Vert-I-Pak
®
Single Package Vertical Air Conditioning System
A-Series
24,000 BTU/h
Installation & Operation Manual
920-159-01 (10-03)
920-159-01 (10-03)
Table of Contents
Installation Recommendations......................................................................................................................................................... 3
I. General Specications
Model Number Identication Guide ................................................................................................................................... 4
VERT-I-PAK Chassis Specications...................................................................................................................................4
II. Installation
1. Utility Closet Dimensions ................................................................................................................................................... 5
2. Wall Plenum & Architectural Louver Installation ................................................................................................................ 6
3. Electrical Information ..................................................................................................................................................... 7-9
4. Indoor Return Air Grille Installation .................................................................................................................................. 10
5. Ductwork Preparation and CFM ....................................................................................................................................... 11
6. Chassis Installation.......................................................................................................................................................... 11
7. Chassis Final Connections (Electrical, Duct, Drain & Wall Thermostat)............................................................................12
8. Final Installation Checklist............................................................................................................................................... 12
III. Chassis Operation
9. Thermostat Control ..........................................................................................................................................................12
10. Low Ambient Protection for Compressor & Fan................................................................................................................12
11. Heating Defrost (Heat Pump Models only)........................................................................................................................12
12. Fresh Air Door...................................................................................................................................................................13
13. Condensate Disposal System .......................................................................................................................................... 13
IV. Service, Maintenance & Warranty
14. Servicing / Chassis Quick Changeouts.............................................................................................................................13
15. Routine Maintenance.......................................................................................................................................................13
16. Warranty ..........................................................................................................................................................................14
V. Vert-I-Pak Accessories .................................................................................................................................................... 15
Please read this manual thoroughly prior to equipment installation or operation. It is the installer’s
responsibility to properly apply and install the equipment. Installation must be in conformance with
the NFPA 70-2002 National Electric Code or current edition and Universal Mechanical Code current
edition and applicable local or national codes.
Proper installation is not difcult but it is essential.
2
920-159-01 (10-03)
12"
24"
60"
VPAK VPAK VPAK
POLE
FENCE
MAJOR OBSTRUCTION
BUILDING
OUTDOOR
CONDENSING
UNIT
72"
24"
SHRUB
6"
60"
60"
60"
6"
60"
60"
6"
60"
60"
SMALL RECESS OK
A
B
60"
60"
60"
60"
LARGER RECESS OK. IF A> 5xB
12"
6"
60"
60"
60"
6"
60"
60"
6"
60"
60"
SMALL RECESS OK
Vert-I-Pak Installation Recommendations
For proper unit performance and maximum operating life please refer to the minimum installation clearances
below.
Figure 1
VERT-I-PAK® units must be installed on an outside wall. Conned spaces and/or covered areas should be
avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more
units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical
clearance of 60" should be maintained between units. Units installed on the bottom oor should be mounted
at least 6" off of the ground.
Figure 2
Any time obstructions are present use
the following guidelines for proper
spacing from the VERT-I-PAK louver:
• For minor obstructions such as lamp
poles or small shrubbery a clearance
of 24" from the outdoor louver should
be maintained.
• For major obstructions such as a solid
fence, wall or other heat rejecting
device like a condensing unit, a minimum distance of 72" should be kept.
The above suggestions are for reference only and do not represent all possible installations. Please contact the factory
for information regarding affects of other installation arrangements.
By following these simple recommendations you can be condent that your Friedrich Vert-I-Pak® will provide years
of worry-free operation.
3
920-159-01 (10-03)
Section I. General Specications
VERT-I-PAK® MODEL IDENTIFICATION GUIDE
MODEL NUMBER V E A 24 K 50 RT A
SERIES
V=Vertical Series
E=Cooling with or without electric heat
H=Heat Pump
DESIGN SERIES
A = 32" and 47" Cabinet
NOMINAL CAPACITY
A-Series (Btu/h)
09 = 9,000
12 = 12,000
18 = 18,000
24 = 24,000
VOLTAGE
K = 208/230V-1Ph-60Hz
ENGINEERING CODE
OPTIONS
RT = Standard Remote Operation
SP = Seacoast Protected
ELECTRIC HEATER SIZE
A-Series
00 = No electric heat
25 = 2.5 KW
34 = 3.4 KW
50 = 5.0 KW
75 = 7.5 KW
10 = 10 KW
Vert-I-Pak® Chassis Specifications
MODEL: V(E,H)A24
Voltage (V) 230/208
Refrigerant R-22
Chassis Width 23.125
Chassis Depth 23.125
Chassis Height ** 47.25
Supply Duct Collar *** 10"
Drain Connection 3/4" FPT
Min. Circuit Amps See Nameplate
CFM Indoor See chart, pg. 11
Max. Duct ESP .4 in. water
NOTES:
** Height includes 2" duct collar & isolators under unit.
*** Factory collar accepts 10" ex duct.
4
920-159-01 (10-03)
electrical
entrance
control box
Exterior Wall
Flexible Ductwork
Rigid Ductwor
k
VPAWP1-8/1-14 Wall Plenum
Plenum
VPDP1 drain pan
beneath unit is
required on all
VEA/VHA24 units.
Drain pan must be
installed prior to
chassis installation
Chassis is
shipped with
vibration
isolators
installed
3" Clearance on all
three sides
minimum for
Optional Platform
Field-supplied
Filter (25" x 20")
58"
29"
VPRG4 Access Panel &
Return Air Filter Grille
Po
wer
Disconnect
II. Installation
1) Utility Closet Dimensions
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on
three sides of the unit must be allowed for return airow, installation access and service access. See Figures 1 & 2 for clearances and
reference dimensions.
Figure 3
Typical Utility Closet
Chassis Shown in Closet, on Optional Platform
Figure 4
Top View
Vert-I-Pak Chassis 2-ton dimensions:
•
23" wide x 23" deep x 47 1/4" high.
VPAWP1-8/1-14 Wall Plenum cut-out
•
dimensions 24 5/8" wide x 30 7/8" high.
VPRG4 Access Panel cutout dimensions:
•
27" wide by 55 3/4" high.
See Figure 8 (Page 10) for proper
•
chassis installation.
NOTE: Drain pan must be installed in closet prior to chassis
insertion into plenum. See Figure 7 (page 8) for drain pan
installation details.
5