Friedrich PZE07K, PZE12K, PZE09K, PZH09K, PZH12K Installation And Operation Manual

...
PTAC Packaged Terminal Air Conditioners & Heat Pumps
Installation and Operation Manual
ZoneAire
®
Tableof Contents
Congratulations
General Instructions
General Specifications············································································································································ 4
Installation Checklist···············································································································································4
PTAC Installation Recommendations························································································································· 5
Wall Sleeve Installation Instructions (PDXWSA)··········································································································· 6
Alternate Wall Instalations
One-Piece Deep Wall Sleeve Installation (PDXWSEXT)
PXDR10 Drain Kit Installation Instructions (optional for new construction)········································································10
PXGA Standard Grille Insta lation Instructions··········································································································· 12
Chassis Install Preparation····································································································································16
Chassis Installation·············································································································································· 18
Friedrich PTAC Digital Control and Unit Features
System Configuration
Digital Control User Input Configuration···················································································································· 22
Digital Control Operation······································································································································· 23
·····················································································································································
···············································································································································
·······································································································································
································································································
·······································································································
···········································································································································
19
21
3
3
7
9
Remote Control Thermostat Installation···················································································································· 24
Remote Thermostat and Low Voltage Control Connections Remote Thermostat······························································· 24
Final Inspection & Start-up Checklist
Basic Troubleshooting
Accessories························································································································································ 29
··········································································································································
························································································································
26
27
NOTE: All PTAC 7K,9K,12K units come with a standard 3.6KW electric heater (20A power cord).All PTAC 15K units come with a standard 5KW electric heater(30A power cord) .
Congratulations
Thank you for your decision to purchase Friedrich. Your new Friedrich has been carefully engineered and manufactured to give you many years of dependable,
efficient operation, maintaining a comfortable temperature and humidity level. Many extra features have been built into your unit to assure quiet operation,
the greatest circulation of cool, dry air, and the most economic operation.
This Installation and Operation Manual has been designed to insure maximum satisfaction in the performance of your unit. For years of trouble-free service,
please follow the installation instructions closely. We cannot overemphasize the importance of proper installation.
WARNING
Refrigeration system
under high pressure
Do not puncture, heat, expose to flame or
incinerate.
Only certified refrigeration technicians should
service this equipment.
R410A systems operate at higher pressures
than R22 equipment. Appropriate safe
service and handling practices must be used.
Only use gauge sets designed for use with
R410A. Do not use standard R22 gauge sets.
Here are some suggestions to help you use your
new Friedrich most efficiently:
1. Carefully read and follow the installation instructions.
2. Make sure the unit is the right capacity for the area being cooled.
An undersized unit makes the unit work too hard, using more
electricity than needed and increases wear. An oversized unit
will cycle on and off too rapidly, and therefore cannot control
humidity as well.
3. Clean the filter frequently (See Routine Maintenance, Page 26).
4. Do not block the air flow to and from the unit.
5. A dirty filter or improperly set controls can affect the cooling
ability of the unit.
6. If cooling is weak and you have verified that the filter is clean
and the controls are properly set, the unit may need service and
you should call your Friedrich service provider to check the unit.
7. Keep blinds, shades and drapes closed on the sunny side of the
room being cooled to reduce radiant heat.
8. Proper insulation helps your unit maintain the desired inside
temperature.
9. Whenever possible, shade south and west facing windows.
10. Keep window coverings away from the unit to provide free air flow.
WARNING
Read Installation Operation Manual
Please read this manual thoroughly prior to equipment installation or operation.
It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with the NFPA 70
-2008 National Electric Code or current edition, International Mechanic Code 2009 or current edition and any other applicable local or national codes.
Failure to do so can result in property damage, personal injury or death.
WARNING
CAUTION
Indicates a hazard which, if not avoided, can result in severe personal injury or
death and damage to product or other property.
Indicates a hazard which, if not avoided, can result in personal injury and
damage to product or other property.
NOTICE
Indicates property damage can occur if instructions are not followed.
General Instructions
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what will happen if the instructions are not followed.
This is a safety Alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol with the word “WARNING” or “CAUTION”. These words mean:
GeneralSpecifications
PDXWS Wall Sleeve Dimensions: 16" H x 42" W x 13-¾" D Front Cover Dimensions: 16" H x 42" W x 7-¾" D
Cut-Out Dimensions: 16-¼" x 42-¼"
MODEL NUMBER
3
Series
PZ = Friedrich Digital PTAC
System
E = Cooling with electric heat H = Heat Pump with Auxiliary Heat
Nominal Capacity
Engineering Digit
Design Series
Chassis
S = Standard
07 = 7,000 Btuh 09 = 9,000 Btuh
Voltage
12= 12,000 Btuh 15= 15,000 Btuh
Nominal Heater Size (230V or 265V)
Installation Checklist
Inspect all components and accessories for damage before and after
installation.
Remove the cardboard wall sleeve support and grill weatherboard.
Check for proper wall sleeve installation in accordance with the wall
sleeve installation instructions.
Check for a subbase kit or other means of structural support which
is required for ALL installations projecting more than 8" into room.
Install the recommended Condensate Drain Kits for complete
condensate removal.
Ensure that the chassis is installed in a 16" high x 42” wide wall sleeve
that is no deeper than 13 ¾".A baffle kit is required if the sleeve
exceeds that depth.
Ensure that chassis and chassis front cover are installed and secured
properly.
Ensure that drapes, bed, bedspread, furniture, etc.DO NOT block
either return or discharge air grilles.
Inspect the condenser air inlet and outlet for any obstructions
(shrubbery, etc ).
Ensure that 'reset' button is pressed on LCD device (only on cord
connected models).
Typical Unit Components and Dimensions
DISCHARGE GRILLE
FILTERS
RETURN AIR GRILLE
WALL SLEEVE
OUTDOOR GRILLE
CHASSIS
FRONT COVER
B
K = 230/208V - 1 Ph. - 60 Hz. R = 265V - 1 Ph. - 60 Hz .
3 = 3 KW
5.0 kw only available on 15,000 BTU models
PTACInstallationRecommendations
PTAC units should be installed no closer than 12" apar t when two units are side by side. If three or more PTAC units are to operate next to one another allow a minimum of 36" between units Also, a vertical clearance of 60" should be maintained between units installed. In the interior of the room the unit should be located a minimum of 1/4" from the floor and a minimum of 36" from the ceiling.
FRP001
Fo r mino r ob str u c tion s
such as lamp poles or small
shrubbery a clearance of
12" from the outdoor louver
should be maintained.
TYPICAL BUILDING ( PLAN VIEW )
For major obstructions such
as a solid fenc e, wal l or
other heat rejecting device
like a condensing unit, a
minimum distance of 36 "
should be kept.
PTAC
12" MINIMUM, MINOR
OBSTRUCTIONS
36" MIMUMUM, MAJOR
36"
POLE
PTAC
12"
36"
36"
SHRUB
PTAC
OBSTRUCTIONS
CONDENSING UNIT
FENCE OR WALL
FRP002
The above suggestions are for reference only and do not represent all possible installations. Please contact Friedrich for information regarding affects of other
installation arrangements. By following these simple recommendations you can be confident that your Friedrich PTAC will provide years of worry free operation.
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances below:
Figure 1
THREE OR MORE PTACs ADJACENT 36" MINIMUM
TYPICAL WINDOW
36"
TWO ADJACENT PTACs 12" MINIMUM
GROUND FLOOR PTACs 6" MINIMUM FROM GRADE
60" VERTICAL MINIMUM BETWEEN PTACs
60"
12"
6"
VIEW: OUTSIDE BUILDING ELEVATION
For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:
Figure 2
Wall Sleeve Installation Instructions (PDXWSA)
NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories
If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these
instructions completely before attempting installation.
WARNING
Falling Object Hazard
Not following Installation Instructions for
mounting your air conditioner can result
in property damage, injury, or death.
NOTICE
DO NOT allow any pitch toward the inside.
Flashing on all 4 sides of the opening is recommended.
Potential property damage can occur if instructions are not followed.
For Deep WallInstallation (Greater than 13 1/4") See Page 9
The following instructions apply ONLY to walls less than 13 ¼" in depth.
1. The PXDR10 Drain Kit,(optional for new construction) see page
10 if applicable, must be installed before the wall sleeve is
installed into the wall.
2. The External Drain (for new construction or unit replacement) see
page 11 if applicable, must be installed before the wall sleeve is
installed into the wall.
Figure 3
Typical Wall Sleeve Installation
3. From inside the building, position the wall sleeve in the opening
and push it into the wall until it protrudes at least ¼” on the
outside(See Figure 9, Page 8).
4. Position the wall sleeve with a slight tilt towards the outside to
facilitate condensate drainage.It should be level side-to-side
and the front should be ¼ bubble higher than the back.
ELECTRICAL
RECEPTACLE
LINTEL TO SUPPORT MASONRY WALLS
42-¼" MIN.
16-¼"
60" MAX.
20" MAX.
13-¾"
SMOOTH SIDE OF SCREW CLIP FACING INTO ROOM
ELECTRICAL RECEPTACLE
INSULATION
WALL OPENING
WALL SLEEVE
INSULATION
NOTE:
All 230/208V units are manufactured with a 60” power cord and all 265V units with a 18” power cord.
FRP003
AlternateWall Instalations
Figure 4
Panel Wall
Figure 6
CurtainWall
Figure 5
Frame and Brick Veneer
Figure 7
Block and Brick Veneer
FRP005
NOTE: Follow all wall system manufacturer installation instructions. For sunrooms and modular buildings, adhere to their installation instructions for
supporting and sealing sleeve to their frames. All wall and window/wall installations must provide for proper drainage. In applications where the
drain holes on the PTAC wall sleeve are not exposed beyond the wall an internal drain system is recommended. It is the installer's responsibility to
ensure there is adequate drainage for the PTAC unit.
CASE FLANGE (BY OTHERS)
WALL OR WINDOW
1/4" MIN PROJECTION
OPTIONAL SUBBASE
LEVELING SCREW
WOOD FRAME
FRP004
1/4" MIN PROJECTION
STEEL LINTEL
11" MIN. WITH SUBBASE
OPTIONAL SUBBASE
LEVELING SCREW
FRP006
1/4" MIN PROJECTION
CONCRETE LINTEL
STEEL LINTEL
13-3/4" MIN. WITHOUT SUBBASE
OPTIONAL SUBBASE
LEVELING SCREW
RECEPTACLE
FINISHED FLOOR
POWER SUPPLY CONDUIT (SUPPLIED BY INSTALLER)
FRP007
13-¾
"
Figure 8
NOTE: The Wall Sleeve must be
horizontally level (side-to-side) and pitched 1/4 bubble to the outside when installed in an opening.
The mounting hole location
should be approximately 2-4” from the top and bottom of the sleeve.
A ¼" MIN.
A B C
Dimension*
Allow
for wall
finishing
Allow
for floor
finishing
Allow for proper drainage
(Minimum) Min. Max.
(Front-to-Back)
C
No Accessories
¼" ¼"
---
---
With Subbase 1-¾" 3-½" 5"
---
With Lateral Duct ¾"
¼"
---
---
Wall Sleeve Tilt
B
---
---
---
¼"
WALL
* If more than one accessory is to be used, use the maximum
dimension. If the wall thickness is more than 13-¾" - (A+ ¼"), a sleeve extension must be used.
Wall Sleeve Attachment
MOUNTING
HOLES
PLASTIC ANCHORS
Figure 9
Dimensions
WALL SLEEVE
SCREWS
ALTERNATE FASTENING METHODS (Field Supplied)
WOOD SCREW
TOGGLE BOLT
EXPANSION ANCHOR BOLT
FRP008
FRP009
5. Drill two 3/16" holes through each side of the sleeve approximately
4" from top and 4" from bottom of sleeve. Screw four #10 x 1"
screws (included) or appropriate fasteners for your installation,
through the holes in the sides of the wall sleeve.
6. Apply sealant around the wall sleeve where it projects through the
inside and outside wall surfaces. Apply the sealant to the screw
heads or the tops of the fasteners used in Step #5.
7. If the chassis and exterior grille are to be installed later, leave the
weatherboard and center support in place, otherwise remove and
dispose of them. (See Figure 13, Page 12).
8. Provide a support lintel if the wall sleeve is installed in a concrete
or masonry wall (See Figure 10, Page 9).
Figure 10
Lintel Installation
MAIN STUDS
JACK STUDS
JACK STUDS
MAIN STUDS
LINTEL
MOUNTING SCREW HOLES
NO HOLES IN BOTTOM OF WALL SLEEVE UNLESS DRAIN KIT IS USED
NOTE: Construct wall opening to comply with all applicable building codes.
FRP010
One-PieceDeep Wall Sleeve
If the wall is thicker than 13 1/4” a deep wall sleeve or wall sleeve extension
MUST be used. The deep wall sleeve may be special ordered through
your Sales Representative.
Installation (PDXWSEXT)
10
PXDR10DrainKit Installation Instructions(optionalfornew construction)
NOTE:. Determine whether drain will be located within the wall, on the
indoor side, or will drain to the exterior of the building.
Follow appropriate instructions below depending on your
particular type of installation.
Internal Drain
NOTE:. If installing an internal drain, you MUST install a drain kit
on the wall sleeve before the wall sleeve is installed.
1. Refer to Figure 11 and locate the drain within the “Preferred”
area of best drainage. Maintain at least a ½” clearance from the
embossed area.
2. Using the mounting plate with the ½” hole as a template, mark
and drill two, 3/16” mounting holes and a ½” drain hole in the
sleeve bottom .
Figure 11
DrainKitLocation and Installation
OPTIONAL AREA
PREFERRED AREA­NO FOAM INSULATION
3. Remove the backing from the gasket and mount it on the flat side
of the mounting plate. (See Figure 12, Page 11). Insert the drain
tube through the hole in the gasket and mounting plate so the
tube flange will be against the wall sleeve.
4. Position the assembly beneath the drilled holes and secure it with #
10-24x ½" machine screws and lock nuts provided . Seal the tops of the screws with silicone caulking.
5. Use ½" ID copper tube, PVC pipe, or vinyl hose (obtained locally)
to connect the internal drain tube to the drain system in the
building.
6. Referring to Figure 12,Detail A, Page 11,locate and assemble the
two cover plates and gaskets over the drain holes at the rear of
the wall sleeve.Attach them with the #10 sheet metal screws
provided.Make certain that the four overflow slots at the rear of
the wall sleeve are not blocked (See drawing of the back of the
sleeve Figure 12, Page 11).
7. If a deep wall extension (PDXWSEXT) is used, after installing the
field supplied flashing,caulk as required. Be sure to caulk around
the flashing and the wall sleeve where the hole was drilled for the
drain tube.
DRAIN TUBE
NUT
IF THE DRAIN MUST BE
REMOVED TO ALLOW ACCESS
3"
FRONT VIEW
FRP011
PXDR10
QUANTITY
DESCRIPTION
2
COVER PLATES
1
MOUNTING PLATE
1
DRAIN TUBE
3
MOUNTING PLATE GASKET
4
#10 X ½” SHEET METAL SCREWS
2
#10-24 X ½ ” MACH. SCREWS
2
#10-24 X ½" LOCKNUTS
LOCATED IN THE OPTIONAL AREA, THE FOAM INSULATION MUST BE CUT AWAY AND
TO THE DRAIN.
SCREW
WALL SLEEVE
GASKET
MOUNTING PLATE
SIDE VIEW
11
External Drain (for new construction or unit replacement)
When using an external drain system, the condensate is removed through either of two drain holes on the back of the wall sleeve. Select the drain
hole which best meets your drainage situation and install the drain kit.
Seal off the other with a cover plate.
Drain Tube Installation (See Figure 12)
1. Peel the backing tape off the gaskets and apply the sticky side
to one cover plate and one mounting plate as shown in Details
A and B.
2. Place the drain tube through the gasket and the mounting plate
with the flange toward the wall sleeve.
3. Attach the drain tube assembly to one of the two drain holes at the
rear of the wall sleeve. The large flange on the mounting plate is
positioned at the bottom of the sleeve facing toward the sleeve,
Detail B. When the drain tube is positioned at the desired angle,
tighten the screws.
Cover Plate Installation
4. Mount the foam gasket to the cover plate. Using two #10 x ½" sheet
metal screws (provided), attach the cover plate to the remaining
drain hole. Make certain the large flange on the plate is positioned
at the bottom of the sleeve.
5. Discard the additional cover plate, gasket, machine screws, and
locknuts.
NOTICE
If the wall sleeve has not been installed, the drain tube must be rotated to a horizontal position until after the sleeve is installed. Tighten the mounting plate screws when the tube is in the proper position. Make certain that the four overflow slots at the rear of the wall sleeve are not blocked (See Figure 12).
When sealing the sleeve on the outside of the building, be careful NOT to let the sealant block the two condensate drain holes or the four overflow slots at the bottom flange of the sleeve.
Potential property damage can occur if instructions are not followed.
Figure 12
Drain Kit Installation
FRP012
NOTE: The large flange on the mounting plate is positioned at the bottom of the sleeve facing toward the sleeve. The drain tube must be rotated to a
horizontal position to allow for the wall sleeve to be installed into the wall. Once the wall sleeve is installed, return the drain tube to a downward
angle.
COVER PLATE
MOUNTING PLATE
NUT
FOAM GASKET
DETAIL B
½” O.D. TUBE
FOAM GASKET
DETAIL A
OVERFLOW
SLOTS
SCREWS
12
PXGAStandardGrille
Installation Instructions
1. Remove the center support and weatherboard if still installed in
the sleeve.
2. Insert six plastic grommets into the grille openings from the outside
of the grille as shown in Figure 13.
3. Insert two #8 x ⅜" sheet metal screws (provided) in the top two
outside edge plastic grommets, and tighten them half way into
the grommets.
4. Grasp the grille by the attached plastic handles. Position
it with the con dens ate drain kno cko uts fac i ng dow n.
From inside the building, maneuver the grille through the wall
sleeve and pull toward you until the screw heads are inserted
into the keyhole slots at the top of the wall sleeve. Tighten the
two screws completely.
5. Insert the remaining screws into the remaining holes and tighten
securely.
WARNING
Falling Object Hazard
Not following Installation Instructions for
mounting your air conditioner can result
in property damage, injury, or death.
Figure 13
Standard Grille
WEATHERBOARD
WALL SLEEVE
STANDARD GRILLE
#8 x 3/8” SHEET METAL SCREW
WALL SLEEVE
PXGA Standard Grille
Quantity
Description
1 6 6
Stamped Aluminum Grille Plastic Grommets #8 x –" Sheet Metal Screws
CENTER SUPPORT
STANDARD GRILLE
PLASTIC GROMMETS
PLASTIC HANDLES
FRP013
13
FUSE/CIRCUIT
BREAKER
Use ONLY type and size fuse or HACR cir­cuit breaker indicated on unit’s rating plate. Proper current protection to the unit is the responsibility of the owner. NOTE: A time delay fuse is provided with 265V units.
GROUNDING
Unit MUST be grounded from branch circuit through service cord to unit, or through separate ground wire provided on per­manently connected units. Be sure that branch circuit or general purpose outlet is
grounded.The field supplied outlet must
match plug on service cord and be within reach of service cord. Refer to Table 1 for proper receptacle and fuse type. Do NOT alter the service cord or plug. Do NOT use an extension cord.
RECEPTACLE
The field supplied outlet must match plug on
service cord and be within reach of service cord. Refer to Table 1 for proper receptacle and fuse type. Do NOT alter the service cord or plug. Do NOT use an extension cord.
A.
Electrical Rating Tables
All units are equipped with standard power cords.
Table 1
Receptacles and Fuse Types
Voltage
230V
265V
Amps
20
30
20
Heater Size
3.6kw
5kw
3.6kw
Receptacles
NEMA# Receptacle
6-20R
6-30R
7-20R
NEMA# Plug
6-20P
6-30P
7-20P
B.
Power Cord Information (230/208V models only)
All Friedrich 230/208V PTAC units are shipped from the factory with a
Leakage Current Detection Interrupter (LCDI) equipped power cord.The
LCDI device meets the UL and NEC requirements for cord connected air
conditioners effective August 2004.
To test your power supply cord:
1. Plug power supply cord into a grounded 3 prong outlet.
2. Press RESET.
3. Press TEST (listen for click;Reset button trips and pops out).
4. Press and release RESET (listen for click;Reset button latches
and remains in).The power supply cord is ready for operation.
NOTE: The LCDI device is not intended to be used as a switch. Once plugged in the unit will operate normally without the need to reset The LCDI device.
If the LCDI device fails to trip when tested or if the power supply cord is
damaged it must be replaced with a new supply cord obtained from the
product manufacturer,and must not be repaired.
Figure 14 Typical LCDI Devices
15/20A/30A LCDI Device
NOTE: Use Copper Conductors ONLY.Wire sizes are per NEC,check local codes for overseas applications.
WARNING
Electrical Shock Hazard
Turn off electrical power before service or installation. ALL electrical connections and wiring MUST be installed by a qualified electrician and conform to the National Code and all local codes which have jurisdiction. Failure to do so can result in property damage, personal injury and/or death.
FRP014
14
TABLE 2
MODEL
HEATER kW
Power Cord Kit
Voltage
Amperage
Receptacle
PZE / PZH07K
3.6
STD
230/208
20
NEMA 6-20r
PZE / PZH09K
3.6
STD
230/208
20
NEMA 6-20r
PZE / PZH12K
3.6
STD
230/208
20
NEMA 6-20r
PZE / PZH15K
5.0
STD
230/208
30
NEMA 6-30r
PZE / PZH09R
3.6
STD
26520NEMA 7-20r
PZE / PZH12R
3.6
STD
26520NEMA 7-20r
Electrical Wiring for 265 Volt Models
Power Cord Installation
All 265V PTAC/PTHP units come with a factory installed non-LCDI
power cord for use in a subbase.If the unit is to be hard-wired refer to
the instructions below.
NOTE: It is recommended that the PXSB subbase assembly,the
PXCJA conduit kit (or equivalent) be installed on all hardwire
units.If installing a flush-floor mounted unit,make sure the
chassis can be removed from the sleeve for service and
maintenance.
To install the line voltage power leads and conduit to chassis, follow the instructions below.
1. Follow the removal process of the chassis’s junction box.
WARNING
Electrical Shock Hazard
Turn off electrical power before service or installation. ALL electrical connections and wiring MUST be installed by a qualified electrician and conform to the National Code and all local codes which have jurisdiction. Failure to do so can result in property damage, personal injury and/or death.
Prepare the 265V(or 230V) power cord for connection to the
2.
chassis’ power cord connector by cutting the cord to the appropriate length.Power cord harness selection shown on Table 2 on page14.
15
Figure 15
4.0 IN.
EXPOSE WIRES (1.0 IN.)
18.0 IN.
TRIM HARNESS TO LENGTH
Figure 17
STRIP WIRE ENDS (0.5 IN.)
SPACER
LEADING SIDE FOR
WIRE HARNESS INSERTION
LOCKNUT
TO WALL JUNCTION
3. Route the cut ends of harness through the conduit connector
assembly and flex conduit sleeve. Be sure to use the supplied conduit bushing to prevent damage to the cord by the conduit. The cord should pass through the Locknut, Spacer, Chassis Junction Box, Conduit Connector, Bushing, then the Conduit Sleeve. See Figure 17.
4. Route the cut ends of the power cord through the elbow connector
at the other end of the conduit. Tighten screws on elbow connect or to secure conduit sleeve.
5. Fasten and secure the elbow connector to the wall junction box
cover with locknut. Place and mount the wall junction box with
the four wall mounting screws making sure to pass the wall lines
through the junction box. Connect and join all wall lines with the
stripped ends using wire nuts. Tighten both screws of the wall
junction box cover to junction box.
SPACER
BUSHING
CONDUIT SLEEVE
EXITING SIDE FOR
WIRE HARNESS
CHASSIS JUNCTION BOX
CONDUIT CONNECTOR
FRP034
Figure 16
TO CHASSIS JUNCTION
STRAIGHT CONNECTOR
FRP015
WALL CONNECTION
GROUND WIRE
HARNESS
JUNCTION BOX COVER
JUNCTION BOX
GROUND SCREW
COVER SCREWS
FRP016
16
Chassis Install Preparation
1. Remove the weatherboard and center support from the sleeve (if
still in place). Be sure an outdoor grille is attached.
Figure 18
NOTE: To avoid breaking the door or hingepins,do not apply excessive
force when installing.
Figure 19
NOTE: Use a wall sleeve adapter kit (PXSE) if installing a P-Series
chassis in a T-Series sleeve.
WARNING
IMPORTANT: When installing a Friedrich PTAC into an existing sleeve,
it is important to ensure that the unit is installed completely. Inspection
of the air seal between the condenser air baffles and around the indoor
mounting flange is recommended.
In some cases additional gaskets or baffling may be required.
Do NOT use in cribs, beds or playpens.
Destroy immediately after opening. This bag
is NOT a toy.
Failure to do so can result in personal injury
and/or death.
2. Remove the front cover contained in a protective plastic bag
from chassis. Remove the bag and dispos e of it properly.
a. From the front cover, slide the right control door pin into the
hole on the right side of the front cover.
b. Slide the left door pin into the hole on the left side of the
front cover opening.
c. Snap cover into place.
Checkto besure thewallsleeve, extension (ifused),grille, and drainkit areinstalled properly beforechassis installation.
WEATHERBOARD
WALL SLEEVE
CENTER SUPPORT
Suffocation Hazards
Keep bag away from babies and children.
FRP018
INSERT PIN IN THIS LOCATION
PIN
CONTROL DOOR
FRP019
If the control door is not installed, follow these steps:
17
CAUTION
Unit Damage Hazard
Failure to follow this caution may result in equipment damage or improper operation.
Failure to remove shipping tape and screw will prevent fresh air vent door from opening and may result in damage to vent door cable.
3. Carefully remove shipping tape from the front panel and vent door.
See Figure 20
4. Remove shipping screw from the vent door, if present. See Fig 21.
Figure 21
Shipping Screw Location
Figure 20
REMOVE SHIPPING
SCREW IF PRESENT
NOTE: If the unit is mounted flush to the floor, the service cord MUST
be rerouted at the bottom of the front cover on the side closest
to the receptacle. A notch MUST be made in the front cover
side where the cord exits the unit. It is the responsibility of
the installer to create an exit notch.
Shipping Tape Location
FRP021
5. Remove front panel. See Figure 22.
Figure 22
RemovingFrontPanel
SHIPPING TAPE
FRP020
2
1
Pull out at the bottom to release it from the tabs (1). Then lift up (2).
FRP022
Chassis Installation
1. Lift unit level and slide unit into wall sleeve until seal rests
firmly against front of wall sleeve.
Figure 23
SecuringUnit
3. Place tabs over top rail (1). Push inward at bottom until panel
snaps into place (2).
4. Reinstall front panel.See Figure 24.
CAUTION
Excessive Weight Hazard
Use two or more people when installing your air conditioner.
Failure to do so can result in back or other injury.
FRP023
2. Locate the four supplied chassis mounting screws.Insert the
screws through the chassis mounting flange holes that are
aligned with the speed nuts in the wall sleeve.Tighten all four
screws (two per side).
Copper refrigerant tubes are NOT handles. Do NOT use tubing to lift or move chassis.
To remove the front cover,pull the bottom end forward and lift it up to
clear the L bracket across the top of the chassis.
5. Plug the cord (if applicable) into the appropriate receptacle.
Restore power to the unit.
Figure 24
FRP024
Replacing FrontPanel
NOTICE
1
2
18
19
Product Features
The new Friedrich digital PTAC has state of the art features to improve guest comfort,indoor air quality and conserve energy.Through the use of specifically designed control software for the PTAC industry Friedrich has accomplished what other.Manufacturer’s have only attempted –a quiet,dependable,affordable
and easy to use PTAC. Below is a list of standard features on every Friedrich PTAC and their benifit to the owner.
DIGITAL TEMPERATURE READOUT
INDIVIDUAL MODE & FAN CONTROL BUTTONS
QUIET START/STOP FAN DEL AY
REMOTE THERMOSTAT OPERATION
INTERNAL DIAGNOSTIC PROGRAM
FACTORY RUN-TEST
By digitally monitoring the desired room temperature, the room is controlled more precisely than con-
ventional systems. The large, easy-to-read LED display can show either the set point or actual room
temperature as selected by owner.
By having separate control buttons and indicators for both fan and mode settings, the Friedrich digital control eliminates the confusion of previous digital PTACs. The accurate temperature setting provides greater guest comfort than other systems.
The fan start and stop delays prevent abrupt changes in room acoustics due to the compressor energiz-
ing or stopping immediately. Upon call for cooling or heating, the unit fan will run for ve seconds prior to energizing the compressor. Also, the fan-off delay allows for “free cooling” by utilizing the already cool
indoor coil to its maximum capacity by running for 30 seconds after the compressor.
Some applications require the use of a wall-mounted thermostat. All new Friedrich PTACs may be switched from unit control to remote thermostat control easily without the need to order a special model or accessory kit.
The Friedrich digital PTAC features a self-diagnostic program that can alert maintenance to component
failures or operating problems. The internal diagnostic program saves properties valuable time when diagnosing running problems.
Factory run-tested units reduce problems in the field.
ELECTRONIC TEMPERATURE LIMITING
ROOM FREEZE PROTECTION
RANDOM COMPRESSOR RESTART
CONDENSATE REMOVAL SYSTEM
By limiting the operating range, the property can save energy by eliminating “max cool” or “max heat” situ­ations common with older uncontrolled systems. The new electronic control allows owners to set operat-
ing ranges for both heating and cooling independently of one another.
When the PTAC senses that the indoor room temperature has fallen to 50°F, the unit will cycle on the fan (high) and the electric strip heat to raise the room temperature to 55°F, and then cyc feature works regardless of the mode selected and can be turned off.
Multiple compressors starting at once can often cause electrical overloads and premature unit failure.
The random power up. The compressor delay will range from 120 to 240 seconds.
Condenser fan utilizes slinger ring technology to pick up condensate from the base pan and disperse it on
to the condenser coil where it evaporates. This helps to cool the coil and increase the energy efciency of the unit.
restart delay eliminates multiple units from starting at once following a power outage or initial
le off again. This
DIGITAL DEFROST
THERMOSTAT
The PZ-Series uses a digital thermostat to accurately monitor the outdoor coil conditions to allow the
heat pump to run whenever conditions are correct. Running the PTAC in heat pump mode saves energy and reduces operating costs. The digital thermostat allows maximization of heat pump run time.
INSTANT HEAT HEAT PUMP MODE
SEPAR ATE HEAT/COOL FAN CYCLE CONTROL
EMERGENCY HEAT OVERRIDE
CENTR AL DESK CONTROL READY
INDOOR COIL FROST SENSOR
ULTRAQUIE T
AIR SYSTEM
HIGH EFFICIENCY
Heat pump models will automatically run the electric heater to quickly bring the room up to temperature when initially energized, then return to heat pump mode. This ensures that the room is brought up to temperature quickly without the usual delay associated with heat pump units.
The owner may choose between fan cycling or fan continuous mode based on property preference. Fan continuous mode is used to keep constant air ow circulation in the room during all times the unit is ‘ON’. Fan cycle will conserve energy by only operating the fan while the compressor or electric heater is operating. ability to set the fan cycling condition independently between heating and cooling mode will increase user comfort by allowing other PTAC brands that only allow one selection).
In the event of a compressor failure in heat pump mode, the compressor may be locked out to provide heat through the resistance heater. This feature ensures that even in the unlikely event of a compressor failure, the room temperature can be maintained until the compressor can be serviced.
All Friedrich digital PTACs have low voltage terminals ready to connect a central desk control energy management system. Controlling the unit from a remote location like the front desk can reduce energy usage and requires no additional accessories on the PTAC unit.
The frost sensor protects the compressor from damage in the event that airflow is reduced or low outdoor temperatures cause the indoor coil to freeze. When the indoor coil reaches 33°F, the compressor is disabled and the fan continues to operate based on demand. Once the coil temperature returns to 59°F, the compressor returns to operation.
The PZ-Series units feature an indoor fan system design that reduces sound levels without lowering
airow or preventing proper air circulation.
The Friedrich PTAC has been engineered so that all functional systems are optimized so that they work
together to deliver the highest possible performance.
the choice of only constantly circulating air in the summer or winter time (unlike
The
DUAL MOTOR
ROTARY COMPRESSOR
ALUMINUM ENDPLATES
TOP-MOUNTED ANTIMICROBIAL AIR FILTERS
FILTERED FRESH
AIR INTAKE
R-410A REFRIGERANT
DIAMONBLUE TECHNOLOGY
BREAK-PROOF CONTROL DOOR
GALVANIZED ZINC WALL SLEEVE AND BASE PAN
The dual-motor design means that the indoor motor can run at slower speeds which reduces sound
levels indoors.
High efciency rotary compressors are used on all Friedrich PTACs to maximize durability and ef­ci ency.
Outdoor coil endplates made from Aluminum reduce corrosion on the outdoor coil common with other coil designs.
All Friedrich PTAC return air filters feature an antimicrobial element that has proven to prevent mold and bacterial growth in laboratory testing.PXFTB replacement All filters are washable, reusable and easily accessed from the top of the unit without the removal of the front cover.
Friedrich PTAC units are capable of introducing up t
The outdoor air passes through a washable mesh screen to prevent debris from entering the airstream.
Friedrich PTAC units use environmentally-friendly refrigerant.
Diamonblue Technology protects the outdoor coil from harsh environments.
Break-proof control door design maintains the integrity of the unit.
Galvanized zinc coated steel wall sleeve and steel base pan undergo an 11-step preparation process,
are powder coated with a polyester finish and cured in an oven for exceptional durability.
filter kits feature the same antimicrobial agent.
o 30 CFM of outside air into the conditioned space.
20
21
System Configuration
Fresh Air Vent Control
The vent control lever is located on the left side of the unit,behind the
front panel.
NOTE: The vent door shipping hardware must be removed before using
the vent control lever.See page17,Figure21,(Remove Shipping
Screw from Vent Door if present).
When vent door is set to CLOSE,only the air inside the room is circulated
and filtered.See Figure 25.
When vent door is set to OPEN,some outdoor air will be drawn into room.
This may reduce heating or cooling efficiency.
Figure 25
Air Vent Control Location
Adjusting Air
To adjust air direction:
1. Remove front panel.See Figure 22.
2. Remove louver screws that hold louver insert in place (from back
side of front panel.See Figure 26.
3. Turn louver insert and rotate180°.See Figure27.
4. Repace louver insert.
5. Replace screws and front panel.
Figure 26
Backside of Front Panel
LOUVER SCREWS
FRP026
Figure 27
AIR DISCHARGE OUTWARD (Default)
AIR DISCHARGE UPWARD
Adjusting
Vent Control (pull level through
label to operate)
FRP025
Louvers
FRP027
22
8
Digital ControlUser InputConfiguration
Dip SwitchSetting
1.
Switch 1-Reserved.
2.
Switch 2-Heat pump enable/disable.
Moving Dip Switch #2 to “OFF” can be set as Emergency Heat Override. In the unlikely event of a compressor failure, a heat pump unit may be switched to operate in only the electric heat mode until repairs can be made.
3.
Switch 3-Electric strip enable/disable.
4.
Switch 4-Heating priority
ON-heat pump to be prior; OFF-Electric heat to be prior
5. Switch 5-Room Freeze Protection
Units are shipped from the factory with the room freeze protection enable. Room Freeze Protection can be switched off at the owner’s preference by moving Dip Switch 5 to “OFF”. This feature will monitor the indoor room
conditions and in the event that the room falls below 40, the unit will
automatically run “heating”. This occurs regardless of mode.
6.
Switch 6-Electric memory enable/disable
The factory setting is enabled. The smart center will remember
user’s setting. After power cut recovery, the unit will operate the
same status as before power cut. Moving Dip Switch 6 to “OFF”
will disable this feature, smart center will no more remember
settings.
7. Switch 7- Medium fan speed for indoor fan ON-when press the HIGH fan
speed, output the medium speed instead; OFF-output the same speed as selected.
8. Switch 8-Reserved.
1 2 3 4 5 6 7
ON
OFF
LOCATION OF DIP SWITCHES ON UNIT
FRP028
The adjustable control dip switches are located at the front portion of the digital Smart Center. The inputs are only visible and accessible with the front cover removed from the PTAC.
Figure 28
Dip Switches
DIP SWITCH
Switch Descrip tion Function
#1 Reserved /
#
2
Heat pump
#
#
#5
Electric strip
3
Reserved
4
Room Freeze Protection
Electric memory
#6
#
#8
enable/disable
Medium fan speed
7
for indoor fan
Reserved
ON-enable heat pump; OFF-disable heat pump, run electric heat only.
ON-enable electric heat; OFF-disable electric heat.
Heating priority
ON-Allows the unit to ensure the indoor room temperature does not fall below 40even when turned off.
OFF-disable freeze protection.
ON-enable; OFF-disable.
ON-When press the HIGH fan speed, output the medium speed instead; OFF-output the same speed as selected.
/ OFF
Reserved
Medium fan speed for indoor fan Electric memory enable/disable Room freeze protection Heating priority Electric strip enable/disable Heat pump enable/disable Reserved
Factory Setting
OFF
HP models-ON Electric heat only-OFF
ON
OFF-Electric heating prior
ON
ON
7K-ON 9K/12K/15K-OFF
Option
/
OFF-Overrides compressor operation(HP models only)
Forbidden moving to OFF
ON-Heat pump prior
OFF
OFF
Forbidden changing factory setting
/
23
Digital Control Operation
°F vs °C Display
The unit is factory configured to display all temperatures in degrees Fahrenheit (°F). To switch to degrees Celsius, press the “UP” and “DOWN” buttons simultaneously for three seconds. The display will switch to C degrees. To revert back to °F, press the “UP” and “DOWN” buttons simultaneously for three seconds. The display will switch to F degrees.
Cooling Mode
Pressing the “Cool” button after turn the unit on will put the unit into
cooling mode. Press “UP” or “DOWN” button to adjust the set point, the
unit will cycle the compressor on and off to maintain a comfortable room.
The compressor will cycle on anytime that the room temperature is 2 °F
above the set point. The fan will either continuous or cycling, depends on
the “Constant Fan” selection. See Constant Fan section.
Heating Mode
After turn on the unit, press the “Heat” button will put the unit into heating
mode.
HeatPumpModels (PZH)
When the “Heat” button is pressed initially the unit may call for heat pump or electric strips (depends on different ambient temperature or DIP Switch 4 settings) to bring the room to the set point. When the room temperature falls 2 °Fbelow the set point, the unit will cycle the compressor or electric strip on. The fan will either continuous or cycling, depends on the “Constant Fan” selection. See Constant Fan section. When the outdoor coil temperature falls below 26 °F for 3 minutes, the unit will operate the electric strip instead of heat pump. Only when the room temperature reaches the set point and the outdoor coil temperature rises to 41 °F, the compressor will be allowed to operate again.
Heat/CoolModels(PZE)
After pressing the “Heat” button, adjust the set point and the unit will cycle the electric strip on and off to maintain a comfortable room. The heater will come on anytime that the room temperature is 2 °F below the set point. The fan will either continuous or cycling, depends on the “Constant Fan” selection. See Constant Fan section.
EmergencyHeatOperation
In the event of a compressor failure in heat pump mode, the compressor may be locked out to provide heat through the electric strip heater. This feature ensures that even in the unlikely event of a compressor failure, the room temperature can be maintained until the compressor can be serviced. Dip switch 2 controls the emergency heat setting.
Pressing the “Constant Fan” button will provide constant or cycle fan operation in cooling or heating modes. The fan speed selection is made by pressing either “High” or “Low” or “Auto” fan speed button.
Setting Temperature Limit
Hold "UP" and "High" fan speed buttons at the same time for 5s, digital tube displayer will show R1-R8, default is R8. The temperature(°F)
range as below:
R1: 63-86
R2: 65-86
R3: 72-90
R4: 72-74
R5: 67-92
R6: 69-90
R7: 68-72
R8: 60-90
Figure 29
Digital Control Panel
FRP029
Constant Fan
24
Remote Control Thermostat Installation
Install Thermostat
1. Approximately 5 ft from the floor.
2. Close to or in a frequently used room,preferably on an inside wall.
3. On a section of wall without pipes or ductwork.
The Thermostat should NOT be mounted:
1. Close to a window,on an outside wall,or next to a door leading
outside.
2. Where it can be exposed to direct sunlight or heat,such as the sun,
a lamp,fireplace or any other temperature radiating object which
may cause a false reading.
3. Close to or in the direct airflow of supply registers and/or return
air grilles.
4. Any areas with poor air circulation,such as a corner,behind a
door,or an alcove.
Remote Thermostatand Low Voltage Control Connections
RemoteThermostat
All Friedrich PZmodel PTAC units are factory configured to be controlled
by either the chassis mounted Smart Center or a 24V remote wall
mounted thermostat.The thermostat may be auto or manual changeover
as long as the control configuration matches that of the PTAC unit.
NOTE: All PZE models require a single stage cool,single stage heat
thermostat.All PZH models require a single stage cool,dual
stage heat thermostat with an B reversing valve control.The
Friedrich RT6 thermostat can be configured for either model.
To control the unit with a wall mounted thermostat follow the steps below:
1. Unplug the unit before doing any work
2. Remove the low voltage terminal block from the unit.
3. Connect the corresponding terminals from the wall thermostat to
the terminal block
4. Plug the terminal block on the unitk.
5. Restore power to the unit.
6. Under stand-by mode, press the “Cool” and “UP” buttons
simultaneously for three seconds, the digital displays character “r”, and the beeper chime twice.
7. The unit is now controlled by the wall thermostat only.
8.
If the accessory escutcheon kit (PDXRTB) is to be used, install
NOTE: The unit control panel no longer controls the unit. To restore the
control panel, press the “Cool” and “UP” buttons simultaneously for three seconds, the digital displays character “P”, and the beeper chime once.
ThermostatConnections
R = 24V Power from Unit
Y = Call for Cooling
W = Call for Heating
B = Reversing Valve Energized in Heating.Mode
GL = Call for Low Fan
GH = Call for High Fan
C = Common Ground
*If only one G terminal is present on thermostat connect to GL for low
speed fan or to GH for high speed fan operation.
it over the existing control panel.
Figure 30
Control board with optional installed
PDXRTB
escutcheon kit
FRP030
25
Front Desk Control Terminal
The Friedrich PZ model PTAC has built-in provisions for connection to an external switch to control power to the unit. The switch can be a central desk control system. For front desk control operation, connect one side of the normal open switch to the R terminal and the other to the FD terminal. The control logic as below:
(a). Turn ON unit: short R and FD then release for one time within 5s. (b). Turn OFF unit: short R and FD then release for twice within 5s. (c). Force unit shut down for one time: short R and FD short over 5s. NOTE: After forced shut down, you can turn on the unit again by control panel.
NOTE: The desk control system and switches must be field supplied.
EnergyManagement
Sometimes known as Front Desk Control, an input is provided so that the unit can be manually disabled from a remote location. If the unit detects 24Vac on this input, it will automatically turn itself off. If no voltage is detected on the input , the unit will run normally.
NOTE:
It is the installer's responsibility to ensure that all control wiring connections are made in accordance with the installation instructions.Improper connection of the thermostat control wiring and/or tampering with the unit's internal wiring can void the equipment warranty.Other manufacturer's PTACs and even older Friedrich models may have different control wire connections.Questions concerning proper connections to the unit should be directed to Friedrich.
WARNING
Electrical Shock Hazard
Turn off electrical power before service or installation.
ALL electrical connections and wiring
MUST be installed by a qualified electrician and conform to the National Code and all local codes which have jurisdiction. Improper connection of the thermostat control wiring and/or tampering with the units internal wiring may result in property damage, personal injury or death.
26
Final Inspection & Start-up Checklist
Inspect and ensure that all components and accessories have been
installed properly and that they have not been damaged during the
installation process.
Check the condensate water drain(s) to ensure they are adequate for
the removal of condensate water, and that they meet the approval of
the end user.
Ensure that all installations concerning clearances around the unit
have been adhered to.Check to ensure that the unit air filter, indoor
coil, and outdoor coil are free from any obstructions.
Ensure that the entire installation is in compliance with all applicable
national and local codes and ordinances that have jurisdiction.
Secure components and accessories, such as the chassis, decorative
front cover and control door.
Start the unit and check for proper operation of all components in
each mode of operation.Instruct the owner or operator of this units
operation, and the manufacturer’s recommended routine maintenance
schedule.
NOTE:. A log for recording the dates of maintenance and/or service
is recommended.
Present the owner or operator of the equipment with the Installation
& Operation manual, all accessory installation instructions, and the
name, address and telephone number of the Authorized Friedrich
Warranty Service Company in the area for future reference if
necessary.
Routine Maintenance
To ensure proper unit operation and life expectancy the following mainte­nance procedures should be performed on a regular basis.
WARNING
Electrical Shock Hazard
Unplug Unit or turn off electrical power to unit prior to performing maintenance
procedures.
Failure to do so can result in electrical
shock or death.
Air Filter
To ensure proper unit operation, the air filters should be cleaned at
least monthly, and more frequently if conditions warrant.The unit must
be turned off before the filters are cleaned.
To remove the air filters,filter grasp the top of the filters and lift out of
the front cabinet.Reverse the procedure to reinstall the filters.
Clean the filters with a mild detergent in warm water, and allow them to
dry thoroughly before reinstalling.
Coils&Chassis
NOTE:. Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and degreaser.The use of harsh cleaning materials may lead to deterioration of the aluminum fins or the coil end plates.
The indoor coil and outdoor coils and base pan should be inspected pe­riodically (annually or semi-annually) and cleaned of all debris (lint, dirt, leaves, paper, etc ) as necessary. Under extreme conditions, more frequent cleaning may by required.Clean the coils and base pan with a soft brush and compressed air or vacuum.A pressure washer may also be used,
however, you must be careful not to bend the aluminium fin pack.Use a
sweeping up and down motion in the direction of the vertical aluminium
fin pack when pressure cleaning coils.
NOTE:. It is extremely important to insure that none of the electrical
and/or electronic parts of the unit get wet. Be sure to cover all electrical
components to protect them from water or spray.
Decorative Front
The decorative front and discharge air grille may be cleaned with a mild
soap or detergent.Do NOT use solvents or hydrocarbon based cleaners
such as acetone,naphtha,gasoline,benzene,etc,to clean the decorative
front or air discharge grilles.
Use a damp (not wet) cloth when cleaning the control area to prevent water
from entering the unit,and possibly damaging the electronic control.
FanMotor & Compressor
The fan motor &.compressor and are permanently lubricated,and require
no additional lubrication.
Wall Sleeve
Inspect the inside of the wall sleeve and drain system periodically(annua-
lly or semi-annually)and clean as required.
Under extreme conditions, more frequent cleaning may be necessary. Clean both of these areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as needed.
27
Basic Troubleshooting
Malfunction
Possible Reasons
S olution
Start Failure
power line bad, units don’t have power supply.
Check the indicator LED on the LCID power head, it should be lit up, if not, push the RESET button, if still don’t have voltage, but power grid has output, you need to change the power cord.
Power cord protection trip.
Check the power cord if somewhere is broken, push the RESET button. If not solved, replace the power cord.
Power cord isn’t fixed well.
Check that whether power cord is fixed well.
PCB fuse is broken.
Check if any load (in fan, out fan, reversing valve, power transformer) is short circuit. Eliminate the error and replace the fuse with the same type.
Bad contact between main board and control panel.
Check the contact wires, make sure all contact well.
Compressor delay start.
It’s normal, compressor will start after 3 minutes
Power fail protection.
When power on, because of auto-restart, unit will delay starting in 120~240s
Unit in protection mode.
Please check the ERROR CODE
Main board or Control panel is bad.
Replace the main board or control panel
Control panel do not work
When the unit is switch to 24V remote thermostat, the control panel will not be functioning.
If you need to use control panel to take control, you need to switch the control. See the Switch Over Between 24V Remote Thermostat and Control Panel in the senior settings section.
Indoor fan/outdoor fan not function or run slowly
Fan is locked by something or the power wires are not fixed well; fan capacitor is not fixed well; fan capacitor is out of service life.
Disconnect the power cord, check whether the fan can run smooth by hand or other tools, whether motor wire is fixed well. For the slow running speed, you could change a new capacitor.
Not well cooling/heating
Something may block the indoor/outdoor air outlet.
Make sure that there is no obstacle at the indoor/outdoor air outlet.
Make sure that the grill is suitable for the unit, inappropriate grill will cause the compressor being protected; make sure that the grill has more than 70% turnover.
Set unsuitable temperature.
Set higher/lower temperature by the control board. NOTE: temperature setting restriction will restrict the setting temperature. See the Setting Temperature Range chapter.
Indoor air filter is dirty.
Should clean the filter every month at least.
Room is hot/cold.
Let unit run a little longer that room temperature will be lower/higher.
Heat leakage between indoor and outdoor.
Block the leakage place.
Indoor coil not cold/heat.
Charge the refrigerant.
Unit has noise
Some moving parts of the unit get loose fixing or cause bad vibration. Something in the air way.
Make sure that all moving parts are assembled well, and nothing is in the air way.
Bad smell when heating
The dust on the E-heater is heating.
The bad smell will disappear a little later.
28
Malfunction Possible Reasons Solution
Service & Assistance
Before calling for service,please check the "Basic Troubleshooting"sec­tion above.This may help you to the answer to your problem,avoid unne­cessary service calls,and save you the cost of a service call if the probl­em is not due to the product itself.If you have checked the "Basic Trouble shooting" section and still need help,here is a list of available services:
You can find the name of you local Authorized Service Provider by visiting our web site at www.friedrich.com.
If you require further assistance you can call the Customer Support Call Center at 1-800-541-6645.
Before calling,please make sure that you have the complete model and serial number,and date of purchase of your equipment available.By provid­ing us with this information we will be better able to assist you.
Our specialists are able to assist you with:
* Inspect and ensure that all components and accessories have been
installed properly and that they have not been damaged during the
installation. * Specifications and Features of our equipment. * Referrals to dealers, and distributors.
* Use and Care information.
* Recommended maintenance procedures.
* Installation information.
* Referrals to Authorized Service Providers and Parts depots.
Outlet temperature is not always cooling/heating
Outlet temperature is not high enough when heating by heat pump.
Fan stops when cooling/heating.
When outdoor ambient temp is low, the heat pump will not be able to offer enough heat. Soon after that, the E-heater will come on to heat.
It is normal when the CONSTANT FAN is OFF. Youcan enable the CONSTANT FAN.
Outdoor is dripping water
Indoor is dripping water
Indoor coil freeze
E2 Indoor return air temperature sensor failure
E3 Indoor coil temperature sensor failure
E4 indoor air outlet temperature sensor failure/air blow out over heat in electric heat mode
E5 Outdoor coil temperature sensor failure.
E8 Overheating protection/defrosting
E9 High pressure protection
Not install the drain pipe kit.
Wall sleeve is not installed correctly.
Outdoor temperature is too low in cooling mode.
Filter is dirty.
Indoor return air temperature sensor open circuit or short circuit.
Indoor coil temperature sensor open circuit or short circuit.
Indoor air outlet temperature sensor open circuit or short circuit; Indoor filter gets dirty or something blocks the air intake.
Outdoor coil temperature sensor open circuit or short circuit.
Indoor fan failure/dirty filter/refrigerating system failure/indoor coil temperature sensor failure.
Outdoor fan failure/refrigerating system failure/high pressure switch failure/outdoor coil temp sensor broken.
Install the drain pipe kit.
Install the wall sleeve according to the installation manual.
When outdoor temperature is drop to 12.8℃(55 ℉)or below, it will cause that indoor coil freeze. Open the fresh air door, and running at fan mode.
Clean the filter to recover the normal air flow
Check the sensor connecting. If the sensor is bad, replace a new one.
Check the sensor connecting. If the sensor is bad, replace a new one.
Check the sensor connecting. If the sensor is bad, replace a new one. Clean the filter and clean the air way.
Check the sensor connecting. If the sensor is bad, replace a new one.
Check the indoor fan/clean filter/refill refrigerant/ replace indoor coil sensor.
Check outdoor fan/refrigerating pipe system/high pressure switch/outdoor coil temp sensor.
29
Accessories
New Construction Accessories
PDXWSA
WALL SLEEVE Galvanized zinc coated steel is prepared in an 11-
step process, then powder coated with a polyester nish and cured
in an oven for exceptional durability. The wall sleeve is insulated for
sound absorption and thermal efciency, 16" H x 42" W x 13
1
PDX WSEX T18
PDXWSEXT24
PDXWSEXT
PXSE
DEEP WALL SLEEVE For walls up to 17
DEEP WALL SLEEVE For walls up to 23
CUSTOM DEEP WALL SLEEVE One piece extended wall sleeve for walls
from 13
1
/4" to 25 1/2" D are available by special order.
SLEEVE EXTENSION RETROFIT KIT Galvanized zinc coated steel, 2
/2" D.
1
/2" D.
Deep wall sleeve PDXWSE XT18 shown with weather panel
sleeve extension attached to the room side of the sleeve to allow for the installation of a PZ-Series Friedrich PTAC in a T-Series sleeve.
PXGA GRILLE Standard, stamped aluminium, anodized to resist chalking and
oxidation.
PXAA PXBG PXSC
ARCHITECTURAL GRILLES Consist of heavy-gauge 6063-T5
aluminum all oy: 42" W x 16" H x 1
1
/8" D
PXAA – Clear, extruded aluminum PXBG – Beige acrylic enamel PXSC – Also available in custom colors.
3
/4" D.
3
PDXWSA
/8"
PXGA
PXDR10 CONDENSATE DRAIN KIT Attaches to the bottom of the wall sleeve for
internal draining of condensate or to the rear wall sleeve ange for ex­ternal draining. Recommended on all units to remove excess conden­sate. Packaged in quantities of ten.
PXCJA CONDUIT KIT WITH JUNCTION BOX Hard wire conduit kit with junc-
tion box for 208/230V and 265V units (subbase not required). Kit includes a means of quick disconnect for easy removal of the chassis. *Required for 265V installations.
PXFTB
REPLACEMENT FILTER PACK These are original equipment return air
lters. They are reusable and can be cleaned by vacuuming, washing, or blowing out, and are sold in convenient ten-packs. (Two lters per
chassis).
PXA A
30
New Construction Accessories
PDXDA A LATERAL DUCT ADAPTER Attaches to the Friedrich PTAC/PTHP unit to di-
rect up to 35% of the total airow to a second room. The unit-mounted duct
plenum features a front-mounted aluminum grille that has two positions to provide the most optimal air direction. The air may be directed to either the left or the right of the unit through the supplied 3 1/2 H" x 7 W" x 47" L plenum. Plenum may be cut to length by the installer. Kit includes duct plenum, front grille, 47" duct extension, duct discharge grille, duct end cap and all necessary mounting hardware.
PDXDEA
LATERAL DUCT EXTENSION Additional 3
1
/2 H" x 7" W x 47" L plenum for
use with the LATERAL DUCT ADAPTER. A maximum of 3 duct exten-
sions total may be used. Note: Ducted airow is reduced as duct length is
increased.
PXSBA DECORATIVE SUBBASE Provides unit support for walls less than six inches
thick. Includes leveling legs, side filler panels and mounting brack­ets for electrical accessories. Accepts circuit breaker, power disconnect switch, or conduit kit.
PXSB ELECTRICAL SUBBASE Provides unit support for walls less than six inches
thick. Includes leveling legs, side ller panels, mounting brackets, a plug­in receptacle and field-wiring access. The subbase also includes elec­trical knockouts for a power disconnect switch or circuit breaker.
PXSB23020 PXSB23030 PXSB26515 PXSB26520 PXSB26530
Electrical Subbase - 230V 20A Electrical Subbase - 230V 30A Electrical Subbase - 265V 15A Electrical Subbase - 265V 20A Electrical Subbase - 265V 30A
RT6
RT6P
DIGITAL REMOTE THERMOSTATS
RT6 Wired single stage cool, single stage heat for PDE models or single
stage cool, dual stage heat for PDH model thermostat features high/low fan speed switch. Thermostat is hard wired and can be batter y powered or
unit powered. Features backlit display and multiple conguration modes.
For use on Friedrich PTACs and Vert-I-Paks.
RT6P Wireless single stage cool, single stage heat for PDE models or sin­gle stage cool, dual stage heat for PDH model thermostat features high/ low fan speed switch. Thermostat is hard wired and can be battery pow-
ered or unit powered. Features backlit display and multiple conguration
modes. For use on Friedrich PTACs and Ver t-I-Paks.
WRT1 WIRELESS DIGITAL REMOTE THERMOSTAT Single stage cool, single
stage heat for PDE models or single stage cool, dual stage heat for PDH model thermostat features high/low fan speed switch. Thermostat is wireless and is battery powered. Features backlit display and multiple
conguration modes. For use on Friedrich PTACs and Vert-I-Paks.
P
DXRTB
REMOTE THERMOSTAT ESCUTCHEON KIT This kit contains ten escutch-
eons that can be placed over the factor y control buttons when a remote wall mounted thermostat is used. The escutcheon directs the guest to the wall thermostat for operation and retains the LED window to display error codes and diagnostic information.
EMRT1
EMWRT1
ENERGY MANAGEMENT THERMOSTATS
EMRT1
Wired thermostat with occupancy sensor.
EMWRT1
Wireless thermostat with occupancy sensor.
EMOCT
Online connection kit.
EMRAF EMRHCF
Remote access fee. Remote humidity control fee.
Friedrich Air Conditioning Co.
10001 Reunion Place, San Antonio, TX 78216
800.541.6645
PACKAGED TERMINAL AIR CONDITIONERS
LIMITED WARRANTY
We will not be responsible for and the user will pay for:
1. Service calls to:
2. Parts or labor provided by anyone other than an authorized service center.
3. Damagecaused by:
1. Repair of the unit
2. A refund to the customer for the prorated value of the unit based upon the remaining warranty period of the unit.
3. Providing a replacement unit of equal value
www.friedrich.com
PZ-SERIES
SAVE THIS CERTIFICATE.It gives you specific rights.You may also have other rights which may vary from state to state and province to province.
In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center, ask the company that installed your unit or contact us - see address and telephone number above. To obtain service and/or warranty parts replacement, you must notify an authorized FRIEDRICHAir Conditioning Co. service center, distributor, dealer, or contractor of any defect within the applicable warranty period.
When requesting service: please have the model and serialnumber from your unit readily available.
Unlesss pecified otherwise herein, the following applies: FRIEDRICH PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS
LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation). Any part found to be defective in the material or workmanship
will be repaired or replaced free of charge by our authorized service center during the normal working hours; and
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty (60) months from the date of installation). ON THE SEALED REFRIGERATION SYSTEM. Any part of the sealed refrigeration system that is defective in material or workmanship will be repaired or replaced free of charge (excluding
freight charges) by our authorized service center during normal working hours. The sealed refrigeration system consists of the compressor, metering device, evapo- rator, condenser, reversing valve, check valve, and the interconnecting tubing.
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United States, Alaska, Ha­waii, Puerto Rico, Mexico and Canada. The warranty applies only if the unit is installed and operated in accordance with the printed instructions and in compliance with applicable local installation and building codes and good trade practices. For international warranty information, contact the FriedrichAir Conditioning Company - International Division.
Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part. Reasonable proof must be presented to
be new or remanufactured. Replacement parts and labor are only warranted for any unused portion of the unit’s warranty.
A)Instruct on unit operation. B)Replace house fuses or correct house wiring. C)Clean or replace air filters. D)Remove the unit from its installed location when not accessible for service required. E) Correct improper installations.
A)Accident,abuse,negligence,misuse,riot,fire,flood,or acts of God. B)operating the unit where is a corrosive atmosphere containing chlorine,fluorine,or any damaging chemicals(other than in a normal residential environment). C)Unauthorized alteration or repair of the unit,which in turn affects its stability or performance. D) Failing to provide proper maintenance and service. E) Using an incorrect power source. F) Faulty installation or application of the unit.
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit. We have not made and do not make any representation or warranty fitness for a particular use or purpose and there is no implied condition of fit­ness for a particular use or purpose. We make no expressed warranties except as stated in this certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection with this unit. Any implied warranties shall last for one year after the
original purchase date. Some states and provinces do not allow limitations on how long an implied warranty or condition lasts, so the above
limitations or exclusions may not apply to you.The provisions of this warranty are in addition to and not a modification of or subtraction from the statutory warranties and other rights and other rights and remedies provided by law.
Performance of Friedrich’s Warranty obligation is limited to one of the following methods:
The method of fullfillment of the warranty obligation is at the sole discretion of Friedrich Air Conditioning.
In case of any questions regarding the provisions of this warranty, the English version will govern.
31
Loading...