Frico AR3500, AR4200 User Manual

AR3500/4200
AR3500/4200
Recessed air curtain for commercial premises, with intelligent control
Recommended installation height * AR3500: 3,5 m AR4200: 4,2 m
With its concealed placement, AR3500/4200 is very unobtrusive and with that particularly suitable for environments where the design is important.
Optimized airflow with
R
Thermozone technology.
Air velocity profile
AR3500 AR4200
m
0,1
1,0
2,0
3,0
10,7 m/s
6,0 m/s
4,4 m/s
3,5 m/s
• Low sound level.
• Mounting with threaded bars. The threaded bars can also be fixed on the inside of the unit e.g. when mounted on a solid suspended ceiling.
• Corrosion proof housing made of hot zinc-plate and powder enamelled steel panels. Colour frame and hatch: white, RAL 9016, NCS S 0500-N. Colour grille: grey, RAL 7046. The frame and hatch can be painted in an optional colour.
0,1
1,0
2,0
3,0
4,0
11,3 m/s
6,1 m/s
4,6 m/s
3,8 m/s
3,3 m/s
3,5
Measurements according to ISO 27327-1. Average values for products in the series.
3,3 m/s
Measurements according to ISO 27327-1. Average values for products in the series.
Control
This air curtain is supplied prepared for the SIRe control system that has many smart and energy saving functions. There are three different levels with different functionality to choose from, Basic, Competent or Advanced. Water heated units must always be supplemented with valves.
SIRe Basic SIRe Competent SIRe Advanced
*) Recommended installation height varies depending on the relevant premises.
For further information and options, see the "Controls" section.
4,2
3,2 m/s
2020-09-09
AR3500/4200
Recommended installation height 3,5 m
1 Ambient, no heat - AR3500 A (IP20)
Type Output
[kW]
AR3510A 0 1100/2300 78 42/62 230V~/2,45 A 1057 38
AR3515A 0 1550/3400 79 43/63 230V~/3,5 A 1567 51
AR3520A 0 2200/4800 80 45/64 230V~/5,2 A 2073 70
Airflow*
3
/h]
[m
1
Sound power* [dB(A)]
Sound
2
pressure* [dB(A)]
3
Voltage Amperage (control)
Length
[mm]
Weight
[kg]
3 Electrical heat - AR3500 E (IP20)
Type Output
steps [kW]
Airflow*
3
/h]
[m
1
AR3510E09 4,5/9 1100/2300 25/12 77 42/62 230V~/2,45 A 400 V3~/13 A 1057 42
AR3515E14 7/13,5 1550/3400 27/13 78 43/63 230V~/3,5 A 400 V3~/19,5 A 1567 61
AR3520E18 9/18 2200/4800 25/11 79 45/64 230V~/5,2 A 400 V3~/26 A 2073 79
t*
[°C]
4
Sound power* [dB(A)]
2
Sound pressure* [dB(A)]
Voltage
3
Amperage (control)
Voltage Amperage (heat)
Length
[mm]
2 Water heat - AR3500 W (IP20)
Type Output*5
[kW]
Airflow*
3
/h]
[m
1
AR3510W 9,4 1100/2300 16/12 1,3 77 42/61 230V~ 2,6 1057 42
AR3515W 14 1550/3400 16/12 2,1 78 42/62 230V~ 3,6 1567 58
AR3520W 21 2200/4800 16/13 2,9 79 44/63 230V~ 5,3 2073 76
2
Water heat - AR3500 WLL, coil for very low temperature water (460 °C) (IP20)
Type Output*6
[kW]
Airflow*
3
/h]
[m
1
AR3510WLL 9,2 1100/2300 14/12 1,3 76 42/61 230V~ 2,6 1057 45
AR3515WLL 14 1550/3400 15/12 2,1 77 42/62 230V~ 3,6 1567 61
AR3520WLL 20 2200/480 0 15/12 2,9 78 44/63 230V~ 5,3 2073 83
4,5
t*
[°C]
t*
[°C]
Water volume [l]
4,6
Water volume [l]
Sound power* [dB(A)]
Sound power* [dB(A)]
2
2
Sound pressure* [dB(A)]
Sound pressure* [dB(A)]
3
3
Voltage
[V]
Voltage
[V]
Amperage
[A]
Amperage
[A]
Length
[mm]
Length
[mm]
Weight
[kg]
Weight
[kg]
Weight
[kg]
Commercial
*1) Lowest/highest airflow of totally 5 fan steps.
2
) Sound power (LWA) measurements according to ISO 27327-2: 2014, Installation type E.
*
3
) Sound pressure (LpA). Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At lowest/
* highest airflow.
4
*
) t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
5
) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
*
6
) Applicable at water temperature 40/30 °C, air temperature, in +18 °C.
*
Approved by SEMKO. Approved for 220V/1ph/60Hz and 380V/3ph/60Hz. Product performance for 220V/1ph/60Hz and 380V/3ph/60Hz will differ from stated data.
AR3500/4200
Recommended installation height 4,2 m
1 Ambient, no heat - AR4200 A (IP20)
Type Output
[kW]
AR4210A 0 1150/2800 76 40/60,5 230V~/4,1 A 1021 50
AR4215A 0 1650/3900 78 42/62 230V~/5,2 A 1530 70
AR4220A 0 2350/5600 79 44/63 230V~/8,1 A 2021 93
AR4225A 0 2850/6700 80 45/64 230V~/9,3 A
3 Electrical heat - AR4200 E (IP20)
Type Output
steps [kW]
AR4210E12 3,9/7,8/12 1150/2800 31/13 76 40/60,5 230V~/4,1 A 400 V3~/17 A 1021 58
AR4215E18 6,0/12/18 1650/3900 33/14 78 42/62 230V~/5,2 A 400 V3~/26 A 1530 81
AR4220E24 7,8/15/23 2350/5600 31/13 79 44/63 230V~/8,1 A 400 V3~/34 A 2021 10 7
AR4225E30 9,9/20/30 2850/6700 32/13 80 45/64 230V~/9,3 A 400 V3~/43 A
Airflow*
3
/h]
[m
Airflow*
3
/h]
[m
1
1
t*
[°C]
4
Sound power* [dB(A)]
Sound power* [dB(A)]
2
2
Sound pressure* [dB(A)]
Sound pressure* [dB(A)]
3
Voltage
3
Amperage (control)
Voltage Amperage (control)
Voltage Amperage (heat)
Length
[mm]
2579
Weight
[kg]
11 8
Length
[mm]
2579
Weight
[kg]
137
2 Water heat - AR4200 W (IP20)
Type Output*5
[kW]
Airflow*
3
/h]
[m
1
AR4210W 17 1100/2700 24/18 1,9 76 40/60 230V~ 4,0 1021 57
AR4215W 25 1600/380 0 25/19 3,0 76 42/60,5 230V~ 5,5 1530 78
AR4220W 35 2300/5500 25/19 4,0 78 43/62 230V~ 8,0 2021 105
AR4225W 44 2700/6500 26/20 5,1 78 45/62,5 230V~ 9,6
2
Water heat - AR4200 WLL, coil for very low temperature water (460 °C) (IP20)
Type Output*6
[kW]
Airflow*
3
/h]
[m
1
AR4210WLL 10 1100/2500 15/12 3,1 76 40/60 230V~ 3,8 1021 58
AR4215WLL 15 1600/360 0 15/12 4,7 76 42/60,5 230V~ 5,2 1530 80
AR4220WLL 21 2300/520 0 15/12 7, 5 78 43/62 230V~ 7, 6 2021 107
AR4225WLL 26 2700/620 0 15/12 9,6 78 45/62,5 230V~ 9,1 2579 137
*1) Lowest/highest airflow of totally 5 fan steps.
2
) Sound power (LWA) measurements according to ISO 27327-2: 2014, Installation type E.
*
3
) Sound pressure (LpA). Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At lowest/highest
* airflow.
4
*
) t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
5
) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
*
6
) Applicable at water temperature 40/30 °C, air temperature, in +18 °C.
*
4,5
t*
[°C]
t*
[°C]
Water volume [l]
4,6
Water volume [l]
Sound power* [dB(A)]
Sound power* [dB(A)]
2
2
Sound pressure* [dB(A)]
Sound pressure* [dB(A)]
3
3
Voltage
[V]
Voltage
[V]
Amperage
[A]
Amperage
[A]
Length
[mm]
79 134
25
Length
[mm]
Weight
[kg]
Weight
[kg]
B
Dimensions AR3500
AR3500/4200
B
595
A
[mm]B[mm]
AR3510 1057 1016
AR3515 1567 1526
AR3520 2073 2031
Dimensions AR4200
1 m: 4 x M8 1,5 m: 4 x M8 2 m: 6 x M8 2,5 m: 6-8 x M8
302
A
Connection dimensions, inside thread: 3/4", DN20
Commercial
638
803
A
[mm]B[mm]
AR4210 1067 1020
AR4215 1577 1520
AR4220 2067 2020
AR4225 2579 2520
296
A
851
Connection dimensions, inside thread: 3/4", DN20
AR3500/4200
Accessories
PA34CBPA34TR PA34VD
FHDN20
PA34TR, threaded bars
Threaded bars for installing unit on to a ceiling. Length 1 m. Used together with ceiling brackets (PA34CB). Supplemented with vibration dampers (PA34VD) for reduced vibration.
PA34CB, ceiling brackets
Ceiling brackets for installing the unit from the ceiling
AR35/42XTT
FHDN20, flexible hoses
Flexible hoses for easy and practical installation of water heated unit. FHDN20: length 350 mm. FHDN2010: length 1 m. DN20.
AR35/42XTT, extension
Outlet/inlet extension for a discreet installation with only the outlet and inlet visible in the ceiling.
using wires or threaded bars (not included). Best combined with vibration dampers (PA34VD) when using threaded bars.
PA34VD, vibration dampers
Reduces vibrations for ceiling installations with threaded bars.
Type Description Quantity included Length
PA34TR15 Threaded bars for AR3510/3515/3520, AR4210/4215 4 1 m
PA34TR20 Threaded bars for AR4220 6 1 m
PA34TR30 Threaded bars for AR4225 8 1 m
PA34CB15 Ceiling brackets for AR3510/3515/3520, AR4210/4215 4
PA34CB20 Ceiling brackets for AR4220 6
PA34CB30 Ceiling brackets for AR4225 8
PA34VD15 Vibration dampers for AR3510/3515/3520, AR4210/4215 4
PA34VD20 Vibration dampers for AR4220 6
PA34VD30 Vibration dampers for AR4225 8
FHDN20 Flexible hoses DN20, inside thread, 90° bend 2 350 mm
FHDN2010 Flexible hoses DN20, inside thread, 90° bend 2 1 m
AR35XTT10 Outlet/inlet extension AR3510 130-210 mm
AR35XTT15 Outlet/inlet extension AR3515 130-210 mm
AR35XTT20 Outlet/inlet extension AR3520 130-210 mm
AR42XTT10 Outlet/inlet extension AR4210 130-210 mm
AR42XTT15 Outlet/inlet extension AR4215 130-210 mm
AR42XTT20 Outlet/inlet extension AR4220 130-210 mm
AR42XTT25 Outlet/inlet extension AR4225 130-210 mm
For mounting, connection, wiring diagrams and other technical information, please see the manual.