Friedrich CP18N30, CP24N30, CP14N10 User Manual

Service & P arts Manual 2007
Compact Programmable
Models CP14N10
CP18N30 CP24N30
CP-14-18-24-Svc-Prts-07 (3-07)
Table of Contents
Outer Component Identifi cation ................................................................................................................................................... 4
Installation Dimensions ................................................................................................................................................................5
Wiring Diagrams ...........................................................................................................................................................................6
Functional Component Defi nitions ...............................................................................................................................................7
Refrigeration System Sequence of Operation ............................................................................................................................8
Sealed Refrigeration System Repairs ....................................................................................................................................9-12
T roubleshooting .....................................................................................................................................................................13-18
Part Diagrams and Part Lists ................................................................................................................................................19-23
Warranty ..................................................................................................................................................................................... 24
The information contained in t his manual is intended for use by a qualifi ed ser vice technician who is familiar
with the safety procedures required i n in stal la tion a nd repair, and who is equipped with the proper tools and test instruments.
Installation or repairs made by unqualifi ed persons can result in hazards subjecting the unqualifi ed person making such repai rs to the risk of injury or electrical shock which can be serious or even fatal not only to them, but also to persons being served by the equipment.
If you install or perform service on equipment, you must assume responsibility for any bodily injur y or proper t y damage which may result to you or others. Friedrich Air Conditioning Co mpany will not be responsible for any injury or property damage arising from improper installation, service, and/or service procedures.
2
Specifi cations and Technical Parameters
Model CP14N10 CP18N30 CP24N30
Function COOLING COOLING COOLING
Rated Voltage 115V ~ 230/208V~ 230/208V~
Rated Frequency 60Hz 60Hz 60Hz
Total Capacity (Btu/h) 14000 18000/17600 23500/23100
Power Input (W) 1430 1850/1810 2740/2710
Rated Input (W) 1540 2478 3538
Rated Current (A) 15 12.57 18.09
Air Flow Volume (CFM) (H) 458.8 458.8 617.6
Dehumidifying Volume (pints/h) 3.38 4.65 8.46
EER / C.O.P BTU/W.H) 9.8 9.7/9.7 8.6/8.5
Energy Class / / /
Fan Type-Piece Centrifugal fl ow fan – 1 Centrifugal fl ow fan – 1 Centrifugal fl ow fan – 1
Diameter-Length (inch) φ7.93 X 4.31 φ7.93 X 4.31 φ8.82 X 4.31
Indoor Side
Outdoor Side
Fan Motor Speed (rpm) (H/M/L) 900/780/730 900/780/730 1000/900/800
Output of Fan Motor (W) 200 200 190
Fan Motor RLA(A) 3 1.45 1.35
Fan Motor Capacitor (uF) 15 MFD 7 MFD 7 MFD
Permissible Excessive Operating Pressure for the Discharge Side (Psig) 300 300 300
Permissible Excessive Operating Pressure for the Suction Side (Psig) 150 150 150
Dimension (H/W/D)( inch) 16.85 x 25.98 x 28.46 16.85 x 25.98 x 28.46 16.85 x 25.98 x 29.29
Dimension of Package (H/W/D)( inch) 19.96 x 31.1 x 29.13 19.96 x 31.1 x 29.13 19.69 x 29.29 x 36.22
Net Weight /Gross Weight (Pounds) 150/163 150/163 165/183
Refrigerant Charge (Ounce) R22/26.46 R22/27.87 R22/33.51
Evaporator Aluminum fi n-copper tube Aluminum fi n-copper tube Aluminum fi n-copper tube
Pipe Diameter (inch) φ0.276 φ0.276 φ0.276
Coil length (l) x height (H) x coil width (L) 16.61 X 15 X 1 16.61 X 15 X 1 16.61 X 15 X 1
Compressor Type ROTARY ROTARY ROTARY
L.R.A. (A) 58 42 56
Compressor RLA(A) 10.9 7.45 11.7/11.0
Compressor Power Input(W) 1182 1700 2425/2480
Overload Protector MRA13425-12007 MRA98982-9200 Built in
Working Temp Range (ºF) 50º-115º 50º-115º 50º-115º
Condenser Aluminum fi n-copper tube Aluminum fi n-copper tube Aluminum fi n-copper tube
Fan Type-Piece Axial fan –1 Axial fan –1 Axial fan –1
Fan Diameter (inch) φ15.59 φ15.59 φ15.59
Performance Data
PERFORMANCE
DATA * Cooling
CP14N10
CP18N30
CP24N30
EVAP. AIR TEMP.
DEG. F
Discharge
Air
59 21 118 173 56 41 54 78 267 12.1 / 58 26.5 115 15 58 22 119 173 66 52 55 77 269 8.3 / 57 23 119 172 66 52 55 77 269 8.5 / 208 57 23 117 197 60 44 50 75 264 12.3 / 56 24 117 195 57 44 50 75 264 13.1 / 208
Temp.
Drop F.
CONDENSER
TEMPERATURE
DEG. F
Discharge
Temp
Suction
Temp
Super
Heat
Sub-Cooling
*Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity.
OPERATING PRESSURES
Suction Discharge
ELECTRICAL RATING S R-22 REF.
Amps
Amps
Cool
Heat
Locked
Rotor Amps
38.9/42.4 27.9
56A(230V) 33.5
Charge in
OZ.
Voltage
230
230
BREAKER
FUSE
60 Hertz
Amps
15
20
3
Outer Component Identifi cati o n
Models: CP14N10, CP18N30, CP24N30
Front intake grille
Cabinet
Air inlet louver
Front grille
Air filter (behind front intake grille)
Power cord
Control panel cover
4
Installation Dimensions
Models: CP14N10, CP18N30, CP24N30
(Top View)
Over 2'
Fence / obstruction
16.85"
Over 1'
(Front View)
25.98"
Over 1'
Wall Or window
Ceiling
Over 1'
(Side View)
Over 1'
Less than
8.66"
Over 2'
5
Wiring Diagrams
CP24N30
CP18N30 / CP14N10
6
Functional Component Defi nitions
MECHANICAL C OMPONEN TS
Vent d o o r Allows introduction of fresh air into the room and /or
exhausts stale room air outside (on select models. ) Plenum assembly Diffuser with directional louvers used to direct
the conditioned airfl ow. Blower wheel Attaches to the indoor side of the fan motor shaft
and is used for distributing unconditioned, room side air though the heat exchanger and delivering conditioned air into the room.
Slinger fan blade Attaches to the outdoor side of the fan motor shaft and is used to move outside air through the condenser coil, while slinging condensate water out of t he base pan and onto the condenser coil, thus lowering the temperature and pressures within the coil.
ELECTRICAL COMPONENTS
Thermostat Used to maintain the speci ed room side comfort
level
Capacitor Reduces line current and steadies the voltage supply , while greatly improving the torque characteristics of the fan motor and compressor motor.
MoneySaver® switch W hen engaged, it sends the power sup ­ply to the fan motor through t he thermost at, which allows for a cycle-fan operation.
Fan Motor Dual- shaf ted fan motor operate s the indoor blower wheel and the condenser fan blade simultaneously.
Heat anticipator Used to provide better thermostat and room air temperature control.
HERMETIC COMPONENTS
Compressor Motorized device used to compress refrigerant
through the sealed system. Check valve A pressure-operated device used to direct the fl ow
of refrigerant to the proper capillary tube, during either the heating or cooling cycle.
Capillary tube A cylindrical meter device used to evenly distribute the fl ow of refrigerant to the heat exchangers (coils.)
7
Refrigeration System Sequence of Operation
A good understanding of t he basic operation of the refrigera ­tion system is essential for the s ervic e technician. Without t his understanding, accurate troubleshooting of refrigeration system problems will be more diffi cult and time consuming, if not (in some cases) entirely impossible. The re frigeration system uses four basic principles (laws) in its operation they are as follows:
1. “Heat always fl ows from a warmer body to a cooler body . ”
2. “Heat must be added to or removed from a substance before a change in state can occur”
3. “Flow is always from a higher pressure area to a lower pressure area.”
4. “The temperature at w hich a liquid or gas c hanges state is dependent upon the pressure.”
The refrigerat ion cycle begins at the compre ssor. Starting the
compressor creates a low pressure in the suction line which draws refrigerant gas (vapor) into the compressor. The compressor then
“compresse s” this refrigerant, raising it s pressure and its (heat
intensity) T emperature.
The refrigerant leaves the compressor through the discharge line
as a hot high pressure gas (vapor). The refrigerant enter s the condenser coil where it gives up some of its heat. The condenser fan moving air across the coil’s fi nned surface facilitates the transfer of heat from the refrigerant to the relatively cooler outdoor air.
When a suffi cient quantity of heat has be en removed from the refrigerant gas (vapor), the refrigerant will “condense” (i.e. change to a liquid). Once the refrigerant has been condensed (changed) to a liquid it is cooled even further by the air that continues to fl ow across the condenser coil.
In the case of the capillary tube this is accomplished (by design) through size (and length) of device, and the pressure difference present across the device.
Since the evaporator co il is under a lower p res sure (due to the suction created by the compressor) than the liquid line, the liquid refrigerant leaves the metering device entering the evaporator coil. As it enters the evaporator coil, the larger area and lower pressure allows the refrigerant to expand and lower its temperature (heat intensity). This expansion is often referred to as “boiling”. Since the unit’s blower is moving Indoor air across the fi nned surface of the evaporator coil, the expanding refrigerant absorbs some of that heat. This results in a lowering of the indoor air temperature, hence the “cooling” effect.
The expansion and absorbing of heat cause the liquid refrigerant
to evaporate (i.e. change to a gas). Once the refrigerant has been evaporated (changed to a gas), it is heated even further by the air that continues to fl ow across the evaporator coil.
The particular system design determines at exactly what point (in
the evaporator) the change of state (i.e. liquid to a gas) takes place. In all cases, however, the refrigerant must be totally evaporated (changed) to a gas before leaving the evaporator coil.
The low pressure (suction) created by the compre ssor caus es
the refrigerant to le ave the evaporator through t he suctio n line as a cool low pressure vapor . The refrigerant then returns to the compressor, where the cycle is repeated.
Refrigerant System Components
The RAC design determines at exactly what point (in the condenser)
the change of state (i.e. gas to a liquid) takes plac e. In all cas es, however, the refrigerant must be totally condensed ( changed) to a
liquid before leaving the condenser coil.
The refrigerant leaves the condenser coil through the liquid line
as a warm high pressure liquid. It next will pass through the refrigerant drier (if so equipped). It is the function of the drier to trap any moisture present in the system, contaminants, and large particulate matter.
The liquid refrigerant nex t enters the metering device. The
metering device is a capillary tube. The purpose of the metering device is to “meter ” (i.e. control or me asure) th e quantity of refrigerant entering the evaporator coil.
Suction Line
Evaporator Coil
Metering Device
Refrigerant Dryer
Discharge Line
Condenser Coil
Compressor
Refrigerant Drier
Liquid
Line
8
Sealed Refrigeration System Repairs
IMPORTANT
ANY SEALED SYSTEM REPAIRS TO COOL -ONLY MODELS REQUIRE THE INST ALLATION OF A LIQUID LINE DRIER.
ALSO, ANY SEALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRE THE INSTALLATION OF A SUCTION LINE DRIER.
EQUIPMENT REQUIRED
1. Voltmeter
2. Ammeter
3. Ohmmeter
4. E.P.A. Approved Refrigerant Recovery System.
5. V acuum Pump ( capable of 200 microns or less vacuum. )
6. Acetylene Welder
7. Electronic H alogen Leak Detector (G.E. Type H-6 or equivalent.)
8. Accurate refrigerant charge measuring device such as:
a. Balance Scales - 1/2 oz. accuracy b. Charging Board - 1/2 oz. accuracy
9. High Pressure Gauge - (0 - 400 lbs.)
1 0. Low Pressure Gauge - (30 - 150 lbs. ) 11 . Vacuum Gauge - (0 - 1000 microns)
EQUIPMENT MUST BE CAPABLE OF:
1. Recovery CFC’s as low as 5%.
2. Evacuation from both the high side and low side of the system simultaneously.
3. Introducing refrigerant charge into high side of the system.
4. Accurately weighing the refrigerant charge actually introduced into the system.
5. Facilities for fl owing nitrogen throu gh refriger ation tubing during all brazing processes.
HERMETIC COMPONENT REP LAC EMEN T
The following proc edure applies when replacing component s in the sealed refrig eration circuit or repairing ref rigerant leaks. (Compressor, condenser, evaporator, capillary tub e, refrigerant
leaks, etc.)
1. Recover the refr igerant from the system at the proc ess tube located on the high side of the system by installing a line tap on the proc ess tube. App ly gauge from pr ocess tube to EP A ap pro v ed gauges from process tube to E PA approved recovery system. Recover CFC’s in system to at least 5%.
2. Cut the process tube below pinch off on the suction side of the compressor .
3. Connect the line from the nitr ogen tank to the suction process tube.
4. Dr ift dry ni trogen through the system and un- solder the more distant connection fi rst. (Filter drier, high side process tube, etc.)
5. Replace inoperative component, and always install a new lter drier. Drift dr y nitrogen through the system when making these connections.
HERMETIC COMPONENT REP LAC EMEN T cont’d
6. Pressurize system to 30 PSIG with proper refrigerant and boost refrigerant pressure to 1 50 PSIG with dry nitrogen.
7. Leak test complete system with electric halogen leak detector, correcting any leaks found.
8. Reduce the system to zero gauge pressure.
9. Connect vacuum pump to high side and low side of system with deep vacuum hoses, or c op per tubin g. (Do n ot use regular hoses.)
1 0. Evacuate system to maximum absolute holding pressure
of 200 micro ns or less. NOTE: This process c an be accelerated by use of heat lamps, or by breaking the vacuum with refrigerant or dry nitrogen at 5,000 microns. Pressure system to 5 PSIG and leave in system a minimum of 10 minutes. Release refrigerant, and proceed with evacuation of a pressure of 200 microns or less.
11. Break vacuum by charging system from the high side with the correct amount of liquid refrigerant specifi ed. This will prevent boiling the oil out of the crankcas e, and damage to the compressor due to over heating.
NOTE: If the entire charge will not enter the high side, allow the remainder to enter the low side in small increments while operating the unit.
12. Restart unit several times after allowing pressures to stabilize. Pinch off process tubes, cut and solder the ends. Remove pinch off tool, and leak check the process tube ends.
SPECIAL PROCE DURE IN THE CASE OF COM PRESSOR MOTOR BURNOUT
1. Recover all refrigerant and oil from the system.
2. Remove compressor, capillary tube and fi lter drier from the system.
3. Flush evaporator condenser and all connecting tubing with dry nitro gen or equivalent, to remove all contamination from system. Inspect suction and discharge line for carbon deposits. Remove and clean if necessary.
4. Reassemble the system, including new drie r str ainer and capil l a ry t u b e .
5. Proceed with processing as outlined under hermetic component replacement.
ROTA RY COMPRESSOR SPECIAL TROUBLESHOOTING AND SERVICE
Basically, troubleshooting and ser vicing rotary c ompressors is the same as on the reciprocating compressor with only one main exception:
NEVER, under any circumstances, charge a rotary compressor through the LOW side. Doing so would cause permanent damage to the new compressor.
9
Loading...
+ 19 hidden pages