Table 4 - Electrical Data
Heat Pumps
Factory Voltage/Hz Voltage MCA
Circuit
/Ph Range
Breakers
Cktl Ckt2
OHS18KA 00 1 230/208-60-1 198-253 15.0 N/A
05 2 230/208-60-I 198-253 15.0 26.0
08 2 230/208-60-I 198-253 15.0 39.0
10 2 230/208-60-1 198-253 15.0 52.0
OHS24KA 00 1 230/208-60-I 198-253 19.9 N/A
05 2 230/208-60-I 198-253 19.9 26.0
08 2 230/208-60-I 198-253 19.9 39.0
10 2 230/208-60-1 198-253 19.9 52.0
OHS30KA 00 1 230/208-60-I 198-253 22.8 N/A
05 2 230/208-60-I 198-253 22.8 26.0
08 2 230/208-60-1 198-253 22.8 39.0
10 2 230/208-60-I 198-253 22.8 52.0
15 2 230/208-60-I 198-253 22.8 39.0
OHS36KA 00 1 230/208-60-I 198-253 27.9 N/A
05 2 230/208-60-1 198-253 27.9 26.0
08 2 230/208-60-I 198-253 27.9 39.0
10 2 230/208-60-I 198-253 27.9 52.0
15 2 230/208-60-1 198-253 27.9 39.0
OHS42KA 0O 1 230/208-60-1 198-253 31.8 N/A
10 2 230/208-60-I 198-253 31.8 52.0
15 2 230/208-60-I 198-253 31.8 39.0
OHS48KA 00 1 230/208-60-I 198-253 41.0 N/A
18 2 230/208-60-1 198-253 41.0 52.0
15 2 230/208-60-I 198-253 41.0 39.0
OHS60KA 00 1 230/208-60-I 198-253 48.0 N/A
15 2 230/208-60-I 198-253 48.0 39.0
MultipleCircuits SingleCircuit
HACR Wire Groung
HACR/ Max Wire Size GroungWire MCA / Max Size Wire
BreakerSize (field) Size (field) Breaker (field) Size
Size (field)
Ckt 1 Ckt2 Ckt 1 Ckt2 Ckt 1 Ckt 2 Ckt 1 C_ 1 Ckt 1 Ckt 1
20 N/A 12 N/A 12 N/A 15 20 10 12
20 30 12 10 12 10 39 40 8 10
20 40 12 8 12 10 52 60 6 10
20 60 12 6 12 10 65 70 4 8
30 N/A 10 N/A 10 N/A 19.9 30 10 10
30 30 10 10 10 10 41 40 8 10
30 40 10 8 10 10 54 60 6 10
30 60 10 6 10 10 67 70 4 8
40 N/A 8 N/A 10 N/A 22.8 40 8 10
40 30 8 10 10 10 51 60 6 10
40 40 8 8 10 10 64 70 4 8
40 60 8 6 10 10 77 80 4 8
40 40 8 8 10 10 81 90 4 8
40 N/A 8 N/A 10 N/A 27.9 40 8 10
40 30 8 10 10 10 54 60 6 10
40 40 8 8 10 10 67 70 4 8
40 60 8 6 10 10 80 80 4 8
40 40 8 8 10 10 81 90 4 8
50 N/A 6 N/A 10 N/A 31.8 50 6 10
50 60 6 6 10 10 84 90 4 8
50 40 6 8 10 10 81 90 4 8
60 N/A 6 N/A 10 N/A 41 60 6 10
60 60 6 6 10 10 88 90 4 8
60 40 6 8 10 10 81 90 4 8
60 N/A 6 N/A 10 N/A 48 60 6 10
60 40 6 8 10 10 88 110 2 6
1 Ifwire is appliedatambientgreaterthan30°C (86°F),consultTable310-16ofthe NEC(ANSI/NFPA70). Theampacityof nonmetallic-sheathedcable(NM),tradenameROMEX,
shallbe thatof 60°C (140°F)conductors,perthe NEC(ANSI/NFPA70)Article336-30. If otherthan uncoated(non-plated),60°Cor 750C(140°For 167°F)insulation,copperwire
(solidwireforI0 AWG andsmaller,strandedwirefor largerthan10AWG)is used,consultapplicabletablesof theNEC(ANSI/NFPA70).
Lengthshownis asmeasured1way alongthewire pathbetweenthe unitand theservicepanelfor voltagedrop notto exceed10V,consultthefactory forlongerwirelengthsif
needed.
3 Time-delayfuse,or HACRtypebreaker.
Table 5 - Unit Sizes and Available Electric Heat
Heating Available
Unit Size Cooling BTU/h at 47°F
BTUh KW
(Heat Pump Mode)
18 17,000 17,000 5,8,10
24 24,600 23,600 5,8,10
30 30,000 25,000 5,8,10,15
36 36,000 34,600 5,8,10,15
42 42,000 42,000 10,!5
48 48,000 48,000 10,!5
60 60,000 54,000 15,20"
Table 6 - Electric Heat Tables
240V-1 208V-1
KW Amps BTU/h Amps BTU/h
5.0 20.8 17,065 18.1 12,800
8.0 31.2 27,320 28.1 24,588
240V-1 208V-1
KW Amps BTU/h Amps BTU/h
10.0 41.6 34,130 36.2 25,600
15.0 62.4 51,200 54.1 38,400
20.0 83.4 68,200 72.4 51,200
*20 KW electric heat available on cooling-only model only; not available on heat pump.