THIS MANUAL CONTAINS RIGGING, ASSEMBLY, START-UP, AND
MAINTENANCE INSTRUCTIONS. READ THOROUGHLY BEFORE
BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESUL T IN D AMAGE OR IMPR OPER OPERATION OF THE UNIT.
SPARE P AR TS LIST....................................................... 64
OPERA TING LOG .......................................................... 65
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
GENERAL INFORMATION
Page 3
PREFACE
This manual has been prepared to acquaint the owner and
serviceman with the INSTALLATION, OPERATION, and
MAINTENANCE procedures as recommended by Frick for
RXB PLUS Rotary Screw Compressor Units.
It is most important that these units be properly applied to
an adequately controlled refrigeration system. Your authorized Frick representative should be consulted for his expert guidance in this determination.
Proper performance and continued satisfaction with these
units is dependent upon:
T o ensure correct installation and application, the equipment
must be properly selected and connected to a properly designed and installed system. The Engineering plans, piping
layouts, etc. must be detailed in accordance with the best
practices and local codes, such as those outlined in ASHRAE
literature.
A refrigeration compressor is a V APOR PUMP. To be certain
that it is not being subjected to liquid refrigerant carryover , it
is necessary that refrigerant controls are carefully selected
and in good operating condition; the piping is properly sized
and traps, if necessary, are correctly arranged; the suction
line has an accumulator or slugging protection; that load
surges are known and provisions made for control; operating cycles and defrosting periods are reasonable; and that
high side condensers are sized within system and compressor design limits.
COMPRESSOR and UNIT IDENTIFICATION
Each compressor unit has 2 identification data plates. The
compressor data plate, containing compressor model and
serial number, is mounted on the compressor body . The unitdata plate, containing unit model, serial number, and Frick
sales order number, is mounted on the side of the motor
base.
NOTE: When inquiring about the compressor or unit, or
ordering repair parts, pro vide the MODEL, SERIAL, and
FRICK SALES ORDER NUMBERS from these data plates.
It is recommended that the entering vapor temperature to
the compressor be superheated to 10
ant saturation temperature. This ensures that all refrigerant
at the compressor suction is in the vapor state.
O
F above the refriger-
DESIGN LIMITATIONS
The compressor units are designed for operation within the
pressure and temperature limits as shown in Frick Pub.
E70-100 SED.
JOB INSPECTION
Immediately upon arrival examine all crates, boxes and exposed compressor and component surfaces for damage.
Unpack all items and check against shipping lists for any
possible shortage. Examine all items for damage in transit.
TRANSIT DAMAGE CLAIMS
All claims must be made by consignee. This is an ICC requirement. Request immediate inspection by the agent of
the carrier and be sure the proper claim forms are executed.
Report damage or shor tage claims immediately to Frick ,
Sales Administration Department, in Waynesboro, PA.
COMPRESSOR DATA PLATE
UNIT DATA PLATE
Page 4
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
FOUNDATION
Each RXB PLUS Rotary Screw Compressor Unit is shipped
mounted on a wood skid which must be removed prior to unit
installation. CA UTION: Allow space f or servicing both ends
of the unit. A minimum of 24 inches is recommended.
The first requirement of the compressor foundation is that it
must be able to support the weight of the compressor package including coolers, oil, and refrigerant charge. Screw
compressors are capable of converting large quantities of
shaft power into gas compression in a relatively small space
and a mass is required to effectively dampen these relatively high frequency vibrations.
Firmly anchoring the compressor package to a suitable foundation by proper application of grout and elimination of piping stress imposed on the compressor is the best insurance
for a trouble free installation. Use only the certified general
arrangement drawings from Frick to determine the mounting foot locations and to allow for recommended clearances
around the unit for ease of operation and servicing. Foundations must be in compliance with local building codes and
materials should be of industrial quality.
The floor should be a minimum of 6 inches of reinforced concrete and housekeeping pads are recommended. Anchor bolts
are required to firmly tie the unit to the floor. Once the unit is
rigged into place (See HANDLING and MOVING), the feet m ust
then be shimmed in order to level the unit. The shims should
be placed to position the feet roughly one inch above the housekeeping pad to allow room for grouting. An expansion-type
epoxy grout must be worked under all areas of the base with
no voids and be allowed to settle with a slight outw ard slope so
oil and water can run off of the base.
When installing on a steel base, the following guidelines should
be implemented to properly design the system base:
1. Use I-beams in the skid where the screw compressor will be
attached to the system base. They should run parallel to the
package feet and support the feet f or their full length.
2. The compressor unit f eet should be continuously welded to
the system base at all points of contact, or bolted.
3. The compressor unit should not be mounted on vibration
isolators in order to hold down package vibration le vels.
4. The customer’ s foundation f or the system base should fully
support the system base under all areas, but most certainly
under the I-beams that support the compressor package.
When installing on the upper floors of buildings, extra precautions should be taken to prevent normal package vibration from being transferred to the building structure. It may
be necessary to use rubber or spring isolators, or a combination of both, to prevent the transmission of compressor
vibration directly to the structure. Howe ver , this may increase
package vibration levels because the compressor is not in
contact with any damping mass. The mounting and support
of suction and discharge lines is also very important. Rubber or spring pipe supports may be required to avoid exciting the building structure at any pipe supports close to the
compressor package. It is best to emplo y a vibration expert
in the design of a proper mounting arrangement.
In any screw compressor installation, suction and discharge lines
should be supported in pipe hangers (preferably within 2 ft. of
vertical pipe run) so that the lines won’t move if disconnected
from the compressor. See table for Allowab le Flange Loads .
A licensed architect should be consulted to determine the
proper foundation requirements for any large engine or turbine drive.
ALLOWABLE FLANGE LOADS
NOZ.
SIZE
NPS
(in.)
1
1.25
1.5
2
3
4
5
6
8
10
12
14
MOMENTS (ft-lbf)LOAD (lbf)
AXIALVERT.AXIALVERT.LAT.LA T.
M
R
25
25
50
100
250
400
425
1000
1500
1500
1500
2000
M
175
200
400
750
1000
1200
1500
1800
25
25
40
70
M
C
25
25
40
70
175
200
400
750
1000
1200
1500
1800
PVCV
L
50
50
100
150
225
300
400
650
1500
1500
1500
1700
50
50
75
125
250
400
450
650
900
1200
1500
2000
L
50
50
75
125
250
400
450
650
900
1200
1500
2000
When applying screw compressors at high pressures, the
customer must be prepared for package vibration and noise
higher than the values predicted for normal refrigeration duty .
Proper foundations and proper installation methods are vital; and ev en then, sound attenuation or noise curtains may
be required to reduce noise to desired levels.
For more detailed information on Screw Compressor F oundations, please request Frick publication S70-210 IB.
FIG. 1 - RECOMMENDED LIFTING METHOD
HANDLING AND MOVING
THIS UNIT MAY BE TOP HEAVY.
USE CARE WHILE HANDLING.
both the length and width of the package to prevent
bending of oil lines and damage to the package.
The unit can be moved with rigging, using a crane or forklift.
The recommended method is to insert lengths of 2" pipe
through the lifting holes in the vertical supports (see FIG. 1).
Alternatively, hooks may be used in rigging, inserting them
in the lifting holes (see FIG. 2).
Use CAUTION in locating the lifting ring. If no motor is
mounted, the lifting ring should be moved off center to the
compressor side of the unit because 60 percent of the weight
is toward the compressor end. If a motor is mounted, appropriate adjustment in the lifting point should be made to
compensate for motor weight. Adjustment of the lifting point
must also be made for any additions to the standard package, such as an external oil cooler, etc., as the center of
balance will be affected.
Spreader bars should be used on
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
FIG. 2 - ALTERNATIVE LIFTING METHOD
The unit can be moved with a forklift by forking under the
skid, or it can be skidded into place with pinch bars by pushing against the skid. NEVER MOVE THE UNIT BY PUSH-
ING OR FORKING AGAINST THE SEPARATOR SHELL
OR ITS MOUNTING SUPPORTS.
SKID REMOVAL
If the unit is rigged into place the skid can be removed by
taking off the nuts and bolts that are fastening the unit mounting supports to the skid before lowering the unit onto the
mounting surface.
If the unit is skidded into place, remove the cross members
from the skid and remove the nuts anchoring the unit to the
skid. Using a 5-ton jack under the separator, raise the unit at
the compressor end until it clears the two mounting bolts.
Spread the skid to clear the unit mounting support, then lower
the unit to the surface. Repeat procedure on opposite end.
MOTOR MOUNTING
The following procedure is required only when the motor is
mounted at the job site.
1. Thoroughly clean the motor feet and mounting pads of
grease, burrs, and other foreign matter to ensure firm seating of the motor.
Page 5
1. Inspect the shaft of the motor and compressor to ensure
that no nicks, grease, or foreign matter is present.
2. Inspect the bores in the coupling hubs to make sure that
they are free of burrs, dirt, and grit.
3. Check that the keys fit the hubs and shafts properly.
CH COUPLING – The T.B. Woods Elastomeric CH Coupling
is used in most applications. It consists of two drive hubs
and a loose, gear-type Hytrel Drive Spacer. The split hub is
clamped to the shaft by tightening the clamp screws. T orque
is transmitted from the motor through the elastomeric gear
which floats freely between the hubs. Install as follows:
IT IS MANDA T OR Y THA T THE COUPLING CENTER BE REMOVED
AND THE DIRECTION OF MOTOR
ROTATION BE CONFIRMED
BEFORE
RUNNING THE
COMPRESSOR. Proper rotation of the compressor shaft
is clockwise looking at the end of the compressor shaft.
FAILURE TO FOLLOW THIS STEP COULD RESULT IN
BACKWARD COMPRESSOR ROTATION WHICH CAN
CAUSE COMPRESSOR FAILURE OR EXPLOSION OF
THE SUCTION HOUSING.
1. Slide one hub onto each shaft as far as possible. It may
be necessary to use a screwdriver as a wedge in the slot to
open the bore before the hubs will slide onto the shafts.
2. Hold the elastomeric gear between the hubs and slide
both hubs onto the gear to fully engage the mating teeth.
Make sure that the keys on the compressor and motor halves
of the coupling are offset 180
O
(see FIG. 3). Center the gear
and hub assembly so there is equal engagement on both
shafts. Adjust the space between hubs as specified in the
CH Coupling Data Table below.
3. Torque the clamping bolts in both hubs to the torque value
given in the CH Data Table. DO NOT USE ANY LUBRI-
CANT ON THESE BOLTS.
4. Proceed to Coupling Alignment.
2. Attach the motor to the base using the bolts and motorraising blocks, if required. Bolt snugly through the base.
3. Weld the four kick bolts into place so that they are positioned to allow movement of the motor feet.
4. Now that the motor has been set, check that the shafts
are properly spaced for the coupling being used. Refer to
the coupling data table for the applicable dimension.
COMPRESSOR/MOTOR COUPLING
INSTALLATION
RXB PLUS units are arranged for direct motor drive and
require a flexible drive coupling to connect the compressor
to the motor. Before installing, perform the following:
The life of the compressor shaft seal and bearings, as well
as the life of the motor bearings, is dependent upon proper
coupling alignment. Couplings may be aligned at the factory but realignment MUST ALWAYS be done on the job
site after the unit is securely mounted on its foundation. Initial alignment must be made prior to start-up and rechecked
after a few hours of operation. Final (HOT) field alignment
can only be made when the unit is at operating temperature. After final (HOT) alignment has been made and found
to be satisfactory for approximately one week, the motor
may be dowelled to maintain alignment.
NOTE: Frick recommends cold aligning the motor .005"
high. This cold misalignment compensates for thermal
growth when the unit is at operating temperature.
Use dial indicators to measure the angular and parallel shaft
misalignment. Coupling alignment is attained by alternately
measuring angular and parallel misalignment and repositioning the motor until the misalignment is within specified
tolerances. The following procedure is recommended.
MISALIGNMENT MUST NOT EXCEED .004" FOR ALL CH COUPLINGS.
FIG. 1 - ANGULAR MISALIGNMENT
ANGULAR ALIGNMENT
1. To check angular alignment, as shown in Fig. 1., attach
dial indicator rigidly to the motor hub. Move indicator stem
so it is in contact with the outside face of compressor hub,
as shown in Fig. 2.
2. Rotate both coupling hubs several revolutions until they
seek their normal axial positions.
Check the dial indicator to be sure that the indicator stem is
slightly loaded so as to allow movement in both directions.
3. Set the dial indicator at zero when viewed at the 12 o’clock
position, as shown in Fig. 2.
O
4. Rotate both coupling hubs together 180
tion), as shown in Fig. 3. At this position the dial indicator
will show TOTAL angular misalignment.
NOTE: The use of a mirror is helpful in reading the indicator dial as coupling hubs are rotated.
5. Loosen motor anchor bolts and move or shim motor to
correct the angular misalignment.
After adjustments have been made for angular misalignment
retighten anchor bolts to prevent inaccurate readings. Repeat Steps 3 through 5 to check corrections. Further adjustments and checks shall be made for angular misalignment
until the total indicator reading is within the specified tolerance.
(6 o’clock posi-
FIG. 2 - DIAL INDICATOR ATTACHED (AT 12 O'CLOCK)
FIG. 3 - DIAL INDICATOR AT 6 O'CLOCK
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
P ARALLEL ALIGNMENT
6. To check parallel alignment, as shown in Fig. 4, reposi-
tion dial indicator so the stem is in contact with the rim of the
compressor hub, as shown in Fig. 5.
Check the dial indicator to be sure that the indicator stem is
slightly loaded so as to allow movement in both directions.
7. Check parallel height misalignment by setting dial indicator at zero when viewed at the 12 o'clock position. Rotate
both coupling hubs together 180
position the dial indicator will show TWICE the amount of
parallel height misalignment.
8. Loosen motor anchor bolts and add or remove shims under
the four motor feet until parallel height misalignment is within
specified tolerance when anchor bolts are retightened.
CARE MUST BE USED WHEN
CORRECTING FOR PARALLEL
MISALIGNMENT TO ENSURE
THAT THE AXIAL SPACING AND ANGULAR MISALIGNMENT IS NOT SIGNIFICANTLY DISTURBED.
9. After the parallel height misalignment is within tolerance,
repeat Steps 1 through 5 until angular misalignment is within
specified tolerance.
O
(6 o'clock position). At this
Page 7
FIG. 4 - PARALLEL MISALIGNMENT
10. Check parallel lateral misalignment by positioning dial
indicator so the stem is in contact with the rim of the compressor hub at 3 o'clock, as shown in Fig. 6.
Set indicator at zero and rotate both coupling hubs together
O
(9 o'clock position), as shown in Fig. 5.
180
Adjust parallel lateral misalignment using the motor adjust-
ing screws until reading is within specified tolerance.
11. Recheck angular misalignment and realign if necessary .
12. Tighten motor anchor bolts and rotate both coupling hubs
together, checking the angular and parallel misalignment
through the full 360
O
travel at 90O increments. If dial read-
ings are in excess of specified tolerance, realign as required.
13. When the coupling hubs have been aligned to within
specified tolerance, a recording of the cold alignment must
be made for unit records and usage during hot alignment.
14. Bump the motor to check for correct compressor rotation. COMPRESSOR ROTATION IS CLOCKWISE WHEN
FACING COMPRESSOR SHAFT (see "CHECKING MOTOR/COMPRESSOR ROTATION", page 8). After verifica-
tion, install gear or disk drive spacer, as applicable.
15. Install the coupling guard before operating the compressor.
FIG. 5 - DIAL INDICATOR ATTACHED (AT 9 O'CLOCK)
FIG. 6 - DIAL INDICATOR AT 3 O'CLOCK
When installing drive spacer, make
sure that hub spacing is within lim-
its shown on the Coupling Data
T able applicable to the coupling being installed and that
the clamping bolt(s) are properly torqued.
Page 8
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
HOT ALIGNMENT OF COMPRESSOR/MOTOR
Hot alignments can only be made after the unit has operated for several hours and all components are at operating
temperatures.
Shut down the unit and quickly affix dial indicator to coupling motor hub, then take readings of both the face and rim
of the compressor hub. If these readings are within tolerance, record reading, attach coupling guard, and restart unit.
However, if the reading is not within limits, compare the hot
reading with the cold alignment and adjust for this difference; i.e. if the rim at 0
the motor rises .005" between its hot and cold state, .005"
of shims should be removed from under the motor.
After the initial hot alignment adjustment is made, restart
unit and bring to operating temperature. Shut down and recheck hot alignment. Repeat procedure unit hot alignment
is within specified tolerance.
COMPRESSOR ROTATION IS CLOCKWISE WHEN FACING THE END OF THE COMPRESSOR SHAFT. Under NO
conditions should the motor rotation be checked with the
coupling center installed as damage to the compressor may
result.
COMPRESSOR
COMPRESSOR UNIT OIL
DO NOT MIX OILS of different
brands, manufacturers, or types.
Mixing of oils may cause excessive
oil foaming, nuisance oil le vel cutouts, oil pressure loss,
gas or oil leakage and catastrophic compressor failure.
Use of oils other than Frick Oil must
be approved in writing by Fric k engineering or warranty claim may be
denied.
Use of filter elements other than
Frick must be approved in writing
by Frick engineering or warranty
claim may be denied.
The oil charge shipped with the unit is the best suited lubricant for the conditions specified at the time of purchase. If
there is any doubt due to the refrigerant, operating pressures, or temperatures; refer to Frick Pub. E160-802 SPC
for guidance.
OIL CHARGE
The normal charging level is midway in the top sight glass
located midway along the oil separator shell. Normal operating level is between the top sight glass and bottom sight
glass. The following table gives the approximate oil charge
quantity.
TABLE - BASIC OIL CHARGE (Gal)
MODELBASIC CHARGE* (GAL.)
1210
1510
1914
2414
3017
3917
5021
HOLDING CHARGE AND STORAGE
Each compressor unit is pressure and leak tested at the
Frick factory and then thoroughly evacuated and charged
with dry nitrogen to ensure the integrity of the unit during
shipping and short term storage prior to installation.
NOTE: Care must be taken when entering the unit to
ensure that the nitrogen charge is safely released.
All units must be kept in a clean, dry location to prevent
corrosion damage. Reasonable consideration must be given
to proper care for the solid state components of the microprocessor. Unit which will be stored for more than two
months must have the nitrogen charge checked periodically.
* Add oil volume for external oil cooler, according to cooler
size selected: 6 x 5 TSOC - 4 gal.; 6 x 5 WCOC - 5 gal.; 8 x
5 TSOC - 6-1/2 gal.; and 8 x 5 WCOC - 8 gal.
Add oil by attaching the end of a suitable pressure type
hose to the oil charging valve, located on the top of the oil
separator on the compressor end of the separator. Using a
pressure-type pump and the recommended Frick oil, open
the charging valve and pump oil into the separator.
Oil distillers and similar equipment which act to trap oil must
be filled prior to unit operation to normal design outlet levels. The same pump used to charge the unit may be used
for filling these auxiliary oil reservoirs.
NOTE: The sight glass, located near the bottom of the
separator shell at the discharge end, should remain
empty when the unit is in operation. The presence of oil
in this end of the vessel during operation indicates liquid carryover or malfunction of the oil return.
OIL HEATER
Standard units are equipped with a 500 watt oil heater, providing sufficient heat to maintain the oil temperature for most
indoor applications during shutdown cycles to permit safe
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
Page 9
start-up. Should additional heating capacity be required
because of unusual environmental condition, contact Frick
Company. The heater is energized only when the unit is not
in operation.
DO NOT ENERGIZE THE HEATER
WHEN THERE IS NO OIL IN THE
UNIT, OTHERWISE THE HEATER
WILL BURN OUT. THE OIL HEA TER WILL BE ENERGIZED
WHENEVER 120 VOLT CONTROL POWER IS APPLIED
TO THE UNIT AND THE COMPRESSOR IS NOT RUNNING
UNLESS THE 10 AMP FUSE (1FU) IN THE CONTROL
PANEL IS REMOVED.
LIQUID INJECTION OIL COOLING
The liquid injection system provided on the unit is self-contained but requires the connection of the liquid line sized as
shown in the table and careful insertion of the expansion
valve bulb into the thermowell provided in the separ ator. High
pressure gas is connected through the regulator to the external por t on the liquid injection valve to control oil temperature. Refer to the liquid injection piping diagram.
NOTE: For booster applications, the high pressure gas
connection must be taken from a high side sour ce (highstage compressor discharge). This should be a minim um
3/8" line connected into the solenoid valve provided. This
gas is required by the expansion valve external port to
control oil temperature.
Where low compression ratios (low condensing pressures)
are anticipated, thermosyphon or water-cooled oil cooling
should be used. It is IMPERATIVE that an uninterrupted
supply of high pressure liquid refrigerant be provided to the
injection system at all times. Two items of EXTREME IM-PORTANCE are the design of the receiver/liquid injection
supply and the size of the liquid line. It is recommended that
the receiver be oversized sufficiently to retain a 5 minute
supply of refrigerant for oil cooling. The evaporator supply
must be secondary to this consideration. Two methods of
accomplishing this are shown.
DUAL DIP TUBE METHOD
The dual dip tube method uses two dip tubes in the receiver. The liquid injection tube is below the evaporator tube to
ensure continued oil cooling when the receiver level is low.
High-stage compressor units may be supplied with singleport (low Vi) or dual-port (low Vi and high Vi), liquid injection
oil cooling. Single port will be furnished for low compression
ratio operation and dual port for high compression ratio operation. Booster compressor units use single-port, liquid injection oil cooling due to the typically lower compression
ratios.
The control system on high-stage units with dual-port, liquid
injection oil cooling switches the liquid refrigerant supply to
the high port when the compressor is operating at higher
compression ratios (3.5 Vi and above) for best efficiency.
The following table giv es the condensing temperature(s) with
the corresponding maximum evaporator temperature limit
for liquid injection usage and the minimum evaporator temperature for a single-port application.
The level control method utilizes a float level control on the
receiver to close a solenoid valve feeding the evaporator
when the liquid falls below that amount necessary for 5 minutes of liquid injection oil cooling.
* Dual Injection Kit will be shipped by Frick
below these temperatures.
Page 10
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
Liquid line sizes and the additional receiver volume (quantity of refrigerant required for 5 minutes of liquid injection oil
cooling) are given in the following table:
REFRXBRATEVOLUME
HIGH191/2–15.4
STAGE241/2–20.6
R-717301/2–25.7
HIGH193/45/845.6
STAGE243/47/860.8
R-22303/47/8751.0
BOOST-191/2–3.5.1
R-717301/2–5.5.2
BOOST-193/41/29.1
R-22303/41/214.5.2
MODELPIPETUBING(lb.)CU.FT.
121/2–10.3
151/2–12.5.4
391/2–308
503/4–401.1
123/45/830.4
153/45/837.5.5
393/47/8951.3
50111251.7
121/2–2.1
151/2–2.5.1
ER241/2–4.5.1
391/2–6.5.2
501/2–-8.5.3
123/41/26.1
153/41/27.1
ER243/41/212.2
393/41/218.3
503/45/824.3
LIQ. LINE SIZE*FLOWLIQUID
SCH 80OD5 MIN
* 100 ft. liquid line. For longer runs, increase line size ac-
cordingly.
NOTE: The water regulating valve shipped with the unit
will be sized to the specific flow for the unit.
THERMOSYPHON OIL COOLING (OPTIONAL)
Thermosyphon oil cooling is an economical, effective method
for cooling oil on screw compressor units. Thermosyphon
cooling utilizes liquid refrigerant at condenser pressure and
temperature which is partially vaporized at the condenser
temperature in a shell and tube- or plate-type vessel cooling the oil to within 15
condensing pressure, is vented to the condenser inlet and
reliquified. This method is the most cost effective of all currently applied cooling systems since no compressor capacity is lost or compressor power penalties incurred. The vapor from the cooler need only be condensed, not compressed. Refrigerant flow to the cooler is automatic, driven
by the thermosyphon principle, and cooling flow increases
as the oil inlet temperature rises.
EQUIPMENT - The basic equipment required for a thermosyphon system consists of:
1. A source of liquid refrigerant at condensing pressure and
temperature located in close proximity to the unit to minimize piping pressure drop. The liquid le vel in the refrigerant
source must be 6 to 8 feet above the center of the oil cooler .
2. A shell and tube- or plate-type oil cooler with a 300 psi
minimum design working pressure on both the oil and refrigerant sides.
Due to the many variations in refrigeration system design
and physical layout, several systems for ensuring the above
criteria are possible.
O
F of that temperature. The vapor, at
WATER-COOLED OIL COOLING (OPTIONAL)
The shell and tube-type, water-cooled oil cooler is mounted
on the unit complete with all oil piping. The customer must
supply adequate water connections and install the two-way
water regulating valve. It is recommended that (local codes
permitting) the water regulator be installed on the water outlet
connection. Insert the water regulator valve bulb and well in
the chamber provided on the oil outlet connection. Determine the size of the water-cooled oil cooler supplied with
the unit, then refer to table for the water connection size
and water flow range (GPM). The water supply must be
sufficient to meet the required flow.
It is imperative that the condition of cooling water and closed
loop fluids be analyzed and maintained regularly and as
necessary to prevent corrosion of heat exchanger surfaces.
The oxygen content of river water and some other cooling
water sources will oxidize steel tubes and cause premature
failure. Careful attention to water treatment is essential to
ensure adequate life of steel cooler tubes if cooling tower
water is used. The condition of heat e xchanger tubes should
be checked semiannually to prevent hazard.
OIL COOLER DATA TABLE
SIZE - InchesAPPROX
WATER FLOW
COOLERWATER CONNRANGE (GPM)
5 Foot Lengths
6" DIA.1 NPT10 – 23
8" DIA.1-1/4 NPT35 – 60
SYSTEM OPERATION - Liquid refrigerant fills the cooler
tube side up to the Thermosyphon receiver liquid level.
Water or hot oil (above the liquid temperature) flowing
through the cooler will cause some of the refrigerant to boil
and vaporize in the tubes. The vapor rises in the return line.
The density of the refrigerant liquid/vapor mixture in the return line is considerably less than the density of the liquid in
the supply line. This imbalance provides a differential pressure that sustains a flow condition to the oil cooler. This relationship involves:
1. Liquid height above the cooler.
2. Oil heat of rejection.
3. Cooler size and piping pressure drops.
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
Page 11
Current thermosyphon systems are using two-pass oil coolers and flow rates based on 4:1 overfeed.
The liquid/vapor returned from the cooler is separated in the
receiver. The vapor is vented to the condenser inlet and need
only be reliquified since it is still at condenser pressure.
INSTALLATION - The shell and tube-type thermosyphon oil
cooler with oil-side piping and a thermostatically controlled
mixing valve (if ordered) are factory mounted and piped. The
customer must supply and install all piping and equipment
located outside of the shaded area on the piping diagram
with consideration given to the following:
1. The refrigerant source, thermosyphon or system receiver, should be in close pro ximity to the unit to minimize piping
pressure drop.
2. The liquid level in the refrigerant source must be 6 to 8
feet above the center of the oil cooler.
3. A safety valve should be installed if refrigerant isolation
valves are used for the oil cooler.
4. F rick recommends the installation of an angle v alve in the
piping before the thermosyphon oil cooler to balance the
thermosyphon system. Frick also recommends the installation of sight glasses at the TSOC inlet and outlet to aid in
troubleshooting. The factory-mounted, plate-type thermosyphon oil cooler requires a refrigerant-side drain valve
to be provided and installed by the customer.
TSOC AND WCOC OPTIONAL OIL SIDE SAFETY RELIEF
- Compressor units, which have valves in the oil piping to
isolate the oil cooler from the oil separator for servicing,
may have factory installed piping to relieve the shell side
(oil side) safety valve directly into the oil separ ator, as sho wn
in the P & I diagrams on pages 58 through 60.
This arrangement uses a special UV stamped safety valve
rated for liquid and vapor relief . The safety v alve is designed
for 500 psi DWP and is set to relieve at 75 psi delta P. The
safety valve piping contains flanged connections should the
valve require maintenance or replacement.
Extra caution should be used when servicing an oil separator with this arrangement. If the oil cooler is valved off
from an oil separator which has been evacuated for servicing, then the oil cooler could relieve into the separator vessel if the 75 psi delta p setpoint is exceeded.
Other units, which do not use this special safety valve arrangement, will have factory mounted safety valves on the
shell side of the oil cooler which the installing contractor
should pipe into house safety systems designated suitable
for oil relief.
The component and piping arrangement shown below is intended only to illustrate the operating principles of thermosyphon oil cooling. Other component la youts ma y be better suited
to a specific installation. Ref er to publication E70-900E for additional information on Thermosyphon Oil Cooling.
CONDENSER
STATIC HEAD
TO O VERCOME
CONDENSER
PRESSURE DROP
8 Ft.
Min.
TSOCA
SYSTEM
SAFETY
VALVE
OIL TEMP
CONTROLVALVE
A
B
HOT
COOL
2
OIL OUT
THERMOSYPHON
OIL COOLER
HOT OIL IN
VAPOR
3
THERMOSYPHON
RECEIVER
LIQUID
LEVEL
C
1
Refrigerant-side drain valve
required for plate-type
thermosyphon oil coolers.
LIQUID OVERFLOW
DRAIN TO RECEIVER
TO SYSTEM
4
EVAPORATOR
SYSTEM
RECEIVER
(Mounted below Thermosyphon
receiver le vel)
1. The thermosyphon oil cooler is supplied with the oil side piped to the compressor unit and stub ends supplied on the refrigerant side.
2. A three-way oil temperature control valve is required where condensing temperature is expected to go below 65
3. A refrigerant-side saf ety valv e is required in this location only when refrigerant isolation valv es are installed between the cooler
and thermosyphon receiver. If no valves are used between the cooler and TSOC receiver, the safety v alv e on the TSOC receiver
must be sized to handle the volume of both vessels. Then, the safety valve on the cooler vent (liquid refrigerant side) can be
eliminated.
4. The system receiver must be below the thermosyphon receiver in this arrangement.
O
F.
Page 12
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
ECONOMIZER - HIGH STAGE (OPTIONAL)
The economizer option provides an increase in system capacity and efficiency by subcooling liquid from the condenser
through a heat exchanger or flash tank before it goes to the
evaporator. The subcooling is provided by flashing liquid in
the economizer cooler to an intermediate pressure level.The
intermediate pressure is provided by a port located part way
down the compression process on the screw compressor.
As the screw compressor unloads, the economizer port will
drop in pressure level, eventually being fully open to suction. Because of this, an output from the microprocessor is
generally used to turn off the supply of flashing liquid on a
shell and coil or DX economizer when the capacity falls below approximately 45%-60% capacity (85%-90% slide valve
position). This is done because the compressor will be more
efficient operating at a higher slide valve position with the
economizer turned off, than it will at a low slide valve position with the economizer turned on. Please note however
that shell and coil and DX economizers can be used at low
compressor capacities in cases where efficiency is not as
important as ensuring that the liquid supply is subcooled. In
such cases, the economizer liquid solenoid can be programmed to be left open whenever the compressor is running.
Due to the tendency of the port pressure to fall with decreasing compressor capacity, a back-pressure regulator
valve (BPR) is generally required on a flash economizer
system (FIG. 3) in order to maintain some preset pressure
difference between the subcooled liquid in the flash vessel
and the evaporators. If the back-pressure regulator valve is
not used on a flash economizer, it is possible that no pressure difference will exist to drive liquid from the flash v essel
to the evaporators, since the flash vessel will be at suction
pressure. In cases where wide swings in pressure are an-
ticipated in the flash economizer vessel, it may be necessary to add an outlet pressure regulator to the flash vessel
outlet to avoid overpressurizing the economizer port, which
could result in motor overload. Example: A system feeding
liquid to the flash vessel in batches.
The recommended economizer systems are shown below.
Notice that in all systems there should be a strainer (STR)
and a check valve (VCK) between the economizer vessel
and the economizer port on the compressor. The strainer
prevents dirt from passing into the compressor and the check
valve prevents oil from flowing from the compressor unit to
the economizer vessel during shutdown.
Other than the isolation valve
needed for strainer cleaning, it is
essential that the strainer be the
last device in the economizer line before the compressor. Also, piston-type check valves are recommended
for installation in the economizer line, as opposed to
disc-type check valves. The latter are more prone to gaspulsation-induced failure. The isolation and check valves and strainer should be located as closely as possible to the compressor, preferably within a few feet.
For refrigeration plants employing multiple compressors on
a common economizing vessel, regardless of economizer
type, each compressor must have a back-pressure regulating valve in order to balance the economizer load, or gas
flow, between compressors. The problem of balancing load
becomes most important when one or more compressors
run at partial load, exposing the economizer port to suction
pressure. In the case of a flash vessel, there is no need for
the redundancy of a back-pressure regulating valve on the
vessel and each of the multiple compressors. Omit the BPR
valve on the flash economizer vessel and use one on each
compressor, as shown in FIG. 4.
FIG. 1 - SHELL and COIL ECONOMIZER SYSTEM
FIG. 2 - DIRECT EXPANSION ECONOMIZER SYSTEM
FIG. 3- FLASH ECONOMIZER SYSTEM
FIG. 4 -MUL TIPLE COMPRESSOR ECONOMIZER SYSTEM
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
Page 13
ELECTRICAL
NOTE: Before proceeding with electrical installation, read
the instructions in the section “Proper Installation of
Electronic Equipment in an Industrial Environment”.
RXB PLUS units are supplied with a SBC (single-board computer) microprocessor control system. Care must be taken
that the controls are not exposed to physical damage during handling, storage, and installation. The microprocessor
enclosure cover must be kept tightly closed to prevent entry
of moisture and foreign matter.
Customer-control power connections are made at the BOTTOM of
the microprocessor enclosure.
Consult local ordinances before installation. Current
transformer wiring should be kept separate. Extreme
care should be taken that metal filings or other foreign
material is not left in the microprocessor enc losure. Use
seal-tight conduit fittings to prevent moisture entry into
the microprocessor enclosure. This is the ONL Y electrical enclosure that should be opened during installation
and it should be kept tightly closed whenever work is
not being performed in it.
1. The compressor motor starter of the specified HP and
voltage for the starting method specified (across-the-line,
autotransformer, wye-delta, or solid state).
NOTE: If starting methods other than across-the-line are
desired, a motor/compressor torque analysis must be
done to ensure that sufficient starting torque is available, particularly in booster applications. Contact FRICK
Company if assistance is required.
2. If specified, the starter package can be supplied as a
combination starter with circuit breaker disconnect. However, the motor overcurrent protection/disconnection device
can be supplied by others, usually as a part of an electrical
power distribution board.
3. A 2.0 KVA control power transformer (CPT), to supply
120 volt control power to the control system and separator
oil heaters, is included. If environmental conditions require
more than a 500 watt oil heater, an appropriately oversized
control transformer will be required.
4. One (1) normally open, compressor-motor-starter auxiliary contact and 1 normally open, oil-pump-motor-star ter
auxiliary contact (opt.) should be supplied and wired as
shown on the starter package wiring diagram. In addition,
the compressor and oil pump motor starter (opt.) coils and
the CPT secondaries should be wired as shown on starter
package wiring diagram.
NOTE: Customer ground required, see Micro Panel Assembly Wiring Diagram.
MOTOR STARTER PACKAGE
5. The compressor motor Current Transformer (CT) can beinstalled on any one phase of the compressor leads. NOTE:
The CT must see all the current on any one phase; therefore in wye-delta applications, BOTH leads of any one
phase must pass through the CT.
6. Oil Pump Option: If the optional oil pump is specified, an
oil pump starter must be a component of the unit starter
package. The pump starter should be equipped with fuses
or, in the case where the compressor motor is a different
voltage from the oil pump motor, a circuit breaker disconnect suitable for separate power feed.
NOTE: Do not install a compressor HAND/OFF/AUTO
switch in the starter package as this would bypass the
compressor safety devices.
Motor starter and interlock wiring requirements are shown
in the wiring diagram, above. All the equipment shown is
supplied by the installer unless a starter package is purchased from Frick . Starter packages should consist of:
NOTE: When compressor motor voltage is different from
oil pump motor voltage, supply a cir cuit breaker disconnect for separate feed in lieu of fuses.
Page 14
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
CURRENT TRANSFORMER (CT) RATIOS
The CT ratio for various motor sizes (with a 5 amp secondary) is given in the following table:
The following table gives the minimum CT burden ratings.
This is a function of the distance between the motor starting
package and the compressor unit.
BA TTER Y B A CKUP
The battery backup prevents data loss during power interruption. It will maintain the adjustable setpoints stored in
RAM (Random Access Memory) for up to 1 year after power
loss. Expected battery life is 10 years. A trickle charge maintains the battery backup at peak charge when control voltage is present.
To prevent power loss, the battery backup is shipped disabled. To enable the batter y backup, a jumper pin located
near the top of the microprocessor circuit board (see illustration page 52) must be moved from OFF (pins 1-2) to ON
(pins 2-3).
NOTE: It is not necessary to disconnect the battery
backup during extended downtime.
BURDENMAXIMUM DISTANCE FROM
RA TINGFRICK P ANEL
USING #USING #USING #
ANSIVA14 AWG12 AWG10 AWG
B-0.12.515 ft25 ft40 ft
B-0.2535 ft55 ft88 ft
B-0.512.593 ft148 ft236 ft
In addition to the starter package interlocks shown on the
starter package diagram, the following optional interlocks
are on the typical RXB PLUS Screw Compressor unit with
the SBC Microprocessor Control System wiring diagram:
1. Remote LOAD, UNLO AD, and RUN interlocks in case the
customer desires to operate the unit from a remote control
device.
2. Alarm Horn output.
3. Control solenoid valve for the economizer option.
For customer control options, consult FRICK Company.
NOTE: The microprocessor will not operate without
EPROM chips installed. When EPROM chips are not installed, the microprocessor display will typically indicate two dark lines across both the upper and lower display screens.
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
OPERATION and START-UP INSTRUCTIONS
GENERAL INFORMATION
OPERATION
Page 15
The Frick RXB PLUS Rotary Screw Compressor Unit is an
integrated system consisting of six major subsystems:
1. Microprocessor Control Panel
2. Compressor
3. Compressor Lubrication System
4. Compressor Oil Separation System
5. Compressor Hydraulic System
6. Compressor Oil Cooling System
MICROPROCESSOR CONTROL PANEL
The information in this section of the manual provides the
logical step-by-step instructions to properly start up and operate the RXB PLUS Rotary Screw Compressor Unit.
THE FOLLOWING SUBSECTIONS MUST BE READ AND
UNDERSTOOD BEFORE ATTEMPTING TO START OR
OPERA TE THE UNIT.
The RXB PLUS compressor is controlled by a state-ofthe-art microprocessor control system. The microprocessor
continuously monitors the compressor unit’s condition and
operation. The microprocessor also directs instructions to
the various compressor unit subsystems.
The microprocessor has a membrane switch keyboard.
Pressing the keyboard in the area outlined as a key will cause
that function to be recognized by the microprocessor. The
keyboard has 32 membrane-type keys.
In addition to the keyboard, there is an emergency stop button. Pushing the emergency stop will bypass the computer
and remove all power from the outputs. This will shut down
the compressor motor and all high voltage to the compres-
sor auxiliary systems such as the oil pump and liquid injection solenoid. THE EMERGENCY STOP BUTTON IS FOR
EMERGENCY SHUTDOWN SITUATIONS ONLY and
MUST NOT BE USED TO ROUTINELY SHUT OFF THE
COMPRESSOR.
The microprocessor continuously monitors the state of the
battery which maintains setpoints and various other data. If
the battery voltage is low, the message “LOW BATT” will
flash in the lower right hand corner of the bottom display
(see page 14 for description of battery backup).
The microprocessor hardware contains an output watchdog circuit. If the microprocessor should fail, this circuit will
disable (turn off) all outputs.
Page 16
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
OPERATION
Revised 2/95
KEYS AND KEY FUNCTIONS
NOTE: The microprocessor will automatically return to
the main operating display after 60 seconds of keyboard nonactivity.
The [CHANGE] ke y rotates the dual display screen through
six display modes. The [CHANGE] key is also used to change
the status of various setpoints.
The [STEP] key steps or moves a set of flashing brackets
through the variable setpoints on the Adjustable setpoints
display, the Auto-cycle display, the Security display and the
Setback display. The setpoint enclosed within the flashing
brackets may be changed or updated. The [STEP] key is
also used when the Annunciator display is selected to step
through the annunciator’s four information displays.
NOTE: The [ * ] key is used to step or move the flashing
brackets, described above, backwards.
The [ENTER] key is used to enter new setpoint limits.
The [CLEAR] key will reset an alarm or cutout indication on
the annunciator screen and will clear the microprocessor to
allow continued operation or restarting if all conditions have
returned to normal and no other control lockouts are in force.
The [NUMERIC KEYPAD] is used to introduce new setpoint
limits.
The [+/-] key is used to toggle between pounds per square
inch gauge (g) and inches of mercury (hg).
1. Operating displays
2. Setpoints displays
3. Annunciator displays
4. Shutdown Record displays
5. Freeze displays
[F1] Operating display
[F2] Security display
[F3] Setback display
[F4] Auto Cycle display
NOTE: On initial powering of the microprocessor, and
any time power has been removed from the microprocessor, onl y the Operating, Setpoints, Ann unciator, and
Shutdown displays will display inf ormation. The Freeze
display will appear as a dark screen. The Freeze display
will only be present after a compressor unit cutout.
OPERATING DISPLAY *, Pages 1 and 2
OP.DISPLAY PAGE 1 Thu 03-01-89 15:33:36
SuctionDischOilCompressor
14.3 hg024 g060 gMan Mode
O
F135OF135OFRunning
-040
OP.DISPLAY PAGE 2 Thu 03-01-89 15:33:36
V Ratio S V PosPump%FLASep 132OF
2.2070%on096%HTR off
AutoAuto U
The [RUN], [STOP], and [REMOTE START] keys control
the starting and stopping of the compressor unit.
The [ALARM SILENCE] k ey will de-energize the alarm horn
output.
The [AUTO], [REMOTE], and [MANUAL] keys control the
operation of the compressor slide valve.
The [AUTO], [MANUAL 2.2], [MANUAL 3.5], and [MANUAL
5.0] keys control the operation of the compressor slide stop .
The [F1] function key will return the operator to the main
operating display. This function may be inv ok ed at any time,
even during setpoint entry.
The [F2] function ke y will call up the Security display. NOTE:
Press the [F2] key , as pr ompted b y the display, to return
to the previously selected display.
The [F3] function ke y will call up the Setback displa y . NOTE:
To exit the Setback display, press the [F1] key as
prompted by the display.
The [F4] function key will call up the Auto Cycle display.
NOTE: T o exit the A uto Cyc le display, press the [F1] key
as prompted by the display.
The microprocessor has two liquid crystal displays in an 8
line by 40 character format, for a total of 320 characters.
When power is first applied to the control panel, the unit will
be in the Operating display mode. To change to a different
display mode, press the [CHANGE] key. The display modes
in their order of rotation are:
OPERATING DISPLAY, P age 1
The Operating display is continuously updated and pro vides
a variety of information in regard to the current status of the
compressor’s condition and performance.
The information furnished by the Operating display is as follows:
The DAY, DATE, and TIME are displayed at the top right of
the display.
NOTE: To set day, date, and time, see TO CHANGE THE
ADJUSTABLE SETPOINTS.
SUCTION - Suction Pressure and Temperature are mea-
sured at the compressor inlet and are, respectively, displayed
in pounds per square inch gauge (g) or inches of mercury
(hg) and degrees Fahrenheit.
DISCH - Discharge Pressure and Temperature are measured at the compressor outlet and are, respectively, displayed
in pounds per square inch gauge (g) and degrees Fahrenheit.
OIL - Oil Pressure and Temperature are measured prior to
entering the compressor and are, respectively, displayed in
pounds per square inch gauge (g) and degrees Fahrenheit.
ALARM/CUTOUT - An Alarm or Cutout message indicates
an Alarm or Cutout setpoint has been reached, or exceeded.
Rotate the display mode to the Annunciator display for details. In the ev ent of a cutout, rotate to the F reez e displa y f or
further details.
*Display for illustrative purposes only.
COMPRESSOR - The compressor displa ys the status of the
compressor unit. The mode of operation will be indicated as
either manual (Man Mode) when the [RUN] key has been
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
OPERATION
pressed, automatic (AUTO MODE) when Auto Cycle has
been activated, remote (RMT MODE) when the [REMOTE]
key has been pressed, or off (OFF MODE).
RECYCLE DELAY - A Recycle Delay message indicates
that the compressor has started and has shut down within
the time delay setpoint period. The Recycle Delay will prevent the compressor from starting until the delay time expires and is intended to prevent damage to the compressor
motor from successive restarts. During Recycle Delay, the
microprocessor will alternatively flash “RECYCLE DELAY”
and the remaining delay time in minutes.
NOTE: Consult Motor Manufacturer for the recommended duration of the Recycle Delay.
Page 17
SETPOINTS PAGE 1B
Dead Band--[/./#]
Prop. Band--[/ / %]
Cycle Time--[/ / sec]
LOW % FLA---[/ / / %]
SETPOINTS PAGE 2MLC Stop LD-[095%]
CT Factor-[078]MLC Force ULD[100%]
Aux1[Alarm] [NO] Hi Disch Cutout-[050 g ]
Aux2[Shutd] [NO] Hi Disch Alarm—[045 g ]
If the [RUN] key is pushed while
the unit is in Recycle Delay, the
compressor will start at the end of
the delay period.
OPERATING DISPLAY, P age 2
V RATIO - Volume Ratio is the ratio selected by the micro-
processor to provide the highest efficiency at any given suction and discharge pressure condition. Immediately below
this, an information space has been provided to indicate
whether V ratio is in the automatic (AUTO) or the manual
(MAN) mode.
SV POS - Slide valve position is display ed as a percentage.
This percentage reflects the mechanical position of the slide
valve and does not reflect the percentage of full load operation. Immediately below this information, space has been
provided to indicate whether SV Pos is in the automatic
(AUT O), manual (MAN), or remote (RMT) mode . The microprocessor will control this function in the automatic mode.
To the right of the mode indicator, two other messages may
appear:
L - Indicates Slide Valve loading.
U - Indicates Slide Valve unloading.
PUMP (Optional) - Pump displays the current status of the
oil pump. The display will read ON or OFF whenever the
HAND-OFF-AUT O switch is selected to A UT O and the compressor is running.
% FLA - Percent Full-Load Amps displays the percentage
of the drive motor, full-load amperage rating that the motor
is currently using.
SETPOINTS PAGE 4
Hi Oil Temp Cutout --[167F] Alarm -- [158F]
Lo Oil Temp Cutout -- [49F]Alarm -- [58F]
Lo Oil Press. Cutout -- [005]Alarm -- [010]
The information furnished by these displays is as follows:
PB-[10%DB-[1.0 #]
SETPOINTS DISPLAY, Page 1A:
CAP CONTROL - The Capacity Control setpoint, reported
in pounds per square inch gauge (g) or inches of mercury
(hg), controls the loading and unloading of the compressor
when Capacity is in the automatic (AUTO) mode.
LO SUCT CUTOUT - The Low Suction Pressure Cutout,
reported in pounds per square inch gauge (g) or inches of
mercury (hg), will shut down the compressor if the suction
pressure drops to this limit or lower, f or 90 seconds or longer .
LO SUCT ALARM - The Low Suction Pressure Alarm, reported in pounds per square inch gauge (g) or inches of
mercury (hg), will trigger a prealarm if the suction pressure
drops to this limit or lower.
ID - The ID number is a prog rammable identification code
in telecommunications to access a specific compressor.
used
SEP - Separator displays the oil separator temperature in
degrees Fahrenheit.
HTR - Heater displays the condition of the oil separator
heater(s), indicating ON or OFF.
FORCED UNLD - A Forced Unload message indicates that
the percentage of motor, full-load amps has exceeded the
maximum limit and the microprocessor is unloading the compressor until the percentage FLA falls back to normal limits.
DATE - The Date displays the current date in the following
format: Month - Day - Year.
DAY - Day will display the current day of the week.
TIME - The Time displays the current time in the following
format: Hours - Minutes - Seconds. The time is in 24:00:00
hour clock format.
BAUD - Shows the baud rate of the RS422 communication
port. Both ports are configured as follows: w ord = 8 bit, parity = none or even, stop = 1 bit. The communications port is
programmable from 300 to 19200 baud.
RECY. DELAY - The Recycle Delay displays the current
recycle delay setpoint in minutes. NOTE: Consult the mo-
tor manufacturer for recommended setpoint.
Page 18
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
OPERATION
SETPOINTS DISPLAY, P a ge 1B:
Dead Band - This is a + (plus) or - (minus) value above or
below the setpoint at which the compressor will neither load
nor unload. A dead band of 1 is the default value. It is adjustable between .5 lb to 5 lb in increments of .5. The [Step]
key is used to select this setpoint; then press the [Change]
key to toggle through the selections.
Proportional Band - This setpoint is used to determine the
amount of time the load/unload solenoid is energized, according to how far from the setpoint the actual control pressure is. The smaller the number, the longer a load/unload
signal will be sent; 10% is the default value. Selections are
2, 5, 10, 15, 20, or 25%. The [Step] k ey is used to select this
setpoint; then press the [Change] ke y to toggle through the
selections.
Cycle Time - Cycle time is the amount of time between the
beginning of each load/unload response. Ten seconds is
the default value. “Cycle Time” is adjustable between 5 and
30 seconds in 5 second intervals. The [Step] key is used to
select a setpoint; then press the [Change] key to toggle
through the selections.
Low % FLA - This setpoint is used to determine if the coupling has broken; 20% is the default value. It is adjustable
from 0 to 100% FLA. Use the [Step] ke y to select a setpoint;
then enter the desired setpoint and press the [Enter] key.
AUX 1 and A UX 2 - May be configured f or either an alarm or
shutdown and with either a normally closed (NC) or normally open (NO) contact.
TO CHANGE THE ADJUSTABLE SETPOINTS:
Adjustable Setpoints are stored in RAM (random access
memory) and are easily changed in the field.
Adjustable Setpoints are lost if
power is interrupted and the bat-
tery is not fully charged. To facilitate reentry, we suggest that a list of Adjustable
Setpoints be affixed to one end of the microprocessor
cabinet for reference.
NOTE: The following procedure also applies to the changing of the Security, Setback, and Auto Cycle display
setpoints.
1. Press the [CHANGE] key to rotate the display to the Ad-
justable Setpoints display.
2. Press the [STEP] key to move or step a set of flashing
brackets through the v arious setpoints. A setpoint is selected
for change or update when it is enclosed by the flashing
brackets.
NOTE: The DAY indicator, itself, will flash when selected
for change or update.
SETPOINTS DISPLAY, Page 2:
MLC STOP LD - The Motor Load Control Stop Load, re-
ported as a percentage of the motor, full-load amps (FLA),
will prevent the compressor capacity control pistons from
loading when the setpoint is equaled or exceeded. NOTE:
Consult motor manufacturer for recommended setpoint.
MLC FORCE ULD - The motor Load Control Force Unload,
reported as a percentage of the motor, full-load amps (FLA),
will force the compressor to unload until the motor, full-load
amps (FLA) fall within 1% of the setpoint or lower. NOTE:
Consult motor manufacturer for recommended setpoint.
HI DISCH CUTOUT - The High Discharge Pressure Cutout,
reported in pounds per square inch gauge (g), will shut down
the compressor if the discharge pressure equals or exceeds
this setpoint.
HI DISCH ALARM - The High Discharge Pressure Alarm,
reported in pounds per square inch gauge (g) will trigger a
prealarm if the discharge pressure equals or exceeds this
setpoint.
CT FACTOR - The Current Transformer Factor records the
proper current transformer factor to match the compressor
motor FLA rating to the current transformer primary rating.
The CTF factor is programmable and its correct value is
determined by the following formula:
CTF =
* See motor nameplate.
** See CT located in starter panel.
EXAMPLE: FLA = 230 Amps
CT = 300 (300:5)
CTF == 78 (Round to whole number)
10x CT (Current Transformer Primary Amps **)
1024 x 230
10 x 300
1024 x FLA (Full Load Amps *)
3. Having selected the setpoint to be changed, the [NUMERIC KEYPAD] may be used to enter the new setpoint.
NOTE: All digits must be entered, including zeros. For
example, (01.0).
NOTE: The D A Y, AUX 1, and AUX 2 setpoints, once selected,
are changed or updated by pressing the [CHANGE] key.
NOTE: Certain setpoints may be reported in either pounds
per square inch gauge (g) or inches of mercury (hg). To
toggle between (g) and (hg), ha ving selected the setpoint,
press the [+/-] key to toggle between (g) and (hg).
4. In the event that an incorrect setpoint is keyed in com-
pletely or partially, press the [CLEAR] key to restore the
original setpoint. Pressing the [CLEAR] key a second time
will eliminate the flashing brackets.
5. Having keyed the desired setpoint, press the [ENTER]
key. The new setpoint will be entered and the flashing br ackets will move or step to the next setpoint.
NOTE: A setpoint entry outside the parameters of the
Adjustable Setpoint display will be refused and the original Adjustable setpoint will be restored.
NOTE: To clear any time values [STEP] to the desired
setpoint, press [CHANGE] and then press [CLEAR].
HOW T O DETERMINE
ADJUST ABLE SETPOINTS:
Adjustable Setpoints should reflect values compatible with
normal system operation. Too high a Low Suction Pressure
Alarm setpoint may cause nuisance prealarms. Similarly,
cutout setpoints should not fall within what are considered
normal plant operation. As a rule of thumb, set the Low Suction Pressure Alarm 5 PSIG lower than the lowest normal
suction pressure. The Low Suction Pressure Cutout should
be 5 to 10 PSIG lower than the Low Suction Pressure Alarm
setpoint.
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
The High Discharge Pressure Cutout should be set at 90%
of the setting of the lowest high side relief valve. The High
Discharge
the Cutout.
The Capacity Control setpoint should be the equivalent of
the normal suction condition.
Pressure Alarm should be set 10 PSIG lower than
OPERATION
FIXED SETPOINTS:
Fixed setpoints define the limits of acceptable compressor
operation. Fix ed Setpoints are factory determined, stored in
programmed memory (PROM), and will remain in memory if
power to the microprocessor is interrupted.
SETPOINTS DISPLAY, Page 3:
OIL HEA TER - The Oil Heater setpoint, reported in degrees
Fahrenheit, turns on the oil separator heater(s) when the oil
temperature equals or falls below this setpoint whenev er the
compressor is NOT running.
LIQ INJ CON - The Liquid Injection Control, reported in degrees Fahrenheit, will shut off the liquid refrigerant supply to
the compressor if the oil temperature equals or falls below
this setpoint.
HI DISCH CUT ported in degrees Fahrenheit, will shut down the compressor if
the discharge temperature equals or exceeds this setpoint.
HI DISCH ALARM - The High Discharge T emperature Alarm,
reported in degrees Fahrenheit, will trigger a prealarm if the
discharge temperature equals or exceeds this setpoint.
The High Discharge Temperature Cutout, re-
SETPOINTS DISPLAY, Fixed, Pa ge 4:
HI OIL TEMP CUTOUT - The High Oil Temperature Cutout,
reported in degrees Fahrenheit, will shut down the compressor if the oil temperature equals or exceeds this setpoint.
HI OIL TEMP ALARM - The High Oil Temperature Alarm,
reported in degrees Fahrenheit, will trigger a prealarm if the
oil temperature equals or exceeds this setpoint.
LOW OIL TEMP CUTOUT - The Low Oil T emperature Cutout,
reported in degrees Fahrenheit, will shut down the compressor if the oil temperature equals or falls below this setpoint.
LOW OIL TEMP ALARM - The Low Oil Temperature Alarm,
reported in degrees Fahrenheit, will trigger a prealarm if the
oil temperature equals or falls below this setpoint.
LO OIL PRESS CUTOUT - The Low Oil Cutout will shut
down the compressor when the oil pressure equals or falls
below this setpoint.
LO OIL PRESS ALARM - The Low Oil Alarm will trigger a
prealarm when the oil pressure equals or falls below this
setpoint.
When a prealarm or cutout occurs, a flashing ALARM or
CUTOUT indicator will appear in the lower right hand corner
of the Operating display. To determine the fault, rotate to the
Annunciator display by pressing the [CHANGE] key.
Page 19
Revised 8/97
ANNUNCIA T OR DISPLAY *
ANNUNCIATOR: PG-01 Thu 03-01-89 15:33:36
(Use STEP key to advance PAGE)
High Press. Cutout*********************
High Press. Alarm*********************
The Annunciator display lists all ke y operative points on nine
sequential displays. These displa ys can be rotated from page
#1 thru page #9 by pressing the [STEP] key . When a prealarm
or cutout is triggered, the pertinent point will flash and the
time of the occurrence will be recorded to the right of the
alarm.
ANNUNCIATOR: PG-11 Thu 03-01-89 15:33:36
(Use STEP key to advance PAGE)
Low Motor Amps*********************
Sensor Fault*********************
*Displays for illustrative purposes only.
Page 20
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
OPERATION
Compressor Differential Cutout - The differential cutout
has been lowered from 55 lb to 25 lb. Cutout will occur after
five minutes. T o allow oper ation at low differential pressures ,
the micro will take the following steps:
A. Force unload the compressor to 50% and display an "F
Unload" when the oil pressure is within 10 lb of the main oil
injection port pressure and the slide valve position is greater
than 50%.
B. Prohibit the compressor from loading and display a "Ld
Inhib" message when the differential is within 15 lb of the
main oil injection port pressure.
Oil Pressure Alarm and cutout - Prelube and Cycling Oil
Pump version when pump is not running. Alarm will occur if
oil pressure is 25 lb below discharge pressure or within 10
lb of suction pressure for 30 seconds. Cutout occurs if oil
pressure is 30 lb below discharge pressure or if oil pressure
is within 7 lb of suction pressure for 10 seconds and alarm
has already been set.
Full Lube and Cycling Oil Pump version when oil pump is
running. Alarm occurs if oil pressure is within 10 lb of discharge pressure for 30 seconds. Cutout occurs when oil
pressure is within 5 lb of discharge pressure for 10 seconds
and oil pressure alarm has been set.
Cycling Oil Pump Control - The oil pump will cut off when
differential pressure between suction and discharge pressure is 55 lb or greater. Upon pump termination the above
cutout logic (pump not running) is utilized. Pump cut-in occurs when the differential pressure between suction and discharge is 45 lb or less. Oil pressure alarm and cutout logic
(pump running) begins after a 30 second delay which allows the oil pump to build pressure.
Prealarms are self-clearing. At this time the alarm will stop
flashing, but the time of the first occurrence will still be recorded to the right of the alarm. Pressing the [CLEAR] key
while at the Annunciator display will clear all alarms and/or
cutouts.
In order to restore the Annunciator display and resume normal operation it will be necessary to go through the following steps:
1. Correct the conditions causing the alarm.
2. Press the [ALARM SILENCE] key. (This action ma y pre-
cede correcting the conditions causing the alarm).
3. To clear or reset the Annunciator pages, press the
[CLEAR] key. This will also clear the ALARM or CUTOUT
indicator from the Operating display.
4. Press [F1] to call up the Operating display. If the conditions causing the alarm have not been corrected or a new
fault has occurred, a new ALARM or CUTOUT message
will appear.
NOTE: Use of the Emergency Stop Button may trip one
or more alarm setpoints.
SHUTDOWN RECORD DISPLAY *
SHUTDOWN RECORD P1 Thu 03-01-89 15:33:36
Hi Oil Temp Cutout *********************
Hi Oil Temp Cutout *********************
Low Temp Cutout *********************
The Shutdown Record display keeps a record of the last six
shutdowns (cutouts). This information will help troubleshoot
persistent operational problems. The most recent cutout will
appear on the top line of page 1 of the display with the oldest appearing on the last or bottom line of page 2. When a
cutout occurs, all information is moved down one line and
the new cutout appears at the top of page 1. When the display is full, the oldest record is dropped off the display and
is not retained in memory. The information presented is echoed from the Annunciator display, providing the type of cutout, the day, the date, and the time. NOTE: This informa-
tion will not be lost due to power failure.
FREEZE DISPLAY *
FREEZE DISPLAY P1 Thu 03-01-89 15:33:36
SuctionDischOilCUTOUT Compressor
14.3 hg120 g 060 gOFF Mode
-040 F135 F 135 F
FREEZE DISPLAY P2 Thu 03-01-89 15:33:36
V RatioSV PosPump%FLASep 132
2.2000%off000%HTR off
AutoAuto L
The Freeze displa y has the same appear ance and contains
the same information as the Operating display. (For a description of the information presented by the Freeze displa y,
refer to the Operating display.) The Freeze display freezes
the information of the Operating display A T THE MOMENTOF A COMPRESSOR CUTOUT. The information on the
Freeze displa y can help the operator to identify the cause of
a fault which occurred when no one was present. The F reeze
display will retain the information generated by a cutout until
a new cutout occurs or power is removed from the microprocessor.
Do not confuse the Freeze display
with the Operating display. In or-
der to avoid confusion remember
that the displayed information on the Operating displa y
is constantly being updated and changed. The Freeze
display is fixed and FREEZE DISPLAY appears in the
upper left hand corner of the display.
NOTE: The Freeze display will appear as a blank screen
when power is initially furnished to the unit, and it will
return to a blank screen anytime power is removed fr om
the microprocessor.