Fortinet FortiGate-5140B User Manual

FortiGate-5140B
Chassis Guide
This FortiGate-5140B Chassis Guide describes FortiGate-5140B hardware features as well as how to install a FortiGate-5140B chassis.
The most recent versions of this and all FortiGate-5000 series documents are available from the FortiGate-5000 page of the Fortinet Technical Documentation web site (http://docs.fortinet.com).
FortiGate-5140B Chassis Guide
01-500-156415-20151104

Warnings and cautions

Warnings and cautions
Only trained and qualified personnel should be allowed to install or maintain FortiGate-5000 series equipment. Read and comply with all warnings, cautions and notices in this document.
• Risk of Explosion if Battery is replaced by an Incorrect Type. Dispose of Used Batteries According to the Instructions.
• Turning off all power switches may not turn off all power to the FortiGate-5000 series equipment. Some circuitry in the FortiGate-5000 series equipment may continue to operate even though all power switches are off.
• FortiGate-5000 equipment must be protected by a readily accessible disconnect device or circuit breaker that can be used for product power down emergencies.
• Many FortiGate-5000 components are hot swappable and can be installed or removed while the power is on. But some of the procedures in this document may require power to be turned off and completely disconnected. Follow all instructions in the procedures in this document that describe disconnecting FortiGate-5000 series equipment from power sources, telecommunications links and networks before installing, or removing FortiGate-5000 series components, or performing other maintenance tasks. Failure to follow the instructions in this document can result in personal injury or equipment damage.
• Install FortiGate-5000 series chassis at the lower positions of a rack to avoid making the rack top-heavy and unstable.
• Do not insert metal objects or tools into open chassis slots.
• Electrostatic discharge (ESD) can damage FortiGate-5000 series equipment. Only perform the procedures described in this document from an ESD workstation. If no such station is available, you can provide some ESD protection by wearing an anti-static wrist strap and attaching it to an available ESD connector such as the ESD sockets provided on FortiGate-5000 series chassis.
• Make sure all FortiGate-5000 series components have reliable grounding. Fortinet recommends direct connections to the building ground.
• If you install a FortiGate-5000 series component in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Make sure the operating ambient temperature does not exceed Fortinet’s maximum rated ambient temperature.
• Installing FortiGate-5000 series equipment in a rack should be such that the amount of airflow required for safe operation of the equipment is not compromised. See
“Cooling fans, cooling air flow, and minimum clearance” on page 25 for details.
• FortiGate-5000 series chassis should be installed by a qualified electrician.
• FortiGate-5000 series equipment shall be installed and connected to an electrical supply source in accordance with the applicable codes and regulations for the location in which it is installed. Particular attention shall be paid to use of correct wire type and size to comply with the applicable codes and regulations for the installation / location. Connection of the supply wiring to the terminal block on the equipment may be accomplished using Listed wire compression lugs, for example, Pressure Terminal Connector made by Ideal Industries Inc. or equivalent which is suitable for AWG-10. Particular attention shall be given to use of the appropriate compression tool specified by the compression lug manufacturer, if one is specified.
• FortiGate-5000 series equipment shall be located in a restricted access location where only crafts personnel are allowed access.
WARNING: The intra-building ports, Gigabit Ethernet, RJ-45 10/100/1000 Base-T Ethernet, and RS-232 Serial ports of any FortiGate, FortiSwitch, and FortiController 5000 Series Boards, including Shelf-Manager of the equipment or subassembly is suitable for connection to intrabuilding or unexposed wiring or cabling only. The intra­building port(s) of the equipment or subassembly MUST NOT be metallically connected to interfaces that connect to the OSP or its wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 6) and require isolation from the exposed OSP cabling. The addition of Primary Protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring.
• FortiGate-5000 series chassis shall be installed and connected to the common bonding network.
• FortiGate-5000 series chassis are suitable for installation in the Central Office and NEC.
• The battery returns of FortiGate-5000 series chassis shall be connected as DC-I.
• All bare grounding connection points to FortiGate-5000 series chassis shall be cleaned and coated with an anti-oxidant solution before connections are made.
• All surfaces on FortiGate-5000 series chassis that are un-plated shall be brought to a bright finish and treated with and anti-oxidant solution before connections is made.
• All non-conductive surfaces on FortiGate-5000 series chassis shall be removed from all threads and connection points to ensure electrical continuity.
• Unambiguous reference to service documentation for instructions for replacement of fuses replaceable only by service personnel.
• The FortiGate-5140B chassis is capable of operating -40 VDC to -60 VDC at a maximum current level 100 A.
Caution: Double pole fusing.
Warnings and cautions
FortiGate-5140B

Contents

Warnings and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
FortiGate-5140B chassis 9
Chassis Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
FortiGate-5140B front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
FortiGate-5140B chassis back panel. . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chassis hardware information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Shipping components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Supported FortiGate, FortiSwitch and FortiController ATCA boards . . . . . . . 13
Power requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Physical description of the FortiGate-5140B chassis . . . . . . . . . . . . . . . 14
FortiGate-5140B shelf managers. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Using the shelf manager CLI . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Shelf Manager fan and power control . . . . . . . . . . . . . . . . . . . . . . . 16
FortiGate-5140B shelf alarm module . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Shelf alarm panel telco alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Air filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cooling fans, cooling air flow, and minimum clearance . . . . . . . . . . . . . . . . 19
Power connection and configuration 21
FortiGate-5140B chassis power level requirements . . . . . . . . . . . . . . . . . . 21
Connecting the FortiGate-5140B chassis to DC power and ground . . . . . . . . . . 22
Connecting a FortiGate-5140B PEM to DC power. . . . . . . . . . . . . . . . . . . 23
Connecting the FortiGate-5140B chassis to ground . . . . . . . . . . . . . . . . . . 25
Supplying power using the FortiGate-5053B power supply shelf and PSU-5000B power
supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Selecting the power supplies and power supply shelves that you need for your
FortiGate-5140B chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Connecting a FortiGate-5140B chassis to the FortiGate-5053B power supply shelf .
28
Turning on FortiGate-5140B chassis power . . . . . . . . . . . . . . . . . . . . . . 30
FortiGate-5140B hardware procedures 31
Mounting the FortiGate-5140B chassis . . . . . . . . . . . . . . . . . . . . . . . . 31
Air flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Inserting 5000 series boards and RTM modules into a FortiGate-5140B chassis . . . 32
Using FortiController-5103B boards for session-aware load balancing . . . . . . . . 32
Using FortiSwitch-5003B boards for backplane communication . . . . . . . . . . . 33
Using FortiSwitch-5203B boards for content clustering . . . . . . . . . . . . . . . . 33
FortiGate-5140B Chassis Guide 01-500-156415-20151104 5
http://docs.fortinet.com/
Contents
Using the shelf manager CLI 34
Connecting to the shelf manager CLI using a serial port and setting up passwords . 35
Connecting to the shelf manager CLI . . . . . . . . . . . . . . . . . . . . . . . 35
Changing the shelf manager root account password . . . . . . . . . . . . . . . 36
Resetting a lost shelf manager password . . . . . . . . . . . . . . . . . . . . . 36
The shelf manager command line interface agent (CLIA) . . . . . . . . . . . . . 37
Using CLIA interactive mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
IPMB addresses, logical and physical slot numbers, and FRU ids . . . . . . . . . . 38
Basic shelf manager CLI Commands . . . . . . . . . . . . . . . . . . . . . . . . . 39
Change IP address of the primary Shelf Manager . . . . . . . . . . . . . . . . . 39
Display the shelf manager firmware version . . . . . . . . . . . . . . . . . . . . 39
List all FRUs in the chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
List all sensors on a FRU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
List only sensors that are outside of established thresholds . . . . . . . . . . . 39
Display sensor data for a FRU . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Display the FRU information for a FRU . . . . . . . . . . . . . . . . . . . . . . 40
Change the speed for a fan tray . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Display the contents of the system event log (sel) . . . . . . . . . . . . . . . . . 40
Clear the system event log (sel) . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Changing the shelf manager IP address and default gateway . . . . . . . . . . . . . 40
Sensor types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Shelf manager CLI commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
activate/deactivate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
clia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
exit/quit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
fru . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
fruinfo. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
getlanconfig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
getthreshold/threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
minfanlevel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
sel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
sensordata . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
setthreshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
shmstatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
showunhealthy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
switchover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
terminate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
user. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Generating SNMP traps for shelf manager system events. . . . . . . . . . . . . . . 63
SNMP trap details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
FortiGate-5140B Chassis Guide
6 01-500-156415-20151104
http://docs.fortinet.com/
Contents
Removing and inserting a fan tray . . . . . . . . . . . . . . . . . . . . . . . . . 69
Setting up SNMP polling for the shelf manager . . . . . . . . . . . . . . . . . . . . 70
Using the shelf manager system event log (SEL). . . . . . . . . . . . . . . . . . . . 71
Before you begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Chassis Design Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Alarm LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Reading the SEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Clearing SEL logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Example IPMC log output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Example FRU log output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Example sensor log output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Sample sections of SEL Output . . . . . . . . . . . . . . . . . . . . . . . . . . 85
For more information 87
Training Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Technical Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Comments on Fortinet technical documentation . . . . . . . . . . . . . . . . . . . 87
Customer service and support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Fortinet products End User License Agreement . . . . . . . . . . . . . . . . . . . . 87
FortiGate-5140B Chassis Guide 01-500-156415-20151104 7
http://docs.fortinet.com/
Contents
FortiGate-5140B Chassis Guide
8 01-500-156415-20151104
http://docs.fortinet.com/
FortiGate-5140B

FortiGate-5140B chassis

This chapter describes the FortiGate-5140B chassis and includes the following sections:
Chassis Overview
FortiGate-5140B front panel
FortiGate-5140B chassis back panel
Chassis hardware information
FortiGate-5140B shelf managers
FortiGate-5140B shelf alarm module
Air filter
Cooling fans, cooling air flow, and minimum clearance

Chassis Overview

You can install up to 14 FortiGate-5000 series boards in the 14 slots of the FortiGate-5140B ATCA chassis. The FortiGate-5140B is a 13U 19-inch rackmount ATCA chassis that contains two redundant hot swappable DC power entry Modules (PEMs). The PEMs connect to -48V DC power and supply 300 W to each chassis slot. The FortiGate-5140B chassis also includes four hot swappable front pluggable cooling fan trays that provide 300W of cooling power per slot and a front replaceable air filter with redundant pressure sensor. If all 14 slots contain FortiGate-5001B boards, the FortiGate-5140B chassis provides a total of 112 FortiGate 10-gigabit ethernet interfaces. If all 14 slots contain FortiGate-5101C boards, the FortiGate-5140B chassis provides a total of 56 FortiGate 10-gigabit ethernet interfaces. If all 14 slots contain FortiGate-5001C boards, the FortiGate-5140B chassis provides a total of 28 FortiGate 10-gigabit ethernet interfaces. If all 14 slots contain FortiGate-5001D boards, the FortiGate-5140B chassis provides a total of 28 40-gigabit ethernet interfaces.
You can also install FortiSwitch-5003B boards in FortiGate-5140B chassis slots 1 and 2 to provide base backplane communications using the dual star 1-gigabit base backplane interface. Base backplane communications can be used for HA heartbeat and other control communications and for data communications. FortiSwitch-5003B boards also provide fabric backplane communication using the FortiGate-5140B fabric backplane channels. The fabric backplane is a dual-star 10-Gigabit switch fabric.
For both base and fabric backplane communications you can install a single FortiSwitch-5003B board in slot 1 and add a second board to slot 2 for redundancy. These boards provide backplane switching for data communication between FortiGate­5000 series boards and for HA clustering.
The FortiGate-5140B chassis supports the following load balancing solutions:
• FortiController-5103B boards can be installed in slots 1 and 2 to provide session-aware load balancing (SLBC) for FortiGate-5001B, 5101C, or 5001C boards in the chassis.
• FortiSwitch-5003B boards can be installed in slots 1 and 2 to form a Enhanced Load Balancing Cluster (ELBC) to load balance traffic to multiple FortiGate-5001B, 5101C or 5001C boards installed in the chassis
• FortiSwitch-5203B boards can be installed in slots 1 and 2 to support content clustering to load balance traffic to multiple FortiGate-5001B boards installed in the chassis.
FortiGate-5140B Chassis Guide 01-500-156415-20151104 9
http://docs.fortinet.com/
FortiGate-5140B front panel FortiGate-5140B chassis
FortiGate-5001B
boards
slots 4, 6, 8, 10,
12, and 14
Cooling
fans (behind the cooling fan
bay cover)
FortiGate-5001B
boards
slots 3, 5, 7, 9,
11, and 13
FortiSwitch-5003B
boards
slots 1 and 2
ES D
socket
Slot
numbers
HandleHandle
Air lter
(behind the
air intake
bezel)
• FortiSwitch-5902D boards can be installed in slots 1 and 2 to support content clustering to load balance traffic to multiple FortiGate-5001D boards installed in the chassis.
Finally, you can add other Fortinet 5000 series boards to a FortiGate-5140B chassis, including the 5000 series FortiMail and FortiManager boards.
Some of the boards installed in a FortiGate-5140B chassis can be operating in a FortiGate HA cluster and some can be operating as standalone FortiGate units. You can also operate multiple HA clusters and standalone FortiGate units in a single FortiGate-5140B chassis.
The FortiGate-5140B chassis requires -48V DC power. If DC power is not available you can install a FortiGate-5053B power supply shelf and PSU-5000B power supplies (purchased separately).

FortiGate-5140B front panel

Figure 1 shows the front of a FortiGate-5140B chassis. Two FortiSwitch-5003B boards
are installed in slots 1 and 2 and 12 FortiGate-5001B boards are installed in slots 3 to 14.
Figure 1: FortiGate-5140B front panel with FortiGate-5001B and FortiSwitch-5003B
boards installed (cable tray not shown)
The following components are visible on the front of the FortiGate-5140B chassis:
FortiGate-5140B Chassis Guide
10 01-500-156415-20151104
http://docs.fortinet.com/
FortiGate-5140B chassis FortiGate-5140B front panel
• The location of the four hot-swappable front replaceable cooling fans (behind the cooling fan bay cover)
• The location of the front-replaceable air filter (behind the air intake bezel).
• The Electrostatic discharge (ESD) socket, used for connecting an ESD wrist band when working with the chassis
• Chassis handles.
Do not operate the FortiGate-5140B chassis with open slots on the front panel. For optimum cooling performance and safety, the chassis slots must contain a FortiGate-5000 series board or an air baffle slot filler. For the same reason, all cooling fan trays and the air filter should be installed while operating the chassis. As well both PEMs must be installed in the back of the chassis.
Figure 2: FortiGate-5140B chassis back panel (cable tray not shown)
RTM
slot numbers
RTM
air bafe
slot covers
ES D
socket
Chassis
ground
connector
(green)
RTN (red)
-48/-60 VDC nom (black)
RTN
(red)
-48/-60 VDC nom (black)
Shelf
Power
Entry Module B
Power
Entry Module A
Managers
Shelf Alarm
Modules
FortiGate-5140B Chassis Guide 01-500-156415-20151104 11
http://docs.fortinet.com/
FortiGate-5140B chassis back panel FortiGate-5140B chassis

FortiGate-5140B chassis back panel

Figure 2 shows the back of a FortiGate-5140B chassis.
The FortiGate-5140B chassis back panel includes two redundant -48V to - 60 VDC power entry modules (PEMs). Fortinet ships the FortiGate-5140B chassis with both installed. The PEMs provide redundant DC power connections for the FortiGate-5140B chassis and distribute DC power to all chassis slots and components.
If you require redundant power you should connect both PEMs to DC power. If redundant power is not required, you can connect one of them. Each PEM includes two power terminals, one for connecting to -48V/-60 VDC (labelled -) and one for connecting to RTN (labelled +). To connect power to the PEMs see, “Power connection and configuration”
on page 21.
The back panel also contains 14 RTM slots numbered to correspond to the front panel slots. The RTM slots are available for FortiGate-5000 RTM modules. When the chassis is shipped, these slots are covered by RTM air baffle slot covers.
The FortiGate-5140B Shelf Managers and the Shelf Alarm Modules (SAMs) are also visible. The factory installed primary shelf manager provides power allocation, cooling, alarms, and shelf status for the FortiGate-5140B chassis. The factory installed primary and secondary Shelf Alarm Modules display alarms and provide telco alarm interfaces. You can also install a secondary shelf manager as a backup for the primary one. For more information about these components, see “FortiGate-5140B shelf managers” on page 14 and “FortiGate-5140B shelf alarm module” on page 16.
The back panel includes the FortiGate-5140B chassis ground connector which must be connected to ground. The chassis also includes an ESD socket on the back panel.

Chassis hardware information

This section introduces FortiGate-5140B hardware components and accessories including power requirements and FortiGate-5000 series boards that can be installed in the chassis.

Shipping components

The FortiGate-5140B chassis ships pre-assembled with the following components (see
Figure 1 on page 10 and Figure 2 on page 11 for the location of the components in the
chassis):
• The 13U FortiGate-5140B chassis
• One shelf manager installed in the back of the chassis
• Two shelf alarm modules (SAMs) installed in the back of the chassis
• Two Power Entry Modules (PEMs) installed in the back of the chassis
• One air filter installed behind the air intake bezel at the bottom of the chassis
• Four cooling fans installed in the fan bays at the top of the chassis
• 13 front panel air baffle slot covers installed in the front panel slots
• 14 RTM air baffle slot covers installed in the RTM slots
• Four 3-ft. power cables with AWG-6 stranded wires and double-hole lugs: Black for
-48VDC and red for RTN. These cables should only be used to connect the FortiGate-5140B PEMs to a FortiGate-5053B power convertor shelf if purchased with your FortiGate-5140B chassis
FortiGate-5140B Chassis Guide
12 01-500-156415-20151104
http://docs.fortinet.com/
FortiGate-5140B chassis Chassis hardware information

Supported FortiGate, FortiSwitch and FortiController ATCA boards

You can install the following FortiGate-5000 series boards in a FortiGate-5140B chassis to provide security services. This includes the following:
ATCA board Interfaces Function
FortiGate-5001B Front Panel: 10 Gbps
Fabric: 10 Gbps
FortiGate-5001C Front Panel: 10 Gbps
Fabric: 10 Gbps
FortiGate-5101C Front Panel: 10 Gbps
Fabric: 10 Gbps
FortiGate-5001D Front Panel: 10 Gbps
Fabric: 40 Gbps
FortiSwitch-5203B Front Panel: 10 Gbps
Fabric: 10 Gbps
FortiController-5902B Front Panel: 10 Gbps
Fabric: 10 Gbps
FortiSwitch-5003B Front Panel: 10 Gbps
Fabric: 10 Gbps
FortiController-5103B Front Panel: 10 Gbps
Fabric: 10 Gbps
*Approximate values, see product datasheets for actual numbers.
FortiOS network security
FortiOS network security
FortiOS network security
FortiOS network security
Content clustering with FortiGate-5001Bs
Content clustering with FortiGate-5001Ds
Backplane switching, FGCP HA, and extended load balancing (ELBC)
Session-aware load balancing
Power Used (WDC)*
Max: 225 Ave: 187
Max: 225 Ave: 187
Max: 226 Ave: 189
Max: 225 Ave: 187
Max: 250 Ave: 210
Max: 270 Ave: 223
Max: 180 Ave: 150
Max: 255
Ave: 213
Heat Dissipation (BTU/hr)*
768
768
774
768
853
919
614
754
The following older Fortinet ATCA boards can also be installed in the FortiGate-5140B chassis:
• FortiGate-5001A
• FortiCarrier-5001A
• FortiGate-5005FA2
• FortiGate-5001FA2
• FortiGate-5001
• FortiGate RTM-XB2
• FortiGate RTM-XD2
• FortiSwitch-5003A
• FortiSwitch-5003
• FortiMail-5001A and 5002
• FortiManager-5001A

Power requirements

The FortiGate-5140B chassis is designed to be installed in a data center or similar location that has available -48VDC power fed from a 100A listed circuit breaker (also called battery power or main DC power). Fortinet expects that most FortiGate-5140B customers will be installing their chassis in a data center or similar location that is already equipped with a -48VDC power system fed from a 100A listed circuit breaker that provides power to existing networking or telecom equipment. The FortiGate-5140B chassis is designed to be connected directly to this DC power system.
FortiGate-5140B Chassis Guide 01-500-156415-20151104 13
http://docs.fortinet.com/
FortiGate-5140B shelf managers FortiGate-5140B chassis
If DC power is not available you can use one or more FortiGate-5053B power converter shelves equipped with PSU-5000B power supplies to convert AC to DC to supply DC power to the FortiGate-5140B chassis from an AC source.

Physical description of the FortiGate-5140B chassis

The FortiGate-5140B chassis is a 13U chassis that can be installed in a standard 19-inch rack. Ta bl e 1 describes the physical characteristics of the FortiGate-5140B chassis.
Table 1: FortiGate-5140B chassis physical description
Dimensions 22.63 x 19 x 22.6 in. (57.5 x 48.3 x 57.4 cm) (H x W x D)
Shipping weight completely assembled with packaging
Chassis weight completely assembled with shelf manager and air baffles (13 front and 14 RTM)
PEM DC terminal torque No more than 3.8 Nm (33.62 lbf.in)
Operating environment
110 lbs (50 kg)
84 lbs (38 kg)
Temperature (long term): 41 to 104°F (+5 to 40°C)
Temperature (short term): 23 to 131°F (-5 to 45°C)
Power consumption
Power input 2x redundant -48 Vdc/-60Vdc, 100A-84A per PEM
Overcurrent Protection
Cooling Capacity
Protected Earth Test EN60950-1, test current 25 A, resistance <100 mOhm
Hipot Test EN60950-1, 1000 V

FortiGate-5140B shelf managers

The FortiGate-5140B chassis includes one or two redundant hot-swappable shelf managers, located in the dedicated shelf manager slots at the bottom right side of the back panel. The primary shelf manager is installed on the left the secondary shelf manager (if present) is installed on the right. The secondary shelf manager is optional.
Relative humidity: 5 to 85% (Non-condensing)
Maximum: 530 W (Power consumed by an empty chassis with four fans, one shelf manager, two shelf alarm modules and two PEMs installed and operating with the fans running at full speed.)
Each PEM includes 5 power channels. Each channel includes its own 100 A fuse.
Front Boards: 300 W per board
RTM: 35 W per module
FortiGate-5140B Chassis Guide
14 01-500-156415-20151104
http://docs.fortinet.com/
FortiGate-5140B chassis FortiGate-5140B shelf managers
Retention
Screw
Ethernet CH0 network
activity LEDs
Ethernet CH1 network
activity LEDs
RS-232
Serial
CH0 and 1 100base-T
Ethernet
Active (Green)Hot Swap
Actuator
Ethernet
Channel Selector
Retention
Screw
Out of Service (Red)
Hot Swap (Blue)
The shelf managers support redundant operation with automatic switchover. If both shelf managers are operating normally, one acts as the active shelf manager and the other as the standby. Usually the primary shelf manager would be the active shelf manager and the secondary shelf manager would be the standby. The shelf managers monitor each other and either can trigger a switchover if necessary. The active shelf manager performs all shelf manager functions. If the active shelf manager fails or is removed, the standby shelf manager takes over all shelf manager functions. If one shelf manager fails or is removed the other will operate independently and the chassis will continue to function normally.
The shelf managers control chassis power allocation, monitor chassis operating parameters, monitor and control chassis cooling, and can signal alarms if the chassis encounters problems. All FortiGate-5000 boards installed in the chassis communicate with the shelf managers.
The shelf managers are factory installed. In most cases users do not have to install or configure the shelf managers.
Each shelf manager has two ethernet interfaces (CH0 and CH1). Both channels connect to the chassis backplane.
• When the Ethernet channel selector button is pushed in (recessed) CH0 connects to the backplane.
• When the Ethernet channel selector button is pulled out you can use the front panel Ethernet connector to connect to CH0.
Each shelf manager also has an RS-232 serial port for connecting to the shelf manager console CLI.
The shelf managers detect alarm conditions and communicate alarm signals to the FortiGate-5140B shelf alarm module.
The shelf managers are hot swappable. You remove a shelf manager by loosening the retention screw that positions the hot swap actuator. This disengages the hot swap switch and puts the shelf manager into hot swap mode. The hot swap LED starts blinking blue. When the hot swap LED turns solid blue you can completely loosen both retention screws and remove the shelf manager from the chassis.
Figure 3: FortiGate-5140B shelf manager front panel
Table 2: FortiGate-5140B shelf manager LEDs
LED State Description
Solid
Indicates that this is the active shelf manager.
Green
FortiGate-5140B Chassis Guide 01-500-156415-20151104 15
http://docs.fortinet.com/
ACT (Active)
Blinking Green
Indicates that this is the standby shelf manager.
FortiGate-5140B shelf alarm module FortiGate-5140B chassis
Table 2: FortiGate-5140B shelf manager LEDs
LED State Description
OOS (Out of Service)
H/S (Hot Swap)
10/100 (CH0 and CH1)
L/A (Link/Activity for CH0 and CH1)
Off Normal Operation.
Red Shelf manager software reboot or other failure.
Off Normal operation.
Blinking Blue
Blue The shelf manager can be removed from the chassis.
Amber 10/100 Mbit link for Ethernet CH0 or CH1.
Green Link/activity for Ethernet CH0 or CH1.

Using the shelf manager CLI

You can use the shelf manager command line interface (CLI) to communicate with the intelligent management controllers of the chassis, with boards in the chassis, and with the shelf manager itself. The CLI is an IPMI-based set of commands that can be accessed directly or through a higher-level management application or a script. Using the CLI, you can access information about the current state of the chassis including current board population, current sensor values, threshold settings, recent events, and overall chassis health.
To get started using the shelf manager CLI, see “Using the shelf manager CLI” on
page 34.
The shelf manager is shutting down in preparation for being removed from the chassis.

Shelf Manager fan and power control

The FortiGate-5140B shelf managers monitor the internal temperature of the FortiGate-5140B chassis and adjust the operating speed of the cooling fans as required.
When the chassis is first powered on all cooling fans run at full speed. Once the shelf manager is up and running, the shelf manager reduces cooling fan speeds to maintain an optimum temperature in the chassis. If shelf managers are not installed or not operating correctly the FortiGate-5140B chassis cooling fans always operate at full speed.

FortiGate-5140B shelf alarm module

The FortiGate-5140B chassis includes two redundant hot-swappable shelf alarm modules (SAMs) each of which provide LED indicators of FortiGate-5140B alarms, a telco alarm connector, and an alarm LED reset buttons. The LED alarm indicators include critical, major, and minor alarms.
FortiGate-5140B Chassis Guide
16 01-500-156415-20151104
http://docs.fortinet.com/
FortiGate-5140B chassis FortiGate-5140B shelf alarm module
Retention
Screw
Reset
Retention
Screw
Telco Alarm
Interface
Out of Service (Red)
Active (Green)
Hot Swap (Blue)
Power OK (Green) Major Alarm (Red)
Minor Alarm (Amber)
Critical Alarm (Red)
The shelf alarm modules support redundant operation with automatic switchover. If both shelf alarm modules are operating normally, one acts as the active shelf alarm module and the other as the standby. Usually the primary shelf alarm module would be active and the secondary module would be the standby. The shelf alarm modules monitor each other and either can trigger a switchover if necessary. By default the shelf alarm module on the left is the active one. The active shelf alarm module performs all shelf alarm functions. If the active shelf alarm module fails or is removed, the standby shelf alarm module takes over all functions.
The Telco Alarm Interface is a standard DB-15 male Telco Form-c connector. The external dry relay Telco alarm interface (48VDC) provides Telco form-c relay connections for minor, major and critical power faults. The cable required to connect to the alarm interface is not supplied by Fortinet. To monitor alarms you should connect to the telco alarm interface of the active shelf alarm panel, which by default is the one on the left.
Figure 4: FortiGate-5140B shelf alarm module front panel
Table 3: FortiGate-5140B shelf alarm module LEDs
LED State Description
Off Normal operation.
OOS (Out of Service)
Blinking Red
Lost connection to the shelf manager or no IPBM bus.
Red Incorrect hardware address or FRU data corruption.
ACT
Green Normal operation.
(Active)
Off Normal operation.
H/S (Hot Swap)
Blinking Blue
The shelf manager is shutting down in preparation for being removed from the chassis.
Blue The shelf alarm module can be removed from the chassis.
POK
Green Input power to the chassis is within limits.
(Power OK)
MJR
Red Major alarm detected in chassis.
(Major Alarm)
MNR
Amber Minor alarm detected in chassis.
(Minor Alarm)
CRIT
Red Critical alarm detected in chassis.
(Major Alarm)
FortiGate-5140B Chassis Guide 01-500-156415-20151104 17
http://docs.fortinet.com/
FortiGate-5140B shelf alarm module FortiGate-5140B chassis
Eth port0
Eth port1
Eth port0
Eth port1
ShMC port1
ShMC port2
ShMC port1
ShMC port2
Base Hub A
ShMC
IPMC IPMC IPMC IPMC
ShMC
Shelf Manager (active)
Shelf Manager (backup)
Base Hub B ATCA board
Redundant IPMB-0 on Backplane
ATCA board
Figure 5 shows the connections between the primary and secondary shelf managers and
the shelf alarm panel.
Figure 5: Ethernet connections between shelf managers and the base backplane
interfaces

Shelf alarm panel telco alarms

The shelf alarm panel telco alarm interface relay circuits are capable of carrying 60 VDC or 1 A with a max. rating of 30 VA. The shelf alarm panel accepts timed pulse inputs for clearing minor and major alarm states. Reset is accomplished by asserting a voltage
18 01-500-156415-20151104
differential from 3.3 V to 48 V for between 200 and 300 ms. The acceptance voltage range is from 0 to 48 VDC continuous (handles up to 60 VDC at a 50% duty cycle). The current drawn by a reset input does not exceed 12 mA.
The alarm LED reset button activates the alarm cutoff (ACO) state for major, minor, and user-defined alarms. You cannot reset critical alarms with the alarm LED reset button.
When the ACO state is activated, active alarm LEDs blink and all of the alarm relays are deactivated. The alarm reset button activates the ACO state but does not clear the alarm completely.
Figure 6: The telco alarm connector (DB-15 male)
FortiGate-5140B Chassis Guide
http://docs.fortinet.com/
FortiGate-5140B chassis Air filter
Table 4: Telco alarm connector pin assignment
Pin Description
1 MinorReset+
2 MinorReset-
3MajorReset+
4MajorReset-
5 CriticalAlarm - NO
6Critical Alarm NC
7Critical Alarm COM
8 Minor Alarm NO
9 Minor Alarm NCt
10 Minor Alarm COM
11 Major Alarm NO
12 Major Alarm NC
13 Major Alarm COM
14 Power NO
15 Power COM

Air filter

The FortiGate-5140B chassis includes a front replaceable air filter that removes dust from intake air and provides static pressure to achieve uniform airflow. The filter must be installed for the chassis to operate normally. If the air filter is not locked into place the redundant air filter presence sensors cause an alarm.
Air filters should be inspected regularly. If dirty or damaged, the filter should be disposed of and replaced. The air filter can be fragile and should be handled carefully.
To service the air filter you must remove the air intake bezel at the bottom of the front of the chassis. See Figure 1 on page 10 for the location of the air intake bezel and air filter. The bezel is held in place by four torq screws which must be loosened before the bezel can be removed. The air filter can be removed using the lower flange as a handle. Gently push the filter and tilt it down to remove it.
Care should be taken when inserting an new air filter to prevent damage to the sensors. To insert a new filter, slide it along the guide rails at each side of the shelf until the filter contacts springs at the back of the chassis. Then tilt the filter up until it locks into place under the card cage. Pull the filter forward to make sure it is locked into place.

Cooling fans, cooling air flow, and minimum clearance

The FortiGate-5140B chassis contains four identical hot-swappable cooling fans installed in the fan cabinet at the top of the chassis. See Figure 1 on page 10 for the location of the cooling fans. Two fans are installed at the top of the cabinet and two at the bottom. The fans at the bottom of the cabinet are not directly under the fans at the top, but are located further towards the back of the cabinet. To be able to reach the bottom fans long handles are attached to them so that you don’t have to insert your hand into the chassis to access them.
FortiGate-5140B Chassis Guide 01-500-156415-20151104 19
http://docs.fortinet.com/
Cooling fans, cooling air flow, and minimum clearance FortiGate-5140B chassis
100 mm
600 mm
600 mmCool air
Intake
Warm air
Exhaust
60 mm
40 mm
Front
Back
Air Filter
(normal operation)
Air Filter
(Tilted down to
remove or insert)
Fan
Fan
To service the fans, open the latches on either side of the fan cabinet and open the cover by pulling it down. Access the top fans by pulling them out. Access the bottom fans by pulling them out by their handles.
You do not need to press a hot swap switch to remove a fan. Just pull it out of the fan cabinet. The shelf manager regulates the fan speed by adjusting the DC voltage supplied to the fan trays.
Table 5: FortiGate-5140B fan tray LEDs
LED Description
HS (Hot Swap) Normally off. Blinking blue indicates that the fan is starting up.
OOS (Out of Service)
Normally off. Blinking red indicates the fan is out of service and should be replaced.
Figure 7: Cooling air flow and required minimum air flow clearance
When installing the chassis, make sure there is enough clearance for effective cooling air flow. See Figure 7 on page 20 for the minimum clearance requirements. The diagram also shows the cooling air flow through the chassis and the location of the air filter and cooling fans. Make sure the cooling air intake and warm air exhaust openings are not blocked by cables or rack construction because this could result in cooling performance reduction and possible overheating and component damage.
20 01-500-156415-20151104
FortiGate-5140B Chassis Guide
http://docs.fortinet.com/
FortiGate-5140B

Power connection and configuration

This chapter describes how to connect DC power to a FortiGate-5140B chassis.
The FortiGate-5140B chassis is designed to be installed in a data center or similar location that has available -48VDC power fed from a 100A listed circuit breaker (also called battery power or main DC power). Fortinet expects that most FortiGate-5140B customers will be installing their chassis in a data center or similar location that is already equipped with a -48VDC power system fed from a 100A listed circuit breaker that provides power to existing networking or telecom equipment. The FortiGate-5140B chassis is designed to be connected directly to this DC power system.
If DC power is not available at the location in which the FortiGate-5140B chassis is to be installed you can use the FortiGate-5053B power converter shelf to convert AC to DC to supply DC power to the FortiGate-5140B chassis.
Fortinet supplies four 3-ft. power cables with AWG-6 stranded wires and double-hole lugs: Black for -48VDC and red for RTN. These cables should only be used to connect the FortiGate-5140B PEMs to a FortiGate-5053B power convertor shelf if purchased with your FortiGate-5140B chassis. The double-hole lugs to be connected to the FortiGate-5140B PEMs include rubber boots that should be installed before energizing the power system. If the power cable length needs to be longer than 3 ft., higher gauge wires should be considered.
If you are connecting your chassis to a local DC power source, use cables that meet your local wiring codes. To connect the wires to the FortiGate-5140B PEMs use 3/4-inch double-hole lugs with insulating boot suitable the DC cables used, such as Thomas & Betts PN 256-30695-1225.
Green AWG-6 wires are recommended for ground connections (not supplied with the chassis).
This chapter describes:
FortiGate-5140B chassis power level requirements
Connecting the FortiGate-5140B chassis to DC power and ground
Connecting a FortiGate-5140B PEM to DC power
Connecting the FortiGate-5140B chassis to ground
Supplying power using the FortiGate-5053B power supply shelf and PSU-5000B
power supplies
Turning on FortiGate-5140B chassis power

FortiGate-5140B chassis power level requirements

This section provides some basic information for determining the power requirements of your FortiGate-5140B chassis. This section provides guidelines only. Actual requirements may vary depending on your installation requirements. Contact Fortinet Support if you need more information.
FortiGate-5140B Chassis Guide 01-500-156415-20151104 21
http://docs.fortinet.com/
Connecting the FortiGate-5140B chassis to DC power and ground Power connection and configuration
The base FortiGate-5140B chassis (empty, with four fans, one shelf manager, two shelf alarm modules and two PEMs installed and operating with the fans running at full speed) requires a maximum of 530 W. Each chassis slot can supply up to 300 W. You can use these numbers to estimate the power requirement for a chassis configuration.

Example: power for a chassis with 5 boards

For example, the power requirement for a FortiGate-5140B chassis with FortiGate, FortiSwitch, or FortiController boards in five slots would be:
530W + (300W * 5) = 2030W

Example: power for a fully-loaded chassis (14 boards)

The power requirement for a fully loaded FortiGate-5140B chassis with boards in all 14 slots would be:
530W + (300W * 14) = 4730W

Connecting the FortiGate-5140B chassis to DC power and ground

Connect the FortiGate-5140B chassis to DC power using the redundant -48V to - 60 VDC power entry modules (PEMs) at the bottom of the chassis back panel. The specified voltage range of the PEMs is -40 VDC to -72 VDC. The chassis ships with both PEMs installed. The PEMs provide redundant DC power connections for the FortiGate-5140B chassis and distribute DC power to all chassis slots and components.
The PEM includes a Reverse Voltage LED that lights if you have reversed the polarity when connecting power.
Each FortiGate-5140B PEM includes four -48V/-60 VDC (labeled as - and connected together internally) and four return connectors (labeled as + and connected together internally). Each PEM supplies 5 power channels. Each channel includes a separate 30A fuse to power a group of 3 to 4 chassis slots or a 20A fuse for fans and Shelf Managers. All terminals should be connected single -48VDC power source with a 100A listed circuit breaker.
To connect the FortiGate-5140B PEMs to DC power you must use power connectors and wires that comply with the local electrical wiring code and the requirements of the facility in which you are installing the FortiGate-5140B chassis.
The PEMs are hot-swappable, which means you can remove and replace a defective PEM while the system is operating (assuming that the FortiGate-5140B system has both PEMs connected for redundancy). It is not necessary to notify the software or reset the system power to remove a PEM. You can add, remove, or replace a second PEM without interrupting FortiGate-5140B operation.
FortiGate-5140B Chassis Guide
22 01-500-156415-20151104
http://docs.fortinet.com/
Power connection and configuration Connecting a FortiGate-5140B PEM to DC power
DC Power Source
-48VDC
connector
RTN (+)
red to power
source RTN
DC Power Source
RTN connector
-48V/-60 VDC
black to power
source -48VDC
Reverse Voltage LED
Fuse LEDs
Active OOS H/S

Crimping guidelines

To connect the PEMs to datacenter power you should use AWG-6 or larger wires depending on the length and the power requirements of your chassis. The ends of these wires must be fitted with 3/4-inch double-hole lugs with insulating boot suitable the DC cables used, such as Thomas & Betts PN 256-30695-1225. Use the following information to crimp and prepare these wires.
Do not crimp energized wires.
Before crimping, slide rubber boot along each wire. Follow these crimping guidelines:
• Strip the insulation from cable. Be careful not to nick cable strands which may later result in stands breaking
• Cable end should be clean: wire brush or clean with emery cloth if necessary. Insert cable into connector until it stops. The insertion length must approximate the stripped length of cable
• Insert connector in die and compress between the markings beginning near the tongue of the connector. Using the wrong installing die may result in a defective connection.
• After crimping, remove all sharp edges, flash or burrs.

Connecting a FortiGate-5140B PEM to DC power

The following procedure describes how to connect power to a PEM. You can repeat this procedure for both PEMs.
Two DC cable sets are required for each PEM connection (and all 4 terminals on each polarity should be used). If for any reason any of the PEM terminals are not used the unused terminals need to be covered with insulated material (or wrapped with electrical tape) as the exposed terminals are a shock hazard.
Figure 8: Connecting a FortiGate-5140B PEM to DC power
FortiGate-5140B Chassis Guide 01-500-156415-20151104 23
http://docs.fortinet.com/
Connecting a FortiGate-5140B PEM to DC power Power connection and configuration
Table 6: FortiGate-5140B PEM LEDs
LED State Description
REV. VOLTAGE (Reverse Voltage)
Off Normal operation
Solid Red Input voltage polarity reversed.
Off Normal operation.
FUSE CH1-4 (Fuses for power channels 1 to 4)
Solid Red Fuse blown or absent.
Blinking
Input power lost
Red
FUSE FANS (Fuses for the cooling fan power channel)
Off Normal operation.
Solid Red Fuse blown or absent.
Blinking
Input power lost.
Red
If all five fuse LEDs are simultaneously blinking input power to the PEM has been lost.
ACTIVE
Solid Green
Normal operation.
Off Normal Operation.
OOS (Out of Service)
Blinking Red
Lost connection to shelf manager or IPMB bus.
Solid Red Incorrect hardware address or FRU data corruption.
Off Normal operation.
H/S (Hot Swap)
Blinking Blue
The PEM is shutting down in preparation for being removed from the chassis.
Blue The PEM can be removed from the chassis.
You need the following equipment to connect a FortiGate-5140B PEM to DC power:
• An electrostatic discharge (ESD) preventive wrist strap with connection cord.
• Two black AWG-6 stranded wires labelled -48V with attached 3/4-inch listed closed loop double-hole lugs with insulating boot suitable for the DC cables used, such as Thomas & Betts PN 256-30695-1225.
• Two red AWG-6 stranded wires labelled RTN with attached 3/4-inch listed closed loop double-hole lugs with insulating boot suitable for he DC cables used, such as Thomas & Betts PN 256-30695-1225.
To connect a FortiGate-5140B PEM to DC power
1 Attach the ESD wrist strap to your wrist and to an ESD socket or to a bare metal
surface on the chassis or frame.
2 Make sure that the PEM and power cord are not energized.
3 Remove the first set of nuts and lock washers from both connectors on the PEM.
4 Connect two black -48V power wires from the DC power source to the connectors on
the FortiGate-5140B PEM labeled - (the connectors on the right side of the PEM) using the double-hole lugs (see Figure 8).
Install each double-hole lug vertically. Do not apply torque of more than 3.8 Nm (33.62 lbf.in).
FortiGate-5140B Chassis Guide
24 01-500-156415-20151104
http://docs.fortinet.com/
Power connection and configuration Connecting the FortiGate-5140B chassis to ground
Data Center
ground
connector
(Central ofce
ground sys tem)
Chassis
Ground
Connector
(green)
5 Connect two red RTN power wires from your location’s RTN terminal to the
connectors on the FortiGate-5140B PEM labeled + (the connectors on the left side of the PEM) using the double-hole lug (see Figure 8).
Install each double-hole lug vertically. Do not apply torque of more than 3.8 Nm (33.62 lbf.in).
6 Install previously removed nuts and washers to secure the connectors.
7 Cover the connectors with rubber boots.
8 Make sure the power wires are secured using tie wraps if required.
9 If required, label the black wires -48V.
10 If required, label the red wires RTN.

Connecting the FortiGate-5140B chassis to ground

The FortiGate-5140B chassis includes a ground terminal on the lower right side of the FortiGate-5140B back panel (see Figure 2 on page 11). The ground terminal provides two connectors to be used with a double-holed lug such as Thomas & Betts PN 256-30695-
1225. This connector must be connected to a local ground connection.
You need the following equipment to connect the FortiGate-5140B chassis to ground:
• An electrostatic discharge (ESD) preventive wrist strap with connection cord.
• One green AWG-6 stranded wire with listed closed loop double-hole lug with insulating boot suitable for minimum 6 AWG copper wire, such as Thomas & Betts PN 256-30695-1225.
Figure 9: Connecting a FortiGate-5140B chassis to ground
To connect the FortiGate-5140B chassis to ground
1 Attach the ESD wrist strap to your wrist and to an ESD socket or to a bare metal
surface on the chassis or frame.
2 Make sure that the chassis and ground wire are not energized.
3 Connect the green ground wire from the local ground to the ground connector on the
FortiGate-5140B chassis (see Figure 9).
4 Secure the ground wire to the chassis.
5 Optionally label the wire GND.
FortiGate-5140B Chassis Guide 01-500-156415-20151104 25
http://docs.fortinet.com/
Supplying power using the FortiGate-5053B power supply shelf and PSU-5000B power supplies Power connection and
PS U-5000B hot swappable
Power Supplies (4)
Edge
Controller

Supplying power using the FortiGate-5053B power supply shelf and PSU-5000B power supplies

If DC power is not available at your location, you can use the FortiGate-5053B and FortiGate-5053B-LC 1U 19-inch rack mount power supply shelves with PSU-5000B hot swappable power supplies to convert AC power to DC power. These components are not supplied with the FortiGate-5140B chassis and must be purchased separately.
Figure 10: FortiGate-5053B power supply shelf with four PSU-5000B power supplies
As already stated, Fortinet supplies four 3-ft. power cables with AWG-6 stranded wires and double-hole lugs: Black for -48VDC and red for RTN. These cables should only be used to connect the FortiGate-5140B PEMs to a FortiGate-5053B power supply shelf if purchased with your FortiGate-5140B chassis. The double-hole lugs to be connected to the FortiGate-5140B PEMs include rubber boots that should be installed before energizing the power system. If the power cable length needs to be longer than 3 ft., higher gauge wires should be used.
The FortiGate-5053B power supply shelf can include up to four PSU-5000B power supplies. The power supply shelf can be connected to high line AC input (186-240VAC) or low line AC input (100-185VAC).
• When connected to high-line AC input, a single power supply can provide 2725W of DC power and a fully populated FortiGate-5053B power supply shelf can provide up to 10.9KW of DC power and 8175W of DC power with 3+1 redundancy with an output voltage of 54 VDC.
• When connected to low-line AC input a single power supply can provide 1200W of DC power and a fully populated FortiGate-5053B power supply shelf can provide up to 4800W of DC power and 3600W of DC power with 3+1 redundancy with an output voltage of 54 VDC.
The FortiGate-5053B power supply shelf edge controller controls and manages the power supplies, provides for redundancy, and provides a control and alarm communication interface for the power supply shelf.
For a more information about the FortiGate-5053B power supply shelf see the FortiGate-
5053B Power Supply Shelf Guide.
To supply power to a FortiGate-5140B chassis you must connect one FortiGate-5053B power supply shelf to one FortiGate-5140B PEM.
You can install extra PSU-5000B power supplies in a single FortiGate-5053B power supply shelf to provide power redundancy. If a PSU-5000B fails or is removed a backup PSU-5000B will continue to supply power.
For a completely redundant power supply you can connect a second FortiGate-5053B power supply shelf to the second FortiGate-5140B PEM.
FortiGate-5140B Chassis Guide
26 01-500-156415-20151104
http://docs.fortinet.com/
Power connection and configuration Supplying power using the FortiGate-5053B power supply shelf and PSU-5000B power

Selecting the power supplies and power supply shelves that you need for your FortiGate-5140B chassis

This section provides some basic information for determining the power requirements of your FortiGate-5140B chassis. Using these power requirements you can decide how many PSU-5000B power supplies and FortiGate-5053Bpower supply shelves you need to provide that power. This section provides guidelines only. Actual requirements may vary depending on your installation requirements. Contact Fortinet Support if you need more information.
The base FortiGate-5140B chassis (empty, with four fans, one shelf manager, two shelf alarm modules and two PEMs installed and operating with the fans running at full speed) requires a maximum of 530 W. Each chassis slot can supply up to 300 W. You can use these numbers to estimate the power requirement for a chassis configuration.
Example: power for a chassis with 5 boards
For example, the power requirement for a FortiGate-5140B chassis with FortiGate, FortiSwitch, or FortiController boards in five slots would be:
530 W + (300 W * 5) = 2030 W
If you are using high-line AC power, one PSU-5000B produces 2725W. Powering a chassis with 5 boards would require one FortiGate-5053B power supply shelf connected to one PEM. The power supply shelf would include one PSU-5000B unit. You can add a second power supply for redundancy. If you want completely redundant power for the chassis you can connect a second FortiGate-5053B unit to the other FortiGate-5140B PEM and include one or two power supplies.
If you are using low-line AC power, one PSU-5000B produces 1200W. Powering a chassis with 5 boards would require one FortiGate-5053B power supply shelf connected to one PEM. The power supply shelf would include two PSU-5000B units. You can add a third power supply for redundancy. If you want completely redundant power for the chassis you can connect a second FortiGate-5053B unit to the other FortiGate-5140B PEM and include two or three power supplies.
Example: power for a fully-loaded chassis (14 boards)
The power requirement for a fully loaded FortiGate-5140B chassis with boards in all 14 slots would be:
530 W + (300 W * 14) = 4730 W
If you are using high-line AC power, one PSU-5000B produces 2725W. Powering a chassis with 14 boards would require one FortiGate-5053B power supply shelf connected to one PEM. The power supply shelf would include two PSU-5000B units and produce a total of 3450W. You can add a third power supply for redundancy. If you want completely redundant power for the chassis you can connect a second FortiGate-5053B unit to the other FortiGate-5140B PEM and include two or three power supplies.
If you are using low-line AC power, one PSU-5000B produces 1200W. Powering a chassis with 14 boards would require one FortiGate-5053B power supply shelf connected to one PEM. The power supply shelf would include four PSU-5000B units. If you want redundant power for the chassis you can add a second FortiGate-5053B unit connected to the other FortiGate-5140B PEM and include four power supplies.
FortiGate-5140B Chassis Guide 01-500-156415-20151104 27
http://docs.fortinet.com/
Loading...
+ 61 hidden pages