FNW XG User Manual

Figure XG
GAUGES & THERMOMETERS
LOW LEAD COMPLIANT
4-1/2” CONTRACTOR’S GAUGE
The contractor’s gauge is designed for a wide variety of industrial applications, but is especially suited for heating and air conditioning systems. The rugged gauge case is made of stainless steel to provide the protection needed in corrosive atmospheres. Connection and wetted internal components meet Federal lead free requirements.
Features:
• Dual Scale (PSI and kPa)
• +/- 1% Grade 1A Per ANSI/ASME B40.100
• Complies with Federal Lead-Free Law (Sec. 1417)
• 304SS Case and Bezel Ring
• Zero Adjustment Screw
• Lead Free Phosphor Bronze Bourdon Tube
• 1/4” Lead Free Brass MNPT Connection
• Brass Movement
• Black Anodized Aluminum Pointer
• White Aluminum Dial with Black and Red Markings
• Lead Free Silver Solder Welding
• Acrylic Lens
• 75% of Full Scale Working Pressure
• 25% Over-Pressure Limit
• -40°F to 150°F (-40°C to 65°C) Process and Ambient Temperature Limit
• IP52 Enclosure Rating
Low Lead Compliant: Referring to laws dening “Lead Free” as wetted surface of pipe, ttings and xtures in
potable water systems that have a weighted average
lead content ≤ 0.25% per the Safe Drinking Water Act
(Sec. 1417) amended 1-4-2011 as well as other state regulations.
LOW
LEAD
COMPLIANT
Dial Resolution
Range (PSI) PSI Per Mark
0 to 30 0.5
0 to 60, 100 1
0 to 160, 200 2
0 to 300 5
Part Numbers
Range (PSI) Part Number
0 to 30 FNWXG030R
0 to 60 FNWXG060R 0 to 100 FNWXG0100R 0 to 160 FNWXG0160R 0 to 200 FNWXG0200R 0 to 300 FNWXG0300R
DOC: FNWXG13 Ver. 10/2013
© 2013 - FNW. All rights reserved. The FNW logo is a trademark of Ferguson Enterprises, Inc., PL Sourcing, PO Box 2778, Newport News, VA 23609 www.fnw.com
The contents of this publication are presented for information purposes only, and while effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, expressed or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and
conditions, which are available on request. We reserve the right to modify or improve the designs or specications of our products at any time without notice. Always verify that you have the most recent product specications or other documentation prior to the installation of these products.