HC_1810R/N, HM_1810R/N
HC_2110R/N, HM_2110R/N
Order parts online
www.follettice.com
Horizon Elite™ Ice Machine Installation Instructions
for Remote Condensing Unit
Drop-in Remote Condensing
®
RIDE
remote ice delivery equipment
Vision™ Remote Condensing
RIDE remote ice delivery equipment
801 Church Lane • Easton, PA 18040, USA
Toll free (877) 612-5086 • +1 (610) 252-7301
REMOTE CONDENSING UNIT
www.follettice.com
Harmony Remote Condensing
Top Mount
Harmony™ Remote Condensing
RIDE remote ice delivery equipment
Bin Remote Condensing
Top Mount
Bin Remote Condensing
RIDE remote ice delivery equipment
01157932R01
1
air in
exhaust
48.00"
(121.9cm)
48.00"
(121.9cm)
24.00"
(61.0cm)
24.00"
(61.0cm)
Condensing Unit Shipping Weight
Model Horizon 1810 Horizon 2110
Single-phase 305 lb (1139 kg) 305 lb (1139 kg)
3-phase 305 lb (1139 kg) 305 lb (1139 kg)
Prior to installation, carefully unpack and inspect the
contents of your condensing unit!
Site preparation
To ensure proper performance, ease of service and warranty coverage, it is critical that you follow
the requirements detailed in this manual. If you cannot meet these requirements or have questions,
call our technical service group at 877.612.5086 for installation support.
1
2.1
1. 1
Condenser Unit Clearances
• Position condenser unit as shown above, with clearances noted above
2
REMOTE CONDENSING UNIT
2.1
1. 2
Condenser installation specications
S-trap
required
Easton Pennsylvania
CORPORATION
PART NO
SERIAL NO
MODEL
SINGLE
FULL LOAD AMPS
HZ
VOLTS
PHASE
MOTOR COMPRESSOR THERMALLY PROTECTED
OZ
CHARGE
REFRIGERANT
PSIG
DESIGN PRESSURE HIGH SIDE
LOW SIDE
208264
MIN. BRANCH CIRCUIT AMPACITY
AMPS
Stock Module Identification Plate
MADE IN
ULU
NSF
THE USA
L
RR
Module No.
MAX. BRANCH CIRCUIT FUSE SIZE
AMPS
C
Product
Service No.
EVAPORATOR
UNIT
➊
➊
P-trap
required
P-trap
required
EVAPORATOR UNIT LEVEL
75' max.
(22.8 m)
➍
CONDENSER UNIT
maximum
line rise
CONDENSER UNIT
maximum
line drop
➋
+35'
(+10.7 m)
+20'
(+6.1 m)
–15'
(–4.6 m)
75' max.
(22.8 m)
➌
➍
Site layout:
• Outdoor ambient temperature range: –20 F to 120 F (–29 C to 49 C)
• Installation with condenser unit elevations above 20' (6.1 m) require an S-trap at the midpoint
of the rise and a P-trap at the top and bottom of the rise
➊
• Maximum line rise must not exceed 35' (10.7 m) ➋
• Maximum line set length must not exceed 75' (22.8 m)
• Maximum line drop must not exceed 15' (4.6 m)
➍
➌
REMOTE CONDENSING UNIT
3
Condenser installation
2
2.1
• Level unit
• Securely attach base of unit using holes
• Required rack system capacity at 0 F
1810N: 15,700 Btu/hr (3956 kcal/hr)
2110N: 18,200 Btu/hr (4586 kcal/hr)
Install condensing unit
found in base plate
(–18C) evaporator (EPR supplied by
installer).
2.2
Electrical requirements
Condensing unit
1810
Single-Phase
Electrical 208-230V, 60Hz
Max Circuit HVACR breaker size 45A 25A 45A 30A
Min Circuit Ampacity 26.2A 15.7A 27.1A 19.9A
• Refer to wiring schematic located in condenser unit electrical box
1810
3-Phase
2110
Single-Phase
2110
3-Phase
CAUTION
• Electrical disconnects required within
10' (3 m) for all hard wired connections
• Install in accordance with NEC and local
electrical codes
4
REMOTE CONDENSING UNIT