DISCHARGETEMPSUCTIONDISCHARGEAMPSLOCKEDCHARGE INCHARGE IN
AIRDROP °FROTOR AMPSOUNCESFLUID OZ.
SH14J30B-A
SH14J30B-A
SH20J30B-A
SH20J30B-A
* Rating Conditions: 80° F. Room Air Temperature and 59% Relative Humidity with 95° F. Outside Air Temperature at 40% Relative Humidity.
56.7823.22792967.8432832
8.5
52.8327.1679.52829.8523932
10.4
3
COMPONENT OPERATION AND TESTING
WARNING
COMPRESSOR WINDING TEST
(See Figure 2.)
DISCONNECT ELECTRICAL POWER TO
THE UNIT BEFORE SERVICING OR
TESTING
COMPRESSORS
Compressors are single phase, 208/230 volt. All
compressor motors are permanent split capacitor
type, using only a running capacitor across the
start and run terminal.
All compressors are internally spring mounted and
externally mounted on rubber isolators.
Line Voltage Overload
The compressor is equipped with an internal line
voltage overload. This overload is embedded in
the windings of the motor to sense the motor
temperature. The overload will open and
disconnect the power to the motor due to high
temperatures caused by:
Remove the compressor terminal box cover and
disconnect the wires from the terminals. Using
an ohmmeter, check continuity across the
following:
FIGURE 2 COMPRESSOR WINDING TEST
Testing Procedures
1.Terminal "C" and "S" - no continuity open winding - replace compressor.
2.Terminal "C" and "R" - no continuity open winding - replace compressor.
1.A locked rotor.
2.Excessive running amps.
3.High discharge temperature.
4.Low refrigerant charge.
FIGURE 1 INTERNAL OVERLOAD
LINE BREAK
INTERNAL OVERLOAD
OHMMETER
4
3.Terminal "R" and "S" - no continuity
open winding - replace compressor.
4.Terminal "C" and the shell of the
compressor – continuity – grounded
motor – replace compressor.
5. Should continuity exist between
terminals "R" and "S", but not between
terminals "C" and "S" and "C" and "R",
the internal overload may be open. If
the compressor is extremely hot, allow
it sufficient time to cool. It may require
as long as one hour for the compressor
to cool sufficiently for the internal
overload to close.
GROUND TEST
FAN MOTOR (Figure 4)
Use an ohmmeter set on its highest scale. Touch
one lead to the compressor body (clean point of
contact, as a good connection is a must) and the
other probe in turn to each compressor terminal.
(See Figure 3.) If a reading is obtained, the
compressor is grounded and must be replaced.
FIGURE 3 TYPICAL GROUND TEST
CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefficiency is
normally due to broken or damaged suction
and/or discharge valves, reducing the ability of
the compressor to pump refrigerant gas.
This condition can be checked as
follows:
1. Install a piercing valve on the suction and
discharge or liquid process tube.
A 230 volt single phase permanent split capacitor
motor is used to drive the evaporator blower and
condenser fan. A running capacitor is wired
across the start and run terminals of the motor.
The motor is totally enclosed and is protected with
a line voltage overload located internally of the
motor. The motor shaft is stainless steel to resist
corrosion.
FIGURE 4 FAN MOTOR
FAN MOTOR – TEST
Disconnect power to the unit.
1. Determine that the capacitor is serviceable.
2. Disconnect the black lead from the circuit
board.
3. Apply "live" test cord leads to the common
terminal of the capacitor and the black lead.
The motor should run at high speed.
2. Attach gages to the high and low sides of the
system.
3. Start the system and run a "cooling or
heating performance test."
If test shows:
A. Below normal high side pressure.
B. Above normal low side pressure.
C. Low temperature difference across the coil.
The compressor valves are faulty replace the compressor.
5
SYSTEM CONTROL SWITCH
(Figure 5)
This switch is double pole, single throw. Check
for continuity between terminals 2 and 3, and 5
and 6.
CAPACITOR – TEST
1. Remove the capacitor from the unit.
2. Check for visual damage such as bulges,
cracks, or leaks.
FIGURE 5 SWITCH, ON-OFF
CAPACITOR, RUN
A run capacitor is wired across the auxiliary and
main winding of a single phase permanent split
capacitor motor such as the compressor and fan
motors. A single capacitor can be used for each
motor or a dual rated capacitor can be used for
both.
The capacitor’s primary function is to reduce the
line current while greatly improving the torque
characteristics of a motor. The capacitor also
reduces the line current to the motor by improving
the power factor of the load. The line side of the
capacitor is marked with a red dot and is wired to
the line side of the circuit. (See Figure 6.)
FIGURE 6 RUN CAPACITOR HOOK–UP
COMPRESSOR
FA N
MOTOR
3. For dual rated capacitors, apply an ohmmeter
lead to the common (C) terminal and the other
probe to the compressor (HERM) terminal.
A satisfactory capacitor will cause a deflection
on the pointer, then gradually move back to
infinity.
4. Reverse the leads of the probe and
momentarily touch the capacitor terminals.
The deflection of the pointer should be two
times that of the first check if the capacitor is
good.
5. Repeat steps 3 and 4 to check the fan motor
capacitor.
NOTE: A shorted capacitor will indicate a low
resistance and the pointer will move more
to the “0” end of the scale and remain there
as long as the probes are connected. An
open capacitor will show no movement of
the pointer when placed across the terminals
of the capacitor.
THERMOSTAT
A cross ambient
thermostat is used
to maintain the desired
comfort level. The
thermostat reacts only to
a change in temperature
at the bulb location.
Important to the
successful operation
of the unit is the position
of the sensing bulb in
relation to the evaporator.
FIGURE 7
SENSING BULB
LOCATION
See Figure 7.
RED DOT
Thermostat
(Part No. 618-225-02)
RANGE:
RUN CAPACITOR
6
60° F ( ± 2° ) to 90° F( ± 4° )
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.