AR3500
14
Supply water temperature:55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 55/35 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510WLL max 190 0 9,0 26,8 0,08 1,0 12,5 37,5 0,15 3,0
min 950 4,5 23,4 0,03 0,3 7, 6 41,6 0,09 1,0
AR3515WLL max 2600 12,3 25,1 0,10 1,0 18,4 39,0 0,22 4,0
min 1300 6,1 22,1 0,04 0,3 11,0 43,0 0,13 2,0
AR3520WLL max 3800 18,0 25,5 0,15 1,0 26,4 38,6 0,32 4,0
min 190 0 9,0 22,3 0,07 0,4 15,8 42,6 0,19 2,0
Supply water temperature:50 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 50/30 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510WLL max 190 0 9,0 28,3 0,10 1,0 9,7 33,1 0,12 2,0
min 950 4,5 24,5 0,04 0,4 5,9 36,5 0,07 1,0
AR3515WLL max 2600 12,3 26,6 0,13 1,0 14,4 34,4 0,17 3,0
min 1300 6,1 23,2 0,06 0,4 8,7 37,8 0,11 1,0
AR3520WLL max 3800 18,0 27,0 0,19 2,0 20,6 34,1 0,25 3,0
min 190 0 9,0 22,3 0,07 0,4 12,5 37,5 0,15 1,0
Supply water temperature: 45 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 45/35 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510WLL max 1900 8,9 30,2 0,14 3,0 10,6 34,6 0,26 7, 0
min 950 4,5 26,0 0,06 0,3 6,3 37,6 0,15 3,0
AR3515WLL max 2600 12,3 28,5 0,18 3,0 15,4 35,5 0,37 9,0
min 1300 6,1 24,7 0,07 1,0 9,0 38,4 0,22 4,0
AR3520WLL max 3800 18,0 29,0 0,27 4,0 22,1 35,2 0,53 9,0
min 190 0 9,0 25,0 0,11 1,0 12,9 38,2 0,31 5,0
Supply water temperature: 40 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 40/30 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510WLL max 1900 9,0 33,0 0,31 10,0 8,0 30,4 0,19 5,0
min 950 4,5 28,4 0,09 1,0 4,8 32,9 0,11 2,0
AR3515WLL max 2600 12,3 31,4 0,34 8,0 11,7 31,3 0,28 6,0
min 1300 6,1 27,0 0,11 1,0 6,9 33,7 0,17 2,0
AR3520WLL max 3800 18,0 31,9 0,53 9,0 16,7 31,1 0,40 6,0
min 190 0 9,0 27,4 0,17 2,0 9,9 33,5 0,24 3,0
Output charts water AR3500
AR3500WLL Special coil