ZoneAire® Select Series PTAC
Cooling Only, Electric Heat, Heat Pump
PURCHASER P.O. # DATE
PROJECT LOCATION
ENGINEER ARCHITECT
SUBMITTED BY FOR APPROVAL FOR REFERENCE
ITEM PLAN DESIGNATION QUANTITY COOLING Btu VOLTAGE FRIEDRICH MODEL
Accessories
PDXWSA Wall Sleeve Qty
PDXWSEXT18
PDXWSEXT24
PDXWSEXT
PXGA Standard Outdoor Louver Qty
PXAA Architectural Louver, clear Qty
PXBG Architectural Louver, beige Qty
PXSC Architectural Louver, color matched Qty
PDXRTB Remote Thermostat Escutcheon Kit Qty
PXDR10 Condensate Drain Kit (pkg/10) Qty
PXSBA Sub Base Qty
PXSE T-Series Sleeve Adapter Qty
PXCJA Conduit Kit w/Junction Box Qty
PDXDAA Lateral Duct Adapter Qty
PDXDEA Lateral Duct Extension Qty
Deep Wall Sleeve- For walls up to
17 1/2" deep
Deep Wall Sleeve- For walls up to
23 1/2" deep
Custom Deep Wall Sleeve, For
walls from 13 1/4" to 25 1/2" deep
Features
Constant room comfort monitoring
“Instant Heat” heat pump mode quickly
heats a room to the desired temperature for
increased comfort
Even heat monitoring checks room
temperature and automatically adds heat
boost if necessary
Room freeze protection- heat initiated if
temperature falls to 40°F in an unoccupied
room, raising temperature to 46°F
Dual motors for quiet operation
Durable, powder coat paint nish
Indoor coil frost sensor protects the
compressor to lengthen the life of the unit.
Random compressor restart protects
electrical systems from overload when
power is restored
Separate heat and cool range limits
Central desk control ready allowing hotel
owners to control units from a central
location
Condensate removal systems uses slinger
ring technology
Qty
Qty
Qty
PXSB23020 Electrical Subbase - 230V 15A and 20A Qty
PXSB23030 Electrical Subbase - 230V 30A Qty
PXSB26520 Electrical Subbase - 265V 20A Qty
PXSB26530 Electrical Subbase - 265V 30A Qty
RT7
RT7P
WRT2
EMRT2
EMWRT2
EMOCT
EMRAF
EMRHCF
PXFTB Replacement Filters (Set of 10) Qty
Wired Digital Thermostat
Wired Programmable Digital Thermostat
Wireless Programmable Digital Thermostat
Wired Thermostat with Occupancy Sensor
Wireless Thermostat with Occupancy Sensor
Online Connection Kit
Remote Access Fee
Energy Management Remote Humidity
Control Fee
Electronic defrost control ensures more run
time in the efcient heat pump mode
Fresh air damper control to bring in fresh
outside air when desired
Washable, antimicrobial air lter
Service error code memory storage
Emergency heat override
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
PTAC ZoneAire Select Series Submittal 2019
CHASSIS SPECIFICATIONS
PZE Series with Electric Heat
Model PZE07K3SB-A PZE09K3SB-A PZE09R3SB-A PZE12K3SB-A PZE12R3SB-A PZE15K5SB-A
PERFORMANCE DATA:
Cooling Btu 7200/6800 9600/9400 9200 12000/11800 12000 14500/14300
Cooling Watts 600/565 815/800 800 1050/1035 1130 1420/1400
Energy Efcient Ratio, EER 12.0 11.8/11.8 11.5 11.4/11.4 10.6 10.2/10.2
Heater Size (kW) 3.6 3.6 3.6 3.6 3.6 5.0
Moisture Removal (pints/hr.) 0.7 1.2 1.6 2.1 3.2 3.0
Sensible Heat Ratio 0.87 0.82 0.82 0.77 0.72 0.72
ELECTRICAL DATA:
Voltage(1 PHASE, 60 Hz) 230/208 230/208 265 230/208 265 230/208
Volt Range 253-187 253-187 292-239 253-187 292-239 253-187
Current (Amps) 2.6/2.7 3.5/3.8 4.2 4.5/5.0 5.92 6.2/6.7
Power Factor 0.99 0.99 0.99 0.96 0.99 0.99
Compressor LRA 13.0 20.0 18.2 28.5 25.9 34.5
Compressor RLA 2.5 3.3 3.0 5.3 4.3 6.4
Outdoor Fan Motor, HP 0.07 0.07 0.1 0.07 0.1 0.09
AIRFLOW DATA:
Indoor CFM, HIGH 335 400 400 470 470 470
Indoor CFM, LOW 250 250 290 360 360 360
Vent CFM 75 75 75 75 75 75
PHYSICAL DATA:
Sleeve Dimensions (H x W x D) 16” x 42” x 13 3/4” (ALL MODELS)
Dimensions with Front (H x W x D) 16” x 42” x 21 1/2” (ALL MODELS)
Cut Out Dimensions (H x W x D) 16 1/4”x 42 1/4” (ALL MODELS)
Net Weight (lbs.) 104 108 113 113 115 115
Shipping Weight (lbs.) 126 130 136 135 137 137
R-410A Charge (oz.) 30.0 32.1 31.4 30.7 30.0 34.2
Dimensions with Packaging (inches) 19” 3/4 x 43 1/2” x 23” (ALL MODELS)
PZH Series Heat Pump
Model PZH07K3SB-A PZH09K3SB-A PZH09R3SB PZH12K3SB-A PZH12R3SB-A PZH15K5SB-A
PERFORMANCE DATA:
Cooling Btu 7200/6800 9600/9400 9200 12000/11800 12000 14500/14300
Cooling Watts 600/565 815/800 800 1050/1035 1130 1420/1400
Energy Efcient Ratio, EER 12.0/12.0 11.8/11.8 11.5 11.4/11.4 10.6 10.2/10.2
Reverse Heating Btu 6400/6300 8500/8200 8500 11000/10800 11400 13600/13200
Heating Watts 530/520 710/685 710 930/920 1000 1180/1150
COP 3.55/3.54 3.51/3.51 3.51 3.47/3.44 3.34 3.38/3.36
Moisture Removal (pints/hr.) 0.7 1.2 1.6 2.1 3.2 3.0
Sensible Heat Ratio 0.87 0.82 0.82 0.77 0.72 0.72
ELECTRICAL DATA:
Voltage(1 PHASE, 60 Hz) 230/208 230/208 265 230/208 265 230/208
Volt Range 253-187 253-187 292-239 253-187 292-239 253-187
Current (Amps) 2.6/2.7 3.5/3.8 4.2 4.5/5.0 5.9 6.2/6.7
Reverse Heat. Amps 2.3/2.5 3.0/3.3 2.7 4.0/4.4 3.8 5.1/5.5
Power Factor 0.99 0.99 0.99 0.96 0.99 0.99
Compressor LRA 13.0 20.0 18.2 28.5 25.9 34.5
Compressor RLA 2.5 3.3 3.1 5.3 4.3 6.4
Outdoor Fan Motor, HP 0.07 0.07 0.1 0.07 0.1 0.09
AIRFLOW DATA:
Indoor CFM, HIGH 335 400 400 470 470 470
Indoor CFM, LOW 250 250 290 360 360 360
Vent CFM 75 75 75 75 75 75
PHYSICAL DATA:
Sleeve Dimensions (H x W x D)
Dimensions with Front (H x W x D)
Cut Out Dimensions (H x W x D)
Net Weight (lbs.) 105 109 113 114 115 116
Shipping Weight (lbs.) 127 131 136 136 137 139
R-410A Charge (oz.) 30.0 32.1 31.4 30.7 30.0 34.2
Dimensions with Packaging (inches) 19” 3/4 x 43 1/2” x 23” (ALL MODELS)
16” x 42” x 13 3/4” (ALL MODELS)
16” x 42” x 21 1/2” (ALL MODELS)
16 1/4”x 42 1/4” (ALL MODELS)
Operating range 0°-115°F.
Due to continuing research in new energy-saving technology, specifications are subject to change without notice.
Five-year warranty limited to installations in the United States, Puerto Rico, Mexico and Canada only.
See warranty documentation for full details.
Friedrich Air Conditioning Co. l 10001 Reunion Place, Suite 500 l San Antonio, TX 78216 l 877.599.5665
www.friedrich.com
RECEPTACLES AND FUSE TYPES
Voltage 230V 265V
Amps
Heater Size
20 30 20
3.6 kW 5.0 kW 3.6 kW
Receptacles
NEMA#
Receptacle
NEMA# Plug
6-20R 6-30R 7-2 0R
6-20P 6-30P 7-20 P
PTAC ZoneAire Select Series Submittal_2019_Rev.1