Hazardgard
®
Hazardous Location Room Air Conditioners
UL LISTED for CLASS 1, DIV 2, GROUPS A, B, C and D.
CERTIFIED in accordance with ISA 12.12.01 and NFPA 70
(NATIONAL ELECTRIC CODE), ANSI/UL 484 Room Air Conditioners
KSA registered model tested in accordance with SASO 2681
THE EXPERTS IN ROOM AIR CONDITIONING

®
Hazardgard
Engineered to perform in the harshest conditions.
HAZARDGARD MEETS
T4 TEMPERATURE
CLASSIFICATION
• Unit surface temperatures will
not rise above 135° C/275° F.
• Operates at low ambient
conditions without freezing at
outdoor ambient temperatures
as low as 7° C/45° F.
• Tolerates higher outdoor
temperatures up to 55° C /130° F.
For more than 30 years, industrial professionals have trusted Hazardgard to deliver safe and reliable
cooling in the most extreme conditions. Hazardgard is specically designed to cool laboratories, control
rooms, living quarters, storage areas and other enclosures situated in hazardous locations; where
specic volatile ammable liquids or gases are handled or used within enclosed containers or systems.
Hazardgard
®
is rated for these conditions:
Model Hazardous Location Classication: Gases
SH15M30A
SH20M30SA
SH20M30B
SH20M50B
SH24N30A
For global applications, Hazardgard cooling capacities are tested in a certied laboratory at moderate (T1*) and hot (T3*) climate conditions
in accordance with SASO (Saudi Arabian Standards Organization) Standard 2681. SASO Standard 2681 is adopted from ISO Standard 5151
for testing and rating for performance of non-ducted air conditioners and heat pumps. Model SH20M30SA is KSA Registered in accordance
with SASO2681 and meets SASO 2663 Energy Ef ciency standard.
ARTICLE 501: Class 1, Division 2, Group A / B / C / D , Temperature Class T4
ARTICLE 505: Class 1, Zone 2, Group II C / IIB / II A , Temperature Class T4
National Electrical Code, NFPA 70
The Friedrich Advantage Reliable Design Backed by Robust Engineering
Quality
Friedrich is an established player
in the air conditioning industry
and is known for manufacturing
quality products.
Off the shelf models allow for efcient manufacturing,
shorter lead times and standardized component parts.
Product Reliability
Used across the globe, Hazardgard
is a tested and reliable product and
not a quick-x, job shop alteration.
Availability
Durability
Robust engineering, commercial
grade components and extensive
eld testing provide the durability
and safety required in hazardous
locations.

DURABILITY & RELIABILITY
• Permanent split capacitor motor
• Hermetically sealed refrigeration system
• Environmentally sealed on/off switch and gold
plated contacts in thermostat for corrosion resistance
• Solid-state control relays for compressor and fan operation
• Commercial grade, enclosed fan motor with hermetically
sealed overload for arc-free operation
• Direct-wired (field supplied), 15-amp circuit
with time delay fuse that will tolerate current
surge without tripping the breaker
• Powder Coated 22-gauge, G60 steel air
conditioner cabinet for corrosion protection
and to withstand years of hard use
• Stainless Steel Fan Shaft
• Coated Coils for Corrosion Protection
COATED COILS FOR CORROSION RESISTANCE
PERFORMANCE IN EXTREME
CONDITIONS
• Hot gas bypass for cooling operation at
low ambient temperatures, down to 45ºF /
7ºC without freezing
• Designed to tolerate high ambient
temperatures, allowing units to operate
in T3 conditions
• ElectroFin® 5-stage, immersion ecoat process, or
Diamonblue Advanced Corrosion Protection
metallic surfaces on the outdoor coil provides outstanding
corrosion resistance protection and extends the life of the
unit, especially in coastal or corrosive environments.
Diamonblue Advanced Corrosion Protection
• STANDARD ON ALL MODELS (except SH24N30A,
see below)
• Anti-corrosive, hydrophilic coating
hours
®
5-stage, Immersion Ecoat Benefits:
ElectroFin
MODEL SH24N30A ONLY
• Excellent adhesion characteristics
• Less than 1% thermal degradation
• Outstanding chemical resistance
• Passed 6048 hrs.ASTM B-117 Salt Spray
MEETS THE FOLLOWING:
• MIL-C-46168 Chemical Agent Resistance
-DS2, HCI Gas
• CID A-A-52474A (GSA)
• MIL-STD 810F, Method 509.4 (Sand and Dust)
• MIL-P-53084 (ME)-TACOM Approval
• MIL-DTL-12468 Decontamination Agent (STB)
• DPG (Douglas Proving Grounds) Soil & Water Exposure Tests
• GM9540P-97 Accelerated Corrosion Test (120 cycles)
• ASTM B117-G85 Modified Salt Spray (Fog) Testing-2,000
• ASTM B117 Salt Spray (tested by ARL for Lockheed Martin)
®
on 100% of
®
Corrosion Protection
5-STAGE ecoat
Engineered to perform
in the harshest
environments
• Offshore oil rigs, on-shore oil
company ofces and reneries
• Petrochemical sites
• Propane ll-up stations
• Paint and varnish storage or
processing plants
• Grain alcohol processors or
storage sites
• Plant areas using strong
solvents or chemicals
• Munitions plants or armories
• PVC or plastics plants and
processing points
• Recycling plants
• Furniture renishing workshops
• Ofce complexes where
methane is a by-product
• Hazardous materials storage

SPECIFICATIONS
Model
Cooling Capacity
Electrical Characteristics
Volts
Rated
Cooling
Amps
Circuit Rating Breaker or
Cooling
T - D Fuse
Capacity (KW)Btu/Hr. Volts - Amps EER
Energy
Efciency
Ratio
Moisture
Removal
Air
Circulation
Pints/ Hr CFM
6 0 H E R T Z
SH15M30 A 15700/15700 230/208 7.9/ 7.8 4.60/4.10 250V-15 9.7/9.7 4.0 375 R-410A
SH20M30B 21000/21000 230/208 10.5/9.4 6.15/6.15 250V-15
SH20M30SA 19000/19000 220 8.5 5.57 250 V-20
(230V) / 250V-20 (208V)
(230V) / 250V-20 (208V)
9.7/9.6 5.5 375 R- 410A
9.7/9.6 5.5 375 R- 410A
SH24N30A 23500/23000 230 11.8 6.8 250V-20 9.7/8 .5 8.0/ 7.5 385 R-410A
50 HERTZ
SH20M50B 21000/19100 240/220 11.6/10.3 6.15 /6.15 250V-15 8.8/8.8 7.0/7. 0 425 R -410A
INSTALLATION INFORMATION
Model
SH15M30 A 15
SH20M30B 17
SH20M30SA 17
SH20M50B 17
SH24N30A 17
Height Width
15
15
15
15
15
/
16” 25
/
16” 25
/
16” 25
/
16” 25
/
16” 25
15
15
15
15
15
Depth with
/
16” 27
/
16” 27
/
16” 27
/
16” 27
/
16” 27
Dimensions
Inches
Depth J Box
Front
to Louvers
(A)
3
/
8” 6” 3
3
/
8” 6” 3
3
/
8” 6” 3
3
/
8” 6” 3
3
/
8” 6” 3
Minimum
Extension
Into Room
1
/
16” 16
1
/
16” 16
1
/
16” 16
1
/
16” 16
1
/
16” 16
Window Width
Inches
Minimum
Extension
Outside Min. Max. Height Width Max. Depth Net Shipping
15
/
16” 27
15
/
16” 27
15
/
16” 27
15
/
16” 27
15
/
16” 27
7
/
8” 42” 16
7
/
8” 42” 18
7
/
8” 42” 18
7
/
8” 42” 18
7
/
8” 42” 18
In-Wall Installation
Finished Hole Inches
3
/
16” 26
3
/
16” 26
3
/
16” 26
3
/
16” 26
3
/
16” 26
3
/
16” 6” 140 167
3
/
16” 6” 166 170
3
/
16” 6” 166 170
3
/
16” 6” 171 175
3
/
16” 6” 180 185
Refrigerant
Weight
Lbs.
Due to continuing engineering research and technology, specications are subject to change without notice.
U.S. MAXIMUM outdoor ambient operating temperature is 115ºF. (46ºC) MAXIMUM TEMPERATURE RATING FOR CL ASS 1, DIVISION 2,
GROUPS A, B, C, D.
Capacity and efciency values at each climate conditions are available upon request.
NOTE: Hazardgard unit must be hard-wired.
Manufactured under Design Patent DES 368, 306 decorative front; Utility Patent 5, 662, 058.
• Sleeve Dimensions Drawing
(A)
Max.
Wall
Depth
Junction
Box
Front
SIDE VIEW
Friedrich Air Conditioning Co. l 10001 Reunion Place, Suite 500 l San Antonio, TX 78216 l 877.599.5665 l www.friedrich.com
BR_HAZ_1-23-20 Printed in USA