Post Ofce Box 1540 · San Antonio, Texas 78295-1540
4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212
(210) 357-4400 · FAX (210) 357-4490
www.friedrich.com
Printed in the U.S.A.
Table Of Contents
Important Safety Information ........................................................................................................................................ 2-4
Unit Identication ............................................................................................................................................................. 6
Chassis Specications for 2009, 2008 Models ............................................................................................................... 7
Performance Data ........................................................................................................................................................... 9
Electrical Data ............................................................................................................................................................... 10
Before Operating the Unit .............................................................................................................................................. 11
How to Operate the QM Programmable ........................................................................................................................ 12
How to Use the QM Programmable Remote Control ..................................................................................................... 13
How to Operate the XQ .................................................................................................................................................. 14
How to Use the XQ Remote Control .............................................................................................................................. 15
How to Operate the QM and Twintemp .................................................................................................................... 16-17
Testing the Electronic Control and Error Code Listings .............................................................................................17-18
Testing the Rotary Control Switches ..........................................................................................................................19-20
Electronic Control Sequence of Operation ..................................................................................................................... 25
Refrigeration Sequence of Operation ............................................................................................................................. 26
Sealed Refrigeration System Repairs ....................................................................................................................... 27-30
Testing the Coil .............................................................................................................................................................. 33
Checking the Reversing Valve .................................................................................................................................. 33-34
Instructions for using Cooling Load Estimate Form ........................................................................................................ 58
Cooling Load Estimate Form .......................................................................................................................................... 60
Heat Load Form ......................................................................................................................................................... 61-62
The information contained in this manual is intended for use by a qualied service technician who is familiar
with the safety procedures required for installation and repair, and who is equipped with the proper tools and
test instruments required to service this product.
Installation or repairs made by unqualied persons can result in subjecting the unqualied person making
such repairs as well as the persons being served by the equipment to hazards resulting in injury or electrical
shock which can be serious or even fatal.
Safety warnings have been placed throughout this manual to alert you to potential hazards that may be
encountered. If you install or perform service on equipment, it is your responsibility to read and obey these
warnings to guard against any bodily injury or property damage which may result to you or others.
We have provided many important safety messages in this manual and on your appliance. Always read
and obey all safety messages.
WARNING
CAUTION
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury,
and tell you what will happen if the instructions are not followed.
NOTICE
Your safety and the safety of others are very important.
This is a Safety Alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol with the word “WARNING”
or “CAUTION”. These words mean:
You can be killed or seriously injured if you do not follow instructions.
You can receive minor or moderate injury if you do not follow instructions.
A message to alert you of potential property damage will have the
word “NOTICE”. Potential property damage can occur if instructions
are not followed.
PERSONAL INJURY OR DEATH HAZARDS
ELECTRICAL HAZARDS:
Unplug and/or disconnect all electrical power to the unit before performing inspections, •
maintenance, or service.
Make sure to follow proper lockout/tag out procedures.•
Always work in the company of a qualied assistant if possible. •
Capacitors, even when disconnected from the electrical power source, retain an electrical charge •
potential capable of causing electric shock or electrocution.
Handle, discharge, and test capacitors according to safe, established, standards, and approved •
procedures.
Extreme care, proper judgment, and safety procedures must be exercised if it becomes necessary •
to test or troubleshoot equipment with the power on to the unit.
2
Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel, •
and sleeve on the room side of the air conditioning unit while cleaning.
Electrical component malfunction caused by water could result in electric shock or other electrically •
unsafe conditions when the power is restored and the unit is turned on, even after the exterior is dry.
Never operate the A/C unit with wet hands.•
Use air conditioner on a single dedicated circuit within the specied amperage rating. •
Use on a properly grounded outlet only.•
Do not remove ground prong of plug.•
Do not cut or modify the power supply cord.•
Do not use extension cords with the unit.•
Follow all safety precautions and use proper and adequate protective safety aids such as: gloves, •
goggles, clothing, adequately insulated tools, and testing equipment etc.
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death. •
REFRIGERATION SYSTEM HAZARDS:
Use approved standard refrigerant recovering procedures and equipment to relieve pressure before •
opening system for repair.
Do not allow liquid refrigerant to contact skin. Direct contact with liquid refrigerant can result in minor •
to moderate injury.
Be extremely careful when using an oxy-acetylene torch. Direct contact with the torch’s ame or hot •
surfaces can cause serious burns.
Make sure to protect personal and surrounding property with re proof materials.•
Have a re extinguisher at hand while using a torch.•
Provide adequate ventilation to vent off toxic fumes, and work with a qualied assistant whenever •
possible.
Always use a pressure regulator when using dry nitrogen to test the sealed refrigeration system for •
leaks, ushing etc.
Make sure to follow all safety precautions and to use proper protective safety aids such as: gloves, •
safety glasses, clothing etc.
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death. •
MECHANICAL HAZARDS:
Extreme care, proper judgment and all safety procedures must be followed when testing, •
troubleshooting, handling, or working around unit with moving and/or rotating parts.
Be careful when, handling and working around exposed edges and corners of sleeve, chassis, and •
other unit components especially the sharp ns of the indoor and outdoor coils.
Use proper and adequate protective aids such as: gloves, clothing, safety glasses etc.•
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.•
3
PROPERTY DAMAGE HAZARDS
FIRE DAMAGE HAZARDS:
Read the Installation/Operation Manual for this air conditioning unit prior to operating.•
Use air conditioner on a single dedicated circuit within the specied amperage rating. •
Connect to a properly grounded outlet only.•
Do not remove ground prong of plug.•
Do not cut or modify the power supply cord.•
Do not use extension cords with the unit.•
Failure to follow these instructions can result in re and minor to serious property damage.•
WATER DAMAGE HAZARDS:
Improper installation maintenance, or servicing of the air conditioner unit, or not following the above •
Safety Warnings can result in water damage to personal items or property.
Insure that the unit has a sufcient pitch to the outside to allow water to drain from the unit. •
Do not drill holes in the bottom of the drain pan or the underside of the unit. •
Failure to follow these instructions can result in result in damage to the unit and/or minor to serious •
property damage.
4
INTRODUCTION
This service manual is designed to be used in conjunction with the installation manuals provided with each air conditioning
system component.
This service manual was written to assist the professional RAC service technician to quickly and accurately diagnose
and repair malfunctions.
This manual will deal with subjects in a general nature. (i.e. all text will not pertain to all models).
TYPICAL UNIT COMPONENTS
Fresh Air
Capillary Tube
Reversing Valve
(some models)
Front Cover
System Switches
Evaporator Coil
Return Air Grille/Filter
Blower Wheel
Blower Motor
IMPORTANT: It will be necessary for you to accurately identify the unit you are servicing, so you can be certain of a
proper diagnosis and repair (See Unit Identication on page 6).
Compressor
Liquid Filter Driers
Condenser Coil
Discharge Air
Outdoor Grille
Sleeve
Condenser Fan Blade
Basepan
5
UNIT IDENTIFICATION
1st Digit – Function
S = Straight Cool, Value Series
Y = Heat Pump
E = Electric Heat
K = Straight Cool
R = Straight Cool
X = Straight Cool
The consumer- through the AHAM Room Air Conditioner Certification Program- can be certain that the AHAM Certification Seal accurately
states the unit’s cooling and heating capacity rating, the amperes and the energy efficiency ratio.
As an ENERGY STAR
®
partner, Friedrich Air Conditioning Co. has determined that the selected ENERGY STAR
®
( ) models meet the ENERGY STAR
®
guidelines for energy efficiency.
* Sleeve dimensions listed on opposite page.
** Operates on 115 volt and is not equipped with supplemental heat. Will not provide heat at temperatures below 40°F.
Friedrich room air conditioners are designed to operate in outdoor temperatures from 50°
F to 115° F.
TwinTemp Heat Pump heating information
(shown inred) indicates heat pump heating per formance. TwinTemp Electric Heat heating information (shown in red) indicates electric heat strip performance.
For TwinTemp Heat Pump electric heating performance refer to corresponding TwinTemp Electric Heat model.
Due to continuing research in new energy-saving technology, specifications are subject to change without notice.
* Minimum extensions when mounted in a window.
** Minimum widths achieved using one side curtain assembly as opposed to both in a standard installation.
† Sleeve P1 does not have thru-the-wall hole dimensions, as these units are fixed chassis and should not be installed thru-the-wall.
NOTE: S,M and L sleeves may be installed in window with no side kits if properly installed.
Discharge Temp Suction Temp Super Heat Sub-Cooling
12377028717.291.057.6208 / 23030
OPERATING PRESSURESELECTRICAL RATINGSR-22 REF.
SuctionDischargeAmps Cool Amps Heat
7.935.032.1208 / 23015
Locked Rotor
Amps
Charge in
OZ.
BREAKER FUSE
Voltage
60 Hertz Amps
*Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity, all systems use R22.
9
ELECTRICAL DATA
Not following the above WARNING could result in re or
electically unsafe conditions which could cause moderate
or serious property damage.
Read, understand and follow the above warning.
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or
installation.
All electrical connections and wiring MUST be
installed by a qualied electrician and conform to
the National Electrical Code and all local codes
which have jurisdiction.
Failure to do so can result in personal injury or
death.
NOTICE
FIRE HAZARD
Wire Size Use ONLY wiring size recommended for single outlet branch circuit.
Fuse/Circuit Breaker Use ONLY the correct HACR type and size fuse/circuit breaker. Read electrical ratings on unit’s
rating plate. Proper circuit protection is the responsibiity of the homeowner.
Grounding Unit MUST be grounded from branch circuit through service cord to unit, or through separate
ground wire provided on permanently connected units. Be sure that branch circuit or general
purpose outlet is grounded.
Receptacle The eld supplied outlet must match plug on service cord and be within reach of service cord.
Do NOT alter the service cord or plug. Do NOT use an extension cord. Refer to the table above
for proper receptacle and fuse type.
The consumer - through the AHAM Room Air Conditioner Certication Program - can
be certain that the AHAM Certication Seal accurately states the unit’s cooling and
heating capacity rating, the amperes and the energy efciency ratio.
*HACR: Heating Air Conditioning and Refrigeration
10
Keep the filter clean
Make sure that your air conditioner is always in top performing condition
.ylralugerretlifehtgninaelcyb
Provide good air flow
Make sure the airflow to and from the unit is clear. Your air conditioner puts the
conditioned air out at the top of the unit, and takes in unconditioned air at the
bottom. Airflow is critical to good operation. It is just as important on the outside
blinds on the sunny side of the dwelling will also add to your unit’s efficiency.
Insulation
Good insulation will be a big help in maintaining desirable comfort levels.
Doors should have weather stripping. Be sure to caulk around doors and
windows.
Proper installation of seal gasket
Make sure the seal gasket has been installed properly to minimize noise
and improve effi ciency. If the seal gasket has not been installed, please
refer to Step 14 of the
installation instructions.
Also, if you switch from Cool mode to Fan Only, and switch back to
COOL mode, there is a three minute delay before the compressor comes
back on.
For the best cooling performance and highest energy efficiency
WARNING: Before operating your unit
Make sure the wiring is adequate for your unit.
If you have fuses, they should be of the time delay type. Before you install
or time delay fuse does not exceed the amp rating listed in Figure 1.
DO NOT use an extension cord.
The cord provided will carry the proper amount of electrical power to the
.tonlliwdrocnois netxena;tinu
Make sure that the receptacle is compatible with
the air conditioner cord plug provided.
This insures proper grounding. If you have a two prong receptacle you
will need to have it replaced with a grounded receptacle by a certifi ed
electrician. The grounded receptacle should meet all national and local
codes and ordinances. Under no circumstances should you remove the
ground prong from the plug. You must use the three prong plug furnished
with the air conditioner.
Test the power cord
All Friedrich room air conditioners are shipped from the factory with a
Leakage Current Detection Interrupter (LCDI) equipped power cord. The
LCDI device meets the UL and NEC requirements for cord connected air
conditioners.
To test your power supply cord:
1. Plug power supply cord into a grounded 3 prong outlet.
2. Press RESET (See Figure 2).
3. Press TEST (listen for click; Reset button trips and pops out).
4. Press and release RESET (listen for click; Reset button latches and
remains in). The power supply cord is ready for operation.
NOTE: LCDI d
evice is not intended to be used as a switch.
Once plugged in the unit will operate normally without the need to reset
the LCDI device.
If the device fails to trip when tested or if the power supply cord is
damaged it must be replaced with a new supply cord from the manufacturer. We recommend you contact our Technical Assistance Line at
(800) 541-6645 ext. 845. To expedite service, please have your model
and serial number available.
MODEL
CIRCUIT RATING
OR TIME DELAY
FUSE
REQUIRED WALL
RECEPTACLE
AMPVOLT
NEMA
NO.
SS08 • SS10 • SS12 • SS14
XQ06 • XQ08 • XQ10 • XQ12
EQ08
KS12 • KS15 • YS09 • XQ05
151255-15R
SS12 • SS16 • SM18
SM21 • KM18
152506 -15R
SM24 • SL28 • KM24
YS13 • ES12 • ES16
202506-20R
SL36 • YM18 • YL24
EM18 • EM24 • EL36
302506-30R
Figure 1
Figure 2
TEST
RESET
WARNING
TEST BEFORE EACH USE
1. PRESS RESET BUTTON
2. PLUG LDCI INTO POWER
RECEPTACLE
3. PRESS TEST BUTTON,
RESET BUTTON SHOULD
POP UP
4. PRESS TEST BUTTON,
FOR USE
DO NOT USE IF ABOVE TEST
FAILS
WHEN GREEN LIGHT IS ON
IT IS WORKING PROPERLY
RESET
TEST
NOTE: Your LCDI device will resemble one of these illustrations.
WARNING
ELECTRICAL SHOCK HAZARD
Make sure your electrical receptacle has the same
configuration as your air conditioner’s plug. If
different, consult a Licensed Electrician.
Do not use plug adapters.
Do not use an extension cord.
Do not remove ground prong.
Always plug into a grounded 3 prong outlet.
Failure to follow these instructions can result in
electrical shock, serious injury or death.
11
A/C
Stop
Mode
Temp
Fan
Timer
O
F
/
O
C
A/C
Start
Timer
On/O
1-4
Speed
Smart
Fan
Check
Filter
Set
Hour
Power
Cool
Money
Saver
®
PM
Fan
Only
Press to reset
13
DISPLAY
8
5
4
2
15
10
7
11
9
6
3
1
14
12
Figure 3
To start unit
1
If your air conditioner is installed and plugged intoaproper re-
hcuoT.ogotydaersiti,elc at pec Power button once. The unit will
automatically be in Cool mode with the temperature set at 75°F
(24°C) and the fan speed at F1, the sleep setting. There is a 3minute delay before the compressor will turn on. (See "Automatic
Component Protection" on this page).
2
Should the Check Filter light turn on when you rst turn on the unit,
touch Check Filter to turn off the light. Check Filter light will come
Clean filter..esufosruoh052ret fano
Touch Check Filter to reset.
To set mode of operation
3
When you rst turn on the unit, it will be in the Cool mode (light on),
with constant fan.
4
Touch MoneySaver®(light on) toactivate the MoneySaver®feature.
This cycles the fan with the compressor so that the fan does not
.noit ac
i dim uh edsevorpmidnaygrenesevassihT.emitehtllanur
(MoneySaver
®
will also run the fan to sample the return airtempera-
ture if the off cycle is too long). Or you may prefer constant fan for
more air movement. To return to constant fan, touch Cool.
5
TouchFan Only (light on) if you wantonly the fan to run. Youmay want
to use thisfeature in conjunctionwith the Fresh Air / Exhaust lever to
bring outside air intoaroom, or to exhauststale air. (See page 7, "Fresh
Air and ExhaustControl"for more information.)
To adjust temperature [60°F (16°C) to 90°F (32°C)]
6
COOLER – Touchand hold untilthe display shows thedesired
room temperature.
7
WARMER– Touchand holduntil the display showsthe desired
room temperature.
8
FAHRENHEIT / CELSIUS – Touch ºF/ºC toshow thetemperature
in Celsius, touch again to show Fahrenheit.
To adjust fan speed
9
Touch 1-4 Speed to see current setting. Touch again to change
(LOW), F3 is medium speed (MED), F4 is high speed (HIGH).
To activate smart fan
10
Touch Smart Fan (light on). Smart Fan will adjust the fan speed
,elpmaxeroF.leveltrofmocderisedehtniatniamotyl lac i tam ot ua
do ir epdednetxenarofnepoeraemohruoynisroodedistuoehtfi
of time, or more people enteraroom, Smart Fan may adjust to a
higher fan speed to compensate for the increased heat load. This
keeps you from having to adjust the fan speed on your own. Smart
Fan cannot be activated in the Fan Only mode.
To deactivate smart fan
11
Touch 1-4 Speed, and select your desired fan speed.
To set hour clock
12
Press Set Hour once to see the current clock setting. Continue
pressing the button until the hour closest to the actual time appears
in the display.
MAKE SURE YOU SET A.M. AND P.M. PROPERLY.Alight will appear in
the upper left corner of the display when the hour is P.M.
You can set the A/C Start and A/C Stopruohenofomum i nimaremit
apa
rt and a maximum of 23 hours apart.
13
TIMER STOP - Press the A/C Stop button and continue pressing
until the hour you want the unit to shut off appears in the display
(A.M. or P.M.). The stop time for cooling will then be set.
14
START TIME - Press A/C Start to view the current start time for
cooling. Continue pressing until the hour you want the unit to start
appears in the display (A.M. or P.M.). The start time for cooling will
then be set.
15
Press the Timer On/ Off button once to activate (light on) the timer
functio
n. Touch Timer On/ Off again (light off) to cancel the timer
-esneebevahsemitffodnanoehtecnO.er
is edosuoyfinoitcnuf
lected, they will remain in memory, and cycle daily until changed.
NOTE:eht,de tpur ret nisirewoprodeggulpnusitinufISet Hour button
ehtrotes erebtsumTimer On/ Off functions will not work.
Automatic component protection
.noitcetorPtnen op moCcitamotuAhtiwdeppiuqesitinuruoY
Toprotect thecompressor ofthe unit,there isathree minutetime delay if you
turn the unit off or if power is interrupted. The fan will not be affected.
How to operate the Friedrich room air conditioner
(QuietMaster Programmable)
12
*
A Friedrich RC1 wireless remote control can be used to operate all
QuietMaster
®
Programmable models.
Figure 4
To start unit
1
POWER - Press the Power button once. The unit will automatically
turn on in the mode and fan speed it was last left on.
To set mode of operation
2
COOL - Press the Cool button toautomatically switch the operating
mode to COOL.
3
FANONLY - Press the Fan Only button ifyou want to run the fan only.
You may want to use this feature in conjunction with the Fresh Air/Exhaust if you want to bring outside air into the room, or exhaust stale
air.
4
MoneySaver®- Press the MoneySaver®button to activate the
MoneySaver
®
feature. This cycles the fan with the compressor so
that the fan does not run all the time.
To adjust temperature
5
COOLER - Press theCooler button to raise the temperature
setting.
6
WARMER - Press theWarmer button to lower the temperature
setting.
To adjust fan speed
7
FAN SPEED - Press the Fan Speed button to see the current set-
ting. Press again to change the fan speed. F1 is the lowest setting
(SLEEP SETTING), F2 is low speed (LOW), F3 is medium (MED),
and F4 is high (HIGH).
To set the hour clock
8
SET HOUR CLOCK- Press SetHour once to see the currentclock set-
ting. Continue pressing the button until you arrive at the current time.
MAKE SURE YOU SET THE A.M. AND P.M. PROPERLY. (NOTE:
MINUTESARE NOT SHOWN ON THEDI
SPLAY.)Alight will appear in
the upper leftcorner ofthe display when the hour is P.M.
How to use the remote control
*
(QuietMaster Programmable)
To set the timer
NOTE: Set the hour clock before attempting to set timer functions. You
can set the timer On/Off a minimum of one hour apart, and a maximum
of 23 hours apart.
9
TIMER START - Press Start to view the current start time for cool-
ing. Continue pressing the Start button until you arrive at the start
time you desire. The start time for cooling will then be set.
10
TIMER STOP - Press the Stop button. Continue pressing the Stop
button until you arrive at the stop time you desire. The stop time for
cooling will then be set.
11
TIMER ON/OFF - Press the On/off button once toactivate (light on)
or deactivate (light off) the timer. Once the Start and Stop times
have beenselected, they will remain in memory, and cycle dailyuntil
changed.
NOTE: If theunit isunplugged orthe poweris interrupted,the HOUR
CLOCK must be reset or the Tim
er On/off functions will not work.
Money
Fan
Timer Operation
Set Hr.
Stop
Start
Temperature
Fan
Cool
On/O
Power
Cooler
OnlySpeed Saver
®
Warmer
8
10
7
11
9
43
1
2
56
13
To startunit
siti,elc at pec erreporpaotnideggulpdnadellatsnisirenoitidnocriaruoyfI
ready togo.The first timethe unitis started, thecompressorwilldelay for three
minutes.See AutomaticComponentProtectiononthe followingpage.
1
Touchthe Power button once.The unitwill automaticallybein Cool
mode with the temperature setat75°F (24°C) andthe fanspeed at
F1, thesleep setting.
To setmodeofoperation
When you rstturnthe uniton, it will be in the Cool mode (lighton),with
constant fan.
2
Touchthe Mode button once to activatethe MoneySaver®(lighton).
MoneySaver
®
ros serp mocehthtiwnafehtselcyctahterutaefasi
so that thefan does notrun allthe time.Thissaves energy and
eromrofnaftnats nocreferpyamuoyrO.noit ac
i dim uh edsevorpmi
ehthcuot,naftnatsnocotnruterot(tnem evomriaMode button two
The FANONLY settingwillcirculate air in the roomwithout thecom-
pressorcomingon.
To adjusttemperature
4
Usethe Mode button to select eitherthe COOL or MoneySaver
®
function
5
COOLER – Touch thebutton to lower theroomair temperature.
6
WARMER – Touch thebutton to raisethe roomair temperature.
7
Pressboth theandehthctiwsotemitemasehttasnottub
temperature readoutfrom Fahrenheit(°F)toCelsius(°C).
Repeat step 7 to switch from °C back to °F.
To adjust fan speed
8
TouchtheFanSpeedbutton to seethe currentsetting. To uchit again
to changespeed. F1isthe lowest setting(SLEEPSETTING/LOW),
F2 is MEDIUM,and F3 is HIGH.
To activate Smart Fan
9
Thereisafourth option,SF, when selectingthe fanspeed.Thisis
the SMARTFAN function.SMART FA NDOESNOT OPERAT EIN
CONJUCTION WITH THEFAN ONLY MODE.
SmartFan will adjustthe fanspeed automaticallyto maintain the
desiredcomfort level. Forexample,ifthe outsidedoors in your home
are opened foranextended period of time,ormorepeople entera
room,Smart Fanmay adjusttoahigherfan speedtocompensate
forthe increasedheatload. This keepsyou from having to adjustthe
fanspeed on your own.
Howtooperate the Friedrich room airconditioner (XQmodels)
PM
Temp/Hour
Cool
Money Saver
®
Fan Only
Clock
Start Time
Stop Time
Power
Fan
Speed
Mode
Timer
Set
Hour
10 11 12
13
7
3 4
5
6
18 92
Figure 5
To setthe hour clock
10
Touchthe SetHour button to seethe currentsetting (clock light
comeson).The numberthatis displayed is the approximatetime
(hour only).Use the
and
buttonstochange thesettings.BE
SURETO SETA.M.AND P. M. ACCORDINGLY. (P.M.isindicated
by ared lightinthe upperleftcornerofthe display).
To setthe timer
NOTE: Setthe HOUR CLOCK before attempting to settimer functions.
Youcan setthe ST ART and STOP timesaminimumofone hour apart,and
amaximumoftwenty-three hours apart.
11
Aftersetting thetime, press the Set Hour button once (Start light
comeson).Use the
andbuttonsto selectthe time that the
unit will START.
12
After selectingthe START time,press the SetHour button oncemore
(Stoplight comeson).Use the
andbuttonsto select the time
that the unitwill STOP.After selecting the stoppingtime, presstheSet Hour button once.
13
Pressthe TimerOn/Off button (light turnson) to activate thetimer
function. To deactivate this function, press the TimerOn/Of f button
once again (lightturns off).Oncethe on andoff timeshavebeen
selected,theywillremaininmemory and cycle dailyuntil changed.
NOTE: If the unitisunplugged or thepower is interrupted,the HOUR
mustbereset or the TimerOn/Off will notfunctionwhendesired.
Automatic componentprotection
Your unit is equipped with Automatic Component Protection. To protectthe
compressorofthe unit, thereisathree minutestart delayifyou turn theunit
offorifpoweris interrupted.The fanoperation will notbeaffected. Also,ifyou
switch from Cool mode to Fan Only,and switch back to Cool mode,there
is athree minute delaybeforethe compressor comesbackon.
14
To set the timer
NOTE: You can set the START and STOP timesaminimum of one hour
apart, andamaximum of 23 hours apart.
Continue pressing the Start button until you arrive at the start time
you desire. The start time for cooling will then be set.
10
TIMER STOP - Press the Stop button. Continue pressing the Stop
button until you arrive at the stop time you desire. The stop time for
cooling will then be set.
11
TIMER ON / OFF - Press the On/Off button to activate (light on) or
deactivate (light off) the timer. Once the on and off times have been
selected, they will remain in memory and cycle daily until changed.
NOTE: If the unit is unplugged or the power is interrupted, the Set Hr.
function must be reset or the On/Off function will not work.
How to use the remote control
To start unit
1
POWER - Press the Power button once. The unit will automatically
start in the mode and fan speed it was last left on.
To set mode of operation
2
COOL - Press the Cool button to automatically switch the operating
mode to COOL.
3
FAN ONLY - Press the Fan Only button if you want to run the fan
only.
4
MoneySaver®- Press the MoneySaver®button to activate the
MoneySaver
®
feature. This feature cycles the fan with the compres-
sor so that the fan does not run all the time.
To adjust temperature setting
5
WARMER - Press theWarmer button to raise the temperature
setting.
6
COOLER - Press theCooler button to lower the temperature
setting.
To adjust fan speed
7
FAN SPEED - Press the Fan Speed button to see the current set-
ting. Press again to change the fan speed. F1 is the lowest setting
(SLEEP / LOW), F2 is MEDIUM, F3 is HIGH, and SF is the SMARTFAN setting.
To set the hour clock
8
SET HOUR CLOCK - Press Set Hr. once to see the current clock
setting. Continue pressing the button until you arrive at the current
time (Hour only). Minutes are not shown on the display. Make sure
that the A.M. / P.M. setting is correct.
Money
Fan
Timer Operation
Set Hr.
Stop
Start
Temperature
Fan
Cool
On/O
Power
Cooler
OnlySpeed Saver
®
Warmer
8
10
7
11
9
43
12
56
Figure 6
Additional RC1 wireless remote controls can be purchased from your Friedrich dealer.
(XQ models)
15
Allow3min. between restarts
SPEED
Sleep
Setting
Low
Cool
Medium
Cool
High
Cool
Fan
Only
O
MINMAX
Money Saver
®
YesNo
Allow 3 min. between restarts
Money Saver
®
MAX
COOL
MAX
HEAT
Low
Cool
Med
Cool
High
Cool
Low
Heat
Med
Heat
High
Heat
Fan
Only
O
YesNo
To start unit
If your air conditioner is installed and plugged into a properly grounded
.eta repootydaersiti,elc atpec er
Mode control (QuietMaster)
The upper dial (Figure 7) allows you to select cooling at four different
speeds, as well as Fan Only (Models SL28 and SL36 only have three
cooling speeds.).
Off - to turn the unit off.
High Cool - for quick cooling.
Medium Cool.erutarepmetderis edaniatniamot-
Low Cool - when cooling demand is low.
Sleep Setting - for nighttime use, or when cooling demand is low.
Fan Only - to circulate air in the room without the compressor coming on.
The Fan Only setting can also be used with the Exhaustevomerotgnittesria
stale air or smoke from the room; or it can be used with the Fresh Air setting
to bring outside air into the room. This is especially useful in the spring and fall
How to operate the Friedrich room air con di tion er
(QuietMaster / Twintemp models)
Figure 7
Figure 8
16
EQ08 models
Function Control
The left knob is a six position control that allows you to
select heat or cool in either low speed or high speed. Plus
you can select fan only if you wish.
High
Heat
Fan
Only
MAX
HEAT
Function Control
The right hand knob is the thermostat - turn it clockwise for
cooler, counter-clockwise for warmer (See Figure 9).
PM
Power
Set
Cool
Money Saver
Fan Only
Clock
Start Time
Stop Time
®
Te mp/Hour
Fan
Speed
Timer
Mode
Hour
FIGURE 10
TESTING THE ELECTRONIC CONTROL
BOARDS FOR QME & XQ MODELS
Checking Room Temperature:
1. Check the room temperature at the electronic control
pad by pressing the “FAN SPEED” button and the
temperature “UP” button at the same time on XQ models.
Low
Heat
Allow3 m in. between restar ts
!
FIGURE 9
Mode
Temp
Fan
Timer
High
Cool
Low
Cool
PM
MAX
COOL
Set
Hour
Check
Filter
Press to reset
Power
Cool
1- 4
Speed
A/C
Stop
Money
Saver
Smart
Fan
A/C
Start
Fan
®
Only
O
O
F
C
/
Timer
2. Check the room temperature at the electronic control
pad by pressing at the same time the “FAN SPEED”
button and the “TEMP ” button on QME models.
The indoor temperature will display for 10 seconds. Indoor
temperature can be viewed in all modes, including the
TEST mode. The display can be changed back to SET
temperature by pressing any key, except the ON/OFF
button, or after 10 seconds has elapsed.
Activating Test Mode:
Activate test mode by pressing at the same time the
“MODE” button and the “TEMP ” button on XQ
models. LEDs for Hour, Start, and Stop will blink 1 bps
while Test Mode is active.
Activate test mode by pressing at the same time the
“MONEY SAVER” button and the “CHECK FILTER”
button on QME models. LED for the Filter Alert will blink
1 bps while Test Mode is active.
FIGURE 11
Test Mode has duration of 90 minutes. Test Mode
can be activated under any conditions, including
Off. Test Mode is cancelled by pressing the On/Off
button, unplugging the unit, or when the 90 minutes
is timed out. All settings revert to the factory default
settings of Cool, 75 degrees F, Timer and Set Hour
features are nonfunctional.
Test Mode overrides the three-minute lockout, all
delays for compressor and fan motor start / speed
change, and no delay when switching modes.
Test Mode default settings are ON, Money Saver,
60 degrees F, and High fan speed.
17
Activating Error Code Mode: (Submode of Test Mode)
Unit must be in Test Mode to enter Error Code Mode
1. Activate Error Code Mode by pressing the “TIMER ON/
OFF” button on XQ models. LED for the “TIMER ON/
OFF” will ash 1 bps while Error Code Mode is active.
Pressing the “TEMP/HR ” button will display 00.
Consecutive presses will scroll through all error codes
logged. Press the “TEMP/HR ” button to see the
reverse order of all error codes logged. When the end of
logged error codes is reached the temperature set point
will appear.
Activate Error Code Mode by pressing at the same time
the “A/C START” button and the “ON/OFF” button on
QME models. LED for the “TIMER ON/OFF” will ash
1 bps while Error Code Mode is active. Pressing the
“TEMP ” button will display 00. Consecutive presses
will scroll through all error codes logged. Press the
“TEMP ” button to see the reverse order of all error
codes logged. When the end of logged error codes is
reached the temperature set point will appear.
IMPORTANT: Error Codes are cleared from the log by
exiting from Error Code Mode. To exit on XQ models,
press Timer On/Off button. To exit QME models,
press A/C Start and On/Off buttons. Or unplug unit to
exit Error Code Mode. Plug unit in after 5 seconds to
resume normal operation of unit.
TESTING THE ELECTRONIC CONTROL
ERROR CODE LISTINGS
E1 SHORT CYCLE SITUATION: Dened as (compressor
powered on before the three minute time delay ten times in
one hour. Investigate and correct short cycling problem.
E2 KEYBOARD STUCK ERROR: If key button(s) are
pressed continuously for twenty seconds or more. If MODE
key is stuck, unit will default to cool. Exit Error Code
Mode to see if error “E2” is no longer displayed and unit is
functioning. Replace board if “E2” still displays after exiting
Error Code Mode.
E6 INDOOR PROBE SHORT: Control assumes
ambient temperature is 90 degree F and unit will
operate. Replace probe.
NOTE: All Error Code displays for Frost & Indoor Probe
will allow unit to operate. Unit may or will ice up if faulty
components not replaced.
FROST PROBE SENSOR: disables compressor at 35
degrees F.
INDOOR PROBE SENSOR: Control range is 60
degrees F to 90 degrees F +/- 2 degrees F.
Indoor temperature will be displayed by pressing:
(QME units) The Fan Speed button and the Temperature button.
(XQ units) The Fan Speed button and the “TEMP “
button.
The indoor temperature will be displayed for 10
seconds. The display will change back to the Set Point
temperature by pressing any key button except for the
On/Off button. The indoor temperature can be viewed
in all modes, including test mode.
Check Filter: The Check Filter indicator turns on after
the fan motor has been operating for 250 hours. The
Check Filter indicator is reset by pressing the Check
Filter button one time only. Power failures will not reset
the 250 hour timer. All time elapsed is stored in memory
and resumes counting after power is restored.
Keep Alive: The electronic control has a memory to
retain all functions and status as set up by the user in
the event of a power failure. Once power is restored
to the unit there is a two second delay before the fan
comes on and approximately three minutes delay
before the compressor is activated, providing that the
mode was set for cooling and the set point temperature
has not been met in the room.
18
E3 FROST PROBE OPEN: Normal operation is allowed.
Ohm frost probe. Replace probe if ohm value not read. If
ohm value is present replace board.
E4 FROST PROBE SHORT: Normal operation allowed.
Replace probe.
E5 INDOOR PROBE OPEN: Control assumes indoor
ambient temperature is 90 degree F and unit will operate.
Ohm indoor probe. Replace probe if ohm value not read.
TESTING THE ROTARY CONTROL SWITCHES
Allow 3 min. between restarts
Money Saver
®
MAX
COOL
MAX
HEAT
Low
Cool
Med
Cool
High
Cool
Low
Heat
Med
Heat
High
Heat
Fan
Only
YesNo
Allow3min. betweenrestarts
SPEED
Sleep
Setting
Low
Cool
Medium
Cool
High
Cool
Fan
Only
MINMAX
MoneySaver
®
YesNo
(Heat Pump & Electric Heat Models)
(See Figure 12)
An e ight position control switch i s used t o regulate the
operation of the fan motor and compressor. The compressor
can be operated with the fan operating at low, medium or
high speed in the cooling or heating mode. The fan motor
can also be operated independently on medium speed. See
switch section as indicated on decorative control panel.
NOTE: Heat pump models with electric heat - in the heat
position, heating element only will be energized when
outdoor temperature is below t he operating range o f the
heat pump.
12
Figure
System Control Panel
Heat Pump & Electric Heat Models
(YS, ES, YM, EM, YL & EL)
3. “ Med Cool” Position - between terminals “C” and “3”,
“C2” and “2”, “M” and “M/S”, “AR” and “5”.
4. “ Hi Cool” Position - between terminals “C” and “3”, “C2”
and “2”, “H” and “M/S”, “AR” and “5”.
5. “ Hi Heat” Position - between terminals “C” and “1”, “C2”
and “4”, “H” and “M/S”, “AR” and “5”.
6. “ Med Heat” Position - between terminals “C” and “1”,
“C2” and “4”, “M” and “M/S”, “AR” and “5”.
7. “ Lo Cool” Position - between terminals “C” and “1”, “C2”
and “4”, “LO” and “M/S”, “AR” and “5”.
8. “ Fan Only” Position - between terminals “L1” and “M”.
13
Figure
System Control Switc
(Heat Pump / Electric
Heat Model
s
h
WARNING
SYSTEM CONTROL SWITCH - TEST
Disconnect leads from control switch. Turn control to position
being tested. There must be continuity as follows:
1. “ Off” Position - no continuity between terminals.
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before
servicing. Failure to follow this warning
could result in serious injury or death.
(See Figure 13)
KS, KM, SL Models
(See Figure 14)
A six position control switch is used to regulate the operation
of the fan motor and compressor. The compressor can be
operated w ith the fan operating at l ow, medium o r high
speed. The fan motor can also be operated independently
on m edium speed. See switch s ection a s indicated on
decorative control panel.
Figure
System Control Panel (KS, KM, SL)
14
2. “ Lo Cool” Position - between terminals “C” and “3”, “C2”
and “2”, “LO” and “M/S”, “AR” and “5”.
19
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.