Pipe
Pipe
Especially, the installation place is very important for the split type air
conditioner because it is very difficult to move from place to place after the
first installation.
Decide the mounting position together with the customer as follows:
The discharge direction can be selected as shown below.
CAUTION
Since 2-way outlet as shown below causes performance
problems, do not set it.
(4 directions)
(3 directions)
100 mm (4") or more
Piping position
(2
directions
)
100 mm (4") or more
100 mm (4") or more
(2
directions
)
100 mm (4") or more
INDOOR UNIT
(1) Install the indoor unit on a place having a sufficient strength so that it
withstands against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be
able to blow all over the room.
(3) Leave the space required to service the air conditioner.
(4) The ceiling rear height as shown in figure.
(5) A place from where the air can be distributed evenly throughout the
room by the unit.
(6) A place from where drainage can be extracted outdoors easily.
(7) Install the unit where noise and vibrations are not amplified.
Obstruction
Strong and durable ceiling
2,400 mm (94")
or more
1,000 mm (39")
or more
1,000 mm (39")
or more
Floor
SELECTING THE MOUNTING POSITION
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the
units will not topple or fall.
CAUTION
1 Do not install where there is the danger of combustible
gas leakage.
2 Do not install near heat sources.
3 If children under 10 years old may approach the unit,
take preventive measures so that they cannot reach
the unit.
(B) Slender setting(A) Standard setting
215 mm (8-15/32")
or more
250 mm (9-27/32")
or more
This mechanism enables the cassette body to move 35 mm (1-3/8")
downward and realizes installation to the space of 215 or 265 mm
(8-15/32" or 10-15/32"). No special works and option is needed.
You can select 2-way setting
[18 to 24 type]
(B) Slender setting(A) Standard setting
265 mm (10-15/32")
or more
300 mm (11-13/16")
or more
[30 to 54 type]
CONNECTION PIPE REQUIREMENT
CAUTION
Install heat insulation around both the gas and liquid pipes.
Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation location
of the refrigerant piping is expected to exceed 70%, install
heat insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that
is 15 mm (19/32") or thicker and if the expected humidity
exceeds 80%, use heat insulation that is 20 mm (3/4") or
thicker.
If heat insulation is used that is not as thick as specified,
condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of
0.045 W/(m·K) or less (at 68 °F).
ELECTRICAL REQUIREMENT
••
••
• Install all electrical works in accordance to the standard.
••
••
• Install the disconnect device with a contact gap of at least 3 mm (1/8")
in all poles nearby the units. (Both indoor unit and outdoor unit)
••
••
• Install the circuit breaker nearby the units.
••
••
• Use pipe with water-resistant heat insulation.
Connection cord (mm2)
MAX.
MIN.
2.5
1.5
••
••
• Electric wire size:
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
1 Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the piping and instal-
lation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always replace the con-
ventional piping and flare nuts with the R410A piping and flare nuts.
2 Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with con-
ventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF
20 threads per inch.]
3 Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
4 When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Contents of change
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm
2
) for high pressure.
–0.1 to 3.8 MPa (–76 cmHg to 38 kgf/cm
2
) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of
residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed,
deformed or discolored portion (especially on the interior surface). Otherwise, the
expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using
conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table. Never
use copper pipes thinner than that in the table even when it is available on
the market.
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
0.80 mm (0.0315 in.)
0.80 mm (0.0315 in.)
0.80 mm (0.0315 in.)
1.00 mm (0.0394 in.)
Pipe outside diameter
Thickness
Thicknesses of Annealed Copper Pipes (R410A)
CAUTION
This installation instruction sheet describes how to install the indoor unit only.
To install the outdoor unit, refer to the installation instruction sheet included with the outdoor unit.
GENERAL
This INSTALLATION INSTRUCTION SHEET briefly outlines where and
how to install the air conditioning system. Please read over the entire set
of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
14000, 18000 BTU/h 24000, 36000,
model 42000 BTU/h model
MODEL
Diameter
Liquid
Gas
6.35 mm (1/4 in.) 9.52 mm (3/8 in.)
12.70 mm (1/2 in.) 15.88 mm (5/8 in.)