Friedrich CP08E10, CP06E10 User Manual 2

Room Air Conditioner
Service and Parts
Manual
CP06 CP08 SVC PARTS 2008(07/08)
0
Power
Mode
Timer 0n/0ff
Fan
Speed
Temp
CoolMoney
Saver
®
Fan Only
Dry
hr
Auto
Swing
www.sylvane.com 1-800-934-9194
CP08E10 CP06E10
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions..........................................................................................................................................3
Dimensions .....................................................................................................................................................6
Outside Dimensions ...................................................................................................................................6
Product Specifications ..................................................................................................................................7
Operation ...................................................................................................................................................... 8
How to Operate Your Friedrich CP........................................................................................................... 9
Disassembly ..................................................................................................................................................10
Mechanical Parts..................................................................................................................................... 10
AirH andling Parts ...................................................................................................................................11
Electrical Parts .........................................................................................................................................12
Refrigerating Cycle...................................................................................................................................13
Schematic Diagram.......................................................................................................................................16
Wiring Diagram.........................................................................................................................................16
Electronic Control Device.........................................................................................................................17
Components Location(For Main P.W.B ASM)...........................................................................................18
Troubleshooting Guide.................................................................................................................................19
Piping System ........................................................................................................................................19
Troubleshooting Guide .............................................................................................................................20
Exploded View ..............................................................................................................................................28
Replacement Parts List ................................................................................................................................29
www.sylvane.com 1-800-934-9194
CAUTION
www.sylvane.com 1-800-934-9194
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instructions will cause harm or damage. The seriousness
is classified by the following indications.
Safety Precautions
WARNING
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property only.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Always install the expansion panel(s).
• Improper assembly or installation may cause incorrect operation, including injury, fire, and
electric shock hazards.
Do not place the power cord near a heater.
• It may cause fire and electric shock.
Do not use the power cord near flammable gas or combustibles such as gasoline, benzene, thinner, etc.
• It may cause explosion or fire.
Do not disassemble or modify products.
• It may cause failure and electric shock.
Service Manual 3
www.sylvane.com 1-800-934-9194
Safety Precautions
Plug in the power plug properly.
• Otherwise, it will cause electric shock or fire.
Do not modify power corDo not modify poDo not modify po dwer cor
Do not modify po length.
Do not operate or stop the unit by inserting or pulling out the power plug.
• It will cause electric shock or fire.
Use the air conditioner on a single outlet circuit.(see page 7.) Do not share the outlet with other appliances.
Do not damage or use an unspecified power cord.
• It will cause electric shock or fire.
Always plug into a grounded outlet.
• •• It will cause electr ic shoc k or fire.
Ventilate before operating air conditionerwhen gas goes out.
It may cause explosion, fire, and burn.
It will cause electric shock or fire.
Do not use the socket if it is loose or damaged.
It may cause fire and electric shock.
• No •• grounding may cause electric shock.
Do not operate with wet hands or in damp environment.
• It will cause electric shock.
4 Room Air Conditioner
Service Manual 5
Safety Precautions
www.sylvane.com 1-800-934-9194
If water enters the product, turn off the the power switch of the main body of appliance. Contact service center after taking the power­plug out from the socket.
• It will cause electric shock or failure of machine.
CAUTION
Never touch the metal parts of the unit when removing the filter.
Do not clean the air conditioner with water.
• Water may enter the unit and degrade the insulation. It may cause an electric shock.
Do not block the inlet or outlet.
They are sharp and may cause injury.
••
Ensure that the outer caseis not damaged by age orwear.
Leaving it damaged couldresult in the air conditioner falling out of the window, creating a safety hazard.
It may cause failure of appliance or
• performance deteriorate.
Be cautious not to touch the sharp edges
when installing.
It may cause injury.
Sharp edges
6 Room Air Conditioner
Dimensions
Dimensions
Outside Dimensions
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
www.sylvane.com 1-800-934-9194
470(18 1/2")525(20 11/16")
/8")
7
353(13
www.sylvane.com 1-800-934-9194
Product SpecificationsProduct SpecificationsProduct SpecificationsProduct Specifications
Specfications
MODLES
ITEMS
POWER SUPPLY
COOLING CAPACITY (Btu/h)
INPUT (W)
RUNNING CURRENT (A)
E.E.R (BTU/W.h)
OPERATING
REFRIGERANT (R-22) CHARGE
EVAPORATOR
CONDENSER
FAN, INDOOR
FAN, OUTDOOR
FAN SPEEDS, FAN/COOLING
FAN MOTOR
OPERATION CONTROL
ROOM TEMP. CONTROL
AIR DIRECTION CONTROL
CONSTRUCTION
PROTECTOR
POWER CORD
DRAIN SYSTEM
OUTSIDE DIMENSION (inch) 18 1/2 x 13 7/8 x 20 11/16
(W x H x D)
INDOOR ( C) 26.7(DB)* 19.4(WB)**
OUTDOOR ( C) 35(DB)* 23.9(WB)**
HORIZONTAL LOUVER (UP & DOWN), AUTOSWING LOUVER (RIGHT&LEFT)
COMPRESSOR OVERLOAD PROTECTOR
FAN MOTOR INTERNAL THERMAL PROTECTOR
(mm) 469 x 353 x 526
CP08E10
1Ø, 115, 60Hz
7,800
720
6.8
10.8
490g(17.3 oz)
Ø7.0, 2ROW 14STACKS
Ø5.0, 2ROW 16STACKS
TURBO FAN
PROPELLER TYPE FAN WITH SLINGER RING
3/3
6 POLES
REMOTE CONTROLLER
THERMISTOR
SLIDE IN-OUT CHASSIS
3 WIRE WITH GROUNDING
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
DRAIN PIPE OR SPLASHED BY FAN SLINGER
285g(10.1 oz)
CP06E10
6,000
560
5.1
10.7
* DB:Dry Bulb **
WB:Wet Bulb
Service Manual 7
Ser 7Ser 77
Operation
Location and Function of Controls
DESIGNED FOR COOLING ONLY
POWERFUL AND INCREDIBLE COOLING
TOP-DOWN CHASSIS FOR THE SIMPLE INSTALLATION AND SERVICE
BUILT-IN ADJUSTABLE THERMOSTAT
WASHABLE ONE-TOUCH FILTER
COMPACT SIZE
Service Manual 8
www.sylvane.com 1-800-934-9194
Operation
6. AUTO SWING
This button can automatically control the air flow direction(left+right).
9 Room Air Conditioner
www.sylvane.com 1-800-934-9194
4
Fan
Speed
Timer
0n/0ff
5
Saver
6
7
Ai r
Po wer
P ur ifi er
0
F
Fa n S p eed
Ti me r
Auto
Swing
Tem p
Mod e
A
S wi ng
hr
Auto
Temp
2
Swing
Power
1
5
6
CoolMoney
Fan
®
Only
Dry
Mode
3
1
2
4
3
dry operation.
(dehumidify operation)
7
To receive the signal from remote controller.
Disassembly
Disassembly
Mechanical Parts
Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord.
1. FRONT GRILLE
1. Open the lnlet grille upward or downward.
2. Remove the screw which fastens the front grille.
3. Pull the front grille from the right side.
4. Remove the front grille.
5. Re-install the component by referring to the removal procedure, above.(See Figure 17)
2. CABINET
1. After disassembling the FRONT GRILLE, remove the 2 screws which fasten the cabinet at both sides.
2. Remove the 2 screws which fasten the cabinet at back.
3. Pull the base pan forward. (See Figure 18)
4. Remove the cabinet.
5.Re-install the component by referring to the removal procedure, above.
3. CONTROL BOX
1. Disconnect the unit from the power source.
2. Remove the front grille.
3. Remove the cabinet.
4. Remove the screw which fastens the control box cover.
5. Remove the housing which connects motor wire in the control box.
6. Remove the 3 leads from the compressor.
7.Discharge the capacitor by placing a 20,000 ohmresistor across the capacitor terminals.
8. Remove the 2 screws which fasten the control
box.(See Figure 19)
9. Pull the control box forward completely.
10. Re-install the components by referring to the removal procedure, above. (See Figure 19)
Figure 17
Figure 19
Figure 18
Service Manual 10
www.sylvane.com 1-800-934-9194
11 Room Air Conditioner
Disassembly
Air Handling Parts
7
1. AIR GUIDE AND BLOWER
1. Remove the front grille.
2. Remove the cabinet.
3. Remove the control box.
4. Remove the 3 screws which fasten the brace.
5. Remove the brace.
6. Remove the 2 screws which fasten the evaporator.
7. Move the evaporator forward and pulling it upward
slightly. (See Figure 20)
8. Move the evaporator to the left carefully.
9. Pull out the hook of orifice by pushing the tabs and
remove it. (See Figure 21)
10. Remove the clamp with a hand plier which secures the blower.
11. Remove the blower.
12. Remove the 4 screws which fasten the air guide from the barrier.
13. Move the air guide backward, pulling out from the base pan.
14. Re-install the components by referring to the removal procedure, above.
2. FAN AND SHROUD
1. Remove the cabinet.
2. Remove the brace.
3. Remove the 3 screws which fasten the condenser.
4. Move the condenser to the left carefully.
5. Remove the clamp which secures the fan.
6. Remove the fan and then pull out the shroud. (See Figure 22)
7. Re-install by referring to the removal procedure.
Figure 20
Figure 21
Figure
22
www.sylvane.com 1-800-934-9194
Service Manual 12
Electrical Parts
Disassembly
www.sylvane.com 1-800-934-9194
3. MOTOR
1. Remove the cabinet.
2. Remove the evaporator.
3. Remove the orifice.
4. Remove the blower.
5. Remove the fan.
6. Remove the control box cover and housing of the motor in the control box.
7. Remove the 2 screws which fasten the motor from the mount motor. (See Figure 23)
8. Remove the motor.
9. Re-install the components by referring to the removal procedure, above.(See Figure 23)
Figure 23
1. OVERLOAD PROTECTOR
1. Remove the cabinet.
2. Remove the nut which fastens the terminal cover.
3. Remove the terminal cover. (See Figure 24)
4. Remove all the leads from the overload protector.
5. Remove the overload protector.
6. Re-install the component by referring to the removal procedure, above.
2. COMPRESSOR
1. Remove the cabinet.
2. Discharge the refrigerant system using a Freon Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
3. Remove the overload protector.
4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
5. Remove the 3 nuts and the 3 washers which fasten the compressor.
6. Remove the compressor. (See Figure 25)
7. Re-install the components by referring to the removal procedure, above.
Figure 24
TM
Figure 25
www.sylvane.com 1-800-934-9194
3. CAPACITOR
1. Remove the control box.
2. Remove the screw which fasten control panel from control box.
3. Remove the screw which located in the front.
4. Open the bottom side of control box.
5. Remove the screw and the clamp which fastens the capacitor.
6. Disconnect all the leads of capacitor terminals.
7. Re-install the components by referring to the removal procedure, above. (See Figure 26)
4. POWER CORD
1. Remove the control box.
2. Open the control box.
3. Disconnect the grounding screw from the control box.
4. Disconnect the 2 receptacles.
5. Remove a screw which fastens the clip cord. (See Figure 27)
6. Remove the power cord.
7. Re-install the component by referring to the above removal procedure, above. (Use only one ground-marked hole for ground connection.)
8. If the supply cord of this appliance is damaged, it must be replaced by the special cord. (The special cord means the cord which has the same specification marked on the supply cord attached at the unit.)
Disassembly
Figure 26
Figure 27
Refrigerating Cycle
CAUTION: Discharge the refrigerant system using a Freon
to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
1.
CONDENSER
1. Remove the cabinet.
2. Remove the 3 screws which fasten the brace.
3. Remove the 3 screws which fasten the condenser and shroud.
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
5. Remove the condenser carefully.
6. Re-install the component by referring to notes. (See Figure 28)
TM
Figure 28
Recovery System. If there is no valve
Service Manual 13
14 Room Air Conditioner
Disassembly
Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a Freon
TM
recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated figure
30A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns counterclock­wise and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold
and entire system.
CAUTION: If high vacuum equip­ment is used, just crack valves A
and B for a few minutes, then open slowly with the two full turns counter­clockwise. This will keep oil from foaming and being drawn into the vacuum pump.
3) Operate the vacuum pump vaccum for 20 to 30 minutes, until 600 microns of vaccum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pres­sure would indicate a possible leak or moisture
remaining in the system. With valves A and B closed, stop the vacuum pump.
4) Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 37B. Open valve C. Discharge the line at the manifold connection.
5) The system is now ready for final charging.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
2) Connect the charging cylinder as shown in figure 30B. With valve C open, discharge the hose at the manifold connection.
3) Open valve A and allow the proper charge to enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not take it. Close valve A.
5) With the unit running, open valve B and add the balance of the charge.
a.
Do not add the liquid refrigerant to the Low-side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps b. and c. until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos braze and braze pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.
NOTICE
www.sylvane.com 1-800-934-9194
2. EVAPORATOR
1. Remove the cabinet.
2. Remove the 2 screws which fasten the evaporator.
3. Move the evaporator sideways carefully.
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections.
5. Remove the evaporator carefully.
6. Re-install the component by referring to notes. (See Figure 29)
3. CAPILLARY TUBE
1. Remove the cabinet.
2. After discharging the refrigerant completely,
unbraze the interconnecting tube at the capillary tube.
3. Remove the capillary tube.
4. Re-install the component by referring to notes.
Figure 29
Service Manual 15
Disassembly
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
A
COMPOUND GAUGE
EVAPORATOR (LOW PRESSURE SIDE)
COMPRESSOR
CAPILLARY TUBE
CONDENSER (HIGH PRESSURE SIDE)
SEE INSETS
BELOW
MANIFOLD
GAUGE
B
Figure 30A-Pulling Vacuum
Figure 30B-Charging
A
B
EXTERNAL VACUUM PUMP
A
CHARGING CYLINDER
LOW
HI
B
C
www.sylvane.com 1-800-934-9194
Service Manual 16
Schematic Diagram
Circuit Diagram
LOCATION
NO.
1
2
3
4
5
6
7
8
Q'TY
PER SET
1
1
1
1
1
1
1
1
DESCRIPTION
POWER CORD ASSEMBLY
FAN MOTOR
COMPRESSOR
DISPLAY P.W.B ASSEMBLY
MAIN P.W.B ASSEMBLY
THERMISTOR
CAPACITOR
OWERLOAD PROTECTOR
www.sylvane.com 1-800-934-9194
2
7
1
6
4
3
8
5
17 Room Air Conditioner
Electronic Control Device
Schematic Diagram
www.sylvane.com 1-800-934-9194
www.sylvane.com 1-800-934-9194
Components Location(For Main P.W.B ASM)
Schematic Diagram
Service Manual 18
19 Room Air Conditioner
Troubleshooting Guide
Troubleshooting Guide
Piping System
Figure 38 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE
OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH
SUCTION LINE COOL LOW PRESSURE VAPOR
COOLED AIR
COMPLETE LIQUID BOIL OFF POINT
LIQUID PRESSURE DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT DISCHARGED AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR LIQUID REFRIGERANT LOW PRESSURE VAPOR
ROOM AIR CONITIONER
EVAPORATOR COILS CONDENSER COILS
CYCLE OF REFRIGERATION
Figure 34
www.sylvane.com 1-800-934-9194
CONDENSER COIL
FAN
CAPILLARY TUBE
MOTOR
COMPRESSOR
BLOWER
EVAPORATOR COIL
Service Manual 20
Troubleshooting Guide
Troubleshooting Guide
In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling.
Ineffective Cooling
Satisfactory operation with temperature difference of inlet & outlet air; 44~50°F (7~10°C)
Replacement of unit if the unit is beyond repair.
Check outdoor coil (heat exchanger) and fan operation.
Check heat load increase.
Check cold air circulation for smooth flow.
Check gas leakage.
Clean condenser.
Not on separate circuit
Check inside gas pressure.
Adjust refrigerant charge.
Malfunction of compressor.
Replacement of compressor.
Check clogging in refrigera­tion circuit.
Repair clogging in refrigeration circuit.
Dirty indoor coil (heat exchanger)
Repair gas leak.
Malfunction of fan.
Clogging of air filter.
Obstruction at air outlet.
Remove obstruction.
www.sylvane.com 1-800-934-9194
21 Room Air Conditioner
Troubleshooting Guide
Fails to Start
Improper thermistor setting
Loose terminal connection
Improper wiring
Check of power source.
Drop of power voltage.
Capacitor check.
Replacement.
Check of control panel setting.
Compressor fails only to start.
Defect of compressor capacitor.
Replacement of compressor (Motor damaged).
Irregular motor insulation (Ω)
Irregular motor resistance (Ω)
Check of circuit breaker and fuse.
Check control panel.
Fan only fails to start.
Improper wiring.
Defect of fan motor capacitor.
Replacement of fan motor.
Regular but fails to start.
Replacement of compressor. (Locking of piston, metal.)
Irregular motor resistance (Ω) Irregular motor insulation (Ω)
www.sylvane.com 1-800-934-9194
Service Manual 22
Troubleshooting Guide
ELECTRIC PARTS TROUBLESHOOTING GUIDE:
Possible Trouble 1
The unit does not operate.
Is the Trans input power
AC 115V?
Is the Trans output power
about AC 14V?
Is shorted the Trans. output?
Is output Voltage of IC01D
DC 12V?
Is output Voltage of IC02D
DC 5V?
Is the voltage No.18 of Micom
DC 5V?
Exchange Main P.W.B Ass'y.
Is the
connection between
Main and Display
all right?
Is the reset circuit all right?
(The No.14 of Micom
is 5V.)
Check the Fuse.
Check the wiring diagram.
Check the Main
P.W.B pattern.
Exchange the Trans.
Exchange D02D~D05D.
Exchange IC01D.
Exchange IC02D.
Exchange IC01A.
Connect connector
exactly.
Check the
P.W.B
pattern.
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES
www.sylvane.com 1-800-934-9194
23 Room Air Conditioner
Troubleshooting Guide
Is Temp.
setting set lower than Room
Temp.-0.5°C?
Is the voltage No.10
of IC01M 0V?
Exchange IC01M.
Set the Temp. setting to lower Temp.
Wait 3 Minutes
Is the Unit for 3 minutes
delay?
Exchange MAIN P.W.B Ass'y.
Is the voltage N0.7 of
IC01M DC 5V?
Check the RY-COMP.
Check the wiring
Diagram.
NO
NO
NO NO
YES
YES
YES
YES
Possible Trouble 2
The compressor does not operate.
Is the wire connection of
RY-COMP all right?
Check the RY-COMP.
Connect LEAD Wire to
RY-COMP again.
NO
YES
Possible Trouble 3
The compressor always operate.
Exchange IC01M.
Exchange IC01M.
Is the voltage NO.1 or 4
of IC01M DC 5V?
Is the voltage NO.13 or 16
of IC01M 0V?
Check the RY-Hi or RY-Lo.
Check the wiring diagram.
NO
NO
YES
YES
Possible Trouble 4
Fan does not operate.
www.sylvane.com 1-800-934-9194
Service Manual 24
Troubleshooting Guide
Is the voltage of Battery
about over 2.3V?
Exchange Receiver Ass'y.
Is the connection of CN-DISP1 all right?
Is the voltage No.16
of CN-DISP1 on Main P.W.B
Ass'y DC 5V?
Exchange the battery.
Check the P.W.B pattern.
Connect connector to CN-DISP1 exactly.
NO
NO
NO
YES
YES
YES
Possible Trouble 5
Romote controller does not operate.
NO
NO
NO
NO
YES
YES
YES
Is the IC01G all right?
Is the connection of CN-DISP1 all right?
Exchange the display P.W.B Ass'y.
Exchange IC01G.
Exchange Q01G,
Q02G, Q03G, Q04G
Connect connector to CN-DISP1 exactly.
Does the Q01G,
Q02G, Q03G Q04G operate normally
on main P.W.B Ass'y?
Possible Trouble 6
It displays abnormally on Display P.W.B Ass'y.
www.sylvane.com 1-800-934-9194
25 Room Air Conditioner
Troubleshooting Guide
ROOM AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING MINIMUM MAXIMUM
115V ± 10% 103.5V 126.5V
COMPLAINT CAUSE REMEDY
Fan motor will not run. No power Check voltage at outlet. Correct if none.
Power supply cord Check voltage to rotary switch. If none, check
power supply cord. Replace cord if circuit is open.
Rotary switch Check switch continuity. Refer to wiring diagram
for terminal identification. Replace switch if defective.
Wire disconnected or Connect wire. Refer to wiring diagram for connection loose terminal identification. Repair or replace loose
terminal.
Capacitor (Discharge Test capacitor. capacitor before testing.) Replace if not within ±10% of manufacturer's
rating. Replace if shorted, open, or damaged.
Will not rotate Fan blade hitting shroud or blower wheel hitting
scroll. Re-align assembly. Units using slinger ring condenser fans must
have 0.22~0.25 inch clearance to the base. If necessary, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Fan motor runs. Revolves on overload Check voltage. See limits on this page.
If not within limits, call an electrician. Test capacitor.
Check bearings. Does the fan blade rotate
freely?
If not, replace fan motor. Pay attention to any change from high speed to
low speed. If the speed does not change, replace the motor.
www.sylvane.com 1-800-934-9194
Service Manual 26
Troubleshooting Guide
COMPLAINT CAUSE REMEDY
Fan motor noise. Fan If cracked, out of balance, or partially missing,
replace it.
Blower If cracked, out of balance, or partially missing,
replace it. Loose set screw Tighten it. Worn bearings If knocking sounds continue when running or
loose, replace the motor. If the motor hums or
noise appears to be internal while running,
replace motor.
Compressor will not run, Voltage Check voltage. See the limits on the preceding fan motor runs. page. If not within limits, call an electrician.
Wiring Check the wire connections; if loose, repair or
replace the terminal. If the wires are discon-
nected, refer to wiring diagram for identification,
and replace the wires. Check the wire connections;
If not according to the wiring diagram, correct
the connections.
Thermistor Check the TEMP control. If not at the lowest
number, set TEMP control to this setting and
restart the unit.
Check the continuity of the thermistor. Replace
the thermistor if the circuit is open.
Rotary Check for continuity, refer to the wiring diagram
for terminal identification. Replace the switch if
the circuit is open. Thermostat Check the position of knob. If not at the coldest
setting, advance the knob to this setting and
restart the unit.
Check the continuity of the thermostat. Replace
the thermostat if the circuit is open.
Capacitor (discharge Check the capacitor. capacitor before Replace if not within ±10% of manufacturer’s servicing.) rating, replace if shorted, open, or damaged.
Compressor Check the compressor for open circuit or
ground. If open or grounded, replace the
compressor. Overload
Check the compressor overload if externally mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)
www.sylvane.com 1-800-934-9194
27 Room Air Conditioner
COMPLAINT CAUSE REMEDY
Compressor cycles on Voltage Check the voltage. See the limits on the overload. preceding page. If voltage is not within these limits,
call an electrician. Overload Check overload, if externally mounted.
Replace if open. (If the compressor temperature
is high, remove the overload, cool, and retest.)
Compressor cycles on Fan motor If not running, determine the cause. Replace if
overload. required.
Condenser air flow Remove the cabinet, inspect the interior surface restriction of the condenser. If restricted, clean carefully
with a vacuum cleaner (do not damage fins) or
brush. Clean the interior base before
re-assembling. Condenser fins If the condenser fins are closed over a large
(damaged) area on the coil surface, head pressures will
increase, causing the compressor to cycle.
Straighten the fins or replace the coil. Capacitor Test the capacitor. Wiring Check the terminals. If loose, repair or replace. Refrigeration system Check the system for a restriction.
Insufficient cooling Air filter If restricted, clean or replace.
Unit undersized Determine if the unit is properly sized for the
area to be cooled.
Excessive noise Blower or fan Check the set screw, or clamp. If loose or miss-
ing, correct. If the blower or fan is hitting scroll
or barrier, rearrange the air handling parts. Copper tubing Remove the cabinet and carefully rearrange the
tubing not to contact the cabinet,
compressor, shroud, and barrier.
Troubleshooting Guide
www.sylvane.com 1-800-934-9194
www.sylvane.com 1-800-934-9194
Exploded View
Exploded View
731273
267110
354210
130910
749740
359012
148000
349600
346811
554030
559010
352380
W48602
149980
135314
159830
349480
147581
135312
249950
238310
349001
130410
268711-1
567480
264110
146812
W0CZZ
567502
554160
550140
352115-1 352115-2
552102
552113
352113
237200
268711-2
135510
35211A
Ser vice Man ual 28
29 Room Air Conditioner
Replacement Parts list
www.sylvane.com 1-800-934-9194
LocNo CP06E10 CP08E10 DESCRIPTION REMARK 130410 67302912 67302905 Base Assy Single R 349001 67303502 67303502 Damper Assembly R 130910 67303714 67303714 Cabinet Assy Single R 135312 67306017 67306017 Grille Assy Front R 135314 67306110 67306110 Grille Assy Inlet R 135510 67400148 67400148 Cover R 147581 67306208 67306208 Louver,Horizontal R 147582 67306264 67306264 Louver,Vertical R 149980 67303108 67303104 Shroud R 159830 67304309 67304309 Filter (Mech) R 238310 67500142 67500142 Escutcheon R 567480 67307806 67307806 Thermistor R 264110 67300020 67300020 Power Cord Assy R 267110 67307704 67307704 Remote Controller R 249950 67305511 67305513 Case Assembly,Control R 237200 67305512 67305512 Panel,Control R
268711-1 67307621 67307621 PWB(PCB) Assy Display R 268711-2 67307622 67307622 PWB(PCB) Assy Main R
146812 67300902 67300902 Swing Louver Motor R 349600 67303604 67303604 Bracket,Motor R 346811 67303013 67303005 Motor Assy Single R 349480 67303412 67303412 Orifice R
352380 67302736 67302736 Duct Assembly R 552102 67400188 67400190 Tube Assy Capillary R 550140 67301900 67301901 Isolator Comp R 559010 67303203 67303203 Fan Assy Axial R 359012 67302609 67302609 Fan Turbo R 148000 67303901 67303901 Supporter R 567502 67301405 67301406 O.L.P. Overload Protect R
W0CZZ 67300718 67302726 Capacitor R 731273 67306312 67306312 installation Kit w/Curtain R
W48602 67302500 67302500 Clamp Spring R
749740 67304002 67304002 Upper Guide Cabinet R
Post Office Box 1540 4200 N. Pan Am Expressway San Antonio, Texas 78295-1540
(210) 357-4400 FAX (210) 357-4490
FRIEDRICH AIR CONDITIONING CO.
Visit our web site at www.friedrich.com
Use Factory Certified Parts...
www.sylvane.com 1-800-934-9194
CP06 CP08 SVC PARTS 2008(07/08)
Loading...