Frick QUANTUM LX Control Panel Maintenance Manual

Form 090.610-M (MAY 2016)
Please check www.johnsoncontrols.com/frick for the latest version of this publication.
File: SERVICE MANUAL - Section 90 Replaces: 090.610 - M (DEC 2012) Dist: 3, 3a, 3b, 3c
MAINTENANCE
FRICK® QUANTUM™
EVAPORATOR
CONTROL PANEL
Version 3.1x
090.610-M (MAY 2016) Page 2
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
TABLE OF CONTENTS
SECTION 1
INTRODUCTION TO THE QUANTUM™ EVAPORTOR CONTROL SYSTEM ................................................................3
SECTION 2
REMOTE PANEL.....................................................................................................................................................9
SECTION 3
Q5 CONTROLLER..................................................................................................................................................13
SECTION 4
Q4 CONTROLLER..................................................................................................................................................23
SECTION 5
DIGITAL BOARD..................................................................................................................................................29
SECTION 6
ANALOG BOARD..................................................................................................................................................35
SECTION 7
SERVICE SCREENS...............................................................................................................................................41
SECTION 8
TROUBLESHOOTING.............................................................................................................................................49
SECTION 9
EVAPORATOR CONTROL PANEL AND REMOTE PANEL DRAWINGS........................................................................51
SECTION 10
REPLACEMENT PARTS..........................................................................................................................................59
THE FOLLOWING PUBLICATIONS ARE AVAILABLE FROM THE JOHNSON CONTROLS® WEBSITE jci.com
090.612-O Frick® Quantum™ LX Evaporator Control Panel Operation
090.610-CS Frick® Quantum™ LX Evaporator Control Panel Communications Setup (setup and wiring for data communica­tion using available protocols)
090.610-M Frick® Quantum™ LX Evaporator Control Panel Maintenance (repair and troubleshooting)
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
090.610-M (MAY 2016)
SECTION 1
INTRODUCTION TO THE QUANTUM™ EVAPORATOR
CONTROL SYSTEM
Page 3
090.610-M (MAY 2016) Page 4
INTRODUCTION TO THE QUANTUM™ LX EVAPORATOR CONTROL SYSTEM
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
INTRODUCTION
The Quantum™ LX Evaporator system consists of two major control components:
The Quantum™ LX Evaporator Control Panel
Evaporator Remote Panel(s)
With the Quantum™ LX Evaporator system version
3.0x and later, a single Evaporator Control Panel can control up to ten remote panels with each remote ca­pable of handling three Evaporator units, for a total possible of thirty units. It is also capable of Ethernet access, which can be viewed remotely through any web browser, or the optional Frick™ Evaporator Op­erator Interface Panel.
The Frick® Quantum™ LX Evaporator control system
consists of ve major areas:
QUANTUM™ LX CONTROL PANEL ENCLOSURE
The Frick® Quantum™ LX Evaporator control
panel enclosure is congured to make it as standard as possible. Since there are nearly an innite number of possible congurations and options, this manual will describe the most common features and arrangements. It is always best to refer to the wiring diagrams, panel layouts, and operational documentation that is included with each unit for exact de­tails regarding equipment operation.
Power Supply - Provides the necessary operating voltages for the proper opera­tion of all control components. Additional information about the power supply can be found later in this manual.
Quantum™ Controller - Evaporator panels are currently supplied with the Q5 control board, but numerous units with the previous version known as the Q4 board also exist. This manual will include information for both of these boards. Both the Q4 and Q5 boards run a soft­ware program that communicates with all Remote Panels, which in turn con­trol the Digital and Analog boards within those panels. This communication allows the controller to read the status of all the I/O boards, and display the data ei­ther on its own display, a Web Browser, or the optional Standard Interface Panel. The Quantum™ controller acts on this data, and provides the necessary con-
trol information to the I/O boards to provide the appropriate control of all input and output signals, based upon the conguration of in­stalled features and options of the Evaporator package. Interaction to the outside world can be achieved through industry-standard com­munications protocols. Additional information is located under the Q4 (or Q5) CONTROLLER section found later in this manual. The Quan­tum™ controller, when loaded with the oper­ating system, is then known as the Quantum™ LX Evaporator system.
EVAPORATOR REMOTE PANEL
The Remote Panel contains the I/O that will control up to three Evaporator units. Up to ten Remote Panels may be connected to the Quantum™ LX Control panel via RS-485 communications, for a maximum total of thirty units.
Power Supply - Provides the necessary oper­ating voltages for the proper operation of all control components. Additional information about the power supply can be found later in this manual.
Digital Input / Output Boards - Digital (on/off) signals are sent and received by these boards. The output signals are used for energizing solenoids, valves, contactors, relays, etc., and the input signals are used to sense the condition of switches, relay contacts, auxiliary contacts, etc. This board runs an independent software program from the Quantum™ LX to control devices, and communicates the status of all devices back to the Quantum™ LX. Ad­ditional information about the Digital Boards is located under the DIGITAL BOARD section found later in this manual.
Analog Input / Output Board - Analog (vari­able) signals are sent and received by this board. The output signals are used for con­trolling damper motors, modulated valves, etc., and the input signals are used to read the values being sent from pressure transduc­ers, temperature sensors, etc. This board runs an independent software program from the Quantum™ LX to control devices, and com­municates the status of all devices back to the Quantum™ LX. The analog board contains 24 analog inputs, and 8 analog outputs. Ad­ditional information about the Analog board is located under the ANALOG BOARD section found later in this manual.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
090.610-M (MAY 2016) Page 5
GENERAL INFORMATION
The components within the control panel can be inadvertently damaged by static electricity or mis-
handling. Only qualied technicians should directly
handle these components.
1. DO NOT attempt to make corrections to the power supply without shutting off the power to the control panel. Accidental shorts can irreparably damage the processor boards or the display screen.
2. DO NOT HANDLE the panel boards when their cables are disconnected without rst attach­ing a properly grounded wrist ground strap to prevent static electrical discharge from your body.
Most problems encountered with the microprocessor and control circuits will be the result of a wiring fault, a blown fuse, faulty I/O module or failure of a peripheral control such as a solenoid coil or a pressure transducer. Faults in the computer, while possible, are unlikely. If a fault develops in the computer, the probability is that all functions will cease and the display screen will go blank. The control system consists of an AC (high volt­age) side, which can be either 120 volts, or 230 volts, and a DC (low voltage) side. The AC side actuates so­lenoids, relays, alarms, and other electromechanical functions. The DC side operates the computer and its various sensors.
WHAT TO DO BEFORE CALLING THE FACTORY
Many times when a suspected Quantum™ problem is called in to the factory, not enough information is pro­vided for the service personnel to assist in solving the problem. This is because the caller most likely is not aware of the type of information that would be use­ful to factory personnel in helping to identify and cor­rect the problem. An example of this is the statement that the Quantum™ is not booting (the main processor board is not starting). Unfortunately, this description is usually vague and only means that there is nothing on the display. A blank screen could be the result of many different problems. The following is a list of possible reasons for no display:
No power
Loose or Faulty Display Cable or Inverter Ca­ble
Bad Display
Bad Backlight Inverter (on CCFT style displays)
Bad Backlight Fluorescent Tube (on CCFT style displays)
Wrong Combination of Display, Cable, Invert­er, or Software
Faulty CPU Board
When working within the panel, the AC high voltage side, which can be either nominal 120 VAC or nomi­nal 230 VAC, CAN CAUSE INJURY OR DEATH.
To troubleshoot the low-voltage side of the control cir­cuits, it is necessary to have the following tools:
1. Accurate digital multimeter (capable of read­ing to DC/AC, mA to the hundreds place)
2. Small wire stripper
3. Small screwdriver (with insulated shaft)
4. Small snip nose pliers
5. Wrist Grounding strap
6. Static free grounded work surface
Note: Proper panel voltage refers to the AC (high volt­age) that has been supplied to the panel, which could be either nominal 120 VAC or nominal 230 VAC.
Before calling the factory for assistance, review the in­formation on the following pages and try to discover and resolve your Quantum™ LX problem. The actual cause of most problems is usually not with the Quan­tum™ board itself, but with something external. How­ever, on the rare occasion that the problem has been identied as being the Quantum™ board, use the fol­lowing section as a guideline for replacing it.
090.610-M (MAY 2016)
Enclosure
Display
Keypad
Control Power
Switch
Page 6
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
QUANTUM™ EVAPORATOR CONTROL PANEL
The following pictorial shows front the Control Panel portion of the unit, and will appear the same for both a Q4 or Q5 control, and shows the following components:
• Enclosure
Display
• Keypad
Control Power Switch
Front of Enclosure
QUANTUM™ LX EVAPORATOR CONTROL PANEL
Power Supply
Communications
120 VAC Power Rear of Display
Quantum™ LX
MAINTENANCE
090.610-M (MAY 2016) Page 7
The inside of the panel will vary, depending on whether it is a Q4 or Q5 based controller. The following pictorial shows both versions:
Q4 Controller
Controller
Connection
Terminal Block
Q4 Panel
Q5 Controller
120 VAC Power
Connection
Communications
Terminals
Interface Board
Q5 Panel
Power Supply
090.610-M (MAY 2016) Page 8
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
NOTES:
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SECTION 2
REMOTE PANEL
090.610-M (MAY 2016) Page 9
090.610-M (MAY 2016)
Field and panel
wiring
HOA
Modules
Analog
Board
Digital
Board
Optional
Digital Board
Page 10
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
THE EVAPORATOR REMOTE PANEL ENCLOSURE
DESCRIPTION
Both versions of the Evaporator control panel, Q4 and Q5, utilize the same Remote panel. With the Quantum™ LX Evaporator system version 3.0x and later, a single Quantum ™ Control Panel can control up to ten remote panels with each remote capable of handling three Evaporator units, for a total possible of thirty units. It is also capable of Ethernet access, which can be viewed remotely through any web browser, or the optional
®
Frick
Evaporator Operator Interface Panel.
The Frick® Quantum™ LX Remote panel enclosure
utilizes available space efciently. The panel is also
equipped with the necessary posts and hardware to
add options in the eld. Each Remote panel is con­gured with one Digital and one Analog board, and a
second Analog board may be present depending upon installed options.
There are additionally two HOA (Hands Off Automatic) boards installed, which allow for overriding the auto­matic function of the control by allowing the user to manually operate outputs.
The DC power/communications harness in this panel
is color-coded. This will make wire identication much
easier. The coding is as follows:
+5VDC - RED
+12VDC - YELLOW
-12VDC - PURPLE
Common/Ground - BLACK
+RX/TX - BLUE
-RX/TX - BLUE w/WHITE stripe
QUANTUM™ LX EVAPORATOR CONTROL PANEL
Power
AC Input
DC
Output
-12 RET RET +5 +5 +12
MAINTENANCE
POWER SUPPLY FOR THE REMOTE PANEL
090.610-M (MAY 2016)
Page 11
DESCRIPTION
CAUTION! Measuring the power supply voltages require the control power to be energized. Extreme care must be observed when taking any readings, as 120 VAC is present within the power supply.
The Remote panel power supply is mounted on the inside at the top of the panel, as shown at the bottom of this page. A three-pin connector provides 120 VAC power to the supply, and a six-pin connector delivers DC power out of the supply. These connections are of a push-on multiple contact connector type. This power supply is not adjustable.
EVAPORATOR REMOTE PANEL POWER
The Evaporator Remote Panel utilizes the +5 VDC, +12 VDC and – 12 VDC voltages from its power supply. To perform measurements on the power supply voltages, use a reliable, calibrated Digital Volt Meter (DVM). The DVM should be accurate to 1/100 of a volt DC. Turn the control power switch to ON.
Measure the voltages on the power supply at the DC output connector as shown below.
Power supply is located at the inside top of the Remote Panel
090.610-M (MAY 2016) Page 12
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SECTION 3
Q5 CONTROLLER
090.610-M (MAY 2016)
Page 13
090.610-M (MAY 2016) Page 14
QUANTUM™ LX EVAPORATOR CONTROL PANEL
Q5 CONTROLLER BOARD
INTRODUCTION
Frick® Controls has released the latest version of the Quantum ™ LX microprocessor board. This brand will be referred to as the Q5. A photo of this board appears here:
MAINTENANCE
Just before fully booting, a Loading bar will appear at the bottom of the screen, showing the percent of load that has completed.
The Operating Status screen will appear.
After the Q5 has properly powered up, the following sequence of events is indicative of proper communica­tion to the analog and digital boards:
The Analog and Digital I/O boards TX/RX lights should be blinking.
Each I/O board should have the power LED lighted and the Active LED should be blinking.
The rst thing that should be checked when troubleshooting the Q5 board is its powering
up sequence.
FEATURES
The Q5 board includes the following features:
6 total USB ports (2 are dedicated, 4 are avail­able)
10/100/1000 Mbps Ethernet Connection
2 RS-422 ports
2 RS-485 ports
External Video monitor connection
LED indicators to verify proper operation of various on board areas (power, communica­tions, Ethernet connectivity, etc.)
2 GB RAM memory
Battery to maintain date and time
WHAT SHOULD OCCUR WHEN APPLYING POWER
When powering up, the following sequence of events are indicative of a properly working main processor board:
The six LED’s in the lower left corner should turn on solid.
WHAT IF THE OPERATING STATUS SCREEN IS NOT SHOWN
If the Operating Status screen is not shown, check the following items:
1. If no LED’s are lit, then check AC and DC pow­er. Refer to the Power Supply section.
2. Check if the lighting of the LED’s is occurring as described in the What Should Occur When Applying Powering section.
If the powering up sequence contin­ues to repeat without displaying the Operating Status screen, then there is a booting problem.
3. Check all plugged connectors for proper seat­ing.
4. Check if an error message is displayed when booting.
• Be sure to write down any error messages exactly as they appear, as well as the top line on the screen where the message appears.
5. Check that the software is OK:
Is the correct software installed?
The on-board “buzzer” should “beep” once.
The display should show several DOS (text) style screens. A penguin image will appear in the upper left corner of the screen as the boot sequence progresses.
Did you just install new software?
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
090.610-M (MAY 2016) Page 15
6. Check the display. If the Q5 board is booting but you have no display, check the following:
Check the backlight tube. Look very closely at the display to see if any­thing is visible in the dark screen. Using a beam type source of good
lighting, such as a ashlight, look for
any ghost type image. If it appears that there is something on the screen but very dark, the problem may be with the backlight tube. There is a sticker on the display mounting plate, that will have a part number that describes the type of display. If there is no sticker, you must take the display apart to identify the display manufacturer.
Verify that both the display cable and
the inverter cable are rmly seated.
It may be necessary to remove the video cable from the back of the dis­play and re-seat it to be sure it is connected properly. Note: This is a small connector and caution should be observed so that it is not dam­aged due to excessive force.
To replace the battery, ensure that the Control Power switch has been turned OFF.
Locate the Battery socket, as shown on the following drawing:
Place your ngernail under the edge of the battery, and
gently lift up. The battery should release itself from the socket easily. Take a new battery and place it into the holder in the same orientation as the old battery (the side with the writing must be facing out). Return the Control Power switch back to ON.
Once the Q5 has rebooted, the correct Date and Time must be set.
Q5 INTERFACE BOARD
An interface board has been developed by Frick con­trols allowing the user to interface exterior connec­tions to the Q5. A photo of this interface board is shown here:
Refer to the Operator Interface sec­tion and check that the display, dis­play cable, and software versions are matched correctly.
BATTERY FUNCTION AND REPLACEMENT
The Q5 board utilizes a battery to maintain correct date and time for the purpose of stamping warnings and shutdowns with the date and time that they occurred. If the date and time are not being maintained properly, this may indicate that the battery is not functioning, and should be replaced. The battery may be ordered through Baltimore Parts (P/N 333Q0001786) or may be purchased at most electronic shops (manufacturers P/N CR-2032). The battery is fully assessable, but is surrounded by sensitive electronic components, so care should be taken when changing.
090.610-M (MAY 2016)
JLVDS2
POWER
LVDS1
CRT1
COM1
COM2
FUSE
DIMM1
CN_POWER1
USB
ETHERNET
CMOS1
Flash Card located
Page 16
QUANTUM™ LX EVAPORATOR CONTROL PANEL
Power Connector
MAINTENANCE
Q5 BOARD
BH1
Battery
CN1
Ethernet
Connector
under the board
here
LED’s
JLVDS3
(See Note 4
below)
JLVDS3
INVERTER1
Inverter
Connector
CN3
CN1000
Ports
LED’s
USB
Ports
NOTE 1: The triangle symbol ( )
COM4
RS-485
Video Connector
RS-232
denotes Pin 1 on connectors. Refer to the chart on the following page for jumper settings.
COM3
RS-485
RS-232
Video Monitor
NOTE 2: Do NOT remove the CN4 jumper. Removal of this jumper will cause the processor to not power up.
NOTE 3: Although the Q5 board is the main controller, most of customer connections will be to the Interface board, as shown later.
NOTE 4: Ensure that this jumper is installed between pins 1 and 2 if a display is used that requires an inverter board. Install the jumper between pins 2 and 3 for an LED display that does not use an inverter board. See also the jumper table on the next page for JLVDS3.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
1 2 3
1 2 3
1 2 3
2
1
1 2 3
2
5
1
1 2
1
1 2 3
2
1
1 2 3
MAINTENANCE
Q5 BOARD JUMPERS, LED’S AND CONNECTORS
JUMPER TABLE
090.610-M (MAY 2016) Page 17
Jumper
Title
CMOS1
(CMOS
Clear)
CN1000
(LCD
Resolution
Selector)
Function Jumper Setting
Normal
(default)
Closed
Clear
CMOS
24-bit
800x600
24-bit
1024x768
18-bit
800x600
18-bit
640x480
(default)
1 2 3
6 4
6 4
6 4 2
6 4
Closed
1-3 Closed
5 3
2-4 Closed JLVDS2
3-5 Closed
3
2-4 Closed
5
1-3 Closed
3
4-6 Closed JLVDS3
3-5 Closed
5 3
4-6 Closed
1 - 2
2 - 3
&
&
&
&
Jumper
Title
CN3
(Touch
Panel Type
Selector)
(Backlight Level Se-
lector)
(Backlight
Control
Mode)
Function Jumper Setting
5-Wire
Touch
Screen 8-Wire
Touch
Screen
(default)
0 – 5V
(default)
0 – 2.5V
3
Voltage
Mode - use
with inverter
(default)
PWM Mode
(Use for LED
display - no
inverter)
1-2 Closed
2-3 Closed
2-3 Closed
1-2 Closed
1-2 Closed
2-3 Closed
NOTE 1: The triangle symbol ( NOTE 2: Jumper CN4 is not shown on this chart, as it must always be installed.
LED DEFINITION TABLE
LED Title Label Color Function
LED1 Red 5VSB LED2 Red 3VSB
Power
LED’s
LED3 Green VCC 12V LED4 Green VCC 5V LED5 Green VCC 3V LED6 Blue Power On OK Status
1000MB Green Giga – LAN Speed
CN1000
(LCD
Resolution
Selector)
100MB Yellow 100MB - LAN Speed
10MB Red 10MB –LAN Speed
ACT
Green
(Blinks)
) denotes Pin 1 on connectors.
LINK Activity
CONNECTOR PINOUT TABLE
Connector
Pin Function
Title
1 Ground (GND)
CN_PWR1
2 Ground (GND)
(Power
Input)
3 VCC 12V
4 VCC 5V
COM1 &
2 Receive (RX)
COM2
(RS-232
3 Transmit (TX)
Communi-
cations)
COM3 &
5 Ground (GND)
1 -RX/TX
COM4
(RS-485
Communi-
cations)
2 +RX/TX
3 Ground (GND)
090.610-M (MAY 2016)
2 1
2 1
Page 18
Baud Rate Jumpers
J15 Not Installed = 19200 (Default) J15 Pins 1-2 Installed = 38400 J15 Pins 3-4 Installed = 56K J15 Pins 1-2 and 3-4 Installed = 115K
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Q5 INTERFACE BOARD
COMM
4
COMM
3
COMM
2
COMM
1
COMM 1 JUMPER SETTINGS COMM 2 JUMPER SETTINGS
Jumper Title Function Jumper Setting
3
RS-422 (4-Wire)
Default
J1
RS-485 (2-Wire)
J2
J3
Pull Down
Default
Pull Up
Default
RS-422
J5
Default
RS-485
RS-422
Default
J6
RS-485 1 - 2 Closed
3 2 1
1 - 2 Closed
2 - 3 Closed
1 Pin Only
1 Pin Only
1 Pin Only
1 - 2 Closed
1 Pin Only
Do Not
Remove J14
Jumper Title Function Jumper Setting
3
3 2 1
1 - 2 Closed
2 - 3 Closed
1 Pin Only
1 Pin Only
1 Pin Only
1 - 2 Closed
1 Pin Only
J7
J13
J16
J17
J18
RS-422 (4-Wire)
Default
RS-485 (2-Wire)
Pull Down
Default
Pull Up
Default
RS-422
Default
RS-485
RS-422
Default
RS-485 1 - 2 Closed
J4
High Speed Target
Default
NOTE: The triangle symbol ( ) denotes Pin 1 on con­nectors.
1 - 2 Closed
J22
High Speed Target
Default
1 - 2 Closed
NOTE: The triangle symbol ( ) denotes Pin 1 on con­nectors.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
090.610-M (MAY 2016)
MAINTENANCE
Q5 INTERCONNECTIONS
The pictorial below depicts the Q5 motherboard, and the necessary interconnects between it and the Interface
Page 19
If the harness for either COMM1 or COMM2 is ever removed for either repair, replacement or troubleshooting, ensure that the pinout matches as shown here when plugging the ends back in. All other Interconnec tion harness ends share the same pinout at both ends.
-
090.610-M (MAY 2016) Page 20
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
POWER SUPPLY (Q5)
DESCRIPTION
The power supply of the Q5 control panel consists a single, 12 volt DC supply, and is located on the DIN rail at the back of the enclosure.
The supply is adjustable and has an indicator to show that it is powered. Refer to the following page for the location for the adjustment.
Power ON
Indicator
12 Volt DCPower Supply
POWER DISTRIBUTION
12 Volt DC Power is distributed to the Q5 processor board and Interface Board.
MEASURING VOLTAGES
CAUTION! Measuring and adjusting the power supply
voltage requires the control power switch to be ener­gized. Extreme care must be observed when taking any readings, as 120 or 230 VAC (depending on incoming system voltage) will be present next to the DC volt­age connector. Adjusting the supply requires the use of a small Philips screwdriver inserted into the supply to access an adjusting potentiometer. CAUTION: It is
possible for the screwdriver (and the person mak­ing the adjustment) to come into contact with po­tentially lethal voltages. Proper Personal Protective Equipment (PPE) measures need to be observed.
LED’s on the Q5 are lit, but nothing appears on the display.
To perform measurements and adjustments on the power supply voltage, use a reliable, calibrated Digi­tal Volt Meter (DVM). The DVM should be accurate to 1/100 of a volt DC. With the control power switch turned ON, wait until the Operating Screen appears. This is because the graphics required to create this screen will draw more current than when the screen is showing the normal POST (DOS) style messages during a boot up. If the screen never appears however (possi­bly due to a voltage problem), you will need to proceed regardless of what is or is not displayed.
In order to properly measure the DC power system, it must be checked at the DC power supply.
ADJUSTMENT
Ensure that the meter is set to the proper range (DC, 0-50 V or equivalent), as well as observing proper wire polarity. The power supply drawing shown on the fol­lowing page applies to all three power supplies. The adjustment access hole for each supply is located on the lower left of the front of the supplies. If an adjust­ment is required, use a thin, Philips screwdriver, insert the tip into the access hole for the appropriate voltage potentiometer (refer to the diagram on the following page for adjustment location). NOTE: Extreme care
must be used when adjusting the potentiometer.
Adjustment should only be performed by qualied
personnel. The use of a non-conductive device is recommended.
All circuit boards within the Q5 control panel require accurately adjusted DC voltages in order to function properly. Periodic measurement and adjustment of the DC power system is recommended for optimum sys­tem operation. Over time, it is possible for tempera­ture, humidity, vibration and component age, to de­grade the accuracy of these voltages. When any of the DC voltages begin to stray from their optimum range, mysterious problems can begin to arise.
Even with a perfectly adjusted supply, it is possible for a potential drop in voltage at each connection point. This drop normally is in the millivolt range, but un­der some conditions, the drop can be much greater (as high as tenths of a volt). Some examples of problems could be:
Loss of or intermittent communications fail­ures.
Q5 reboots for no apparent reason.
+ -DCG N L
120 VAC
or
240 VAC
QUANTUM™ LX EVAPORATOR CONTROL PANEL
+12 VDC Adjustment
Locate the DC power supply terminals. Place the negative lead on - and the positive lead on +. Verify that the DVM is displaying in the range of +12.10 to +12.20.
If adjustment is required, locate the adjustment access hole on the +12 VDC supply, as previously shown. While watching the DVM, slowly rotate the screwdriver blade clockwise to increase the voltage or counter-clockwise to decrease until the voltage is correctly adjusted.
POWER SUPPLY REPLACEMENT
If the power supply is found to be bad, or not capable of acceptable adjustment, the failing supply will need replacing. Refer to the Recommended Spare Parts list for the appropriate part number.
MAINTENANCE
090.610-M (MAY 2016) Page 21
090.610-M (MAY 2016) Page 22
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SECTION 4
Q4 CONTROLLER
090.610-M (MAY 2016) Page 23
090.610-M (MAY 2016) Page 24
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Q4 CONTROLLER BOARD
INTRODUCTION
Frick® Controls has strived to remain on the cutting edge of microprocessor technology and development. Because of the ever-increasing speed, memory fea­tures, and power of microprocessors, Frick® will con­tinue to introduce the latest advancement in micropro­cessor control technology.
The display should show several DOS (text) style screens. A penguin image will appear in the upper left corner of the screen as the boot sequence progresses.
Just before fully booting, a Loading bar will appear at the bottom of the screen, showing the percent of load that has completed.
The Operating Status screen will appear.
After the Q4 has properly powered up, the following sequence of events is indicative of proper communi­cation to the analog and digital boards:
The Analog and Digital I/O boards TX/RX lights should be blinking.
Each I/O board should have the power LED lighted and the Active LED should be blink­ing.
WHAT IF THE OPERATING STATUS SCREEN IS NOT SHOWN
If the Operating Status screen is not shown, check the following items:
Q4 Board
WHAT SHOULD OCCUR WHEN APPLYING POWER
The rst thing that should be checked when trouble­shooting the Q4 board is it’s powering up sequence.
When powering up the Q4, the following sequence of events are indicative of a properly working main pro­cessor board:
Green PWR (Power) LED will turn on solid.
Red FLASH LED will ash several times early
in the boot sequence. It is normally not lit.
LED D8 (on the smaller board) will start to blink at the rate of about once-per-second. It will continue to blink after the Q4 has booted. The only time that this ashing rate is inter­rupted, is when a key is pressed on the key­pad.
1. If no LED’s are lit, then check AC and DC pow­er. Refer to the Power Supply section.
2. Check if the lighting of the LED’s is occurring as described in the What Should Occur When Applying Powering section.
If the powering up sequence continues
to repeat without displaying the Operat­ing Status screen, then there is a booting problem.
3. Check for bad connections.
4. Check if an error message is displayed when booting.
Be sure to write down any error mes-
sages exactly as they appear.
5. Check that the software is OK:
Is the correct software installed?
Did you just install new software?
6. Remove Flashcard and reboot. This will cause the Q4 to boot under a pre-LX operating software. If it boots properly under this older software, then trying re-booting from the Flashcard again. If it doesn’t boot with the card, then the Flashcard could be corrupted, and needs to be replaced.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
Battery Release
MAINTENANCE
090.610-M (MAY 2016) Page 25
7. Check the display. If the Q4 board is booting but you have no display, check the following:
Check the backlight tube. Look very closely
at the display to see if anything is visible in the dark screen. Using a beam type source of
good lighting, such as a ashlight, look for any
ghost type image. If it appears that there is something on the screen but very dark, the problem may be with the backlight tube. On the LG Philips, NEC and Sharp displays this tube is eld replaceable. On the Samsung dis­play it is not available and the display will have to be replaced. There may be a sticker on the display mounting plate. If there is, it will have a part number that describes the type of dis­play. If there is no sticker, you must take the display apart to identify the display manufac­turer.
Verify that both the display cable and the in-
verter cable are rmly seated. These cables
both originate from the same connector on the Q4. It may be necessary to remove the video cable from the back of the display and re-seat it to be sure it is connected properly. Note: This is a small connector and caution should be observed so that it is not damaged due to excessive force.
BATTERY FUNCTION AND REPLACEMENT
The Q4 board utilizes a battery to maintain correct date and time for the purpose of stamping warnings and shutdowns with the date and time that they oc­curred. If the date and time are not being maintained properly, it may indicate that the battery is not func­tioning, and should be replaced. The battery may be ordered through Baltimore Parts (P/N 333Q0001786) or may be purchased at most electronic shops (manufac­turers P/N CR-2032).
The battery is partially covered by the communications daughter board, and is located directly beneath the COM1 port (it may be necessary to unplug any con­nector that is plugged into COM1 to fully access the battery).
To replace the battery, ensure that the Control Power switch has been turned OFF.
Locate the Battery Release Clip on the following draw­ing:
Clip
Refer to the Operator Interface section and
check that the display, display cable, and soft­ware versions are matched correctly.
Battery
Battery
Holder
Simply push the clip away from the battery, to release the battery from the holder. Remove the battery, ob­serving the orientation. Take a new battery and place it into the holder in the same orientation as the old battery (the side with the writing must be facing out). Reinstall the COM1 plug (if removed), and return the Control Power switch back to ON.
Once the Q4 has rebooted, the correct Date and Time must be set.
090.610-M (MAY 2016) Page 26
RS-422/485
RS-422/485
USB Connector
(Depending on board version,
USB could be located in either
of these two locations.
COM-3
(PL6)
RS-232
connector
COM-1
(TB1)
LK2
PL1
RS-422/485
connector
PL2
3.3 Volt Battery
PL3
COM-2
COM-2
(TB2)
(TB2)
connector
connector
PL5
PL7
LK1
PL
Flash Card Socket
(located under
board)
LK4
A
LK3
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Q4 BOARD
+5VDC
Power
PL
9
PL8
COM-1
4
3
2
1
TB1
A B
LK
TB2
7
LK
LK
5
4
6
3
2
1
COM-2
COM-2
PL
B
11
PL 12
PL10 PL6
RS-
422
LK2
RS-
422
LK1
TB3
LK 10
LK
LK
LK
LK
LK
RET / GND
+12VDC
PL13
PL14
COM1
(TX)
COM1
(RX)
9
8
A B
7
COM2
(TX)
LK
6
LK
5
A
4
3
RS-232
2
3
PL 15
-RX/-TX (I/O Boards) +RX/+TX (I/O Boards)
PL 17
PL 18
LK9
LK8
POR T 80H
D4 D5 D7
D3
D2
LK16
D1
B
LK17
1
Baltimore Parts with LK4
set to B position for an
4
1
3
2
0
D11
D1
D9
0
COM2
(RX)
B A
KB
This assembly is
shipped from
LG Philips Display.
If using a Samsung,
NEC or Sharp
Display, set LK4
to position A. LX panels use
the Sharp display.
PL 19
PL 24
LK12
P
PL16
5
6
7
ON
D13
D1
8
2
7
SW1
6
LK11
W
SU
FL
SP
AS H
PL2
D6
LK11
PL4
D8
PL
PL1
3
Keypad
Cable
Communications Board
(small top board)
COM-2
(TB3)
RS-232
connector
Display
Cable
CAT-5 Ethernet
NOTE: There are duplicate numbers for the links on the processor (larger) board and the communications (smaller) board. If you must make a change to a jumper (link), ensure that you modify the correct link.
Processor Board
(large botom board)
Controller Board Pictorial
Processor Board Jumpers
2 second Watchdog timer timeout
LK1
LK2
LK3
LK4
LK5
LK6
LK7
LK8
LK9
LK10
LK11
LK12
* Standard Setting
in
8 second Watchdog timer timeout
out*
Watchdog timer Enabled
in*
Watchdog timer Disabled
out
+5V Backlight Voltage (not used)
A
+12V Backlight Voltage (all displays)
B *
+5V Supply (Samsung, NEC, Sharp)
A
+3.3V Supply (LG Philips & Sharp LED Display)
B *
COM4 IRQ3
A
COM4 IRQ10
B *
COM3 IRQ4
A
COM3 IRQ11
B *
Battery Backup Enabled
A *
Battery Backup Disabled (CMOS Cleared)
B
RS-485 Receiver Enabled
in*
RS-485 Receiver Disabled
out
RS-485 Terminated
in*
RS-485 Not Terminated
out
RS-422 Terminated
in
RS-422 Not Terminated
out*
Bit 1 of 259H “Logic 1” User Application Link
in*
Bit 1 of 259H “Logic 0” User Application Link
out
Bit 2 of 259H “Logic 1” User Application Link
in*
Bit 2 of 259H “Logic 0” User Application Link
out
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Q4 BOARD SETTINGS
090.610-M (MAY 2016) Page 27
Communications Board Jumpers
Com-1 (TB1)
in
LK2
LK7
LK8
LK9
LK10
LK16
* Standard Setting
Terminate COM1
out*
No termination
in
Pull down COM1
out*
No pull down
in
Pull up COM1
out*
No pull up
in
Pull down COM1
out*
No pull down
in
Pull up COM1
out*
No pull up
AB*COM1 RS-422 (TB1)
COM1 RS-485 (TB1)
Com-2 (TB2 - TB3)
LK1 in
LK3 in
LK4 in
LK5 in
LK6 in
LK11 A
LK17 A
* Standard Setting
Terminate COM2
out*
No termination Pull down COM2
out*
No pull down Pull up COM2
out*
No pull up Pull down COM2
out*
No pull down Pull up COM2
out*
No pull up Select RS-232 for COM2 (TB2)
B*
Select RS-422/RS-485 for COM2 (TB3) COM2 RS-422 (TB2)
B*
COM2 RS-485 (TB2)
RS-422/485
RS-422/485 (Rx-/Tx-)
RS-422/485 (Rx-/Tx+)
RS-422 (Tx-)
RS-422 (Tx+)
RS-422/485
RS-422/485 (Rx-/Tx-)
RS-422/485 (Rx-/Tx+)
RS-422 (Tx-)
RS-422 (Tx+)
090.610-M (MAY 2016)
+5 VDC
Common
+12 VDC
+5V
RET
AC Input
DC
Output
RET RET +5 +12
Page 28
QUANTUM™ LX EVAPORATOR CONTROL PANEL
EVAPORATOR LX CONTROL PANEL POWER SUPPLY
CAUTION! Measuring the power supply voltages require the control power to be energized. Extreme care must be observed when taking any readings, as 120 VAC is present within the power supply.
The Q4 controller utilizes only the +5 VDS and +12 VDC voltages from the power supply. To perform measurements on the power supply voltages, use a reliable, calibrated Digital Volt Meter (DVM). The DVM should be accurate to 1/100 of a volt DC. Turn the control power switch to ON.
MAINTENANCE
Q4 POWER SUPPLY
Measure the voltages on the power supply at the DC output connector as shown below:
The following voltage range is considered to be acceptable:
+5 VDC supply (+5.15 to +5.20 VDC)
+12 VDC supply (+11.8 to +12.2 VDC)
If the voltages from the power supply are within the acceptable ranges, then measure them at the Q4 control board, as shown below:
If the voltages from the power supply are within the acceptable ranges, then measure them at the last I/O board in the daisychain, as shown below:
If any of the voltages measure outside of the acceptable range, yet measured correctly at the power supply, then a problem with the wiring harness should be suspected and checked.
REPLACEMENT
If the power supply is found to be bad, or out of adjustment, it will need replacing.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SECTION 5
DIGITAL BOARD
090.610-M (MAY 2016) Page 29
090.610-M (MAY 2016)
+5V
RET
Page 30
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
DIGITAL BOARD
INFORMATION
The information that follows in this section can help locate problems that can occur with Digital Input and Output circuit boards, and their interaction with the Q4/Q5 controller.
Therefore, any time that a connector is unplugged from the daisy-chain, these voltages and signals cannot continue through the daisy-chain to the next board. Whenever a plug is not to be inserted into a board, either for service or if not all boards are present, then a shunting plug (refer to Replacement Parts list) must be installed onto the open connector.
DIGITAL BOARD DESCRIPTION
The Digital Boards only require the +5 Vdc voltage
The Digital Board is actually a small microprocessor board and programmed to control discrete outputs, or accept discrete inputs, from external electrical devices. Each Digital Board has the capability of 24 independent channels or I/O (Input/Output). With the Quantum™ LX Evaporator Control, some of these I/O channels are dedicated as to their function, through the operating system (software), enabled options and external wiring. Each channel that is used by the software will have a module plugged into it. A yellow module indicates that it is used for Inputs, a black module is used for Outputs. The standard Quantum™ LX Evaporator Control can have up to two Digital Boards (depending on options).
COMMUNICATIONS LED'S
The controller is in constant communication with all Digital (and Analog) Boards. You will notice on each Digital and Analog board, that there are a pair of LED’s labeled as RX and TX. These letters represent Receive
(RX) and Transmit (TX). These LED’s should be ashing
at a high rate during normal operation. This indicates that the Q5 (or Q4) control board, and the Digital Board that you are looking at, are properly communicating with each other.
• Reference the JUMPER AND DIPSWITCH SETTINGS section later in this manual. This section contains the dipswitch settings for addressing the Digital I/O Boards. When these switches are properly set, the Q5 (or Q4) board is able to serially communicate with each I/O board and provide control signals and data exchange. If these switches are not properly set, the result will be lost or failed communications, or the wrong outputs being energized, or the wrong inputs being received.
CONNECTIONS TO THE QUANTUM™
The Frick® Evaporator control system utilizes up to two Digital, and one Analog Boards. To connect all of these boards together so that the Q4/Q5 can control them, they must be interconnected with a wiring harness that provides all of the necessary D.C. voltage requirements, as well as the communications capabilities. Upon close examination of this harness, you will notice that each of the connectors have two rows of connections. The wires that are inserted into the positions of one row, are internally daisy-chained on each I/O board, to continue the voltages and signals to the adjacent row.
and the Return (or common) for logic power. The communications signals (RX & TX) are required by all boards.
LOGIC VOLTAGE (POWER) LED
Located on the Digital Board is a Power LED. This LED will be illuminated as long as the Control Power switch is ON, and the proper voltage is present at the Remote panel power supply. The power supply generates the +5 VDC voltage, and passes it on through the Power­I/O harness. This LED does not indicate however that the proper voltage is necessarily present at the board, only that the voltage is enough to energize the voltage sensing circuitry. If a voltage related problem is suspected with regard to a Digital Board, the only way to actually determine this is to read the voltage on a Digital Voltage Meter (DVM). This may be accomplished by locating the white power/communications connector on the board. Notice that the Digital Board has one of these connectors on both ends of the board. The associated power/communications harness will only be plugged into one of these connectors. Take the red (positive) probe of the DVM and carefully insert the end into the “+5V” lead, and the black (negative) probe end into the “RET” (Return or Common) lead, as shown below:
Set the DVM to read DC, and set the proper range. The voltage reading must read a minimum of +5.0 Vdc. The Power-I/O harness will have an associated voltage drop at each board connection. As an example, if you
are reading the voltage at the rst I/O board in the
daisy-chain, and it reads 4.98 Vdc, you can be assured that the voltage at the subsequent connections for the remaining boards will be lower yet. The voltage will need to be corrected for proper operation of the system. The cause for a low voltage reading could be:
The power supply may need adjustment (see the section on power supplies).
QUANTUM™ LX EVAPORATOR CONTROL PANEL
5 4 3
COM OUT VDC
2
1
90-140VAC
120 VAC
4
3
3-8 VDC
2
1
3A 280VAC
120 VAC Output
HOT
NEUTRAL
Position1
Position2
Position3
Position4
MAINTENANCE
090.610-M (MAY 2016) Page 31
The Power-I/O communications harness has a problem (a new harness may be needed).
A problem may exist with one of the I/O boards (Digital or Analog).
If the power LED is not lighted, check the cable for proper connectivity. Note: Each board provides the necessary connections to feed all signals to the following connectors. If the auxiliary Analog or Digital Board is not present then a jumper plug (see Recommended Spare Parts List) must be installed to daisychain the signals.
The most common symptom that is be exhibited by a low +5 Vdc voltage to the Digital Boards is an alarm message that reads Digital Board Reset Shutdown.
ACTIVE LED
The Digital Board(s) have an Active LED indicator on the board that blinks when the board’s software is running.
If the Active LED is not blinking, check to ensure that the EPROM is installed properly. The EPROM is located in chip slot U8, next to the power connector.
DIGITAL INPUTS
A Digital Input is the portion of the hardware that allows devices such as limit switches, relay contacts, and level switches, to interface with the Quantum™. The software program within the Quantum™ is constantly looking at these Input channels, via communications, and based upon whether a control voltage is present or not, will provide the necessary control for an associated Output channel.
The following pictorial shows a side view of the 120 VAC Input module. The color of an Input module is yellow:
DIGITAL OUTPUTS
A Digital Output is the portion of the hardware that the Quantum™ is to control (energize). These devices include solenoids, relay coils, and heaters to be energized, based upon the logic within the Quantum™ LX software program.
The following pictorial shows a side view of the 120 VAC Output module. The color of an Output module is black:
Although this Output module is labeled as 280 VAC on the top, and on the side, it can be used on both 120 and 240 volt applications.
Never plug an Input module into a position designated for an Output module.
You will notice that when a module is plugged into the Digital Board, there is a fuse located directly adjacent to the module. This fuse is of the plugable variety, and must be plugged into the OUT position for an Output module.
CHECKING THE DIGITAL INPUTS AND OUTPUTS
Some problems that may be encountered involve troubleshooting the digital inputs and outputs. The Digital I/O (Input / Output) Boards have six Digital I/O (DIO) board connectors labeled P1 through P6. The Input and Output modules are wired to a DIO connector plug. Position 3 provides power and position 4 is a neutral on the DIO connectors. Positions 1, 2, 5, and 6 are signal connections, as shown below:
Never plug a 120 Volt Input module into a 240 Volt system, and vice-versa. Never plug an Output module into a position designated for an Input module.
You will notice that when a module is plugged into the Digital board, there is a fuse located directly adjacent to the module. This fuse is of the plugable variety, and must be plugged into the IN position for an Input module.
Signal
Signal
Signal
Signal
The Digital I/O board’s I/O modules are congured by
proper module selection, AC or DC, operating voltage, input or output, and moving the fuse to the in or out position. An LED is associated with each module and displays the state of each module. A lit LED represents an Input that is High, receiving a signal or an Output that is On.
If a properly congured Digital I/O is not responding correctly, rst look at the Digital Board on the Digital
I/O Screen and check if the module is on. If it is not on, check if the LED on the Digital Board is also not lit. If the LED is not lit, then check the fuse. If the fuse is OK, then check the module.
090.610-M (MAY 2016) Page 32
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
FUSE TESTING AND REPLACEMENT
1. Power off the panel.
2. Open the panel door.
3. Remove the questionable fuse.
4. Place the questionable fuse into the fuse tester at the one end of each Digital I/O Board (refer to the Digital Board drawings at the end of this section for exact fuse tester location).
5. Power on the panel.
6. Check the LED on the tester. If the LED is lit, the fuse is OK.
7. Power off the panel.
8. If the fuse is faulty, check for external shorts on the corresponding circuit, the replace the fuse with a new plug-type fuse (refer to Recommended Spare Parts list).
INPUT AND OUTPUT MODULE TESTING AND REPLACEMENT
1. Power off the panel.
2. Open the panel door.
3. Replace the questionable module.
4. Power on the panel.
5. If it is an Output module, check for proper panel voltage on the DIO connector plug. Check the voltage between position 4 (neutral) and the associated position to the Output module.
6. If it is an Input module, check if the associated LED is on when power is applied to the module.
TROUBLESHOOTING AN OUTPUT
1. Make sure the LED associated with the Output is on when power is applied to the module.
2. If the LED is not on when it should be and there is no operating condition preventing it, contact the
®
Service Department.
Frick
3. If the LED is on when it should be, check for proper panel voltage on the DIO connector plug. Check the voltage between the position 4 (neutral) and the associated position to the Output module.
4. If the voltage is OK, check for proper panel voltage between the associated position to the Output module on the DIO connector and the associated position on the terminal strip.
5. If the voltage is OK, check the wiring external to the panel.
6. If voltage is not OK, check the fuse.
7. If the fuse is OK then check the module.
8. If the module is OK, check for proper panel voltage on the DIO connector plug between position 3 (Hot) and position 4 (neutral).
TROUBLESHOOTING AN INPUT
1. Make sure the LED associated with the Input is on when power is applied to the module.
2. If the LED is on then the fuse and Input module are good.
3. If the LED is on and there is no input voltage, replace the Input module.
4. If the LED is not on when power is applied, check the fuse.
5. If the fuse is good, replace the Input module.
6. If you are receiving an Alarm or Shutdown from a digital input in which the adjacent LED indicator light is on, check the Digital I/O screen to see if that channel is turning on and off. If so, replace the input module.
REPLACING A DEFECTIVE DIGITAL BOARD
The procedure to replace a Digital board is outlined below:
1. Shut off control power.
2. Remove the old board from the machine and
the new board from its packing and place both on an anti-static surface.
3. Remove any required chip(s) from the
defective board and install them in the replacement board.
4. Check that all jumpers, dipswitches and
components are properly setup on the new board using the old board as a reference (refer to the Digital Settings tables near the end of this section).
5. Install the modied replacement board in the
panel.
After replacing or installing a Digital Board and powering on the control panel, select User Level 1 or higher, then select the Setpoints Menu, then the Communications Menu. On the Communications Screen is a button labeled as [Redetect I/O Comms]. Clicking on the [Redetect I/O Comms] button will cause the controller to examine the internal I/O communications of the panel, and initialize all connected boards If a board has been removed, a communication error shutdown will be issued until this key is selected. The About screen will show what was detected.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
TEST FUSE HERE.
IF LAMP LIGHTS
SPARE FUSE
P8
D8
1
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
5A
F7
F8
F9
F10
F3
F2
F1
F4
F5
F6
F11
F12
F13
F15
F14
F17
F16
F18
F23
F22
F21
F24
F19
F20
BOARD REVISION L EVEL BOARD PART NUMBER
Frick
SERIAL #
REVISION
PART # 640D0062H
PROGRAM EPROM
DIO
I/O COMMUNICATION
ACTIVITY LAMPS
D25
TX
D26
RX
D28
ACTIVE
MICROPROCESSOR
WATCHDOG LAMP
(BLINKS IF OK)
M7
D7
M8
M9
D9
M10
D10
M3
D3
M2
D2
M1
D1
M4
D4
M5
D5
M6
D6
M11
D11
M12
D12
M13
D13
M15
D15
M14
D14
M17
D17
M16
D16
M18
D18
M23
D23
M22
D22
M21
D21
M24
D24
M19
D19
M20
D20
1
AMP794068-1
POWER ON
D29
+5 VOLTS
+12 VOLTS
-12 VOLTS
GND
-RX / -TX
+RX / +TX
BOARD DC POWER
I/O COMMUNICAT IONS
+5 DC
U8
P7
FUSE POSITION DETERMINES
INPUT OR OUTPUT
DIGITAL I/O BOARD
NOTE 1: ALL OUTPUTS ARE RATED FOR A
Liquid (Zone A)
Suction (Zone A)
HOT
NEUTRAL
Hot Gas (Zone A)
Bleed (Zone A)
Liquid (Zone C)
Suction (Zone C)
HOT
NEUTRAL
Hot Gas (Zone C)
Bleed (Zone C)
Aux. Output (Zone C)
Aux. Input (Zone A)
HOT
NEUTRAL
Aux. Input (Zone B)
Aux. Input (Zone C)
Fan (Zone C)
Defrost Initiate (Zone C)
HOT
NEUTRAL
Aux. Output (Zone A)
Aux. Output (Zone B)
Hot Gas (Zone B)
Bleed (Zone B)
HOT
NEUTRAL
Fan (Zone B)
Defrost Initiate (Zone B)
Fan (Zone A)
Defrost Initiate (Zone A)
HOT
NEUTRAL
Liquid (Zone B)
Suction (Zone B)
1
P5
1
P4
1
P2
1
P1 1 P3
1
P6
IN
OUT
IN
IN
OUT
IN
IN
OUT
OUT
IN
IN
OUT
IN
OUT
OUT
OUT
IN
IN
OUT
OUT
IN
IN
OUT
IN
OUT
OUT
IN
IN
OUT
IN
IN
OUT
IN
OUT
OUT
OUT
OUT
OUT
INSTALLED
FUSE
SPARE
FUSE
D27
FUSE TESTER
1
AMP794068-1
COMMUNICATION S JUMPERS
OPEN
DIPSWITCH SETTINGS S IGNIFY
DP1
J5
J7
J8
J9
J10
MAINTENANCE
DIGITAL I/O BOARD PICTORIAL
090.610-M (MAY 2016) Page 33
INPU T MODULE
OUTPUT MODULE
FUSE
MAXIMUM 2 AMP LOAD.
OUT
IN
IN
OUT
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
INPUT MOD ULE
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
INPUT MOD ULE
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
OUTPUT MODULE
IN
INPU T MODULE
OUTPUT MODULE
OUT
OUT
IN
IN
IN
5A
OUTPUT MODULE
OUTPUT MODULE
INPUT MOD ULE
INPUT MOD ULE
INPUT MOD ULE
090.610-M (MAY 2016)
Quantum™ LX
Control Board
Comm. 4
(Zones
1-15)
Comm. 3
(Zones 16-30)
I/O Group 1
Zones 16, 17, 18
Digital Board
Digital Board
Analog Board
I/O Group 2
Zones 19, 20, 21
Digital Board
Digital Board
Analog Board
I/O Group 3
Zones 22, 23, 24
Digital Board
Digital Board
Analog Board
I/O Group 4
Zones 25, 26, 27
Digital Board
Digital Board
Analog Board
I/O Group 5
Zones 28, 29, 30
Digital Board
Digital Board
Analog Board
I/O Group 1
Zones 1, 2, 3
Digital Board
Digital Board
Analog Board
I/O Group 2
Zones 4, 5, 6
Digital Board
Digital Board
Analog Board
I/O Group 3
Zones 7, 8, 9
Digital Board
Digital Board
Analog Board
I/O Group 4
Zones 10, 11, 12
Digital Board
Digital Board
Analog Board
I/O Group 5
Zones 13, 14, 15
Digital Board
Digital Board
Analog Board
Page 34
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
DIGITAL BOARD SETTINGS
COMMUNICATIONS SETTINGS
The following table is to be used when conguring the Quantum™ for external communications.
J5
J7
J8
J9
J10
in 120 ohm long communications line termination.
out* No termination.
in RS-422/485 transmit pull-up for long communications lines.
out* No pull-up.
in RS-422 transmit pull-up for long communications lines.
out* No pull-up.
in RS-422/485 receive pull-down for long communications lines.
out* No pull-down.
in RS-422 receive pull-down for long communications lines.
out* No pull-down.
* = standard setting
DIPSWITCH SETTINGS
The following table is to be used to set the digital board addresses. Refer to and study the diagram at the bottom of this page
to determine the correct board conguration.
Comm. 4 of Quantum™ (Zones 1-15) Comm. 3 of Quantum™ (Zones 16-30)
I/O
Group
1
2
3
Digital
Board #
SW1 SW2 SW3 SW4 SW5 SW6
1 On On On On Off On 6 Off On Off On Off On 6 Off On Off On Off On
2 Off On On On Off On 7 On Off Off On Off On 7 On Off Off On Off On 3 On Off On On Off On 8 Off Off Off On Off On 8 Off Off Off On Off On
4 4 Off Off On On Off On 4 4 Off Off On On Off On
9 On On On Off Off On 9 On On On Off Off On
5 5 On On Off On Off On 5 5 On On Off On Off On
10 Off On On Off Off On 10 Off On On Off Off On
I/O
Group
1
2
3
Digital
Board #
SW1 SW2 SW3 SW4 SW5 SW6
1 On On On On Off On
2 Off On On On Off On
3 On Off On On Off On
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SECTION 6
ANALOG BOARD
090.610-M (MAY 2016) Page 35
090.610-M (MAY 2016) Page 36
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
ANALOG BOARD
OVERVIEW
The Frick® Quantum™ LX Evaporator control panel is capable of reading external analog devices, such as temperature probes and pressure sensors. It uses these input signals for the purpose of monitoring and control. As an example, if an external temperature sensor begins to read a higher than expected temperature in some area, the controller would sense this change, and provide the necessary output control signal to remedy the situation, or provide a warning. Unlike a digital signal, which is typically either an on or off state, an analog signal can assume a wide range of values, such as a temperature probe’s reading a wide range of temperatures.
The method used for receiving (and sending) these signals, is the analog board. The analog devices are wired directly to the board, and the on-board software/ hardware converts the electrical signals received from these devices into data, which is then sent on to the Q4 or Q5 control board via communications, and is monitored by the control software.
GENERAL DESCRIPTION
This board features twenty-four input channels, and eight output channels. The board channels are
congured through software, rather than using physical
jumpers. A more detailed description of the operation of this board is provided in the sections that follow. A drawing f this board is shown here:
ANALOG BOARD DESCRIPTION
The Analog Board is actually a small microprocessor board and is programmed to control analog outputs, or accept analog inputs, from external electrical devices. Each enhanced board has the capability of 24 independent input channels. With the Quantum™ Evaporator Control, these I/O channels are dedicated through the software and external wring, as to the function of each channel.
COMMUNICATIONS LED’S
The Quantum™ controller is in constant communication with the Analog (and Digital) Board(s). You will notice on each Analog and Digital board, that there is a pair of LED’s that are labeled as RX and TX. These letters represent receive
(RX) and Transmit (TX). These LED’s should be ashing at
a high rate during normal operation. This indicates that the Quantum™ LX, and the board that you are looking at, are properly communicating with each other.
Refer to the JUMPER AND DIPSWITCH SETTINGS section later in this section. This section contains the dipswitch settings for addressing the Analog I/O Boards. When these switches are properly set, the Quantum™ LX is able to serially communicate with each I/O board and provide control signals and data exchange. If these switches are not properly set, the result can be one of the following:
Lost or failed communications (displayed in
the Communications Status box on the Home screen)
The wrong analog input signals being received
The wrong analog output signals being sent
from the board.
CONNECTIONS TO THE QUANTUM™
As stated earlier, the Quantum™ Evaporator control system utilizes up to two Digital, and one Analog Board. In order to connect all of these boards together so that the Quantum™ can control them, they must be interconnected with a wiring harness that provides all of the necessary D.C. voltage requirements, as well as the communications capabilities. A diagram of this wiring harness can be found later in this manual (see the Power I/O Wiring Harness drawing). This harness has a 6-pin connector at one end that plugs into the Quantum™. Another connector plugs into the power supply. The remaining three connectors (16 pin) will plug into each of the Digital and Analog Boards in the system.
Upon close examination of this harness, you will notice that each of the connectors have two rows of connections. The wires that are inserted into the positions of one row, are internally daisy-chained on each I/O board, to continue the voltages and signals to the adjacent row. Therefore, any time that a connector is unplugged from the daisy-chain, these voltages and signals cannot continue through to the
QUANTUM™ LX EVAPORATOR CONTROL PANEL
+5V
RET
MAINTENANCE
090.610-M (MAY 2016) Page 37
next board. Whenever a plug is not to be inserted onto a board, either for servicing, or if not all boards are present because of the options that are present, then a shunting plug (refer to the Replacement Parts list) must be installed onto the open connector.
The Analog Board requires the +5 Vdc for logic, the
-12 Vdc for internal voltage reference, and +12 Vdc for external sensors (plus or +) and the Return (common or
-). The communications signals (RX & TX) are required by all boards.
LOGIC VOLTAGE (POWER) LED’S
Located on the Analog Board are two power LED’s. The
rst of these is D1 LED (+5VDC), and will be illuminated
as long as the Control Power switch is ON, and the proper voltage is present at Analog Board connector P3. The power supply generates the +5 VDC voltage, and passes it on through the Power-I/O harness. This LED does not indicate however that the proper voltage is necessarily present at the board, only that the voltage is enough to energize the voltage sensing circuitry.
If a voltage related problem is suspected with regard to the Analog Board, the best way to actually determine this is to read the voltage on a DVM (Digital Volt Meter. This may be accomplished by locating the white power / communications connector on the board. Notice that the Analog Board has only one of these connectors. The associated power / communications harness plugs in to it. Take the red (positive) probe of the DVM and carefully insert the end into the +5V lead, and the black (negative) probe end into the RET (Return or Common) lead, as shown below:
If the power LED is not lighted, check the cable for proper connectivity. Note: Each board provides the necessary connections to feed all signals to the following connectors. If the auxiliary Analog or Digital Board is not present then a jumper plug (Part # 640B0039H01) must be installed to daisy-chain the signals.
The second power LED is D5 (+24Vdc). This +24Vdc voltage is generated on the Analog Board from the +5Vdc supply being fed from the Remote panel power supply. If the +5Vdc is present as stated earlier, then this LED will illuminate if the on-board +24Vdc supply is functioning properly.
ACTIVE LED
The Analog Board has an Active LED indicator that blinks when the board’s software is running.
If the Active LED is not blinking, it could be an indication that the internal program is not running. Try powering the Remote panel off, then back on to see if the Active light starts blinking. If not, a new board may be required.
ANALOG INPUTS
An Analog Input is the portion of the hardware that allows devices such as temperature sensors and pressure transducers, to interface with the Quantum™ The software program within the Quantum™ is constantly looking at these Input channels, via communications, and based upon what the voltage or current level of the channel is, will provide the necessary control for an associated action.
Analog inputs arrive at the board on connectors P4 through P10. Each of these connectors can receive two channels (for a total of twenty-four).
ANALOG OUTPUTS
An Analog Output is the portion of the hardware that
Set the DVM to read DC, and set the proper range. The voltage reading must read a minimum of +4.98 Vdc. The Power-I/O harness will have an associated voltage drop at each board connection. As an example, if you
are reading the voltage at the rst I/O board in the
daisy-chain, and it reads 4.98 Vdc, you can be assured that the voltage at the subsequent connections for the remaining boards will be lower yet. The voltage will need to be corrected for proper operation of the system. The cause for a low voltage reading could be:
The Remote panel power supply may need adjustment (see the section on power supplies).
The Power-I/O communications harness has a problem (a new harness may be needed).
A problem may exist with one of the I/O boards (Digital or Analog).
the Quantum™ uses to provide control. These outputs are dedicated for a 4-20 mA signal and cannot be
changed through the software conguration.
TROUBLESHOOTING THE ANALOG INPUTS AND OUTPUTS
Some problems that may be encountered involve troubleshooting the Analog inputs and outputs. The Analog Board has twelve Analog I/O board connectors labeled P4 through P10. The external Analog devices are wired to a connector plug. Position 1 connects to the plus (+) of the external device for channel 1, position 2 connects to the signal (SIG) of the external device for channel 1 and position 3 connects to ground (GND) of the external device for channel 1. Position 4 connects to the plus (+) of the external device for channel 2, position 5 connects to the signal (SIG) of the external device for channel 2 and position 6 connects
090.610-M (MAY 2016)
GND
Channel 2 +
Channel 1
Channel 1
Channel 2
Signal
GND
Page 38
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
to ground (GND) of the external device for channel 2, as shown below:
Signal
Each input channel is congurable through the
operating software. There are twenty-four analog input channels that can be selected for 4-20 mA, 0-5 Vdc, ICTD, or RTD. Besides properly setting the
software conguration, each channel is setup through
software calibration for the proper transducer type and range, and each transducer must be calibrated through the appropriate sensor calibration screen. Improper setup of either the hardware or software will result in incorrect operation or range.
The most common fault associated with the improper reading of the analog channels other than hardware or software setup problems fall into one of the following categories:
REPLACING A DEFECTIVE ANALOG BOARD
The procedure to replace an Analog board is outlined below:
1. Ensure that all channel conguration
information for the board being replaced has been written down.
2. Shut off control power.
3. Unplug all connectors from the board.
4. Remove the old board from the unit and remove the new board from its packing and place both on an anti-static surface.
5. Check that all jumpers, dipswitches and components are properly setup on the new board using the old board as a reference (refer to the Analog Settings tables near the end of this section).
6. Install the modied replacement board in the
panel.
7. Plug all connectors back in.
8. Turn on control power.
9. After the panel has rebooted, access the
Analog Board Conguration Setup screen, and re-enter the correct channel conguration.
The default setup of the new board will be loaded to the processor. It is imperative that
the channel conguration screen be accessed to ensure that the channels are congured
properly for the application.
Sensor fault
Wiring problem
Improper grounding of system.
An open wire, shorted wire, or faulty sensor will usually give a reading at either the minimum or maximum end of the range scale. An erratic reading or a reading
that seems to oat up and down is usually indicative
of a grounding problem. When a single transducer or cable is shorted to earth (or system) ground, this can show up as a whole assortment of problem channels.
The easiest way to nd a short to earth problem is to
disconnect all the sensor plugs and ohm out each plug
screw terminal to earth for open (innite) impedance.
All sensors should read open to earth. The third pin on pressure sensors is ground.
After replacing or installing an Analog Board and powering on the control panel, select User Level 1 or higher, then select the Setpoints Menu, then the Communications Menu. On the Communications Screen is a button labeled as [Redetect I/O Comms]. Clicking on the [Redetect I/O Comms] button will cause the controller to examine the internal I/O communications of the panel, and initialize all connected boards If a board has been removed, a communication error shutdown will be issued until this key is selected. The About screen will show what was detected.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
P1 - J-TAGG Port
SW1 - DIP Switch
LK3 & LK4 -
D5 - +24Vdc Power LED
CH. 1 Output – Variable Spe ed (Zone A)
CH. 5 Output
CH. 2 Output – Variable Spe ed (Zone B)
CH. 6 Output
CH. 3 Output – Variable Spe ed (Zone C)
CH. 7 Output
CH. 4 Output
CH. 8 Output
CH. 5 Input – Ammonia (Zone B)
CH. 7 Input
CH. 6 Input – Ammonia (Zone C)
CH. 8 Input
CH. 1 Input – Control Te mp. (Zone A)
CH. 3 Input – Control Te mp. (Zone C)
CH. 2 Input – Control Te mp. (Zone B)
CH. 4 Input – Ammonia (Zone A)
CH. 9 Input
CH. 11 Input
CH. 10 Input
CH. 12 Input
CH. 13 Input
CH. 15 Input
CH. 14 Input
CH. 16 Input
+5 Vdc
+12 Vdc
+Tx/+Rx
D1 - +5Vdc Power
D9 - Active LED
D3 – Not used
D2 – Not used
D7 - COMM Rx LED
D8 - COMM Tx LE
LK1 - Install for 1 20 ohm terminator
P1
LK3
LK4
1
2
3
4
5
6 7 8
SW1
Open
U4
U7
U8
U6
U1
LK1
U15 U3
U2
P4A (Inputs)
(CH1) (CH2)
P4B (Inputs)
(CH3) (CH 4)
P5A (Inputs)
(CH5) (CH6)
P5B (Inputs)
(CH7) (CH 8)
P6A (Inputs)
(CH9) (CH 10)
P6B (Inputs)
(CH11) (CH12)
P7A (Inputs)
(CH13) (CH14)
P7B (Inputs)
(CH15) (CH16)
P9A (Inputs)
(CH17) (CH18)
P9B (Inputs)
(CH19) (CH20)
P10A (Inputs)
(CH21) (CH22)
P10B (Inputs)
(CH23) (CH24)
P11B (Output s)
(CH5) (CH6) (CH7) (CH8)
P11A (Output s)
(CH1) (CH2) (CH3) (CH4)
U10
U20
U19
U21
U11
U24
U22
U12
D5
24VDC
D1
5VDC
D9
Act
D3
CRx
D2
CTx
D7
Rx
D8
Tx
P12
U15
U16
U14
U17
U18
U13
U23
CH. 17 Input
CH. 19 Input
CH. 18 Input
CH. 20 Input
CH. 21 Input
CH. 23 Input
CH. 22 Input
CH. 24 Input
MAINTENANCE
090.610-M (MAY 2016) Page 39
ANALOG BOARD PICTORIAL
Install for Vib ration
on RS-485 Communicat ions
090.610-M (MAY 2016)
Quantum™ LX
Control Board
Comm. 4
(Zones
1-15)
Comm. 3
(Zones 16-30)
I/O Group 1
Zones 16, 17, 18
Digital Board
Digital Board
Analog Board
I/O Group 2
Zones 19, 20, 21
Digital Board
Digital Board
Analog Board
I/O Group 3
Zones 22, 23, 24
Digital Board
Digital Board
Analog Board
I/O Group 4
Zones 25, 26, 27
Digital Board
Digital Board
Analog Board
I/O Group 5
Zones 28, 29, 30
Digital Board
Digital Board
Analog Board
I/O Group 1
Zones 1, 2, 3
Digital Board
Digital Board
Analog Board
I/O Group 2
Zones 4, 5, 6
Digital Board
Digital Board
Analog Board
I/O Group 3
Zones 7, 8, 9
Digital Board
Digital Board
Analog Board
I/O Group 4
Zones 10, 11, 12
Digital Board
Digital Board
Analog Board
I/O Group 5
Zones 13, 14, 15
Digital Board
Digital Board
Analog Board
Page 40
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
ANALOG BOARD SETTINGS
COMMUNICATIONS
The following table is to be used when conguring the Quantum™ for external communications.
LK1
In 120 ohm long communications line termination.
Out * No termination.
* default setting
MISCELLANEOUS
In
LK2
Out * In
LK3
Out * In
LK4
Out *
* default setting
NOTE: Although LK2, 3 and 4 are not used, they must still be set for the default positions.
Not Used
Not Used
Not Used
DIPSWITCH SETTINGS
The following table is to be used to set the analog board addresses. Refer to and study the diagram at the bottom of this page
to determine the correct board conguration.
Comm. 4 of Quantum™ (Zones 1-15) Comm. 3 of Quantum™ (Zones 16-30)
I/O
Group
Analog
Board
#
SW1SW2SW3SW4SW5SW6SW7SW
8
Group
I/O
Analog
Board
#
SW1SW2SW3SW4SW5SW6SW7SW
8
1 1 Off Off Off Off Off Off Off Off 1 1 Off Off Off Off Off Off Off Off
2 2 On Off Off Off Off Off Off Off 2 2 On Off Off Off Off Off Off Off
3 3 Off On Off Off Off Off Off Off 3 3 Off On Off Off Off Off Off Off
4 4 On On Off Off Off Off Off Off 4 4 On On Off Off Off Off Off Off
5 5 Off Off On Off Off Off Off Off 5 5 Off Off On Off Off Off Off Off
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SECTION 7
SERVICE SCREENS
090.610-M (MAY 2016)
Page 41
090.610-M (MAY 2016) Page 42
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SERVICE SCREENS
SERVICE – Communications Log
DESCRIPTION: This screen allows the technician to view
the status of all communications ports.
The following user selectable buttons are provided:
[Show Comm1]
[Show Comm2]
[Show Comm3]
[Show Comm4]
This screen allows the technician to view all of the communications information that the Quantum™ LX is receiving and transmitting, one port at a time. Simply select the button at the upper right side of the screen that corresponds to the port that you wish to view. The selected
port name (in this case Comm4) will appear in the upper left side of the screen.
Each time a new command is sent or received, the screen will need to be refreshed by selecting the [Show CommX] button (where X is replaced with the comm port number).
This screen will display all data that is coming through the selected Communications (Comm) port. The top line of data is the most recent activity. At the left of each line, you should see whether the data is IN or OUT (Receive or Send), and the actual data (in Hexadecimal format). This information can be used to compare against the data being sent and received at the other end of the communications link, to verify proper operation.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SERVICE – Communications Loop-Back Test
090.610-M (MAY 2016)
Page 43
DESCRIPTION: This screen allows the user to test the integrity of each of the communications channels, by using a Loop-Back
cable. Refer to the Evaporator Communications Manual (090.610- CS) for specic information about this test.
090.610-M (MAY 2016) Page 44
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SERVICE – Diagnostics
DESCRIPTION: The Diagnostics screen has been provided as a way for the user to test the Ethernet connection.
Refer to the Evaporator Communications manual (090.610-CS) for further information on this screen.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SERVICE – Software Maintenance
090.610-M (MAY 2016)
Page 45
DESCRIPTION: This screen allows the technician to perform
system software maintenance. NOTE: Use caution when accessing this screen remotely with a web browser.
Perform the following steps to prepare the Quantum™ LX for software maintenance:
• Ensure that all setpoint values have been documented as a safety precaution. Install a USB device into the provided connection on the Quantum™.
With power ON, insert the USB device into the USB port. Ensure that the tabbed key of the drive connector is plugged in as shown in Figure 1 of this section.
Go to User Level 2. The default password is 20.
Press the [Menu] key.
Cursor down to Service… and press [Enter].
Cursor down to Software Maintenance and press the [Enter] key.
The following selections have been provided:
1) Save Setpoints - Use this option to save all setpoints and custom text to a USB device as a form of backup:
• Press [1] to Save Setpoints.
The program will read the USB device, and
the following dialog box will appear:
Any numerals that appear on the center line of this box will represent units that have already been saved (from 0 to 99). If no units have yet been saved, the center line will be blank.
• Enter a number on the keypad that corresponds to the unit number that you wish to save, and then press [Enter]. If the unit number has not been saved before, the
setpoints will be saved to a le on the USB
device (a progress bar will appear asking you to Please Wait… In the future, any time you try to write the setpoints to this number, you will be prompted with a message telling you that the set number already exists – do you wish to overwrite it? Answer by highlighting the Yes button, and pressing [Enter] if you wish to overwrite the values. If you enter a number that does not appear on the center line, no such warning will appear.
After the le has been written, the dialog
boxes will disappear, and you can either exit or continue with another function.
2) Full System Install - Use this option to install the program:
• Ensure that all setpoint values have been
documented as a safety precaution.
• Press [2] to do a Full System Install.
If a valid USB device with the operating system
loaded on it is plugged in, the software will be loaded. If however, there is no USB device installed, or the device does not contain the operating software, the following dialog box will appear:
090.610-M (MAY 2016)
QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 46
• If the above dialog box appears, you must insert a valid software upgrade USB device.
3) Restore Setpoints – Use this option to re-load previously saved setpoints and custom text to the Quantum™.
• Ensure that all setpoint values have been
documented as a safety precaution. Install the previously saved setpoint USB device into the provided connection on the Quantum™.
• Press [3] to Restore Setpoints.
• The software program will read the USB
device, and the following dialog box will appear:
Any numerals that appear on the center line of
this box will represent units that have already been saved (from 0 to 99). If no units have yet been saved, the center line will be blank and therefore there are no setpoints to restore.
• Enter a number on the keypad that
corresponds to the unit number that you wish to restore, and then press [Enter].
• A progress bar will appear asking you to
Please Wait…
After the le has been written or updated,
the dialog boxes will disappear, and you can either exit, or continue with another function.
4) Delete Setpoints – Use this option to delete the setpoints and custom text for a particular unit:
MAINTENANCE
• The software program will read the USB device, and the following dialog box will appear:
Any numerals that appear on the center line of this box will represent units that have already been saved (from 0 to 99). If no units have yet been saved, the center line will be blank, and therefore there are no setpoints to delete.
• Enter a number on the keypad that corresponds to the unit number that you wish to delete, highlight the Ok button, and then press [Enter]. You will be prompted with a new dialog box which will ask you OK to delete set number (0-99)?
Highlight the Yes button, and press [Enter]. The dialog box will be updated with a new message stating that Set number (0-99) has been deleted!
• Press [Enter] to return to the Software Maintenance menu.
5) Exit - Use this selection to leave this screen:
• While leaving the USB device plugged in, press [5] to Exit.
During the reboot of the Quantum™ LX, a message will appear that says, “A System
Update le has been detected on the mounted
USB device. Do you wish to perform this update?” Select [Yes], and a System Update will be performed.
• At the conclusion of the System Update, a message will appear that says, “The USB device can now be removed and power should be recycled.” Follow these instructions.
Setpoint Defaults When Performing A Quantum™ LX Software Upgrade
• Ensure that all setpoint values have been documented as a safety precaution. Install the previously saved setpoints USB device into the provided connection on the Quantum™.
Press the [4] button.
The term software upgrade refers to the whole procedure of Saving Setpoints, Full System Installs, and Restoring Setpoints when on the Software Maintenance screen. They get set to these default values even after a Restore Setpoints is performed, so the individual doing the upgrade must then set them manually to what they need to be if they are critical to the application.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
This drawing represents one version of the LX where
MAINTENANCE
USB Memory Stick Plug-in locations
090.610-M (MAY 2016) Page 47
This version of the LX has a
USB connector located on the
the USB stick plugs into the mother board with the
use of an adapter.
daughter board, no adapter is
required.
Q4 USB Location
Q5 USB Locations
090.610-M (MAY 2016) Page 48
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
MISCELLANEOUS MAINTENANCE SCREENS
About
DESCRIPTION: The About screen shows the Analog and
Digital boards that have been detected. If a board has lost communications, a shutdown will be issued. All outputs are turned off on a Digital Board that has lost communications. All inputs will get set to their minimum value range on an Analog Board that has lost communications. A loss of
communications to an analog board should result in sensor fault shutdown message that is associated with the sensors on that board. If the RX LED on the I/O board is blinking but the board was not detected on the About screen, or an I/O Comm failure occurs, check the address of the board.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SECTION 8
TROUBLESHOOTING
090.610-M (MAY 2016) Page 49
TROUBLESHOOTING A PROBLEM THAT APPEARS
UNEXPLAINABLE
When there is a problem that makes no sense due to unexplainable things happening, check the following:
Is the panel powered by an isolating power source such as a control transformer?
Is the panel powered from a lighting or utility panel?
Has the unit ever worked properly?
If the unit used to work properly, try to determine
when the problem rst showed up.
It is important to know if the problem occurs randomly, frequently, or all the time.
Check what the temperature is at the unit location. Is it very hot or very cold?
Make sure that a motor is not blowing exhaust air on the control panel.
If it just started to act up, then check if there was
recently a severe lightning storm, re, ood, or a
plant accident. If any of the following conditions are possible, then check for it:
Has any water, refrigerant, or oil leaked into the panel or conduit?
If it just started to act up, then check if anything was recently changed in the system (i.e. software or hardware.)
If it just started to act up, then check if any service was recently done to the unit or its electrical system?
If the Quantum™ is unexplainably shutting down, try disconnecting the communications cable to see if the problem goes away.
Check if the communications cable shields are tied to machine ground at only one location. For a PLC or Opto22 based system, the shield should normally be tied only at the PLC or Opto22 panel.
®
Check that you are using the Frick communications cable. See manual to match proper cable with type of communications (i.e., RS-422, RS-232, RS-485, or some other type of factory communication bus system.)
If this is an older plant, has the plant wiring been brought up to code?
recommended
Is power wiring mixed with control wiring?
Is power wiring mixed with sensor wiring?
• Is power wiring mixed with communications wiring?
• Ensure that pressure transducers are properly grounded. The two types of transducers you may have are as follows: an older type has an 8 to 10 inch 3-conductor pigtail coming out of the transducer. This type will have the attaching cable’s shield cut off and insulated at the transducer end. The shield is then tied to a panel ground terminal in the panel. The newer type has the cable as an integral part of the housing and has the shield crimped to the case at the transducer end. This type of transducer has the cable’s shield cut off and insulated in the control panel.
Ensure that temperature transducers are properly grounded. The temperature probes usually have two short wires coming out of the sensor, and are tied to a shielded cable at the thermal well head. The shield is insulated at the temperature probe and grounded at the panel end.
Check if one of the temperature probes has a signal wire shorted to machine ground. To do this,
rst pull the orange plug from the appropriate
channel of the Analog board and then use a DVM and check each white wire to machine ground and each black wire to machine ground.
Check that all inductive loads (i.e. Coils, Solenoids, or Relays, etc.) connected to the I/O output modules have surge suppressers across them, preferably at the devices and not at the panel end.
Make sure that you have a continuous ground back to the power source. The ground connection must be aluminum or copper. A conduit ground will not work.
Ensure that there is no AC wiring lying next to any printed circuit boards.
Unexplainable unit failures are usually indicative of noise due to wiring problems (i.e. incorrect earth grounds, mixed power and control wiring, unsuppressed coils, etc)
If the unit is unexplainably shutting down, check if the machine shares power with something else.
090.610-M (MAY 2016) Page 50
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
ERASING THE SYSTEM SETPOINTS
In the event it becomes necessary to erase the systems setpoints, use the following procedure:
1. Ensure that the existing setpoints are documented if possible.
2. Power the controller down.
3. Locate the processor board (located in the Quantum™ LX Evaporator Control Panel).
4. If the processor has the Q4 processor board, locate and temporarily remove LK11 (on the larger of the two boards).
5. Power the unit up.
6. Wait for one minute to allow the processor to fully boot.
7. Power the unit down.
8. Replace LK11 if removed for the Q4.
9. Power back up.
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
090.610-M (MAY 2016) Page 51
SECTION 9
EVAPORATOR CONTROL PANEL AND REMOTE PANEL
DRAWINGS
This table lists the numbers for the drawings that appear on the following pages. The drawings shown here is the latest revision as of the printing of this manual. These drawings appear here for reference purposes only, and are subject to change without notice. When installing, or servicing equipment, always refer to the actual drawings that are included with the control panel for the latest information.
Wiring Diagrams Page Drawing Number
Digital Inputs/Outputs 52 - 54 643D0015 Rev. E
Analog Inputs/Outputs 55 - 57 643D0015 Rev. E Communications Wiring Diagrams 58 N/A
090.610-M (MAY 2016) Page 52
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
WIRING DIAGRAMS
Digital Inputs/Outputs (Page 1 of 3)
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Digital Inputs/Outputs (Page 2 of 3)
090.610-M (MAY 2016)
Page 53
090.610-M (MAY 2016) Page 54
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Digital Inputs/Outputs (Page 3 of 3)
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Analog Inputs/Outputs (Page 1 of 3)
090.610-M (MAY 2016) Page 55
090.610-M (MAY 2016) Page 56
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Analog Inputs/Outputs (Page 2 of 3)
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
Analog Inputs/Outputs (Page 3 of 3)
090.610-M (MAY 2016)
Page 57
090.610-M (MAY 2016) Page 58
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
COMMUNICATIONS WIRING DIAGRAMS
TO CUSTOMER REMOTE COMPUTER/DCS
RS-485 COMMUNICATIONS
To Customer
Remote
Computer /
DCS System
To Customer
Remote
Computer /
DCS System
-RX/-TX
+RX/+TX
- Cable -
Belden #9841
#24 AWG or Equal
-RX
+RX
-TX
+TX
- Cable -
Belden #9841
#24 AWG or Equal
Q3 or Q4
COM-2 (TB2)
BLK
CLR
Q1 or Q2
COM-2 (P12)
BLK
1
CLR
2
3
4
5
6
EVAPORATOR #2
7
8
EVAPORATOR #1
TO CUSTOMER REMOTE COMPUTER/DCS
RS-422 COMMUNICATIONS
Q1 or Q2
COM-2 (P12)
BLK
GRN
BLK
RED
EVAPORATOR #1
BLK
1
GRN
2
BLK
3
4
RED
5
6
7
8
Q3 or Q4
COM-2 (TB2)
EVAPORATOR #2
Q3 or Q4
COM-2 (TB2)
BLK
1
CLR
2
3
4
1
BLK
2
CLR
3
4
Q5
COM-2 (P11)
1
2
3
4
-RX/-TX
+RX/+TX
5
EVAPORATOR #3
EVAPORATOR #4
Q3 or Q4
COM-2 (TB2)
BLK
1
GRN
2
BLK
3
RED
4
EVAPORATOR #3
1
BLK
2
GRN
3
BLK
RED
4
Q5
COM-2 (P11)
EVAPORATOR #4
1
-RX
2
+RX
-TX
3
4
+TX
5
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
SECTION 10
REPLACEMENT PARTS
090.610-M (MAY 2016) Page 59
090.610-M (MAY 2016) Page 60
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
QUANTUM™ LX EVAPORATOR REPLACEMENT PARTS (Page 1 of 2)
Evaporator Q5 Operator Interface Panel
Frick Number SAP Number Description
Circuit Breakers
639A0206H05 484047 5 Amp circuit breaker
Control Power
639A0185H10 483963 2-Pos. Selector Switch (Control Power) 639A0185H30 483966 Latch, 3 Across (Attaches contact block to switch mechanism)
Display
639A0261H01 484329 CCFT inverter 639B0117H01 670741 Display Harness 639C0132H01 484379 Display 639C0143H01 670593 Mounting plate (for Display, CPU and Interface board) 640A0032H02 569676 Plexiglas Fill-piece for display 639A0278H01 548266 Display adapter board (Bat wing) 639B0104H01 552141 Inverter cable
Flash Cards and Software
649A1112Gxx 901354 Program Flash Card (the xx indicates program version) 649A1063G99 485995 Quantum™ LX Setpoint Saver (USB Drive)
Harnesses
639D0218H01 850941 DC power and communications harness
639D0191H02 696514 Keypad and Communications cable kit
Keypads
640D0186H01 484621 Keypad/overlay with Frick
®
logo (Quantum™ LX)
Power Supplies
639B0115H02 642308 12 VDC power supply
Quantum™ Controllers
639C0141G01 686440 Q5 Board (Advantage) 639B0116H01 677556 Q5 Interface Communications Board
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
090.610-M (MAY 2016)
QUANTUM™ LX EVAPORATOR REPLACEMENT PARTS (Page 2 of 2)
Evaporator Remote Panels
Part Number Description
Analog Board
640C0057G01 Analog Board #1 (Replaces existing 32 channel board #1 only - no hardware) 640C0057G33 Analog Board #1 (Field Upgrade Kit – Includes 32 channel board #1, connectors & hardware.)
Circuit Breakers (for optional panel heater)
639A0206H03 3 Amp circuit breaker
Digital Boards
111Q0281061 Output Module, 24-280 volt AC 333Q0000116 Input Module, 120 volt AC 333Q0001326 Fuse, 5 amp, 250 V 640C0024G31 Digital Board #1 (Replaces existing board) 640C0024G32 Digital Board #2 (Replaces existing board)
Harnesses
639C0124H01 DC power 640B0059H01 AC power 649B0931H01 DC power and communications harness 649D5579H01 AC power and I/O 649D5622H01 AC I/O harness, 2nd Digital board 640B0039H01 Shunting plug (for troubleshooting only)
Page 61
Panel Heater (Optional)
333Q0001179 Heater, ex, 120 VAC, 150 W
Power Supplies
640B0060H01 DC Power Supply 639A0262H01 5 VDC Power Supply 639A0262H02 12 VDC Power Supply 639A0262H03 24 VDC Power Supply
HOA Modules
639C0123H01 HOA Assembly, Complete DIN Rail Mounted 649B0776H01 HOA Module (no labels) 333Q0001738 HOA Fuse, 2 Amp
090.610-M (MAY 2016) Page 62
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
NOTES
QUANTUM™ LX EVAPORATOR CONTROL PANEL
MAINTENANCE
NOTES
090.610-M (MAY 2016) Page 63
May 2016 Form Revisions
Page reformat throughout
Updated Frick Industrial Refrigeration logo throughout
Form 090.610 - M (2016-05)
Supersedes: 090.610 - M (2012-12)
Subject to change without notice
© 2016 Johnson Controls Inc. - ALL RIGHTS RESERVED
Published in USA • 05/16 • PDF
JOHNSON CONTROLS
100 CV Avenue Waynesboro, PA 17268-1206 USA Phone: 717-762-2121 • FAX: 717-762-8624
www.johnsoncontrols.com/frick
Loading...