General Instructions ................................................................................................................................................................................................................. 3
General Specications ............................................................................................................................................................................................................. 4
One-Piece Deep Wall Sleeve Installation (PDXWSEXT) ........................................................................................................................................................ 9
PXDR10 Drain Kit Installation Instructions (optional for new construction) ........................................................................................................................... 10
External Drain (for new construction or unit replacement) .................................................................................................................................................... 11
PXGA Standard Grille Installation Instructions ...................................................................................................................................................................... 12
Electrical Wiring for 265 Volt Models ..................................................................................................................................................................................... 14
How To Connect ..................................................................................................................................................................................................................... 19
Friedrich PTAC Digital Control and Unit Features ................................................................................................................................................................. 20
System Conguration ............................................................................................................................................................................................................. 22
Digital Control User Input Conguration ................................................................................................................................................................................ 23
Digital Control Operation ....................................................................................................................................................................................................... 24
Remote Control Thermostat Installation ................................................................................................................................................................................25
Remote Thermostat and Low Voltage Control Connections .................................................................................................................................................25
Final Inspection & Start-up Checklist..................................................................................................................................................................................... 27
Service & Assistance ............................................................................................................................................................................................................. 29
NOTE: All PTAC 7000, 9000, 12000 units come with a standard 3 kW power cord. All PTAC 15000 units come with a standard 5 kW power cord.
For units using our optional heating cords (0kW, 2kW, 3kW, and 5kW) please refer to page 14 for the proper accessory part numbers and
power cord installation instructions.
2
Congratulations
WARNING
Read Installation Operation
Manual
Please read this manual thoroughly prior to
equipment installation or operation.
It is the installer’s responsibility to properly
apply and install the equipment. Installation
must be in conformance with the NFPA 70
-2008 National Electric Code or current edition,
International Mechanic Code 2009 or current
edition and any other applicable local or
national codes.
Failure to do so can result in property damage,
personal injury or death.
Thank you for your decision to purchase Friedrich. Your new Friedrich has been carefully engineered and manufactured to give you many years of dependable,
efcient operation, maintaining a comfortable temperature and humidity level. Many extra features have been built into your unit to assure quiet operation,
the greatest circulation of cool, dry air, and the most economic operation.
General Instructions
This Installation and Operation Manual has been designed to insure maximum satisfaction in the performance of your unit. For years of trouble-free service,
please follow the installation instructions closely. We cannot overemphasize the importance of proper installation.
and the controls are properly set, the unit may need service and
WARNING
Refrigeration system
under high pressure
Do not puncture, heat, expose to flame or
incinerate.
Only certified refrigeration technicians should
service this equipment.
R410A systems operate at higher pressures
than R22 equipment. Appropriate safe
service and handling practices must be used.
Only use gauge sets designed for use with
R410A. Do not use standard R22 gauge sets.
Here are some suggestions to help you use your
new Friedrich most efficiently:
1. Carefully read and follow the installation instructions.
2. Make sure the unit is the right capacity for the area being cooled.
An undersized unit makes the unit work too hard, using more
electricity than needed and increases wear. An oversized unit
will cycle on and off too rapidly, and therefore cannot control
humidity as well.
3. Clean the lter frequently (See Routine Maintenance, Page 27).
4. Do not block the air ow to and from the unit.
5. A dirty lter or improperly set controls can affect the cooling
ability of the unit.
6. If cooling is weak and you have veried that the lter is clean
you should call your Friedrich service provider to check the unit.
7. Keep blinds, shades and drapes closed on the sunny side of the
room being cooled to reduce radiant heat.
8. Proper insulation helps your unit maintain the desired inside
temperature.
9. Whenever possible, shade south and west facing windows.
10. Keep window coverings away from the unit to provide free air ow.
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all
safety messages.
This is a safety Alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol with the word “WARNING”
or “CAUTION”. These words mean:
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you
what will happen if the instructions are not followed.
ANIN
WARNING
CAUTION
NOTICE
Indicates a hazard which, if not avoided, can result in severe personal injury or
death and damage to product or other property.
Indicates a hazard which, if not avoided, can result in personal injury and
damage to product or other property.
Indicates property damage can occur if instructions are not followed.
3
General Specifications
MODEL NUMBER
07 = 7,000 Btuh
09 = 9,000 Btuh
Nominal Capacity
12= 12,000 Btuh
15= 15,000 Btuh
Series
PD = Friedrich Digital PTAC
System
X = Accessory
E = Cooling with or without electric heat
H = Heat Pump with Auxiliary Heat
Voltage
K = 230/208V - 1 Ph. - 60 Hz.
R = 265V - 1 Ph. - 60 Hz.
Nominal Heater Size (230V or 265V)
0 = No Heater*
2 = 2.0 KW 3 = 3.0 KW 5 = 5.0 KW**
***No Heater only available on 230V PDE models
5.0 kw only available on 9000, 12000 and 15000 BTU models
Chassis
S = Standard
Design Series
Note: All PTAC models with a C design series or
later come standard with Diamonblue seacoast
protection and digital controls.
Engineering Digit
PDXWS Wall Sleeve Dimensions:
16" H x 42" W x 13-¾" D
Front Cover Dimensions:
16" H x 42" W x 7-¾" D
Cut-Out Dimensions:
16-¼" x 42-¼"
Typical Unit Components and Dimensions
FILTERS
RETURN AIR GRILLE
FRONT COVER
CHASSIS
OUTDOOR GRILLE
WALL SLEEVE
DISCHARGE
GRILLE
Installation Checklist
q Inspect all components and accessories for damage before and after
installation.
q Remove the cardboard wall sleeve support and grill weatherboard.
q Check for proper wall sleeve installation in accordance with the wall
sleeve installation instructions.
q Check for a subbase kit or other means of structural support which
is required for ALL installations projecting more than 8" into room.
q Install the recommended Condensate Drain Kits for complete
condensate removal.
4
q Ensure that the chassis is installed in a 16" high x 42” wide wall sleeve
that is no deeper than 13 ¾". A bafe kit is required if the sleeve
exceeds that depth.
q Ensure that chassis and chassis front cover are installed and secured
properly.
q Ensure that drapes, bed, bedspread, furniture, etc. DO NOT block
either return or discharge air grilles.
q Inspect the condenser air inlet and outlet for any obstructions
(shrubbery, etc.)
q Ensure that 'reset' button is pressed on LCD device (only on cord
connected models).
PTAC Installation Recommendations
36" MIMUMUM, MAJO
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances
below:
Figure 1
PTAC units should be installed
no closer than 12" apart when
two units are side by side. If
three or more PTAC units are to
operate next to one another allow
a minimum of 36" between units.
Also, a vertical clearance of 60"
should be maintained between
units installed. In the interior
of the room the unit should be
located a minimum of 1/4" from
the oor and a minimum of 36"
from the ceiling.
TYPICAL
WINDOW
36"
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
TWO ADJACENT PTACs
12" MINIMUM
GROUND FLOOR PTACs
6" MINIMUM FROM GRADE
60" VERTICAL
MIMUMUM
BETWEEN
PTACs
60"
12"
6"
VIEW: OUTSIDE BUILDING ELEVATION
For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:
Figure 2
•Fo r m i n or obstruc t i o n s
such as lamp poles or small
shrubbery a clearance of
12" from the outdoor louver
should be maintained.
•For major obstructions such
as a sol id fence, wall or
other heat rejecting device
like a condensing unit, a
minimum dist ance of 36"
should be kept.
12" MINIMUM, MINOR
OBSTRUCTIONS
R
OBSTRUCTIONS
TYPICAL BUILDING ( PLAN VIEW )
36"
PTAC
12"
POLE
CONDENSING UNIT
36"
FENCE OR WALL
36"
CATPCATP
SHRUB
FRP001
FRP002
The above suggestions are for reference only and do not represent all possible installations. Please contact Friedrich for information regarding affects of other
installation arrangements. By following these simple recommendations you can be condent that your Friedrich PTAC will provide years of worry free operation.
5
Wall Sleeve Installation Instructions (PDXWS)
NOTICE
DO NOT allow any pitch toward the inside.
Flashing on all 4 sides of the opening is recommended.
Potential property damage can occur if instructions are
not followed.
NOTE:Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories. If the sleeve
projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions completely before
attempting installation.
WARNING
Falling Object Hazard
Not following Installation Instructions for
mounting your air conditioner can result
in property damage, injury, or death.
For Deep Wall Installation (Greater than 13 1/4")
See Page 9
The following instructions apply ONLY to walls less than 13 ¼" in depth.
1. The PXDR10 Drain Kit (optional for new construction) see page 10
if applicable, must be installed before the wall sleeve is installed
into the wall.
2. The External Drain (for new construction or unit replacement) see
page 11, if applicable, must be installed before the wall sleeve is
installed into the wall.
Figure 3
Typical Wall Sleeve Installation
"
LINTEL TO SUPPORT
MASONRY WALLS
20
"
MAX.
42-¼
MIN.
13-¾
"
16-¼
3. From inside the building, position the wall sleeve in the opening and
push it into the wall until it protrudes at least ¼” on the outside. Do
not allow sleeve to be pulled. (See Figure 11, Page 10).
4. Position the wall sleeve with a slight tilt towards the outside to
facilitate condensate drainage. It should be level side-to-side and
the front should be ¼ bubble higher than the back.
ELECTRICAL
RECEPTACLE
"
60
"
MAX.
SMOOTH SIDE OF SCREW
CLIP FACING INTO ROOM
ELECTRICAL
RECEPTACLE
WALL OPENING
WALL SLEEVE
INSULATION
NOTE: All 230/208V units are manufactured with a” power cord and all 265V units with a ” power cord.
6
60
INSULATION
18
FRP008
Alternate Wall Installations
Figure 4
Panel Wall
OPTIONAL SUBBASE
LEVELING SCREW
FRP003
Figure 6
Curtain Wall
CASE FLANGE
(BY OTHERS)
OPTIONAL SUBBASE
LEVELING SCREW
WALL OR
WINDOW
1/4" MIN
PROJECTION
FRP004
Figure 5
Frame and Brick Veneer
WOOD FRAME
OPTIONAL SUBBASE
LEVELING SCREW
1/4" MIN
PROJECTION
STEEL
LINTEL
11" MIN.
WITH SUBBASE
FRP005
Figure 7
Block and Brick Veneer
CONCRETE LINTEL
RECEPTACLE
FINISHED FLOOR
1/4" MIN
PROJECTION
STEEL
LINTEL
13-3/4" MIN.
WITHOUT SUBBASE
POWER SUPPLY CONDUIT
(SUPPLIED BY INSTALLER)
FRP006
NOTE: Follow all wall system manufacturer installation instructions. For sunrooms and modular buildings, adhere to their installation instructions for
supporting and sealing sleeve to their frames. All wall and window/wall installations must provide for proper drainage. In applications where the
drain holes on the PTAC wall sleeve are not exposed beyond the wall an internal drain system is recommended. It is the installer's responsibility
to ensure there is adequate drainage for the PTAC unit.
7
Figure 8
Wall Sleeve Attachment
MOUNTING
HOLES
PLASTIC ANCHORS
Figure 9
Dimensions
WALL
SLEEVE
SCREWS
ALTERNATE
FASTENING METHODS
(Field Supplied)
WOOD SCREW
TOGGLE BOLT
NOTE: The Wall Sleeve must be
EXPANSION
ANCHOR BOLT
horizontally level (side-to-side)
and pitched 1/4 bubble to the
outside when installed in an
opening.
The mounting hole location
should be approximately 2-4”
from the top and bottom of the
sleeve.
FRP007
A
13-¾"
B
¼"
C
WALL
MIN.
Dimension*
No Accessories
With Subbase1-¾"3-½"5"
With Lateral Duct¾"
Wall Sleeve Tilt¼"
* If more than one accessory is to be used, use the maximum
dimension. If the wall thickness is more than 13-¾" - (A+ ¼"),
a sleeve extension must be used.
AB
Allow
for wall
finishing
(Minimum)Min. Max.
¼"
Allow
for floor
finishing
¼"
¼"
---
---
---------
C
Allow
for proper
drainage
(Front-to-Back)
---
---
---
FRP009
8
5. Drill two 3/16" holes through each side of the sleeve approximately
4" from top and 4" from bottom of sleeve. Screw four #10 x 1"
screws (included) or appropriate fasteners for your installation,
through the holes in the sides of the wall sleeve.
6. Apply sealant around the wall sleeve where it projects through the
inside and outside wall surfaces. Apply the sealant to the screw
heads or the tops of the fasteners used in Step #5.
7. If the chassis and exterior grille are to be installed later, leave the
weatherboard and center support in place, otherwise remove and
dispose of them. (See Figure 13, Page 12).
8. Provide a support lintel if the wall sleeve is installed in a concrete
or masonry wall (See Figure 10, Page 9).
Figure 10
Lintel Installation
JACK STUDS
MAIN STUDS
NOTE: Construct wall opening to comply with all applicable building codes.
MAIN STUDS
JACK STUDS
LINTEL
MOUNTING
SCREW HOLES
NO HOLES IN BOTTOM OF WALL
SLEEVE UNLESS DRAIN KIT IS USED
FRP010
One-Piece Deep Wall Sleeve
Installation (PDXWSEXT)
If the wall is thicker than 13 1/4” a deep wall sleeve or wall sleeve extension
MUST be used. The deep wall sleeve may be special ordered through
your Sales Representative.
9
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.