Friedrich XQ08L10-A, XQ05L10-A, XQ06L10-A, XQ10L10-A, XQ12L10-A Service Manual

...
Service Manual
2006
Room Air Conditioners
RAC-Svc-06 (3-06)
t
s u a
h x
E
Y C N
CIE
I F F
E H
IG
H
PER U S
M P
r e
w o P
ff O / n
O
l
o o C
®
r e
v a S y
e n
Mo
e
n
d
a
o
F
M
ly
d
n
e
O
e
n
p
a F
S
k
c lo C
t
r
t
ta
e
S
S r e
m i T
r
u o H
ff O
/
p
n
to
O
S
t u h
s t
n
r
e
u
V o H
/ p
m e T
TABLE OF CONTENTS
INTRODUCTION
Warranty ............................................................................. 3
Routine Maintenance ......................................................... 4
Unit Identifi cation / Nomenclature ...................................... 5
Performance Data .............................................................. 6
Electrical Data .................................................................... 7
Functional Component Defi nitions .................................... 8
Electronic Controls ......................................................... 8-9
Refrigeration Sequence of Operation .............................. 10
Sealed Refrigeration Repairs ...................................... 10-11
Refrigerant Charging ................................................... 12-14
Troubleshooting ...........................................................15-22
Wiring Diagrams ......................................................... 23-35
Thi s ser vic e manu al is des igned to be u sed in conjun ction with
the installation manuals provided with each air conditioning system component.
This service manual was written to assist the professional
RAC service technician to quickly and accurately diagnose and repair malfunctions.
This manual will deal with subjects in a general nature.
(i.e. all text will not pertain to all models).
TYPICAL UNIT COMPONENTS
Capillary Tube
Reversing Valve (some models)
Front Cover
System Switches
Evaporator Coil
Return Air Grille/Filter
Blower Wheel
Blower Motor
Fresh Air
Compressor
Basepan
Liquid Filter Driers
Condenser Coil
Discharge Air
Outdoor Grille
Sleeve
Condenser Fan Blade
The information contained in this manual is intended for use by a qualifi ed ser vice techn ician who i s famili ar with t he safet y procedures requ ired in install ation an d repair, and who is equipped with the proper tools and test instruments.
Installation or repairs made by unqualifi ed persons can result in hazards subjecting the unqualified person making such repairs to the risk of injury or electrical shock which can be serious or even fatal not only to them, but also to persons being served by the equipment.
If you install or perform service on equipment, you must assume responsibility for any bodily injury or property damage which may result to you or others. Friedrich Air Conditioning Company will not be responsible for any injury or property damage arising from improper installation, service, and/or service procedures.
IMPORTANT:
It will be necessary for you to accurately identify the unit you are servicing, so you can be certain of a proper diagnosis and repair (See Unit Identifi cation).
2
Friedrich Air Conditioning Company
P.O. Box 1540
San Antonio, TX 78295
210.357.4400
www.friedrich.com
ROOM AIR CONDITIONERS
LIMITED WARRANTY
FIRST YEAR
ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from
date of original purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service. Any additional labor cost for removing inaccessible units and/or charges for mileage related to travel by a Service Agency that exceeds 25 miles one way will be the responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within twelve months from the date of the original purchase.
SECOND THROUGH FIFTH YEAR
SEALED REFRIGERANT SYSTEM: If the Sealed Refrigeration System (defined for this purpose as the compressor, condenser
coil, evaporator coil, reversing valve, check valve, capillary, filter drier, and all interconnecting tubing) supplied by FRIEDRICH in your Room Air Conditioner fails because of a defect in workmanship or material within sixty months from date of purchase, FRIEDRICH will pay a labor allowance and parts necessary to repair the Sealed Refrigeration System; PROVIDED FRIEDRICH will not pay the cost of diagnosis of the problem, removal, freight charges, and transportation of the air conditioner to and from the Service Agency, and the reinstallation charges associated with repair of the Sealed Refrigeration System. All such cost will be the sole responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within sixty months from the date of the original purchase.
APPLICABILITY AND LIMITATIONS: This warranty is applicable only to units retained within the Fifty States of the U.S.A., District of Columbia, and Canada. This warranty is not applicable to:
1. Air filters or fuses.
2. Products on which the model and serial numbers have been removed.
3. Products which have defects or damage which results from improper installation, wiring, electrical current
OBTAINING WARRANTY PERFORMANCE: Service will be provided by the FRIEDRICH Authorized Dealer or Service Organization in your area. They are listed in the Yellow Pages. If assistance is required in obtaining warranty performance, write
to: Room Air Conditioner Service Manager, Friedrich Air Conditioning Co., P.O. Box 1540, San Antonio, TX 78295-1540.
LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES. Anything in the warranty notwithstanding, ANY IMPLIED WARRANTIES OF FITNESS FOR PARTICULAR PURPOSE AND/OR MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THIS EXPRESS WARRANTY. MANUFACTURER EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGE FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY.
NOTE: Some states do not allow limitations on how long an implied warranty lasts, or do not allow the limitation or exclusion of
consequential or incidental damages, so the foregoing exclusions and limitations may not apply to you.
OTHER: This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
PROOF OF PURCHASE: Owner must provide proof of purchase in order to receive any warranty related services.
All service calls for explaining the operation of this product will be the sole responsibility of the consumer.
All warranty service must be provided by an Authorized FRIEDRICH Service Agency, unless authorized by FRIEDRICH prior to repairs being made.
characteristics, or maintenance; or caused by accident, misuse or abuse, fire, flood, alterations and/or misapplication of the product and/or units installed in a corrosive atmosphere, default or delay in performance caused by war, government restrictions or restraints, strikes, material shortages beyond the control of FRIEDRICH, or acts of God.
(10-04)
3
ROUTINE MAINTENANCE
NOTE: Units are to be inspected and serviced by qualifi ed service personnel only.
Routine maintenance is required annually or semi-annually, depending upon annual usage.
1. Clean the unit air intake fi lter at least every 250 to 300 fan hours of operation or when the unit’s indicator light is on if so equipped. Clean the fi lters with a mild detergent in warm water and allow to dry thoroughly before reinstalling.
2. The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected periodically (yearly or bi-yearly) and cleaned of all debris (lint, dirt, leaves, paper, etc.). Clean the coils and base pan with a soft brush and compressed air or vacuum. If using a pressure washer, be careful not to bend the aluminium fi n pack. Use a sweeping up and down motion in the direction of the vertical aluminum fi n pack when pressure cleaning coils. Cover all electrical components to protect them from water or spray. Allow the unit to dry thoroughly before reinstalling it in the sleeve.
NOTE: Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and degreaser.
Inspect the indoor blower housing, evaporator blade, condenser fan blade, and condenser shroud periodically (yearly or
bi-yearly) and clean of all debris (lint, dirt, mold, fungus, etc.) Clean the blower housing area and blower wheel with an antibacterial / antifungal cleaner. Use a biodegradable cleaning agent and degreaser on condenser fan and condenser shroud. Use warm or cold water when rinsing these items. Allow all items to dry thoroughly before reinstalling them.
3. Periodically (at least yearly or bi-yearly): inspect all control components, both electrical and mechanical, as well as the power supply. Use proper testing instruments (voltmeter, ohmmeter, ammeter, wattmeter, etc.) to perform electrical tests. Use an air conditioning or refrigeration thermometer to check room, outdoor and coil operating temperatures. Use a sling psychrometer to measure wet bulb temperatures indoors and outdoors.
4. Inspect the surrounding area (inside and outside) to ensure that the units’ clearances have not been compromised or altered.
5. Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris. Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as needed.
6. Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry thoroughly before reinstalling it in the chassis.
4
UNIT IDENTIFICATION
Model Number Code
S S 08 L 1 0 A
1st Digit – Function
S = Straight Cool, Value Series Y = Heat Pump E = Electric Heat K = Straight Cool R = Straight Cool X = Straight Cool W = Thru-the Wall,
WallMaster Series
2nd Digit
C = Casement Q = Q-Star S = Small Chassis M = Medium Chassis L = Large Chassis H = HazardGard
3rd and 4th Digit - Approximate BTU/HR (Cooling)
Heating BTU/Hr capacity listed in the Specifi cation/Performance Data Section
8th Digit – Engineering
Major change
7th Digit – Options
0 = Straight Cool & Heat Pump Models
1 = 1 KW Heat Strip, Normal 3 = 3 KW Heat Strip, Normal 4 = 4 KW Heat Strip, Normal 5 = 5 KW Heat Strip, Normal
6th Digit – Voltage
1 = 115 Volts 3 = 230-208 Volts
5th Digit
Alphabetical Modifi er
RAC Serial Number Identifi cation Guide
Serial Number Decade Manufactured
L=0 C=3 F=6 J=9
A=1 D=4 G=7
B=2 E=5 H=8
Year Manufactured
A=1 D=4 G=7 K=0
B=2 E=5 H=8
C=3 F=6 J=9
Month Manufactured
A=Jan D=Apr G=Jul K=Oct
B=Feb E=May H=Aug L=Nov
C=Mar F=Jun J=Sept M=Dec
L C G R 00001
Production Run Number
Product Line
R = RAC
P = PTAC
E = EAC
V = VPAK
H = Split
5
PERFORMANCE DATA
Model
EVAPORATOR AIR TEMP °F
Discharge
Air
CONDENSER
TEMP °F
Temp
Drop °F Suction Discharge
DISCHARGE
TEMP
SUCTION
TEMP
SUPER
HEAT
SUB-
COOLING
OPERATING PRESSURES
ELECTRICAL RATINGS
Amps
Cool
Amps
Heat
Locked
Rotor Amps
R-22
REF.
Charge
in OZ.
BREAKER
FUSE
Voltage
60 Hertz
Amps
Q-Chassis
XQ05L10-A 54 27 120 150 68 17 19 85 256 4.8 28.0 18.3 115 15 XQ06L10-A 55 26 121 157 65 13 27 87 261 5.0 24.0 21.0 115 15 XQ08L10-A 52 29 128 167 60 13 33 81 283 6.8 36.2 22.1 115 15 XQ10L10-A 50 31 130 176 65 20 29 75 287 9.2 44.0 19.2 115 15 XQ12L10-A 51 29 126 166 51 6 30 75 271 11.0 56.0 31.0 115 15 EQ08L11-A 52 29 124 173 69 21 29 82 283 6.5 10.7 36.2 20.0 115 15
S-Chassis
SS08L10-B 56 24 119 154 68 13 26 85 252 6.6 36.2 23.0 115 15 KS10L10-A 52 29 117 162 64 15 21 83 244 8.0 42.0 26.0 115 15 RS10L10-A 58 23 117 166 68 15 21 83 244 8.0 42.0 26.0 115 15 SS10L10-B 57 23 117 166 65 16 23 82 243 7.5 42.0 26.0 115 15 KS12L10-A 52 29 122 169 61 13 24 82 266 9.0 44.0 26.5 115 15 RS12L10-A 53 27 124 169 62 13 30 82 266 9.3 44.0 32.0 115 15 SS12L10-B 53 27 124 169 62 13 30 82 266 9.3 44.0 32.0 115 15 KS15L10 -A 51 30 125 182 62 16 29 77 278 12.2 61.0 29.0 115 15 RS15L10-A 53 27 125 184 62 16 27 77 278 12.3 61.0 29.0 115 15 SS14L10-B 53 27 125 184 62 15 27 78 268 12.3 61.0 29.2 115 15 KS12L30 -A 48 32 129 176 48 34 36 76 287 12.3 24.0 31.0 208 / 230 15 SS12L30 -B 57 24 121 170 67 17 27 83 258 5.4 21.0 28.0 208 / 230 15 SS16L30-B 50 31 130 176 53 8 35 77 279 7.9 35.0 32.1 208 / 230 15 RS16L30-A 50 31 130 176 53 8 35 77 279 7.4 35.0 32.0 208 / 230 15 ES12L33-A 56 25 121 167 65 15 28 83 256 4.8 15.1 21.0 28.0 208 / 230 20 ES16L33-A 49 32 130 179 50 8 34 75 279 7.4 15.1 35.0 32.0 208 / 230 20 YS09L10-A 60 20 116 164 71 18 17 89 239 7.1 8.5 44.0 25.1 115 15 YS09L10-B 60 20 116 164 71 18 17 89 239 7.1 8.5 44.0 25.1 115 15 YS09L10A-A 60 20 116 164 71 18 17 89 239 7.1 8.5 44.0 25.1 115 15 YS13L33-A 58 23 123 175 69 22 29 79 266 5.2 5.3 / 15.1 24.0 30.0 208 / 230 20
M-Chassis
KM24L30-A 50 31 132 187 56 14 37 70 287 11.2 68.0 53.0 208 / 230 20 RM24L30-A 50 31 132 187 56 14 37 70 287 11.2 68.0 53.0 208 / 230 20 YM18L34-A 49 31 125 182 64 22 27 72 271 8.5 8.7 / 18.6 41.0 43.0 208 / 230 30 RM18L30-A 49 31 125 175 63 21 31 72 271 8.7 42.0 39.5 208 / 230 15 EM18L34-A 49 31 125 175 63 21 31 72 271 8.1 18.9 42.0 39.5 208 / 230 15 KM18L30-A 49 31 125 175 63 21 31 72 271 8.1 42.0 39.5 208 / 230 15 SM18L30-A 53 28 122 175 66 13 25 82 255 7.3 37.0 44.0 208 / 230 15 KM21L30-A 50 31 127 185 57 15 34 73 274 9.4 43.0 45.0 208 / 230 15 SM21L30-A 50 31 127 185 57 15 34 73 274 9.4 43.0 45.0 208 / 230 15 EM24L35 50 31 132 187 56 14 37 70 287 11.2 25.0 68.0 53.0 208 / 230 30 SM24L30 50 31 132 187 56 14 37 70 287 11.2 68.0 53.0 208 / 230 20
L-Chassis
SL28L30-A 53 28 128 172 56 13 29 73 259 13.0 68.0 50.1 208 / 230 20 SL36L30-A 49 31 133 192 53 12 37 70 287 17.2 91.0 57.6 208 / 230 30 SL36L30-B 49 31 133 192 53 12 37 70 287 17.2 91.0 57.6 208 / 230 30 EL36L35-A 49 32 133 194 53 13 38 70 302 18.0 25.0 91.0 60.0 208 / 230 30 YL24L35-A 52 29 122 175 65 23 29 72 262 10.9 11.2 / 24.6 68.0 74.0 208 / 230 30
Casement
SC06L10-A 47 33 128 166 47 14 23 74 290 6.7 40.0 20.0 115 15
HazardGard
SH15L30-A 54 26 206 129 61 16 98 76 258 8.2 28.5 208 / 230 15 SH20L30-A 46 34 125 196 52 8 28 75 271 10.1 39.0 208 / 230 20
6
ELECTRICAL DATA
Wire Size Use ONLY wiring size recommended for
single outlet branch circuit.
Fuse/Circuit Use ONLY type and size fuse or HACR
Breaker circuit breaker indicated on unit’s rating
plate. Proper current protection to the unit is the responsibility of the owner.
Grounding Unit MUST be grounded from branch
circuit through service cord to unit, or through separate ground wire provided on permanently connected units. Be sure that branch circuit or general purpose outlet is grounded.
Receptacle The fi eld supplied outlet must match plug on
service cord and be within reach of service cord. Do NOT alter the service cord or plug. Do NOT use an extension cord. Refer to the table above for proper receptacle and fuse type.
ELECTRIC SHOCK HAZARD.
Turn off electric power before service or installation.
All electrical connections and wiring MUST be installed by a qualifi ed electrician and conform to the National Electrical Code and all local codes which have jurisdiction.
Failure to do so can result in property damage, personal injury and/or death.
The consumer - through the A HAM Room Air Conditioner Cer tifi cation Program - can be certain that the AHAM Certifi cation Seal accurately states the unit ’s cooling and heating capacity rating, the amperes and the energy effi ciency ratio.
7
FUNCTIONAL COMPONENT DEFINITIONS
MECHANICAL COMPONENTS
Bellows condensate valve Temperature-sensitive valve
that opens up to drain off condensate water when the outside temperature falls below 40°F and closes when the outside temperature reaches 58°F.
Vent door Allows introduction of fresh air into the room and/or exhausts stale room air outside (on select models.)
Plenum assembly Diffuser with directional louvers used to direct the conditioned airfl ow.
Blower wheel Attaches to the indoor side of the fan motor shaft and is used for distributing unconditioned, room side air though the heat exchanger and delivering conditioned air into the room.
Slinger fan blade Attaches to the outdoor side of the fan motor shaft and is used to move outside air through the condenser coil, while slinging condensate water out of the base pan and onto the condenser coil, thus lowering the temperature and pressures within the coil.
ELECTRICAL COMPONENTS
Thermostat Used to maintain the specifi ed room side
comfort level
System switch Used to regulate the operation of the fan motor, the compressor or to turn the unit off. For troubleshoot­ing, refer to the wiring diagrams and schematics in the back of this service manual.
Capacitor Reduces line current and steadies the voltage supply, while greatly improving the torque characteristics of the fan motor and compressor motor.
ELECTRICAL COMPONENTS cont’d
MoneySaver® switch When engaged, it sends the power
supply to the fan motor through the thermostat, which allows for a cycle-fan operation.
Fan Motor Dual-shafted fan motor operates the indoor blower wheel and the condenser fan blade simultaneously.
Solenoid Used to energize the reversing valve on all heat pump units.
Heating element Electric resistance heater, available in 3.3,
4.0 or 5.2 kW on select TwinTemp
®
models.
Heat anticipator Used to provide better thermostat and room air temperature control.
HERMETIC COMPONENTS
Compressor Motorized device used to compress refrigerant
through the sealed system.
Reversing valve A four-way switching device used on all heat pump models to change the fl ow of refrigerant to permit heating or cooling.
Check valve A pressure-operated device used to direct the fl ow of refrigerant to the proper capillary tube, during either the heating or cooling cycle.
Capillary tube A cylindr ic al met er dev ice used t o eve nly di s­tribute the fl ow of refrigerant to the heat exchangers (coils.)
ELECTRONIC CONTROLS
TESTING THE ELECTRONIC CONTROLS
CHECK FILTER light will come on after 250 hours of use.
Touch CHECK FILTER to reset.
8
PM
72
Cool
Cooler
Speed
1-4
A/C
Stop
On/Off
Set Hour
Clock
Money
Saver
Warmer
Smart
Fan
A/C
Start
Check
Filter
Press to reset
Fan
Only
0F/0
C
Timer
On/Off
Electronic Control
ELECTRONIC CONTROLS
TESTING THE ELECTRONIC CONTROL
XQ/WS BOARDS & QME BOARDS
Activating Test Mode: Activate test mode by pressing at the same time the “MODE” button and the temperature
“DOWN” button on XQ & WS models. LEDs for Hour, Start,
and Stop will blink 1 bps while Test Mode is active.
Activate test mode by pressing at the same time the “MONEY
SAVER” button and the “CHECK FILTER” button on QME models. LED for the Filter Alert will blink 1 bps while Test
Mode is active.
Test Mode has duration of 90 minutes. Test Mode can be
activated under any conditions, including Off. Test Mode is cancelled by pressing the On/Off button, unplugging the unit, or when the 90 minutes is timed out. All settings revert to the factory default settings of Cool, 75° F, Timer and Set Hour features are nonfunctional.
Test Mode overrides the three-minute lockout, all delays for
compressor and fan motor start / speed change, and no delay when switching modes.
Test Mode default settings are ON, Money Saver, 60° F, and
High fan speed.
Activating Error Code Mode: (Submode of Test Mode) Unit must be in Test Mode to enter Error Code Mode
Activate Error Code Mode b y pressi ng the “TIMER ON/OFF” button on XQ & WS models. LED for the “TIMER ON/OFF” will fl ash 1 bps while Error Code Mode is active. Pressing the
“TEMP/HR + “ button will display 00. Consecutive presses
will scroll through all error codes logged. Press the “TEMP/ HR - “ button to see the reverse order of all error codes
logged. When the end of logged error codes is reached the
temperature set point will appear.
Activate Error Code Mode by pressing at the same time the
“A/ C START ” button and the “ON/OFF” button on QME
models. LED for the “TIMER ON/OFF” will fl ash 1 bps while Error Code Mode is active. Pressing the “WARMER” button will display 00. Consecutive presses will scroll through all error codes logged. Press the “COOLER” button to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.
TESTING THE ELECTRONIC CONTROL
ERROR CODE LISTINGS
IMPORTANT: Error Codes are cleared from the
log by exiting from Error Code Mode. To exit on XQ models, press Timer On/Off button. To exit QME models, press A/C Start and On/Off buttons. Or un plug u nit t o ex i t Error Code Mode. P l ug unit in a f ter 5 seconds to resume normal operation of unit.
TESTING THE ELECTRONIC CONTROL
ERROR CODE LISTINGS
E1 SHORT CYCLE SITUATION: Keyboard is fine.
Investigate and defi ne short cycling problem.
E2 KEYBOARD STUCK ERROR: If key button(s) are pressed continuously for twenty seconds or more. If MODE key is stuck, unit will default to cool. Exit Error Code Mode to see if error “E2 ” is no longer displayed and unit is f unc tioning. Replace board if “E2” still displays after exiting Error Code Mode.
E3 FROST PROBE OPEN: If ohm value is present, replace board.
E4 FROST PROBE SHORT: Replace board.
E5 INDOOR PROBE OPEN: Replace board.
E6 INDOOR PROBE SHORT: Replace board.
NOTE: All Error Code displays for Frost & Indoor Probe will allow
unit to operate. Unit may or will ice up if faulty components not replaced.
FROST PROBE SENSOR: disables compressor at 35° F.
INDOOR PROBE SENSOR: Control range is 60° F to 90°
F +/- 2° F.
Indoor temperature will be displayed by pressing:
(QME units) The Fan Speed button and the Warmer button.
(XQ units) The Fan Speed button and the Temp Up button.
The indoor temperature will be displayed for 10 seconds. The display will change back to the Set Point temperature by
pressing any key button except for the On/Off button. The indoor temperature can be viewed in all modes, including test mode.
Check Filter: The Check Filter indicator turns on after the fan motor has been operating for 250 hours. The Check Filter indicator is reset by pressing the Check Filter button one time only,. Power failures will not reset the 250 hour timer. All time elapsed is stored in memory and resumes counting after power is restored.
Keep Alive: The electronic control has a memory to retain all functions and status as set up by the user in the event of a power failure. Once power is restored to the unit there is a two second delay before the fan comes on and approximately three minutes delay before the compressor is activated, providing that the mode was set for cooling and the set point temperature has not been met in the room.
9
REFRIGERATION SYSTEM SEQUENCE OF OPERATION
A good understanding of the basic operation of the refrigera­tion system is essential for the service technician. Without this understanding, accurate troubleshooting of refrigeration system problems will be more diffi cult and time consuming, if not (in some cases) entirely impossible. The refrigeration system uses four basic pr inciples (laws) in its operation they are as follows:
1. “Heat always fl ows from a warmer body to a cooler body.”
2. “Heat must be added to or removed from a substance
before a change in state can occur”
3. “Flow is always from a higher pressure area to a lower
pressure area.”
4. “The temperature at which a liquid or gas changes state
is dependent upon the pressure.”
The refrigeration cycle begins at the compressor. Starting
the compressor creates a low pressure in the suction line which draws refrigerant gas (vapor) into the compressor.
The compressor then “compresses” this refrigerant, raising
its pressure and its (heat intensity) Temperature.
The refrigerant leaves the compressor through the discharge
line as a hot high pressure gas (vapor). The refrigerant enters the condenser coil where it gives up some of its heat. The condenser fan moving air across the coil’s fi nned surface facilitates the transfer of heat from the refrigerant to the relatively cooler outdoor air.
When a suffi cient quantity of heat has been removed from the refrigerant gas (vapor), the refrigerant will “condense” (i.e. change to a liquid). Once the refrigerant has been condensed (changed) to a liquid it is cooled even further by the air that continues to fl ow across the condenser coil.
The RAC design determines at exactly what point (in the
condenser) the change of state (i.e. gas to a liquid) takes place. In all cases, however, the refrigerant must be totally condensed (changed) to a liquid before leaving the condenser coil.
The refrigerant leaves the condenser coil through the liquid
li ne as a w arm high pressure liqui d. It n ext will pass thr ough the refrigerant drier (if so equipped). It is the function of the drier to trap any moisture present in the system, contaminants, and large particulate matter.
The liquid refrigerant next enters the metering device. The
metering device is a capillary tube. The purpose of the metering device is to “meter” (i.e. control or measure) the quantity of refrigerant entering the evaporator coil.
In the case of the capillary tube this is accomplished (by design) through size (and length) of device, and the pressure difference present across the device.
Since the evaporator coil is under a lower pressure (due to the suction created by the compressor) than the liquid line,
the liquid refrigerant leaves the metering device entering the evaporator coil. As it enters the evaporator coil, the larger area and lower pressure allows the refrigerant to expand and lower its temperature (heat intensity). This expansion is often referred to as “boiling”. Since the unit’s blower is moving Indoor air across the fi nned surface of the evaporator coil, the expanding refrigerant absorbs some of that heat. This results in a lowering of the indoor air temperature, hence the “cooling” effect.
The expansion and absorbing of heat cause the liquid
refrigerant to evaporate (i.e. change to a gas). Once the refrigerant has been evaporated (changed to a gas), it is heated even further by the air that continues to fl ow across the evaporator coil.
The particular system design determines at exactly what
point (in the evaporator) the change of state (i.e. liquid to a gas) takes place. In all cases, however, the refrigerant must be totally evaporated (changed) to a gas before leaving the evaporator coil.
The low pressure (suction) created by the compressor
causes the refrigerant to leave the evaporator through the suction line as a cool low pressure vapor. The refrigerant then returns to the compressor, where the cycle is repeated.
Refrigerant System Components
Suction Line
Evaporator Coil
Metering Device
Refrigerant Dryer
Refrigerant Drier
SEALED REFRIGERATION SYSTEM REPAIRS
Discharge Line
Condenser Coil
Compressor
Liquid
Line
IMPORTANT
ANY SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LI QU ID LINE DRIER. ALSO, A NY SE ALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRE THE INSTALLATION OF A SUCTION LINE DRIER.
10
EQUIPMENT REQUIRED
HERMETIC COMPONENT REPLACEMENT cont’d
1. Voltmeter
2. Ammeter
3. Ohmmeter
4. E.P.A. Approved Refrigerant Recovery System.
5. Vacuum Pump (capable of 200 microns or less vacuum.)
6. Acetylene Welder
7. Electronic Halogen Leak Detector (G.E. Type H-6 or
equivalent.)
8. Accurate refrigerant charge measuring device such as: a. Balance Scales - 1/2 oz. accuracy b. Charging Board - 1/2 oz. accuracy
9. High Pressure Gauge - (0 - 400 lbs.)
10. Low Pressure Gauge - (30 - 150 lbs.)
11. Vacuum Gauge - (0 - 1000 microns)
EQUIPMENT MUST BE CAPABLE OF:
1. Recovery CFC’s as low as 5%.
2. Evacuation from both the high side and low side of the
system simultaneously.
3. Introducing refrigerant charge into high side of the
system.
4. Accurately weighing the refrigerant charge actually
introduced into the system.
5. Facilities for fl owing nitrogen through refrigeration
tubing during all brazing processes.
HERMETIC COMPONENT REPLACEMENT
The following procedure applies when replacing components
in the sealed refrigeration circuit or repairing refrigerant
le aks. (Comp resso r, condenser, evaporator, capillar y tube, refrigerant leaks, etc.)
1. Recover the refrigerant from the system at the process
tub e located on t he high si de of the s ystem by ins talling a line tap on the process tube. Apply gauge from process tube to EPA approved gauges from process tube to EPA approved recovery system. Recover CFC’s in system to at least 5%.
2. Cut the process tube below pinch off on the suction
side of the compressor.
3. Connect the line from the nitrogen tank to the suction
process tube.
4. Drift dry nitrogen through the system and un-solder
the more distant connection fi rst. (Filter drier, high side process tube, etc.)
5. Replace inoperative component, and always install a
new fi lter drier. Drift dry nitrogen through the system when making these connections.
6. P res sur ize sy stem to 30 PS IG w ith proper refr igerant and boost refrigerant pressure to 150 PSIG with dry nitrogen.
7. Leak test complete system with electric halogen leak detector, correcting any leaks found.
8. Reduce the system to zero gauge pressure.
9. Connect vacuum pump to high side and low side of system with deep vacuum hoses, or copper tubing. (Do not use regular hoses.)
10. Evacuate system to maximum absolute holding pressure of 200 microns or less. NOTE: This process can be accelerated by use of heat lamps, or by breaking the vacuum with refrigerant or dry nitrogen at 5,000 microns. Pressure system to 5 PSIG and leave in system a minimum of 10 minutes. Release refrigerant, and proceed with evacuation of a pressure of 200 microns or less.
11. Break vacuum by charging system from the high side with the correct amount of liquid refrigerant specifi ed.
This will prevent boiling the oil out of the crankcase,
and damage to the compressor due to over heating.
NOTE: If the entire charge will not enter the high side, allow the remainder to enter the low side in small increments while operating the unit.
12. Restart unit several times after allowing pressures to stabilize. Pinch off process tubes, cut and solder the ends. Remove pinch off tool, and leak check the process tube ends.
SPECIAL PROCEDURE IN THE CASE OF COMPRESSOR MOTOR BURNOUT
1. Recover all refrigerant and oil from the system.
2. Remove compressor, capillary tube and fi lter drier from the system.
3. Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent, to remove all contamination from system. Inspect suction and discharge line for carbon deposits. Remove and clean if necessary.
4. Reassemble the system, including new drier strainer and capillary tube.
5. Proceed with processing as outlined under hermetic component replacement.
ROTARY COMPRESSOR SPECIA L TROUBLESHOOTI NG AND SERVICE
Basically, troubleshooting and servicing rotary compressors is the same as on the reciprocating compressor with only one main exception:
NEVER, under any circumstances, charge a rotary
compressor through the LOW side. Doing so would cause permanent damage to the new compressor.
11
REFRIGERANT CHARGING
NOTE: BECAUSE THE RAC SYSTEM IS A SEALED
SYSTEM, SERVICE PROCESS TUBES WILL HAVE TO BE INSTALLED. FIRST INSTALL A LINE TAP AND REMOVE REFRIGERANT FROM SYSTEM. MAKE NECESSARY SEALED SYSTEM REPAIRS AND VACUUM SYSTEM. CRIMP PROCESS TUBE LINE AND SOLDER END SHUT. DO NOT LEAVE A SERVICE VALVE IN THE SEALED SYSTEM.
Proper refrigerant charge is essential to proper unit operation. Operating a unit with an improper refrigerant charge will result in reduced performance (capacity) and/or effi ciency. Accordingly, the use of proper charging methods during servicing will insure that the unit is functioning as designed and that its compressor will not be damaged.
Too much refrigerant (overcharge) in the system is just as
bad (if not worse) than not enough refrigerant (undercharge).
They both can be the source of certain compressor failures if
they remain uncorrected for any period of time. Quite often, other problems (such as low air fl ow across evaporator, etc.) are misdiagnosed as refrigerant charge problems. The refrigerant circuit diagnosis chart will assist you in properly diagnosing these systems.
An overcharged unit will at times return liquid refrigerant (slugging) back to the suction side of the compressor eventually causing a mechanical failure within the compressor.
This mechanical failure can manifest itself as valve failure,
bearing failure, and/or other mechanical failure. The specifi c type of f ailure w ill be in fl uenced by the amount of li quid bei ng returned, and the length of time the slugging continues.
Not enough refrigerant (Undercharge) on the other hand, will cause the temperature of the suction gas to increase to the point where it does not provide suffi cient cooling for the
compressor motor. When this occurs, the motor winding temperature will increase causing the motor to overheat and possibly cycle open the compressor overload protector. Continued overheating of the motor windings and/or cycling of the overload will eventually lead to compressor motor or overload failure.
METHOD OF CHARGING
The acceptable method for charging the RAC system is the
Weighed in Charge Method. The weighed in charge method is applicable to all units. It is the preferred method to use, as it is the most accurate.
The weighed in method should always be used whenever
a charge is removed from a unit such as for a leak repair, compressor replacement, or when there is no refrigerant charge left in the unit. To charge by this method, requires the following steps:
1. Install a piercing valve to remove refrigerant from the sealed system. (Piercing valve must be removed from the system before recharging.)
2. Recover Refrigerant in accordance with EPA regulations.
3. Install a process tube to sealed system.
4. Make necessary repairs to system.
5. Evacuate system to 250 - 300 microns or less.
6. Weigh in refrigerant with the property quantity of R-22 refrigerant.
7. Start unit, and verify performance.
8. Crimp the process tube and solder the end shut.
NOTE: In order to access the sealed system it will be necessary to install Schrader type fi ttings to the process tubes on the discharge and suction of the compressor. Proper refrigerant recovery procedures need to be adhered to as outlined in EPA Regulations. THIS SHOULD ONLY BE ATTEMPTED BY QUALIFIED SERVICE PERSONNEL.
12
REFRIGERANT CHARGING cont’d
UNDERCHARGED REFRIGERANT SYSTEMS
An und ercharged syste m will re sult in poor per formance (l ow pressures, etc.) in both the heating and cooling cycle.
Whenever you service a unit with an under charge of refrigerant, always suspect a leak. The leak must be repaired before charging the unit.
To check for an undercharged system, turn the unit on, allow
the compressor to run long enough to establish working pressures in the system (15 to 20 minutes).
During the cooling cycle you can listen carefully at the exit of the metering device into the evaporator; an intermittent hissing and gurgling sound indicates a low refrigerant charge.
NOTE: Heat pump refrigeration drawing
Intermittent frosting and thawing of the evaporator is another indication of a low charge, however, frosting and thawing can also be caused by insuffi cient air over the evaporator.
Checks for an undercharged system can be made at the compressor . If the compressor seems quieter than normal, it is an indication of a low refrigerant charge. A check of the amper age drawn by the compressor motor should show a lower reading. (Check the Unit Specifi cation.) After the unit has run 10 to 15 minutes, check the gauge pressures.
Gauges connected to system with an under charge will have low head pressures and substantially low suction pressures.
OVERCHARGED REFRIGERANT SYSTEMS
Compressor amps will be near normal or higher. Noncon­densables can also cause these symptoms. To confi rm,
remove some of the charge, if conditions improve, system may be overcharged. If conditions don’t improve, Noncon-
densables are indicated.
Whenever an overcharged system is indi cated, always make sure that the problem is not caused by air fl ow problems. Improper air fl ow ov er the e vap orator coil may in dicate s ome of the same symptoms as an overcharged system.
An over charge can cause the compressor to fail, since it would be “slugged” with liquid refrigerant.
The charge for any system is critical. When the compressor
is noisy, suspect an overcharge, when you are sure that the air quantity over the evaporator coil is correct. Icing of the evapora tor will not be encountered because the refriger ant will boil later if at all. Gauges connected to system will usually have higher head pressure (depending upon amount of overcharge). Suction pressure should be slightly higher.
13
REFRIGERANT CHARGING cont’d
RESTRICTED REFRIGERANT SYSTEM
A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.
Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other.
With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal current when compared to the unit specification. With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load). Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.
The following conditions are based primar ily on a system in the cooling mode.
Troubleshooting a restricted refrigerant system can be diffi cult. The following proce dures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.
• A partial restriction allows some of the refrigerant to circulate through the system.
• With a complete restriction there is no circulation of refrigerant in the system.
• Restricted refrigerant systems display the same symptoms as a “low-charge condition.”
• When the unit is shut off, the gauges may equal ize very slowly.
• Gauges connected to a completely re stricted system will run in a deep vacuum. When the unit is shut off, the gauges will not equalize at all.
14
TROUBLESHOOTING TOUCH TEST CHART: TO SERVICE REVERSING VALVES
NORMAL FUNCTION OF VALVE
VALVE OPERATING CONDITION
Normal Cooling
Normal Heating
Valve will not shift from cool to heat.
Valve will not shift from cool to heat.
Starts to shift but does not complete reversal.
Apparent leap in heating.
Will not shift from heat to cool.
NOTES:
COIL
Compressor
from Compressor
SUCTION TUBE to
DISCHARGE TUBE
Tub e to I N S I D E
COIL
LEFT Pilot
Tub e to O U T SIDE
Capillary Tube
RIGHT Pilot
Capillary Tube
* TEMPERATURE OF VALVE BODY
** WARMER THAN VALVE BODY
12 3 456 POSSIBLE CAUSES CORRECTIONS
Hot Cool
Hot Cool
Check Electrical circuit and coil
Check refrigeration charge
Hot Cool Cool,
Hot Cool
Hot Cool
Warm Cool
Hot Warm Warm Hot *TVB Hot
Hot Warm Warm Hot Hot Hot Both ports of pilot open.
Hot Hot Hot Hot *TVB Hot Body damage. Replace valve
Hot Hot Hot Hot Hot Hot Both ports of pilot open.
Hot Cool
Hot Cool
Hot Cool
Hot Cool
Hot Cool
Hot Cool
Warm Cool
Cool
as (2)
Hot
as (1)
as (2)
Cool, as (2)
Cool, as (2)
Cool, as (2)
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Warm,
as (1)
Hot
*TVB TVB
as (1)
Cool
*TVB TVB
as (2)
MALFUNCTION OF VALVE
No voltage to coil. Repair electrical circuit.
Defective coil. Replace coil.
Low charge. Repair leak, recharge system.
Pressure differential too high. Recheck system.
Hot,
*TVB Hot
as (1)
Hot,
*TVB *TVB Clogged pilot tubes.
as (1)
Hot,
as (1)
as (1)
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Hot Hot
Hot,
*TVB Warm Defective Compressor. Replace compressor
*TVB *TVB Piston needle on end of slide leaking.
** WVB ** WVB Pilot needle and piston needle leaking.
*TVB *TVB Pressure differential too high.
Hot *T VB Dirt in bleeder hole.
Hot *TVB Piston cup leak.
Hot Hot Defective pilot. Replace valve.
Warm *TVB Defective compressor. Replace compressor
Pilot valve okay. Dirt in one bleeder hole.
Piston cup leak
Both por ts of pilot open. (Back seat port did not close).
Not enough pressure differential at start of stroke or not enough fl ow to maintain pres­sure differential.
Body damage. Replace valve
Valve hung up at mid-stroke. Pumping vol­ume of compressor not suffi cient to maintain reversal.
Clogged pilot tube.
De-energize solenoid, raise head pres­sure, reenergize solenoid to break dirt loose. If unsuccessful, remove valve, wash out. Chec k on air before installing. If no movement, replace valve, add strainer to discharge tube, mount valve horizontally.
Stop unit. After pressures equalize, restart with solenoid energized. If valve shifts, reattempt with compressor running. If still no shift, replace valve.
Raise head pressure, operate solenoid to free. If still no shift, replace valve.
Raise head pressure, operate solenoid to free partially clogged port. If still no shift, replace valve.
Check unit for correct operating pressures and charge. Raise head pressure. If no shift, use valve with smaller port.
Raise head pressure, operate solenoid. If no shift, use valve with smaller ports.
Raise head pressure, operate solenoid. If no shift, use valve with smaller ports.
Raise head pressure, operate solenoid. If no shift, replace valve.
Operate valve several times, then recheck. If excessive leak, replace valve.
Operate valve several times, then recheck. If excessive leak, replace valve.
Stop unit. Will reverse during equalization period. Recheck system
Raise head pressure, operate solenoid to free dir t. If still no shift, replac e valve.
Raise head pressure, operate solenoid. Remove valve and wash out. Check on air before reinstalling, if no movement, replace valve. Add strainer to discharge tube. Mount valve horizontally.
Stop unit. After pressures equalize, restart with solenoid de -energized. If valve shift s, reattempt with compressor running. If it still will not reverse while running, replace the valve.
15
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Problem Possible Cause Action
Low voltage
T-stat not set cold enough or inop­erative
Compressor hums but cuts off on
Compressor does not run
Problem Possible Cause Action
Fan motor
does not run
B10 overload
Open or shorted compressor wind­ings
Open overload Test overload protector & replace if inoperative
Open capacitor Test capacitor & replace if inoperative
Inoperative system switch
Broken, loose or incorrect wiring
Inoperative system switch Test switch & replace if inoperative
Broken, loose or incorrect wiring Refer to applicable wiring diagram
Open capacitor Test capacitor & replace if inoperative
Fan speed switch open Test switch & replace if inoperative
Inoperative fan motor
Check voltage at compressor. 115V & 230V units will operate at 10% voltage variance
Set t-stat to coldest position. Test t-stat & replace if inoperative
Hard start compressor. Direct test compressor. If compressor starts, add starting components
Check for continuity & resistance
Test for continuity in all positions. Replace if inoperative
Refer to appropriate wiring diagrams to check wiring
Test fan motor & replace if inoperative (be sure internal overload has had time to reset)
16
Problem Possible Cause Action
Undersized unit Refer to industry standard sizing chart
Set to coldest position. Test t-stat & replace if necessary
Use pressure wash or biodegradable cleaning agent to clean
Close doors. Instruct customer on use of this feature
Check amperage draw against nameplate. If not conclusive, make pressure test
Does not cool or
only cools slightly
T-stat open or inoperative
Dirty fi lter Clean as recommended in Owner's Manual
Dirty or restricted condenser or evaporator coil
Poor air circulation Adjust discharge louvers. Use high fan speed
Fresh air or exhaust air door open on applicable models
Low capacity - undercharge Check for leak & make repair
Compressor not pumping properly
Problem Possible Cause Action
Replace fuse, reset breaker. If repeats, check
Fuse blown or circuit tripped
fuse or breaker size. Check for shorts in unit wiring & components
Power cord not plugged in Plug it in
Unit does not run
System switch in "OFF" position Set switch correctly
Inoperative system switch Test for continuity in each switch position
Loose or disconnected wiring at switch or other components
Check wiring & connections. Reconnect per wiring diagram
Problem Possible Cause Action
Dirty fi lter Clean as recommended in Owner's Manual
Check for dirty or obstructed coil. Use
Restricted airfl ow
pressure wash or biodegradable cleaning agent to clean
Evaporator coil
freezes up
Inoperative t-stat Test for shorted t-stat or stuck contacts
Short of refrigerant De-ice coil & check for leak
Inoperative fan motor Test fan motor & replace if inoperative
De-ice coil. Check temp. differential (delta T)
Partially restricted capillary tube
across coil. Touch test coil return bends for same temp. Test for low running current
Problem Possible Cause Action
Unit undersized. Test cooling performance & replace with larger unit if needed
Check for partially iced coil & check temperature split across coil
Check for oil at silver soldered connections. Check for partially iced coil. Check split across coil. Check for low running amperage
Check operation of t-stat. Replace if contacts remain closed.
Compressor runs
continually & does
not cycle off
Excessive heat load
Restriction in line
Refrigerant leak
T-stat contacts stuck
T-stat incorrectly wired Refer to appropriate wiring diagram
Problem Possible Cause Action
Disconnect power to unit. Remove cover
T-stat contacts stuck
of t-stat & check if contacts are stuck. If so, replace t-stat
T-stat does not turn
unit off
T-stat set at coldest point
Turn to higher temp. setting to see if unit cycles off
Incorrect wiring Refer to appropriate wiring diagrams
Unit undersized for area to be cooled
Refer to industry standard sizing chart
17
Problem Possible Cause Action
Overload inoperative. Opens too soon
Compressor restarted before system pressures equalized
Check operation of unit. Replace overload if system operation is satisfactory
Allow a minimum of 2 minutes to allow pressures to equalize before attempting to restart. Instruct customer of waiting period
Check voltage with unit operating. Check for
Compressor runs
for short periods
only. Cycles on
overload
Low or fl uctuating voltage
Incorrect wiring Refer to appropriate wiring diagram
Shorted or incorrect capacitor
Restricted or low air fl ow through condenser coil
Compressor running abnormally hot
other appliances on circuit. Air conditioner should be in separate circuit for proper voltage & fused separately
Check by substituting a known good capacitor of correct rating
Check for proper fan speed or blocked condenser
Check for kinked discharge line or restricted condenser. Check amperage
Problem Possible Cause Action
Place jumper across t-stat terminals to check if unit operates. If unit operates, replace t-stat.
T-stat does not
turn unit on
Loss of charge in t-stat bulb
Loose or broken parts in t-stat Check as above
Incorrect wiring Refer to appropriate wiring diagram
Problem Possible Cause Action
Poorly installed
Refer to Installation Manual for proper installation
Fan blade striking chassis Reposition - adjust motor mount
Noisy operation
Compressor vibrating
Check that compressor grommets have not deteriorated. Check that compressor mounting parts are not missing
Improperly mounted or loose cabinet parts
Check assembly & parts for looseness, rubbing & rattling
Problem Possible Cause Action
Evaporator drain pan overfl owing Clean obstructed drain trough
Evaporator drain pan broken or cracked. Reseal or replace
Check installation instructions. Reseal as required
Clean the dirty evaporator coil. Use pressure wash or biodegradable cleaning agent to clean
Water leaks into
the room
Condensation forming on base pan
Poor installation resulting in rain entering the room
Condensation on discharge grille louvers
Chassis gasket not installed Install gasket, per Installation manual
Downward slope of unit is too steep
Refer to installation manual for proper installation
18
Problem Possible Cause Action
Water "spitting"
into room
Sublimation: When unconditioned saturated, outside air mixes with conditioned air, condensation forms on the cooler surfaces
Downward pitch of installation is too steep
Restricted coil or dirty fi lter
Ensure that foam gaskets are installed in between window panes & in between the unit & the sleeve. Also, ensure that fresh air/exhaust vents (on applicable models) are in the closed position & are in tact
Follow installation instructions to ensure that downward pitch of installed unit is no less than 1/4" & no more than 3/8"
Clean & advise customer of periodic cleaning & maintenance needs of entire unit
Problem Possible Cause Action
Excessive moisture
Insuffi cient air circulation thru area to be air conditioned
Oversized unit Operate in "MoneySaver" position
Adjust louvers for best possible air circulation
Inadequate vapor barrier in building structure, particularly
Advise customer
fl oors
Problem Possible Cause Action
T-stat differential too narrow Replace t-stat
T-stat short cycles
Plenum gasket not sealing, allowing discharge air to short cycle t-stat
Restricted coil or dirty fi lter
Check gasket. Reposition or replace as needed
Clean & advise customer of periodic cleaning & maintenance needs of entire unit
Problem Possible Cause Action
Anticipator (resistor) wire disconnected at t-stat or system
Refer to appropriate wiring diagram
switch
Prolonged off
cycles (automatic
operation)
Anticipator (resistor) shorted or open
Disconnect plus from outlet. Remove resistor from bracket. Insert plug & depress "COOL" & "FAN AUTOMATIC" buttons. Place t-stat to warmest setting. Feel resistor for temperature. If no heat, replace resistor
Partial loss of charge in t-stat bulb causing a wide differential
Replace t-stat
Problem Possible Cause Action
Outside water
leaks
Evaporator drain pan cracked or obstructed
Water in compressor area
Obstructed condenser coil
Fan blade/slinger ring improperly positioned
Repair, clean or replace as required
Detach shroud from pan & coil. Clean & remove old sealer. Reseal, reinstall & check
Use pressure wash or biodegradable cleaning agent to clean
Adjust fan blade to 1/2" of condenser coil
19
HEAT / COOL ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Problem Possible Cause Action
Disconnect power to unit. Remove resistor Heat anticipator (resistor) shorted (on applicable models)
Room temperature
uneven
(Heating cycle)
Problem Possible Cause Action
Unit will not defrost
Wide differential - partial loss of t-stat bulb charge
Incorrect wiring
Incorrect wiring Refer to appropriate wiring diagram
Defrost control timer motor not advancing (applicable models)
Defrost control out of calibration (applicable models)
Defrost control contacts stuck
Defrost control bulb removed from or not making good coil contact
from t-stat bulb block. Plus in unit & allow to
operate. Feel resistor for heat. If not heat,
replace resistor
Replace t-stat & check
Refer to appropriate wiring diagram. Resistor
is energized during "ON" cycle of compressor
or fan.
Check for voltage at "TM" & "TM1" on timer. If
no voltage, replace control
If outside coil temperature is 25F or below, &
preselected time limit has elapsed, replace
defrost control
If contacts remain closed between terminals
"2" & "3" of the defrost control after
preselected time interval has passed, replace
control
Reinstall & be assured that good bulb to coil
contact is made
Problem Possible Cause Action
Check if operating properly. Instruct customer
on proper use of control
Check heat rise across coil. If unit operates
effi ciently, check if insulation can be added
to attic or walls. If insulation is adequate,
recommend additional unit or larger one
T-stat should close at 38°F. Check continuity of
control. If temperature is below 38°F, replace
control
Check for adequate fan air across heater.
Check control for open at 160°F & close at
150°F
Does not heat
adequately
Exhaust or fresh air door open
Dirty fi lter Clean as recommended in Owner's Manual
Unit undersized
Outdoor t-stat open (applicable models)
Heater hi-limit control cycling on & off
Shorted supplementary heater Ohmmeter check, approx. 32-35 ohms
Incorrect wiring Check applicable wiring diagram
20
Problem Possible Cause Action
Incorrect wiring Refer to applicable wiring diagram
Defective solenoid coil Check for continuity of coil
Unit cools when
heat is called for
Reversing valve fails to shift
Block condenser coil & switch unit to cooling.
Allow pressure to build up in system, then
switch to heating. If valve fails to shift, replace
valve.
Inoperative system switch Check for continuity of system switch
Problem Possible Cause Action
Heating capillary tube partially restricted
Check for partially starved outer coil. Replace
heating capillary tube
Switch unit several times from heating to
Cooling adequate,
but heating
insuffi cient
Check valve leaking internally
cooling. Check temperature rise across
coil. Refer to specifi cation sheet for correct
temperature rise
De-energize solenoid coil, raise head Reversing valve failing to shift completely; bypassing hot gas
pressure, energize solenoid to break loose.
If valve fails to make complete shift, replace
valve.
TROUBLESHOOTING CHART — COOLING
REFRIGERANT SYSTEM DIAGNOSIS – HEATING
Low Suction Pressure High Suction Pressure Low Head Pressure High Head Pressure
Low Load Conditions High Load Conditions Low Load Conditions High Load Conditions
Low Air Flow Across High Air Flow Across Refrigerant System Low Air Flow Across Indoor Coil Indoor Coil Restriction Outdoor Coil
Refrigerant System Reversing Valve not Reversing Valve not Restriction Fully Seated Fully Seated
Undercharged Overcharged
Moisture in System Defective Compressor Defective Compressor
Undercharged
in System
Overcharged
Noncondensables (air)
21
TROUBLESHOOTING CHART — HEATING
REFRIGERANT SYSTEM DIAGNOSIS – HEATING
Low Suction Pressure High Suction Pressure
Low Airfl ow
Across Outdoor Coil
Refrigerant System
Restriction
Undercharged Overcharged
Moisture in System Defective Compressor
Outdoor Ambient Too High
for Operation in Heating
Reversing Valve not
Fully Seated
ELECTRICAL TROUBLESHOOTING CHART — HEAT PUMP
HEAT PUMP
Low Head Pressure
Refrigerant System
Restriction
Reversing Valve not
Fully Seated
Undercharged
Defective Compressor
High Head Pressure
Outdoor Ambient Too High
For Operation In Heating
Low Airfl ow Across
Indoor Coil
Overcharged
Noncondensables (air)
Is Line Voltage
Present at the Solenoid
YES
Is the Solenoid Coil Good?
YES
Reversing Valve Stuck
Replace the Reversing Valve
SYSTEM COOLS WHEN
HEATING IS DESIRED.
NO
NO
Is the Selector Switch
Set for Heat?
Replace the Solenoid Coil
22
MODEL
SC06H10D
23
MODELS
XQ05L10-A,B; XQ06L10-A,B,C,D; XQ08L10-A,B; XQ10L10-A,B; XQ12L10-A,B
24
MODELS
KS10L10-A, RS10L10-A, KS12L10-A, KS12L30-A, KS15L10-A, RS15L10-A, RS16L30-A,
RM18L30-A, KM18L30-A, KM21L30-A, RM24L30-A, KM24L30-A
25
MODELS
SS08L10-A/B, SS10L10-A/B, SS12L10-A/B; SS12L30-A/B, SS14L10-A/B,
SS16L30-A/B, SM18L30-A/B, SM21L30-A/B, SM24L30-A/B
26
MODEL
SL36L30-A
27
MODEL
SL28L30-A
28
MODELS
SL36L30-B
29
MODEL
EQ08L11-A
30
MODELS
ES12L33-A, ES16L33-A, EM18L34-A, EM24L35-A
31
MODEL
EL36L35-A
32
MODEL
YS09L10-A, YS09L10-B
33
MODELS
YS13L33-A, YM18L34-A
34
MODELS
YL24L35-A
35
Friedrich Air Conditioning Co. Post Office Box 1540 • San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway • San Antonio, Texas 78218-5212 (210) 357-4400 • FAX (210) 357-4480 www.friedrich.com
Printed in the U.S.A.
RAC-Svc-06 (3-06)
Loading...