Friedrich CP Line CP08, CP Line ZQ10, CP Line ZQ08, ZQ08, ZQ10 Installation And Operation Manual

Room Air Conditioner Installation and Operation
Manual
*_'riedrich
CP Line
115 Volts CP08 ZQ08 ZQ10
Registering Your Room Air Conditioner
on-line at www.friedrich.com (USA only). For your future convenience, record the model information here.
MODEL NUMBER SERIAL NUMBER PURCHASE DATE
Congratulations!
You have purchased a Friedrich
room air conditioner. The Friedrich units are designed to give maximum
comfort and quietness.
Table of Contents
Introduction .................................................................................. 2
Safety Precautions ....................................................................... 3
How to operate your Friedrich ................................................... 5
How to operate your Friedrich ZStar® ......................................6
Adjusting the Air Flow Direction................................................. 7
Care and Maintenance ................................................................. 8
Hardware Location ....................................................................... 9
Installation Instructions ........................................................ 15
Troubleshooting Tips ................................................................. 17
Warranty ...................................................................................... 18
Introduction
Before Operating Your Unit
Make sure the wiring is adequate for your unit.
If you havefuses, they should beof the time delay type. Beforeyou install or relocate this unit, be sure that the amperage rating of the circuit breaker or time delay fuse does notexceed the amp rating listed in figure 1.
DO NOT use an extension cord.
The cord provided will carry the proper amount of electrical powerto the unit; an extension cord will not.
Make sure that the receptacle is compatible with the wall plug provided.
This insures proper grounding. If you have a two-prong receptacle you will need to havethe circuit replaced by a certified electrician with a grounded circuit that meets all national and local codes and ordinances.You must use the three-prong plug furnished with the air conditioner.
MODEL
CP08 ZQ08 ZQ10
CIRCUIT
RATING OR
TIME DELAY
FUSE
AMP VOLT
15 125
PLUG FACE
NEMA NO.
5-15P
@
Figure 1
For the Best Cooling Performance and Energy Efficiency
Keep the filter clean
Make sure that your air conditioner is always in top performing condition by cleaning the filter regularly.
Instructionsfor removing and cleaningthe filter can be found on page 8.
Provide good airflow
Make sure that the airflow to and from the unit is clear. Your air conditioner puts the air out atthe top of the unit, and takes in air at the bottom. Airflow is critical for good operation. It is just as important on the outside ofthe building that the airflow around the unit exterior is not blocked.
Unit Placement
Ifyour air conditioner can be placed in a window or a wall that is shaded by a tree or another building, the unit will operate even more efficiently. Using drapes or blinds on the sunny sideof the dwellingwill also add toyour unit's efficiency.
/nsu/ation
Good insulation will be a big help in maintaining desirable comfort levels. Doorsshould have weather stripping. Be sureto caulk around doors and windows.
Safety Precautions
To prevent injury and property damage, follow these instructions.
incorrect operation due to ignoring of instruction can cause harm or damage. The seriousness is classified by the following indications.
'_//_ WARNING This symbol indicates the possibility of death or serious injury. /
J
/_ CAUTION This symbol indicates the possibility of injury or damage to
properties only.
Meanings of symbols used in this manual are as shown below.
Never Do This
,0__ Always Do This
I/_ WARNING}
Otherwise, it will cause electric shock or fire due to heat
generation.
it will cause electric shock or fire due to heat generation.
it wi(I cause eiectric shock or fire.
If the power cord is damaged, it must be reptaced by the manufacturer or a Friedrich-certified service agent.
it will cause electric shock or fire it will cause electric shock. due to heat generation.
®
This could lead to hea(th probiems.
They are sharp and may cause an injury.
I CAUTION I
Water may enter the unit and degrade the insulation. It may
cause an electric shock.
Since the fan rotates at high speed during operation, it may cause an injury.
® ®
It could cause dust to accumulate on the heat
exchanger.
It may cause an electric shock.
This could injure the pets or plants.
It may cause a fire or deformation of the cabinet.
Do not use this air conditioner to preserve precision devices, food,
pets, plants, and art objects. It may cause deterioration of quality, etc.
Use caution when handling the case. Grip it firmly and do not allow it to slip while holding it.
Use heavy gloves to handte the case if necessary.
DO NOT allow the case to slide
against your skinT
edges
How to operate your Friedrich
Fan Speed
Timer Mode //il I
C ° _
@
Control and Remote Control Operations
I. POWER
Operation begins when this button is pressed and stops when you press the button again.
2. TEMPERATURE CONTROL
The thermostat monitors room temperature to maintain the desired temperature.
The thermostat can be set between 60°F~86°F (16°C~30°C).
The unit takes an average of 30 minutes to adjust the roomtemperature by I°F.
3. OPERATION MODE SELECTOR
Select cooling mode to cool the room. Select Money Saver_ mode for energy saving operation. Select fan mode for basic ventilatingfan operation. Select dry mode for dry operation.
4.FAN SPEEDSELECTOR
Forincreased powerwhile cooling, select a higher fan speed.
3 steps: High; Low; Med
5. ON/OFF TIMER
The timer can be set to start and stop the
unit inhourly increments (up to 12 hours).
6.REMOTE CONTROLSENSOR
Inserting the Remote Control Batteries
1.Push out the cover on the back of the remote control with your
thumb
2. Pay attention to polarity and insert two new AAA 1.5V
batteries.
3. Reattach the cover.
NOTE: Donotuserechargeabiebatteries.Makesurethat bothbatteriesarenew.
Inorderto preventdischarge,removethebatteriesfrom theremotecontrolif theairconditioneris notgoingto be
usedforanextendedperiodoftime Keeptheremotecontrolawayfromextremelyhotor
humidplaces. Tomaintainoptimaloperationofthe remotecontrol,the
remotesensorshouldnotbeexposedtodirectsunlight.
Theremotecontrolcanbemountedonawallusingthe mountableholder.(Friedrichdoesnotprovidethis.)
How to operate your Friedrich ZStar
Function Controls
MED H{GN
FAN@_COOL
LO ED
FAN _ COOL
O
LOW COOL
OPERATRON
5
THERMOSTAT
Off - Turns air conditioner off. Med Fan - Med speed fan operation without cooling.
Low Fan - Low speed fan operation without cooling. High Cool - Cooling with high speed fan operation. Med Cool- Coolingwith med speed fan operation. Low (3ool - Cooling with low speed fan operation.
This automatically controls the temperature of the indoor air. Turn the knob so that arrow points to the higher numberfor greater cooling. Point the arrow to the lower number for more moderate cooling. (i.e. the higher the number, the greater the cooling)
FOR NORMAL COOLING
1. Turn the operation switch to the High Cool or the Low Cool setting.
2. Set the Thermostat control to the desired temperature mark 5 (the mid-point is a good starting position). If the room temperature is not satisfactory after a reasonable time, adjust the control to a cooler or warmer
setting, as appropriate.
FOR MAXIMUM COOLING
1. Turn the Operation Knob to the HighCool setting.
2. Set the Thermostat control to the largest (9) temperature mark.
FOR QUIETER OPERATION
1. Turn the Operation Knob to the Low Cool setting.
2. Set the Thermostat control as needed.
CAUTION
When the air conditioner has finished cooling the room and is turned off or set to the fan position, wait at least 3 minutes before resetting to the cooling operation again.
Adjusting the Air Flow Direction
Vent Control
For maximum cooling efficiency, CLOSE the vent. This will allow internal air circulation. OPENthe vent to discharge stale air.
CLOSE ,-=-VENT JLOPEN
NOTE : Before using the ventilation feature, position
the vent lever by pulling Part A out straight and snapping it into place.
¢_'r"""
LuJ_p. "".
Part "" z--::--X"
Adjusting the Air Flow Direction
Airflow can be adjusted by changing the direction of the air conditioner's louvers.
Adjusting Horizontal Air Flow Direction
Adjusting the vertical louvers left and rightwill change horizontal airflow.
Adjusting Vertical Air Flow Direction
Adjusting the horizontal louver up and downwill change vertical airflow. The louvercan be
adjusted by pressing in at the top or button of the horizontal louver.
Adjusting horizontal air flow Adjusting vertical air flow
Recommended orientation of louvers
Adjust louversto face upwards when cooling to maximize cooling efficiency.
Care and Maintenance
Turnthe power off and unplug the power plug before cleaning the air conditioner.
Air Filter
The air filter behind the inletgrille should be checked and cleaned at least once every2 weeks (oras necessary) to maintain optimal performanceof the air conditioner.
How to remove the air filter
1.The grille may be opened from the top for easy maintenance after installation.
2. Open the inlet grille by pulling out on the exposed door on the top of the unit (based on installation).
3. Pull the tab slightlyto release the filter. Pullthe filter in the same direction as the opening.
4. Clean the filter with warm, soapy water.
5. Rinse off and gently shake off excess water from the filter. Make sure filter is completely dry before
replacing it.
Drainage
The base pan may overflow due to high humidity. To drain the excess water, remove the drain cap from the back of the unit and secure the drainpipe. When pressing the drainpipe into place, apply force in the direction away from the fins to avoid injuring yourself.
Drain pipe
Drain cap
Hardware Location
Product Features
/_ CAUTION
This applianceshould be installed in accordance with local andnational wiring regulations. This manual acts as a guide to help to explain product features.
®
®
©
© ®
Positioning the Power cord
You can choose between two methods below according to your window stool shape and preference.
Fasten the stopper using 2 screw holes, and lead ° Fastenthe stopper usingleft screw hole, and rotate out the power cord through slit "A". properlyto leadthe power cord out through slit "B".
Power cord
Power cord
/
0
How to Install the Unit
1.To prevent vibration and excess noise, make sure the unit is installed securely and firmly
2. Install the unit where the sunlight does not Cooled air shine directly on the unit. _-_
3. The outside of the cabinet must extend outward for at least 12" and there should __
z_
be no obstacles, such asa fence or wall, within 20" from the back of the cabinet, as it will prevent heat radiationof the
condenser. Restriction of outside air will greatly reduce
the cooling efficiency of the air conditioner.
Awning
Fence
CAUTION: All side louvers of the cabinet must remain exposed and unobstructed to the outside of the
structure.
4. Install the unit with a rear, downward slope, so the back isslightly lowerthan the front (about 1/4"buble on a level). This will force condensation to flow tothe outside.
5. Install the unit with the bottom about 30"~60'' above thefloor level.
Window Requirements
NOTE: All supporting parts should be secured to firm wood, masonry, or metal.
This unit is designed for installation instandard
double hung windows with actual opening widths
from 22" to 36".
The top and bottom window sash must open
sufficiently to allow a clear vertical opening of 15"
from the bottom of the upper sash to the window
stool.
l I:;;;;= I t
22"to 36"...........
. 15"min . Stoo|
[vvlinTramecur[aln/ ,, /I
( :
I ',
, Interior wall ",20 1/I2"rain.
(Withoutframecurtain'
............Offset
: I/2" to 1%"
si,
\Exterior
Installation Kit Contents
NO. NAME OF PARTS Q'TY
1 FRAME CURTAIN 2 2 SILL SUPPORT 2 3 BOLT 2 4 NUT 2
5 SCREW (TYPE A) 16 6 SCREW (TYPE B) 3 7 SCREW (TYPE C) 5
8 FOAM-STRIP 1 9 UPPER GUIDE 1
10 FOAM-PE 1 11 FRAME GUIDE 2 12 WINDOW LOCKING BRACKET 1
13 FOAM-PE 1
Suggested Tool Requirements
I SCREWDRIVER(+,-), RULER, KNIFE, HAMMER, PENCIL, LEVEL
PREPARATION OF CHASSIS
1.Remove the screws which fasten the cabinet at both sides and at the back.(4 total)
2. Slide the unit from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet.
3. Cut the window sash seal to the proper length. Peel off the backing and attach the Foam-PE @to the
underside of the window sash.
4. Remove the backing from the top upper guide Foam-PE
® and attach it to the bottom of the Upper Guide ®.
5. Attach the upper guide onto the top of the cabinet with 3 Type A screws ®.
6. Insert the Frame Guides ® into the bottom of the cabinet.
7. Insert the Frame Curtain O intothe Upper Guide (_ and Frame Guides @.
8. Fasten the curtains to the unit with 4-Type A screws _).
.-....
(Type A)d
Shipping Screws
)(Type A)
Cabinet Installation
1.Open the window. Mark a line on center of the
window stool. Carefully place the cabinet on the window
stool and align the center mark on the bottom front with the center line marked in the
window stool.
Upper Guide
Window stool
Front Angle
Fig. 1
2. Pull the bottom window sash down behind the Upper Guide untilthey meets.
NOTE: Do not pull the window sash down so
tightly that the movement of Frame Curtain Q is restricted.
Window Sash
\
Foam-pe (_) ...... _'(_
Cabinet ..........
Frame Curtain
Foam-pe
Upper guide
Fig. 2
3. Loosely assemble the Sill Support (_ using the parts in Fig. 3.
Bolt@
OUTDOOR
\
Sill Support@
4. Select the position that will placethe Sill Support @ near the outer most point on sill (See Fig. 4)
NOTE: Be careful when you installthe cabinet
(Frame Guides ® are brokeneasily).
5. Attach the Sill Support Q to the cabinet track hole in relation to the selected position using 2 -type A @ screws in each support
(See Fig. 4).
Frame Guide@
INDOOR
Screw(Type A) G
/
// /
Cabinet
OUTDOOR
Fig. 4
6. The cabinet should be installed with a very slight tilt (about 1/2")downwardtoward the outside
(See Fig. 5). Adjust the bolt and the nut of Sill Support Ofor balancing the cabinet.
Screw(Type B) C._
7. Attach the cabinet to the window stool by driving the screws ® [Type B: Length 16mm (518inch)
and below.] through the front angle into window stool.
8. Pull each Frame Curtain to each window sash track, and repeat step 2.
9. Attach each Frame Curtain _ to the window sash using screws O (TypeC). (See Fig. 6)
CAUTION: Do not drill a hole in the bottom pan.
The unit is designed to operate with
approximately 1/2"of water in bottom of pan.
There is no need to add water if the
pan isdry.
Sill Support
i:: : J
._Sash track
Front Angle
\
Screw(Type B)
Fig. 5
Fig. 6
10. Slide the unit into the cabinet. (See Fig. 7)
CAUTION: For security purpose, reinstall the 2
screws (Type A) at cabinet's side, that
were removed in step 1 on page 10.
Screw(Type A)
Power cord Screw
(Type A)
Fig. 7
11.Cut the Foam-Strip ®to the proper length (window width) and insert between the upper
window sash and the lower window sash. (See Fig. 8)
Foam-Strip8_
Fig. 8
12.AttachtheWindowLockingBracket@withaTypeC screw0. (SeeFig.9)
Window locking
bracket 1@
13. Attach thefront grille to the cabinet by inserting the tabs on the grille into the tabs on the front of the cabinet. Push the grille in until it snaps into place. (See Fig. 10)
14. Pull down the inletgrille and secure itwith a Type A screw _) through the front grille. (See Fig. 11)
15. Window installation of room air conditioner is now completed. See ELECTRICAL DATA for
inserting power cord to electrical outlet.
Fig. 9
Fig. 10
Fig. 11
Installation Instructions
Read these instructions completely and carefully.
Tools You Will Need
Phillips-head screwdriver
Flat-blade screwdriver
Ruler or tape measure
Before YouBegin
3 Scissors or knife
3 Pencil
3 Level
3 Hammer
NOTE TO INSTALLER: Leavethese instructions with the air conditioner after
installation is completed.
NOTE TO CONSUMER: Keep this Installation and Operation Manual for future use.
Important notes:
It is recommended that proper attire be worn
during installation.
Forpersonal safety, this air conditioner must
be properlygrounded.
It is important to havethe wall outlet and circuit checked by a qualified electrician ifthere is any doubt as to whether a proper ground exists.
CAUTION:
Do not under any circumstances, cut or remove
the third (ground) prong from the power cord. Do not change the plug on the power cord of
this air conditioner. Aluminum house wiring may present special
problemsELonsult a qualified electrician.
Electrical Safety
115V~
Powercord may include a current interrupter device.A test and reset button is provided on the plug case. Thedevice should be tested on a periodic basis by first pressing the TEST button and then the
RESET button. If the TEST button does not
trip or ifthe RESET button will not stay
engaged, discontinue use ofthe air conditioner and contact a qualified service
technician.
UseWall Receptacle
©
Standard 125V, 3-wire grounding
receptacle rated 15A, 125V AC
PowerSupply
Use 15AMR time delayfuse or 15 AMR
circuit breaker.
Use of extension cords Because of potential safety hazards, we strongly discourage the use of an extension cord. However,
ifyou wish to use an extension cord, usea CSA certified/UL-listed3-wire (grounding) extension cord, rated 15A,
125V.
All wiring should be made in accordance with local electrical codes and regulations.
Aluminum house wiring may pose special problems.Consult a qualified electrician.
ELECTRICAL SAFETY
IMPORTTANT GROUNDING INSTRUCTIONS
Air conditioner has a three-prong grounding plug on its power supply cord, which must be plugged into properly grounded three-prong wall receptacle foryour protectionagainst possible shock hazard.
Troubleshooting Tips
Troubleshooting Tips save time and money! Reviewthe chart below first and you may not need to call for service.
Normal Operation
Youmay hear a pinging noise caused by water being picked up and thrown against thecondenser on rainy days or whenthe humidity is high. Thisdesign feature helps remove moistureand improve efficiency.
You may hear the thermostat click when the compressor cycles on and off.
Water will collect in the base pan during high humidity or on rainy days. The water may overflow and
drip from the outdoor side of the unit.
The fan may run even when the compressor does not.
Your air conditioner is designed to cool in warm weather when the outside temperature is above
60°F(16°C) and below 115°F(46°C).
Abnormal Operation
Air conditioner does not start
Air conditioner does not cool as it should
Air conditioner freezing up
Make sure the air conditioner plug is pushed completely intothe outlet.
Check the housefuse/circuit breakerbox and replacethe fuse or reset the breaker.
If powerfailure occurs, turn the Mode Control to Off. When power is restored, wait 3 minutes to restart the
air conditioner to prevent tripping of the compressor overload.
Press the RESET button located on the power cord plug. If the RESET button will not stay eng
aged, discontinue use of the air conditioner and
contact a qualified service technician.
Make sure there are no curtains, blinds, or furniture blocking the front ofthe air conditioner.
*Turn the knobto a higher setting. The highest
setting provides maximum cooling.
Clean the filter at least every 2 weeks. See the operating instructions section.
When the air conditioner is first turned on you need to allow time for the roomto cool down.
Check for open furnace floor registers and cold air returns.
Set the air conditioner's vent to the closed position.
See Air Conditioner Freezing Up below.
_lc_ th_flo_ Set the mode control on high fan untilthe icethaws _thir out.
FRIEDRICHAIRCONDITIONINGCO,
Post Office Box 1540 S_tn Antonio, Tex_s 78295-154O
(210) 357-4400 FAX (210) 357-4490
ROOM AIR CONDITIONERS
LIMITED WARRANTY
FIRST YEAR
ANY PART: If any part supplied by FRIEDRICH falls because of a defect in workmanship or material within twelve months from date of original purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service.
Any additional labor cost for removing inaccessible units and/or charges for mileage related to travel by a Service Agency that exceeds 25 miles one way will be the responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within twelve months from the date of the original purchase.
SECOND THROUGHFIFTHYEAR
SEALED REFRIGERANT SYSTEM: If the sealed refrigeration system (defined for this purpose as the compressor, condenser coil, evaporator coil, reversing valve, check valve, capillary, filter drier, and all interconnecting tubing) supplied by FRIEDRICH in your Room
Air Conditioner fails because of a defect in workmanship or material within sixty months from date of purchase, FRIEDRICH will pay a labor allowance and parts necessary to repair the Sealed Refrigeration System; PROVIDED FRIEDRICH will not pay the cost of diagnosis
of the problem, removal, freight charges and transportation of the air conditioner to and from the Service Agency, and the reinstallation charges associated with repair of the Sealed Refrigeration System. All such cost will be the sole responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within sixty months from the date of the original purchase.
APPLICABILITY AND LIMITATIONS: This warranty is applicable only to units retained within the Fifty States of the U.S.A., District of Columbia, and Canada. This warranty is not applicable to:
1. Air filters or fuses.
2. Products on which the model and serial numbers have been removed.
3. Products which have defects or damage which results from improper installation, wiring, electrical current characteristics, or maintenance; or caused by accident, misuse or abuse, fire, flood, alterations and/or misapplication of the product and/or units installed in a corrosive atmosphere, default or delay in performance caused by war, government restrictions or restraints, strikes,
material shortages beyond the control of FRIEDRICH, or acts of God.
OBTAINING WARRANTY PERFORMANCE: Service will be provided by the FRIEDRICH Authorized Dealer or Service Organization in your area. They are listed in the Yellow Pages.If assistance is required in obtaining warranty performance, write to: Room Air Conditioner Service Manager, Friedrich Air Conditioning Co., R O. Box 1540, San Antonio, TX 78295-1540.
LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES. Anything in the warranty notwithstanding, ANY IMPLIED WARRANTIES OF FITNESS FOR PARTICULAR PURPOSE AND/OR MERCHANTABILITY SHALL BE LIMITED TO
THE DURATION OF THIS EXPRESS WARRANTY. MANUFACTURER EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGE FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY.
NOTE: Some states do not allow limitations on how long an implied warranty lasts,or do not allow the limitation or exclusion of consequential or incidental damages,so the foregoing exclusions and limitations may not apply to you.
OTHER: This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
PROOF OF PURCHASE: Owner must provide proof of purchase in order to receive any warranty related services.
All service calls for explaining the operation of this product will be the sole responsibility of the consumer.
All warranty service must be provided by an Authorized FRIEDRICH Service Agency, unless authorized by FRIEDRICH prior to repairs being made.
In case of questions regarding the provisions of this warranty, the English version will govern.
Revised 08/01
FRIEDRICH AIR CONDITIONING CO
Visit our web site at www friedrich com
Post Office Box 1540 4200 N Pan Am Expressway * San Antonio, Texas 78295-1540
(210) 357-4400 FAX (210) 357-4490 P/NO: 3828A21016C
Loading...