Frick RXB PLUS Installation Operation & Maintenance

S70-101 IOM/JAN 2000
File: SERVICE MANUAL - Section 70 Replaces: S70-101 IOM/APR 96 Dist: 3, 3a, 3b, 3c
Installation - Operation - Maintenance
ROTARY SCREW COMPRESSOR UNITS
WITH
MICROPROCESSOR CONTROL
ALL REFRIGERANTS
THIS MANUAL CONTAINS RIGGING, ASSEMBLY, START-UP, AND MAINTENANCE INSTRUCTIONS. READ THOROUGHLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE IN­STRUCTIONS COULD RESUL T IN D AMAGE OR IMPR OPER OPERA­TION OF THE UNIT.
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
Page 2
INSTALLATION - OPERATION - MAINTENANCE
TABLE OF CONTENTS
GENERAL INFORMA TION
Preface..............................................................................3
Design Limitations ............................................................3
Job Inspection...................................................................3
Transit Damage Claims.....................................................3
Compressor/Unit Identification ..........................................3
INSTALLATION
Foundation ........................................................................4
Handling and Moving ........................................................4
Skid Removal....................................................................5
Motor Mounting .................................................................5
Compressor/Motor Coupling Installation ..........................5
Coupling Alignment Procedure .........................................6
Hot Alignment of Compressor/Motor ................................8
Checking Motor/Compressor Rotation .............................. 8
Holding Charge and Storage ............................................ 8
Compressor Oil .................................................................8
Oil Charge.........................................................................8
Oil Heater..........................................................................8
Liquid Injection Oil Cooling ...............................................9
Dual Dip Tube Method.......................................................9
Level Control Method........................................................9
Water-Cooled Oil Cooling ...............................................10
Thermosyphon Oil Cooling ............................................. 1 0
Economizer - High Stage ................................................ 12
Electrical .........................................................................13
Motor Starter Package ....................................................13
Current Transformers (CT) Ratios...................................14
Minimum Burden Ratings................................................14
Battery Backup ...............................................................14
OPERA TION
General Information ........................................................15
Microprocessor Control Panel .........................................15
Keys and Key Functions .................................................16
To Change The Adjustable Setpoints.............................. 1 8
How To Determine Adjustable Setpoints......................... 18
Temperature-Pressure Control Program.........................22
Lead-Lag (Option)...........................................................24
Communications Troubleshooting ...................................24
How The Microprocessor Works - Summary ..................25
Multiple Compressor Sequencing...................................26
Microprocessor Telecommunications ..............................27
Communications Protocol Specifications ....................... 2 7
RXB Compressor ............................................................30
Compressor Lubrication System..................................... 30
Full-Lube Oil System ......................................................30
Compressor Oil Separation System ...............................30
Compressor Hydraulic System ....................................... 31
Compressor Oil Cooling Systems...................................32
Single-Port Liquid Injection ............................................. 3 2
Dual-Port Liquid Injection ................................................ 3 3
Liquid Injection Adjustment Procedure ...........................33
Prestart Checklist............................................................34
Initial Start-up Procedure ................................................35
Normal Start-up Procedure ............................................. 35
Restarting Unit After Power Failure.................................35
MAINTENANCE
Normal Maintenance Operations ....................................36
Compressor Shutdown and Start-up ..............................36
General Instructions For Replacing
Compressor Unit Components....................................36
Suction Check Valv e Bypass Valve ................................. 36
Oil Filter, Single...............................................................36
Oil Filter, Dual ................................................................. 3 7
Strainer, Oil Return ......................................................... 37
Strainer, Oil Pump (Optional)..........................................37
Strainer, Liquid Injection ................................................. 37
Coalescer Filter Element ................................................3 8
Changing Oil ...................................................................38
Recommended Maintenance Program ...........................38
Vibration Analysis ........................................................... 39
Oil Quality and Analysis..................................................39
Motor Bearings ...............................................................39
Operating Log .................................................................39
Maintenance Schedule ................................................... 40
Troubleshooting Guide .................................................... 4 1
Abnormal Operation Analysis and Correction ................41
Troubleshooting The Microprocessor..............................42
EPROM Memory I/C Chip Replacement ........................45
SBC Board Replacement................................................45
Microprocessor Display Replacement ............................45
Output Fuse Replacement .............................................. 45
Pressure Transducers - Testing....................................... 45
Pressure Transducer Conversion Data ...........................45
Pressure Transducers - Replacement.............................46
Volumizer Potentiometer - Replace/Adjust .....................47
Temperature/Pressure Adjustment ................................. 47
Bare Compressor Mounting ............................................47
Troubleshooting The RXB PLUS:
Compressor.................................................................48
Oil Separator System ..................................................48
Hydraulic System ........................................................ 48
Full-Time Pump Systems ............................................49
Liquid Injection Oil Cooling .........................................49
Thermal Expansion Valves .............................................50
Temperature Control Valve..............................................51
Wiring Diagrams .............................................................52
P and I Diagrams ............................................................ 58
PROPER INSTALLA TION OF ELECTRONIC
EQUIPMENT ............................................................... 61
SPARE P AR TS LIST....................................................... 64
OPERA TING LOG .......................................................... 65
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
GENERAL INFORMATION
Page 3
PREFACE
This manual has been prepared to acquaint the owner and serviceman with the INSTALLATION, OPERATION, and MAINTENANCE procedures as recommended by Frick for RXB PLUS Rotary Screw Compressor Units.
It is most important that these units be properly applied to an adequately controlled refrigeration system. Your autho­rized Frick representative should be consulted for his ex­pert guidance in this determination.
Proper performance and continued satisfaction with these units is dependent upon:
CORRECT INSTALLATION PROPER OPERATION REGULAR, SYSTEMATIC MAINTENANCE
T o ensure correct installation and application, the equipment must be properly selected and connected to a properly de­signed and installed system. The Engineering plans, piping layouts, etc. must be detailed in accordance with the best practices and local codes, such as those outlined in ASHRAE literature.
A refrigeration compressor is a V APOR PUMP. To be certain that it is not being subjected to liquid refrigerant carryover , it is necessary that refrigerant controls are carefully selected and in good operating condition; the piping is properly sized and traps, if necessary, are correctly arranged; the suction line has an accumulator or slugging protection; that load surges are known and provisions made for control; operat­ing cycles and defrosting periods are reasonable; and that high side condensers are sized within system and compres­sor design limits.
COMPRESSOR and UNIT IDENTIFICATION
Each compressor unit has 2 identification data plates. The compressor data plate, containing compressor model and serial number, is mounted on the compressor body . The unit data plate, containing unit model, serial number, and Frick sales order number, is mounted on the side of the motor base.
NOTE: When inquiring about the compressor or unit, or ordering repair parts, pro vide the MODEL, SERIAL, and FRICK SALES ORDER NUMBERS from these data plates.
It is recommended that the entering vapor temperature to the compressor be superheated to 10 ant saturation temperature. This ensures that all refrigerant at the compressor suction is in the vapor state.
O
F above the refriger-
DESIGN LIMITATIONS
The compressor units are designed for operation within the pressure and temperature limits as shown in Frick Pub. E70-100 SED.
JOB INSPECTION
Immediately upon arrival examine all crates, boxes and ex­posed compressor and component surfaces for damage. Unpack all items and check against shipping lists for any possible shortage. Examine all items for damage in transit.
TRANSIT DAMAGE CLAIMS
All claims must be made by consignee. This is an ICC re­quirement. Request immediate inspection by the agent of the carrier and be sure the proper claim forms are execut­ed.
Report damage or shor tage claims immediately to Frick , Sales Administration Department, in Waynesboro, PA.
COMPRESSOR DATA PLATE
UNIT DATA PLATE
Page 4
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
FOUNDATION
Each RXB PLUS Rotary Screw Compressor Unit is shipped mounted on a wood skid which must be removed prior to unit installation. CA UTION: Allow space f or servicing both ends
of the unit. A minimum of 24 inches is recommended.
The first requirement of the compressor foundation is that it must be able to support the weight of the compressor pack­age including coolers, oil, and refrigerant charge. Screw compressors are capable of converting large quantities of shaft power into gas compression in a relatively small space and a mass is required to effectively dampen these rela­tively high frequency vibrations.
Firmly anchoring the compressor package to a suitable foun­dation by proper application of grout and elimination of pip­ing stress imposed on the compressor is the best insurance for a trouble free installation. Use only the certified general arrangement drawings from Frick to determine the mount­ing foot locations and to allow for recommended clearances around the unit for ease of operation and servicing. Foun­dations must be in compliance with local building codes and materials should be of industrial quality.
The floor should be a minimum of 6 inches of reinforced con­crete and housekeeping pads are recommended. Anchor bolts are required to firmly tie the unit to the floor. Once the unit is rigged into place (See HANDLING and MOVING), the feet m ust then be shimmed in order to level the unit. The shims should be placed to position the feet roughly one inch above the house­keeping pad to allow room for grouting. An expansion-type epoxy grout must be worked under all areas of the base with no voids and be allowed to settle with a slight outw ard slope so oil and water can run off of the base.
When installing on a steel base, the following guidelines should be implemented to properly design the system base:
1. Use I-beams in the skid where the screw compressor will be attached to the system base. They should run parallel to the package feet and support the feet f or their full length.
2. The compressor unit f eet should be continuously welded to the system base at all points of contact, or bolted.
3. The compressor unit should not be mounted on vibration isolators in order to hold down package vibration le vels.
4. The customer’ s foundation f or the system base should fully support the system base under all areas, but most certainly under the I-beams that support the compressor package.
When installing on the upper floors of buildings, extra pre­cautions should be taken to prevent normal package vibra­tion from being transferred to the building structure. It may be necessary to use rubber or spring isolators, or a combi­nation of both, to prevent the transmission of compressor vibration directly to the structure. Howe ver , this may increase package vibration levels because the compressor is not in contact with any damping mass. The mounting and support of suction and discharge lines is also very important. Rub­ber or spring pipe supports may be required to avoid excit­ing the building structure at any pipe supports close to the compressor package. It is best to emplo y a vibration expert in the design of a proper mounting arrangement.
In any screw compressor installation, suction and discharge lines should be supported in pipe hangers (preferably within 2 ft. of vertical pipe run) so that the lines won’t move if disconnected from the compressor. See table for Allowab le Flange Loads .
A licensed architect should be consulted to determine the proper foundation requirements for any large engine or tur­bine drive.
ALLOWABLE FLANGE LOADS
NOZ. SIZE
NPS
(in.)
1
1.25
1.5 2 3 4 5 6 8
10 12 14
MOMENTS (ft-lbf) LOAD (lbf)
AXIAL VERT. AXIAL VERT. LAT.LA T.
M
R
25 25
50 100 250 400 425
1000 1500 1500 1500 2000
M
175 200 400
750 1000 1200 1500 1800
25 25 40 70
M
C
25 25 40
70 175 200 400 750
1000 1200 1500 1800
PVCV
L
50
50 100 150 225 300 400 650
1500 1500 1500 1700
50 50
75 125 250 400 450 650 900
1200 1500 2000
L
50 50
75 125 250 400 450 650 900
1200 1500 2000
When applying screw compressors at high pressures, the customer must be prepared for package vibration and noise higher than the values predicted for normal refrigeration duty . Proper foundations and proper installation methods are vi­tal; and ev en then, sound attenuation or noise curtains may be required to reduce noise to desired levels.
For more detailed information on Screw Compressor F oun­dations, please request Frick publication S70-210 IB.
FIG. 1 - RECOMMENDED LIFTING METHOD
HANDLING AND MOVING
THIS UNIT MAY BE TOP HEAVY. USE CARE WHILE HANDLING.
both the length and width of the package to prevent bending of oil lines and damage to the package.
The unit can be moved with rigging, using a crane or forklift. The recommended method is to insert lengths of 2" pipe through the lifting holes in the vertical supports (see FIG. 1). Alternatively, hooks may be used in rigging, inserting them in the lifting holes (see FIG. 2).
Use CAUTION in locating the lifting ring. If no motor is mounted, the lifting ring should be moved off center to the compressor side of the unit because 60 percent of the weight is toward the compressor end. If a motor is mounted, ap­propriate adjustment in the lifting point should be made to compensate for motor weight. Adjustment of the lifting point must also be made for any additions to the standard pack­age, such as an external oil cooler, etc., as the center of balance will be affected.
Spreader bars should be used on
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
INSTALLATION
FIG. 2 - ALTERNATIVE LIFTING METHOD
The unit can be moved with a forklift by forking under the skid, or it can be skidded into place with pinch bars by push­ing against the skid. NEVER MOVE THE UNIT BY PUSH-
ING OR FORKING AGAINST THE SEPARATOR SHELL OR ITS MOUNTING SUPPORTS.
SKID REMOVAL
If the unit is rigged into place the skid can be removed by taking off the nuts and bolts that are fastening the unit mount­ing supports to the skid before lowering the unit onto the mounting surface.
If the unit is skidded into place, remove the cross members from the skid and remove the nuts anchoring the unit to the skid. Using a 5-ton jack under the separator, raise the unit at the compressor end until it clears the two mounting bolts. Spread the skid to clear the unit mounting support, then lower the unit to the surface. Repeat procedure on opposite end.
MOTOR MOUNTING
The following procedure is required only when the motor is mounted at the job site.
1. Thoroughly clean the motor feet and mounting pads of grease, burrs, and other foreign matter to ensure firm seat­ing of the motor.
Page 5
1. Inspect the shaft of the motor and compressor to ensure
that no nicks, grease, or foreign matter is present.
2. Inspect the bores in the coupling hubs to make sure that they are free of burrs, dirt, and grit.
3. Check that the keys fit the hubs and shafts properly. CH COUPLING – The T.B. Woods Elastomeric CH Coupling
is used in most applications. It consists of two drive hubs and a loose, gear-type Hytrel Drive Spacer. The split hub is clamped to the shaft by tightening the clamp screws. T orque is transmitted from the motor through the elastomeric gear which floats freely between the hubs. Install as follows:
IT IS MANDA T OR Y THA T THE COU­PLING CENTER BE REMOVED AND THE DIRECTION OF MOTOR
ROTATION BE CONFIRMED
BEFORE
RUNNING THE COMPRESSOR. Proper rotation of the compressor shaft is clockwise looking at the end of the compressor shaft. FAILURE TO FOLLOW THIS STEP COULD RESULT IN BACKWARD COMPRESSOR ROTATION WHICH CAN CAUSE COMPRESSOR FAILURE OR EXPLOSION OF THE SUCTION HOUSING.
1. Slide one hub onto each shaft as far as possible. It may
be necessary to use a screwdriver as a wedge in the slot to open the bore before the hubs will slide onto the shafts.
2. Hold the elastomeric gear between the hubs and slide both hubs onto the gear to fully engage the mating teeth. Make sure that the keys on the compressor and motor halves of the coupling are offset 180
O
(see FIG. 3). Center the gear and hub assembly so there is equal engagement on both shafts. Adjust the space between hubs as specified in the CH Coupling Data Table below.
3. Torque the clamping bolts in both hubs to the torque value given in the CH Data Table. DO NOT USE ANY LUBRI-
CANT ON THESE BOLTS.
4. Proceed to Coupling Alignment.
2. Attach the motor to the base using the bolts and motor­raising blocks, if required. Bolt snugly through the base.
3. Weld the four kick bolts into place so that they are posi­tioned to allow movement of the motor feet.
4. Now that the motor has been set, check that the shafts are properly spaced for the coupling being used. Refer to the coupling data table for the applicable dimension.
COMPRESSOR/MOTOR COUPLING
INSTALLATION
RXB PLUS units are arranged for direct motor drive and
require a flexible drive coupling to connect the compressor to the motor. Before installing, perform the following:
FIG. 3 - COUPLING/SHAFT KEYS INSTALLATION
CH COUPLING DATA TABLE
19.0
25.4
25.4
31.8
COUPLING HUB
15/16 1-3/8
1-13/16
2-3/8
23.8
34.9
46.0
60.3
FACE SPACING
7/8
1-1/16
1-1/8
1-7/16
CH
COUP-
LING SIZE in. mm mm mmin. in. mm in. in. mm in. mm ft-lb Nm ft-lb Nm
6 7 8
9C
BETWEEN SHAFT SPACING
MIN *
3 3
3-13/16
3-9/16
76.2
76.2
96.8
90.5
3-1/4
3-7/16
4
5-7/16
MAX
101.6
138.1
161.9
149.2
SHAFT ENGAGEMENT MIN MAX
3/4
1 1
1-1/4
22.2
27.0
28.6
36.5
MAXIMUM
INDICATOR
.004 .004 .004 .004
TOTAL
READING
.104 .104 .104 .104
DRIVE COUPLING
CLAMP
BOLT
TORQUE
10 20 35 35
13.6
27.1
47.5
47.5
KEYWAY
SETSCREW
TORQUE
13 13 13 13
17.6
17.6
17.6
17.6
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
Page 6
INSTALLATION
COUPLING ALIGNMENT PROCEDURE
The life of the compressor shaft seal and bearings, as well as the life of the motor bearings, is dependent upon proper coupling alignment. Couplings may be aligned at the fac­tory but realignment MUST ALWAYS be done on the job site after the unit is securely mounted on its foundation. Ini­tial alignment must be made prior to start-up and rechecked after a few hours of operation. Final (HOT) field alignment can only be made when the unit is at operating tempera­ture. After final (HOT) alignment has been made and found to be satisfactory for approximately one week, the motor may be dowelled to maintain alignment.
NOTE: Frick recommends cold aligning the motor .005" high. This cold misalignment compensates for thermal growth when the unit is at operating temperature.
Use dial indicators to measure the angular and parallel shaft misalignment. Coupling alignment is attained by alternately measuring angular and parallel misalignment and reposi­tioning the motor until the misalignment is within specified tolerances. The following procedure is recommended.
MISALIGNMENT MUST NOT EX­CEED .004" FOR ALL CH COU­PLINGS.
FIG. 1 - ANGULAR MISALIGNMENT
ANGULAR ALIGNMENT
1. To check angular alignment, as shown in Fig. 1., attach
dial indicator rigidly to the motor hub. Move indicator stem so it is in contact with the outside face of compressor hub, as shown in Fig. 2.
2. Rotate both coupling hubs several revolutions until they seek their normal axial positions.
Check the dial indicator to be sure that the indicator stem is slightly loaded so as to allow movement in both directions.
3. Set the dial indicator at zero when viewed at the 12 o’clock position, as shown in Fig. 2.
O
4. Rotate both coupling hubs together 180 tion), as shown in Fig. 3. At this position the dial indicator will show TOTAL angular misalignment.
NOTE: The use of a mirror is helpful in reading the indi­cator dial as coupling hubs are rotated.
5. Loosen motor anchor bolts and move or shim motor to
correct the angular misalignment. After adjustments have been made for angular misalignment
retighten anchor bolts to prevent inaccurate readings. Re­peat Steps 3 through 5 to check corrections. Further adjust­ments and checks shall be made for angular misalignment until the total indicator reading is within the specified toler­ance.
(6 oclock posi-
FIG. 2 - DIAL INDICATOR ATTACHED (AT 12 O'CLOCK)
FIG. 3 - DIAL INDICATOR AT 6 O'CLOCK
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
INSTALLATION
P ARALLEL ALIGNMENT
6. To check parallel alignment, as shown in Fig. 4, reposi-
tion dial indicator so the stem is in contact with the rim of the compressor hub, as shown in Fig. 5.
Check the dial indicator to be sure that the indicator stem is slightly loaded so as to allow movement in both directions.
7. Check parallel height misalignment by setting dial indica­tor at zero when viewed at the 12 o'clock position. Rotate both coupling hubs together 180 position the dial indicator will show TWICE the amount of parallel height misalignment.
8. Loosen motor anchor bolts and add or remove shims under the four motor feet until parallel height misalignment is within specified tolerance when anchor bolts are retightened.
CARE MUST BE USED WHEN CORRECTING FOR PARALLEL
MISALIGNMENT TO ENSURE THAT THE AXIAL SPACING AND ANGULAR MISALIGN­MENT IS NOT SIGNIFICANTLY DISTURBED.
9. After the parallel height misalignment is within tolerance,
repeat Steps 1 through 5 until angular misalignment is within specified tolerance.
O
(6 o'clock position). At this
Page 7
FIG. 4 - PARALLEL MISALIGNMENT
10. Check parallel lateral misalignment by positioning dial
indicator so the stem is in contact with the rim of the com­pressor hub at 3 o'clock, as shown in Fig. 6.
Set indicator at zero and rotate both coupling hubs together
O
(9 o'clock position), as shown in Fig. 5.
180 Adjust parallel lateral misalignment using the motor adjust-
ing screws until reading is within specified tolerance.
11. Recheck angular misalignment and realign if necessary .
12. Tighten motor anchor bolts and rotate both coupling hubs
together, checking the angular and parallel misalignment through the full 360
O
travel at 90O increments. If dial read-
ings are in excess of specified tolerance, realign as required.
13. When the coupling hubs have been aligned to within specified tolerance, a recording of the cold alignment must be made for unit records and usage during hot alignment.
14. Bump the motor to check for correct compressor rota­tion. COMPRESSOR ROTATION IS CLOCKWISE WHEN
FACING COMPRESSOR SHAFT (see "CHECKING MO­TOR/COMPRESSOR ROTATION", page 8). After verifica-
tion, install gear or disk drive spacer, as applicable.
15. Install the coupling guard before operating the compres­sor.
FIG. 5 - DIAL INDICATOR ATTACHED (AT 9 O'CLOCK)
FIG. 6 - DIAL INDICATOR AT 3 O'CLOCK
When installing drive spacer, make
sure that hub spacing is within lim-
its shown on the Coupling Data T able applicable to the coupling being installed and that the clamping bolt(s) are properly torqued.
Page 8
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
HOT ALIGNMENT OF COMPRESSOR/MOTOR
Hot alignments can only be made after the unit has oper­ated for several hours and all components are at operating temperatures.
Shut down the unit and quickly affix dial indicator to cou­pling motor hub, then take readings of both the face and rim of the compressor hub. If these readings are within toler­ance, record reading, attach coupling guard, and restart unit. However, if the reading is not within limits, compare the hot reading with the cold alignment and adjust for this differ­ence; i.e. if the rim at 0 the motor rises .005" between its hot and cold state, .005" of shims should be removed from under the motor.
After the initial hot alignment adjustment is made, restart unit and bring to operating temperature. Shut down and re­check hot alignment. Repeat procedure unit hot alignment is within specified tolerance.
O
and 180O readings indicates that
INSTALL COUPLING GUARD BE­FORE OPERATING COMPRES­SOR.
CHECKING MOTOR/COMPRESSOR
ROTATION
COMPRESSOR ROTATION IS CLOCKWISE WHEN FAC­ING THE END OF THE COMPRESSOR SHAFT. Under NO
conditions should the motor rotation be checked with the coupling center installed as damage to the compressor may result.
COMPRESSOR
COMPRESSOR UNIT OIL
DO NOT MIX OILS of different brands, manufacturers, or types.
Mixing of oils may cause excessive oil foaming, nuisance oil le vel cutouts, oil pressure loss, gas or oil leakage and catastrophic compressor failure.
Use of oils other than Frick Oil must be approved in writing by Fric k en­gineering or warranty claim may be denied.
Use of filter elements other than Frick must be approved in writing by Frick engineering or warranty claim may be denied.
The oil charge shipped with the unit is the best suited lubri­cant for the conditions specified at the time of purchase. If there is any doubt due to the refrigerant, operating pres­sures, or temperatures; refer to Frick Pub. E160-802 SPC for guidance.
OIL CHARGE
The normal charging level is midway in the top sight glass located midway along the oil separator shell. Normal oper­ating level is between the top sight glass and bottom sight glass. The following table gives the approximate oil charge quantity.
TABLE - BASIC OIL CHARGE (Gal)
MODEL BASIC CHARGE* (GAL.)
12 10 15 10 19 14 24 14 30 17 39 17 50 21
HOLDING CHARGE AND STORAGE
Each compressor unit is pressure and leak tested at the Frick factory and then thoroughly evacuated and charged with dry nitrogen to ensure the integrity of the unit during shipping and short term storage prior to installation.
NOTE: Care must be taken when entering the unit to ensure that the nitrogen charge is safely released.
All units must be kept in a clean, dry location to prevent corrosion damage. Reasonable consideration must be given to proper care for the solid state components of the micro­processor. Unit which will be stored for more than two
months must have the nitrogen charge checked peri­odically.
* Add oil volume for external oil cooler, according to cooler size selected: 6 x 5 TSOC - 4 gal.; 6 x 5 WCOC - 5 gal.; 8 x 5 TSOC - 6-1/2 gal.; and 8 x 5 WCOC - 8 gal.
Add oil by attaching the end of a suitable pressure type hose to the oil charging valve, located on the top of the oil separator on the compressor end of the separator. Using a pressure-type pump and the recommended Frick oil, open the charging valve and pump oil into the separator.
Oil distillers and similar equipment which act to trap oil must be filled prior to unit operation to normal design outlet lev­els. The same pump used to charge the unit may be used for filling these auxiliary oil reservoirs.
NOTE: The sight glass, located near the bottom of the separator shell at the discharge end, should remain empty when the unit is in operation. The presence of oil in this end of the vessel during operation indicates liq­uid carryover or malfunction of the oil return.
OIL HEATER
Standard units are equipped with a 500 watt oil heater, pro­viding sufficient heat to maintain the oil temperature for most indoor applications during shutdown cycles to permit safe
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
INSTALLATION
Page 9
start-up. Should additional heating capacity be required because of unusual environmental condition, contact Frick Company. The heater is energized only when the unit is not in operation.
DO NOT ENERGIZE THE HEATER WHEN THERE IS NO OIL IN THE
UNIT, OTHERWISE THE HEATER WILL BURN OUT. THE OIL HEA TER WILL BE ENERGIZED WHENEVER 120 VOLT CONTROL POWER IS APPLIED TO THE UNIT AND THE COMPRESSOR IS NOT RUNNING UNLESS THE 10 AMP FUSE (1FU) IN THE CONTROL PANEL IS REMOVED.
LIQUID INJECTION OIL COOLING
The liquid injection system provided on the unit is self-con­tained but requires the connection of the liquid line sized as shown in the table and careful insertion of the expansion valve bulb into the thermowell provided in the separ ator. High pressure gas is connected through the regulator to the ex­ternal por t on the liquid injection valve to control oil tem­perature. Refer to the liquid injection piping diagram.
NOTE: For booster applications, the high pressure gas connection must be taken from a high side sour ce (high­stage compressor discharge). This should be a minim um 3/8" line connected into the solenoid valve provided. This gas is required by the expansion valve external port to control oil temperature.
Where low compression ratios (low condensing pressures) are anticipated, thermosyphon or water-cooled oil cooling should be used. It is IMPERATIVE that an uninterrupted supply of high pressure liquid refrigerant be provided to the injection system at all times. Two items of EXTREME IM- PORTANCE are the design of the receiver/liquid injection supply and the size of the liquid line. It is recommended that the receiver be oversized sufficiently to retain a 5 minute supply of refrigerant for oil cooling. The evaporator supply must be secondary to this consideration. Two methods of accomplishing this are shown.
DUAL DIP TUBE METHOD
The dual dip tube method uses two dip tubes in the receiv­er. The liquid injection tube is below the evaporator tube to ensure continued oil cooling when the receiver level is low.
High-stage compressor units may be supplied with single­port (low Vi) or dual-port (low Vi and high Vi), liquid injection oil cooling. Single port will be furnished for low compression ratio operation and dual port for high compression ratio op­eration. Booster compressor units use single-port, liquid in­jection oil cooling due to the typically lower compression ratios.
The control system on high-stage units with dual-port, liq­uid injection oil cooling switches the liquid refrigerant supply to the high port when the compressor is operating at higher compression ratios (3.5 Vi and above) for best efficiency.
The following table giv es the condensing temperature(s) with the corresponding maximum evaporator temperature limit for liquid injection usage and the minimum evaporator tem­perature for a single-port application.
TABLE - EVAPORATOR TEMPERATURE with
SINGLE-PORT LIQUID INJECTION
MAXIMUM MINIMUM *
EVAPORATOR EV AP TEMP
CONDENS- TEMPERATURE FOR FOR
ING LIQUID INJECTION SINGLE PORT
TEMP USAGE (LOW V i)
R-717 R-22 R-717 & R-22
75OF +10OF+5 85OF +25OF +15OF -17OF 95OF +35OF +25OF -11OF
105OF +40OF +35OF- 4
O
F -23OF
O
F
LEVEL CONTROL METHOD
The level control method utilizes a float level control on the receiver to close a solenoid valve feeding the evaporator when the liquid falls below that amount necessary for 5 min­utes of liquid injection oil cooling.
* Dual Injection Kit will be shipped by Frick below these temperatures.
Page 10
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
Liquid line sizes and the additional receiver volume (quan­tity of refrigerant required for 5 minutes of liquid injection oil cooling) are given in the following table:
REF RXB RATE VOLUME
HIGH 19 1/2 15 .4
STAGE 24 1/2 20 .6
R-717 30 1/2 25 .7
HIGH 19 3/4 5/8 45 .6
STAGE 24 3/4 7/8 60 .8
R-22 30 3/4 7/8 75 1.0
BOOST- 19 1/2 3.5 .1
R-717 30 1/2 5.5 .2
BOOST- 19 3/4 1/2 9 .1
R-22 30 3/4 1/2 14.5 .2
MODEL PIPE TUBING (lb.) CU.FT.
12 1/2 10 .3 15 1/2 12.5 .4
39 1/2 30 8 50 3/4 40 1.1
12 3/4 5/8 30 .4 15 3/4 5/8 37.5 .5
39 3/4 7/8 95 1.3 50 1 1 125 1.7
12 1/2 2.1 15 1/2 2.5 .1
ER 24 1/2 4.5 .1
39 1/2 6.5 .2 50 1/2 –- 8.5 .3
12 3/4 1/2 6 .1 15 3/4 1/2 7 .1
ER 24 3/4 1/2 12 .2
39 3/4 1/2 18 .3 50 3/4 5/8 24 .3
LIQ. LINE SIZE* FLOW LIQUID
SCH 80 OD 5 MIN
* 100 ft. liquid line. For longer runs, increase line size ac-
cordingly.
NOTE: The water regulating valve shipped with the unit will be sized to the specific flow for the unit.
THERMOSYPHON OIL COOLING (OPTIONAL)
Thermosyphon oil cooling is an economical, effective method for cooling oil on screw compressor units. Thermosyphon cooling utilizes liquid refrigerant at condenser pressure and temperature which is partially vaporized at the condenser temperature in a shell and tube- or plate-type vessel cool­ing the oil to within 15 condensing pressure, is vented to the condenser inlet and reliquified. This method is the most cost effective of all cur­rently applied cooling systems since no compressor capac­ity is lost or compressor power penalties incurred. The va­por from the cooler need only be condensed, not com­pressed. Refrigerant flow to the cooler is automatic, driven by the thermosyphon principle, and cooling flow increases as the oil inlet temperature rises.
EQUIPMENT - The basic equipment required for a ther­mosyphon system consists of:
1. A source of liquid refrigerant at condensing pressure and temperature located in close proximity to the unit to mini­mize piping pressure drop. The liquid le vel in the refrigerant source must be 6 to 8 feet above the center of the oil cooler .
2. A shell and tube- or plate-type oil cooler with a 300 psi minimum design working pressure on both the oil and re­frigerant sides.
Due to the many variations in refrigeration system design and physical layout, several systems for ensuring the above criteria are possible.
O
F of that temperature. The vapor, at
WATER-COOLED OIL COOLING (OPTIONAL)
The shell and tube-type, water-cooled oil cooler is mounted on the unit complete with all oil piping. The customer must supply adequate water connections and install the two-way water regulating valve. It is recommended that (local codes permitting) the water regulator be installed on the water outlet connection. Insert the water regulator valve bulb and well in the chamber provided on the oil outlet connection. Deter­mine the size of the water-cooled oil cooler supplied with the unit, then refer to table for the water connection size and water flow range (GPM). The water supply must be
sufficient to meet the required flow.
It is imperative that the condition of cooling water and closed loop fluids be analyzed and maintained regularly and as necessary to prevent corrosion of heat exchanger surfaces. The oxygen content of river water and some other cooling water sources will oxidize steel tubes and cause premature failure. Careful attention to water treatment is essential to ensure adequate life of steel cooler tubes if cooling tower water is used. The condition of heat e xchanger tubes should be checked semiannually to prevent hazard.
OIL COOLER DATA TABLE
SIZE - Inches APPROX
WATER FLOW
COOLER WATER CONN RANGE (GPM)
5 Foot Lengths
6" DIA. 1 NPT 10 – 23 8" DIA. 1-1/4 NPT 35 – 60
SYSTEM OPERATION - Liquid refrigerant fills the cooler tube side up to the Thermosyphon receiver liquid level.
Water or hot oil (above the liquid temperature) flowing through the cooler will cause some of the refrigerant to boil and vaporize in the tubes. The vapor rises in the return line. The density of the refrigerant liquid/vapor mixture in the re­turn line is considerably less than the density of the liquid in the supply line. This imbalance provides a differential pres­sure that sustains a flow condition to the oil cooler. This re­lationship involves:
1. Liquid height above the cooler.
2. Oil heat of rejection.
3. Cooler size and piping pressure drops.
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
INSTALLATION
Page 11
Current thermosyphon systems are using two-pass oil cool­ers and flow rates based on 4:1 overfeed.
The liquid/vapor returned from the cooler is separated in the receiver. The vapor is vented to the condenser inlet and need only be reliquified since it is still at condenser pressure.
INSTALLATION - The shell and tube-type thermosyphon oil cooler with oil-side piping and a thermostatically controlled mixing valve (if ordered) are factory mounted and piped. The customer must supply and install all piping and equipment located outside of the shaded area on the piping diagram with consideration given to the following:
1. The refrigerant source, thermosyphon or system receiv­er, should be in close pro ximity to the unit to minimize piping pressure drop.
2. The liquid level in the refrigerant source must be 6 to 8 feet above the center of the oil cooler.
3. A safety valve should be installed if refrigerant isolation
valves are used for the oil cooler.
4. F rick recommends the installation of an angle v alve in the piping before the thermosyphon oil cooler to balance the thermosyphon system. Frick also recommends the installa­tion of sight glasses at the TSOC inlet and outlet to aid in troubleshooting. The factory-mounted, plate-type ther­mosyphon oil cooler requires a refrigerant-side drain valve to be provided and installed by the customer.
TSOC AND WCOC OPTIONAL OIL SIDE SAFETY RELIEF
- Compressor units, which have valves in the oil piping to
isolate the oil cooler from the oil separator for servicing, may have factory installed piping to relieve the shell side (oil side) safety valve directly into the oil separ ator, as sho wn in the P & I diagrams on pages 58 through 60.
This arrangement uses a special UV stamped safety valve rated for liquid and vapor relief . The safety v alve is designed for 500 psi DWP and is set to relieve at 75 psi delta P. The safety valve piping contains flanged connections should the valve require maintenance or replacement.
Extra caution should be used when servicing an oil sepa­rator with this arrangement. If the oil cooler is valved off from an oil separator which has been evacuated for ser­vicing, then the oil cooler could relieve into the separa­tor vessel if the 75 psi delta p setpoint is exceeded.
Other units, which do not use this special safety valve ar­rangement, will have factory mounted safety valves on the shell side of the oil cooler which the installing contractor should pipe into house safety systems designated suitable for oil relief.
The component and piping arrangement shown below is in­tended only to illustrate the operating principles of thermosy­phon oil cooling. Other component la youts ma y be better suited to a specific installation. Ref er to publication E70-900E for ad­ditional information on Thermosyphon Oil Cooling.
CONDENSER
STATIC HEAD TO O VERCOME CONDENSER PRESSURE DROP
8 Ft. Min.
TSOCA
SYSTEM
SAFETY
VALVE
OIL TEMP
CONTROLVALVE
A
B
HOT
COOL
2
OIL OUT
THERMOSYPHON
OIL COOLER
HOT OIL IN
VAPOR
3
THERMOSYPHON RECEIVER
LIQUID
LEVEL
C
1
Refrigerant-side drain valve required for plate-type thermosyphon oil coolers.
LIQUID OVERFLOW DRAIN TO RECEIVER
TO SYSTEM
4
EVAPORATOR
SYSTEM
RECEIVER
(Mounted below Thermosyphon
receiver le vel)
1. The thermosyphon oil cooler is supplied with the oil side piped to the compressor unit and stub ends supplied on the refriger­ant side.
2. A three-way oil temperature control valve is required where condensing temperature is expected to go below 65
3. A refrigerant-side saf ety valv e is required in this location only when refrigerant isolation valv es are installed between the cooler
and thermosyphon receiver. If no valves are used between the cooler and TSOC receiver, the safety v alv e on the TSOC receiver must be sized to handle the volume of both vessels. Then, the safety valve on the cooler vent (liquid refrigerant side) can be eliminated.
4. The system receiver must be below the thermosyphon receiver in this arrangement.
O
F.
Page 12
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
ECONOMIZER - HIGH STAGE (OPTIONAL)
The economizer option provides an increase in system ca­pacity and efficiency by subcooling liquid from the condenser through a heat exchanger or flash tank before it goes to the evaporator. The subcooling is provided by flashing liquid in the economizer cooler to an intermediate pressure level.The intermediate pressure is provided by a port located part way down the compression process on the screw compressor.
As the screw compressor unloads, the economizer port will drop in pressure level, eventually being fully open to suc­tion. Because of this, an output from the microprocessor is generally used to turn off the supply of flashing liquid on a shell and coil or DX economizer when the capacity falls be­low approximately 45%-60% capacity (85%-90% slide valve position). This is done because the compressor will be more efficient operating at a higher slide valve position with the economizer turned off, than it will at a low slide valve posi­tion with the economizer turned on. Please note however that shell and coil and DX economizers can be used at low compressor capacities in cases where efficiency is not as important as ensuring that the liquid supply is subcooled. In such cases, the economizer liquid solenoid can be pro­grammed to be left open whenever the compressor is run­ning.
Due to the tendency of the port pressure to fall with de­creasing compressor capacity, a back-pressure regulator valve (BPR) is generally required on a flash economizer system (FIG. 3) in order to maintain some preset pressure difference between the subcooled liquid in the flash vessel and the evaporators. If the back-pressure regulator valve is not used on a flash economizer, it is possible that no pres­sure difference will exist to drive liquid from the flash v essel to the evaporators, since the flash vessel will be at suction pressure. In cases where wide swings in pressure are an-
ticipated in the flash economizer vessel, it may be neces­sary to add an outlet pressure regulator to the flash vessel outlet to avoid overpressurizing the economizer port, which could result in motor overload. Example: A system feeding liquid to the flash vessel in batches.
The recommended economizer systems are shown below. Notice that in all systems there should be a strainer (STR) and a check valve (VCK) between the economizer vessel and the economizer port on the compressor. The strainer prevents dirt from passing into the compressor and the check valve prevents oil from flowing from the compressor unit to the economizer vessel during shutdown.
Other than the isolation valve needed for strainer cleaning, it is
essential that the strainer be the last device in the economizer line before the compres­sor. Also, piston-type check valves are recommended for installation in the economizer line, as opposed to disc-type check valves. The latter are more prone to gas­pulsation-induced failure. The isolation and check val­ves and strainer should be located as closely as pos­sible to the compressor, preferably within a few feet.
For refrigeration plants employing multiple compressors on a common economizing vessel, regardless of economizer type, each compressor must have a back-pressure regulat­ing valve in order to balance the economizer load, or gas flow, between compressors. The problem of balancing load becomes most important when one or more compressors run at partial load, exposing the economizer port to suction pressure. In the case of a flash vessel, there is no need for the redundancy of a back-pressure regulating valve on the vessel and each of the multiple compressors. Omit the BPR valve on the flash economizer vessel and use one on each compressor, as shown in FIG. 4.
FIG. 1 - SHELL and COIL ECONOMIZER SYSTEM
FIG. 2 - DIRECT EXPANSION ECONOMIZER SYSTEM
FIG. 3- FLASH ECONOMIZER SYSTEM
FIG. 4 -MUL TIPLE COMPRESSOR ECONOMIZER SYSTEM
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
INSTALLATION
Page 13
ELECTRICAL
NOTE: Before proceeding with electrical installation, read the instructions in the section Proper Installation of Electronic Equipment in an Industrial Environment”.
RXB PLUS units are supplied with a SBC (single-board com­puter) microprocessor control system. Care must be taken that the controls are not exposed to physical damage dur­ing handling, storage, and installation. The microprocessor enclosure cover must be kept tightly closed to prevent entry of moisture and foreign matter.
Customer-control power connec­tions are made at the BOTTOM of
the microprocessor enclosure. Consult local ordinances before installation. Current transformer wiring should be kept separate. Extreme care should be taken that metal filings or other foreign material is not left in the microprocessor enc losure. Use seal-tight conduit fittings to prevent moisture entry into the microprocessor enclosure. This is the ONL Y electri­cal enclosure that should be opened during installation and it should be kept tightly closed whenever work is not being performed in it.
1. The compressor motor starter of the specified HP and
voltage for the starting method specified (across-the-line, autotransformer, wye-delta, or solid state).
NOTE: If starting methods other than across-the-line are desired, a motor/compressor torque analysis must be done to ensure that sufficient starting torque is avail­able, particularly in booster applications. Contact FRICK Company if assistance is required.
2. If specified, the starter package can be supplied as a
combination starter with circuit breaker disconnect. Howev­er, the motor overcurrent protection/disconnection device can be supplied by others, usually as a part of an electrical power distribution board.
3. A 2.0 KVA control power transformer (CPT), to supply 120 volt control power to the control system and separator oil heaters, is included. If environmental conditions require more than a 500 watt oil heater, an appropriately oversized control transformer will be required.
4. One (1) normally open, compressor-motor-starter auxil­iary contact and 1 normally open, oil-pump-motor-star ter auxiliary contact (opt.) should be supplied and wired as shown on the starter package wiring diagram. In addition, the compressor and oil pump motor starter (opt.) coils and the CPT secondaries should be wired as shown on starter package wiring diagram.
NOTE: Customer ground required, see Micro Panel As­sembly Wiring Diagram.
MOTOR STARTER PACKAGE
5. The compressor motor Current Transformer (CT) can be installed on any one phase of the compressor leads. NOTE: The CT must see all the current on any one phase; there­fore in wye-delta applications, BOTH leads of any one phase must pass through the CT.
6. Oil Pump Option: If the optional oil pump is specified, an
oil pump starter must be a component of the unit starter package. The pump starter should be equipped with fuses or, in the case where the compressor motor is a different voltage from the oil pump motor, a circuit breaker discon­nect suitable for separate power feed.
NOTE: Do not install a compressor HAND/OFF/AUTO switch in the starter package as this would bypass the compressor safety devices.
Motor starter and interlock wiring requirements are shown in the wiring diagram, above. All the equipment shown is supplied by the installer unless a starter package is pur­chased from Frick . Starter packages should consist of:
NOTE: When compressor motor voltage is different from oil pump motor voltage, supply a cir cuit breaker discon­nect for separate feed in lieu of fuses.
Page 14
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
INSTALLATION
CURRENT TRANSFORMER (CT) RATIOS
The CT ratio for various motor sizes (with a 5 amp second­ary) is given in the following table:
VOLTAGE
HP 200 230 380 460 575 2300 4160
20 100:5 100:5 100:5 100:5 100:5 - ­25 100:5 100:5 100:5 100:5 100:5 - ­30 200:5 100:5 100:5 100:5 100:5 - ­40 200:5 200:5 100:5 100:5 100:5 - ­50 200:5 200:5 100:5 100:5 100:5 - ­60 300:5 200:5 200:5 100:5 100:5 - -
75 300:5 300:5 200:5 200:5 100:5 - ­100 400:5 300:5 200:5 200:5 200:5 - ­125 500:5 400:5 300:5 200:5 200:5 - ­150 500:5 500:5 300:5 300:5 200:5 - ­200 800:5 600:5 400:5 300:5 300:5 100:5 50:5 250 800:5 800:5 500:5 400:5 300:5 100:5 50:5
MINIMUM BURDEN RATINGS
The following table gives the minimum CT burden ratings. This is a function of the distance between the motor starting package and the compressor unit.
BA TTER Y B A CKUP
The battery backup prevents data loss during power inter­ruption. It will maintain the adjustable setpoints stored in RAM (Random Access Memory) for up to 1 year after power loss. Expected battery life is 10 years. A trickle charge main­tains the battery backup at peak charge when control volt­age is present.
To prevent power loss, the battery backup is shipped dis­abled. To enable the batter y backup, a jumper pin located near the top of the microprocessor circuit board (see illus­tration page 52) must be moved from OFF (pins 1-2) to ON (pins 2-3).
NOTE: It is not necessary to disconnect the battery backup during extended downtime.
BURDEN MAXIMUM DISTANCE FROM
RA TING FRICK P ANEL
USING # USING # USING #
ANSI VA 14 AWG 12 AWG 10 AWG
B-0.1 2.5 15 ft 25 ft 40 ft B-0.2 5 35 ft 55 ft 88 ft B-0.5 12.5 93 ft 148 ft 236 ft
In addition to the starter package interlocks shown on the starter package diagram, the following optional interlocks are on the typical RXB PLUS Screw Compressor unit with the SBC Microprocessor Control System wiring diagram:
1. Remote LOAD, UNLO AD, and RUN interlocks in case the customer desires to operate the unit from a remote control device.
2. Alarm Horn output.
3. Control solenoid valve for the economizer option.
For customer control options, consult FRICK Company.
NOTE: The microprocessor will not operate without EPROM chips installed. When EPROM chips are not in­stalled, the microprocessor display will typically indi­cate two dark lines across both the upper and lower dis­play screens.
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
OPERATION and START-UP INSTRUCTIONS
GENERAL INFORMATION
OPERATION
Page 15
The Frick RXB PLUS Rotary Screw Compressor Unit is an integrated system consisting of six major subsystems:
1. Microprocessor Control Panel
2. Compressor
3. Compressor Lubrication System
4. Compressor Oil Separation System
5. Compressor Hydraulic System
6. Compressor Oil Cooling System
MICROPROCESSOR CONTROL PANEL
The information in this section of the manual provides the logical step-by-step instructions to properly start up and op­erate the RXB PLUS Rotary Screw Compressor Unit.
THE FOLLOWING SUBSECTIONS MUST BE READ AND UNDERSTOOD BEFORE ATTEMPTING TO START OR OPERA TE THE UNIT.
The RXB PLUS compressor is controlled by a state-of­the-art microprocessor control system. The microprocessor continuously monitors the compressor units condition and operation. The microprocessor also directs instructions to the various compressor unit subsystems.
The microprocessor has a membrane switch keyboard. Pressing the keyboard in the area outlined as a key will cause that function to be recognized by the microprocessor. The keyboard has 32 membrane-type keys.
In addition to the keyboard, there is an emergency stop but­ton. Pushing the emergency stop will bypass the computer and remove all power from the outputs. This will shut down the compressor motor and all high voltage to the compres-
sor auxiliary systems such as the oil pump and liquid injec­tion solenoid. THE EMERGENCY STOP BUTTON IS FOR
EMERGENCY SHUTDOWN SITUATIONS ONLY and MUST NOT BE USED TO ROUTINELY SHUT OFF THE COMPRESSOR.
The microprocessor continuously monitors the state of the battery which maintains setpoints and various other data. If the battery voltage is low, the message “LOW BATT will flash in the lower right hand corner of the bottom display (see page 14 for description of battery backup).
The microprocessor hardware contains an output watch­dog circuit. If the microprocessor should fail, this circuit will disable (turn off) all outputs.
Page 16
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
OPERATION
Revised 2/95
KEYS AND KEY FUNCTIONS
NOTE: The microprocessor will automatically return to the main operating display after 60 seconds of keybo­ard nonactivity.
The [CHANGE] ke y rotates the dual display screen through six display modes. The [CHANGE] key is also used to change the status of various setpoints.
The [STEP] key steps or moves a set of flashing brackets through the variable setpoints on the Adjustable setpoints display, the Auto-cycle display, the Security display and the Setback display. The setpoint enclosed within the flashing brackets may be changed or updated. The [STEP] key is also used when the Annunciator display is selected to step through the annunciators four information displays.
NOTE: The [ * ] key is used to step or move the flashing brackets, described above, backwards.
The [ENTER] key is used to enter new setpoint limits. The [CLEAR] key will reset an alarm or cutout indication on
the annunciator screen and will clear the microprocessor to allow continued operation or restarting if all conditions have returned to normal and no other control lockouts are in force.
The [NUMERIC KEYPAD] is used to introduce new setpoint limits.
The [+/-] key is used to toggle between pounds per square inch gauge (g) and inches of mercury (hg).
1. Operating displays
2. Setpoints displays
3. Annunciator displays
4. Shutdown Record displays
5. Freeze displays [F1] Operating display
[F2] Security display [F3] Setback display [F4] Auto Cycle display
NOTE: On initial powering of the microprocessor, and any time power has been removed from the micropro­cessor, onl y the Operating, Setpoints, Ann unciator, and Shutdown displays will display inf ormation. The Freeze display will appear as a dark screen. The Freeze display will only be present after a compressor unit cutout.
OPERATING DISPLAY *, Pages 1 and 2
OP.DISPLAY PAGE 1 Thu 03-01-89 15:33:36
Suction Disch Oil Compressor
14.3 hg 024 g 060 g Man Mode
O
F 135OF 135OF Running
-040
OP.DISPLAY PAGE 2 Thu 03-01-89 15:33:36
V Ratio S V Pos Pump %FLA Sep 132OF
2.2 070% on 096% HTR off
Auto Auto U
The [RUN], [STOP], and [REMOTE START] keys control the starting and stopping of the compressor unit.
The [ALARM SILENCE] k ey will de-energize the alarm horn output.
The [AUTO], [REMOTE], and [MANUAL] keys control the operation of the compressor slide valve.
The [AUTO], [MANUAL 2.2], [MANUAL 3.5], and [MANUAL
5.0] keys control the operation of the compressor slide stop . The [F1] function key will return the operator to the main
operating display. This function may be inv ok ed at any time, even during setpoint entry.
The [F2] function ke y will call up the Security display. NOTE:
Press the [F2] key , as pr ompted b y the display, to return to the previously selected display.
The [F3] function ke y will call up the Setback displa y . NOTE: To exit the Setback display, press the [F1] key as prompted by the display.
The [F4] function key will call up the Auto Cycle display. NOTE: T o exit the A uto Cyc le display, press the [F1] key as prompted by the display.
The microprocessor has two liquid crystal displays in an 8 line by 40 character format, for a total of 320 characters. When power is first applied to the control panel, the unit will be in the Operating display mode. To change to a different display mode, press the [CHANGE] key. The display modes in their order of rotation are:
OPERATING DISPLAY, P age 1
The Operating display is continuously updated and pro vides a variety of information in regard to the current status of the compressors condition and performance.
The information furnished by the Operating display is as fol­lows:
The DAY, DATE, and TIME are displayed at the top right of the display.
NOTE: To set day, date, and time, see TO CHANGE THE ADJUSTABLE SETPOINTS.
SUCTION - Suction Pressure and Temperature are mea-
sured at the compressor inlet and are, respectively, displayed in pounds per square inch gauge (g) or inches of mercury (hg) and degrees Fahrenheit.
DISCH - Discharge Pressure and Temperature are measur­ed at the compressor outlet and are, respectively, displayed in pounds per square inch gauge (g) and degrees Fahren­heit.
OIL - Oil Pressure and Temperature are measured prior to entering the compressor and are, respectively, displayed in pounds per square inch gauge (g) and degrees Fahrenheit.
ALARM/CUTOUT - An Alarm or Cutout message indicates an Alarm or Cutout setpoint has been reached, or exceeded. Rotate the display mode to the Annunciator display for de­tails. In the ev ent of a cutout, rotate to the F reez e displa y f or further details.
*Display for illustrative purposes only.
COMPRESSOR - The compressor displa ys the status of the compressor unit. The mode of operation will be indicated as either manual (Man Mode) when the [RUN] key has been
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
OPERATION
pressed, automatic (AUTO MODE) when Auto Cycle has been activated, remote (RMT MODE) when the [REMOTE] key has been pressed, or off (OFF MODE).
RECYCLE DELAY - A Recycle Delay message indicates that the compressor has started and has shut down within the time delay setpoint period. The Recycle Delay will pre­vent the compressor from starting until the delay time ex­pires and is intended to prevent damage to the compressor motor from successive restarts. During Recycle Delay, the microprocessor will alternatively flash RECYCLE DELAY and the remaining delay time in minutes.
NOTE: Consult Motor Manufacturer for the recom­mended duration of the Recycle Delay.
Page 17
SETPOINTS PAGE 1B Dead Band--[/./#]
Prop. Band--[/ / %] Cycle Time--[/ / sec]
LOW % FLA---[/ / / %]
SETPOINTS PAGE 2 MLC Stop LD-[095%] CT Factor-[078] MLC Force ULD[100%] Aux1[Alarm] [NO] Hi Disch Cutout-[050 g ] Aux2[Shutd] [NO] Hi Disch Alarm[045 g ]
If the [RUN] key is pushed while the unit is in Recycle Delay, the compressor will start at the end of the delay period.
OPERATING DISPLAY, P age 2
V RATIO - Volume Ratio is the ratio selected by the micro-
processor to provide the highest efficiency at any given suc­tion and discharge pressure condition. Immediately below this, an information space has been provided to indicate whether V ratio is in the automatic (AUTO) or the manual (MAN) mode.
SV POS - Slide valve position is display ed as a percentage. This percentage reflects the mechanical position of the slide valve and does not reflect the percentage of full load opera­tion. Immediately below this information, space has been provided to indicate whether SV Pos is in the automatic (AUT O), manual (MAN), or remote (RMT) mode . The micro­processor will control this function in the automatic mode. To the right of the mode indicator, two other messages may appear:
L - Indicates Slide Valve loading. U - Indicates Slide Valve unloading.
PUMP (Optional) - Pump displays the current status of the oil pump. The display will read ON or OFF whenever the HAND-OFF-AUT O switch is selected to A UT O and the com­pressor is running.
% FLA - Percent Full-Load Amps displays the percentage of the drive motor, full-load amperage rating that the motor is currently using.
SETPOINTS PAGE 3 HIGH STAGE RXB NP-22 Oil Heater----- [113F] Liq Inj Con-------[122F]
Hi Disch Cut -[212F] Hi Disch Alarm -[194F]
SETPOINTS PAGE 4 Hi Oil Temp Cutout --[167F] Alarm -- [158F] Lo Oil Temp Cutout -- [49F] Alarm -- [58F] Lo Oil Press. Cutout -- [005] Alarm -- [010]
The information furnished by these displays is as follows:
PB-[10% DB-[1.0 #]
SETPOINTS DISPLAY, Page 1A:
CAP CONTROL - The Capacity Control setpoint, reported
in pounds per square inch gauge (g) or inches of mercury (hg), controls the loading and unloading of the compressor when Capacity is in the automatic (AUTO) mode.
LO SUCT CUTOUT - The Low Suction Pressure Cutout, reported in pounds per square inch gauge (g) or inches of mercury (hg), will shut down the compressor if the suction pressure drops to this limit or lower, f or 90 seconds or longer .
LO SUCT ALARM - The Low Suction Pressure Alarm, re­ported in pounds per square inch gauge (g) or inches of mercury (hg), will trigger a prealarm if the suction pressure drops to this limit or lower.
ID - The ID number is a prog rammable identification code in telecommunications to access a specific compressor.
used
SEP - Separator displays the oil separator temperature in degrees Fahrenheit.
HTR - Heater displays the condition of the oil separator heater(s), indicating ON or OFF.
FORCED UNLD - A Forced Unload message indicates that the percentage of motor, full-load amps has exceeded the maximum limit and the microprocessor is unloading the com­pressor until the percentage FLA falls back to normal limits.
SETPOINTS DISPLAY *
SETPOINTS PAGE 1A ID=[33] [03-01-89] Cap. Control-----[14.3 hg] Thu [15:33:36] Lo Suct Cutout -[20.0 hg] Baud----[ 2400] Lo Suct Alarm --[18.0 hg] Recy.Delay-[30]
*Display for illustrative purposes only.
DATE - The Date displays the current date in the following format: Month - Day - Year.
DAY - Day will display the current day of the week. TIME - The Time displays the current time in the following
format: Hours - Minutes - Seconds. The time is in 24:00:00 hour clock format.
BAUD - Shows the baud rate of the RS422 communication port. Both ports are configured as follows: w ord = 8 bit, par­ity = none or even, stop = 1 bit. The communications port is programmable from 300 to 19200 baud.
RECY. DELAY - The Recycle Delay displays the current recycle delay setpoint in minutes. NOTE: Consult the mo-
tor manufacturer for recommended setpoint.
Page 18
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
OPERATION
SETPOINTS DISPLAY, P a ge 1B:
Dead Band - This is a + (plus) or - (minus) value above or
below the setpoint at which the compressor will neither load nor unload. A dead band of 1 is the default value. It is ad­justable between .5 lb to 5 lb in increments of .5. The [Step] key is used to select this setpoint; then press the [Change] key to toggle through the selections.
Proportional Band - This setpoint is used to determine the amount of time the load/unload solenoid is energized, ac­cording to how far from the setpoint the actual control pres­sure is. The smaller the number, the longer a load/unload signal will be sent; 10% is the default value. Selections are 2, 5, 10, 15, 20, or 25%. The [Step] k ey is used to select this setpoint; then press the [Change] ke y to toggle through the selections.
Cycle Time - Cycle time is the amount of time between the beginning of each load/unload response. Ten seconds is the default value. Cycle Time” is adjustable between 5 and 30 seconds in 5 second intervals. The [Step] key is used to select a setpoint; then press the [Change] key to toggle through the selections.
Low % FLA - This setpoint is used to determine if the cou­pling has broken; 20% is the default value. It is adjustable from 0 to 100% FLA. Use the [Step] ke y to select a setpoint; then enter the desired setpoint and press the [Enter] key.
AUX 1 and A UX 2 - May be configured f or either an alarm or shutdown and with either a normally closed (NC) or nor­mally open (NO) contact.
TO CHANGE THE ADJUSTABLE SETPOINTS:
Adjustable Setpoints are stored in RAM (random access memory) and are easily changed in the field.
Adjustable Setpoints are lost if power is interrupted and the bat-
tery is not fully charged. To facili­tate reentry, we suggest that a list of Adjustable Setpoints be affixed to one end of the microprocessor cabinet for reference.
NOTE: The following procedure also applies to the chang­ing of the Security, Setback, and Auto Cycle display setpoints.
1. Press the [CHANGE] key to rotate the display to the Ad-
justable Setpoints display.
2. Press the [STEP] key to move or step a set of flashing brackets through the v arious setpoints. A setpoint is selected for change or update when it is enclosed by the flashing brackets.
NOTE: The DAY indicator, itself, will flash when selected for change or update.
SETPOINTS DISPLAY, Page 2:
MLC STOP LD - The Motor Load Control Stop Load, re-
ported as a percentage of the motor, full-load amps (FLA), will prevent the compressor capacity control pistons from loading when the setpoint is equaled or exceeded. NOTE:
Consult motor manufacturer for recommended setpoint. MLC FORCE ULD - The motor Load Control Force Unload,
reported as a percentage of the motor, full-load amps (FLA), will force the compressor to unload until the motor, full-load amps (FLA) fall within 1% of the setpoint or lower. NOTE:
Consult motor manufacturer for recommended setpoint. HI DISCH CUTOUT - The High Discharge Pressure Cutout,
reported in pounds per square inch gauge (g), will shut down the compressor if the discharge pressure equals or exceeds this setpoint.
HI DISCH ALARM - The High Discharge Pressure Alarm, reported in pounds per square inch gauge (g) will trigger a prealarm if the discharge pressure equals or exceeds this setpoint.
CT FACTOR - The Current Transformer Factor records the proper current transformer factor to match the compressor motor FLA rating to the current transformer primary rating. The CTF factor is programmable and its correct value is determined by the following formula:
CTF =
* See motor nameplate. ** See CT located in starter panel.
EXAMPLE: FLA = 230 Amps CT = 300 (300:5)
CTF = = 78 (Round to whole number)
10x CT (Current Transformer Primary Amps **)
1024 x 230 10 x 300
1024 x FLA (Full Load Amps *)
3. Having selected the setpoint to be changed, the [NU­MERIC KEYPAD] may be used to enter the new setpoint. NOTE: All digits must be entered, including zeros. For example, (01.0).
NOTE: The D A Y, AUX 1, and AUX 2 setpoints, once selected, are changed or updated by pressing the [CHANGE] key.
NOTE: Certain setpoints may be reported in either pounds per square inch gauge (g) or inches of mercury (hg). To toggle between (g) and (hg), ha ving selected the setpoint, press the [+/-] key to toggle between (g) and (hg).
4. In the event that an incorrect setpoint is keyed in com-
pletely or partially, press the [CLEAR] key to restore the original setpoint. Pressing the [CLEAR] key a second time will eliminate the flashing brackets.
5. Having keyed the desired setpoint, press the [ENTER] key. The new setpoint will be entered and the flashing br ack­ets will move or step to the next setpoint.
NOTE: A setpoint entry outside the parameters of the Adjustable Setpoint display will be refused and the origi­nal Adjustable setpoint will be restored.
NOTE: To clear any time values [STEP] to the desired setpoint, press [CHANGE] and then press [CLEAR].
HOW T O DETERMINE
ADJUST ABLE SETPOINTS:
Adjustable Setpoints should reflect values compatible with normal system operation. Too high a Low Suction Pressure Alarm setpoint may cause nuisance prealarms. Similarly, cutout setpoints should not fall within what are considered normal plant operation. As a rule of thumb, set the Low Suc­tion Pressure Alarm 5 PSIG lower than the lowest normal suction pressure. The Low Suction Pressure Cutout should be 5 to 10 PSIG lower than the Low Suction Pressure Alarm setpoint.
RXB PLUS ROTARY SCREW COMPRESSOR UNITS S70-101 IOM
The High Discharge Pressure Cutout should be set at 90% of the setting of the lowest high side relief valve. The High Discharge the Cutout.
The Capacity Control setpoint should be the equivalent of the normal suction condition.
Pressure Alarm should be set 10 PSIG lower than
OPERATION
FIXED SETPOINTS:
Fixed setpoints define the limits of acceptable compressor operation. Fix ed Setpoints are factory determined, stored in programmed memory (PROM), and will remain in memory if power to the microprocessor is interrupted.
SETPOINTS DISPLAY, Page 3:
OIL HEA TER - The Oil Heater setpoint, reported in degrees
Fahrenheit, turns on the oil separator heater(s) when the oil temperature equals or falls below this setpoint whenev er the compressor is NOT running.
LIQ INJ CON - The Liquid Injection Control, reported in de­grees Fahrenheit, will shut off the liquid refrigerant supply to the compressor if the oil temperature equals or falls below this setpoint.
HI DISCH CUT ­ported in degrees Fahrenheit, will shut down the compressor if the discharge temperature equals or exceeds this setpoint.
HI DISCH ALARM - The High Discharge T emperature Alarm, reported in degrees Fahrenheit, will trigger a prealarm if the discharge temperature equals or exceeds this setpoint.
The High Discharge Temperature Cutout, re-
SETPOINTS DISPLAY, Fixed, Pa ge 4:
HI OIL TEMP CUTOUT - The High Oil Temperature Cutout,
reported in degrees Fahrenheit, will shut down the compres­sor if the oil temperature equals or exceeds this setpoint.
HI OIL TEMP ALARM - The High Oil Temperature Alarm, reported in degrees Fahrenheit, will trigger a prealarm if the oil temperature equals or exceeds this setpoint.
LOW OIL TEMP CUTOUT - The Low Oil T emperature Cutout, reported in degrees Fahrenheit, will shut down the compres­sor if the oil temperature equals or falls below this setpoint.
LOW OIL TEMP ALARM - The Low Oil Temperature Alarm, reported in degrees Fahrenheit, will trigger a prealarm if the oil temperature equals or falls below this setpoint.
LO OIL PRESS CUTOUT - The Low Oil Cutout will shut down the compressor when the oil pressure equals or falls below this setpoint.
LO OIL PRESS ALARM - The Low Oil Alarm will trigger a prealarm when the oil pressure equals or falls below this setpoint.
When a prealarm or cutout occurs, a flashing ALARM or CUTOUT indicator will appear in the lower right hand corner of the Operating display. To determine the fault, rotate to the Annunciator display by pressing the [CHANGE] key.
Page 19
Revised 8/97
ANNUNCIA T OR DISPLAY *
ANNUNCIATOR: PG-01 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) High Press. Cutout ********************* High Press. Alarm *********************
ANNUNCIATOR: PG-02 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Low Press. Cutout ********************* Low Press. Alar m *********************
ANNUNCIATOR: PG-03 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Oil Press. Cutout ********************* Oil Press. Alarm *********************
ANNUNCIATOR: PG-04 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Hi Oil Temp Cutout ********************* Hi Oil Temp Alarm *********************
ANNUNCIATOR: PG-05 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Low Oil Temp Cutout ********************* Low Oil Temp Alarm *********************
ANNUNCIATOR: PG-06 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Disch. Temp Cutout ********************* Disch. Temp Alarm *********************
ANNUNCIATOR: PG-07 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Comp. Auxiliary ********************* Pump Aux. Not Used *********************
ANNUNCIATOR: PG-08 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Oil Level ********************* Comp. Differential *********************
ANNUNCIATOR: PG-09 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Superheat Cutout ********************* Superheat Alarm *********************
ANNUNCIATOR: PG-10Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Aux. 1 (Alarm) ********************* Aux. 2 (Shutdown) *********************
The Annunciator display lists all ke y operative points on nine sequential displays. These displa ys can be rotated from page #1 thru page #9 by pressing the [STEP] key . When a prealarm or cutout is triggered, the pertinent point will flash and the time of the occurrence will be recorded to the right of the alarm.
ANNUNCIATOR: PG-11 Thu 03-01-89 15:33:36 (Use STEP key to advance PAGE) Low Motor Amps ********************* Sensor Fault *********************
*Displays for illustrative purposes only.
Page 20
RXB PLUS ROTARY SCREW COMPRESSOR UNITSS70-101 IOM
OPERATION
Compressor Differential Cutout - The differential cutout
has been lowered from 55 lb to 25 lb. Cutout will occur after five minutes. T o allow oper ation at low differential pressures , the micro will take the following steps:
A. Force unload the compressor to 50% and display an "F Unload" when the oil pressure is within 10 lb of the main oil injection port pressure and the slide valve position is greater than 50%.
B. Prohibit the compressor from loading and display a "Ld Inhib" message when the differential is within 15 lb of the main oil injection port pressure.
Oil Pressure Alarm and cutout - Prelube and Cycling Oil Pump version when pump is not running. Alarm will occur if oil pressure is 25 lb below discharge pressure or within 10 lb of suction pressure for 30 seconds. Cutout occurs if oil pressure is 30 lb below discharge pressure or if oil pressure is within 7 lb of suction pressure for 10 seconds and alarm has already been set.
Full Lube and Cycling Oil Pump version when oil pump is running. Alarm occurs if oil pressure is within 10 lb of dis­charge pressure for 30 seconds. Cutout occurs when oil pressure is within 5 lb of discharge pressure for 10 seconds and oil pressure alarm has been set.
Cycling Oil Pump Control - The oil pump will cut off when differential pressure between suction and discharge pres­sure is 55 lb or greater. Upon pump termination the above cutout logic (pump not running) is utilized. Pump cut-in oc­curs when the differential pressure between suction and dis­charge is 45 lb or less. Oil pressure alarm and cutout logic (pump running) begins after a 30 second delay which al­lows the oil pump to build pressure.
Prealarms are self-clearing. At this time the alarm will stop flashing, but the time of the first occurrence will still be re­corded to the right of the alarm. Pressing the [CLEAR] key while at the Annunciator display will clear all alarms and/or cutouts.
In order to restore the Annunciator display and resume nor­mal operation it will be necessary to go through the follow­ing steps:
1. Correct the conditions causing the alarm.
2. Press the [ALARM SILENCE] key. (This action ma y pre-
cede correcting the conditions causing the alarm).
3. To clear or reset the Annunciator pages, press the [CLEAR] key. This will also clear the ALARM or CUTOUT
indicator from the Operating display.
4. Press [F1] to call up the Operating display. If the condi­tions causing the alarm have not been corrected or a new fault has occurred, a new ALARM or CUTOUT message will appear.
NOTE: Use of the Emergency Stop Button may trip one or more alarm setpoints.
SHUTDOWN RECORD DISPLAY *
SHUTDOWN RECORD P1 Thu 03-01-89 15:33:36 Hi Oil Temp Cutout ********************* Hi Oil Temp Cutout ********************* Low Temp Cutout *********************
SHUTDOWN RECORD P2 Thu 03-01-89 15:33:36 Low Temp Cutout ********************* Disch. Temp Cutout ********************* Disch. Temp Cutout *********************
The Shutdown Record display keeps a record of the last six shutdowns (cutouts). This information will help troubleshoot persistent operational problems. The most recent cutout will appear on the top line of page 1 of the display with the old­est appearing on the last or bottom line of page 2. When a cutout occurs, all information is moved down one line and the new cutout appears at the top of page 1. When the dis­play is full, the oldest record is dropped off the display and is not retained in memory. The information presented is ech­oed from the Annunciator display, providing the type of cut­out, the day, the date, and the time. NOTE: This informa-
tion will not be lost due to power failure.
FREEZE DISPLAY *
FREEZE DISPLAY P1 Thu 03-01-89 15:33:36
Suction Disch Oil CUTOUT Compressor
14.3 hg 120 g 060 g OFF Mode
-040 F 135 F 135 F
FREEZE DISPLAY P2 Thu 03-01-89 15:33:36
V Ratio SV Pos Pump %FLA Sep 132
2.2 000% off 000% HTR off
Auto Auto L
The Freeze displa y has the same appear ance and contains the same information as the Operating display. (For a de­scription of the information presented by the Freeze displa y, refer to the Operating display.) The Freeze display freezes the information of the Operating display A T THE MOMENT OF A COMPRESSOR CUTOUT. The information on the Freeze displa y can help the operator to identify the cause of a fault which occurred when no one was present. The F reeze display will retain the information generated by a cutout until a new cutout occurs or power is removed from the micro­processor.
Do not confuse the Freeze display
with the Operating display. In or-
der to avoid confusion remember that the displayed information on the Operating displa y is constantly being updated and changed. The Freeze display is fixed and FREEZE DISPLAY appears in the upper left hand corner of the display.
NOTE: The Freeze display will appear as a blank screen when power is initially furnished to the unit, and it will return to a blank screen anytime power is removed fr om the microprocessor.
O
F
SECURITY DISPLAY *
SECURITY DISPLAY Press F2 To Exit Setpoints Access ---- [Enabled ] Keyboard
Enter Access Code -[*****]
*Display for illustrative purposes only.
Loading...
+ 46 hidden pages