This service manual is designed to be used in conjunction with the installation manuals provided with each air conditioning
system component.
This service manual was written to assist the professional RAC service technician to quickly and accurately diagnose and
repair malfunctions.
This manual will deal with subjects in a general nature. (i.e. All text will not pertain to all models).
Basepan
Condenser Fan Blade
Discharge Air
Outdoor Grille
Sleeve
IMPORTANT:It will be necessary for you to accurately identify the unit you are servicing, so
you can be certain of a proper diagnosis and repair. (See Unit Identification.)
The information contained in this manual is intended for use by a qualified service technician
who is familiar with the safety procedures required in installation and repair, and who is
equipped with the proper tools and test instruments.
Installation or repairs made by unqualified persons can result in hazards subjecting the
unqualified person making such repairs to the risk of injury or electrical shock which can
be serious or even fatal not only to them, but also to persons being served by the equipment.
If you install or perform service on equipment, you must assume responsibility for any
bodily injury or property damage which may result to you or others. Friedrich Air Conditioning
Company will not be responsible for any injury or property damage arising from improper
installation, service, and/or service procedures.
3
Page 4
UNIT IDENTIFICAUNIT IDENTIFICA
UNIT IDENTIFICA
UNIT IDENTIFICAUNIT IDENTIFICA
Model Number Code
SQ06J 1 0A
TIONTION
TION
TIONTION
1st Digit – Function
S = Straight Cool, Value Series
C = Straight Cool, Budget
Series
Y = Heat Pump
E = Electric Heat
K = Straight Cool, Challenger
Series
W = Thru-the Wall, WallMaster
Series
2nd Digit
C = Casement
P = PowerMiser "Portable"
Q = Q-Star
M = Medium Chassis
L = Large Chassis
W = Built -In
H = HazardGard
8th Digit – Engineering
Major change
7th Digit – Options
0 = Straight Cool & Heat Pump Models
1 = 1 KW Heat Strip, Normal
3 = 3 KW Heat Strip, Normal
4 = 4 KW Heat Strip, Normal
5 = 5 KW Heat Strip, Normal
8 = 8 KW Heat Strip, Normal
6th Digit – Voltage
1 = 115 Volts
2 = 230 Volts
3 = 230-208 Volts
5th Digit
Alphabetical Modifier
3rd and 4th Digit Approximate BTU/HR
(Cooling)
Heating BTU/Hr capacity listed in
the Specification/Performance
Data Section
RAC Serial Number Identification Guide
Serial Number
Decade Manufactured
L=0C=3F=6J=9
A=1D=4G=7
B=2E=5H=8
Year Manufactured
A=1D=4G=7K=0
B=2E=5H=8
C=3F=6J=9
Month Manufactured
A=Jan D=Apr G=JulK=Oct
B=Feb E=May H=Aug L=Nov
C=Mar F=Jun J=Sep M=Dec
LAGS 00001
Production Run Number
PRODUCT LINE
S=RAC
P=PTAC
E=EAC
V=VPAK
H=Split
4
Page 5
Room Air Conditioner Specifications ENERGY STAR® Compliant
✭Sleeve dimensions are listed on the following page.
✭✭These heat pumps have no supplemental electric and should not be operated below 37F.
As an ENERGY STAR partner, Friedrich Air Conditioning co. has determined that the selected ENERGY STA R (M) models meet the ENERGY STA R
requirements for energy efficiency.
Evaporator Air CFM300325425600
Exhaust Air CFMYesYesYesYes
Dehumidification Pts/Hr1.73.55.27.0
Width2515/16"2515/16"2515/16"28"
Height1515/16"1515/16"1715/16"203/16"
Depth273/8"273/8"273/8"335/8"
Minimum Ext. Into Room31/16"31/16"31/16"33/16"
Minimum Ext. to Outside1615/16"1615/16"1615/16"1815/16"
Net Weight113117166198
Shipping Weight124128153217
89001060014300
PERFORMANCEEVAPORATOR AIROPERATINGELECTRICALR-22COMP.
DATA*TEMP. °F.PRESSURESRATINGSREFRIG.OIL
CoolingDISCHARGETEMP.SUCTIONDISCHARGEAMPSLOCKEDCHARGE INCHARGE IN
AIRDROP °FROTOR AMPSOZ.FLUID OZ.
YS09J10-1
YS13J33-156.024.075.02806.029.030.011.8
YM18J34A-253.027.074.02778.742.054.030.0
YL24J35A-155.025.077.027212.061.069.032.0
* Rating Conditions:80°F Room Air Temperature and 50% Relative Humidity with
95°F Outside Air Temperature at 40% Relative Humidity.
Minimum Ext. Into Room7-1/2"7-1/2"7-1/2"7-1/2"7-1/2"
Minimum Ext. To Outside9/16"9/16"9/16"9/16"9/16"
Net Weight84921028694
Shipping Weight103111121107116
Watts35503550
29502950
BTUH1100011000
91009100
18
Page 19
PERFORMANCE
DATA*
Cooling
EVAPORATOR AIROPERATINGELECTRICALR-22COMP.
TEMP. °F.PRESSURESRATINGSREFRIG.OIL
DISCHARGETEMP.SUCTION DISCHARGE AMPSLOCKEDCHARGE IN CHARGE IN
AIRDROP °F.ROTOR AMPS OUNCESFLUID OZ.
WE09A33D58.022.0802954.520.02011.8
4.9
WE12A33D55.025.0762955.726.33611.8
6.3
WE13A33D47.132.9733086.333.03811.8
6.8
WY09A33D58.022.0802954.520.02611.8
4.8
WY12A33E55.025.0762955.826.34311.8
6.2
*Rating Conditions:80°F. Room Air Temperature and 50% Relative Humidity with
95°F. Outside Air Temperature at 40% Relative Humidity.
PERFORMANCEVOLTSBTUHCFMHEAT RISE
DATA (Heating)HIGH SPEED
WE09A33D2301100026039.0
2089100
WE12A33D2301100029035.0
2089100
WE13A33D2301100025040.0
2089100
19
Page 20
PERFORMANCE DATA*WY09A33D*WY12A33E
(Heating)
BTUH@70°F Inside 62°F Outside970012400
@70°F Inside 57°F Outside930012000
@70°F Inside 52°F Outside880011400
**@70°F Inside 47°F Outside8200/810010800/10400
@70°F Inside 42°F Outside760010000
@70°F Inside 37°F Outside68009000
@70°F Inside 35°F Outside11000/910011000/9100
Evaporator Air Temperature Rise
@70°F Inside 62°F Outside32.0037.60
@70°F Inside 57°F Outside30.7536.40
@70°F Inside 52°F Outside29.1034.50
**@70°F Inside 47°F Outside27.10/26.8032.70/31.50
@70°F Inside 42°F Outside25.1030.30
@70°F Inside 37°F Outside22.5027.30
@70°F Inside 35°F Outside36.40/30.1033.30/27.60
AMPS@70°F Inside 62°F Outside4.05.6
@70°F Inside 57°F Outside3.95.5
@70°F Inside 52°F Outside3.855.4
**@70°F Inside 47°F Outside3.8/4.15.3/5.6
@70°F Inside 42°F Outside3.65.1
@70°F Inside 37°F Outside3.44.8
@70°F Inside 35°F Outside16.0/14.716.0/14.7
Watts@70°F Inside 62°F Outside8801280
@70°F Inside 57°F Outside8701260
@70°F Inside 52°F Outside8601220
**@70°F Inside 47°F Outside835/8101175/1155
@70°F Inside 42°F Outside8001130
@70°F Inside 37°F Outside7601070
@70°F Inside 35°F Outside3550/29503550/2950
Suction/Head PSIG
@70°F Inside 62°F Outside66/31561/325
@70°F Inside 57°F Outside62/28559/290
@70°F Inside 52°F Outside57/28553/275
**@70°F Inside 47°F Outside53/26549/255
@70°F Inside 42°F Outside49/21545/240
@70°F Inside 37°F Outside45/20341/220
@70°F Inside 35°F Outside44/20040/215
* Heating Element comes on at 35°F outside ambient and compressor shuts off.
** AHAM Rating Conditions.
20
Page 21
Refrigeration SystemRefrigeration System
Refrigeration System
Refrigeration SystemRefrigeration System
Sequence of OperationSequence of Operation
Sequence of Operation
Sequence of OperationSequence of Operation
A good understanding of the basic operation of the refrigeration
system is essential for the service technician. Without this
understanding, accurate troubleshooting of refrigeration
system problems will be more difficult and time consuming, if
not (in some cases) entirely impossible. The refrigeration
system uses four basic principles (laws) in its operation they
are as follows:
1. "Heat always flows from a warmer body to a cooler body."
2. "Heat must be added to or removed from a substance
before a change in state can occur"
3. "Flow is always from a higher pressure area to a lower
pressure area."
4. "The temperature at which a liquid or gas changes state
is dependent upon the pressure."
The refrigeration cycle begins at the compressor. Starting
the compressor creates a low pressure in the suction line which
draws refrigerant gas (vapor) into the compressor. The
compressor then "compresses" this refrigerant, raising its
pressure and its (heat intensity) Temperature.
The refrigerant leaves the compressor through the discharge
line as a hot high pressure gas (vapor). The refrigerant enters
the condenser coil where it gives up some of its heat. The
condenser fan moving air across the coil's finned surface
facilitates the transfer of heat from the refrigerant to the
relatively cooler outdoor air.
When a sufficient quantity of heat has been removed from
the refrigerant gas (vapor), the refrigerant will "condense" (i.e.
change to a liquid). Once the refrigerant has been condensed
(changed) to a liquid it is cooled even further by the air that
continues to flow across the condenser coil.
The RAC design determines at exactly what point (in the
condenser) the change of state (i.e. gas to a liquid) takes
place. In all cases, however, the refrigerant must be totally
condensed (changed) to a liquid before leaving the condenser
coil.
The refrigerant leaves the condenser coil through the liquid line
as a warm high pressure liquid. It next will pass through the
refrigerant drier (if so equipped). It is the function of the drier to
trap any moisture present in the system, contaminants, and large
particulate matter.
The liquid refrigerant next enters the metering device. The metering
device is a capillary tube. The purpose of the metering device is to
"meter" (i.e. control or measure) the quantity of refrigerant entering
the evaporator coil.
In the case of the capillary tube this is accomplished (by design)
through size (and length) of device, and the pressure difference
present across the device.
Since the evaporator coil is under a lower pressure (due to the
suction created by the compressor) than the liquid line, the liquid
refrigerant leaves the metering device entering the evaporator coil.
As it enters the evaporator coil, the larger area and lower pressure
allows the refrigerant to expand and lower its temperature (heat
intensity). This expansion is often referred to as "boiling". Since
the unit's blower is moving Indoor air across the finned surface of
the evaporator coil, the expanding refrigerant absorbs some of
that heat. This results in a lowering of the indoor air temperature,
hence the "cooling" effect.
The expansion and absorbing of heat cause the liquid refrigerant
to evaporate (i.e. change to a gas). Once the refrigerant has
been evaporated (changed to a gas), it is heated even further by
the air that continues to flow across the evaporator coil.
The particular system design determines at exactly what point (in
the evaporator) the change of state (i.e. liquid to a gas) takes
place. In all cases, however, the refrigerant must be totally
evaporated (changed) to a gas before leaving the evaporator coil.
The low pressure (suction) created by the compressor causes the
refrigerant to leave the evaporator through the suction line as a
cool low pressure vapor. The refrigerant then returns to the
compressor, where the cycle is repeated.
* Optional 30 Amp Kit (618-869-00) is recommended in 208 Volt power supply areas that fall below 208 Volts.
For more information, call the Friedrich Service Department.
Due to a program of continuing improvement, specifications are subject to change without notice.
ablesables
ables
ablesables
Wire SizeUse ONLY wiring size recommended for
single outlet branch circuit.
Fuse/CircuitUse ONLY type and size fuse or HACR
Breakercircuit breaker indicated on unit's rating
plate. Propercurrent protection to the unit
is the responsibility of the owner.
GroundingUnit MUST be grounded from branch circuit
through service cord to unit, or through
separate ground wire provided on
permanently connected units. Be sure that
branch circuit or general purpose outlet is
grounded.
ReceptacleThe field supplied outlet must match plug on
service cord and be within reach of service
cord.
Do NOT alter the service cord or plug. Do
NOT use an extension cord. Refer to the
table above for proper receptacle and fuse
type.
INSTALLATION NOTES:
Supply Cord - All with right angle plug 6' on 115V; 5' on 230/208V.
Room air conditioners include accessories for window or thru-wall
installation. TwinTemp models include accessories for thru-wall
installation. Window mounting requires use of optional
accessory kit as listed below:
Electric shock hazard.Electric shock hazard.
Electric shock hazard.
Electric shock hazard.Electric shock hazard.
Turn off electric power before service or installation.
All electrical connections and wiring MUST be installed by a qualified
electrician and conform to the National Electrical Code and all local
codes which have jurisdiction.
Failure to do so can result in property damage, personal injury and/or
death.
FRIEDRICH AIR CONDITIONING COFRIEDRICH AIR CONDITIONING CO
FRIEDRICH AIR CONDITIONING CO
FRIEDRICH AIR CONDITIONING COFRIEDRICH AIR CONDITIONING CO
Post Office Box 1540 • San Antonio, Texas 78295-1540
4200 N. Pan Am Expressway • San Antonio, Texas 78218-5212
(210) 357-4400 • FAX (210) 357-4480
Visit us on the Internet at www.friedrich.com
22
..
.
..
The consumer - through the AHAM Room Air Conditioner
Certification Program - can be certain that the AHAM
Certification Seal accurately states the unit's cooling and
heating capacity rating, the amperes and the energy
efficiency ratio.
Page 23
COMPONENTS OPERATION
& TESTING
WARNING
DISCONNECT ELECTRICAL POWER TO
UNIT BEFORE SERVICING OR TESTING
COMPRESSORS
Compressors are single phase, 115 or 230/208 volt, depending
on the model unit. All compressor motors are permanent split
capacitor type using only a running capacitor across the start
and run terminal.
All compressors are internally spring mounted and externally
mounted on rubber isolators.
WINDING TEST
Remove compressor terminal box cover and disconnect wires
from terminals. Using an ohmmeter, check continuity across
the following: (See Figure 1)
GROUND TEST
Use an ohmmeter set on its highest scale. Touch one lead to
the compressor body (clean point of contact as a good connection is a must) and the other probe in turn to each compressor terminal (see Figure 2.) If a reading is obtained, the
compressor is grounded and must be replaced.
Figure 2
Typical Ground Test
1. Terminal "C" and "S" - no continuity - open winding replace compressor.
2. Terminal "C" and "R" - no continuity - open winding replace compressor.
3. Terminal "R" and "S" - no continuity - open winding replace compressor.
Figure 1
Compressor Winding Test
CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefficiency is normally due to
broken or damaged suction and/or discharge valves, reducing
the ability of the compressor to pump refrigerant gas.
This condition can be checked as follows:
1. Install a piercing valve on the suction and discharge or
liquid process tube.
2. Attach gauges to the high and low sides of the system.
3. Start the system and run a “cooling or heating
performance test.”
If test shows:
A. Below normal high side pressure.
B. Above normal low side pressure.
C. Low temperature difference across coil.
The compressor valves are faulty - replace the
compressor.
THERMAL OVERLOAD (External)
Some compressors are equipped with an external overload
which is located in the compressor terminal box adjacent to
the compressor body (See Figure 3.)
23
Page 24
The overload is wired in series with the common motor
terminal. The overload senses both major amperage and
compressor temperature. High motor temperature or
amperage heats the disc causing it to open and break the
circuit to the common motor terminal.
CHECKING THE INTERNAL OVERLOAD
(See Figure 4)
Figure 4
Internal Overload
Figure 3
Heat generated within the compressor shell is usually due to:
1. High amperage.
2. Low refrigerant charge.
3. Frequent recycling.
External Overload
1.With no power to unit, remove the leads from the compressor terminals.
2.Using an ohmmeter, test continuity between terminals
C-S and C-R. If not continuous, the compressor overload is open and the compressor must be replaced.
4. Dirty condenser.
TERMINAL OVERLOAD - TEST
(Compressor - External Type)
1. Remove overload.
2. Allow time for overload to reset before attempting to
test.
3. Apply ohmmeter probes to terminals on overload wires.
There should be continuity through the overload.
TERMINAL OVERLOAD (Internal)
Some model compressors are equipped with an internal
overload. The overload is embedded in the motor windings to
sense the winding temperature and/or current draw. The
overload is connected in series with the common motor
terminal.
Should the internal temperature and/or current draw become
excessive, the contacts in the overload will open, turning off
the compressor. The overload will automatically reset, but may
require several hours before the heat is dissipated.
FAN MOTOR
A single phase permanent split capacitor motor is used
to drive the evaporator blower and condenser fan. A
self-resetting overload is located inside the motor to
protect against high temperature and high amperage
conditions. (See Figure 5)
24
Page 25
Figure 5
FAN MOTOR - TEST
1.Determine that capacitor is serviceable.
Fan Motor
Figure 6
System Control
Panel
(SQ Models Only)
SYSTEM CONTROL SWITCH (SQ Models)
(See Figure 6)
2.Disconnect fan motor wires from fan speed switch or
system switch.
3.Apply "live" test cord probes on black wire and common
terminal of capacitor. Motor should run at high speed.
4.Apply "live" test cord probes on red wire and common
terminal of capacitor. Motor should run at low speed.
5.Apply "live" test cord probes on each of the remaining
wires from the speed switch or system switch to test
intermediate speeds. If the control is in the
"MoneySaver" mode and the thermostat calls for
cooling, the fan will start - then stop after approximately
2 minutes; then the fan and compressor will start
together approximately 2 minutes later.
Figure 7
SYSTEM SWITCH
(SQ Only)
A five-position control switch is used to regulate the operation
of the fan motor and compressor. The compressor can be
operated with the fan operating at low, medium or high speed.
The fan motor can also be operated independently on medium
speed. See switch section as indicated on the decorative
control panel.
SYSTEM CONTROL SWITCH - TEST (See Figure 7)
Disconnect the leads from the control switch. There must be
continuity as follows:
1. "Off" Position - no continuity between terminals.
2. "Lo Cool" Position - between terminals "L1" and "C", "Lo"
and MS".
3. "Med Cool" Position - between terminals "L1" and "C",
"M" and "MS".
4. "Hi Cool" Position - between terminals L1" and "C", "H"
and "MS".
5. "Fan Only" Position - between terminals "L1" and "2".
RESISTOR
(Heat Anticipator) (SQ Only)
Failure of the resistor will cause prolonged "off" and "on" cycles
of the unit. When replacing a resistor, be sure and use the
exact replacement. Resistor rating 115 Volts 12500 ohm, 1.05
watts.
25
Page 26
Figure 8
ROCKER SWITCH
1. "Off" - Turns everything off.
2. "Hi Fan" - Maximum circulation of filtered room
air (no cooling.)
3. "Low Fan" - Fan runs slower for less circulation
of filtered room air.
4. "Low Cool" - Fan runs slowly for quiet operation
when maximum cooling is not needed.
5. "Hi Cool" - Highest fan speed for maximum cooling.
MONEYSAVER® SWITCH
(Rocker Switch) (See Figure 8)
This rocker switch can be depressed to either YES or NO. In
the YES position you will get the most economical operation.
Both the fan and the compressor will cycle on and off together,
maintaining the selected temperature at a more constant level
and reducing the humidity more efficiently. This control will
only operate when the unit is in a cooling mode. In the NO
position, the fan will run constantly as long as the unit is in the
cooling mode. Disconnect leads from switch. Depress switch
to function being tested.
1. When YES is depressed, there should be continuity
between terminals "1" and "2."
2. When NO is depressed, there should be continuity
between terminals "2" and "3."
SYSTEM CONTROL SWITCH
("KQ" Models Only) (See Figure 9)
The KQ Model unit uses a five position control switch to regulate the operation of the unit. Function of each position (clockwise rotation) is as follows:
Figure 10
SYSTEM CONTROL SWITCH - TEST
(See Figure 19)
Turn knob to phase of switch to be tested. There must be
continuity as follows:
System Control Switch
("KQ" Models Only)
Figure 9
26
System Control Panel
("KQ" Models Only)
1. "Hi Fan" Position - between terminals "L1" and "H".
2. "Low Fan" Position - between terminals "L1" and "L".
3. "Low Cool" Position - between terminals "L1" and "L" and
"C".
4. "Hi Cool" Position - between terminals "L1" and "H" and
"C".
Page 27
SYSTEM CONTROL SWITCH
("YQ" Model Only) (See Figure 11)
The YQ Model unit uses a six position control switch to regulate
the operation of the unit (see Figure 9). Function of each
position (Clockwise rotation) is as follows:
Figure 12
System Control Switch
("YQ" Models Only)
Figure 11
SYSTEM CONTROL PANEL
("YQ" Model Only)
1. "Off" - Turns everything off.
2. "Fan Only" - To circulate filtered room air, but no cooling
or heating.
3. "Hi Cool" - Fan runs continuously, compressor goes on
and off to maintain the selected room temperature.
5. "Hi Heat" Position - between terminals "C" and "1", and
"C" and "4".
ROTARY (SYSTEM) SWITCH ("SC" Model) (See Figure 13)
A rotary four position switch is used to turn on the unit and
select the operation desired. Switch selection is as follows:
Figure 13
SYSTEM CONTROL PANEL
("SC" Model Only)
4. "Lo Cool" - Fan runs continuously, compressor goes on
and off to maintain the selected room temperature.
5. "Lo Heat" - Fan Runs continuously, heating turns on and
off to maintain the selected room temperature.
6. "Hi Heat" - Fan Runs continuously, heating turns on and
off to maintain the selected room temperature.
SYSTEM CONTROL SWITCH - TEST (See Figure 12)
Turn knob to phase of switch to be tested. There must be
continuity as follows:
1. "Fan Only" Position - between terminals "C" and "1".
2. "Hi Cool" Position - between terminals "C" and "1", "C"
and "3".
3. "Lo Cool" Position - between terminals "C" and "2", and
"C" and "3".
4. "Lo Heat" Position - between terminals "C" and "2", and
"C" and "4".
1."Hi Cool" Turns on the compressor and fan at high
speed
2."Lo Cool" Turns on the compressor and fan at low
speed.
3."Fan Only" Turns on the fan at high speed.
4."Off"Turns everything off.
The switching arrangement of the control is as follows: (See
Figure 14.)
1."Off"All contacts open.
2."Hi Fan
Contacts closed between terminals "L1" and
"1".
27
Page 28
3. "Hi Cool" Contacts closed between terminals "L1" to "1"
and "L1" and "C".
4. "Lo-Cool" Contacts are closed between terminals "L1" to
"2" and "L1 to "C".
Figure 15
System Control Panel
WS Models
Figure 14
1. Disconnect leads from control switch.
2. Check continuity between all switch positions shown in
Figure 14.
SYSTEM CONTROL SWITCH
("WS" Models) (See Figure 15)
A five position control switch is used to regulate the operation
of the fan motor and compressor. The compressor can be
operated with the fan operating at low, medium or high speed.
The fan motor can also be operated independently on medium
speed. See switch section as indicated on decorative control
panel
SYSTEM CONTROL SWITCH
(SC Model Only)
Figure 16
System Control
Switch
WS Models
SYSTEM CONTROL SWITCH
("WE" & "WY" Models) (See Figure 17)
An eight position switch is used to regulate the operation of
the fan motor, compressor and electric heater. The unit can
be operated in cooling or heating mode with the compressor
or electric heater on and the fan motor operating on low,
medium or high speed.
SYSTEM CONTROL SWITCH - TEST
Disconnect leads from control switch (See Figure 16.)
There must be continuity as follows:
1. "Off" Position - no continuity between terminals.
2. "Lo Cool" Position - between terminals "L1" and "C", "LO"
and "MS."
3. "Med Cool" Position - between terminals "L1" and "C",
"M" and "MS".
4. "Hi Cool" Position - between terminals "L1" and C", "H"
and "MS."
5. "Fan Only" Position - between terminals "L1" and "2."
28
The fan motor can also be operated independently on medium
speed. See switch section as indicated on decorative control
panel.
Figure 17
System Control Panel
WE & WY Models
Page 29
SYSTEM CONTROL SWITCH - TEST (See Figure 18)
Disconnect leads from control switch. Turn control to position
being tested. There must be continuity as follows:
1. "Off" Position-no continuity between terminals.
2. "Lo Cool" Position-between terminals "C" and "3", "C2"
and "2", "LO" and "M/S", "AR" and "5".
3. "Med Cool" Position-between terminals "C" and "3",
"C2" and "2", "M" and "M/S", "AR" and "5".
4. "Hi Cool" Position-between terminals "C" and "3", "C2"
and "2", "H" and "M/S", "AR" and "5".
5. "Hi Heat" Position-between terminals "C" and "1", "C2"
and "4", "H" and "M/S", "AR" and "5".
6. "Med Heat" Position-between terminals "C" and "1",
"C2" and "4", "M" and "M/S", "AR" and "5".
7. "Lo Cool" Position-between terminals "C" and "1", "C2"
and "4", "LO" and "M/S", "AR" and "5".
2. "Lo Cool" Position - between terminals "L1" and "C," "LO"
and "MS."
3. "Med Cool" Position - between terminals "L1" and "C,"
"M" and "MS."
4. "Hi Cool" Position - between terminals "L1" and "C," "H"and
"MS."
5. "Fan Only" Position - between terminals "L1" and "2."
Figure 19
System Control Panel -
Used by all Small, Medium and Large
chassis units (KS, SS, KM, SM, KL, SL)
8. "Fan Only" Position-between terminals "L1" and "M".
Figure 18
System Control Switch (WE & WY Models)
(Heat Pump & Electric Heat Models)
SYSTEM CONTROL SWITCH KS, SS, KM, SM, KL, SL
Models (See Figure 19)
A five position control switch is used to regulate the operation
of the fan motor and compressor. The compressor can be
operated with the fan operating at low, medium or high speed.
The fan motor can also be operated independently on medium
speed. See switch section as indicated on decorative control
panel.
Figure 20
System Control Switch
SYSTEM CONTROL SWITCH - TEST (See Figure 20)
Disconnect leads from control switch.
There must be continuity as follows:
1. "Off" Position - no continuity between terminals.
29
Page 30
SYSTEM CONTROL SWITCH (See Figure 21)
A six-position control switch is used to regulate the operation
of the fan motor and compressor. The compressor can be
operated with the fan operating at low, medium or high speed.
The fan motor can also be operated independently on
medium speed. See switch section as indicated on decorative
control panel.
Figure 23
System Control Switch
Figure 21
System Control Panel
Used on Deluxe Series (RS & RM)
SYSTEM CONTROL SWITCH (See Figure 23)
(Heat Pump & Electric Heat Models)
An eight position control switch is used to regulate the
operation of the fan motor and compressor. The compressor
can be operated with the fan operating at low, medium or high
speed in the cooling or heating mode. The fan motor can also
be operated independently on medium speed. See switch
section as indicated on decorative control panel.
1. "Off" Position - everything is off.
2. "Lo Cool" Position - fan operates on low speed,
compressor is on.
3. "Med Cool" Position - fan operates on medium speed,
compressor is on.
SYSTEM CONTROL SWITCH - TEST
Disconnect leads from control switch (See Figure 22.)
There must be continuity as follows:
Figure 22
4. "Hi Cool" Position - fan operates on high speed,
compressor is on.
5. "Hi Heat" Position - fan operates on high speed,
compressor or electric heater is on.
6. "Med Heat" Position - fan operates on medium speed,
compressor or electric heater is on.
30
Page 31
SYSTEM CONTROL SWITCH (See Figure 24)
(Heat Pump & Electric Heat Models)
7. "Lo Heat" Position - fan operates on low speed,
compressor or electric heater is on.
An eight position control switch is used to regulate the
operation of the fan motor and compressor. The compressor
can be operated with the fan operating at low, medium or high
speed in the cooling or heating mode. The fan motor can also
be operated independently on medium speed. See switch
section as indicated on decorative control panel.
1. "Off" Position - everything is off.
2. "Lo Cool" Position - fan operates on low speed,
compressor is on.
3. "Med Cool" Position - fan operates on medium speed,
compressor is on.
4. "Hi Cool" Position - fan operates on high speed,
compressor is on.
5. "Hi Heat" Position - fan operates on high speed,
compressor or electric heater is on.
6. "Med Heat" Position - fan operates on medium speed,
compressor or electric heater is on.
8. "Fan Only" Position - operates on medium speed.
NOTE: Heat pump models with electric heat - in the heat
position, heating element only will be energized when
outdoor temperature is below the operating range of
the heat pump.
Figure 25
SYSTEM CONTROL SWITCH - TEST (See Figure 25)
SYSTEM CONTROL SWITCH
(Heat Pump & Electric Heat Models)
Figure 24
SYSTEM CONTROL PANEL
(Heat Pump & Electric Heat Models)
All Small, Medium, & Large Chassis units.
(YS, ES, YM, EM, YL AND EL)
Disconnect leads from control switch. Turn control to position
being tested. There must be continuity as follows:
1. "Off" Position - no continuity between terminals.
2. "Lo Cool" Position - between terminals "C" and "3", "C2"
and "2", "LO" and "M/S", "AR" and "5".
3. "Med Cool" Position - between terminals "C" and "3", "C2"
and "2", "M" and "M/S", "AR" and "5".
4. "Hi Cool" Position - between terminals "C" and "3", "C2"
and "2", "H" and "M/S", "AR" and "5".
5. "Hi Heat" Position - between terminals "C" and "1", "C2"
and "4", "H" and "M/S", "AR" and "5".
6. "Med Heat" Position - between terminals "C" and "1", "C2"
and "4", "M" and "M/S", "AR" and "5".
7. "Lo Cool" Position - between terminals "C" and "1", "C2"
and "4", "LO" and "M/S", "AR" and "5".
8. "Fan Only" Position - between terminals "L1" and "M".
31
Page 32
Smart Center Electronic Control Center:
(See Figure 26)
FILTER ALERT light will come on after 250 hours of use. Touch
FILTER ALERT to reset.
TO ADJUST TEMPERATURE
COOLER - Touch COOLER to see setting, touch again to
change.
TO SET MODE OF OPERATION
When unit is first turned on, it will be in the COOL mode (light
on), with constant fan.
Touch MONEYSAVER (light on) to activate the MoneySaver
feature. (MoneySaver is a feature that cycles the fan with the
compressor so that the fan does not run all the time. This
saves energy and improves dehumidification.) If customer
prefers a constant fan for more air movement, touch
MONEYSAVER again and unit will return to constant fan.
Touch FAN ONLY (light on) and only the fan will run. This
feature may be used in conjunction with the FRESH AIR/EXHAUST lever to bring outside air into a room, or to exhaust
stale air.
ELECTRONIC CONTROLFigure 26
WARMER - Touch WARMER to see setting, touch again to
change.
Touch °F/°C to show desired temperature in Fahrenheit or
Celsius.
TO ADJUST FAN SPEED
Touch SPEED to see current setting. Touch again to change
speed. F1 is lowest setting (sleep setting), F2 is LOW, F3 is
MED, and F4 is HIGH.
TO ACTIVATE SMART FAN
Touch SMART FAN (light on). Smart Fan will adjust the fan
speed automatically to maintain the desired comfort level. For
example, if the outside doors in the home are open for an
extended period of time, or more people enter a room, Smart
Fan may adjust to a higher fan speed to compensate for the
increased heat load. This keeps from having to adjust the fan
speed on your own, or from having to change the desired
temperature you have selected. Smart Fan will also run to
test temperature if the off cycle is long.
TO SET HOUR CLOCK
Touch SET HOUR CLOCK to see setting. To change, touch
and hold until hour closest to the actual time appears in the
display. MAKE SURE A.M. AND P.M. ARE SET PROPERLY.
(Minutes will NOT show on display.)
TO SET THE TIMER
NOTE: SET HOUR CLOCK before attempting to set timer
functions.
The TIMER ON/OFF times can be set a minimum of one
hour apart and a maximum of twenty-three hours apart.
STOP TIME - Touch A/C STOP and hold until the hour the
unit needs to shut off appears in the display A.M. or P.M.)
START TIME - Touch A/C START and hold until the hour the
unit needs to come on appears in the display (A.M. or P.M.)
Touch TIMER ON (light on) to activate the timer function. TouchTIMER OFF (light off) to cancel the timer function desired.
Once the on and off times have been selected, they will remain
in memory, and cycle daily until changed, or until the unit is
subject to a power interruption.
32
Page 33
TESTING THE ELECTRONIC CONTROL
2001 XQ BOARDS & QME BOARDS
Checking Room Temperature:
1. Check the room temperature at the electronic control pad
by pressing the "FAN SPEED" button and the temperature"UP" button at the same time on XQ models.
2. Check the room temperature at the electronic control pad
by pressing at the same time the "FAN SPEED" button
and the "WARMER" button on QME models.
The indoor temperature will display for 10 seconds. Indoor
temperature can be viewed in all modes, including the TEST
mode. The display can be changed back to SET
temperature by pressing any key, except the ON/OFF
button, or after 10 seconds has elapsed.
Activating Test Mode: Activate test mode by pressing at the
same time the "MODE" button and the temperature
"DOWN" button on XQ models. LEDs for Hour, Start, and
Stop will blink 1 bps while Test Mode is active.
Activate test mode by pressing at the same time the
"MONEY SAVER" button and the "FILTER ALERT" button
on QME models. LED for the Filter Alert will blink 1 bps
while Test Mode is active.
Test Mode has duration of 90 minutes. Test Mode can be
activated under any conditions, including Off. Test Mode is
cancelled by pressing the On/Off button, unplugging the
unit, or when the 90 minutes is timed out. All settings revert
to the factory default settings of Cool, 75 degrees F, Timer
and Set Hour features are nonfunctional.
Test Mode overrides the three-minute lockout, all delays
for compressor and fan motor start / speed change, and no
delay when switching modes.
Test Mode default settings are ON, Money Saver, 60 degrees F,
and High fan speed
.
Activating Error Code Mode: (Submode of Test Mode) Unit
has to be in Test Mode to enter Error Code Mode
1. Activate Error Code Mode by pressing the "TIMER ON/OFF" button on XQ models. LED for the "TIMER ON/OFF"
will flash 1 bps while Error Code Mode is active. Pressing
the "TEMP/HR + " button will display 00. Consecutive
presses will scroll through all error codes logged. Press
the "TEMP/HR - " button to see the reverse order of all
error codes logged. When the end of logged error codes is
reached the temperature set point will appear.
Activate Error Code Mode by pressing at the same time
the "A/C START" button and the "ON/OFF" button on QME
models. LED for the "TIMER ON/OFF" will flash 1 bps while
Error Code Mode is active. Pressing the "WARMER" button
will display 00. Consecutive presses will scroll through all
error codes logged. Press the "COOLER" button to see
the reverse order of all error codes logged. When the end
of logged error codes is reached the temperature set point
will appear.
IMPORTANT
Error Codes are cleared from the log by exiting from
Error Code Mode. To exit on XQ models, press Timer
On/Off button. To exit QME models, press A/C Start
and On/Off buttons. Or unplug unit to exit Error Code
Mode. Plug unit in after 5 seconds to resume normal
operation of unit.
TESTING THE ELECTRONIC CONTROL
ERROR CODE LISTINGS
E1 SHORT CYCLE SITUATION: Defined as (compressor
powered on before the three minute time delay ten times in
one hour. Investigate and correct short cycling problem.
E2 KEYBOARD STUCK ERROR: If key button(s) are pressed
continuously for twenty seconds or more. If MODE key is stuck,
unit will default to cool. Exit Error Code Mode to see if error
"E2" is no longer displayed and unit is functioning. Replace
board if "E2" still displays after exiting Error Code Mode.
E3 FROST PROBE OPEN: Normal operation is allowed. Ohm
frost probe. Replace probe if ohm value not read. If ohm value
present replace board.
E4 FROST PROBE SHORT: Normal operation allowed.
Replace probe.
E5 INDOOR PROBE OPEN: Control assumes indoor ambient
temperature is 90 degree F and unit will operate. Ohm indoor
probe. Replace probe if ohm value not read.
E6 INDOOR PROBE SHORT: Control assumes ambient
temperature is 90 degree F and unit will operate. Replace
probe.
NOTE: All Error Code displays for Frost & Indoor Probe will
allow unit to operate. Unit may or will ice up if faulty components
not replaced.
FROST PROBE SENSOR: disables compressor at 35
degrees F.
INDOOR PROBE SENSOR: Control range is 60 degrees F
to 90 degrees F +/- 2 degrees F.
Indoor temperature will be displayed by pressing:
(QME Units) The Fan Speed button and the Warmer button.
( XQ Units) The Fan Speed button and the Temp Up button.
The indoor temperature will be displayed for 10 seconds. The
display will change back to the Set Point temperature by
pressing any key button except for the On/Off button. The
indoor temperature can be viewed in all modes, including test
mode.
Filter Alert: The Filter Alert indicator turns on after the fan
motor has been operating for 250 hours. The Filter Alert
indicator is reset by pressing the Filter Alert button one time
only,. Power failures will not reset the 250 hour timer. All time
elapsed is stored in memory and resumes counting after power
is restored.
Keep Alive: The electronic control has a memory to retain all
functions and status as set up by the user in the event of a
power failure. Once power is restored to the unit there is a
two second delay before the fan comes on and approximately
three minutes delay before the compressor is activated,
33
Page 34
providing that the mode was set for cooling and the set
point temperature has not been met in the room.
TEST:
1. Remove leads from thermostat.
THERMOSTAT ("SQ & KQ" Models) - See Figure 27.
Thermostat is used to cycle the compressor on and off at the
comfort level desired. The thermostat has a range from 60°
±2°F to 90° ±4°F, with a differential of 5°F. Turning the knob
clockwise lowers the indoor room temperature setting, while
turning the knob counter clockwise raises the indoor
temperature.
TEST:
Remove wires, turn thermostat to its coldest position. Check
for continuity between the two terminals. Turn thermostat to
warmest position, check continuity to see if contacts open.
NOTE: Temperature must be in range listed to check
thermostat.
Figure 27
2. Turn thermostat knob clockwise to its coldest position.
3. Test for continuity between the two terminals. Contacts
should be closed.
4. Turn thermostat knob counterclockwise to its warmest
position.
5. Test for continuity - contacts should be open.
NOTE: The thermostat must be within the temperature
range listed to open and close.
Figure 29
To maintain the comfort level desired, a cross ambient type
thermostat is used. The thermostat has a range from 65° ±2°F
to 87° ±3°F. The thermostat bulb is positioned in front of the
evaporator coil to sense the return air temperature. Thermostat malfunction or erratic operation is covered in the troubleshooting section of this manual.
THERMOSTAT (SC Model Only)
THERMOSTAT ("YQ" Model Only)
See Figure 28.
This thermostat is single pole-double throw, cross ambient
with a range of 60° to 92°F and a differential of ±2°F. Terminal
"2" is common.
Figure 28
34
THERMOSTAT ("YQ" Models Only)
TEST:
1. Remove leads from thermostat.
2. Turn thermostat knob clockwise to its coldest position.
3. Test for continuity between the two terminals. Contacts
should be closed.
4. Turn thermostat knob counterclockwise to its warmest
position.
5. Test for continuity - contacts should be open.
NOTE: The thermostat must be within the temperature
range listed to open and close.
Page 35
THERMOSTAT - Models ES, YS, EM, YM, EL, YL
(See Figure 29)
A cross ambient thermostat is used on all heat pump and
electric heat units. In addition to cycling the unit in a heating
or cooling operation, the thermostat will terminate the cooling
cycle in the event ice forms on the evaporator coil, in this
case the thermostat functions as a de-ice control. A resistor
(anticipator) is positioned within a plastic block to supply a
small amount of heat to the bulb area to prevent long "off
cycles" in the "Cool-Fan Auto" (MoneySaver) position (see
Figure 8.) A current feedback through the fan motor windings
during "off cycle" completes the circuit to the resistor.
In the heating cycle, the heat anticipator is energized to supply
a small amount of heat during the "on" cycle. This will open
the contacts in the thermostat prematurely to maintain a closer
differential between the "cut in" and "cut out" temperature.
The heat anticipator is energized in the heating mode
regardless of whether fan is placed in the automatic
(MoneySaver) or constant run position.
RANGE:Cooling Model Thermostat
60°F (±2°) to 92°F (±4°),
Figure 30
Figure 31
THERMOSTAT BULB LOCATION
("SQ" Models Only)
Thermostat sensor holder 020 and
anticipator (4712D-140) to be positioned
between the 4th and 5th and 6th and 7th
rows of tubes from the
bottom of the coil at
dimension shown
THERMOSTAT BULB LOCATION
("KQ", "YQ" and "SC" Models Only)
Thermostat sensor holder 020 to be
positioned between the 4th and 5th and
6th and 7th rows of tubes from the bottom
of the coil at dimension shown
TEST:
Cooling/Heating Models: Remove wires from thermostat
and check continuity between terminal "2" (common) and "3"
for cooling. Check between terminals "2" (common) and "1"
for heating. Also check that contacts in thermostat open after
placing in either position. NOTE: Temperature must be within
range listed to check thermostat. Refer to the troubleshooting
section in this manual for additional information on thermostat
testing.
THERMOSTAT ADJUSTMENT
No attempt should be made to adjust thermostat. Due to the
sensitivity of the internal mechanism and the sophisticated
equipment required to check the calibration, it is suggested
that the thermostat be replaced rather than calibrated.
Thermostat bulb must be straight to insure proper
performance.
THERMOSTAT BULB LOCATION
The position of the bulb is important in order for the thermostat
to function properly. The bulb of the thermostat should be
located approximately 45° to a maximum of 60° from
horizontal. Also, do not allow the thermostat bulb to touch
the evaporator coil. (See Figures 30 and 31.)
DEFROST THERMOSTAT
(Heat Pump Models Only)
(See Figure 32)
This thermostat is single pole - double throw with contacts
between terminals "2" and "3" closing on temperature rise
and contacts between terminals "2" and "1" closing on
temperature fall. When the contacts between terminals "2"
and "1" make, power is supplied to the heater element.
This control is dual purpose control that acts as an outdoor
thermostat and defrost control.
When the sensing bulb, attached to the condenser coil, senses
enough icing on the outdoor coil, it will interrupt power to the
compressor and supply power to the heating element until
the coil temperature reaches above 43°, then the heater will
shut off and the unit will resume operating in the reverse cycle
mode.
When the outdoor coil temperature drops below 20°, the unit
will operate in electric heat mode continuously until the outdoor
coil temperature rises above 43°.
The fan motor will not turn off when defrost occurs, and the 4way valve will not reverse.
35
Page 36
Figure 32
DEFROST THERMOSTAT
(Heat Pump Models)
RESISTOR (Heat Anticipator) (See Figure 34)
Failure of the resistor will cause prolonged "off" and "on" cycles
of the unit. When replacing a resistor, be sure and use the
exact replacement. Resistor ratings are as follows:
115 Volt - 5,000 ohms 3 watt
230 Volt - 20,000 ohms 3 watt
DEFROST BULB LOCATION
(Heat Pump Models Only)
(See Figure 33)
The defrost control bulb must be mounted securely and in the
correct location to operate properly.
Figure 33
DEFROST THERMOSTAT BULB
LOCATION (All Heat Pump Models)
(See Figure 32)
Figure 34
RESISTOR
CAPACITOR, RUN (See Figure 35)
A run capacitor is wired across the auxiliary and main winding
of a single phase permanent split capacitor motor such as the
compressor and fan motor. A single capacitor can be used
for each motor or a dual rated capacitor can be used for both.
Slide the bulb
end of the
thermostat
defrost under
the retainer as
shown
Retainer
The capacitor's primary function is to reduce the line current
while greatly improving the torque characteristics of a motor.
The capacitor also reduces the line current to the motor by
improving the power factor of the load. The line side of the
capacitor is marked with a red dot and is wired to the line side
of the circuit.
CAPACITOR - TEST
1. Remove capacitor from unit.
2. Check for visual damage such as bulges, cracks, or leaks.
36
Page 37
Figure 35
CAPACITOR HOOK-UP
3. For dual rated, apply an ohmmeter lead to common (C)
terminal and the other probe to the compressor (HERM)
terminal. A satisfactory capacitor will cause a deflection
on the pointer, then gradually move back to infinity.
4. Reverse the leads of the probe and momentarily touch
the capacitor terminals. The deflection of the pointer
should be two times that of the first check if the capacitor
is good.
5. Repeat steps 3 and 4 to check fan motor capacitor.
DUAL RATED RUN
NOTE: The slide (check) inside the valve is made of
teflon. Should it become necessary to replace the
check valve, place a wet cloth around the valve
to prevent overheating during the brazing
operation.
CHECK VALVE OPERATION
In the cooling mode of operation, high pressure liquid enters
the check valve forcing the slide to close the opposite port
(liquid line) to the indoor coil. Refer to refrigerant flow chart.
This directs the refrigerant through the filter drier and cooling
capillary tube to the indoor coil.
In the heating mode of operation, high pressure refrigerant
enters the check valve from the opposite direction, closing
the port (liquid line) to the outdoor coil. The flow path of the
refrigerant is then through the filter drier and heating capillary
to the outdoor coil.
Failure of the slide in the check valve to seat properly in either
mode of operation will cause flooding of the cooling coil. This
is due to the refrigerant bypassing the heating or cooling
capillary tube and entering the liquid line.
HEAT PUMPS: REVERSING VALVE
(See Figure 37)
NOTE: A shorted capacitor will indicate a low resistance
and the pointer will move to the "0" end of the
scale and remain there as long as the probes are
connected.
An open capacitor will show no movement of the
pointer when placed across the terminals of the
capacitor.
CHECK VALVE
(See Figure 36)
A unique two-way check valve is used on the reverse cycle
heat pumps. It is pressure operated and used to direct the
flow of refrigerant through a single filter drier and to the proper
capillary tube during either the heating or cooling cycle
Figure36
ONE-WAY CHECK VALVE
Heat Pump Models)
A reversing valve is used to change the refrigerant flow within
the system to permit heating or cooling.
The reversing valve consists of a main valve body which
houses the slide and piston, plus a pilot valve which is activated
by a solenoid.
There are three tubes connected to one side of the main valve
body and one tube on the opposite side. The single tube is
connected to the compressor discharge line. The center tube
on the opposite side is the common suction line to the
compressor. The outside tubes are connected to the indoor
and outdoor coils.
The pivot valve is responsible for directing the refrigerant flow
to the indoor or outdoor coil. There are three small tubes
connected to the pilot valve body. The center pilot tube is the
common pilot tube and is connected to the center suction line.
The outside tubes are connected to each end of the main
valve body. The pilot valve consists of a needle valve and
spring.
When the solenoid is de-energized, the spring tension closes
one pilot port while the other remains open. When the solenoid
is energized, the opposite end is closed. The piston in the
main valve is pressure operated and will always travel in the
direction of the open pilot tube port which provides a path to
the center tube. Pressure which will increase in the opposite
side of the valve will escape through a bleed port located in
each piston. When de-energized, the valve will be in the cooling
position.
37
Page 38
Figure 37
REVERSING VALVE
SOLENOID COIL
(Heat Pump Models Only) (See Figure 37)
The solenoid coil is an electromagnetic type coil mounted on
the reversing valve and is energized during the operation of
the compressor in the heating cycle.
Should the reversing valve fail to shift during the heating cycle,
test the solenoid coil.
TO TEST:
1. Disconnect power to unit.
2. Disconnect coil leads.
3. Attach probes of an ohmmeter to each coil lead and check
for continuity.
TESTING REVERSING VALVE
Occasionally, the reversing valve may stick in the heating or
cooling position or in the mid-position.
When stuck in the mid-position, part of the discharge gas from
the compressor is directed back to the suction side, resulting
in excessively high suction pressure.
Check the operation of the valve by starting the system and
switching the operation from "Cooling" to "Heating" and then
back to "Cooling". Do not hammer on valve.
If valve fails to change its position, test the voltage to the valve
coil while the system is in the heating cycle. If voltage to coil is
satisfactory, replace reversing valve.
Should the valve fail to shift from cooling to heating, block the
air flow through the outdoor coil and allow the discharge
pressure to build in the system. Then switch the system from
heating to cooling.
If the valve is stuck in the heating position, block the air flow
through the indoor coil and allow discharge pressure to build
in the system. Then switch the system from heating to cooling.
NOTE: Do not start unit with solenoid coil removed from valve,
or do not remove coil after unit is in operation. This
will cause the coil to burn out.
VALVE, DRAIN PAN (See Figure 38)
During the cooling mode of operation, condensate which
collects in the drain pan is picked up by the condenser fan
blade and sprayed onto the condenser coil. This assists in
cooling the refrigerant plus evaporating the water.
During the heating mode of operation, it is necessary that water
be removed to prevent it from freezing during cold outside
temperatures. This could cause the condenser fan blade to
freeze in the accumulated water and prevent it from turning.
To provide a means of draining this water, a bellows type drain
valve is installed over a drain opening in the base pan.
This valve is temperature sensitive and will open when the
outside temperature reaches 40°F. The valve will close
gradually as the temperature rises above 40°F to fully close
at 60°F.
Should the valve fail to shift in either position after increasing
the discharge pressure, replace the valve.
NOTE: When brazing a reversing valve into the system, it is
of extreme importance that the temperature of the valve does
not exceed 250° F at any time.
Wrap the reversing valve with a large rag saturated with
water. "Re-wet" the rag and thoroughly cool the valve after
each brazing operation of the four joints involved.
The wet rag around the reversing valve will eliminate
conduction of heat to the valve body when brazing the line
connection.
38
Figure 38
BELLOWS ASSEMBLY
DRAIN PAN VALVE
Page 39
HEATING ELEMENT (See Figure 39)
SEALED REFRIGERATION SYSTEM REPAIRS
All heat pumps and electric heat models are equipped with a
heating element with the exception of the YS09J10. The "YS",
"ES" and "EK12" models are equipped with a 3.3 KW element.
The "YM", "EM" and "EK18" models are equipped with a 4.0
KW element. The "YL" and "EL" models are equipped with a
5.2 KW element.
The heating element contains a fuse link and a heater limit
switch. The fuse link is in series with the power supply and
will open and interrupt the power when the temperature
reaches 161.6°F, or a short circuit occurs in the heating
element. Once the fuse link separates, a new fuse link must
be installed. NOTE: Always replace with the exact
replacement.
The heater element has a high limit control. This control is a
bimetal thermostat mounted in the top of the heating element.
Figure 39
HEATING ELEMENT
IMPORTANT
ANY SEALED SYSTEM REPAIRS TO HEAT PUMP
MODELS REQUIRES THE INSTALLATION OF A
SUCTION LINE DRIER IN THE SUCTION LINE
BETWEEN THE EVAPORATOR AND THE REVERSING
VALVE.
EQUIPMENT REQUIRED
1. Voltmeter
2. Ammeter
3. Ohmmeter
4. E.P.A. Approved Refrigerant Recovery System.
5. Vacuum Pump (capable of 200 microns or less vacuum.)
6. Acetylene Welder
7. Electronic Halogen Leak Detector (G.E. Type H-6 or
equivalent.)
Should the fan motor fail or filter become clogged, the high
limit control will open and interrupt power to the heater before
reaching an unsafe temperature condition.
The control is designed to open at 110°F ±6°F. Test continuity
below 110°F and for open above 110°F.
The heating element for the "Y" model is energized by an
outdoor thermostat. The outdoor thermostat is adjusted at a
predetermined temperature to bring on the heating element
and turn off the compressor. The room thermostat will then
control the cycling of the element when the selected indoor
temperature is reached.
Testing of the elements can be made with an ohmmeter across
the terminals after the connecting wires have been removed.
A cold resistance reading of approximately 14.5 ohms for the
3.3 KW heater, 11.9 ohms for the 4.0 KW heater and 9.15
ohms for the 5.2 KW heater should be registered.
8. Accurate refrigerant charge measuring device such as:
a. Balance Scales - 1/2 oz. accuracy
b. Charging Board - 1/2 oz. accuracy
9. High Pressure Gauge - (0 - 400 lbs.)
10. Low Pressure Gauge - (30 - 150 lbs.)
11. Vacuum Gauge - (0 - 1000 microns)
EQUIPMENT MUST BE CAPABLE OF:
1. Recovery CFC's as low as 5%.
2. Evacuation from both the high side and low side of the
system simultaneously.
3. Introducing refrigerant charge into high side of the system.
4. Accurately weighing the refrigerant charge actually introduced into the system.
5. Facilities for flowing nitrogen through refrigeration tubing during all brazing processes.
39
Page 40
HERMETIC COMPONENT REPLACEMENT
The following procedure applies when replacing components
in the sealed refrigeration circuit or repairing refrigerant leaks.
(Compressor, condenser, evaporator, capillary tube, refrigerant
leaks, etc.)
1.Recover the refrigerant from the system at the process
tube located on the high side of the system by installing
a line tap on the process tube. Apply gauge from process
tube to EPA approved gauges from process tube to
EPA approved recovery system. Recover CFC's in
system to at least 5%.
SPECIAL PROCEDURE IN THE CASE OF
COMPRESSOR MOTOR BURNOUT
1.Recover all refrigerant and oil from the system.
2.Remove compressor, capillary tube and filter drier from
the system.
3.Flush evaporator condenser and all connecting tubing
with dry nitrogen or equivalent, to remove all
contamination from system. Inspect suction and
discharge line for carbon deposits. Remove and clean
if necessary.
2.Cut the process tube below pinch off on the suction
side of the compressor.
3.Connect the line from the nitrogen tank to the suction
process tube.
4.Drift dry nitrogen through the system and un-solder the
more distant connection first. (Filter drier, high side
process tube, etc.)
5.Replace inoperative component, and always install a
new filter drier. Drift dry nitrogen through the system
when making these connections.
6.Pressurize system to 30 PSIG with proper refrigerant
and boost refrigerant pressure to 150 PSIG with dry
nitrogen.
7.Leak test complete system with electric halogen leak
detector, correcting any leaks found.
8.Reduce the system to zero gauge pressure.
9.Connect vacuum pump to high side and low side of
system with deep vacuum hoses, or copper tubing. (Do
not use regular hoses.)
10.Evacuate system to maximum absolute holding
pressure of 200 microns or less. NOTE: This process
can be speeded up by use of heat lamps, or by breaking
the vacuum with refrigerant or dry nitrogen at 5,000
microns. Pressure system to 5 PSIG and leave in
system a minimum of 10 minutes. Release refrigerant,
and proceed with evacuation of a pressure of 200
microns or less.
4.Reassemble the system, including new drier strainer
and capillary tube.
5.Proceed with processing as outlined under hermetic
component replacement.
ROTARY COMPRESSOR SPECIAL
TROUBLESHOOTING AND SERVICE
Basically, troubleshooting and servicing rotary compressors
is the same as on the reciprocating compressor with only a
few exceptions.
1.Because of the spinning motion of the rotary, the mounts
are critical. If vibration is present, check the mounts
carefully.
2.The electrical terminals on the rotary are in a different
order than the reciprocating compressors. The terminal
markings are on the cover gasket. Use your wiring
diagram to insure correct connections.
REFRIGERANT CHARGING
NOTE: BECAUSE THE RAC SYSTEM IS A SEALED
SYSTEM, SERVICE PROCESS TUBES WILL HAVE TO
BE INSTALLED. FIRST INSTALL A LINE TAP AND
REMOVE REFRIGERANT FROM SYSTEM. MAKE
NECESSARY SEALED SYSTEM REPAIRS AND
VACUUM SYSTEM. CRIMP PROCESS TUBE LINE AND
SOLDER END SHUT. DO NOT LEAVE A SERVICE
VALVE IN THE SEALED SYSTEM.
11.Break vacuum by charging system from the high side
with the correct amount of refrigerant specified. This
will prevent boiling the oil out of the crankcase.
NOTE: If the entire charge will not enter the high side,
allow the remainder to enter the low side in small
increments while operating the unit.
12.Restart unit several times after allowing pressures to
stabilize. Pinch off process tubes, cut and solder the
ends. Remove pinch off tool, and leak check the process
tube ends.
40
Proper refrigerant charge is essential to proper unit
operation. Operating a unit with an improper refrigerant
charge will result in reduced performance (capacity) and/or
efficiency. Accordingly, the use of proper charging methods
during servicing will insure that the unit is functioning as
designed and that its compressor will not be damaged.
Too much refrigerant (overcharge) in the system is just as
bad (if not worse) than not enough refrigerant
(undercharge). They both can be the source of certain
compressor failures if they remain uncorrected for any
period of time. Quite often, other problems (such as low air
Page 41
refrigerant charge problems. The refrigerant circuit diagnosis
chart will assist you in properly diagnosing these systems.
An overcharged unit will at times return liquid refrigerant
(slugging) back to the suction side of the compressor eventually
causing a mechanical failure within the compressor. This
mechanical failure can manifest itself as valve failure, bearing
failure, and/or other mechanical failure. The specific type of
failure will be influenced by the amount of liquid being returned,
and the length of time the slugging continues.
Not enough refrigerant (Undercharge) on the other hand, will
cause the temperature of the suction gas to increase to the
point where it does not provide sufficient cooling for the
compressor motor. When this occurs, the motor winding
temperature will increase causing the motor to overheat and
possibly cycle open the compressor overload protector.
Continued overheating of the motor windings and/or cycling
of the overload will eventually lead to compressor motor or
overload failure.
The weighed in method should always be used whenever a
charge is removed from a unit such as for a leak repair,
compressor replacement, or when there is no refrigerant
charge left in the unit. To charge by this method, requires the
following steps:
1. Install a piercing valve to remove refrigerant from the
sealed system. (Piercing valve must be removed from
the system before recharging.)
2. Recover Refrigerant in accordance with EPA regulations.
3. Install a process tube to sealed system.
4. Make necessary repairs to system.
5. Evacuate system to 250 - 300 microns or less.
6. Weigh in refrigerant with the property quantity of R-22
refrigerant.
METHOD OF CHARGING
The acceptable method for charging the RAC system is the
Weighed in Charge Method. The weighed in charge method
is applicable to all units. It is the preferred method to use, as it
is the most accurate.
7. Start unit, and verify performance.
8. Crimp the process tube and solder the end shut.
NOTE: In order to access the sealed system it will be necessary to install Schrader
type fittings to the process tubes on the discharge and suction of the compressor.
Proper recovery refrigerant procedures need to be adhered to as outlined in EPA
Regulations. THIS SHOULD ONLY BE ATTEMPTED BY QUALIFIED SERVICE
PERSONNEL.
Undercharged Refrigerant SystemsUndercharged Refrigerant Systems
Undercharged Refrigerant Systems
Undercharged Refrigerant SystemsUndercharged Refrigerant Systems
An undercharged system will result in poor performance (low
pressures, etc.) in both the heating and cooling cycle.
Whenever you service a unit with an undercharge of
refrigerant, always suspect a leak. The leak must be repaired
before charging the unit.
To check for an undercharged system, turn the unit on, allow
the compressor to run long enough to establish working
pressures in the system (15 to 20 minutes).
Intermittent frosting and thawing of the evaporator is another
indication of a low charge, however, frosting and thawing can
also be caused by insufficient air over the evaporator.
Checks for an undercharged system can be made at the
compressor . If the compressor seems quieter than normal, it
is an indication of a low refrigerant charge. A check of the
amperage drawn by the compressor motor should show a
lower reading. (Check the Unit Specification.) After the unit
has run 10 to 15 minutes, check the gauge pressures.
During the cooling cycle you can listen carefully at the exit of
the metering device into the evaporator; an intermittent hissing
and gurgling sound indicates a low refrigerant charge.
Gauges connected to system with an undercharge will have
low head pressures and substantially low suction pressures.
41
Page 42
NOTE: Heat pump refrigeration drawing
Overcharged Refrigerant SystemsOvercharged Refrigerant Systems
Overcharged Refrigerant Systems
Overcharged Refrigerant SystemsOvercharged Refrigerant Systems
Compressor amps will be near normal or higher.
Noncondensables can also cause these symptoms. To
confirm, remove some of the charge, if conditions improve,
system may be overcharged. If conditions don’t improve,
Noncondensables are indicated.
Whenever an overcharged system is indicated, always make
sure that the problem is not caused by air flow problems.
Improper air flow over the evaporator coil may indicate some
of the same symptoms as an overcharged system.
An over charge can cause the compressor to fail, since it would
be "slugged" with liquid refrigerant.
The charge for any system is critical. When the compressor
is noisy, suspect an overcharge, when you are sure that the
air quantity over the evaporator coil is correct. Icing of the
evaporator will not be encountered because the refrigerant
will boil later if at all. Gauges connected to system will usually
have higher head pressure (depending upon amount of
overcharge). Suction pressure should be slightly higher.
42
Page 43
Restricted Refrigerant SystemRestricted Refrigerant System
Restricted Refrigerant System
Restricted Refrigerant SystemRestricted Refrigerant System
A quick check for either condition begins at the evaporator.
With a partial restriction, there may be gurgling sounds at the
metering device entrance to the evaporator. The evaporator
in a partial restriction could be partially frosted or have an ice
ball close to the entrance of the metering device. Frost may
continue on the suction line back to the compressor.
Often a partial restriction of any type can be found by feel, as
there is a temperature difference from one side of the
restriction to the other.
With a complete restriction, there will be no sound at the
metering device entrance. An amperage check of the
compressor with a partial restriction may show normal current
when compared to the unit specification. With a complete
restriction the current drawn may be considerably less than
normal, as the compressor is running in a deep vacuum (no
load.) Much of the area of the condenser will be relatively cool
since most or all of the liquid refrigerant will be stored there.
The following conditions are based primarily on a system in
the cooling mode.
Troubleshooting a restricted refrigerant system can be
difficult. The following procedures are the more common
problems and solutions to these problems. There are two
types of refrigerant restrictions: Partial restrictions and
complete restrictions.
A partial restriction allows some of the refrigerant to circulate
through the system.
With a complete restriction there is no circulation of refrigerant
in the system.
Restricted refrigerant systems display the same symptoms
as a "low-charge condition."
When the unit is shut off, the gauges may equalize very slowly.
Gauges connected to a completely restricted system will run
in a deep vacuum. When the unit is shut off, the gauges will
not equalize at all.
43
Page 44
Routine MaintenanceRoutine Maintenance
Routine Maintenance
Routine MaintenanceRoutine Maintenance
NOTE: Units are to be inspected and serviced by qualified service personnel only.
1.Clean the unit air intake filter at least every 250 to 300 fan hours of operation or when the unit's indicator light is on if so
equipped. Clean the filters with a mild detergent in warm water and allow to dry thoroughly before reinstalling.
2.The indoor coil (evaporator coil), the outdoor coil (condenser coil) and base pan should be inspected periodically (yearly
or bi-yearly) and cleaned of all debris (lint, dirt, leaves, paper, etc.). Clean the coils and base pan with a soft brush and
compressed air or vacuum. If using a pressure washer, be careful not to bend the aluminium fin pack. Use a sweeping
up and down motion in the direction of the vertical aluminum fin pack when pressure cleaning coils. Cover all electrical
components to protect them from water or spray. Allow the unit to dry thoroughly before reinstalling it in the sleeve.
NOTE: Do not use a caustic coil cleaning agent on coils or base pan. Use a biodegradable cleaning agent and
degreaser.
Inspect the indoor blower housing, evaporator blade, condenser fan blade, and condenser shroud periodically (yearly or
bi-yearly) and clean of all debris (lint, dirt, mold, fungus, etc.) Clean the blower housing area and blower wheel with an
antibacterial / antifungal cleaner. Use a biodegradable cleaning agent and degreaser on condenser fan and condenser
shroud. Use warm or cold water when rinsing these items. Allow all items to dry thoroughly before reinstalling them.
3.Periodically (at least yearly or bi-yearly): inspect all control components, both electrical and mechanical, as well as the
power supply. Use proper testing instruments (voltmeter, ohmmeter, ammeter, wattmeter, etc.) to perform electrical
tests. Use an air conditioning or refrigeration thermometer to check room, outdoor and coil operating temperatures. Use
a sling psychrometer to measure wet bulb temperatures indoors and outdoors.
4.Inspect the surrounding area (inside and outside) to ensure that the units' clearances have not been compromised or
altered.
5.Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and debris.
Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and ensure that
the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as needed.
6.Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry thoroughly
before reinstalling it in the chassis.
44
Page 45
TROUBLESHOOTING TOUCH TEST CHART
TO SERVICE REVERSING VALVES
NORMAL FUNCTION OF VALVE
VALV E
OPERATING
CONDITION
SUCTION TUBE
to Compressor
Tube to INSIDE
from Compressor
DISCHARGE TUBE
COIL
Tube to OUTSIDE
COIL
LEFT Pilot
Capillary Tube
RIGHT Pilot
Capillary Tube
* TEMPERATURE OF VALVE BODY
** WARMER THAN VALVE BODY
NOTES:
123456POSSIBLE CAUSESCORRECTIONS
NormalHotCoolCool Hot*TVBTVB
Coolingas (2) as (1)
Normal HeatingHotCoolHot Cool *TVBTVB
as (1) as (2)
MALFUNCTION OF VALVE
No voltage to coil.
Defective coil.
Low charge
Pressure differential too high.
Pilot valve okay. Dirt in one
Hot
bleeder hole.
Piston cup leak
Clogged pilot tubes.
Hot
Hot
Hot
Hot
Hot
Both ports of pilot open. (Back seat
port did not close).
Defective Compressor
Not enough pressure differential at
start of stroke or not enough flow to
maintain pressure differential.
Body damage
Both ports of pilot open.
Body damage
Valve hung up at mid-stroke. Pumping
volume of compressor not sufficient to
maintain reversal.
Both ports of pilot open.
Piston needle on end of slide leaking.
Pilot needle and piston needle leaking
**
Pressure differential too high
.
Clogged pilot tube.
Dirt in bleeder hole.
Valve will
not shift
from cool to
heat.
Valve will
not shift
from cool to
heat.
Starts to
shift but
does not
complete
reversal.
Apparent
leap in
heating.
Hot
Hot
Hot
Wa rm
Hot
Hot
Hot
Hot
Hot
Hot
Hot
Hot
Check Electrical circuit and coil
Check refrigeration charge
Cool
Cool
Cool
Cool
Wa rm
Wa rm
Hot
Hot
Cool
Cool
Cool
Cool
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Warm
Warm
Hot
Hot,
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Hot,
as (1)
Warm,
as (1)
Hot
Hot
Hot
Hot
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
*TVB
*TVB
Hot
*TVB
*TVB
Hot
*TVB
Hot
*TVB
**
WVB
*TVB
Hot
*TVB
Warm
*TVB
WVB
*TVB
*TVB
Will not shift
from heat to
cool.
Valve operated satisfactorily PRIOR to compressor motor burnout – caused by dirt and small greasy particles inside the valve. TO CORRECT: Remove valve, thoroughly
wash it out. Check on air before reinstalling, or replace valve. Add strainer and filter-drier to discharge tube between valve and compressor.
Hot
Hot
Wa rm
Cool
Cool
Cool
as (1)
Warm,
Hot,
Hot,
as (1)
as (1)
Cool,
as (2)
Cool,
as (2)
Cool,
as (2)
Hot
Hot
Warm
*TVB
Hot
*TVB
Piston cup leak
Defective pilot.
Defective compressor.
Repair electrical circuit.
Replace coil.
Repair leak, recharge system.
Recheck system.
Deenergize solenoid, raise head pressure,
reenergize solenoid to break dirt loose. If
unsuccessful, remove valve, wash out. Check
on air before installing. If no movement, replace
valve, add strainer to discharge tube, mount
valve horizontally.
Stop unit. After pressures equalize, restart with
solenoid energized. If valve shifts, reattempt
with compressor running. If still no shift, replace
valve.
Raise head pressure, operate solenoid to free.
If still no shift, replace valve.
Raise head pressure, operate solenoid to free
partially clogged port. If still no shift, replace
valve.
Check unit for correct operating pressures and
charge. Raise head pressure. If no shift, use
valve with smaller port.
Replace valve
Raise head pressure, operate solenoid. If no
shift, replace valve.
Replace valve
Raise head pressure, operate solenoid. If no
shift, use valve with smaller ports.
Raise head pressure, operate solenoid. If no
shift, replace valve.
Operate valve several times, then recheck. If
excessive leak, replace valve.
Operate valve several times, then recheck. If
excessive leak, replace valve.
Stop unit. Will reverse during equalization
period. Recheck system
Raise head pressure, operate solenoid to free
dirt. If still no shift, replace valve.
Raise head pressure, operate solenoid.
Remove valve and wash out. Check on air
before reinstalling, if no movement, replace
valve. Add strainer to discharge tube. Mount
valve horizontally.
Stop unit. After pressures equalize, restart with
solenoid deenergized. If valve shifts, reattempt
with compressor running. If it still will not
reverse while running, replace the valve.
Replace valve.
45
Page 46
TROUBLESHOOTING COOLING
Compressor does not
run.
PROBLEM
Fan motor
does not run.
POSSIBLE CAUSEPROBLEM
Low voltage.
Thermostat not set cold enough or
inoperative.
Compressor hums but cuts off on
overload.
Open or shorted compressor
windings.
Open overload.
Open capacitor.
Inoperative system switch.
Broken, loose or incorrect wiring.
POSSIBLE CAUSE
Inoperative system switch.
Broken, loose or incorrect wiring.
Open Capacitor.
Fan speed switch open.
Inoperative fan motor.
TO CORRECT
Check for voltage at compressor. 115 volt and 230
volt units will operate at 10% voltage variance
Set thermostat to coldest position. Test thermostat
and replace if inoperative.
Hard start compressor. Direct test compressor. If
compressor starts, add starting components.
Check for continuity and resistance.
Test overload protector and replace if inoperative.
Test capacitor and replace if inoperative.
Test for continuity in all positions. Replace if
inoperative.
Refer to appropriate wiring diagram to check wiring.
TO CORRECT
Test switch and replace in inoperative.
Refer to applicable wiring diagram.
Test capacitor and replace if inoperative.
Test switch and replace if inoperative.
Test fan motor and replace if inoperative. (Be
sure internal overload has had time to reset.)
PROBLEM
Does not cool, or cools
only slightly.
PROBLEM
Unit does not run.
POSSIBLE CAUSE
Undersized unit.
Thermostat open or inoperative.
Dirty filter.
Dirty or plugged condenser or
evaporator coil.
Poor air circulation in area being
cooled.
Fresh air or exhaust air door open
on applicable models.
Low capacity – undercharge.
Compressor not pumping properly.
Fuse blown or circuit tripped.
Power cord not plugged in.
System switch in "Off" position.
Inoperative system switch.
Loose or disconnected wiring at switch or
other components.
TO CORRECT
Refer to Sizing Charts.
Set to coldest position. Test thermostat and
replace if necessary.
Clean as recommended in Owner’s Manual.
Use steam or detergents to clean.
Adjust discharge air louvers. Use high fan
speed.
Close doors. Instruct customer on use of this
feature.
Check for leak and make repair.
Check amperage draw against nameplate. If
not conclusive, make pressure test.
TO CORRECT
Replace fuse, reset breaker. If repeats, check fuse
or breaker size. Check for shorts in unit wiring and
components.
Set switch correctly.
Test for continuity in each switch position.
Check wiring and connections. Reconnect per wiring
diagram.
46
Page 47
PROBLEM
Evaporator coil
freezes up.
POSSIBLE CAUSE
Dirty filter.
Restricted air flow.
Inoperative thermostat.
Short of refrigerant.
Inoperative fan motor.
Partially restricted capillary.
TO CORRECT
Clean as recommended in Owner’s Manual.
Check for dirty or obstructed coil - clean as required.
Test for shorted thermostat or stuck contacts.
De-ice coil and check for leak.
Test fan motor and replace if inoperative.
De-ice coil. Check temperature differential across
coil. Touch test coil return bends for same temperature. Test for low running current.
PROBLEMPOSSIBLE CAUSE
Excessive heat load.
Compressor runs
continually.
Does not cycle off.
Thermostat does not
turn unit off.
PROBLEM
Compressor attempts
to start, or runs for
short periods only.
Cycles on overload.
Restriction in line.
Refrigerant leak.
Thermostat contacts stuck
Thermostat incorrectly wired.
POSSIBLE CAUSE
Thermostat contacts stuck.
Thermostat set at coldest point.
Incorrect wiring.
Unit undersized for area to be cooled.
POSSIBLE CAUSETO CORRECT
Overload inoperative. Opens too soon.
Compressor attempts to start before
system pressures are equalized.
Low or fluctuating voltage.
Incorrect wiring.
Shorted or incorrect capacitor.
Restricted or low air flow through
condenser coil.
Compressor running abnormally hot.
TO CORRECT:
Unit undersized. Test cooling performance of unit.
Replace with larger unit.
Check for partially iced coil. Check temperature split
across coil.
Check for oil at silver soldered connections. Check
for partially iced coil. Check split across coil. Check
for low running amperage.
Check operation of thermostat. Replace if contacts
remain closed.
Refer to appropriate wiring diagram.
TO CORRECT:PROBLEM
Replace thermostat.
Turn to higher temperature setting to see if the unit
cycles off.
Refer to appropriate wiring diagram.
Refer to Sizing Chart.
Check operation of unit. Replace overload if
system operation is satisfactory.
Allow a minimum of two (2) minutes for pressures
to equalize before attempting to restart. Instruct
customer of waiting period.
Check voltage with unit operating. Check for other
appliances on circuit. Air conditioner should be on
separate circuit for proper voltage, and be fused
separately.
Refer to appropriate wiring diagram.
Check by substituting a known good capacitor of
correct rating.
Check for proper fan speed or blocked condenser.
Check for kinked discharge line or restricted
condenser. Check amperage.
Thermostat does not
turn unit on.
POSSIBLE CAUSE
Loss of charge in thermostat bulb.
Loose or broken parts in thermostat.
Incorrect wiring.
TO CORRECTPROBLEM
Place jumper across thermostat terminals to check
if unit operates. If unit operates, replace thermostat.
Check as above.
Refer to appropriate wiring diagram.
47
Page 48
PROBLEM
Noisy operation.
POSSIBLE CAUSE
Poorly installed unit.
Fan blade striking chassis.
Compressor vibrating.
Improperly mounted or loose cabinet
parts.
TO CORRECT
Refer to Installation Instructions for proper
installation.
Reposition - adjust motor mount.
Check that compressor grommets have not
deteriorated. Check that compressor mounting parts
are not missing.
Check assembly and parts for looseness, rubbing
and rattling.
PROBLEM
Water leaks into room.
PROBLEM
Thermostat short
cycles.
PROBLEM
Prolonged off-cycles.
(automatic operation)
TO CORRECTPOSSIBLE CAUSE
Evaporator drain pan overflowing.
Condensation forming on base pan.
Poor installation resulting in rain
entering room.
Condensation on discharge grilles.
Clean obstructed drain trough.
Evaporator drain pan broken or cracked. Reseal or
replace.
Check Installation Instructions. Reseal as required.
Dirty evaporator coil - clean. Very high humidity
level.
POSSIBLE CAUSETO CORRECT
Thermostat differential too narrow.
Plenum gasket not sealing, allowing
discharge air to short cycle thermostat.
Restricted coil or dirty filter.
Tubular insulation missing from top of
thermostat bulb.
Thermostat bulb touching thermostat
bulb support bracket.
Replace thermostat.
Check gasket. Reposition or replace.
Clean and advise customer of periodic cleaning of
filter.
Replace tubular insulation on bulb.
(Applicable models.)
Adjust bulb bracket.
(Applicable models.)
TO CORRECT
POSSIBLE CAUSE
Anticipator (resistor) wire disconnected
at thermostat or system switch.
Anticipator (resister shorted or open).
(Applicable models.)
Partial loss of charge in thermostat
bulb causing a wide differential.
Refer to appropriate wiring diagram.
Disconnect plug from outlet. Remove resistor from
bracket. Insert plug and depress "Cool" and "Fan Auto (MoneySaver)” buttons. Place thermostat to
warmest setting. Feel resistor for temperature. If no
heat, replace resistor.
Replace thermostat.
PROBLEM
Switches from
cooling to heating.
48
POSSIBLE CAUSE
Thermostat sticking.
Incorrect wiring.
TO CORRECT
Change room thermostat.
Refer to appropriate wiring diagram.
Page 49
PROBLEM
Outside water leaks.
Evaporator drain pan cracked or
obstructed.
Water in compressor area.
Obstructed condenser coil.
Fan blade and slinger ring improperly
positioned.
TO CORRECTPOSSIBLE CAUSE
Repair, clean or replace as required.
Detach shroud from pan and coil. Clean and
remove old sealer. Reseal, reinstall and check.
Steam clean.
Adjust fan blade to 1/2" clearance from condenser
coil.
PROBLEM
High indoor
humidity.
POSSIBLE CAUSE
Insufficient air circulation in air conditioned area.
Oversized unit.
Inadequate vapor barrier in building
structure, particularly floors.
Set thermostat to a warmer position.
Replace — do not attempt to adjust.
Check compressor wiring. Check for open internal
or external overload. Check wiring.
Test system switch
TO CORRECT
Clean as recommended in Owner’s Manual.
Check if outdoor thermostat is energizing the heating
element at its predetermined temperature setting
Check control setting.
TO CORRECT
Check continuity of switch.
Check applicable wiring diagram.
TO CORRECT
Incorrect differential setting. Replace thermostat.
Check voltage to resistor. If voltage okay, remove
resistor from thermostat bulb block. With current on,
feel resistor for warmth. If no heat can be felt,
replace anticipator.
Wide differential — partial loss of
thermostat bulb charge.
Incorrect wiring.
POSSIBLE CAUSE
Incorrect wiring.
Defrost control timer motor not advancing.
Defrost control out of calibration.
Defrost control contacts stuck.
Defrost control bulb removed from coil,
or not making good coil contact.
TO CORRECT
Disconnect power to unit. Remove resistor from
thermostat bulb block. Plug in unit and allow to
operate. Feel resistor for heat. If no heat is felt,
replace resistor.
Replace thermostat and check.
Refer to appropriate wiring diagram. Resistor is
energized during the "on" cycle of compressor or
fan.
TO CORRECT
Refer to appropriate wiring diagram.
Check for voltage at "TM" and "TM1" on timer. If
voltage, replace control.
If outside coil temperature is 25° F or below, and
preselected time limit has elapsed, replace the
defrost control.
If the contacts remain closed between terminals "2"
and "3" of the defrost control after preselected time
interval has passed, replace control.
Reinstall and assure that good bulb to coil contact is
made.
50
Page 51
PROBLEMPOSSIBLE CAUSETO CORRECT
Defective thermostat - replace.
Check if operating properly. Instruct customer
Unit does not heat
adequately.
Outdoor thermostat does not cut off
compressor at the preselected temperature and bring on heating element.
Fresh air or exhaust door open.
on proper use of control.
Dirty filter.
Unit undersized.
Clean as recommended in Owner’s Manual.
Check heat rise across coil. Refer to perfor-
mance data sheet on heat rise at various
outdoor ambients. If heat rise is satisfactory,
check if insulation can be added to attic or
walls.
PROBLEMPOSSIBLE CAUSETO CORRECT
Unit cools when
heat is called for.
PROBLEM
Unit does not heat
adequately.
Incorrect wiring.
Defective solenoid coil.
Reversing valve fails to shift.
Inoperative system switch.
POSSIBLE CAUSE
Outdoor thermostat does not cut off
compressor at the preselected temperature and bring on the heating element.
Fresh air or exhaust door open.
Dirty filter.
Unit undersized.
Refer to applicable wiring diagram.
Check for continuity of coil.
Block condenser coil and switch unit to cooling.
Allow pressure to build up in system, then
switch to heating. If valve fails to shift, replace
valve.
Check for continuity of system switch.
TO CORRECT
Defective thermostat — replace.
Check if operating properly. Instruct customer on
proper use of control.
Clean as recommended in Owner’s Manual
Check heat rise across coil. Refer to performance
data sheet on heat rise at various outdoor ambients. If
heat rise is satisfactory, check if insulation can be
added to attic or walls.
Unit cools when
heat is called for.
Cooling adequate —
heating insufficient.
POSSIBLE CAUSEPROBLEM
Incorrect wiring.
Defective solenoid coil.
Reversing valve fails to shift.
Reversing valve failing to shift
completely — bypassing hot gas.
TO CORRECT
Refer to applicable wiring diagram.
Check for continuity of coil.
Block condenser coil and switch unit to cooling. Allow
pressure to build up in the system, then switch to
heating. If valve fails to shift, replace valve.
Check for continuity of system switch.
TO CORRECT
Check for partially starved outer coil. Replace heating
capillary tube.
Switch unit several times from heating to cooling.
Check temperature rise across the coil. Refer to
specification sheet for correct temperature rise.
Deenergize solenoid coil, raise head pressure, energize solenoid to break loose. If valve fails to make
complete shift, replace valve.
51
Page 52
Compressor will not turn
off and operate on heating
element only during low
outside ambients.
POSSIBLE CAUSEPROBLEM
Outdoor thermostat.
(Applicable models.)
TO CORRECT
Refer to the heating data on applicable models for
the preselected temperature the compressor shuts
off and the electric element is energized.
Compressor shuts off on
outdoor thermostat but
element does not heat.
POSSIBLE CAUSEPROBLEM
Fuse link.
Heating element shorted.
Incorrect wiring.
Heat relay or heater contactor coil open.
TO CORRECT
Check fuse link for continuity. If defective, replace.
Check amperage draw of element. If no amperage,
replace.
Check voltage to element. If voltage is okay, check
wiring.
Defective coil. Test coil for continuity.
52
Page 53
Troubleshooting Heating
(Cooling/Electric Models)
Heater relay or contactor coil open.
Heater relay or contactor stuck open,
Fan Operates –
heating element does
not come on.
pitted or burned.
High limit control open.
Open thermal fuse.
Open or shorted element.
Loose connections.
TO CORRECTPOSSIBLE CAUSEPROBLEM
Check continuity of coil.
Inspect, test continuity with ohmmeter.
Check continuity – if open, replace.
Check continuity. Check reason for failure.
Check voltage across heater terminals. Check
amperage draw of heater.
Tighten all terminals.
PROBLEMPOSSIBLE CAUSE
Restricted filter.
Cycling high limit control.
Heating inadequate.
Exhaust or fresh air door open.
PROBLEM
Fan operates in "Con-
stant" position, but not in
"Automatic" (Money-
Saver).
PROBLEM
Long "off" and "on"
cycles.
POSSIBLE CAUSE
Fan relay contacts open.
Inoperative system switch.
Loose connection.
POSSIBLE CAUSE
Heat anticipator (resistor) shorted.
Defective thermostat.
TO CORRECT
Clean as recommended in Owner’s Manual.
Control is set to open at 155°F ± 5°F and close at
130°F ± 8°F. If cycling prematurely, replace control.
Check position of fresh air door control slide. Adjust
cable if door does not close properly.
TO CORRECT
Check continuity of fan relay. NOTE: Some models
have the fan relay energized during the heating
cycle while others do not.
Check continuity between terminals "L2" and "3" of
the system switch.
Check connections on system switch and fan relay.
TO CORRECT
Disconnect power to unit. Remove resistor from
thermostat bulb block. Plug in unit and allow to
operate. Feel resistor for heat. If no heat is felt,
replace resistor.
Replace thermostat and check operation.
PROBLEM
Fan motor does not
operate in "Constant"
or "MoneySaver"
position.
Cooling adequate,
heating insufficient.
POSSIBLE CAUSE
Defective motor.
Open or shorted capacitor.
Condenser fan frozen to base pan.
Loose connections.
Reversing valve failing to shift
completely – bypassing hot gas.
TO CORRECT
Check and replace.
Replace capacitor and check.
Check if drain pan valve is open. If not, replace.
Check all connections. Check voltage to fan motor.
TO CORRECT
Check for partially starved outer coil. Replace
heating capillary tube.
Switch unit several times from heating to cooling.
Check temperature rise across coil. Refer to specification sheet for correct temperature rise.
Deenergize solenoid coil, raise head pressure,
energize solenoid to break loose. If valve fails to
make complete shift, replace valve.
53
Page 54
PROBLEM
Compressor will not
turn off and operate on
heating element only
during low outside
ambients.
POSSIBLE CAUSE
Outdoor thermostat.
(Applicable models.)
TO CORRECT
Refer to the heating data on applicable models for
WIRING DIAGRAM FOR MODELS YS13J33, YM18J34A & YL24J35A
65
Page 66
WIRING DIAGRAM FOR MODEL YS09J10A
66
Page 67
TESTING THE ELECTRONIC CONTROL
2001 XQ BOARDS & QME BOARDS
Checking Room Temperature:
1. Check the room temperature at the electronic control pad by pressing at the same time the
"FAN SPEED" button and the temperature "UP" button on XQ models.
2. Check the room temperature at the electronic control pad by pressing at the same time the
"FAN SPEED" button and the "WARMER" button on QME models. The indoor temperature
will display for 10 seconds. Indoor temperature can be viewed in all modes, including the
TEST mode. The display can be changed back to SET temperature by pressing any key,
except the ON/OFF button, or after 10 seconds has elapsed.
Activating Test Mode: Activate test mode by pressing at the same time the "MODE" button and
the temperature "DOWN" button on XQ models. LEDs for Hour, Start, and Stop will blink 1
bps while Test Mode is active. Activate test mode by pressing at the same time the "MONEYSAVER" button and the "FILTER ALERT" button on QME models. LED for the Filter Alert will
blink 1 bps while Test Mode is active.
Test Mode has duration of 90 minutes. Test Mode can be activated under any conditions,
including Off. Test Mode is cancelled by pressing the On/Off button, unplugging the unit, or
when the 90 minutes is timed out. All settings revert to the factory default settings of Cool, 75
degrees F, Timer and Set Hour features are nonfunctional.
Test Mode overrides the three-minute lockout, all delays for compressor and fan motor start /
speed change, and no delay when switching modes.
Saver, 60 degrees F, and High fan speed
Activating Error Code Mode: (Submode of Test Mode) Unit has to be in Test Mode to enter Error
Code Mode
1. Activate Error Code Mode by pressing the "TIMER ON/OFF" button on XQ models. LED for
the "TIMER ON/OFF" will flash 1 bps while Error Code Mode is active. Pressing the "TEMP/HR + " button will display 00. Consecutive presses will scroll through all error codes logged.
Press the "TEMP/HR - " button to see the reverse order of all error codes logged. When the
end of logged error codes is reached the temperature set point will appear.
Activate Error Code Mode by pressing at the same time the "A/C START" button and the "ON/OFF" button on QME models. LED for the "TIMER ON/OFF" will flash 1 bps while Error Code
Mode is active. Pressing the "WARMER" button will display 00. Consecutive presses will scroll
through all error codes logged. Press the "COOLER" button to see the reverse order of all
error codes logged. When the end of logged error codes is reached the temperature set point
will appear.
.
Test Mode default settings are ON, Money
IMPORTANT
Error Codes are cleared from the log by exiting from Error Code Mode. To exit on XQ models,
press Timer On/Off button. To exit QME models, press A/C Start and On/Off buttons. Or unplug
unit to exit Error Code Mode. Plug unit in after 5 seconds to resume normal operation of unit.
67
Page 68
QUICK REFERENCE GUIDE
QuietMaster® Electronic Room Air Conditioner
920–044-01 (11/2000)
TO START UNIT
Touch the ON/OFF button. The unit will automatically be in regular COOLING mode
with the temperature set at 75°F (24°C) and the fan speed at F1 (SLEEP).
NOTE: Should the FILTER ALERT light flash when you first turn the unit on, touch the
FILTER ALERT button to turn off the flashing light.
TO ADJUST TEMPERA TO ADJUST TEMPERA
TO ADJUST TEMPERA
TO ADJUST TEMPERA TO ADJUST TEMPERA
COOLER – Touch
the display shows the desired room temperature.
WARMER – Touch WARMER and hold until
the display shows the desired room temperature.
FAHRENHEIT / CELSIUS – Touch ºF / ºC to
show the temperature in Celsius, touch again to
show Fahrenheit.
TO ADJUST THE FAN SPEED
Touch SPEED 1-4 until the display shows the
desired fan speed. F1 is the lowest setting (SLEEP
SETTING), F2 is LOW, F3 is MEDIUM, F4 is
HIGH. Touch SMART FAN (light on) and the fan
speed will adjust automatically to maintain the
desired comfort level.
Touch SPEED 1-4 for manual control of fan
speeds
TURETURE
TURE
TURETURE
COOLER
and hold until
TOUCH
ON / OFF
PM
DISPLAY
CoolerWarmer
PM
DISPLAY
SPEED
1 – 4
°
SMART
FA N
F / °C
TO SET THE CL TO SET THE CL
TO SET THE CL
TO SET THE CL TO SET THE CL
Smart Center
®
ELECTRONIC CONTROLS
TO SET THE TIMER TO SET THE TIMER
TO SET THE TIMER
TO SET THE TIMER TO SET THE TIMER
STOP TIME – Touch A/C STOP and hold until the hour you want the unit to shut off
appears in the display.
START TIME – Touch A/C START and hold until the hour you want the unit to come on
appears in the display.
Touch TIMER ON (light on) to activate the timer function. Touch TIMER OFF (light
off) to cancel the timer function. Once the on and off times have been selected, they will
remain in memory. However, if the power is interrupted, set the CLOCK TIME again.
F F
or complete operating instructions refer to the Operating Guide.or complete operating instructions refer to the Operating Guide.
z
F
or complete operating instructions refer to the Operating Guide.
F F
or complete operating instructions refer to the Operating Guide.or complete operating instructions refer to the Operating Guide.
68
Touch SET HOUR CLOCK and hold until the
hour closest to the actual time appears in the
display. Make sure you set A.M. and P.M. properly.
Minutes will NOT show on the display.
OCK TIMEOCK TIME
OCK TIME
OCK TIMEOCK TIME
A /C
Stop
PM
PM
DISPLAY
Set Hour
Clock
DISPLAY
A /C
Start
Timer
On/Off
Page 69
QUICK REFERENCE GUIDE
XSTAR® Room Air Conditioner
TO START UNIT
Touch the POWER ON/OFF button. The unit will automatically be in regular COOLING
mode with the temperature set at 75°F (24°C) and the fan speed at F1 (SLEEP).
TO ADJUST TEMPERA TO ADJUST TEMPERA
TO ADJUST TEMPERA
TO ADJUST TEMPERA TO ADJUST TEMPERA
COOLER – Touch and hold until the display shows the desired room temperature.
WARMER – Touch and hold until the display shows the desired room temperature.
TURETURE
TURE
TURETURE
920–117-00 (12/00)
TOUCH
POWER
On/Off
PM
DISPLAY
TO ADJUST THE FAN SPEED
Touch FAN SPEED until the display
shows the desired fan speed. F1 is the lowest
setting (SLEEP SETTING / LOW), F2 is MED,F3 is HIGH, and SF is SMART FAN. With
SMART FAN on, the fan speed will adjust automatically to maintain the desired comfort
level.
TO SET THE CLOCK TIME
Touch SET HOUR (Clock light On), then press or until the hour closest to the actual
time appears in the display. Make sure you set A.M. and P.M. properly.
Minutes will NOT show on the display.
TO SET THE TIMER TO SET THE TIMER
TO SET THE TIMER
TO SET THE TIMER TO SET THE TIMER
START TIME – After the clock time has been set, press SET HOUR (START light on) then
press and until the hour you want the unit to come on appears in the display.
STOP TIME – After the start time has been set, press SET HOUR (STOP light on), then
press and until the hour you want the unit to shut off appears in the display.
Touch TIMER ON (light on) to activate the timer function. Touch TIMER OFF (light off) to
cancel the timer function. Once the on and off times have been selected, they will remain in
memory. However, if the power is interrupted, set the CLOCK TIME again.
PM
PM
Set
Hour
PM
DISPLAY
FA N
SPEED
DISPLAY
Set
Hour
DISPLAY
Timer
On/Off
FF
or complete operating instructions refer to the Operating Guide.or complete operating instructions refer to the Operating Guide.
z
F
or complete operating instructions refer to the Operating Guide.
FF
or complete operating instructions refer to the Operating Guide.or complete operating instructions refer to the Operating Guide.
69
Page 70
FRIEDRICH AIR CONDITIONING COFRIEDRICH AIR CONDITIONING CO
FRIEDRICH AIR CONDITIONING CO
FRIEDRICH AIR CONDITIONING COFRIEDRICH AIR CONDITIONING CO
• Post Office Box 1540 • San Antonio, Texas 78295-1540
• 4200 N. Pan Am Expressway • San Antonio, Texas 78218-5212
• (210) 357-4400 • FAX (210) 357-4480
Visit us on the Internet at www.friedrich.com
Printed in the U.S.A.
..
.
..
RACServMn (01/02)
70
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.