Friedrich 920-159-01 User Manual

Vert-I-Pak
®
Single Package Vertical Air Conditioning System
A-Series
24,000 BTU/h
Installation & Operation Manual
920-159-01 (10-03)
920-159-01 (10-03)
Table of Contents
Installation Recommendations......................................................................................................................................................... 3
I. General Specications
Model Number Identication Guide ................................................................................................................................... 4
VERT-I-PAK Chassis Specications...................................................................................................................................4
II. Installation
1. Utility Closet Dimensions ................................................................................................................................................... 5
2. Wall Plenum & Architectural Louver Installation ................................................................................................................ 6
3. Electrical Information ..................................................................................................................................................... 7-9
4. Indoor Return Air Grille Installation .................................................................................................................................. 10
5. Ductwork Preparation and CFM ....................................................................................................................................... 11
6. Chassis Installation.......................................................................................................................................................... 11
7. Chassis Final Connections (Electrical, Duct, Drain & Wall Thermostat)............................................................................12
8. Final Installation Checklist............................................................................................................................................... 12
III. Chassis Operation
9. Thermostat Control ..........................................................................................................................................................12
10. Low Ambient Protection for Compressor & Fan................................................................................................................12
11. Heating Defrost (Heat Pump Models only)........................................................................................................................12
12. Fresh Air Door...................................................................................................................................................................13
13. Condensate Disposal System .......................................................................................................................................... 13
IV. Service, Maintenance & Warranty
14. Servicing / Chassis Quick Changeouts.............................................................................................................................13
15. Routine Maintenance.......................................................................................................................................................13
16. Warranty ..........................................................................................................................................................................14
V. Vert-I-Pak Accessories .................................................................................................................................................... 15
Please read this manual thoroughly prior to equipment installation or operation. It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with the NFPA 70-2002 National Electric Code or current edition and Universal Mechanical Code current edition and applicable local or national codes.
Proper installation is not difcult but it is essential.
2
920-159-01 (10-03)
12"
24"
60"
VPAK VPAK VPAK
POLE
FENCE
MAJOR OBSTRUCTION
BUILDING
OUTDOOR CONDENSING UNIT
72"
24"
SHRUB
6"
60"
60"
60"
6"
60"
60"
6"
60"
60"
SMALL RECESS OK
A
B
60"
60"
60"
60"
LARGER RECESS OK. IF A> 5xB
12"
6"
60"
60"
60"
6"
60"
60"
6"
60"
60"
SMALL RECESS OK
Vert-I-Pak Installation Recommendations
For proper unit performance and maximum operating life please refer to the minimum installation clearances
below.
Figure 1
VERT-I-PAK® units must be installed on an outside wall. Conned spaces and/or covered areas should be avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical clearance of 60" should be maintained between units. Units installed on the bottom oor should be mounted at least 6" off of the ground.
Figure 2
Any time obstructions are present use the following guidelines for proper spacing from the VERT-I-PAK louver:
• For minor obstructions such as lamp poles or small shrubbery a clearance of 24" from the outdoor louver should be maintained.
• For major obstructions such as a solid fence, wall or other heat rejecting device like a condensing unit, a mini­mum distance of 72" should be kept.
The above suggestions are for reference only and do not represent all possible installations. Please contact the factory for information regarding affects of other installation arrangements.
By following these simple recommendations you can be condent that your Friedrich Vert-I-Pak® will provide years of worry-free operation.
3
920-159-01 (10-03)
Section I. General Specications
VERT-I-PAK® MODEL IDENTIFICATION GUIDE
MODEL NUMBER V E A 24 K 50 RT A
SERIES
V=Vertical Series E=Cooling with or without electric heat H=Heat Pump
DESIGN SERIES
A = 32" and 47" Cabinet
NOMINAL CAPACITY A-Series (Btu/h)
09 = 9,000 12 = 12,000 18 = 18,000 24 = 24,000
VOLTAGE
K = 208/230V-1Ph-60Hz
ENGINEERING CODE
OPTIONS
RT = Standard Remote Operation SP = Seacoast Protected
ELECTRIC HEATER SIZE A-Series
00 = No electric heat 25 = 2.5 KW 34 = 3.4 KW 50 = 5.0 KW 75 = 7.5 KW 10 = 10 KW
Vert-I-Pak® Chassis Specifications
MODEL: V(E,H)A24
Voltage (V) 230/208
Refrigerant R-22
Chassis Width 23.125
Chassis Depth 23.125
Chassis Height ** 47.25
Supply Duct Collar *** 10"
Drain Connection 3/4" FPT
Min. Circuit Amps See Nameplate
CFM Indoor See chart, pg. 11
Max. Duct ESP .4 in. water
NOTES: ** Height includes 2" duct collar & isolators under unit. *** Factory collar accepts 10" ex duct.
4
920-159-01 (10-03)
electrical entrance
control box
Exterior Wall
Flexible Ductwork
Rigid Ductwor
k
VPAWP1-8/1-14 Wall Plenum
Plenum
VPDP1 drain pan beneath unit is required on all VEA/VHA24 units. Drain pan must be installed prior to chassis installation
Chassis is shipped with vibration isolators installed
3" Clearance on all
three sides
minimum for
Optional Platform
Field-supplied Filter (25" x 20")
58"
29"
VPRG4 Access Panel & Return Air Filter Grille
Po
wer
Disconnect
II. Installation
1) Utility Closet Dimensions
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on three sides of the unit must be allowed for return airow, installation access and service access. See Figures 1 & 2 for clearances and reference dimensions.
Figure 3
Typical Utility Closet
Chassis Shown in Closet, on Optional Platform
Figure 4
Top View
Vert-I-Pak Chassis 2-ton dimensions:
• 23" wide x 23" deep x 47 1/4" high.
VPAWP1-8/1-14 Wall Plenum cut-out
• dimensions 24 5/8" wide x 30 7/8" high.
VPRG4 Access Panel cutout dimensions:
• 27" wide by 55 3/4" high.
See Figure 8 (Page 10) for proper
• chassis installation.
NOTE: Drain pan must be installed in closet prior to chassis insertion into plenum. See Figure 7 (page 8) for drain pan installation details.
5