Friedrich CP05C10 User Manual 2

Room Air Conditioner
Service and Parts
Manual
CP05.Svc(05/06)
CP05C10
—2—
CONTENTS
1.1 FEATURES.....................................................................................................................................................3
1.2 SPECIFICATIONS .........................................................................................................................................3
1.3 LOCATIONS OF CONTROLS .......................................................................................................................4
1.4 SAFETY PRECAUTIONS ..............................................................................................................................4
1.5 INSULATION RESISTANCE TEST ................................................................................................................4
2. DISASSEMBLY INSTRUCTIONS ................................................................................................5
2.1 MECHANICAL PARTS ..................................................................................................................................5
2.1.1 FRONT GRILLE ....................................................................................................................................5
2.1.2 CABINET................................................................................................................................................5
2.1.3 CONTROL BOARD................................................................................................................................5
2.2 AIR HANDLING PARTS ................................................................................................................................6
2.2.1 AIR GUIDE UPPER ..............................................................................................................................6
2.2.2 ORIFICE, TURBO FAN AND FAN .........................................................................................................6
2.2.3 MOTOR ..................................................................................................................................................7
2.2.4 AIR GUIDE.............................................................................................................................................7
2.3 ELECTRICAL PARTS ....................................................................................................................................7
2.3.1 OVERLOAD PROTECTOR ...................................................................................................................7
2.3.2 COMPRESSOR .....................................................................................................................................8
2.3.3 CAPACITOR ..........................................................................................................................................8
2.3.4 THERMOSTAT .......................................................................................................................................8
2.3.5 ROTARY SWITCH..................................................................................................................................8
2.3.6 POWER CORD .....................................................................................................................................9
2.4 REFRIGERANT CYCLE ................................................................................................................................9
2.4.1 CONDENSER .......................................................................................................................................9
2.4.2 EVAPORATOR ....................................................................................................................................10
2.4.3 CAPILLARY TUBE ..............................................................................................................................10
3. TROUBLESHOOTING GUIDE ....................................................................................................
3.1 OUTSIDE DIMENSIONS..............................................................................................................................12
3.2 PIPING SYSTEM........................................................................................................................................13
3.3 TROUBLESHOOTING GUIDE....................................................................................................................14
12
4. CIRCUIT DIAGRAM...........................................................................................................................19
5. EXPLODED VIEW..............................................................................................................................20
6. SERVICEPARTS LIST....................................................................................................................21
1. PREFACE
CP05C10
This service manual provides various service information, including the mechanical and electrical parts, etc. This room air conditioner was manufactured and assembled under a strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 FEATURES
• DESIGNED FOR COOLING ONLY
• BUILT-IN ADJUSTABLE THERMOSTAT
• WASHABLE ONE-TOUCH FILTER
• COMPACT SIZE
1.2 SPECIFICATIONS
MODELS
ITEMS
COOLING CAPACITY (BTU/h) 5,100
POWER SUPPLY (Phase, V, Hz)1ø, 115V, 60HZ
INPUT (W) 520
OPERATING CURRENT (AMP.) 4.4
REFRIGERANT CONTROL CAPILLARY TUBE
REFRIGERANT CHARGE (R-22) 330g (11.6 oz)
INSIDE FAN TURBO FAN
OUTSIDE FAN PROPELLER FAN WITH SLINGER RING
AIR DISCHARGE 2-WAY (RIGHT AND LEFT)
CHASSIS TOP-DOWN
PROTECTOR
TEMPERATURE CONTROL THERMISTOR
FAN MOTOR 6 POLES, 21W
• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR FOR FAN MOTOR
—4—
1.3 LOCATIONS OF CONTROLS
1
2
3
4
6
5
MONEY SAVER
2
The fan stops when the compressor stops cooling.
Approximately every 3 minutes the fan will turn on and sample the room air to determine if more cooling is needed.
TEMPERATURE SETTING
1
These buttons control the temperature of the room.
The temperature can be set within a range of 60°F to 86°F, in increments of 1°F.
ON/OFF TIMER
4
ON–When the air conditioner is off, it can be set to automatically
come on in 1 to 12 hours from its previous setting. Each touch will increase the timer by 1 hour. OFF–When the air conditioner is on, it can be set to automatically turn off in 1 to 12 hours. Each touch will increase the timer by 1 hour. After the timer has been on for 30 minutes, the temperature will automatically rise 2°F, and after another 30 minutes, it will automatically rise 2°F again. The temperature will then stay the same until the timer goes OFF.
To cancel the timer, press the TIMER pad until the display time disappears.
POWER
5
To turn the unit ON, push the button. To turn the unit OFF, push the button again.
This button takes priority over any other buttons.
When you first turn it on, the unit is on the High cool mode and the temp. at 72°F
FAN SPEED
6
Everytime you push this button it will rotate between the following fan speeds:
High (F3) Low(F1) Medium (F2) High (F3)
Power
Temp
Fan Speed
Timer Mode
Money
Saver
5 1
6 34
2
OPERATION MODE SELECTOR
3
Everytime you push this button, it will rotate between the COOL, FAN and DRY modes.
5
2. DISASSEMBLY INSTRUCTIONS
2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE
1. Pull the inlet grille forward.
2. Remove the screw securing the Front Grille. (Fig. 3)
3. Push the grille up from the bottom and pull the top of the grille away from the case to lift the top tabs out of their slots. (Fig. 4)
4. Carefully position the grille, bottom first, and snap back into place.
5. Reposition the screw that secures the front grille
2.1.2 CABINET
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to section 2.1.1)
3. Remove 9 screws that secure the cabinet to the
base pan and condenser. (See Figure 3)
4. Lift the cabinet from the unit.
5. Re-install by referring to the procedures above.
2.1.3 CONTROL 2.1.3 CONTROL PANEL
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove 1 screws that secure the control board to
base pan and air guide. (See Figure 4)
5. Pull the control 5. Pull the control panel toward yourself.
the fan motor and compressor. (See Figure 5)
7. Re-install components by referring to procedures
above. (Refer to wiring diagram on page 23 in this manual or inside control board.)
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
NOTE : Controls, wires, and capacitor are now
accessible for servicing. Discharge the capacitor before servicing. See step
2.3.3 on page 8 for procedures.
6
2.2 AIR HANDLING PARTS
2.2.1 AIR GUIDE UPPER
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove the control panel.
(Refer to Section 2.1.3)
5. Remove 2 screws that secure the upper air guide
to air guide lower. (See Figure 6)
6. Lift upper air guide upward.
7. Re-install by referring to the procedures above.
2.2.2 ORIFICE, TURBO FAN AND FAN
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove the control board.
(Refer to Section 2.1.3)
5. Remove the air guide upper.
(Refer to Section 2.2.1)
6. Remove 2 screws that secure the base pan to
condenser. (See Figure 7)
7. Remove screw that secures the shroud to
channel of condenser.
8. Press the snap area of shroud with your thumbs.
This allows you to remove it from the condenser.
9. Lift the compressor upward with the evaporator
and condenser. (See Figure 7)
10. Remove the orfice by pushing the snap area of the air guide blower. (See Figure 8)
11. Remove the clamp springs which are clamped to the shaft of fan and turbo fan by hand plier. (See Figure 9)
12. Pull the fan and turbo fan outward.
13. Remove the shroud.
14. Re-install by referring to the procedures above.
Figure 6
Figure 7
Figure 8
Figure 9
7
2.2.3 MOTOR
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove the control panel. (Refer to Section 2.1.3)
5. Remove the upper air guide. (Refer to Section 2.2.1)
6.
Remove the compressor, turbo fan, fan and shroud. (Refer to
Section
2.2.2)
7.
Remove 2 screws that secure the motor to the motor mount . (See Figure 10)
8. Remove the motor.
9.
Re-install by referring to the procedures above.
2.2.4 AIR GUIDE
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove the control panel. (Refer to Section 2.1.3)
5. Remove the upper air guide . (Refer to Section 2.2.1)
6.
Remove the compressor, turbo fan, fan and shroud. (Refer to
Section
2.2.2)
7.
Remove the motor. (Refer to
Section
2.2.3)
8. Remove 2 screws that secure the air guide to the base pan. (See Figure 11)
9. Push the air guide backward and lift it upward. (See Figure 11)
10. Re-install by referring to the procedures above.
2.3 ELECTRICAL PARTS
2.3.1 OVERLOAD PROTECTOR
1. Remove the front grille and cabinet. (Refer to Section 2.1)
2. Remove the nut which fastens the terminal cover.
3. Remove the terminal cover.
4. Remove all the leads from the overload protector.
5. Remove the overload protector.
6. Re-install the components by referring to the removal procedure above. (See Figure 12 and 13)
Figure 10
Figure 12
Figure 13
Figure 11
8
2.3.2 COMPRESSOR
1. Remove the front grille and cabinet. (Refer to Section 2.1)
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the overload protector. (Refer to Section 2.3.1)
4. After discharging the unit completely, unbrace the suction and discharge pipes at the compressor connections.
5. Remove 3 nuts which fasten the compressor.
6. Remove the compressor.
7. Re-install by referring to the removal procedure above. (See Figure 14)
2.3.3 CAPACITOR
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control panel. (Refer to Section 2.1.3)
3. Discharge the capacitor by placing a 20 K resistor across the capacitor terminals.
4. Remove the screw which fastens the capacitor clamp.
5. Remove all the leads of capacitor terminals.
6. Re-install the components by referring to the removal procedure above. (See Figure 15)
2.3.4 THERMISTOR
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control panel. (Refer to Section 2.1.3)
3. Disconnect the thermistor terminals from main P.W.B assembly.
4. Remove the thermistor.
5. Re-install the components by referring to the removal procedure above. (See Figure 16)
2.3.5 CONTROL BOARD
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control panel. (Refer to Section 2.1.3)
3. Pull the control board forward and pull out it.
4. Remove 2 lead wire terminals.
5. Re-install the components by referring to the removal procedure above. (See Figure 17)
Figure 14
Figure 15
Figure 16
Figure 17
9
2.3.6 POWER CORD
1. Disconnect the unit from source of power.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove a screw that secures control panel to base pan. (Refer to Section 2.1.3)
5. Pulls the control board toward you.
6. Disconnect the 2 receptacles and remove the grounding screw.
7. Remove a screw securing the clip with cord to the control panel.
8. Pull the power cord.
9. Re-install by referring to procedures above.
2.4 REFRIGERANT CYCLE
2.4.1 CONDENSER
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the air guide. (Refer to Section 2.2.1)
4. Remove 2 screws which fasten the condenser.
5. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
6. Remove the condenser.
7. Re-install by referring to the procedures above.
Figure 18
Figure19
2.4.2 EVAPORATOR
1. Remove the cabinet.
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the upper air guide . (Refer to Section
2.2.1)
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
5. Remove the evaporator.
6. Re-install by referring to the procedures above.
2.4.3 CAPILLARY TUBE
1. Remove the cabinet.
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the upper air guide. (Refer to Section
2.2.1)
4. After discharging the refrigerant completely, unbraze the interconnecting tube of the capillary tube.
5. Remove the capillary tube.
6. Re-install by referring to the procedures above.
NOTES
Replacement of the refrigeration cycle.
1. When replacing the refrigerating cycle, be sure to discharge the refrigerant by using a refrigerant recovery system.
2. After discharging the unit completely, remove the desired components, and unbraze the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with service valves.
5. After completing the above procedures, the valve must be removed .
6. Evacuate as follows: 6-1. Connect the vacuum pump, as illustrated in
figure 21A.
6-2. Start the vacuum pump. Slowly open manifold
valves A and B with two full turns counter­clockwise and leave the valves closed. The vacuum pump is now pulling through valves A and B up to valve C by means of manifold and the entire system.
CAUTION : If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counter-clock-
wise. This will keep oil from foaming and being drawn into the vacuum pump.
6-3. Operate the vacuum pump for 20 to 30 min-
utes, until 600 micron vacuum is obtained. Close valves A and B and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.
6-4. Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure 23B. Open valve C. Discharge the line at the manifold connection.
6-5. The system is now ready for final charging.
7. Recharge as follows: 7-1. Rotary compressor systems are charged from
the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which is installed as the system is opened.
7-2. Connect the charging cylinder as shown in fig-
ure 21B. With valve C open, discharge the hose at the manifold connection.
7-3. Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
7-4. If more charge is required, the high-side will
not take it. Close valve A.
7-5. With the unit running, open valve B and add
the balance of the charge. a. Do not add the liquid refrigerant to the low-
side.
b. Watch the low-side gauge, allow pressure to
rise to 30 lbs.
c. Turn off valve B and allow the pressure to
drop.
d. Repeat steps B and C until the balance of
the charge is in the system.
7-6. When the unit is operating correctly, use the
pinch-off tool with the unit still running and the clamp on the pinch-off tube. Using a tube cut­ter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit, allow setting for a while and then test the leak­age of the pinch-off connection.
10
11
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment, pinch-off tool capable of making a vapor proof seal, leak detector, tubing cutter, hand tools to remove components and service valve.
B
A
B
A
B
A
COMPOUND GAUGE
SEE INSETS
BELOW
CAPILLARY TUBE
EVAPORATOR (LOW PRESSURE SIDE)
COMPRESSOR
CONDENSER (HIGH PRESSURE SIDE)
EXTERNAL VACUUM PUMP
LO HI
CHARGING CYLINDER
MANIFOLD
GAUGE
C
Figure 21A-Pulling Vacuum Figure 21B-Charging
12
2.4.4 ELECTRICAL DATA
USE OF EXTENSION CORDS
Because of potential safety hazards, we strongly discourage the use of an extension cord. However, if you wish to use an extension cord, use a CSA certified/UL-listed 3-wire (grounding) extension cord, rated 15A, 125V.
Do not under any circumstances cut or remove the grounding prong from the plug.
Line Cord Plug Use Wall Receptacle Power Supply
Power supply cord with 3-prong grounding plug
Standard 125V, 3-wire grounding receptacle rated 15A, 125V AC
Use 15 AMP, time delay fuse, or circuit breaker.
3. TROUBLESHOOTING GUIDE
3.1 OUTSIDE DIMENSIONS (unit: mm [in])
370 (14 9/16")
312 (12 1/4")
370 (14 9/16")
312 (12 1/4")
29 (1
5
/32")
120 (4 3/4")
27.5 (1
3
/32")
346 (13
5
/8")
472 (18 9/16")
42 (1 21/32")
42 (1
21
/32")
155(6
3/32
")
12
(0.4
1/16
")
472 (18 9/16")
22.5(0.8
3/32
")
13
3.2 PIPING SYSTEM
Following is a brief description of the important components and their function in what is called the refrigeration system. Reference should be made to Figure 32 to follow the refrigerating cycle and the flow of the refrigerant in the cooling cycle.
COOLED AIR
HOT DISCHARGED AIR
MOTOR
COMPRESSOR
ROOM AIR HEAT LOAD
CAPILLARY TUBE
(LIQUID REFRIGERANT)
LIQUID OUTLET
VAPOR INLET COMPLETE LIQUID BOIL OFF POINT
SUCTION LINE COOL LOW PRESSURE VAPOR
LIQUID PRESSURE DROP
DISCHARGE
LINE
NOT HIGH PRESSURE
VAPOR
OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH
EVAPORATOR COILS CONDENSER COILS
ROOM AIR CONDITIONER
CYCLE OF REFRIGERATION
HIGH PRESSURE VAPOR LIQUID REFRIGERANT LOW PRESSURE VAPOR
OIL
Figure 32
CONDENSER COILS
FAN
CAPILLARY
MOTOR
TUBE
TURBO FAN EVAPORATOR
COILS
14
3.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused by an electrical defect. The other is Ineffective Air Con-
ditioning caused by a defect in the refrigeration circuit and improper application.
Unit is running but cooling is ineffective.
Ineffective Cooling
Satisfactory operation with temperature difference of inlet & outlet air; 18~26°F.
Replacement of unit if the unit is beyond repair.
Check outdoor coil (heat exchanger) and fan operation.
Check heat load increase.
Check cold air circulation for smooth flow.
Check for gas leakage.
Clean condenser.
Not on dedicated circuit.
Check inside gas pressure.
Adjust refrigerant charge.
Malfunction of compressor.
Replacement of compressor.
Check for restriction in refri ­geration circuit.
Remove restriction in refrigeration circuit.
Dirty indoor coil (heat exchanger)
Repair gas leak.
Malfunction of fan.
Clogging air filter.
Obstruction at air outlet.
Remove obstruction.
15
Fails to Start
Improper thermostat setting
Loose terminal connection
Improper wiring
Check voltage power source.
Drop of power voltage.
Capacitor check.
Replacement.
Check control switch setting.
Compressor fails to start.
Defect of compressor or capacitor.
Replacement of compressor (Motor damaged).
Irregular motor insulation (Ω)
Irregular motor resistance (Ω)
Check of circuit breaker and fuse.
Gas leakage of feeler bulb of thermostat.
Check control switch.
Fan fails to start.
Improper wiring.
Defect of fan motor or capacitor.
Replacement of fan motor.
Regular but fails to start.
Replacement of compressor.
Irregular motor resistance (Ω) Irregular motor insulation (Ω)
COMPLAINT CAUSE REMEDY
Fan motor will not run. No power Check voltage at outlet. Correct if none.
Power supply cord Check voltage to electronic control board. If none,
check power supply cord. Replace cord if circuit is open.
Wire disconnected or Connect wire. Refer to wiring diagram for connection loose terminal identification. Repair or replace loose
terminal.
Capacitor (Discharge Test capacitor. capacitor before testing.) Replace if not within ±10% of manufacturer's
rating. Replace if shorted, open, or damaged.
Will not rotate Fan blade hitting shroud or blower wheel hitting
scroll. Re-align assembly. Units using slinger ring condenser fans must
have 1/4" inch clearance to the base. If necessary, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Fan motor runs. Revolves on overload Check voltage. See limits on this page.
If not within limits, call an electrician. Test capacitor.
Check bearings. Does the fan blade rotate freely? If not, replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
16
ROOM AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING MINIMUM MAXIMUM
115V ± 10% 103.5V 126.5V
17
COMPLAINT CAUSE REMEDY
Fan motor noise. Fan blade If cracked, out of balance, or partially missing,
replace it.
Blower wheel If cracked, out of balance, or partially missing,
replace it.
Loose set screw Tighten it.
Worn bearings If knocking sounds continue when running
replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
Compressor will not run, Voltage Check voltage. See the limits on the preceding fan motor runs. page. If not within limits, call an electrician.
Wiring Check the wire connections; if loose, repair or
replace the terminal. If the wires are discon­nected, refer to wiring diagram for identification, and replace the wires. Check the wire connections; If not according to the wiring diagram, correct the connections.
Thermistor Check the TEMP control. If not at the lowest
number, set TEMP control to this setting.
Check the continuity of the thermistor. Replace
the control board if the circuit is open.
Capacitor (discharge Check the capacitor. capacitor before Replace if not within ±10% of manufacturer’s servicing.) rating, replace if shorted, open, or damaged.
Compressor Check the compressor for open circuit or
ground. If open or grounded, replace the compressor.
Overload
Compressor cycles on Voltage Check the voltage. See the limits on the overload. preceding page. If voltage is not within these limits,
Overload Check overload, if externally mounted.
Check the compressor overload if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
call an electrician.
Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
18
COMPLAINT CAUSE REMEDY
Compressor cycles on Fan motor If not running, determine the cause. Replace if overload. required.
Condenser air flow Remove the cabinet, inspect the interior surface restriction of the condenser. If restricted, clean carefully
with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before re-assembling.
Condenser fins If the condenser fins are closed over a large (damaged) area on the coil surface, head pressures will
increase, causing the compressor to cycle.
Straighten the fins or replace the coil. Capacitor Test the capacitor. Wiring Check the terminals. If loose, repair or replace. Refrigeration system Check the system for a restriction.
Insufficient cooling Air filter If restricted, clean or replace.
Unit undersized Determine if the unit is properly sized for the
area to be cooled.
Excessive noise Blower or fan Check the set screw, or clamp. If loose or miss-
ing, correct. If the blower or fan is hitting scroll
or barrier, rearrange the air handling parts. Copper tubing Remove the cabinet and carefully rearrange the
tubing not to contact the cabinet,
compressor, shroud, and barrier.
19
4. CIRCUIT DIAGRAM
WH(BL)
POWER INPUT
BK(BR)
(Ribbed) (Plain)
GN/YL
(GN)
GN/YL(GN)
THERMISTOR
BK BK BLRDBL
RD
CN-TH1
YL YL
OR(BR) OR(BR)
OR
SYNC
MOTOR
RY-LO
RY-HI
CN-WORK
CN-SYNC CN-DISP
DISPLAY P.W.B ASM
RY-SYNC
250V/T2A (115V/T2A)
TRANS
FORMER
ZNR
43
RY-COMP
MAIN P.W.B ASM
BK
BK
WH
BK
RD BL BL
OLP
RD
MOTOR
CAPACITOR
F
R
S
COMP.
C
C
H
3854A20022K WIRING DIAGRAM
RY-MID
FUSE
LOC
ATION
NO.
DESCRIPTION
1 POWER CORD ASSY
PART NO.
CP05C10
67300020
2 FAN MOTOR 67303026
3 COMPRESSOR 67301616
67300718
4 CAPACITOR
OVERLOAD PROTECTOR 67301405
5
Q'TY
PER SET
1
1 1 1
1
20
5. EXPLODED VIEW
352390
130410
359012
W48602
354210
349480
352390-1
149980
559011
346811
554030
W48602
130910
550140
554160
567502
352115
552102
352111
352113
35211A
135313
135303
152302
135312
132111-2
132111-1
147582-1
147581
159900-1
269310
238310
W0CZZ
249950
268714
263230
137215
268712
267110
749740
6. SERVICE PARTS LIST
CP05C10
21
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
R: Service Parts N: Non Service Parts
LocNo FRIEDRICH DESCRIPTION
130410 67302921 Base Assy Single
130910 67303709 Cabinet Assy Single
135312 67306003 Grille Assy Front
135313 67304200 Grille Assy Inlet
14758
1 67304600 Link
147582-
149980 67303115 Shroud
152302 67304300 Filter (Mech)
238310 67500115 Escutcheon
269310 67300020 Power Cord Assy 349480 67307700 Remote Controller
352111 6730761
352115 67307612 PWB(PCB) Assy Main 35238
352390 67303026 Motor Assy Single 354210 67303410 Orifice
35211A 67302222 Tube Assy Suction
352113 67302306 Tube Assy Discharge
352115 6730202
352390-1 67302727 Air Guide Assy Upper
35239
550140 67301900 Isolator Comp
352111 67302120 Tube Assy Capillary 554160 67301616 Compressor
559011 67302613 Fan Assy Axial
359012 67302612 Fan Turbo 567502 67301405 O.L.P.
W0CZZ 67300718 Capacitor
1 67304501 Louver Vertical 2 ea.
0 67307806 Thermistor
0 67302734 Air Guide Assy Lower
CP05C10
1 PWB(PCB) Assy Display
1 Tube Assy Evaporator In
W48602 67302500 Clamp Spring
13211
1-1 67306310 Installation Kit w/Curtains L
13211
1-2 67306311 Installation Kit w/Curtains R
749740 67304005 Upper Guide Cabinet
22
MEMO
23
MEMO
Post Office Box 1540 4200 N. Pan Am Expressway San Antonio, Texas 78295-1540
(210) 357-4400 FAX (210) 357-4490
FRIEDRICH AIR CONDITIONING CO.
Visit our web site at www.friedrich.com
CP05.Svc (05/06)
Use Factory Certified Parts...
Loading...