Friedrich C24YJ, C36YJ Specsheet

Pro Series | Ductless Split Systems
SINGLE ZONE • CEILING CASSETTE HEAT PUMPS
The contractor’s line with extensive features to make installation and service
faster and easier. Exceptional efficiency and dependable performance.
MC24Y3J, MC36Y3J
Low prole indoor unit is recessed into the ceiling for a clean look and greater clearance.
NOTE: Grilles are sold separately.
Precision Inverter® technology (variable speed compressor)
Soft start compressor
Natural air flow
4-Way cooling
Surge Cool/Heat
Cooling/Heating/Fan mode
Dry mode
Sleep mode
Independent vane control
3 Fan speeds
Evaporator frost control
24-hour on/off timer
Auto restart
Auto changeover
Temperature display on remote
Ultra-quiet turbo fan
DiamonGold Advanced
Corrosion Protection
Clean, modern look
Flexible installation
ENERGY STAR
Precise air distribution
Capable of branch duct to
adjacent closet or bathroom
®
qualified models
Operates in extreme conditions
Built-in low ambient standard, down to 14°F (Cooling mode)
Low ambient operation down to
-4°F (Heating mode)
WIRELESS
REMOTE CONTROL
10 | FLOATING AIR® SERIES DUCTLESS
MR24UY3J MR36UY3J
PRECISION
WARRANTY
COMPRESSOR WARRANTY
PRO SERIES SPECIFICATIONS
PERFORMANCE RATINGS Single Zone Cassette - Heat Pumps
SYSTEM MODEL NO. C24YJ C36YJ INDOOR MODEL MC24Y3J MC36Y3J OUTDOOR MODEL MR24UY3J MR36UY3J
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 24,000 36,000 CAPACITY COOLING (MIN~MAX) Btu 9,700~26,700 14,000~42,000
@
CAPACITY HEATING CAPACITY HEATING @170 F (RATED) Btu 18,600 26,000 CAPACITY HEATING (MIN~MAX) Btu 10,900~30,000 14,500~45,000 COOLING AMPS 15.1 20.2 HEATING AMPS 16.0 24.0 SENSIBLE HEAT RATIO .77 .76 SEER 17.0 19.0 EER 12.6 13.5 HSPF 9.7 9.5 ENERGY STAR * Yes Yes MOISTURE REMOVAL Pts/h 5.1 7.7 AIRFLOW (LOW, MED, HIGH ) CFM 459 / 530 / 600 918 / 989 / 1,060 SOUND RATING - INDOOR H/M/L dB(A) 38/36/34 46/44/43 SOUND RATING - OUTDOOR dB(A) 62 67 OPERATING RANGE (COOLING) °FDB 5~118 5~118 OPERATING RANGE (HEATING) °FWB -4~64 -4~64 EST. YEARLY OPERATING COST $ 172 240
ELECTRICAL DATA
POWER SOURCE V 208/230/60/1 208/230/60/1 MINIMUM AMPACITY A 18.1 24.5 COOLING WATTS W 1910 2970 MAX. TD FUSE/BREAKER A 30 40 POWER AND COMMUNICATION CABLE
REFRIGERATION SYSTEM
REFRIGERANT R410A R410A COMPRESSOR TYPE Twin Rotary Twin Rotary CONNECTIONS Flare Flare LIQUID LINE O.D. in 3/8 3/8 SUCTION LINE O.D. in 5/8 5/8 FACTORY PRECHARGE ft 25 25 REFRIGERANT CHARGE oz 71 120 MIN./MAX. LINE LENGTH ft 25~164 25~246 MAX. HEIGHT DIFFERENCE ft 98 98
DIMENSIONS & WEIGHT
INDOOR UNIT W X H X D in 33-1/16 x 8-1/16 x 33-1/16 33-1/16 x 11-3/8 x 33-1/16 NET WEIGHT lbs 45 54 SHIPPING WEIGHT lbs 58 65 INDOOR UNIT GRILLE** W X H X D in 37-3/8 x 15/16 x 37-3/8 37-3/8 x 15/16 x 37-3/8 INDOOR UNIT GRILLE** NET WEIGHT lbs 11 11 OUTDOOR UNIT W X H X D in 37-7/16 x 32-7/8 x 13 37-13/32 x 54-3/8 x 13 NET WEIGHT lbs 132 203 SHIPPING WEIGHT lbs 146 227 TOTAL NET WEIGHT lbs 178 257 TOTAL SHIPPING WEIGHT lbs 203 293
470 F (RATED) Btu 27,000 40,000
No. x AWG
4 x 14AWG 4 x 14AWG
Your operating costs will depend on your utility rates and use. The estimated operating cost is based on a electricity cost of $ .12 per kWh. For more information, visit w ww.ftc.gov/energy.
*System meets ENERGY STAR® published minimums. **Models require grille. Sold separately. Due to continuing research in new energy-saving technology, specications are subject to change without notice.
11