and a Bucket Full LED. (See Figure 7a1.) On the single speed model, there is no Fan Speed Switch. (See Figure 7a2.) A Humidistat cycles both the fan and compressor ON or OFF to maintain humidity at the set level. The humidity sensing element is a nylon film which stretches with increased humidity and contracts with decreased humidity. This action turns a switch in the control ON and OFF to cycle the unit.
Figure 7a1
4. Disconnect two black wires and one red wire connected to Fan Speed Switch. (Only on two speed models.)
5. Remove control assembly.
6. Reverse procedure to reassemble.
To Remove Humidistat
1. Disconnect dehumidifier from electrical supply.
2. Remove control knob from front of control assembly.
3. Disconnect three black wires connected to two terminals on Humidistat.
4. Pull back on four tabs to release the humidistat. (See Figure 7c.) Pull back on top tabs first, tilting humidistat towards you, then pull back on bottom tabs and pull humidistat free from assembly.
5. Reverse procedure to reassemble.
Figure 7a2
To Remove Control Assembly
1. Disconnect dehumidifier from electrical supply.
NOTE: See Figure 7b for location of electrical wires.
2. Disconnect one red and two white wires connected to Bucket Full Light. (One of the white wires is pigtailed to the red wire on one of the terminals.)
3. Disconnect two black wires connected to Humidistat.
Figure 7c
Figure 7b
To Remove Full Bucket Pilot Light
1. Disconnect dehumidifier from electrical supply.
2. Disconnect three wires connected to two terminals on pilot light. (See figure 7b.)
3. Using needle nose pliers, squeeze plastic tabs against pilot light and push light through hole in assembly. (See Figure 8a.)
Bucket Switch
The bucket switch is a Single Pole, Double Throw (SPDT) device that shuts off the dehumidifier when the bucket is full. The switch is activated by a float (see Figure 8c) mounted inside the bucket. The switch is mounted to the frame directly behind the bucket. (See Figure 8d.)
NOTE: This unit will not operate with the bucket removed.
Figure 8a
To Test Fan Speed Switch (2 speed models only)
1. Disconnect dehumidifier from electrical supply.
2. Disconnect three wires connected to three terminals on fan switch.
3. Using a multimeter on resistence scale, take following readings: (See Figure 8b.)
With fan switch in HI: Terminals 1 & 2 0 ohms
Terminals 1 & 3 max resistence Terminals 2 & 3 max resistence
With fan switch in LO: Terminals 1 & 2 max resistence
Terminals 1 & 3 0 ohms Terminals 2 & 3 max resistence
Figure 8b
To Remove Fan Speed Switch (2 speed models only)
The Fan Speed Switch is very difficult to remove without destroying it. Do not attempt to remove the switch unless it is faulty. Then, it really doesnt matter if the switch is damaged during removal. However, do be careful not to damage the control assembly during removal. The new switch will fit into place nicely once the faulty switch has been removed.
Figure 8c
Figure 8d
To Remove Float:
1. Disconnect dehumidifier from electrical supply.
2. Remove bucket. (See procedure To Remove Bucket on page 6.)
3. Drain any condensate that may be in the bucket.
4. Remove pin holding float to bucket. (See Figure 6e.)
5. Remove float through top access hole in bucket.
6. Reverse procedure to reassemble.
Figure 8e
NOTE: When reinstalling float into bucket, ensure the float is positioned so the tongue protrudes through the front hole in the bucket. Then the pin is inserted through the hole in the tongue and snapped into the slot in the bucket.
To Remove Bucket Switch:
1. Disconnect dehumidifier from electrical supply.
2. Remove three electrical leads from terminals on bucket switch.
3. Squeeze tabs together and push up on switch from bottom. (See Figure 8f.)
Figure 8f
To Test Bucket Switch:
1. Test resistance between three terminals on switch. (See Figura 9a.)
2. Using Multimeter on resistance scale, with switch in AT REST position, resistance readings should be as follows :
Common - Normally Open = Max. resistance Common - Normally Closed = Zero resistance
With switch arm DEPRESSED, readings should be as follows:
Common - Normally Open = Zero resistance Common - Normally Closed = Max. resistance
3. Replace switch if readings are not within range.
Figure 9a
Defrost Thermostat
The defrost thermostat is mounted on the suction line close to the compressor. When the ambient temperature drops below 65°F, the evaporator coil temperature also drops and frost begins to form on the evaporator surface. When the suction line temperature reaches 37°F at the location of the defrost thermostat, the thermostat opens the circuit to the compressor. When the accumulated frost melts and the suction line has warmed to 59°F, the defrost thermostat closes, allowing the compressor to restart. The fan motor will continue to run when thermostat is open.
To Remove Defrost Thermostat:
1. Disconnect dehumidifier from electrical supply.
NOTE: Refer to procedures on page 6 to remove bucket, front grille, top cap and wrapper.
2. Remove bucket, front grille, top cap and wrapper.
3. Locate defrost thermostat just above compressor on suction line.0
4. Disconnect two wire leads from thermostat.
5. Remove insulation from around Defrost Thermostat so spring clip is exposed.
6. Press on spring clip with thumb and raise thermo­stat free from evaporator coil.(See Figure 9b.)
7. Reverse procedure to reassemble.
To Test Defrost Thermostat:
1. Using Multimeter on resistance scale, read resistance of thermostat between the two leads. At room temperature (above 60°F), resistance should be zero (0), indicating the thermostat is closed.
2. To see if thermostat opens when temperature drops to 37°F, bury thermostat in bucket of ice. With multimeter still connected to two thermostat leads, watch resistance scale to see if it goes to maximum when temperature drops to 37°F. (Place thermometer in ice bucket to monitor exact temperature at which thermostat opens.)
3. Replace thermostat if readings are not within limits.
NOTE: When replacing the thermostat, make sure the insulation is wrapped firmly around the thermostat to prevent heat loss.
Motor, Motor Bracket and Blower Wheel
The shaded pole Fan Motor can be single or two speed, depending on the model. The motor turns a Blower Wheel (7 L x 2 W) rather than a fan blade.This motor does not have a Start winding, but instead employs a shading coil in the stator to produce starting torque in the proper direction. When the motor speeds up, the shading coil does not affect the motors operation.
The fan motor is permanently lubricated. However, some motors have oil ports and should be oiled after two years of service.
To Remove Blower Assembly
1. Disconnect dehumidifier from electrical supply.
NOTE: Refer to procedures on page 6 to remove bucket, front grille, top cap and wrapper.
2. Remove bucket, front grille, top cap and wrapper.
3. Remove four screws from motor bracket. (See Figure 9c.)
4. Pull blower assembly towards you and lift up and out of unit. (See Figure 9d.)
Figure 9b
Figure 9c Figure 9d
5. Disconnect three wires going to the Control Assembly.
6. Use a pair of pliers to remove compression clamp holding blower wheel to motor shaft. (See Figures 10c and 10d.)
7. Pull blower wheel off of motor shaft and free from blower assembly.
Figure 10c
To Remove Casters
1. Disconnect dehumidifier from electrical supply.
2. Lay humidifier on floor, front grille facing up.
3. Use a hammer and screwdriver to release locking tabs securing casters to base. (See Figure 10c.)
4. Reverse procedure to reassemble.
Figure 10c
Figure 10d
8. Lift off styrofoam scroll chassis.
9. To remove motor from motor bracket, remove two hex head nuts holding motor to bracket.
10. Reverse procedure to reassemble.
NOTE: When reassembling blower wheel to motor shaft, make sure blower wheel is pressed onto shaft as far as it will go.
To Test Motor
1. Using an ohmmeter, take resistance readings of HI and LO speed windings. Readings should be as follows:
LO Speed Red & White leads 45W ± 10% HI Speed Black & White leads 30W ± 10%
2. If readings are not within limits, replace motor.
10
Compressor
There are two types of compressors used on dehumidifiers:
1. Permanent Split Capacitor compressor (Rotary)
2. Split Phase compressor (Reciprocating)
Permanent Split Capacitor (PSC) Compressor
This compressor has a Start and Run winding with a capacitor wired in series with the Start winding. When power is applied, the capacitor assists in bringing the compressor motor to optimum speed.
Split Phase Compressor
This compressor has a Start and Run winding. On models equipped with a current activated relay, the relay is wired in series with the Run winding. When power is applied to the Run winding, The high starting current pulls the relay armature up, closing contacts to complete the circuit to the Start winding. The motor starts and accelerates to a point where the current is reduced enough to allow the relay to drop out and disconnect the circuit to the Start winding. This point occurs at about 80% of full speed. The motor continues to accelerate to full speed on the Run winding alone. On models with PTC relay, current is applied to both windings at the same time. This starts the compressor. As current flows through the relay to the Start winding, the relay will increase in resistance . Within a fraction of a second, the resistance will climb high enough for the Start winding to drop out.
CAUTION: Replacement compressors are charged with oil at the factory. Care should be exercized when replacing a compressor to avoid spilling any oil.
To Test Compressor Motor
WARNING: WHENEVER TESTING A COMPRESSOR, EXTREME CAUTION SHOULD BE USED TO PREVENT DAMAGING THE TERMINALS. A COMPRESSOR WITH A DAMAGED TERMINAL OR A GROUNDED WINDING CAN EXPEL A TERMINAL FROM ITS INSULATED HOUSING WHEN THE COMPRESSOR IS ENERGIZED. IF THIS HAPPENS, A MIXTURE OF REFRIGERANT AND OIL WILL BE RELEASED THAT CAN BE IGNITED BY AN EXTERNAL HEAT SOURCE (OPEN FLAME, HEATER, ETC.). ALSO, IF THERE IS AIR IN THE SYSTEM WHEN THIS HAPPENS, A SPARK AT THE COMPRESSOR SHELL COULD IGNITE THE REFRIGERANT AND OIL MIXTURE.
1. Disconnect dehumidifier from electrical supply.
2. Remove leads from compressor terminals.
3. Check for grounded windings by testing continuity from each terminal to any copper tubing connected directly to compressor. If continuity is indicated, motor windings are grounded and compressor will have to be replaced.
4. Check for open windings by checking continuity from Start-to-Run terminals. If no continuity is found, a winding is open and compressor must be replaced.
Possible Causes of Compressor Overloading or Overheating
1. Shorted winding. Recheck Start and Run windings.
2. Low voltage. With dehumidifier disconnected, check voltage at electrical outlet. Voltage should be of 115 VAC,+/- 10%.
3. Plug in dehumidifier and check voltage. If voltage is not within +/- 10% of 115 VAC, compressor break down or overheating may occur. Excessive voltage drop during start-up or while running may be cause of motor overload opening.
4. Defective run capacitor (if supplied). If compressor will not start (or starts slowly), or compressor runs but draws high current, test capacitor.
5. Dirty evaporator and/or condenser.
6. Insufficient air passing over condenser.
The compressor can also be operated on a test cord when connected as illustrated below.
CAUTION: If compressor is a permanent split capacitor type, use only a known good electrolytic capacitor, rated for compressor being tested. This running capacitor must be in circuit while compressor is running.
Compressor Test Cord for PSC Compressor
NOTE: If compressor has a permanent split
capacitor (PSC) motor, running capacitor should be tested first.
11
Compressor Test Cord for Split Phase
Compressor
Running Capacitors
Running capacitors are used on some compressor motors to increase the efficiency of the motor by improving the power factor.
Always replace running capacitors with capacitors of like type and mF (microfarad) rating. Pay particular attention to the voltage rating.
To Test Capacitor
WARNING: AN INTERNALLY SHORTED CAPACITOR MAY EXPLODE IF ENERGIZED DIRECTLY WITH LINE VOLTAGE. CHECK ONLY WITH AN OHMMETER OR CAPACITOR TESTER. AFTER TESTING, ALWAYS DISCHARGE CAPACITOR WITH A 20,000W (OHM), 2 WATT RESISTOR PLACED ACROSS THE TERMINALS.
1. Disconnect dehumidifier from electrical supply.
2. Remove wrapper.
3. Discharge capacitor.
NOTE: Best method of discharging capacitor is with insulated copper wire in series with a 20,000 ohm, 2 watt resistor. Place this high resistance jumper across capacitor terminals.
4. Disconnect capacitor wiring.
5. Connect ohmmeter across terminals of capacitor to be checked:
a. If capacitor is good, needle should jump toward
zero ohms and quickly drop back to infinity. b. If needle does not move, capacitor is open. c. If needle reads constant value at near zero
ohms, capacitor is shorted.
d. If needle jumps toward zero and falls back to
constant high resistance value (not infinity), capacitor has high resistance leak.
e. Check for ground from each terminal of capacitor
to bare metal of capacitor case. Resistance should be infinite. If resistance is less than infinite, capacitor is grounded.
Replace capacitor if it is open, shorted, grounded or has a high resistance leak.
Compressor Overload Protector
An overload protector is attached to the compressor to detect excessive heat or a current overload. If the overload is actuated, it will shut off the current to the compressor and automatically reset itself after a short cool down period. The compressor will attempt to start after the cool down period.
The overload is located under the terminal cover. To gain access to the overload, disconnect the dehumidifier from the electrical supply and remove the terminal cover.
To Test Overload
1. Disconnect dehumidifier from electrical supply.
2. Remove wrapper.
3. Remove terminal cover.
4. Disconnect all wiring to overload and check across overload terminals with ohmmeter. (Overload should be at room temperature when checked.) Zero ohms (0W) should be indicated.
NOTE: Always replace terminal cover and gasket to protect overload and compressor terminals from moisture and corrosion.
To Test Relay (Split Phase Compressor)
1. Disconnect dehumidifier from electrical supply.
2. Remove relay and overload cover from compressor.
3. Disconnect wire to relay and remove relay from compressor terminals (pull straight off).
4. Check continuity of relay coil (refer to wiring diagram for proper terminals to check across). If relay coil checks OK, use compressor test cord to test compressor.
5. If PTC relay is used, check resistance between L1 and Start winding. Resistance should be no more than 4 ohms at room temperature.
To Replace Relay (Split Phase Compressor)
1. Disconnect humidifier from electrical supply.
2. Remove wrapper.
3. Remove relay cover from relay and overload.
4. Remove wire from relay and pull straight off.
5. Reverse procedures to reassemble.
12
REFRIGERATION SYSTEM & SERVICE
NOTICE: Instructions given here are furnished as a guide. Persons attempting to use these instructions to make repairs to the sealed refrigeration system should have a working knowledge of refrigeration, previous training on sealed system repair, and an EPA certification for servicing refrigeration systems.
IMPORTANT NOTICE Effective July 1, 1992, the United States clean air act governs the disposal of refrigerants such as R-22. Therefore, when discharging or purging the sealed system, use an EPA approved refrigerant recovery system as outlined in the final rule on the protection of stratospheric ozone and refrigerant recycling which was published in the Federal Register May 14, 1993.
NOTE: Frigidaire does not permit the use of recovered refrigerant in the servicing of our products for in-warranty
and out-of-warranty repairs or for products covered by service contracts. Therefore, only new refrigerant or refrigerant that has been reclaimed back to new specifications by a refrigerant manufacturer is to be used.
DEFINITIONS
Recovery:
to remove refrigerant in any condition from a system and store it in an external container without necessarily testing or processing it in any way.
Recycling:
to clean refrigerant for reuse by oil separation and single or multiple passes through devices, such as replaceable core filter-driers, which reduce moisture, acidity and particulate matter. This term usually applies to proce­dures implemented at the field job site or at a local service shop.
Reclaim:
to reprocess refrigerant to new product specifications by means which may include distillation. Will require chemi­cal analysis of the refrigerant to determine that appropri­ate product specifications are met. This term usually implies the use of processes or procedures available only at a reprocessing or manufacturing facility.
SAFETY WARNINGS
Compressor Testing
Whenever testing a compressor, extreme caution should be used to prevent damaging the terminals. A compres­sor with a damaged terminal or a grounded winding can expel a terminal from its insulated housing when the compressor is energized. If this happens, a mixture of refrigerant and oil will be released that could be ignited by an external heat source (open flame, heater, etc.). Also, if there is air in the system when this happens, a spark at the compressor shell could ignite the refrigerant and oil mixture.
Charging Sealed Systems
Overcharging a refrigeration system with refrigerant can be dangerous. If the overcharge is sufficient to immerse the major parts of the motor and compressor in liquid refrigerant, a situation has been created which, when
followed by a sequence of circumstances, can lead to the compressor shell seam separating.
A hydraulic block then occurs, preventing the compres­sor from starting. This condition is known as locked rotor. Electric current continues to flow through the compressor motor windings which become, in effect, electric resistance heaters. The heat produced begins to vaporize the excess refrigerant liquid, causing a rapid increase in system pressure. If the compressor protective devices fail, the pressure within the system may rise to extremes far in excess of the design limits. Under these conditions, the weld seam around the compressor shell can separate with explosive force, spewing oil and refrigerant vapor which could ignite.
To eliminate this exceedingly rare but potential hazard, never add refrigerant to a sealed system. If refrigerant is required, evacuate the existing charge and recharge with the correct measured amount of the refrigerant specified for the system.
SOLDERING
WARNING: WEAR APPROVED SAFETY GLASSES WHEN WORKING WITH OR ON ANY PRESSURIZED SYSTEM OR EQUIPMENT. HAVE AN APPROVED DRY TYPE FIRE EXTINGUISHER HANDY WHEN USING ANY TYPE OF GAS OPERATED TORCH.
1. All joints to be soldered must have proper fit. Clearance between tubes to be soldered should be from .001 to .006. It is not practical to actually measure this; however, you do not want dry fit or loose fit. Tubing joints should overlap about distance of their diameter except for restrictor tubes, which should be inserted 1.25
2. Clean all joint areas with fine steel wool or, preferably, abrasive cloth, such as grit cloth No. 23 or Scotch-Brite.
13
3. Apply thin film of liquid flux recommended for silver soldering to surfaces to be joined, and to surfaces immediately adjacent to joint.
4. Align tubing so no stress is on joint. Do not move tubing while solder is solidifying or leaks will result.
CAUTION: During application of heat, use wet cloths to prevent heat from conducting to areas other than soldered joint. Use a sheet of metal as a heat deflector to keep flame away from flammable materials and painted surfaces.
5. Use torch of adequate capacity so joint can be quickly heated with minimum of heat travel to other points. Use good grade of silver solder.
6. Solder connections. If tubing is properly cleaned and fluxed, solder will flow readily. Use only enough solder to make a good bond.
7. Allow joint to cool, then wash exterior with water to remove flux.
SEALED SYSTEM
The dehumidifying system is similiar to that of a room air conditioner, except for size. The condenser and evaporator are both fin and tube coils of copper tubing with aluminum fins. Both coils are placed in the air stream.
A capillary tube controls the refrigerant flow from the condenser to the evaporator. The suction tube from the evaporator outlet to the compressor is insulated to prevent sweating.
NOTE: Check the performance of the dehumidifier and electrical system before attempting to repair the sealed system.
SEALED SYSTEM DIAGNOSIS
Undercharged System
Disconnect fan motor leads and start the unit. A slight, uniform film of frost should form on the entire evaporator within about 10 minutes. If it does not, the system is possibly undercharged.
Overcharged System
Operate the unit for at least 30 minutes in a room temperature of 75°F to 85°F. The top of the compressor should be warm to the touch. This applies to a recipro­cating compressor only. If it is cool or cold, the system is possibly overcharged. On models eqipped with Rotary compressors, check for frost or cold tempera­tures all the way to the top of the accumulator.
An overcharged system must be evacuated and recharged. Purging off excess refrigerant is not legal or practical, as there is no way of determining the amount to purge.
Pressure Equalizing (System Unloading)
If an attempt is made to start the unit too soon after it has stopped, the compressor may fail to start and will cycle on the overload protector. This is caused by high head pressure and low suction pressure. Allow the pressures to equalize through the capillary tube. Pressure equalizing (system unloading) will usually take 2 to 3 minutes.
Refrigerant Leaks
An undercharge of refrigerant is usually caused by a leak in the system. Such leaks must be located, the refrigerant recovered, and the leak repaired before evacuating and recharging. Simply adding the refrigerant or recharging will not permanently correct the problem and may lead to a compressor burn out.
NOTE: Do not replace a component because the system is undercharged unless a nonrepairable leak is found within the system components.
If a leak cannot be readily found, the system should be pressurized to at least 75 psig (gauge pressure). If necessary, attach a ¼ line piercing valve to the com­pressor process tube and add enough refrigerant for testing. (Only use the refrigerant specified on the serial nameplate.)
NOTE: The line piercing valve (clamp-on type) should be used for test purposes only. It must be removed from system after it has served its purpose.
If an undercharged system is found, perform the following:
Leak test unit.  Recover refrigerant.  Repair Leak.  Evacuate and recharge unit with proper amount of
refigeratant.
NOTE: Always leak test system after recharging.
Most leaks can be found with a Halide torch. However, for very small leaks, it may be necessary to use an Electronic Leak Detector, or the soap bubble method to pinpoint the leaks.
CAUTION: Be sure the system has a positive pressure before using the soap bubble method of leak detecting. A vacuum within the system could draw in moisture and contaminants.
After servicing a system, always leak test the entire system, especially new joints before final recharging. Clean off any soldering flux, if used, from the joints before
14
leak testing, as flux can seal off pinhole leaks that would show up later.
COMPONENT REPLACEMENT
CAUTION: It is extremely important to verify the type of refrigerant in a system before starting any sealed system repair. Check serial plate for the correct refrigerant type and charge.
When replacing components, all copper joints must be joined with silver solder or Sil-Fos.
CAUTION: Be careful not to damage adjacent parts when using a torch on soldered joints. If necessary, use a metal heat shield, or wrap a wet cloth around the tubing to reduce heat transfer.
COMPRESSOR REPLACEMENT
CAUTION: NEVER install a new compressor without first checking for possible system contamination.
CAUTION: The end of flushing hose of tank regulator must be equipped with a hand shut-off valve (Robinair No. 40380). Close hand shut-off valve and adjust nitrogen regulator to correct pressure before proceeding with flushing procedure.
To Use Refrigerant To Flush The System:
CAUTION: Refrigerant used for flushing must be captured in a recovery bag. Meter amount of refrigerant used for flushing with your charging cylinder. DO NOT OVERFILL THE BAG.
1. Remove suction and discharge lines on compressor and disconnect capillary tube from condenser. Connect pro­cess coupling to outlet and inlet tube of condenser.
2. Connect hose to outlet process coupling and charging cylinder. Connect another hose to inlet coupling and recovery bag.
3. Open charging cylinder and allow refrigerant to flow through condenser until discharge into bag is clear.
4. Connect process fitting to compressor suction line. Flush evaporator and capillary tube.
To check for contamination, obtain an oil sample from an old compressor.
 If oil has burned odor, but no color change or
residue  follow instructions in section Installing A New Compressor on page 14.
 If oil has burned odor and shows contamination
(dark color) or feels gritty  follow instructions in next section, To Flush The System. Remove as much contamination as possible from system before installing new compressor.
To Flush The System
NOTE: The system should be flushed with dry
nitrogen. However, you must use R-22 if refrigerant is used to flush system. This is the only refrigerant that can be used to flush the system and it must be recovered.
CAUTION: Use extreme care when using dry nitrogen to flush systems. Pressure in nitrogen cylinder could be as high as 2000 psi. Nitrogen cylinder must be equipped with approved pressure regulator and pressure relief valve. Ensure that your hoses have adequate ratings for pressure involved, and that all of your equipment is in good condition.
NOTE: If unable to get refrigerant flow through
capillary tube, remove capillary tube from evaporator and flush again.
5. If cap tube is blocked, replace cap tube.
6. Reassemble system.
Installing a New Compressor
All replacement compressors are shipped with rubber plugs in the suction, discharge, and process tubes and contain the correct oil charge and a holding charge of inert gas. Models with Reciprocating Compressors have a low-side process tube attached to the compressor shell. Models with Rotary Compressors have a process tube on the high side of the system soldered into the compressor discharge line
WARNING: DO NOT OPERATE COMPRESSOR WHEN CHARGING LIQUID REFRIGERANT INTO SYSTEM THROUGH ITS PROCESS TUBE.
Before installing the replacement compressor, remove the discharge plug and check for the pop sound of the inert gas leaving the compressor.
CAUTION: DO NOT use compressor if you do not hear this sound.
A new compressor which is cold (e.g. after having been kept in a cold service van) should be left to warm to the surrounding temperature before the plugs on the compressor connections are removed. This will help prevent condensation from forming
15
in the oil and the compressor. Also, avoid opening the system when any of the components or lines are cold.
CAUTION: Release holding charge (release slowly to avoid oil discharge) on new compressor to ensure that there is no leak in seam or tubing. Then, reinstall rubber plug.
1. Disconnect electrical supply to dehumidifier.
2. Remove bucket, front grille, top cap and wrapper.
3. Remove one screw at bottom of support of blower motor assembly.
4. Bend all four tabs on top and bottom of condenser to outside and pull blower assembly away from condenser.
5. Recover refrigerant by using EPA approved recovery system.
6. Remove leads from compressor motor terminals.
7. Remove mounting clips or bolts holding compressor to base.
8. After refrigerant is completely recovered, cut suction and discharge lines as close to compressor as possible. Leave only enough tubing to pinch off and seal defective compressor. Plug or tape any open system tubing to avoid entrance of moisture and air into system. Remove inoperable compressor and transfer mounting parts to new compressor.
9. Install new compressor in exact same manner as original compressor.
10.Reform suction and discharge lines to align with new compressor. If they are too short, use additional lengths of tubing. Joints should overlap 0.5 inch to provide sufficient area for good solder joint. Clean and mark area where tubing should be cut. Cut tubing with tubing cutter. Work as quickly as pos­sible to avoid letting moisture and air into system.
NOTE: If process tube is too short, silver solder four inch piece of tubing onto process tube at this time.
11. Solder all connections according to soldering
procedure outlined on page 12.
12. Evacuate and charge system using recommended
procedure described under Evacuating and Recharging on pages 15 to 16.
13. Reconnect compressor terminal leads.
14. Reassemble unit.
NOTE:On models equipped with Rotary Compres­sors, the process tube is on the high side of the system. If you need access to the low pressure side of the system, it is necessary to install a T in the suction line and add a process tube to it.
To Remove Evaporator or Capillary Tube:
1. Disconnect dehumidifier from electrical supply.
2. Remove bucket, front grille, top cap and wrapper.
3. Recover refrigerant.
4. To replace capillary tube, unsweat tube from evaporator and condenser. Remove and replace.
5. To replace evaporator, unsweat capillary tube and suction line.
6. Remove top and center screws from left side of evaporator.
7. Swing evaporator out from right hand side of condenser.
To Remove Condenser:
1. Disconnect dehumidifier from electrical supply.
2. Remove bucket, front grille, top cap and wrapper.
3. Recover refrigerant.
4. Unsweat capillary tube and discharge line.
5. Remove three screws securing evaporator and condenser from left side and one screw from bottom right securing condenser.
6. Pull suction line forward far enough to allow evaporator to bepulled out.
7. Remove one screw at bottom of support of blower motor assembly.
8. Bend all four tabs on top and bottom of condenser to outside and pull blower assembly away from condenser.
9. Lift condenser out and replace.
NOTE: Prior to reassembling condenser and evapo­rator, the gap aound right and left srew hole brackets must be sealed with Permagum. See Figure 16a.
Gap
Screw Hole Brackets
Figure 16a
10.Reassemble in reverse order.
Filter Dryer
Dehumidifiers are not equipped with a filter dryer, but as a servicer, if you feel you need a filter dryer in this system after doing your repair, a filter dryer is available through the Replacement Parts System.
EVACUATING AND RECHARGING
Equipment Needed:
 Heated Dial-A-Charge charging cylinder  Standard 3-port manifold gauge set:
 four charging hoses  Tee fitting with valve core stem removed (Robinair No. 40396)
 Hand shut-off valve (Robinair No.40380)  Two stage vacuum pump  Process tube adapter kit (Robinair No. 12458)  Tubing cutter  Pinch-off tool capable of making leak proof seal  Complete brazing torch set  Small 3-corner file  Grit cloth or Scotch-Brite  45% silver solder and flux or sil floss
16
Installing Evacuation and Recharging Equipment
1. Disconnect dehumidifier from electrical supply.
2. Install process tube adaptor on process tube leaving as much tube as possible.
3. Attach refrigeration service gauge manifold to system in following order:
Low-side (compound gauge) to process tubeCenter port manifold hose before hand shut-off
valve to charging cylinder.
Center port manifold hose after hand shut-off
valve to vacuum pump.
Evacuating System
To achieve the required levels of evacuation, a properly maintained two- stage vacuum pump in good condition is required. It is absolutely essential to maintain your vacuum pump according to the manufacturers instructions including required oil changes at the recommended intervals. Vacuum pump oil should a l w a y s be changed after evacuating a contaminated system.
Vacuum pump performance should be checked periodically with a micron gauge.
Charging The System
CAUTION: After charging the system with liquid, be certain to wait at least 5 minutes before starting the compressor to give the refrigerant a chance to disperse throughout the system. Otherwise, the compressor could be damaged by attempting to pump excessive quantities of liquid.
Preparing the Charging Cylinder:
1. Charging cylinder must have at least eight ounces more refrigerant than required charge.
2. Plug in cylinder heater and bring pressure up to 30 pounds above gauge pressure at ambient temperature. Maintain, but do not exceed, this 30 pound increase in gauge pressure during system charging.
WARNING: DO NOT USE EXTERNAL HEAT SOURCE ON CYLINDER OR EXCEED MAXIMUM GAUGE PRESSURE ON CHARGING SYSTEM.
1. Make certain that charging cylinder valve, hand shut-off valve, and manifold gauge valves are closed.
2. Start vacuum pump.
3. Open hand shut-off valve and slowly open manifold valve, turning counterclockwise, for two full rotations.
CAUTION: If high vacuum equipment is used, just crack manifold valve for a few minutes, then open slowly for two full turns, counterclockwise. This will prevent the com­pressor oil from foaming and being drawn into the vacuum pump.
4. Operate vacuum pump for minimum of 30 minutes to attain minimum of 29.9 (500 micron) vacuum or until vacuum of 500 microns is obtained..
5. Close hand shut-off valve to vacuum pump. Watch compound gauge for several minutes. If reading rises, there is leak in system, go to step 6. If no leak is indicated, stop vacuum pump. System is now ready for charging.
6. If leak is indicated, stop vacuum pump and introduce small charge of refrigerant into system by cracking valve on bottom of charging cylinder until system is pressurized to 40 or 50 psig.
7. Leak test low-side. Close compound gauge. Run compressor for few minutes and leak test high­side. When leak is found, recapture refrigerant using EPA approved recovery system, repair and go back to step 1.
To Charge System:
1. Make certain that hand shut-off valve to vacuum pump is closed.
2. Set charging cylinder scale to pressure indicated on cylinder pressure gauge.
3. Observe refrigerant level in sight glass. Subtract amount to be charged into system and note shut off point.
4. Open charging cylinder valve slowly and allow proper charge to enter system.
5. As soon as refrigerant in sight glass has gone down to predetermined level, close charging cylinder valve.
WARNING: DISCONNECT THE CHARGING CYLINDER HEATER AT THIS TIME TO PREVENT THE CYLINDER PRESSURE FROM EXCEEDING ITS MAXIMUM LIMITS.
6. Allow system to sit for five minutes.
7. Turn on dehumidifier compressor. Run compressor for few minutes and monitor system pressures.
8. When satisfied that unit is operating correctly, clamp process tube with pinchoff tool while unit is still running.
9. Remove process tube adaptor and solder the process tube closed.
11.Turn on unit. After few minutes, check process tubes for refrigerant leaks.
FINAL LEAK TEST
1. With dehumidifier turned OFF, leak test all low-side system components.
2. Turn unit ON and run until condenser is warm. Leak test high-side system components.
17
WIRING DIAGRAMS - DATA SHEETS
ELECTRICAL WIRING DIAGRAM
Single Speed Fan - Models With Reciprocating Compressors
18
ELECTRICAL WIRING DIAGRAM
2 Speed Fan - Models With Reciprocating Compressors
19
ELECTRICAL WIRING DIAGRAM
2 Speed Fan - Models With Rotary Compressor
20
SGNITARREIFIDIMUHED
J03HDF/J52HDFsledoM
srH42/stniP 03/52
HWK/sretiL 0.1/48.
:ledoM Y2C06AMF :#traP 207306723 :ARL 2.03 :daolrevO 35-ZZBFS897MT4 :N/P 218617E
:yaleRtratS 20-1500PRTM
:egrahCliO cc082
rotaropavE
:N/P )2202-E-CHD(018056723fotraP
:htgneL "83.01 :.D.O
:htoomS 4 :llaW ).ltuO&.lnI(610.
:devoorG 01 :epyT )LWniM8110.("C"
:hcnI/sniF .rvL51 :lairetaM .mulA2400.
:thgieHsniF "2.11
:oTtelnIylfrettuB eniLnoDI390./090.
.resnednocworelgnis
gnibuT
:N/PnoitcuS demroF104403723 :aiD
:N/PegrahcsiD demroF103403723 :aiD
:ssecorP 01H428A648 :aiD DO61/5
ycneuqerF ztreH06
egatloV CAV511
rosserpmoCgnusmaS
metsySriA
:gfMrotoMnaF PS:epyTnalliMcM
:#traP 904056723
:seloP 6 :emarF )21.5.aiD(24
:spmA 10.1 :sttaW 19 :roticapaC enoN
:leehWrewolB 100063723#"2x'7nergrohT
egarepmA 5.6
rotcaFrewoP 97.0
resnednoC
:N/P )2202-E-CHD(018056723fotraP
61/5
woR1.BT41L-.TAM
htiwstekcarbnommocemasehtnodetnuomsilioC
61/5
DO
4/1
DO
:aiD:N/PelgruG-itnA
:aiD:N/PnoitcuS-snarT
:htgneL "83.01 :.D.O
:htoomS 4 :llaW ).ltuO&.lnI(610.
:devoorG 01 :epyT )LlWniM8110.("C"
:hcnI/sniF 51 :.ltaM .mulA2400.
rotcirtseR
:epyT caigawoD.hciMreppoClanoitaNRFM/.BT.paC :eziS eulB780.-"52x930. :N/P )341211A(108363723
:oTtelnIylfrettuB enilnoDI552.-352.
:oTteltuOylfrettuB enilnoDI390.-090.
61/5
.mottobehttaebutdn2ehtni
:LTAM woR1.BT41
sireniartS.rotaropavehtiwtekcarbdnenommocsahlioC
slortnoC
:N/PtatsidimuH 102263723
:N/PlortnoCezeerF
stloV 511
:MPR 029
:yrDMFC 502
:ABDdnuoS
:thgieWtinU
iHdeepS
tnaregirfeR
seznuO5.6yletamixorppAtadegrahC22R
21
SGNITARREIFIDIMUHED
J04DDFledoM
srH42/stniP 04
HWK/sretiL 61.1
:ledoM )decudeRdnuoS(6863-1-351HSO
:#traP 817518E :ARL 43
:daolrevO )WDA-42-TSM(108617E :yaleRCTP )100717E(104AE8 :egrahCliO cc053
rotaropavE
:N/P )A2202-E-EHD.BAL(108163723fotraP
:htgneL "83.01 :.D.O
:htoomS 4 :llaW ).ltuO&.lnI(610.
:devoorG 81 :epyT )LWniM8110.("C"
:hcnI/sniF 31 :lairetaM .mulA2400.
:thgieHsniF "8.8
:oTtelnIylfrettuB enilnoDI491./191
gnibuT
:N/PnoitcuS 106263723 :aiD
:N/PegrahcsiD 105163723 :aiD
:N/PelgruG-itnA 206153723 :aiD
:ssecorP 01H428A648 :aiD
:noitalusnInoitcuS )199(507446E)1(607448E
ycneuqerF ztreH06
egatloV CAV511
sttaW 086
rosserpmoCdlociremA
metsySriA
:gfMrotoMnaF PS:epyTnalliMcM :#traP deepS1/deepS290/704056723 :seloP 6 :emarF )21.5.aiD(24 :spmA 10.1 :sttaW 19 :roticapaC enoN
:leehWrewolB 100063723#"2x'7nergrohT
egarepmA 5.7
rotcaFrewoP 86.
resnednoC
:N/P )3202-CHD.BAL(100163723fotraP
61/5
:ltaM woR2.BT22
:htgneL "83.01 :.D.O
:htoomS 4 :llaW ).ltuO&.lnI(610.
:devoorG 42 :epyT )LlWniM8110.("C"
:hcnI/sniF 51 :.ltaM .mulA2400.
:oTteltuOylfrettuB enilnoDI601.-201.
61/5
:LTAM woR2.BT82
"2.11=H.mottobehttaebutdn2ehtnisireniartS
rotcirtseR
61/5
DO
4/1
DO
61/3
DO
61/5
DO
:epyT caigawoD.hciMreppoClanoitaNRFM/.BT.paC :eziS )151211A(990.-"72x940.
:N/P )demroF(102463723
slortnoC
:N/PtatsidimuH 102263723
:N/PlortnoCezeerF
stloV 511511
:MPR 008029
:yrDMFC 571502
:ABDdnuoS
:thgieWtinU
woLiHdeepS
tnaregirfeR
.zO0.8yletamixorppAtadegrahC22R
22
SGNITARREIFIDIMUHED
J05DDFledoM
srH42/stniP 05
HWK/sretiL 55.1
:ledoM A11HC690AQ :#traP 701745A :ARL 62 :daolrevO )WDA-42-TSM(108617E
:yaleRCTP )277363A(683-47021ARM
:roticapaC 03 :DFM CAV073
:egrahCliO cc052
rotaropavE
:N/P )1202-E-EHD.BAL(104163723fotraP
:htgneL "83.01 :.D.O
:htoomS 4 :llaW ).ltuO&.lnI(610.
:devoorG 81 :epyT )LWniM8110.("C"
:hcnI/sniF 31 :lairetaM .mulA2400.
hgieHsniF "0.11:t
gnibuT
:N/PnoitcuS 102061723 :aiD
rosserpmoCratsdloG
8/3
:oTtelnIylfrettuB enilnoDI491./191
:N/PegrahcsiD 107363723 :aiD
:N/PelgruG-itnA 723 3 30615 :aiD
:N/PebuTssecorP 104061723 :aiD
:N/PnoitcuS-snarT 403101903 :aiD
sttaW 057
:ltaM woR2.BT22
8/3
61/5
61/3
ycneuqerF ztreH06
egatloV CAV511
DO
DO DO
61/5
DO
61/5
DO
egarepmA 8.6
rotcaFrewoP 69.
metsySriA
:gfMrotoMnaF PS:epyTnalliMcM
:#traP deepS2704056723
:seloP 6 :emarF )21.5.aiD(24
:spmA 10.1 :sttaW 19 :roticapaC enoN
:leehWrewolB 100063723#"2x'7nergrohT
resnednoC
:N/P )3202-CHD.BAL(100163723fotraP
:htgneL "83.01 :.D.O
:htoomS 4 :llaW ).ltuO&.lnI(610.
:devoorG 42 :epyT )LlWniM8110.("C"
:hcnI/sniF 51 :.ltaM .mulA2400.
:oTteltuOylfrettuB enilnoDI111.-801.
61/5
rotcirtseR
:epyT caigawoD.hciMreppoClanoitaNRFM/.BT.paC :eziS )611211A(601.-"04x450.
:N/P )demroF(109363723
:LTAM woR2.BT82
.mottobehttaebutdn2ehtnisireniartS
slortnoC
:N/PtatsidimuH 102263723
:N/PlortnoCezeerF
stloV 511511
:MPR 087029
:yrDMFC 561502
:ABDdnuoS
:thgieWtinU
woLiHdeepS
tnaregirfeR
.zO0.11yletamixorppAtadegrahC22R
23
SGNITARREIFIDIMUHED
J06DDF
srH42/stniP 06
HWK/sretiL 86.1
:ledoM B11HC690AQ :#traP 701745A :ARL 62 :daolrevO )WDA-42-TSM(108617E
:yaleRCTP )277363A(683-47021ARM
:roticapaC 03 :DFM CAV073
:egrahCliO cc052
rotaropavE
:N/P )1202-E-EHD.BAL(104163723fotraP
:htgneL "83.01 :.D.O
:htoomS 4 :llaW ).ltuO&.lnI(610.
:devoorG 81 :epyT )LWniM8110.("C"
:hcnI/sniF 31 :lairetaM .mulA2400.
hgieHsniF "0.11:t
gnibuT
:N/PnoitcuS 102061723 :aiD
rosserpmoCratsdloG
8/3
:oTtelnIylfrettuB enilnoDI491./191
:N/PegrahcsiD 107363723 :aiD
:N/PelgruG-itnA 723 3 30615 :aiD
:N/PebuTssecorP 104061723 :aiD
:N/PnoitcuS-snarT 403101903 :aiD
sttaW 007
)yratoR(
:ltaM woR2.BT22
8/3
61/5
61/3
ycneuqerF ztreH06
egatloV CAV511
DO
DO DO
61/5
DO
61/5
DO
egarepmA 3.6
rotcaFrewoP 79.
metsySriA
:gfMrotoMnaF PS:epyTnalliMcM
:#traP 804056723
:seloP 6 :emarF )21.5.aiD(24
:spmA 60.1 :sttaW 29 :roticapaC enoN
:leehWrewolB 100063723#"2x'7nergrohT
resnednoC
:N/P )4202-CHD.BAL(102363723fotraP
:htgneL "83.01 :.D.O
:htoomS 4 :llaW ).ltuO&.lnI(610.
devoorG 83: :epyT )LlWniM8110.("C"
:hcnI/sniF 51 :.ltaM .mulA2400.
:oTteltuOylfrettuB enilnoDI111.-801.
61/5
rotcirtseR
:epyT caigawoD.hciMreppoClanoitaNRFM/.BT.paC :eziS )611211A(601.-"04x450.
:N/P )demroF(109363723
:LTAM woR3.BT24
.mottobehttaebutdn2ehtnisireniartS
slortnoC
:N/PtatsidimuH 102263723
:N/PlortnoCezeerF
stloV 511511
:MPR 087029
:yrDMFC 561502
:ABDdnuoS
:thgieWtinU
woLiHdeepS
tnaregirfeR
.zO0.11yletamixorppAtadegrahC22R
24
Loading...