Frick RWB II Plus Operation & Maintenance Manual

S70-200 OM/DEC 99
File: SERVICE MANUAL - Section 70 Replaces: S70-200 OM/MAR 99 Dist: 3, 3a, 3b, 3c
OPERATION - MAINTENANCE
MICROPROCESSOR CONTROL
S70-200 OM Page 2
RWB II PLUS MICROPR OCESSOR CONTROL
Contents
MICROPROCESSOR CONTROL PANEL ....................................................................................................................................3
KEYS AND KEY FUNCTIONS......................................................................................................................................................4
TO CHANGE THE ADJUSTABLE SETPOINTS: ...........................................................................................................................6
HOW TO DETERMINE ADJUSTABLE SETPOINTS: ...................................................................................................................7
TEMPERATURE-PRESSURE CONTROL PROGRAM (OPTION) .............................................................................................10
LEAD-LAG OPTION....................................................................................................................................................................12
COMMUNICA TIONS TROUBLESHOO TING ..............................................................................................................................13
HOW THE MICROPROCESSOR WORKS - SUMMARY -..........................................................................................................13
MULTIPLE COMPRESSOR SEQUENCING ...............................................................................................................................14
SUGGESTED PROGRAMMABLE CONTROLLER PROGRAM TO DECODE
MICROPROCESSOR OUTPUT DATA CODES ...................................................................................................................14
MICROPROCESSOR OUTPUT DATA CODE.............................................................................................................................15
MICROPROCESSOR TELECOMMUNICA TIONS .............................................................................................. ........................16
COMMUNICATIONS PROTOCOL SPECIFICATIONS:...............................................................................................................16
TROUBLESHOOTING THE RWB II PLUS MICROPROCESSOR..............................................................................................20
GENERAL INFORMATION .........................................................................................................................................................20
TROUBLESHOOTING FRICK SBC MICR OPR OCESSOR SYSTEM ........................................................................................20
TESTING MICRO-PANEL ALARMS/CUTOUTS .........................................................................................................................23
EPROM MEMORY I/C CHIP REPLACEMENT .............................................................................................. .............................25
SBC BOARD REPLACEMENT ...................................................................................................................................................25
MICROPROCESSOR DISPLAY REPLACEMENT......................................................................................................................25
OUTPUT FUSE REPLACEMENT...............................................................................................................................................25
SBC WIRING DIAGRAM.............................................................................................................................................................26
POINT-TO-POINT FIELD WIRING DIAGRAM ............................................................................................................................26
MICRO COMPONENT PLACEMENT DIA GRAM .......................................................................................................................27
RWB II PLUS TELECOMMUNICATIONS ...................................................................................................................................27
MICROPANEL ASSEMBLY WIRING DIAGRAMS.......................................................................................................................28
RECOMMENDED SPARE PARTS - CURRENT DESIGN ..........................................................................................................32
– Designates changes or new information on referenced pages. See page and topic for matching symbol.
RWB II PLUS MICROPR OCESSOR CONTROL
OPERATION
MICROPROCESSOR CONTROL PANEL
S70-200 OM
Page 3
The following must be read in addi­tion to the Operation adn Start-up in­structions in S70-200 IOM before at­tempting to start or operate the unit.
The RWB II PLUS compressor is controlled by a state-of­the-art microprocessor control system. The microprocessor continuously monitors the compressor unit’s condition and operation. The microprocessor also directs instructions to the various compressor unit subsystems.
The microprocessor has a membrane switch keyboard. Pressing the keyboard in the area outlined as a ke y will cause that function to be recognized by the microprocessor. The keyboard has 32 membrane type keys.
In addition to the keyboard, there is an emergency stop b ut­ton. Pushing the emergency stop will bypass the computer and remove all power from the outputs.
RUN
STOP
FUNCTION
F1
F2
F3
F4
CLEAR
4
8
+/-
SLIDE STOP
AUTO
MANUAL
INCREASE
MANUAL
DECREASE
CHANGE
SLIDE VALVE
AUTO
REMOTE
MANUAL
LOAD
MANUAL UNLOAD
SETPOINT ENTRY
STEP
1
2
5
6
9
*
EMERGENCY STOP
COMPRESSOR
REMOTE
START
ALARM
SILENCE
ENTER
3
7
0
This will shut down the compressor motor and all high volt­age to the compressor auxiliary systems such as the oil pump and liquid injection solenoid. THE EMERGENCY
STOP BUTT ON IS FOR EMERGENCY SHUTDOWN SITU­A TIONS ONLY and MUST NOT BE USED TO ROUTINELY SHUT OFF THE COMPRESSOR.
The microprocessor continuously monitors the state of the battery which maintains setpoints and various other data. If the battery voltage is low, the message “LOW BATTERY” will flash in the lower right hand corner of the bottom dis­play (see S70-200 IOM for description of battery backup).
The microprocessor hardware contains an output watch­dog circuit. If the microprocessor should fail, this circuit will disable (turn off) all outputs.
S70-200 OM Page 4
RWB II PLUS MICROPR OCESSOR CONTROL
OPERATION
KEYS AND KEY FUNCTIONS
NOTE: The microprocessor will automatically return to the main operating display after 60 seconds of keybo­ard nonactivity.
The [CHANGE] k ey rotates the dual displa y screen through six display modes. The [CHANGE] key is also used to change the status of various setpoints.
The [STEP] key steps or moves a set of flashing brackets through the variable setpoints on the Adjustable setpoints display, the Auto-cycle display, the Security display and the Setback display. The setpoint enclosed within the flashing brackets may be changed or updated. The [STEP] key is also used when the annunciator display is selected to step through the annunciator’s four information displays.
NOTE: The [ * ] key is used to step or move the flashing brackets, described above, backwards.
The [ENTER] key is used to enter new setpoint limits. The [CLEAR] ke y will reset an alarm or cutout indication on
the annunciator screen and will clear the microprocessor to allow continued operation or restarting if all conditions have returned to normal and no other control lockouts are in force.
The [NUMERIC KEYP AD] is used to introduce new setpoint limits.
The [+/-] key is used to toggle between pounds per square inch gauge (g) and inches of mercury (hg).
The [RUN], [STOP], and [REMOTE START] keys control the starting and stopping of the compressor unit.
The [ALARM SILENCE] key will de-energize the alarm horn output.
The [AUT O], [REMOTE], and [MANUAL] keys control the operation of the compressor slide valve and mo v eab le slide stop.
The [F1] function key will return the operator to the main operating display. This function may be invoked at any time, even during setpoint entry.
display mode. To change to a different display mode, press the [CHANGE] k ey. The displa y modes in their order of rota- tion are:
1. Operating display
2. Adjustable Setpoints display
3. Adjustable Setpoints display #2
4. Fixed Setpoints display
5. Annunciator display (4 pages)
6. Shutdown Record display
7. Freeze display
[F1] Operating display [F2] Security display [F3] Setback display [F4] Auto Cycle display
NOTE: On initial powering of the microprocessor, and any time power has been removed from the micropro­cessor, onl y the Operating, Setpoints, Ann unciator, and Shutdown displays will display information. The freeze display will appear as a dark screen. The Freeze display will only be present after a compressor unit cutout and power has not been interrupted to the microprocessor. The cutout must be on a safety setpoint. When power is lost to the micro, it will not show the freeze display.
OPERATING DISPLAY *
OPERATING DISPLAY: Thu 10-01-87 15:33:36 Suction Disch Oil Filter Compressor
20.0 g 180 g 170 g 01PSID MAN Mode +015 F 140 F 135 F RUNNING
V Ratio S V Pos Pump %FLA Sep 132 F
4.6 090% OFF 080% HTR off Auto D Auto L FORCED UNLD ALARM C.C.=20.0 g LOW-BATTERY
*Display for illustrative purposes only. The Operating display is continuously updated and pro vides
a variety of information in regard to the current status of the compressor’s condition and performance.
The information furnished by the Operating display is as fol­lows:
The DAY, DATE, and TIME are displayed at the top right of the display.
The [F2] function key will call up the Security display. NO TE:
Press the [F2] key , as prompted b y the displa y, to return to the previously selected display.
The [F3] function k ey will call up the Setback displa y. NO TE: To exit the Setback display, press the [F1] key as prompted by the display.
The [F4] function key will call up the Auto Cycle display. NOTE: T o exit the A uto Cycle displa y, press the [F1] key as prompted by the display.
The [DISPLAY BACKLIGHT] key will toggle the dual LCD display backlights on and off. A preset delay will shut off the backlight after ten minutes elapsed time.
The microprocessor has two liquid crystal displays in an 8 line by 40 character format, for a total of 320 characters. There are 9 different display modes. When power is first applied to the control panel, the unit will be in the Operating
NOTE: To set day, date, and time; see TO CHANGE THE ADJUSTABLE SETPOINTS.
SUCTION - Suction Pressure and Temperature are mea-
sured at the compressor inlet and are, respectively, displayed in pounds per square inch gauge (g) or inches of mercury (hg) and degrees Fahrenheit.
DISCH - Discharge Pressure and Temperature are measur­ed at the compressor outlet and are, respectively, displayed in pounds per square inch gauge (g) and degrees Fahrenheit.
OIL - Oil Pressure and Temperature are measured prior to entering the compressor and are, respectively, displayed in pounds per square inch gauge (g) and degrees Fahrenheit.
FIL TER - Pressure drop across the oil filter. On the model 676 only, the bear ing oil filter pressure drop is displayed. The main oil injection feed filter pressure drop is shown on a unit mounted gauge.
RWB II PLUS MICROPR OCESSOR CONTROL
OPERATION
S70-200 OM
Page 5
COMPRESSOR - Compressor displays the status of the
compressor unit. The mode of operation will be indicated as either manual (MAN MODE) when the [RUN] key has been pressed, automatic (AUTO MODE) when Auto Cycle has been activated, remote (RMT MODE) when the [REMOTE] key has been pressed, or off (OFF MODE).
V RATIO - Volume Ratio is the ratio selected by the micro­processor to provide the highest efficiency at any given suc­tion and discharge pressure condition. Immediately below this, an information space has been provided to indicate whether V ratio is in the automatic (AUTO) or the manual (MAN) mode. The microprocessor will control this function only in the automatic mode. To the right of the mode indica­tor, two other messages may appear:
I - Indicates V Ratio increase. D - Indicates V Ratio decrease.
SV POS - Slide valve position is display ed as a percentage. This percentage reflects the mechanical position of the slide valve and does not reflect the percentage of full load opera­tion. Immediately below this information, space has been provided to indicate whether SV Pos is in the automatic (AUT O), manual (MAN), or remote (RMT) mode . The micro­processor will control this function in the automatic mode. To the right of the mode indicator, two other messages may appear:
L - Indicates Slide Valve loading. U - Indicates Slide Valve unloading.
PUMP - Pump displays the current status of the oil pump. The display will read ON or OFF whenev er the HAND-OFF-
-AUTO switch is selected to AUTO and the compressor is running.
% FLA - Percent Full Load Amps displa ys the percentage of the drive motor full load amperage rating that the motor is currently using.
NOTE: Consult Motor Manufacturer for the recom­mended duration of the Recycle Delay.
If the [RUN] key is pushed while the unit is in Recycle Delay, the com­pressor will start at the end of the delay period.
C.C. - Capacity Control, located at the bottom left of the
display, indicates the current capacity control suction pres­sure setpoint in pounds per square inch gauge (g) or inches of mercury (hg).
ADJUSTABLE SETPOINTS DISPLAY *
ADJUSTABLE SETPOINTS: ID=[33] [10-01-87] Cap. Control---[20.0 g ] Thu [15:33:36] Lo Suct Cutout-[12.0 g ] Baud----[ 2400] Lo Suct Alarm--[16.0 g ]
Hi Disch Cutout-[225 g ] Aux1[Alarm][NO] Hi Disch Alarm--[215 g ] Aux2[Shutd][NC] M.L.C. Stop Load--[095%] CT Factor-[078] M.L.C. Force Unld-[100%] Recy.Delay-[30]
The Adjustable Setpoints display lists the adjustable set­points which define the limits of the compressor package operation. When these limits are reached, or exceeded, alarm or compressor shutdown will occur. The inf orma
an
tion fur-
nished by the Adjustable Setpoints display is as follows: CAP CONTROL - The Capacity Control setpoint, reported
in pounds per square inch gauge (g) or inches of mercury (hg), controls the loading and unloading of the compressor when SV POS is in the automatic (AUTO) mode.
LO SUCT CUTOUT - The Low Suction Pressure Cutout, re­ported in pounds per square inch gauge (g) or inches of mercury (hg), will shut down the compressor if the suction pressure drops to this limit, or lower, f or 120 seconds or longer.
SEP - Separator displays the oil separator temperature in degrees Fahrenheit.
HTR - Heater displays the condition of the oil separator heater(s), indicating ON or OFF.
ALARM/CUTOUT - An Alarm or Cutout message indicates an Alarm or Cutout setpoint has been reached, or exceeded. Rotate the display mode to the Annunciator display for de­tails. In the e vent of a cutout, rotate to the Freeze display for further details.
FORCED UNLD - A Forced Unload message indicates that the percentage of motor full load amps has exceeded the maximum limit and the microprocessor is unloading the com­pressor until the percentage FLA falls back to normal limits.
RECYCLE DELAY - A Recycle Delay message indicates that the compressor has started and has shut down within the time delay set point period. The Recycle Delay will pre­vent the compressor from starting until the delay time ex­pires and is intended to prevent damage to the compressor motor from successive restarts. During Recycle Delay, the microprocessor will alternatively flash “RECYCLE DELAY” and the remaining delay time in minutes.
*Display for illustrative purposes only.
LO SUCT ALARM - The Low Suction Pressure Alarm, re­ported in pounds per square inch gauge (g) or inches of mercury (hg), will trigger a prealarm if the suction pressure drops to this limit, or lower.
HI DISCH CUTOUT - The High Discharge Pressure Cutout, reported in pounds per square inch gauge (g), will shut down the compressor if the discharge pressure equals, or exceeds, this setpoint.
HI DISCH ALARM - The High Discharge Pressure Alarm, reported in pounds per square inch gauge (g) will trigger a pre-alarm if the discharge pressure equals, or exceeds, this setpoint.
M.L.C. STOP LOAD - The Motor Load Control Stop Load, reported as a percentage of the motor full load amps (FLA), will prevent the compressor slide valve from loading when the setpoint is equaled, or exceeded. NOTE: Consult mo-
tor nameplate for recommended setpoint. M.L.C. FORCE UNLD - The motor Load Control Force Un-
load, reported as a percentage of the motor full load amps (FLA), will force the compressor to unload until the motor full load amps (FLA) fall within 1% of the setpoint, or lower.
NOTE: Consult motor nameplate f or recommended set­point.
S70-200 OM Page 6
RWB II PLUS MICROPR OCESSOR CONTROL
OPERATION
ID - The ID number is a programmable identification code
used in telecommunications to access a specific compres­sor.
DATE - The Date displays the current date in the following format: Month - Day - Year.
DAY - Day will display the current day of the week. TIME - The Time displays the current time in the following
format: Hours - Minutes - Seconds. The time is in 24:00:00 hour clock format.
BAUD - Shows the baud rate of the RS422 communication ports 1 and 2. Both ports are configured as follows: word = 8 bit, parity = none or even, stop = 1 bit. The communications ports are programmable from 300 to 19200 baud.
AUX 1 and A UX 2 - May be configured f or either an alarm or shutdown and with either a normally closed (NC) or nor­mally open (NO) contact.
CT FACTOR - The Current Transformer Factor records the proper current transformer factor to match the compressor motor FLA rating to the current transformer primary rating. The CTF factor is programmable and its correct value is determined by the following formula:
CTF =
1024 x FLA (Full Load Amps) 10 x CT (Current Transformer Primary Amps)
EXAMPLE: FLA = 230 Amps
CT = 300 (300:5)
CTF =
1024x 230 = 78 (Round to whole number)
10 x 300
RECY. DELAY - The Recycle Delay displays the current recycle delay setpoint in minutes. NOTE: Consult motor
manufacturer for recommended setpoint.
ADJUSTABLE SETPOINTS PAGE 2 *
ADJUSTABLE SETPOINTS Page 2:
Start Diff Press--[100g] Dead Band--[1.0#] Prop. Band-[10 %] Cycle Time-[10 sec]
Low % FLA--[020 %]
Dead Band - This is a + (plus) or - (minus) value above or below the setpoint at which the compressor will neither load nor unload. A dead band of 1 is the default value. It is adjustable between .5 lbs. to 5 lbs. in increments of .5. The “Step” key is used to select this setpoint; then press the “Change” key to toggle through the selections.
Cycle Time - Cycle time is the amount of time between the beginning of each load/unload response. Ten seconds is the default value. “Cycle Time” is adjustable between 5 and 30 seconds in 5 second intervals. The “Step” key is used to select a setpoint; then press the “Change” key to toggle through the selections.
Low % FLA - This setpoint is used to determine if the cou­pling has broken. 20% is the default value. It is adjustable from 0 to 100% FLA. Use the “Step” k ey to select a setpoint; then enter the desired setpoint and press the “Enter” key.
TO CHANGE THE ADJUSTABLE SETPOINTS:
Adjustable Setpoints are stored in RAM (random access memory) and are easily changed in the field.
Adjustable Setpoints are lost if power is interrupted and the battery
is not fully charged. To facilitate re­entry, we suggest that a list of Adjustable Setpoints be affixed to one end of the microprocessor cabinet for reference. For your convenience, a blank Adjustable set-
points display which may be photocopied has been provided (See page 10).
NOTE: The following procedure also applies to the c hang­ing of the Security, Setbac k, and A uto Cycle display set­points.
1. Press the [CHANGE] key to rotate the display to the Ad-
justable Setpoints display.
2. Press the [STEP] key to move or step a set of flashing brackets through the v arious setpoints. A setpoint is selected for change or update when it is enclosed by the flashing brackets.
NOTE: The DAY indicator, itself, will flash when selected for change or update.
3. Having selected the setpoint to be changed, the [NU- MERIC KEYPAD] may be used to enter the new setpoint. NOTE: All digits must be entered, including zeros. For example, (01.0).
NOTE: The D A Y, A UX 1, and A UX 2 setpoints, once selected, are changed or updated by pressing the [CHANGE] key.
NOTE: Certain setpoints may be reported in either pounds per square inch gauge (g) or inches of mercury (hg). To toggle between (g) and (hg), having selected the setpoint, press the [+/-] key to toggle between (g) and (hg).
4. In the event that an incorrect setpoint is keyed in all or
part, press the [CLEAR] key to restore the original setpoint. Pressing the [CLEAR] key a second time will eliminate the flashing brackets.
Proportional Band - This setpoint is used to determine the amount of time the load/unload solenoid is energized, ac­cording to how far from the setpoint the actual control pres­sure is. The smaller the number, the longer a load/unload signal will be sent. 10% is the def ault value . Selections are 2, 5, 10, 15, 20, or 25%. The “Step” ke y is used to select this setpoint; then press the “Change” key to toggle through the selections.
*Display for illustrative purposes only.
5. Having keyed the desired setpoint, press the [ENTER] key. The new setpoint will be entered and the flashing brac k­ets will move or step to the next setpoint.
NOTE: A setpoint entry outside the parameters of the Adjustable Setpoint display will be refused and the origi­nal Adjustable setpoint will be restored.
NOTE: To clear any time values [STEP] to the desired setpoint, press [CHANGE] and then press [CLEAR].
RWB II PLUS MICROPR OCESSOR CONTROL
OPERATION
S70-200 OM
Page 7
HOW T O DETERMINE
ADJUSTABLE SETPOINTS:
Adjustable Setpoints should reflect values compatible with normal system operation. Too high a Low Suction Pressure Alarm setpoint may cause nuisance prealarms. Similarly, cutout setpoints should not fall within what are considered normal plant operation. As a rule of thumb, set the Low Suc­tion Pressure Alarm 5 PSIG lower than the lowest normal suction pressure. The Low Suction Pressure Cutout should be 5 to 10 PSIG lower than the Low Suction Pressure Alarm setpoint.
The High Discharge Pressure Cutout should be set at 90% of the setting of the lowest high side relief valve. The High Discharge the Cutout.
The Capacity Control setpoint should be the equivalent of the normal suction condition.
FIXED SETPOINTS: HIGH STAGE PRELUBE OIL PUMP PGM/A Hi Disch Cut----[212F] Hi Disch Alarm--[194F] Liq Inj Con 113F
Hi Oil Temp Cut-[167F] Filter------[25] Hi Oil Temp Alarm[158F]Oil Heater[113F] Lo Oil Temp Cut--[49F] Lo Oil Cut-[030] Lo Oil Temp Alarm[58F] Lo Oil Alrm[025]
The Fixed Setpoints display lists all fix ed setpoints, program version, plus low oil alarm and low oil cutout setpoints. Fixed Setpoints define the limits of acceptable compressor opera­tion. Fixed Setpoints are factory determined, stored in pro­grammed memory (PROM), and will remain in memory if power to the microprocessor is interrupted.
HI DISCH CUT - The High Discharge Temperature Cutout, reported in degrees Fahrenheit, will shut down the com­pressor if the discharge temperature equals or exceeds this setpoint.
Pressure Alarm should be set 10 PSIG lower than
FIXED SETPOINTS DISPLAY *
PRELUBE, FULL LUBE, or CYCLING - Pump type will be
indicated.
PGM/ - Microprocessor Program version. LIQ INJ CON - The Liquid Injection Control, reported in de-
grees Fahrenheit, will shut off the liquid refrigerant supply to the compressor if the oil temperature equals or falls be­low this setpoint.
FILTER - The Oil Filter setpoint will trigger an alarm when the differential pressure across the oil filter equals or ex­ceeds 25 pounds per square inch (PSI) for 15 seconds, or longer.
OIL HEA TER - The Oil Heater setpoint, reported in degrees Fahrenheit, turns on the oil separator heater(s) when the oil temperature equals or falls below this setpoint whenever the compressor is NOT running.
Compressor Differential Cutout - The differential cutout has been lowered from 55 lb to 25 lb. Cutout will occur after five minutes. T o allo w operation at low differential pressures, the micro will take the following steps:
A. Force unload the compressor to 50% and display an "F Unload" when the oil pressure is within 10 lb of the main oil injection port pressure and the slide valve position is greater than 50%.
B. Prohibit the compressor from loading and display a "Ld Inhib" message when the differential is within 15 lb of the main oil injection port pressure.
Oil Pressure Alarm and cutout - Logic has been revised to same logic as currently used on RXB/RXF. The new logic is as follows:
Prelube and Cycling Oil Pump version when pump is not running. Alarm will occur if oil pressure is 25 lb below dis­charge pressure or within 10 lb of suction pressure for 30 seconds. Cutout occurs if oil pressure is 30 lb below dis­charge pressure or if oil pressure is within 7 lb of suction pressure for 10 seconds and alarm has already been set.
HI DISCH ALARM - The High Discharge T emperature Alarm, reported in degrees Fahrenheit, will trigger a prealarm if the discharge temperature equals or exceeds this setpoint.
HI OIL TEMP CUT - The High Oil Temperature Cutout, re­ported in degrees Fahrenheit, will shut down the compressor if the oil temperature equals or exceeds this setpoint.
HI OIL TEMP ALARM - The High Oil Temperature Alarm, reported in degrees Fahrenheit, will trigger a prealarm if the oil temperature equals or exceeds this setpoint.
LOW OIL TEMP CUT - The Low Oil Temperature Cutout, reported in degrees Fahrenheit, will shut down the com­pressor if the separator oil temperature equals or falls be­low this setpoint.
LOW OIL TEMP ALARM - The Low Oil Temperature Alarm, reported in degrees Fahrenheit, will trigger a prealarm if the separator oil temperature equals or falls below this setpoint.
HIGH STAGE or BOOSTER - Compressor application indi­cator.
Full Lube and Cycling Oil Pump version when oil pump is running. Alarm occurs if oil pressure is within 10 lb of dis­charge pressure for 30 seconds. Cutout occurs when oil pressure is within 5 lb of discharge pressure for 10 seconds and oil pressure alarm has been set.
Cycling Oil Pump Control - The oil pump will cut off when differential pressure between suction and discharge pres­sure is 55 lb or greater. Upon pump ter mination the above cutout logic (pump not running) is utilized. Pump cut-in oc­curs when the differential pressure between suction and dis­charge is 45 lb or less. Oil pressure alarm and cutout logic (pump running) begins after a 30 second delay which al­lows the oil pump to build pressure.
*Display for illustrative purposes only.
S70-200 OM Page 8
RWB II PLUS MICROPR OCESSOR CONTROL
OPERATION
ANNUNCIATOR DISPLAY *
ANNUNCIATOR: PG-1 Thu 10-01-87 15:33:36 (Use STEP key to advance PAGE) High Press. Cutout ********************* High Press. Alarm *********************
Low Press. Cutout ********************* Low Press. Alarm ********************* Oil Press. Cutout ********************* Oil Press. Alarm *********************
ANNUNCIATOR: PG-2 Thu 10-01-87 15:33:36 (Use STEP key to advance PAGE) Hi Oil Temp Cutout ********************* Hi Oil Temp Alarm *********************
Low Temp Cutout ********************* Low Temp Alarm ********************* Disch. Temp Cutout ********************* Disch. Temp Alarm *********************
ANNUNCIATOR: PG-3 Thu 10-01-87 15:33:36 (Use STEP key to advance PAGE) Comp. Auxiliary ********************* Pump Auxiliary *********************
Oil Level ********************* Comp. Differential ********************* Dirty Filter *********************
ANNUNCIATOR: PG-4 Thu 10-01-87 15:33:36 (Use STEP key to advance PAGE) Aux. 1 (Alarm) ********************* Aux. 2 (Shutdown) *********************
Low Motor Amps Sensor Fault
When a prealarm or cutout occurs, a flashing ALARM or CUTOUT indicator will appear in the lower right hand cor-
ner of the Operating display. To determine the fault, rotate to the Annunciator display by pressing the [CHANGE] key.
The Annunciator display lists all ke y operative points on f our sequential displays. These displa ys can be rotated from page #1 through page #4 by pressing the [STEP] key. When a prealarm or cutout is triggered, the pertinent point will flash, and the time of the occurrence will be recorded to the right of the alarm. Prealarms are self-clearing. At this time the alarm will stop flashing, but the time of the first occurrence will still be recorded to the right of the alarm. Pressing the [CLEAR] key while at the Annunciator display will clear all alarms and/or cutouts.
In order to restore the Annunciator display and resume nor­mal operation it will be necessary to go through the follow­ing steps:
1. Correct the conditions causing the alarm.
4. Press [F1] to call up the Operating display. If the condi-
tions causing the alarm have not been corrected or a new fault has occurred, a new ALARM or CUT OUT message will appear.
NOTE: Use of the Emergency Stop Button may trip one or more alarm setpoints.
SHUTDOWN RECORD DISPLAY *
SHUTDOWN RECORD: Thu 10-01-87 15:33:36 (Use STEP key to advance PAGE) Hi Oil Temp Cutout Wed 09-30-87 16:22:54 Comp Auxiliary Sat 08-22-87 09:47:02
Low Temp Cutout Thu 08-20-87 11:17:33 Pump Auxiliary Mon 08-17-87 18:53:11 Disch. Temp Cutout Tue 07-14-87 06:22:09 Oil Pres Cutout Fri 07-08-87 14:06:21
The Shutdown Record display keeps a record of the last six shutdowns (cutouts). This information will help troubleshoot persistent operational problems. The most recent cutout will appear on the top line of the display with the oldest appearing on the last or bottom line. When a cutout occurs, all inf orma­tion is moved down one line and the new cutout appears at the top. When the displa y is full, the oldest record is dropped off the display and is not retained in memory. The informa­tion presented is echoed from the Annunciator display; pro­viding the type of cutout, the day, the date, and the time.
NOTE: This information will not be lost due to power failure.
FREEZE DISPLAY *
FREEZE DISPLAY: Thu 10-01-87 15:33:36 Suction Disch Oil Filter Compressor
20.0 g 225 g 170 g 01PSID OFF Mode +015 F 140 F 135 F RECYCLE
V Ratio S V Pos Pump %FLA Sep 132 F
4.6 090% OFF 080% HTR off Auto Auto CUTOUT C.C.=20.0 g
The Freeze displa y has the same appear ance and contains the same information as the Operating display. (For a de­scription of the information presented by the Freeze displa y, refer to the Operating display.) The Freeze display freezes the information of the Operating display A T THE MOMENT OF A COMPRESSOR CUTOUT. The information on the Freeze displa y can help the operator to identify the cause of a fault which occurred when no one was present. The Freeze display will retain the information generated by a cutout un­til a new cutout occurs or power is removed from the micro­processor.
Do not confuse the Freeze display
with the Operating display . In order
to avoid confusion remember that the displayed information on the Operating display is constantly being updated and changed. The Freeze dis­play is fixed and FREEZE DISPLA Y appear s in the upper left hand corner of the display.
2. Press the [ALARM SILENCE] key. (This action may pre-
cede correcting the conditions causing the alarm).
3. To clear or reset the Annunciator pages, press the [CLEAR] key. This will also clear the ALARM or CUTOUT
indicator from the Operating display.
NOTE: The Freeze display will appear as a blank screen when power is initially furnished to the unit, and it will return to a blank screen anytime power is removed fr om the microprocessor.
*Display for illustrative purposes only.
RWB II PLUS MICROPR OCESSOR CONTROL
OPERATION
S70-200 OM
Page 9
SECURITY DISPLAY *
SECURITY DISPLAY: Thu 10-01-87 15:33:36
Setpoints Access---[Enabled ] Keyboard
Enter Access Code---[*****]
Press F2 To Exit
The [F2] function key will call up the Security display. The Security display allows the operator to either enable or dis­able the microprocessor’s keyboard and, thereby, prevent unauthorized tampering with the various adjustable setpoints. When enabled, the microprocessor ke yboard is fully opera­tive and the security lockout is not in effect. When disabled, the keyboard is rendered partially nonfunctional. All displa ys will still be accessible through the keyboard. If any attempt is made to enter new adjustable setpoints, ho w e v er, the mi­croprocessor will default to the Security display.
TO ENABLE THE KEYBOARD, press the [STEP] key so that the brackets beside Enter Access Code flash, key the proper five digit access code, and press [ENTER]. The Set­points Access will toggle from disabled to enabled and ad­justable set point entry is now possible.
TO DISABLE THE KEYBOARD, press the [F2] function key to call up the Security display. Press the [STEP] key until the brackets beside Enter Access Code flash, k ey the proper five digit access code, and press [ENTER]. Now, press the [STEP] key until the brac kets beside Setpoints Access flash and press the [CHANGE] key to toggle from enab led to dis­abled.
TO CHANGE THE ACCESS CODE, press the [F2] function key to call up the Security display. Press the [STEP] key until the brackets beside Enter Access Code flash, key the proper five digit access code, and press [ENTER]. Now, select the Enter Access Code a second time by pressing the [STEP] key until the brackets beside Setpoints Access flash, key in the new five digit access code, and press [EN-
TER]. NOTE: Power loss will not effect the Security display. NOTE: IF NO ACCESS CODE WAS ENTERED AND THE
DISABLED COMMAND WAS SELECTED, THE ACCESS CODE IS [00000].
LOST OR FORGOTTEN ACCESS CODE: Consult Frick
Company for assistance.
SETBACK DISPLAY *
SETBACK DISPLAY: Thu 10-01-87 15:33:36 Press F1 To Exit Setback Setpoint-[05.0 g ] Active-[No ] Start Stop Start Stop
Mon-[--:--]-[06:00] Fri-[16:00]-[--:--] Tue-[--:--]-[--:--] Sat-[--:--]-[--:--] Wed-[--:--]-[--:--] Sun-[--:--]-[--:--] Thu-[--:--]-[--:--]
*Display for illustrative purposes only.
The [F3] function key will call up the Setback display. The Setback feature enables automatic operation at two sepa­rate suction conditions on a preset time schedule. Having entered the desired Setback setpoint, enter the start and stop time or times, and select Active: (Yes) or (No).
NOTE: To change the Setback setpoints, refer to “TO CHANGE THE ADJUST ABLE SETPOINTS”
AUTO CYCLE DISPLAY *
AUTO CYCLE Thu 10-01-87 16:33:36 DISPLAY: Press F1 To Exit
Suction Pressure--------[20.0 g ]
Compressor Start--------[20.0 g ] Compressor Stop---------[18.0 hg] Minimum Slide Valve-----[00%] Auto Cycle Active-------[No ]
The Auto Cycle display provides for independently adjus­table setpoints to turn the compressor on and off in response to the suction pressure or as an adjustable setpoint to limit the minimum slide valve position.
NOTE: To change the Auto Cycle setpoints, refer to “TO CHANGE THE ADJUSTABLE SETPOINTS”
SUCTION PRESSURE - Constantly monitors and displays
the suction pressure in pounds per square inch gauge (g) or inches of mercury (hg).
COMPRESSOR START - Compressor Start-up will bring the compressor back on line when the suction pressure rises to the displayed setpoint.
COMPRESSOR STOP - Compressor Stop will shut down the unit if the suction pressure drops to or below the dis­played setpoint limit. NOTE: This limit must be set higher than Low Suction Pressure Cutout and the Low Suction Pres­sure Alarm setpoints.
MINIMUM SLIDE VALVE - Minimum Slide Valve Position, shown as a percentage, will limit the slide valve position to the displayed setpoint.
AUTO CYCLE ACTIVE - Indicates whether Auto Cycle is active (YES) or not active (NO). Press the [CHANGE] key while at this setpoint to change the status. Upon deactiva­tion, the compressor will return to the previous mode of op­eration.
ANALOG OFFSET DISPLAY*
ANALOG OFFSET: Suc Disch Oil Sep Filt Spare Econ Temp +0 +0 +0 +0 +0.0 Pres +0.0 +0 +0 +0 +0 Channel 10 12 13 Press +0 +0 0
The Analog Offset Display is accessed by pressing +/- key. All analog values can be offset + or - 3 to 9 units depending on which value is being adjusted. Use the [STEP] key to step to the desired setpoint. Press the [CHANGE] key to change the value of the offset by 1. The actual analog value will be displayed on the top line of the display. The “Econ” and channels 10, 12, 13 are displayed but do not pertain to the standard program.
S70-200 OM Page 10
RWB II PLUS MICROPR OCESSOR CONTROL
OPERATION
Sensor Fault Failure - A “Sensor F ault” cutout was added
to the program to stop the compressor if a temperature or pressure sensor is at its minimum or maximum limit for 5 seconds. The following channels and conditions will cause this cutout:
O
F)
F)
O
F)
Channel 1 - Suction Temp Low or High (-67 to 113 Channel 2 - Low or High Discharge Temp (32 or 212OF) Channel 3 - Low or High Oil Temp (0 or 180
O
Channel 4 - Low or High Separator Temp (0 or 180 Channel 6 - Low or High Oil Pressure (<0 g or 285 g) Channel 8 -
Low or High Discharge Pressure (<0 g or 285 g)
Channel 9 - Low Suction Pressure (29 hg only) Pulse Load Signal at 100% Slide Valve Position - This
new feature will stop loading the compressor when 100% slide valve is display ed. The load signal will pulse for 2 sec­onds every minute when the slide valve is at 100% and the pressure is above setpoint.
TEMPERA TURE-PRESSURE CONTROL
PROGRAM (OPTION)
NOTE: The following displays are provided only when the Temperature-Pressure Control Program option has been ordered with the RWB II Plus Rotary Screw Com­pressor Unit.
SETPOINTS DISPLAY PAGE 1 *
CONTROL - This setpoint is used to select either Pressure Capacity Control or Temperature Capacity Control. NOTE: There are only two setpoints, press f or pressure capac­ity control and temp for temperature capacity control.
CC - The capacity control setpoint is for normal operation,
not setback. CUTOUT -This setpoint will stop the compressor if the suc-
tion pressure drops below the pressure setpoint for 90 sec­onds or if the CC Temperature drops below the temperature setpoint. There is no time delay on the temperature cutout.
ALARM - An alarm will be activated if the suction pressure drops below the pressure setpoint or if the CC Temperature drops below the temperature setpoint. There is no time de­lay for either.
PB - The Proportional Band (PB) is used to determine the amount of time the load/unload solenoid is energized, ac­cording to how far away from the setpoint the actual control pressure or temperature is. The smaller the number , the more load/unload will be sent. A PB of 10% is def ault. It is adjust­able to 2, 5, 10, 15, 20, or 25 percent.
DB - The Dead Band (DB) is a + (plus) or - (minus) value above or below the setpoint which the compressor will nei­ther load nor unload. It is adjustable between .5 and 5.0 psig or degrees, in increments of .5 units.
SETPOINTS PAGE 1 Capacity Control=Press C.C. CUTOUT ALARM PB DB CT Press 25.3g 01.3g 05.3g 10 1.0 10 Temp +40.0F +32.0F +33.0F 10 0.5 10 offset-act Sup Heat-Alarm-10F-no Sep Cond-Alarm-10F-no
* Display for illustrative purposes only. The Setpoints Display is accessed by pressing the
[CHANGE] key.
ADJUSTABLE SETPOINTS FORM
ADJUSTABLE SETPOINTS: ID = [ ] [ - - ]
Cap. Control ———[ ] Thu [ : : ]
Lo Suct Cutout ——[ ] Baud ———————[ ]
Lo Suct Alarm ———[ ]
Hi Disch Cutout ——[ ] Aux 1 [ ] [ ]
Hi Disch Alarm ——[ ] Aux 2 [ ] [ ]
CT - The Cycle Time (CT) setpoint is the amount of time between the beginning of each load/unload response. It is adjustable to 5, 10, 15, 20, 25, or 30 seconds.
Use the [STEP] key to step to the desired setpoint, then press the [CHANGE] key to change the CC , PB, DB and CT values. Enter the desire value for the remaining setpoints and press [ENTER] when complete.
M.L.C. Stop Load —[ ] CT Factor ———[ ]
M.L.C. Force Unld —[ ] Recy. Delay ——[ ]
Photocopy and fill in applicable data for your unit. Retain for reference if reentry is required.
Loading...
+ 22 hidden pages