Friedrich VEA09K00SPE, VEA09K50SPE, VEA12K00RTE, VEA12K00RTG, VEA12K25RTB Owner’s Manual

...
Vert-I-Pak®
SinglePackageVerticalAirCenditieningSystem
A-Series 9,000 I 12,000 I 18,000 BTU/h
Installation& OperationManual
920-075-07 (10-03)
920-075-07(10-03)
TableofContents
GeneralSpecifications
InstallationRecommendations.......................................................................................................................................... 3
Model NumberIdentification Guide ................................................................................................................................... 4
VERT-I-PAKChassisSpecifications .................................................................................................................................... 4
III.
IV.
V.
Installation
1. UtilityClosetDimensions................................................................................................................................................... 5
2. WallPlenum&ArchitecturalLouverInstallation................................................................................................................ 6
3. ElectricalInformation ..................................................................................................................................................... 7-9
4. IndoorReturnAirGrillelnstallation .................................................................................................................................. 10
5. DuctworkPreparationandCFM....................................................................................................................................... 11
6. ChassisInstallation.......................................................................................................................................................... 11
7. ChassisFinalConnections (Electrical,Duct,Drain& WallThermostat) ............................................................................ 12
8. FinalInstallationChecklist............................................................................................................................................... 12
ChassisOperation
9. ThermostatControl .......................................................................................................................................................... 13
10. LowAmbientProtection for Compressor& Fan................................................................................................................ 13
11. HeatingDefrost(HeatPumpModelsonly)........................................................................................................................ 13
12. FreshAirDoor................................................................................................................................................................... 13
13. CondensateDisposalSystem .......................................................................................................................................... 13
Service& Warranty
14. Servicing/ ChassisQuickChangeouts............................................................................................................................. 13
15. Warranty.......................................................................................................................................................................... 14
Ver_l-PakAccessories .................................................................................................................................................... 15
Please read this manual thoroughly prior to equipment installation or operation, it is the installer's responsibility to properly apply and install the equipment, installation must be in conformance
with the NFPA 70-2002 National Electric Code or current edition and Universal Mechanical Code current edition and applicable local or national codes.
Proper installation is not difficult but it is essential.
2
920-075-07 (10-03)
Vert-I-Pak Installation Recommendations
Forproperunitperformanceandmaximumoperatinglifepleaserefertothe minimuminstallationclearancesbelow.
Figure I
VERT-I-PAK ® units must be installed on an outside wall. Confined spaces and/or covered areas should be avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more
units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical
clearance of 60" should be maintained between units. Units installed on the bottom floor should be mounted at least 6" off of the ground.
SMALL RECESS OK 60" 60"
D D D
60" E
60" E
D D D
J
6" 7_
Figure2
Any time obstructions are present use the following guidelines for proper
spacing from the VERT-I-PAK louver:
For minor obstructions such as lamp poles or small shrubbery aclearance
of 24" from the outdoor louver should be maintained.
For major obstructions such as a solid fence, wall or other heat rejecting device like a condensing unit, a mini- mum distance of 72" should be kept.
6" 3
D D D D
_A_
LARGER RECESS OK IF A> 5xB
\
D
D
60'_
D
D
BUILDING
OUTDOOR "72" UNIT
MAJOR OBSTRUCTION
FENCE
H
12"
The above suggestions are for reference only and do not represent all possible installations. Please contact the factory for information regarding affects of other installation arrangements.
By following these simple recommendations you can be confident that your Friedrich Vert-I-Pak ®will provide years
of worry-free operation.
3
920-075-07 (10-03)
Section I. GeneralSpecifications
MODEL NUMBER
SERIES
V=Vertical Series
E=Cooling with or without electric heat H=Heat Pump
DESIGN SERIES
A = 32" Cabinet
NOMINAL CAPACITY A-Series (Btu/h)
09 = 9,000 12 = 12,000 18 = 18,000
VOLTAGE
K = 208/230V-1Ph-60Hz
MODEL:
Voltage (V)
Refrigerant Chassis Width
Chassis Depth Chassis Height ** Shipping Wx D x H
Supply Duct Cellar*** Drain Connection
Min. Circuit Amps CFM Indoor
Max. Duct ESP
V A
V(E,H)A09
230 / 208
R-22
23.125"
23.125"
32.25"
25,00" x 28,50" x35.00"
10"
3/4" FPT
.3 in. water
ENGINEERING CODE
OPTIONS
RT = Standard Remote Operation SP = Seacoast Protected
ELECTRIC HEATER SIZE A-Series
00 = No electric heat 25 = 25 KW 34 = 3.4 KW 50 = 5.0 KW
V(E,H)A12
230 /208
R-22
23.125"
23.125" 32,25"
26.00" x 28.50" x 35.00" 10"
3/4" FPT
See Chassis Nameplate
See Charts 2 & 3 (Page 10)
,3in.water
V(E,H)A18
230 /208
R-22 23,125" 23,125"
32.25"
26.00" x 28.50" x 35.00"
10"
3/4" FPT
,3 in. water
NOTES:
** Height includes 2" ductcollar & isolatorsunder unit. *** Factory collar accepts 10" flex duct.
4
920-075-07(10-03)
II. Installation
1) UtilityClosetDimensions
Recommended utilityclosetdimensions anda typical indoorinstallationareillustrated inFigure 3. Three inches minimumclearance on
three sides of the unit must be allowed for return airflow, installationaccess and service access. See Figures 3 and 4 for clearances and referencedimensions.
Figure3
25"x 20" Filter
(Field Supplied)
Typical Utility Closet
VPRG4 Access Panel and
Return Air Filter Grille
See Figure 8, Page 10 for return air options
Chassis Shownin Closet, on Optional Platform
Rigid Ductwork
Electrical
Connection
Flexible Ductwork
,VPAWP1-8/1-14
Wall Plenum
Plenum Divider
Wiring
Power
Disconnect
3/4" FPT Drain Connection
Vert-I-Pak Chassis dimensions: 23 _/e"wide x 23 _/_'deep x32 V4"high.
VPAWP1-8/1-14 WallPlenumcut-out dimensions24 SlY'wide x307/j, high.
VPRG4 Access Panel cutoutdimensions: 27"wide by 553/4"high.
See Figure9 (Pg11)for properchassis installation.
Figure4
Top View f
7 tl
2 wl
Optional Platform
Chassis installs 23/e'' into Plenum
3" Clearance on all three sides
minimum for service and installation•
f
6t_
5