Follett HCC1400A User Manual

Page 1
HCC1400A, HCC1400W Icemakers
Operation and Service Manual
After Serial Number C20000
Following installation, please forward this manual
to the appropriate operations person.
801 Church Lane • Easton, PA 18040, USA Toll free (800) 523-9361 • (610) 252-7301 Fax (610) 250-0696 • www.follettice.com
00171587R00
Page 2
Follett Corporation Equipment Return Policy
Follett equipment may be returned for credit under the following conditions:
1. The equipment is new and unused.
2. A return authorization number has been issued by customer service within 30 days after shipment.
3. Follett receives the equipment at the factory in Easton, PA within 30 days after issuance of the return authorization number.
4. The equipment must be returned in Follett packaging. If the packaging has been damaged or discarded, Follett will forward, at the customer’s expense, new packaging.
Note: Return freight charges are the responsibility of the customer. If equipment is returned and is damaged because of
improper packaging, Follett Corporation will not be held responsible.
Credit will be issued when: The equipment has been inspected by Follett and deemed suitable to be returned to stock.
Note: A 15% restocking charge will be deducted from the credit. If the cost to return the product to stock exceeds 15%, the
actual cost will be deducted.
2
Page 3
Table of contents
Welcome to Follett Corporation Specifications Operation
Cleaning Weekly exterior care Monthly condenser cleaning
Semi-annual evaporator cleaning
Service
Icemaker operation Water system Electrical system Normal control board operation Test points Time delay and self flushing jumpers Error faults Hard error Soft errors Relay output indication Compressor/refrigerant solenoid output Wiring diagram Compressor data Gearmotor data Resistance of windings Mechanical system Evaporator disassembly Evaporator reassembly Refrigeration system Refrigeration pressure data Refrigeration system diagram Refrigerant charge size Refrigerant replacement requirements Evacuation Ambients Ice capacity test Bin full detection system Troubleshooting Replacement parts
4 5 7 7 7 7
7 12 12 13 14 14 15 15 15 15 15 15 15 16 17 17 17 18 18 20 23 23 23 24 24 24 24 24 25 26 28
3
Page 4
Welcome to Follett
Follett equipment enjoys a well-deserved reputation for excellent performance, long-term reliability and outstanding after-the-sale support. To ensure that this equipment delivers the same degree of service, we ask that you review the installation manual (provided as a separate document) before beginning to install the unit. Our instructions are designed to help you achieve a trouble-free installation. Should you have any questions or require technical help at any time, please call our technical service group at (800) 523-936 or (610) 252-7301.
Before you begin
After uncrating and removing all packing material, inspect the equipment for concealed shipping damage. If damage is found, notify the shipper immediately and contact Follett Corporation so that we can help in the filing of a claim, if necessary.
Check your paperwork to determine which model you have. Follett model numbers are designed to provide information about the type and capacity of Follett equipment. Following is an explanation of the different model numbers in the 1400 series.
Horizon Series Icemaker Model Number Configurations
AVSC 1400HC
Icemaker Voltage Series Condenser
HC Horizon Chewblet
† Ice Manager Diverter Valve Systems can be used to fill any two of these bins or dispensers with a single ice machine.
Chewblet is a registered trademark of Follett Corporation, registered in the US.
C 208-230/60/1
®
(self-contained only)
D Low side 115/60/1 Condensing unit 208-230/60/1
(remote condensing only)
E 230/50/1
(self-contained only)
1000 up to 1036 lbs (471kg)
1400 up to 1450 lbs (658kg)
A Air-cooled, self-contained W Water-cooled, self-contained R Air-cooled, remote condensing unit N Air-cooled, no condensing unit for connection to parallel rack system
Application Configuration
V Vision™ H Harmony™ B Ice storage bin J Drop-in M Ice Manager diverter valve system
S Satellite-fill™ T Top-mount
CAUTION
• Warranty does not cover exterior or outside installations.
• Moving parts. Do not operate with front cover removed.
• Hot parts. Do not operate with cover removed.
• To reduce risk of shock, disconnect power before servicing.
• Most ice machine cleaners contain citric or phosphoric acid, which can cause skin irritation. Read caution label on product and follow instructions carefully.
• Ice is slippery. Maintain counters and floors around dispenser in a clean and ice-free condition.
• Ice is food. Follow recommended cleaning instructions to maintain cleanliness of delivered ice.
4
Page 5
Specifications
Electrical
Each icemaker requires its own separate circuit with electrical disconnect within 10 ft (6m). Equipment ground required. Standard electrical – 208-230/60/1 Maximum icemaker fuse – 20 amps each Amperage – 12 amps 6 ft (2m) NEMA 6-20 cord and plug provided on icemaker
Plumbing
3/8" OD push-in water inlet 3/4" MPT drain 1/4" FPT condenser inlet (water-cooled condenser only) 1/4" FPT condenser drain (water-cooled condenser only)
Notes: 3/4" vented drain line must slope a minimum of 1/4" per foot (6mm per 30.4cm run). Drain to be hard piped and insulated. To prevent back flow, do not connect drains. Separate drains for icemaker and condenser. Water shut-off recommended within 10 feet (3m). Follett recommends installation of a Follett water filter system (part# 00130286) in icemaker inlet water line.
Ambient
Air temperature 100˚F/38˚C max. 50˚F/10˚C min. Water temperature 90˚F/32˚C max. 45˚F/7˚C min. Water pressure – potable 70 psi max. (483 kPa) 10 psi min. (69 kPa)
Note: Water-cooled condenser pressure 150 psi (1034 kPa)
Heat rejection
Air-cooled rejects 16,000 BTU/hr to air Water-cooled rejects 16,400 BTU/hr to water
Ice production
Air-cooled icemaker capacity/24 hrs.
Ambient Air Temperature F/C
60
F
16
C
1591
1454
50
722
10
1509
1374
60
684
16
1396
1270
70
633
21
1364
1267
80
619
27
Inlet Water Temperature F/C
1270
1169
90
576
32
660
541
576
575
530
70
80
21
27
1315
596
1197
543
1178
534
1129
512
1071
486
90 32
1187
538
1127
511
1068
484
1020
462 969 440
100
38
1056
479
1030
467 932 423 902 409 870 395
Water-cooled icemaker capacity/24 hrs.
Ambient Air Temperature F/C
60
70
F
16
1356
615
1272
577
1160
526
1065
483 999 453
21
1356
615
1272
577
1160
526
1065
483 999 453
1356
615
1272
577
1160
526
1065
483 999 453
Inlet Water Temperature F/C
C 50 10 60 16 70 21 80 27 90 32
lbs kg lbs kg lbs kg lbs kg lbs kg
80
90 32
1356
615
1272
577
1160
526
1065
483 999 453
100
38
1356
615
1272
577
1160
526
1065
483 999 453
lbs kg lbs kg lbs kg lbs kg lbs kg
27
5
Page 6
Dimensions and clearances
Entire front of icemaker must be clear of obstructions/connections to allow removal.
1" (26mm) clearance above icemaker for service.
1" (26mm) minimum clearance on sides.
The intake and exhaust air grilles must provide at least 170 sq in (968 sq cm) of open area.
Air-cooled model HCC1400A icemakers – 18" (458mm) minimum clearance between discharge and air intake-grilles.
Front View Side View Back View
Ice transport hose connection
Air exhaust
Air intake
23.50"
(597mm)
Stock Module Identification Plate Module No. Product
Service No.
21.28" (541mm)
CORPORATION
MODEL
FULL LOAD AMPS
208264
MOTOR COMPRESSOR THERMALLY PROTECTED
REFRIGERANT
DESIGN PRESSURE HIGH SIDE
MIN. BRANCH CIRCUIT AMPACITY
MAX. BRANCH CIRCUIT FUSE SIZE
21.05" (535mm)
Easton Pennsylvania
SERIAL NO
PART NO
SINGLE
HZ
VOLTS
PHASE
CHARGE
OZ
LOW SIDE
PSIG
AMPS
MADE IN
U
NSF
THE USA
LUL
RR
AMPS
C
23.8" (580mm)
NEMA 6-20
15.56"
right angle
1/4" FPT condenser inlet
1/4" FPT condenser drain
6.97"
(177mm)
Air exhaust both sides
(395mm)
2.72" (69mm)
3/8" OD push-in water inlet
3/4" MPT drain
G
2.53"
(64mm)
29.63" (753mm)
2.43" (62mm)
6
Page 7
Operation
Cleaning and preventive maintenance (all models)
Note: Do not use bleach to sanitize or clean the icemaker.
Preventive maintenance
Periodic cleaning of Follett’s icemaker system is required to ensure peak performance and delivery of clean, sanitary ice. The recommended cleaning procedures that follow should be performed at least as frequently as recommended, and more often if environmental conditions dictate.
Cleaning of the condenser can usually be performed by facility personnel. Cleaning of the icemaker system, in most cases, should be performed by your facility’s maintenance staff or a Follett authorized service agent. Regardless of who performs the cleaning, it is the operator’s responsibility to see that this cleaning is performed according to the schedule below. Service problems resulting from lack of preventive maintenance will not be covered under the Follett warranty.
Weekly exterior care
The exterior may be cleaned with a stainless cleaner such as 3M Stainless Steel Cleaner & Polish or equivalent.
Monthly condenser cleaning (air-cooled icemaker only)
1. Use a vacuum cleaner or stiff brush to carefully clean condenser coils of air-cooled icemakers to ensure optimal performance.
2. When reinstalling counter panels in front of remote icemakers, be sure that ventilation louvers line up with condenser air duct.
Semi-annual evaporator cleaning (every 6 months)
WARNING
• Wear rubber gloves and safety goggles (and/or face shield) when handling ice machine cleaner or sanitizer.
CAUTION
• Use only Follett approved SafeCLEAN™ Cleaner (part #00132001) and NU-CALGON IMS-II SANITIZER.
• Do not mix Cleaner and Sanitizer solutions together.
• DO NOT USE BLEACH.
• It is a violation of Federal law to use these solutions in a manner inconsistent with their labeling.
• Read and understand all labels printed on packaging before use.
Note: Complete procedure for cleaning an sanitizing MUST be followed. Ice must be collected for 10 minutes before putting ice machine back into service.
1. To clean – Remove cover. Press the CLEAN button. The machine will drain. Wait for the LO WATER light to come on (Fig. 1).
Note: For Ice Manager diverter valve
application, refer to manual #00169045 for icemaker and diverter valve cleaning process.
Fig. 1
LO WATER
C
L
E
A
N
7
Page 8
2. Mix 1 gallon (3.8L) 120˚F (49˚C) water and
7 ounces (198g) (one 7 ounce packet of Follett SafeCLEAN ice machine cleaner, part#-00132001). Locate cleaning cup. Fill until HI WATER light comes on (Fig. 2). Note: Do not use bleach to sanitize or clean the icemaker.
3. Replace cover on cleaning cup. Wait until machine restarts. Machine will clean, then flush 3 times in approximately 12 minutes (Fig. 3).
Fig. 2
HI WATER
Fig. 3
4. To sanitize – Press CLEAN button. The machine will drain. Wait for LO WATER light to come on (Fig. 4).
Fig. 4
12
LO WATER
C
L
E
A
N
8
Page 9
5. Mix 1 gallon 120˚F (49˚C) water and 1.6 ounces (48ml) NU-CALGON IMS-II SANITIZER. Fill until HI WATER light comes on (Fig. 5). Note: Do not use bleach to sanitize or clean the icemaker.
6. Replace cover on cleaning cup. Wait until machine restarts. Machine will sanitize, then flush 3 times in approximately 12 minutes (Fig. 6).
Fig. 5
HI WATER
Fig. 6
7. To clean transport tube – Press power switch OFF (Fig. 7).
12
Fig. 7
9
Page 10
8. Disconnect coupling as shown (Fig. 8).
9. Using disposable food service grade gloves, insert dry Sani-Sponge™ (kit part# 00132068). Next,-insert Sani-Sponge soaked in Nu-Calgon IMS-II sanitizer solution. Push both Sani-Sponges down ice transport tube with supplied pusher tube (Fig. 9).
Fig. 8
Fig. 9
1
16"
(407mm)
10. Remove and discard 16" (407mm) pusher tube (Fig. 10).
2
3
Fig. 10
10
Page 11
11. Reconnect coupling. Press power switch ON. Ice pushes Sani-Sponges through tube (Fig. 11).
12. Place a sanitary (2 gallon or larger) container in bin or dispenser to collect Sani-Sponges and ice for 10 minutes. Collect 5.5 lbs of ice from unit. Discard ice and Sani-Sponges (Fig. 12).
Fig. 11
Fig. 12
11
Page 12
Service
Icemaker operation (all models)
Follett’s icemaker consists of five distinct functional systems covered in detail as follows:
• Water system
• Electrical control system
• Mechanical assembly
• Refrigeration system
• Bin full
The Horizon icemaker overview
The Follett Horizon icemaker uses a horizontal, cylindrical evaporator to freeze water on its inner surface. The refrigeration cycle is continuous; there is no batch cycle. The evaporator is flooded with water and the level is controlled by sensors in a reservoir. A rotating auger (22 RPM) continuously scrapes ice from the inner wall of the evaporator. The auger moves harvested ice through the evaporator into an ice extrusion canal. The ice is forced through a restrictive nozzle that squeezes out the water and creates the Chewblet. The continuous extrusion process pushes the Chewblets through a transport tube into a dispenser or bin.
A solid state PC board controls and monitors the functionality of the ice machine. In addition to sequencing electrical components, the board monitors various operational parameters. A full complement of indicator lights allows visual status of the machine's operation. Additionally, the PC board controls the self-flushing feature of the icemaker. The evaporator water is periodically drained and replenished to remove minerals and sediment.
A unique “bin full” detection system is incorporated in the Horizon icemaker. A switch located at the ice discharge port of the machine detects the position of the transport tube. When the bin fills up with ice, the transport tube moves out of the normal running position, and the switch turns the ice maker off. A domed housing at the end of the transport tube contains the ice extrusion loads during shut down.
Harvest system diagram
ice transport tube
water inlet
compression nozzle
auger
12
Page 13
Water system
The water level in the evaporator is controlled by a feed solenoid and level detecting sensors. Referencing the diagram below, water sensing rods extend down into the reservoir at the end of the evaporator assembly. The system works via electrical conductivity as follows:
One of the longest probes is a common. When water is between any of the other probes and the common, the PC board will sense the activation. During normal operation, the water level rises and falls between the Normal High and Normal Low sensors. As water is consumed to make ice, the level will fall until the Normal Low sensor is exposed, triggering the water feed solenoid on. Water will fill until the Normal High sensor is activated.
Note: The potable water dissolved solids content must be greater than 10 ppm for the water control system to function properly. If using reverse osmosis water filtration system, ensure T.D.S level is greater than 10 ppm.
Water system diagram
Water level diagram
Normal
operating
range
Normal LO
Alarm LO
Common
13
Normal HI
Page 14
Electrical system
Normal control board operation
The PC board indicator lights provide all the information necessary to determine the machine's status. Green indicator lights generally represent “go” or normal operation; Yellow indicators represent normal off conditions; Red indicators generally represent alarm conditions, some of which will lock the machine off.
A green light labeled POWER indicates power to the machine. A flashing green light labeled CPU is normal and indicates that the Central Processing Unit “heart beat” is working. All other normal operation status indicators are covered as follows:
Ice machine disposition Operating conditions
Legend:
ON OFF
ON or OFF FLASHING
1. Ice machine is making ice.
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
2. Ice machine is not making ice.
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
3. Ice machine is not making ice.
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
POWER
LOW BIN
POWER
LOW BIN
POWER
LOW BIN
1. Normal running.
2. Normal time delay. When the bin fills with ice, the LOW BIN light goes out and the refrigeration and auger drive systems immediately shut down. (Note: The fan motor will continue to run for 10 minutes to cool condenser) The TIME DELAY light comes on, initiating the time delay period. When the time delay expires, the machine will restart provided that the LOW BIN light is on.
3. Normal purge indicator. After a selected period of ice making time has elapsed (1 or 2 hours), the ice machine will automatically self-flush. The compressor will shut down but the fan and gearmotor will continue to run. After the flush is complete the machine will refill and start without a time delay.
14
Page 15
Test points:
The Horizon PC board incorporates on-board test points that can be used to determine various electrical outputs. The test point holes allow a standard probe to be inserted for quick voltage measurement. For 208-230 systems, use TP-4 (L2) as the common for testing outputs for solenoids, motors, etc.
Error faults:
The Horizon PC board monitors various operating parameters including high pressure, auger gearmotor amperage limits, clogged drain, and high and low water alarm conditions. There are two types of errors namely “hard” or “soft”. A hard error is one that shuts the machine off and will not allow restart until the reset button is pressed. Even cycling power will not reset a hard error. A soft error can either be automatically reset should the condition rectify, or if power is cycled. Should an error occur, consult the troubleshooting guide in this manual or a Follett service technician. Note: there are two types of LO WATER and HI AMPS errors as listed below.
Soft errors:
HI AMPS: The PC board monitors the amperage of the auger motor. Should the gear motor experience current draw above the 3.8 amps limit the machine will shut down and the TIME DELAY, HI AMP, and SERVICE LED’s will be illuminated. After the time delay the machine will restart and the TIME DELAY, HI AMP, and SERVICE LED’s will clear.
LO WATER: During operation, the water level cycles between the normal low and normal high sensors. Should the water be shut off to a running machine, a soft error will occur. The error sequence is as follows: During operation, the water level falls to the normal low sensor, and when it does the water feed solenoid is energized. If water is not detected at the normal low sensor within 120 seconds, a soft error will occur. The machine will shut down, but the water feed solenoid will remain energized. Should water return, it will fill to the normal low sensor and the machine will resume normal operation. The error will clear automatically.
DRAIN CLOG: The drain clog sensor, located in the plastic drain pan behind the drain solenoid, will detect the presence of water just below the top edge of the pan. If water does not properly flow out of the drain pan it will rise to the sensor, especially during a self-flushing purge cycle.
Hard error:
HI AMPS:
1. “Two strikes” feature. If the gearmotor has a second HI AMP occurrence during the countdown period (6 hours after a HI AMP time delay) a hard error will occur and the HI AMP and SERVICE LED’s will be illuminated.
2. No current. To prevent the refrigeration system from running without gearmotor rotation the PC board will indicate HIGH AMP and SERVICE if the drive relay is energized and there is no current draw.
HI PRESSURE: Should the refrigeration pressure rise above 425 psi, a hard error will occur. Even if pressure fall-back below the reset point of 295 psi, the error will not clear and the machine will not restart.
LO WATER:
1. There is a sensor in the water reservoir that reaches down to the very bottom. The machine will not start if water is not present at this sensor.
2. A hard error will occur should water not be present within 60 seconds of power up or if the sensors are disconnected or damaged.
Relay output indication:
Each relay on the board has an indicator light associated with its output. For example, when the relay for the water feed solenoid is energized, the adjacent indicator light glows green.
Comp/Sol output:
The output for the compressor is labeled COMP/SOL.
15
Page 16
Wiring diagram
20Watt
230Vac
20Watt
230Vac
FCV-1 FCV-2
DRAIN
INPUT
WATER
S1
50/60Hz
#7
#8
5
4
#37
#38
L1
L2
208V/230Vac
L1
~12 Amp DRAW RUNNING
L2
2
O I
OFF/ON
1
240Vac / 20FLA
GND
J52
P52
CONTACTOR
#19
20FLA
240Vac
K11
POTENTIAL
RELAY
5
6
4
#43
SNUBBER
#18
1ÿ/230Vac
P1
COMP
R
C
#45
#44
12
#41
C2 START
#39
S
#46
#42
C1 RUN
#40
#47
M1
1/2hp Max
MOTOR
M2
BLU
.6 Amp Max
FAN
BRN
GRN
801 CHURCH LANE
EASTON, PA 18040, USA
FOR SERVICE CALL:
00135780R06
800-523-9361 OR 610-252-7301
ON THE WEB: www.follettice.com
HI
1
2
3
PRESS
OPEN @ 425 PSI
HIGH PRESSURE
CLOSE @ 295 PSI
OPENS @ EXCESS
J50
#1
CB1
#2
#3
GRN
BRN
BLU
P
2
PE
J31
J32
RESET
SWITCH
GRAY / GRAY PAIR
SIGNAL
RETURN
1
2
J3
J33
J34
POWER (G)
LOW BIN (G)
AUGER ON (G)
REFRIG ON (G)
TIME DELAY (Y)
CLEANING (Y)
PURGE (Y)
SERVICE (R)
HI AMPS (R)
HI PRESS (R)
LO PRESS (R)
DRAIN CLOG (R)
HI WATER (R)
LO WATER (R)
CPU (G)
#33
#32
#30
#31
TP7
TP8
#2
BLU
#38
#11
J13
J14
J15
J16
J17
IN
H2O
J18
H2O
DRN
J9
J8
J10
J12
J11
TP4
D10
D15
J7
L2
TP11
#37
J6
J5
J4
L1
#34
TP5
DRV
NOC
BRN
TP6
FAN
K3
AMP
SENSING
D6
D9
#12
TP3
J2
SOL
COMP
D5
CNO
K1
CONTROL PC BOARD
J21
J22J23
1
J51
3
8
LE
DRAIN
4
CLOG
BIN
7
LE
COM
2
FULL
1
1
1
JUMPER
J24
1
RED / GRAY PAIR
GRAY / GRAY PAIR
RETURN
INPUT 2
6
LE
HIGH
NORM
(CONTACT CLOSURE)
OR
4
LE
LOW
ALARM
COM
LOW
NORM
WATER LEVEL
3
LE
orizon 1400 Series Self-contained Icemaker
2
LE
BLU
-V BLK
BRN
OUT (light on)
+V
(3 WIRE)
16
MOM
S3
CLEAN
MAINT
S2
PURGE
Page 17
Compressor data
Compressor current draw
Air-cooled
Ambient air temp. 60˚F/16˚C 70˚F/21˚C 80˚F/27˚C 90˚F/32˚C 100˚F/38˚C
8.01A 8.26A 8.77A 9.06A 9.36A
Water-cooled
Condenser water temp 50˚F/10˚C 60˚F/16˚C 70˚F/21˚C 80˚F/27˚C 90˚F/32˚C
9.09A 9.14A 9.06A 9.15A 9.39A
Locked rotor amps 96.8
Gearmotor data
Brother
Gearmotor current 2.8A (nominal)
Locked rotor amps 15 amps
Resistance of windings
208-230 vac gearmotor (Brother) 6.2Ω
Compressor start winding 3.5Ω
Compressor run winding 0.7Ω
Fan motor 38Ω
17
Page 18
Mechanical system
Evaporator disassembly
1. Press PURGE button to purge evaporator, and then turn power OFF.
2. Unscrew and remove stream divider as shown.
3. Unplug and remove gearmotor as shown.
4. Remove all traces of petrol-gel from the auger shaft.
Fig. 13
Fig. 14
5. Unscrew and disconnect transport tube from louvered docking assembly.
6. Unplug sensor at the electrical box.
7. Remove vent tube from shuttle housing as shown.
Fig. 15
18
Page 19
8. Loosen nut on V-band clamp and remove.
9. Remove V-band clamp from front of evaporator.
10. Remove main housing as shown.
11. Remove and discard mating ring and seal.
12. Carefully remove auger.
Fig. 16
Fig. 17
19
Page 20
Evaporator reassembly
1. Remove and inspect O ring seal. Discard if damaged in any way.
2. Clean O ring groove. Lubricate O ring with petrol-gel and reinstall.
3. Press new mating ring into main housing as shown.
4. Lube the shaft with liquid soap in the area shown and slip on seal and spring.
Note: Do not touch the sealing surfaces. Use
cardboard disk to install.
Fig. 18
Fig. 19
Cardboard
disc
5. Reinstall main housing as shown.
Lube
with soap
Do not
touch
Fig. 20
20
Page 21
6. Orient auger shaft with keyway in the upward position.
7. Force main housing into position against evaporator and place 1/4" (7mm) diameter Phillips screwdriver into hole in the auger shaft.
8. Replace V-band clamp as shown.
9. Replace nut on V-band clamp and tighten.
10. Remove screwdriver.
11. Reconnect transport tube to louvered docking assembly.
12. Plug sensor in at the electrical box.
13. Reconnect vent tube to the shuttle housing as shown.
Fig. 21
Note: Shuttle housing removed for clarity
Fig. 22
14. Apply a coat of petrol-gel to the auger shaft.
15. Install gearmotor, making sure that insulation is properly seated between gearmotor and main housing as shown.
16. Firmly tighten four gearmotor bolts in place.
17. Insert a bolt into the auger shaft and finger tighten.
Fig. 23
Apply
petrol-gel
21
Page 22
18. Using a wrench, rotate the shaft clockwise to align the keyways in the gear housing and the shaft so as to accept the key.
19. Insert the key into the keyway.
20. Remove bolt and reinstall the washer and bolt. Place retainer over bolt and secure with nut and washer.
Fig. 24
Fig. 25
21. Lubricate body of stream divider with petrol-gel and reinstall.
22. Plug gearmotor power cord into electrical box.
Fig. 26
Apply petrol-gel
22
Page 23
Refrigeration system
Refrigerant pressure data
Air-cooled condensers (air) 50˚F/10˚C 60˚F/16˚C 70˚F/21˚C 80˚F/27˚C 90˚F/32˚C 100˚F/38˚C
Pressure (psig) discharge/suction 190/25 217/29 241/29 276/32 317/36 358/39
Water-cooled condensers (water) 50˚F/10˚C 60˚F/16˚C 70˚F/21˚C 80˚F/27˚C 90˚F/32˚C
Pressure (psig) discharge/suction 235/21 237/21 238/20 236/21 315/33
Note: The water control valve is factory set to maintain 238 ± 15 psi discharge pressure @ 70˚ F water.
Refrigeration system diagram
high side
refrigeration
line run
filter dryer
thermostatic
expansion
valve
high side
service port
low side
service port
condenser
low side
refrigeration
line run
compressor
High pressure vapor
High pressure liquid
Low pressure liquid
23
Low pressure vapor
Page 24
Refrigeration charge
All service on refrigeration systems must be performed in accordance with all federal, state and local laws. It is the responsibility of the technician to ensure that these requirements are met. Recharging icemaker to other than factory specifications will void the warranty.
R404A icemaker charge specifications
Model Charge Refrigerant type
HCC1400A (air-cooled) 34oz (652g) R404A
HCC1400W (water-cooled) 21oz (426g) R404A
Refrigerant replacement requirements
1. Non-contaminated refrigerant removed from any Follett refrigeration system can be recycled and returned
to the same system after completing repairs. Recycled refrigerant must be stored in a clean, approved storage container. If additional refrigerant is required, virgin or reclaimed refrigerant that meets ARI standard 700-88 must be used.
2. In the event of system contamination (for example, a compressor burn out, refrigerant leak, presence of
non-condensibles or moisture), the system must be repaired, evacuated and recharged using virgin or reclaimed refrigerant that meets ARI standard 700-88.
3. Follett Corporation does not approve of recovered refrigerants. Improper refrigeration servicing procedures
will void the factory warranty.
Evacuation
Evacuate the system to a level of 500 microns. When the 500 micron level is reached, close all valves. Allow the system to sit for approximately 20 minutes. During this period the system pressure should not rise. If the system pressure rises and stabilizes there is moisture in the system and further evacuation is needed. If the pressure continues to rise check the system for leaks.
Ambients Minimum Maximum
Air temperature1 50˚F/10˚C 100˚F/37.8˚C Water temperature2 45˚F/7˚C 90˚F/32.2˚C
1
Ambient air temperature is measured at the air-cooled condenser coil inlet.
2
Ambient water temperature is measured in the icemaker water reservoir.
Ice capacity test
Icemaker production capacity can only be determined by weighing ice produced in a specific time period.
1. Replace all panels on icemaker.
2. Run icemaker for at least 15 minutes.
3. Weigh and record weight of container used to catch ice.
4. Catch ice for 15 or 20 minutes.
5. Weigh harvested ice and record total weight.
6. Subtract weight of container from total weight.
7. Convert fractions of pounds to decimal equivalents (ex. 6 lbs 8oz = 6.5 lbs).
8. Calculate production using following formula:
1440 min. x wt. of ice produced = Production capacity/24 hr. period Total test time in minutes
9. Calculated amount per 24 hours should be checked against rated capacity for same ambient and water
temperatures in Ice Production Tables.
24
Page 25
“Bin full” detection system
The Follett Horizon icemaker incorporates a unique “bin full” detection system that consists of the shuttle and actuator. The shuttle incorporates a flag and sensor. Referencing the figure below, the normal running position of the flag is down, out of the sensor. When the bin fills to the top and ice can no longer move through the tube, the machine will force the shuttle flag up into the sensor, shutting the machine off. The shuttle actuator, located above the ice bin allows the ice to curl up within it when the bin is full. In this way, there are no loads generated that would tend to lift off the lid of the bin.
Shuttle flag and sensor
Shuttle actuator
Running
Off
Running
Off
25
Page 26
Troubleshooting
Please see “Service” section for a description of each function.
Ice machine disposition Possible causes Corrective actions
Legend:
ON OFF
ON or OFF FLASHING
1. Ice machine is in running condition but not making ice.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
2. The CPU is not flashing.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
3. Machine in TIME DELAY without full bin.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
4. Ice machine is not making ice. Locked in PURGE.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
1. Defective compressor.
2. Defective start relay.
3. Defective start capacitor.
4. Defective run capacitor.
5. Defective main contactor.
POWER
6. No output from PC board.
1. Processor has been damaged.
POWER
1. Ice jamming due to improperly installed transport tube causing a false shuttle.
2. Shuttle stuck in up position.
3. Damaged or improperly installed thermostat (open).
POWER
4. Transport tube backed-out of coupling.
1. A self-flush occurred but could not drain evaporator due to a failed drain solenoid valve.
2. A self-flush occurred but could not drain evaporator due to water reservoir or ice machine not
POWER
being level.
1. Replace compressor.
2. Replace start relay.
3. Replace start capacitor.
4. Replace run capacitor.
5. Replace main contactor.
6. Replace PC board.
1. Replace PC board.
1. Correct transport tube routing.
2. Repair or replace shuttle mechanism.
3. Replace or reposition thermostat.
4. Correct coupling installation.
1. Replace drain solenoid valve.
2. Level ice machine. Check water reservoir to make sure it is not tilted towards the compressor.
5. Ice machine is not making ice. HI AMPS.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
6. Ice machine is not making ice.
HI PRESSURE.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
1. Poor water quality causing ice to jam auger.
2. Damaged shuttle mechanism or thermostat (closed).
3. Kinked transport tube (thermostat systems).
POWER
4. Intermittent drive output from PC board. Evaporator will freeze causing a hi amps error.
5. Gearmotor is unplugged.
1. High ambient temperatures >100˚F (38˚C).
2. Poor ventilation or air recirculation.
POWER
3. Clogged condenser.
4. Fan not working properly. No air flow.
• Blocked fan blades
• No fan output from PC board
• Faulty fan motor
26
1. Clean ice machine. Increase flushing frequency.
2. Replace or repair shuttle mechanism/ thermostat.
3. Straighten transport tube.
4. Replace PC board.
5. Plug in gearmotor.
(see page 15 for “no current” details)
1. Air condition area to below 100˚F
(38˚C).
2. Reposition ice machine or properly ventilate. Prevent ice machine exhaust from recirculating.
3. Clean condenser grille.
4. Correct air flow.
• Remove any blockage from fan blades
• Replace PC board
• Replace fan motor
Page 27
Ice machine disposition Possible causes Corrective actions
Legend:
ON OFF
ON or OFF FLASHING
7. Ice machine is not making ice. Drain clog.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
8. Ice machine is making ice. Excessive water in bin or coming into bin from transport tube.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
9. Ice machine is not making ice. Lo water.
LOW BIN
AUGER ON
REFRIG ON
PURGE
TIME DELAY
CLEANING
SERVICE
HI AMPS
HI PRESS
DRAIN CLOG
HI WATER
CPU
LO WATER
1. Drain hose kinked or plugged causing water to back up.
2. Improper floor drain routing/pitch causing water to back up.
3. High TDS levels and leaking
POWER
drain solenoid may cause an errant drain clog.
1. Failed water sensors. Processor assumes there is no water when there is water.
2. Blocked reservoir vent.
3. Defective water feed solenoid valve. Stuck in open position.
POWER
1. Water supply is turned off.
2. Low water pressure.
POWER
3. Defective water feed solenoid valve. Stuck in closed position.
4. No water feed output from PC board.
1. Remove kink or blockage from drain hose.
2. Re-route floor drain.
3. Clean area around drain sensor and/or replace Drain solenoid valve.
1. Clean or replace water probe assembly. Check wiring connections.
2. Clean or replace vent tubes.
3. Replace water feed solenoid valve.
1. Turn water supply on. If evaporator was completely empty the reset button may have to be pressed to restart the ice machine.
2. Ice machine will eventually start when water reaches normal lo level.
3. Replace water feed solenoid valve.
4. Replace PC board.
27
Page 28
Replacement parts
Evaporator assembly
1
Order parts online www.follettice.com
2
3
5
4
6
7
20
21
22
10
18
23
28
36
19
18
17
24
30
16
23
27
32
31
23
18
35
17
15
9
8
12
11
24
23
14
13
25
33
26
24
29
34
28
37
41
40
38
23
28
39
Page 29
Order parts online www.follettice.com
Reference # Description Part #
1 Tube, ice transport, molded 00130666 2 Shuttle assembly (includes 00115600 & 00130666) 00130815 3 Switch, optical 00130849 4 Compression nozzle 00115774 5 Elbow, water 00134502 6 Gasket, shuttle 00115600 7 Stream divider 00142521 8 Auger bolt 00116988 9 Washer 00161513 10 Retainer, auger bolt 00161366 11 Kit, auger bolt (auger bolt, washer, retainer, nut and washer) 00161406 12 Key 00117804 13 Bolts, gearmotor mounting (4) 00130641 14 Gearmotor, 240V (includes capacitor) 00130807 15 Gasket, gearmotor 00121632 16 Main housing (includes 00112946 & 00116962) 00142539 17 Coupling, V-band 00130708 18 O ring 00116962 19 Seal, auger shaft 00112946 20 Cup, sanitizer 00130674 21 Gasket, sanitizer 00124032 22 Cap, sanitizer (includes 00124032) 00130880 23 Tubing, water, 3/8" OD 502719 24 Tubing, water, 1/4" OD 502079 25 Hardware, mounting, evaporator cap 00130989 26 Solenoid, water feed (240V) 00130831 27 Tee, water 00134494 28 Sensor assembly, water level and drain clog 00171363 29 Cap, evaporator (includes 00125468 & 00130989) 00130740 30 Clip, water shut-off valve 502922 31 Strainer, water 502920 32 Valve, shut-off, water 502921 33 Auger (includes 00112946 & 00116962) 00147256 34 Evaporator (includes 00112946, (2) 00116962 & 00121616) 00137570 35 Journal housing and bearing (includes (2) 00116962) 00130716 36 Reservoir, water 00130690 37 Base, evaporator 00130732 38 Boot, solenoid 00160309 39 Solenoid, purge (240V) 00130765 40 Insulation, evaporator 00121616 41 Spacers, solenoid 00160317 Not shown Insulation, evaporator cap 00125468
29
Page 30
Air-cooled assembly
Order parts online www.follettice.com
1
2
3
4
6
10
6
7
8
9
13
11
30
12
Page 31
Order parts online www.follettice.com
Reference # Description Part #
1 Condenser (includes 00130922) 00137588 2 Shroud, condenser 00137596 3 Fan motor assembly 00121566 4 Electrical box support 00156035 5 Cut-out, high pressure safety 00117077 6 Insulation, bulb, TXV 00106534 7 Drier 00134593 8 Valve, expansion, thermal (includes 502830 and 00106534) 00136317 9 Insulation, TXV 502830 10 Hardware, evaporator mounting base (set of four) 00130971 11 Compressor 00133652 12 Base, icemaker 00137604 15 Fan blade 00170290
31
Page 32
Water-cooled assembly
Order parts online www.follettice.com
1
3
2
4
14
5
6
7
8
10
9
16
15
6
11
12
13
15
11
17
32
18
12
13
Page 33
Order parts online www.follettice.com
Reference # Description Part #
1 Electrical box support 00156035 2 Elbow, water 00129486 3 Valve, water regulating 00131052 4 Union, water 202148 5 Cut-out, high pressure safety 00117077 6 Insulation, bulb, TXV 00106534 8 Drier 00134593 8 Valve, expansion, thermal (includes 502830 and 00106534) 00130997 9 Insulation, TXV 502830 10 Condenser, w/c 00117234 11 Elbow, water, 90˚ 00129478 12 Valve, shut-off, water 502222 13 Coupling 206411 14 Hardware, evaporator mounting base 00130971 15 Ty-rap 204584 16 Receiver 00123109 17 Compressor 00133652 18 Base, icemaker 00137604
33
Page 34
Electrical box
Order parts online www.follettice.com
1
2
6
3
7
4
5
8
9
10
11
12
13
15
14
34
Page 35
Order parts online www.follettice.com
Reference # Description Part #
1 Cover, electrical box, air/water-cooled 00130872 2 Board, control circuit, 240V (includes 00130906) 00132902 3 Stand off’s (set of 6) 00130906 4 Capacitor, compressor run 00133512 5 Clamp, run capacitor 00133603 6 Relay, compressor starting (includes wire harness) 00161810 7 Contactor 00117010 8 Capacitor, compressor starting 00133504 9 Cap, capacitor 00133587 10 Bracket, capacitor 207625 11 Switch, evaporator purge 00114371 12 Switch, evaporator clean 00117036 13 Switch, icemaker power 208867 14 Circuit breaker, 4 amp 00126912 15 Power lead, 240V 00135533
35
Page 36
Integration kit – top-mount and Satellite-fill
Top mount configuration
Order parts online www.follettice.com
12
10
13
2
2
11
4
5
6
7
8
Satellite-fill configuration
1
1
12
11
10
2
4
5
6
7
8
9
2
36
Page 37
Order parts online www.follettice.com
Reference # Description Part #
1 Shuttle actuator 00171322 2 Clamp 500377 3 Actuator elbow (includes 00167122 and 209100) 00171264 4 Screws 209100 5 Gasket 00167122 6 Actuator body 00171272 7 Gasket, coupling 00126532 8 Ring, locking (includes 00126532) 00171371 9 Ice transport tube, 10' (3m) 00171280 9 Ice transport tube, 20' (6m) 00171298 10 Insulation, transport tube 501176 11 Insulation, elbow 00168922 12 Insulation, actuator 00168930 13 Ice transport tube, top mount, 30" (762mm) 00171306 Not shown Integration kit, top mount 00171389 Not shown Integration kit, Satellite-fill (requires transport tube) 00171397 Not shown Extension-fill tube, 9" 00135723 Not shown Extension-fill tube, 4" 00153684 Not shown Follett SafeCLEAN ice machine cleaner (case of 24 x 7oz packets) 00132001 Not shown Sani-spong kit 00132068
37
Page 38
Skins assembly
208264
Stock Module Identification Plate
Service No.
Module No. Product
R
E
F
R
I
G
E
R
A
N
T
MO
D
E
L
M
O
T
O
R
C
O
M
P
R
E
S
SO
R
T
H
E
R
M
A
L
LY
P
R
O
T
E
C
T
E
D
E
a
s
to
n
P
e
n
n
s
y
l
v
an
i
a
U
FU
L
L
L
O
A
D
A
M
P
S
MA
X
.
B
R
A
N
C
H
C
I
R
C
U
I
T
F
U
SE
S
I
Z
E
M
I
N
.
B
R
A
N
C
H
C
I
RC
U
I
T
A
M
P
A
C
I
T
Y
D
E
S
I
G
N
P
R
E
S
S
U
RE
H
I
G
H
S
I
D
E
A
M
P
S
A
M
P
S
V
O
L
T
S
C
O
R
P
O
R
A
T
I
O
N
S
E
R
I
A
L
N
O
NS
F
P
H
A
S
E
S
I
N
G
L
E
C
H
A
R
G
E
LO
W
S
I
D
E
P
A
R
T
N
O
P
SI
G
T
HE
U
SA
M
A
D
E
I
N
O
Z
L
L
U
R
C
R
HZ
1
Order parts online www.follettice.com
2
7
3
6
5
4
15
a i n a
v yl
s n n
e P
O
n
N
o t
T
s
R
E
a
L
A
E
P
G N SI
E
S A H P
Z
Z
O
H
O
N
N
O
L I T
A
G
I
I
A
R
R
PS
E
O
S
P
E
R
G
ED
O
R
T
C
S
A
T
EC
L
H
T
C
O
O
V
N
R
I
P
E
E
D
D
A
I
LY
A
S
M
S
L
U
A
E
W
H
L
M
O
T
E
R
L
E
F
D
H
O
T
NS
M
R
O
S S E
S
R
P
P
M
M
A
O
D
C
A
R
O
O
L
T
L
O L U
M F
S P
M
E
T
A
D
N
I
A
S
H
ER
S
G
G
I
P
I R
H
M A
E
EF
R R
U
S
S E R
Y
P
T I
N
C A P
IG S
M
A
E
T
I
D
U
C
E R I
Z
I C
S
H
E S
C
U
N
F
A
R
IT
B
U
C N. I
R I
M
C
H C N A
BR . X A M
208264
Stock Module Identification Plate Module No. Product
Service No.
12
11
17
16
13
10
9
8
38
14
18
Page 39
Order parts online www.follettice.com
Reference # Description Part #
1 Grille, intake 00122846 2 Front cover, air- & water-cooled (includes 00122846) 00137612 3 Tubing, water, 1/4" OD 502079 4 Tubing, drain 00144923 5 Fitting, drain 00109728 6 Fitting, water inlet 502924 7 Elbow, water inlet 502925 8 Coupling (includes 00144675) 00171207 9 O ring 00144675 10 Bulkhead fitting 00171215 11 Nut 00145342 12 Hose clamp 500377 13 Power cord, 240V 00134445 14 Louvered docking assembly (includes 0123182) 00137620 15 Clamp, drain line 00114520 16 Screws 208568 17 Bulkhead connector kit 0017223 18 Cover, access, utility 00123182 Not shown Gasket, intake 00135574 Not Shown Louver, intake/exhaust (13.75"x17.75") 00128066
39
Page 40
Chewblet is a registered trademark of Follett Corporation, registered in the US.
801 Church Lane • Easton, PA 18040, USA Toll free (800) 523-9361 • (610) 252-7301 Fax (610) 250-0696 • www.follettice.com
00171587R00
05/07
Loading...