FMI VT32EN-A Series, VTC32EN Series, TC32EN Series, VT32EP-A Series, T32EP-A Series Owner's Operation And Instruction Manual

...
DIRECT-VENT FIREPLACE
PFS
USC
OWNER’S OPERATION AND INSTALLATION MANUAL
®
NATURAL GAS “TUDOR” MODELS (V)T32EN-A, (V)TC32EN SERIES
PROPANE/LP GAS “TUDOR” MODELS (V)T32EP-A, (V)TC32EP
SERIES
WARNING: If the information in this manual is not fol-
lowed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com
Safety Information ............................................... 2
TABLE OF CONTENTS
Product Identication ........................................... 5
Local Codes......................................................... 5
Product Features ................................................. 5
Pre-Installation Preparation ................................. 6
Location of Termination Cap ................................ 8
Requirements for the Commonwealth of
Massachusetts..................................................... 9
Venting Installation Instructions ......................... 10
Fireplace Installation.......................................... 19
Wiring Diagram .................................................. 28
SAFETY INFORMATION
WARNING: Improper in­stallation, adjustment, al-
teration, service or main­tenance can cause in-
jury or property damage.
Refer to this manual for correct installation and
operational procedures.
For assistance or addi­tional information con-
sult a qualied installer, service agency or the gas supplier.
This appliance may be in-
stalled in an aftermarket,*
permanently located, manufactured (mobile) home, where not prohib­ited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certied kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Operating Fireplace ........................................... 29
Inspecting Burners............................................. 30
Cleaning and Maintenance ................................ 29
Troubleshooting ................................................. 32
Replacement Parts ............................................ 35
Service Hints ..................................................... 35
Technical Service............................................... 35
Specications .................................................... 35
Parts List............................................................ 36
Accessories ....................................................... 40
Warranty Information ...........................Back Cover
State of Massachusetts: The installation must
be made by a licensed plumber or gas tter in
the Commonwealth of
Massachusetts.
WARNING: This product
contains and/or generates
chemicals known to the State of California to cause cancer or
birth defects or other reproduc­tive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, re, explosions, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This fireplace complies with the National Safety Standards and is listed and tested by PFS Corporation to ANSI Z21.50/CSA 2.22
standard as vented gas replace.
NOTICE: Decorative product not for use as a heating appliance.
www.fmiproducts.com
116647-01H2
SAFETY INFORMATION
Continued
This replace must be installed by a qualied (certied or licensed) service person. It has a sealed gas combustion chamber that uses a coaxial pipe (pipe within a pipe and having the same center) venting system. It brings in fresh air for combustion through the outer pipe
and combustion gases are exhausted through the inner pipe. If the glass door assembly and venting pipe are not properly seated, connected and sealed, carbon monoxide leakage
(spillage) can occur.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the u, with
headaches, dizziness or nausea. If you have these signs, the replace may not be working
properly. Get fresh air at once! Have replace serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease
or anemia, those under the inuence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gases are odorless. An odor-making agent
is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this replace.
WARNING: Any change to this replace or its controls can be
dangerous.
WARNING: Do not use a blower insert, heat exchanger insert or
other accessory not approved for use with this replace.
Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this replace. Use only the gas type indicated on replace name plate.
Carefully supervise young children when they are in the room with replace.
This replace reaches high temperatures. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
116647-01H 3
www.fmiproducts.com
SAFETY INFORMATION
Continued
Do not operate replace with glass door removed, cracked or broken.
Keep the appliance area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
Do not place clothing or other ammable material on or near re­place. Never place any objects on replace.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with
other gases unless a certied kit is used.
2. For propane/LP replace, do not place propane/LP supply tank(s) inside any
structure. Locate propane/LP supply
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank of less than 100 lb. capacity.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup­plier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains
or other combustible (ammable) objects can make contact with the replace front
• in high trafc areas
5. Do not modify this replace under any
circumstances. Any parts removed for servicing must be replaced prior to operat-
ing replace.
6. Turn fireplace off and let cool before servicing, installing or repairing. Only a
qualied service person should install, service or repair this replace. Have re­place inspected annually by a qualied
service person.
7. You must keep control compartments, burners and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before
cleaning replace.
8. Have venting system inspected annually
by a qualied service person. If needed,
have venting system cleaned or repaired. See Cleaning and Maintenance, page 30.
9. Do not use this replace to cook food or burn paper or other objects.
10. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70.
11. Do not use replace if any part has been
under water. Immediately call a qualied
service person to arrange for replacement of the unit.
12. Do not operate replace if log is broken.
13. Provide adequate clearances around air openings.
www.fmiproducts.com
116647-01H4
PRODUCT IDENTIFICATION
Upper Louver Panel
Door Screen
(TC32 Series)
Figure 1 - Direct-Vent Fireplace with Electronic Ignition
(T32 Series)
Glowing Embers
Burner Assembly
Electronic Control Valve
LOCAL CODES
Install and use replace with care. Follow all
local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI
Z223.1/NFPA 54*.
Glass Door Assembly
Lower Louver Panel
(T32 Series)
Switch Bracket for Optional Remote and Blower
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Flue Collar
Nailing Flange
Log Set
Grate Assembly
Lava Rock
PRODUCT FEATURES
These are a few facts that can help you un-
derstand and enjoy your direct-vent replace:
• The venting system may be routed to the
outside of your home in several ways. It
may vent through the roof (vertical) or it may vent to an outside/exterior wall (hori­zontal). The vent pipe installation is very
important to allow for proper operation. You must follow the venting instructions very carefully for either vertical or horizontal applications.
• This replace may be installed in any room
of your house provided all local codes and these installation instructions are followed.
• The blower requires electricity if installed.
If you plan to install the blower at a later date, outlet must be wired at the bottom of
the replace when framing.
116647-01H 5
www.fmiproducts.com
• The electronic ignition creates spark to
ignite the pilot light. It does not require any matches, batteries or any other sources of ignition to light the pilot.
• Each time you turn on your replace, you
may notice some amount of condensation
on the inside of the replace glass. This
is normal and will disappear after 10-20 minutes of operation.
Your direct-vent gas replace system (re­place and venting) is a balanced and sealed
gas operating unit. It requires approximately 10-20 minutes of operating time before the
ame pattern stabilizes.
D
RW
FW
PRE-INSTALLATION PREPARATION
LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efcient loca­tion for your FMI PRODUCTS, LLC direct-vent
replace. Make sure that rafters and wall studs
are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some com­mon locations. Be aware of all restrictions and precautions before deciding the exact location
for your replace and termination cap. When deciding the location of your replace,
follow these rules:
• Do not connect this replace venting to a chimney ue serving a separate solid-fuel burning replace or appliance.
• Due to high temperatures, do not locate this replace in high trafc areas, windy or
drafty areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on
carpeting, vinyl tile or any combustible ma­terial other than wood, it must be installed on a metal or wood panel extending the full
width and depth of the replace. See Figure
3.
Flush with a wall
Through exterior wall enclosed in a chase
Corner installation
Figure 2 - Common Fireplace Locations
22 1/2"
16 5/8"
34 3/8"
Figure 3 - Fireplace Bottom Dimensions
www.fmiproducts.com
• Your fireplace is designed to be used in
zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the back, sides or top of
your replace, except where standoff spacers
are integrally attached. If standoff spacers
are attached to your replace, these spacers
can be placed directly against wall or framing material. See framing details on page 7.
• If you plan on installing a television or
entertainment center recessed above
your replace, it is recommended that you
maintain a minimum 18" above top of louver opening.
• When locating termination cap, it is impor­tant to observe the minimum clearances shown in Figure 7, page 8.
• If recessing into a wall, you can avoid extra framing by positioning your replace
against an already existing framing mem­ber.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with 450º
F heat-resistant paint to coordinate with the
exterior nish.
• There must not be any obstruction such as
bushes, garden sheds, fences, decks or util­ity buildings within 24" from the front of the termination cap.
• Do not locate termination cap where exces­sive snow or ice build up may occur. Be sure to clear vent termination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 0" Perpendicular walls 6" Floor 0" Ceiling to louver opening 42" Front 36" Top 0"
Vent (See venting instructions for specic venting clearances.)
Combustible material with a maximum thick-
ness of 5/8" may be ush with the top front of replace.
* For back and sides of replace, do not pack
with insulation or other materials. 0" clear­ance to combustible materials are for framing purpose only.
116647-01H6
PRE-INSTALLATION PREPARATION
A
B
E
F
G
H
D
C
Nailing Tabs
C
B
A
D
E
F
G
Top of Louver Opening
3
2
1
4
5
6
7
Wall
Continued
NOTICE: This replace is in­tended for use as supplemental heat. Use this replace along with your primary heating sys­tem. Do not install this replace as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using replace. This will help circulate the heat throughout the house. In the event of a power outage, you can use this replace as a heat source.
FRAMING AND FINISHING
Figure 4 shows typical framing of this re­place. Figure 5 shows framing for corner installation. All minimum clearances must be met.
For available accessories for this replace,
see Accessories on page 40. If you are using a separate combustible mantel piece, refer to Figure 6 for proper installation height. You can install noncombustible mantels at any height above the replace. Note: Noncombustible mantels may discolor!
13 5/8"
10 3/8"
39 3/8"
28 1/2"
Nailing
97/8"
343/8"
Tabs
345/8"
541/8"
Figure 5 - Framing Clearances for Corner
Installation
323/8"
Figure 4 - Framing Clearances for
345/8"
17" (Horiz. Vent) 20" (Vert. Vent)
Ref.
Mantel
Depth Ref.
Mantel from Top of
Louver Opening
1 14" A 16" 2 12" B 14" 3 10" C 12" 4 8" D 10" 5 6" E 8" 6 4" F 6" 7 2" G 4"
Figure 6 - Clearances for Combustible
Mantels
Installation Against an Exterior Wall
116647-01H 7
www.fmiproducts.com
LOCATION OF TERMINATION CAP
D
E
V
B
L
A = clearance above grade, veranda, porch, deck, or balcony [*12" (30.5 cm) minimum] B = clearance to window or door that may be opened [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] C = clearance to permanently closed window [minimum 12" (30.5 cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24" (61 cm) from the center-line of the terminal [18" (45.7 cm) minimum] E = clearance to unventilated soffit [12" (30.5 cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within 36" (91.4 cm) horizontally from the center line of the regulator
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
† vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances
A
A = 6" (15.2 cm)
V
C
F
V
B
TERMINATION CAP
V
Fixed
Closed
Openable
V
Openable
B
AIR SUPPLY INLET
X
B
V
Fixed
Closed
B
J
V
X
A
I = clearance to service regulator vent outlet [*72" (182.9 cm) minimum] J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] K = clearance to a mechanical air supply inlet [*In Canada, 6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within 10 ft. (3 m) horizontally] L = † clearance above paved side-walk or a paved driveway located on public property [*84" (213.3 cm) minimum] M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡] N = clearance above a roof shall extend a minimum of 24" (61 cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18" (45.7 cm)
Outside Corner Recessed Location
V
B = 6" (15.2 cm)
B
H
I
G
G
GAS METERRESTRICTED AREA
M
(TERMINATION PROHIBITED)
C
N
N
G
V
G
V
K
V
X
A
D
C
E
V
Balcony with No Side Wall
G
V
G = 12" (30.5 cm) minimum clearance
Figure 7 - Minimum Clearances for Termination Cap
Balcony with Perpendicular Side Wall
H
V
J
Combustible & Noncombustible H = 24" (61 cm) J = 20" (50.8 cm)
www.fmiproducts.com
C = Maximum depth of 48" (121.9 cm) for recessed location D = Minimum width for back wall of recessed location ­ Combustible - 38" (965 mm) Noncombustible - 24" (61 cm) E = Clearance from corner in recessed location­ Combustible - 6" (15.2 cm) Noncombustible - 2" (5.1 cm)
116647-01H8
REQUIREMENTS FOR THE COMMONWEALTH OF
MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall ex-
haust vent termination is less than seven (7) feet above nished grade in the area of the venting,
including but not limited to decks and porches,
the following requirements shall be satised:
INSTALLATION OF CARBON MONOXIDE DETECTORS
At the time of installation of the side wall horizon­tal vented gas fueled equipment, the installing
plumber or gastter shall observe that a hard
wired carbon monoxide detector with an alarm
and battery backup is installed on the oor level
where the gas equipment is to be installed. In
addition, the installing plumber or gastter shall
observe that a battery operated or hard wired car­bon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualied licensed professionals for the installation
of hard wired carbon monoxide detectors. In the event that the side wall horizontally
vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next
adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery
operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
SIGNAGE
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than 1/2" in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
116647-01H 9
www.fmiproducts.com
INSPECTION
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
• The equipment listed in Chapter 10 entitled
"Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as
adopted by the Board; and
• Product Approved side wall horizontally
vented gas fueled equipment installed in a room or structure separate from the dwell­ing, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of
the venting system design or the venting
system components; and
• A complete parts list for the venting system
design or venting system.
Gas Equipment Venting System Not
Provided
When the manufacturer of a Product Ap­proved side wall horizontally vented gas fu­eled equipment does not provide the parts for
venting the ue gases, but identies "special
venting systems", the following requirements
shall be satised by the manufacturer:
The referenced "special venting system" in­structions shall be included with the appliance
or equipment installation instructions; and
• The "special venting systems" shall be Prod-
uct Approved by the Board, and the instruc­tions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting in­structions, all parts lists for venting instruc­tions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
VENTING INSTALLATION INSTRUCTIONS
NOTICE: Read these instruc-
tions completely before at­tempting installation.
These models are tested and approved for
use with FMI PRODUCTS, LLC (direct-vent)
pipe components and terminations. The venting system must terminate on the
outside of the structure and can not be at-
tached to a chimney or ue system serving a
separate solid fuel or gas burning appliance. A direct-vent appliance must have its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the following guidelines:
• When venting system terminates horizon­tally on an outside wall, you may install a standoff if the termination cap is to be
installed directly on a combustible nish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which
could cause a re.
• Vent pipe air space clearances to com-
bustibles are 1" on all sides except on the horizontal sections, which requires 2" clear­ance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
• Snorkel terminations are required when
minimum clearance to grade cannot be met
(see Figure 16 on page 14).
• Have replace and selected vent compo-
nents on hand to help determine the exact measurements when elbowing or offsetting.
Always use wall restops when penetrating walls and restops when penetrating ceil-
ings or attic spaces.
• If using a venting conguration of only
horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termination is required.
WARNING: Read all instruc-
tions completely and thoroughly before attempting installation.
Failure to do so could result in
serious injury, property damage or loss of life.
NOTICE: Failure to follow these
instructions will void the warranty.
IMPORTANT: Do not seal vent cap to pipe. Cap must be removable for service.
INSTALLATION PRECAUTIONS
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or
when on roof tops
• Be aware of electrical wiring locations in
walls and ceilings
The following actions will void the warranty on your venting system:
Installation of any damaged venting component
• Unauthorized modication of the venting system (Do not cut or alter vent compo­nents)
• Installation of any component part not
manufactured or approved by FMI PROD­UCTS, LLC
• Installation other than as instructed by
these instructions
WARNING: This gas replace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serv­ing a separate solid fuel burning appliance. Each direct-vent gas appliance must use a separate vent system. Do not use com­mon vent systems.
WARNING: Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which require 2" clearances from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
www.fmiproducts.com
116647-01H10
INSTALLATION PLANNING
(Framing
Detail)
11
1
/2"
11
1
/2" Inside Framing
11
1
/2"
8 1/2"
Vent Opening
Combustible Wall
Vent Opening
Noncombustible Wall
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall restop. Hori­zontal installations using round termination
require exterior portion of wall restop (see Figure 14, page 13).
1. Set the replace in its desired location and
determine the route your horizontal venting
will take. Do not secure the replace until
all venting has been installed. Some instal-
lations require sliding the replace in and out of position to make nal venting con-
nections. Figures 14 through 18 on pages
13 through 15 show different congurations
for venting with horizontal termination that will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may
want to adjust the location of the replace.
2. Direct vent pipe sections and components are designed with special twist-lock con­nections.
Twist-Lock Procedure: The female ends
of the pipes have locking lugs (inden­tations). These lugs will slide straight
into matching slots on the male ends
of adjacent pipes. Push pipe sections
together and twist one section clockwise approximately one-quarter turn until the
sections are fully locked (see Figure 8).
Note: Horizontal runs of vent must be supported every three feet. Use wall straps for this purpose.
3. Use a 45° elbow to connect venting
system to replace ue collar. The elbow
is designed to be twist-locked onto the
ue collar as described in step 2. IM­PORTANT: Do not attempt to alter the
configuration of the elbow by cutting, twisting, bending, etc.
4. Assemble the desired combination of pipe
and elbows to the replace ue collar. If
there are long portions of venting run, pre­assembled pipe sections may be installed as subassemblies for convenience.
5. Carefully determine the location where the vent pipe assembly will penetrate the outside wall. The center of the hole should line up with the center-line of the horizontal
116647-01H 11
VENTING INSTALLATION INSTRUCTIONS
Continued
vent pipe. Mark the wall for a 11 1/2" x 11
1
/2" square hole. Cut and frame the square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, such as masonry block or concrete, a 8 1/2"
hole with zero clearance is acceptable (see Figure 9).
WARNING: Do not recess
vent termination into any wall. This will cause a re hazard.
Female Locking Lugs
Male Slots
Figure 8 - Vent Pipe Connections
www.fmiproducts.com
Figure 9 - Vent Opening Requirements
Center of Hole
VENTING INSTALLATION INSTRUCTIONS
Continued
6. Noncombustible Exterior Wall: Position the horizontal vent cap in the center of the 8
1
/2" round hole and attach to the exterior wall with four screws. Note: The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete or other types of sidings. Before attaching the vent cap to exterior wall, run
a bead of non-hardening mastic (pliable sealant) around the outside edges to make
a seal between it and the outside wall.
Combustible Exterior Wall: For vinyl siding,
stucco or wood exteriors, a siding standoff may be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damag­ing the siding materials. Siding material must be cut to accommodate standoff. Bolt the vent cap to the standoff. Apply non-hardening mastic around outside edge of standoff. Position the standoff/ cap assembly in the center of the 111/2" square hole and attach to exterior wall
with wood screws provided (see Figure
11). The siding standoff must sit ush
against the exterior fascia material.
7. Combustible Exterior Wall Only: Slide the
wall restop over the vent pipe before connecting horizontal run to vent cap (see Figure 12).
8. Carefully move replace, with vent as-
sembly attached, toward wall and insert vent pipe into horizontal termination. The pipe overlap should be a minimum of 11/4"
(see Figure 13, page 13).
9. Combustible Exterior Wall Only: Slide wall
restop against interior wall surface and
attach with screws provided (see Figure
12). See Figure 13, page 13 for horizontal
termination details.
10. Place replace into position and shim with
noncombustible material if needed. Nail or
screw side anges to framing to secure unit in place. IMPORTANT: Make sure re- place is level before securing. If replace
is not level it will not work properly.
Cut Siding Away to Fit Standoff
Standoff
Wood Screw
Vent Cap
Screws
Apply Mastic to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior)
Interior Wall Surface
Wall Firestop
Apply Mastic to All Four Sides
Vent Cap
Wood Screw
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
www.fmiproducts.com
Vent Cap
(Horizontal Termination)
Screw
Horizontal Vent Pipe
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
116647-01H12
VENTING INSTALLATION INSTRUCTIONS
Minimum Pipe Overlap 11/4"
Wall Firestop
Siding Standoff
Screws
Continued
GROUND FLOOR INSTALLATION Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or square termination (up to 12" horizontal pipe)
• NOT FOR CORNER INSTALLATION
45° Elbow Horizontal High Wind Square Termination
Direct Vent Pipe
Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall
Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding
Horizontal Termination Congurations
Figures 14 through 18 show different con-
gurations and alternatives for venting with horizontal termination. Each gure includes
a chart with critical minimum and maximum dimensions which MUST be met. IMPOR-
TAN T: If using a venting conguration of only
horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termina­tion is required.
10 3/4" x 10 3/4" Framed Opening
Standoff Installed
High Wind Termination
Apply Mastic to Outside Edge of Standoff
Exterior Wall with Vinyl Siding
WARNING: Never run vent
downward as this may cause
excessive temperatures which could cause a re. Operation of improperly installed and main­tained venting system could result in serious injury, property damage or loss of life.
Adjustable
Pipe 12" Max.
Wall Firestop
Square Termination
Vertical (V) Horizontal (H)
29 3/4" 17" max.
45° Elbow
Wall Firestop
Figure 14 - Horizontal Termination
Conguration for Square or Round
Termination
Exterior Portion of Wall
Firestop (Round Termination Only)
Horizontal Round Termination
116647-01H 13
www.fmiproducts.com
VENTING INSTALLATION INSTRUCTIONS
Continued
CORNER INSTALLATION Recommended Applications:
• Corner ground oor installation
• Ground oor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
• Basement installation where one foot clearance from ground to termination is possible
Not to Exceed
Square Termination
Wall Firestop
Figure 15 - Horizontal Termination Conguration for Corner Installation Using One
SNORKEL TERMINATION INSTALLATION Recommended Applications:
• Installations requiring a vertical rise on
building exterior
• Any installation using snorkel termination
to achieve one foot above ground
(H) Limits
45° Elbow
Vertical (V) Required
Vertical (V) Vertical Pipe Horizontal (H)
*43 3/4" min. None 30" max. 53 3/4" min. 1 ft. 48" max. 65 3/4" min. 2 ft. 60" max. 77 3/4" min. 3 ft. 84" max.
89 3/4" min. 4 ft. 20' max.
* Ground Floor Corner Venting
Snorkel Termination
90° Elbow
As Required
for (V), See
Chart for Pipe Section Required
90° Elbow
Not to Exceed
(H) Limits
90° Elbow
Wall Firestop
45° Elbow
Snorkel terminations are available for instal­lations requiring a vertical rise on the exterior of the building. If installing snorkel termination below grade, you must provide proper drain­age to prevent water from entering snorkel
termination (see Figure 16). Do not back ll
around snorkel termination.
Snorkel
Termination
90° Elbow
12" Min.
Wall
Firestop
Square Termination
12" Min.
Snorkel
Termination
12" Min.
12" Min.
Adequate
Drainage
Figure 16 - Snorkel Termination Congurations for Below Ground Installation
www.fmiproducts.com
116647-01H14
VENTING INSTALLATION INSTRUCTIONS
Continued
HORIZONTAL SYSTEM INSTALLATION USING TWO 90° ELBOWS
The following congurations show the minimum vertical rise requirements for a horizontal
system using two 90° elbows.
Venting with Two 90° Elbows
Horizontal (H1) +
Vertical (V) Horizontal (H1) Horizontal (H2)
5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' max. 20' max. 20' max. 8' max. 20' max.
45° Elbow
Figure 17 - Horizontal Termination Conguration for Venting Using Two 90° Elbows
Venting with Two 90° Elbows
Horizontal (H1) +
Vertical (V) Horizontal (H2)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max. 20' max. 20' max.
Figure 18 - Horizontal Termination Conguration for Venting Using Two 90° Elbows
116647-01H 15
with Termination at 90° with Fireplace
www.fmiproducts.com
45° Elbow
VENTING INSTALLATION
INSTRUCTIONS
Continued
INSTALLATION FOR VERTICAL
TERMINATION
Note: Vertical restrictor must be installed in all vertical installations.
1. Determine the route your vertical venting
will take. If ceiling joists, roof rafters or
other framing will obstruct the venting
system, consider an offset (see Figure 19)
to avoid cutting load bearing members. Note: Pay special attention to these instal­lation instructions for required clearances
(air space) to combustibles when passing
through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum verti­cal rise of the venting system and any maximum horizontal offset limitations.
2. Set the replace in desired location. Drop
a plumb line down from the ceiling to the
position of the replace exit ue. Mark the
center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.
Drop a plumb line from the inside of the
roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.
Roof Flashing
Wall Strap
45° Elbow
Flat Ceiling Installation
1. Cut a 11 1/2" square hole in the ceiling us-
ing the locating hole as a center point. The opening should be framed to 11 1/2" x 11
1
/2" inside dimensions, as shown in Figure
9 on page 10 using framing lumber the
same size as the ceiling joists. If the area
above the ceiling is an insulated ceiling
or an attic, nail restop from the top side.
This prevents loose insulation from falling into the required clearance space. If the area above the ceiling is a living space,
install restop below the framed hole. The restop should be installed with no less than three nails per side (see Figure 20).
2. Assemble the desired lengths of pipe
and elbows necessary to reach from the
replace ue up through the restop. Be
sure all pipe and elbow connections are
fully twist-locked (see Figure 8, page 10).
3. Cut a hole in the roof using the locating
hole as a center point. (Cover any ex­posed open vent pipes before cutting hole
in roof.) The 11 1/2" x 11 1/2" hole must be measured on the horizontal; actual length
may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materi­als. Frame the opening as shown in Figure 9, page 11.
4. Connect a section of pipe and extend up
through the hole.
Note: If an offset is needed to avoid ob-
structions, you must support the vent pipe every 3 feet. Use wall straps for this pur-
pose (see Figure 19). Whenever possible,
use 45° elbows instead of 90° elbows. The
45° elbow offers less restriction to the ow of the ue gases and intake air.
5. Place the ashing over the pipe section(s)
extending through the roof. Secure the
base of the ashing to the roof and fram­ing with roong nails. Be sure roong
material overlaps the top edge of the
ashing as shown in Figure 19. There
must be a 1" clearance from the vent pipe to combustible materials.
If area above is an attic or insulated
area, install restop
above framed hole.
If area above is living
space, install restop
below framed hole.
Ceiling Firestop
Figure 19 - Offset with Wall Strap and 45°
Elbows
www.fmiproducts.com
Figure 20 - Installing Firestop
116647-01H16
VENTING INSTALLATION
INSTRUCTIONS
Continued
6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements described in Figure 7 on page 8. Note: You must in­crease vent height for steep roof pitches.
Nearby trees, adjoining rooines, steep
pitched roofs and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.
7. Twist-lock the vent cap onto the last sec­tion of vent pipe.
Note: If the vent pipe passes through any oc-
cupied areas above the rst oor, including
storage spaces and closets, you must enclose pipe. You may frame and sheetrock the en­closure with standard construction material. Make sure and meet the minimum allowable
clearances to combustibles. Do not ll any of
the required air spaces with insulation.
Vertical Termination Congurations
Figures 21 through 24 show four different
congurations for vertical termination.
Venting with Two 90° Elbows
Horizontal (H1) +
Vertical (V) Horizontal (H2)
5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.
45° Elbow
Venting with One 90° Elbow
Vertical (V) Horizontal (H)
5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.
45° Elbow
Note: Install restrictor into inner collar of
replace as shown.
Figure 22 - Vertical Venting Conguration
Using One 90° Elbow (Vertical Round
High Wind Termination Shown)
Note: Install restrictor into inner collar of
replace as
shown.
45° Elbow
Note: Install restrictor into inner collar of
replace as
shown.
Figure 21 - Vertical Venting
Conguration Using Two 90° Elbows
with Two Horizontal Runs (Vertical
Round High Wind Termination Shown)
116647-01H 17
www.fmiproducts.com
Note: Vertical (V1) + Vertical (V2) = 40' max.
Figure 23 - Vertical Venting Conguration
Using Two 90° Elbows (Vertical Round
High Wind Termination Shown)
Venting with Two 90° Elbows
Vertical (V1) Horizontal (H)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max.
VENTING INSTALLATION
INSTRUCTIONS
Continued
Vertical Venting
V = 40' max.
Note: Install restrictor into inner
collar of replace
as shown.
45° Elbow
Figure 24 - Vertical Venting
Conguration With No Horizontal Run
(Vertical Round High Wind Termination
Shown)
HIGH ALTITUDE INSTALLATION
Your FMI PRODUCTS, LLC direct-vent
replace has been tested and approved for
elevations from 0-2,000 feet.
When installing this replace at an elevation
above 2,000 feet, you may need to decrease the input rating by changing the existing
burner orice to a smaller size. Reduce input
4% for each 1,000 feet above sea level. Check
with your local gas company for proper orice size identication.
Consult your local gas company to help de-
termine the proper orice for your location.
For assistance with any high altitude installa­tion contact FMI PRODUCTS, LLC’s Custom­er Service Department at 1-866-328-4537.
PARTS LIST FOR VENTING KITS
AND COMPONENTS
FMI PRODUCTS, LLC (5"/8") Pipe & Vent Kits Number Description
P58-6 6" Section Double Wall Pipe, Galvanized
P58-12 12" Section Double Wall Pipe, Galvanized
P58-24 24" Section Double Wall Pipe, Galvanized
P58-36 36" Section Double Wall Pipe, Galvanized
P58-48 48" Section Double Wall Pipe, Galvanized
PA58-712 Adjustable 7"-12" Section Double Wall Pipe, Galvanized
E58-45 45° Elbow, Galvanized E58-90 90° Elbow, Galvanized VKG-58 Ground Floor Vent Kit, Galvanized
(Includes: 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop,
Horizontal Square Termination,
16 Screws)
VKB-58 Basement Vent Kit, Galvanized
(Includes: 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop,
Horizontal Square Termination,
4' Pipe, 90° Elbow, 20 Screws)
VKS-58 Snorkel Vent Kit, Galvanized
(Includes: 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop,
36" Snorkel Termination, 4' Pipe,
1' Pipe, 90° Elbow, 26 Screws)
VKR-58 Roof Vent Kit, Galvanized
(Includes: 45° Elbow, 7"-12" Adjustable Pipe, Flue Restrictor,
Vertical High Wind Termination, 2' Pipe, 4' Pipe, Wall Firestop, Storm Collar, Roof Flashing
[0/12 - 6/12], 26 Screws)
VKC-58 Corner Vent Kit, Galvanized
(Includes 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop,
Horizontal Termination, 6" Pipe,
90° Elbow, 18 Screws)
www.fmiproducts.com
116647-01H18
VENTING INSTALLATION
INSTRUCTIONS
Number Description
Continued
HHTK-58 High Wind Round Horizontal Termination Kit (Includes Round Termination, Wall Firestop,
45° Elbow)
HHT-58 High Wind Round Termination Kit, Galvanized
HTK-58 Horizontal Round Termination Kit
(Includes Round Termination, Wall Firestop, 45° Elbow)
HT-58 Horizontal Round Termination, Galvanized
HTS-58 Horizontal Square Termination, Galvanized
HTKS-58 Horizontal Square Termination Kit
(Includes: Square Termination, Wall Firestop, 45° Elbow)
HTS-58 Horizontal Square Termination, Galvanized
VT-58 Vertical Round Termination, Galvanized
ST-58-14 14" Snorkel Termination, Galvanized
ST-58-36 36" Snorkel Termination, Galvanized
SC-58 Storm Collar, Galvanized WF-58 Wall Firestop, Galvanized RF-58-6 Roof Flashing - 0 to 6/12 Pitch,
Galvanized RF-58-12 Roof Flashing - 6/12 to 12/12
Pitch, Galvanized VR-58 Vertical Restrictor, Galvanized S-58 Vinyl Siding Standoff,
Galvanized WS-58 Wall Strap CS-58 Cathedral Ceiling Support FP-58 Firestop Plate SF-58 Stucco Flashing - For use
with HTS-58 RF-58 Flat Roof Flashing
116647-01H 19
www.fmiproducts.com
CHECK GAS TYPE
Use proper gas type for the replace unit you
are installing. If your gas supply is not correct,
do not install replace. See retailer where you purchased the replace for proper replace
according to your gas type or to purchase gas
conversion kit (see Accessories, page 40).
INSTALLING OPTIONAL BLOWER ACCESSORY
NOTICE: If installing blower in an existing replace with gas connections, shut off gas supply and disconnect replace from gas supply. Contact a qualied service person to do this.
electrical outlet installed in the
right side of the bottom of the replace base area, be sure that the electrical power to the outlet is turned off before proceeding with blower installation. Failure to do this may result in serious injury.
Model BK Installation
Follow all instructions provided in the blower accessory kit.
1. Attach the power cord to the blower motor
by rmly pushing the two female terminals
at the end of the power cord onto the two
spade terminals on the blower motor (see Figure 25).
2. Attach green ground wire from power cord to blower housing using screw provided
(see Figure 25). Tighten screws securely.
FIREPLACE
INSTALLATION
WARNING: If there is a duplex
Side View
Lower Firebox Cavity
Spade Terminals
Green Ground Wire
Screw
Figure 25 - Blower Model BK
Exhaust Port
Blower Location
Magnetic Strips
FIREPLACE
Var
iable
Fan Switch
White
White
Black
Green
On
110/11
5
V.A.C.
Blower Motor
Black
Black
Black
Off
INSTALLATION
Continued
3. Place the blower against the lower rear
wall of the rebox outer wrapper with the
exhaust port directed upward. The blower
will t inside the back opening and be held
in position against the back wall by the
magnets (see Figure 25, page 19).
4. Be certain that all wire terminals are securely attached to terminals on blower motor and that the screw retaining the green ground wire is tight.
5. Mount speed control box to switch bracket by placing the plastic control shaft forward through the opening in the switch bracket
(see Figure 26).
6. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against front panel. Place control knob provided on shaft.
7. Turn on power to duplex outlet if pre­viously turned off per the warning in column 2, page 19.
8. Plug in blower power cord. a. If your rebox is installed as a free-
standing unit with an accessory man­tel, determine whether the power cord will exit the left side or the right side of
the rebox. Route power cord through
exit hole and plug the power cord into
a wall receptacle near the rebox.
b. If your rebox installation is recessed
and/or pre-wired, plug the power cord into the duplex outlet provided. Refer
to your rebox owner’s manual for
instructions on wiring the duplex outlet.
CAUTION: Never touch the
blower wheel while in operation.
9. Check to make sure that the power cord is completely clear of the blower wheel and
that there are no other foreign objects in
blower wheel. Turn blower on and check for operation. Turn blower off by turning knob fully counterclockwise before continuing.
10. Peel off the backing paper and stick the supplied wiring diagram decal on the
rebox bottom approximately 12" in front of the blower (see Figure 27).
www.fmiproducts.com
Locknut
Speed Control
Control Shaft
Blower Plug-In
Duplex Outlet
(Located
underneath
rebox oor
Switch Bracket
Control Knob
against lower right outside
wall)
Figure 26 - Attaching Speed Control to
Firebox
Wiring Diagram Decal 12" in Front of Blower
Figure 27 - Location of Wiring Diagram
Decal (Model May Vary From Illustration)
Model BKT Installation
Note: The BKT blower is for application into direct-vent models only. When installing the BKT thermostatically-controlled blower, you
must rst secure the wiring connections from the thermal switch to the blower (if it has not already been factory installed).
1. Attach green ground wire from power cord to blower housing using screw provided
(see Figure 28) Tighten screws securely
with a Phillips screwdriver.
2. Connect wire harness and power cord
terminals. Connect the jumper wire to
the blower motor terminal to the terminal of the thermal switch. Connect one wire of the thermal switch and one wire to the other remaining blower motor terminal.
Note: The power cord outer insulation sleeve may have to be stripped slightly to allow enough wire length to reach and make all connections. DO NOT trim excessive length away. Just enable enough to make all con­nections securely.
116647-01H20
Blue
Variable
Fan Switch
Fan Switch
(N.O.)
Green
White
On
110/115
V.A.C.
Blower
Motor
Black
Off
1
2
Black
FIREPLACE INSTALLATION
Continued
3. Place the blower against the lower rear
wall of the rebox outer wrapper with
the exhaust port directed upward. Attach Thermal disc magnetic bracket to the bot-
tom of the rebox sub-oor. The thermo­disc must be oriented near the replace
Thermal Disc Magnetic Bracket Assembly
Power Cord
bottom as shown in Figure 28, in order to sense temperature and properly operate. The blower will be held in position against the back wall by the magnets incorporated
onto the blower housing (see Figure 28).
4. Be certain that all wire terminals are securely attached to terminals on blower motor and that the screw retaining the green ground wire is tight.
5. Mount the speed control box against the
To Thermal Switch
Phillips Screw
Jumper Wire
mounting plate provided in the lower re­place cavity by placing the plastic control
shaft forward through the round hole (see Figure 26, page 20).
6. While supporting speed control, secure
Thermodisc
control shaft with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against mounting plate. Place
control knob provided on shaft (see Figure 26, page 20).
7. Check to make sure that the power cord is completely clear of the blower wheel and
Route BKT Blower Through This Area
Side View Firebox Bottom
Figure 28 - Blower Model BKT
that there are no other foreign objects in
blower wheel. Also double check all wire leads and make sure wire routing is not
Blower Wiring Diagram
pinched or in a precarious position. Correct accordingly.
8. Turn on power to duplex outlet if previ­ously turned off per the warning in column 2, page 19.
9. Plug in blower power cord to duplex outlet.
10. The blower will only run when the speed control knob is in the ON position and
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dan­gerous operation. Verify proper operation after servicing.
the thermal switch senses temperature
after the replace begins to heat up. The blower speed can be adjusted by rotating
the control knob. To turn off, turn knob fully counterclockwise until it clicks off. If the blower is ON and has been running with the
replace operating, the blower will continue to run for a short time after the replace has
been turned off. As the thermal switch cools down, the blower shuts down automatically.
11. Peel off the backing paper and stick the supplied wiring diagram decal on the
rebox bottom approximately 12" in front of the blower (see Figure 27, page 20).
116647-01H 21
Figure 29 - Blower Wiring Diagram for
Thermostat-Controlled Models
www.fmiproducts.com
To Blower Motor Terminal
Air Flow Direction
Ring Terminal on Green Wire
Blower Location
Magnets
Magnetic Strips
Air Flow Direction
FIREPLACE INSTALLATION
Continued
INSTALLING GAS PIPING TO FIREPLACE LOCATION
WARNING: A qualified service person must connect replace to gas supply. Follow all local codes.
CAUTION: For propane/LP units, never connect replace directly to the propane/LP sup­ply. This replace requires an external regulator (not supplied). Install the external regulator be­tween the replace and propane/ LP supply.
Installation Items Needed
Before installing replace, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connec­tor (if allowed by local codes)
* An equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the equipment shutoff valve from your retailer.
For propane/LP connection only, the installer must supply an external regulator. The exter­nal regulator will reduce incoming gas pres­sure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, re­place regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 30. Pointing the vent down protects it from freezing rain or sleet.
www.fmiproducts.com
CAUTION: Use only new,
black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" inside diameter or greater to allow proper gas volume to replace. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up.
NPT tap must be upstream from replace (see Figure 31).
External Regulator
Vent Pointing Down
Figure 30 - External Regulator with Vent
Pointing Down (Propane/LP Only)
Equipment Shutoff Valve with 1/8" NPT Tap*
Approved Flexible Gas Line
3" Minimum
Cap Pipe Nipple Tee Joint
Sediment Trap/Drip Leg
Figure 31 - Gas Connection
* The equipment shutoff valve may be sup­plied with the appliance or you can purchase it from your retailer.
Propane/LP Supply Tank
Natural - From
Gas Meter (5.5"
W.C. to 10.5"
W.C. Pressure)
Propane/LP From External
Regulator (11"
W.C. to 14"
W.C. Pressure)
116647-01H22
FIREPLACE
INSTALLATION
Continued
IMPORTANT: Install main gas valve (equip­ment shutoff valve) in an accessible location.
The main gas valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff
valve to replaces. Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could
result in clogged replace valves.
Red Surface
Equipment Shutoff Valve
1/2" NPT Incoming Gas Line
Note: Wire Connections Not Shown for Clarity
Figure 32 - Connecting Flexible Gas Line
Flexible Gas Line Do NOT Kink
Inlet Pressure Tap
to Electronic Valve
Indicates For Propane/LP Use Only
Outlet Pressure Tap
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 31, page 22. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and
replace. Locate sediment trap/drip leg where
trapped matter is not likely to freeze. A sedi­ment trap traps moisture and contaminants.
This keeps them from going into replace
gas controls. If sediment trap/drip leg is not
installed or is installed wrong, replace may
not run properly.
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not provided)
1. Open lower louver door panel by gen­tly pulling forward.
2. Route exible gas line (provided by installer) from equipment shutoff valve to replace. Route exible gas supply
line through one of the access holes
on side of replace.
3. Attach exible gas line from gas supply to control valve (see Figure 32).
4. Check all gas connections for leaks. See Checking Gas Connections.
116647-01H 23
www.fmiproducts.com
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and external to unit, for leaks after
installing or servicing. Correct all leaks at once.
WARNING: Never use an open ame to check for a leak. Apply noncorrosive leak detection uid to all joints. Bubbles forming show a leak. Correct all leaks at once.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2
psig (3.5 kPa) will damage replace gas
regulator.
2. Cap off open end of gas pipe where equip­ment shutoff valve was connected.
3. Pressurize supply piping system by either opening propane/LP supply tank valve for
propane/LP gas replace or opening main
gas valve located on or near gas meter for
natural gas replace or using compressed
air.
4. Check all joints of gas supply piping sys­tem. Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Reconnect fireplace and equipment shutoff valve to gas supply. Check recon-
nected ttings for leaks.
FIREPLACE INSTALLATION
Continued
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure
33).
2. Pressurize supply piping system by either opening propane/LP supply tank valve for
propane/LP gas replace or opening main
gas valve located on or near gas meter for
natural gas replace or using compressed
air.
3. Check all joints from propane/LP supply tank
for propane/LP or gas meter for natural
gas to equipment shutoff valve (see Figure 34 or Figure 35). Apply noncorrosive leak detection uid to all joints. Bubbles forming
show a leak. Correct all leaks at once.
Equipment Shutoff Valve
Figure 33 - Equipment Shutoff Valve
Equipment Shutoff Valve
Propane/LP Supply Tank
Open
Closed
PRESSURE TESTING FIREPLACE GAS CONNECTIONS
1. Open equipment shutoff valve (see Figure
33).
2. Open propane/LP supply tank valve for
propane/LP replace or main gas valve
located on or near gas meter for natural
gas replace.
3. Make sure control knob of replace is in
the OFF position.
4. Check all joints from equipment shutoff valve to gas valve (see Figure 34 or Figure
35). Apply noncorrosive leak detection uid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Light replace (see Operating Fireplace, page 29). Check all other internal joints
for leaks.
6. Turn off replace (see To Turn Off Gas to Appliance, page 29).
REMOVING/REPLACING GLASS
DOOR
Figure 34 - Checking Gas Joints for
Gas Valve
Propane/LP Gas Fireplace
Equipment Shutoff Valve
Gas Meter
Gas Valve
Figure 35 - Checking Gas Joints for
Natural Gas Fireplace
CAUTION: Do not operate this replace with a broken glass door panel or without the glass door panel securely in place. For replacement part information see Replacement Parts, page 35.
CAUTION: Wear gloves and safety glasses while handling or removing broken glass. Do not remove if glass is hot. Keep chil­dren and pets away from glass.
WARNING: If replace has been running, turn off and un­plug replace. Let cool before removing glass door or louvers.
www.fmiproducts.com
116647-01H24
FIREPLACE INSTALLATION
Lock
Unlock
Continued
Removing Louver Panels
Remove the top and bottom louver panels by simultaneously pulling both top end spring latches towards the center of the appliance until they are disengaged from the locating
holes (see Figure 36). Repeat for bottom
spring latches and pull the louvers outward. To install or replace items removed, simply reverse the procedures above.
Spring Latch
Louver Panel
Figure 36 - Removing Louver Panel
Removing Screen Door Assembly (TC32 Series)
Push screen door assembly in toward the bottom left and right sides until the magnetic door latch pops the screen door out. Hold the screen door assembly at the bottom and swing the door up to disengage the tabs on the top of the door from inside the slots un­derneath the upper face.
Door Screen Tabs
(TC32 Series)
Slots underneath Upper Face
Replacing Screen Door Assembly (TC32 Series)
Push magnetic door latch out to the open position. Position screen door tabs with slot openings in upper face frame. Swing door screen assembly in towards the bottom face, Press in on the bottom of door screen until magnetic door latch is pushed in.
Removing Glass Door
If replacement of glass is necessary, the entire assembly, glass and frame, must be replaced. If glass is broken, wear gloves and tape the remaining fragments onto the frame.
1. Remove screen assembly by pushing the rod either left or right and then down and forward to remove screen/rod assembly
from the rebox. Set assembly aside.
2. Lift up on latches to unlock. There are two
on top of rebox and two below rebox that hold glass door in place (see Figure 38).
3. While holding glass door to prevent it from
falling and causing injury, remove the ve
screws from the hinge located on the left side
of door frame assembly (see Figure 38).
4. Remount the new frame at the hinge with
ve new screws before closing door. This
will ensure seating of the gasket.
5. Close glass door frame. Lock latches by plac­ing the bar under the tab on door and pushing
down and back on latch (see Figure 38).
6. Replace screen/rod assembly by revers­ing step 1.
7. Replace louvers by reversing procedure under Removing Louver Panels, for T32 series.
8. Replace screen door assembly, see remov-
ing screen door assembly, (for TC32 series).
Cleaning Glass Door
See Cleaning and Maintenance on page 30.
Latch
Screw
Magnetic Door Latches
(TC32 Series)
Figure 37 - Removing/Replacing Screen
Door Assembly (TC32 Series)
Hinge
Glass Frame Assembly
Figure 38 - Removing/Replacing Glass
Door
116647-01H 25
www.fmiproducts.com
FIREPLACE INSTALLATION
1
Continued
INSTALLING OPTIONAL BRICK
LINER MODEL BL32D
WARNING: If replace has been running, turn off and un­plug replace. Let cool before installing brick liner.
This brick liner kit is optional. You may pur­chase brick liner from your local retailer or see page 35.
CAUTION: Always handle
brick panels with two hands. Do not force brick panels into place. Excessive force will break brick panels.
1. Remove top and bottom louvers to allow access to door latches.
2. Unlock door latches and open glass door. See steps 1 and 2 of Removing/Replacing Glass Door, page 24.
3. If installing brick liner in new replace,
go to step 4. If installing brick liner in an
existing replace, carefully remove logs,
lava rock and ember material.
4. Remove three screws from deflector
shield on the inside top of rebox. Set
shield and screws aside.
5. Install rear brick panel rst. Rest bottom edge of panel on back edge of grate (see Figure 39).
6. Install left side brick panel by sliding it between the grate and the side of the
rebox (see Figure 40).
7. Install the right brick panel using the same method described
8. Replace deector shield using screws
removed in step 4.
9. Follow instructions beginning in column 2 to install logs, lava rock and ember mate­rial.
10. Close glass door, lock latches on top and
bottom of door and replace screen (see
steps 5 and 6 of Removing Glass Door,
page 25).
11. Close top and bottom louvers.
Left Side Brick Panel
Figure 40 - Installing Side Brick Panels
INSTALLING LOGS, LAVA ROCK
AND GLOWING EMBERS
It is very important to install these logs exactly as instructed. Do not modify logs. Only use
logs supplied with replace.
Open louvers, remove screen, unlock door latches and open glass door. See steps 1 and 2 of Removing Glass Door, page 25. Install
logs according to instructions for replace
model numbers.
1. Find and place log #1 (rear log). The log has a at bottom with a slit cut into it to sit over the grate ap, (see Figure 41).
Rear Brick Panel
Figure 39 - Installing Rear Brick Panel
www.fmiproducts.com
Grate Flap
Grate
Slit Cut Underneath Log
Figure 41 - Installing Log No. 1
116647-01H26
FIREPLACE INSTALLATION
2
3
4
5
6
Continued
2. Rest log #2 (front log) on pins on front part of grate (see Figure 42).
Grate
Metal Pins
5. Place log #5 (base log) onto front left part of grate making sure log ts over metal pin
of grate. See Figure 45.
6. Place log #6 (left log) onto pin on left side
of front log, the rear part of log rests over
the log no. 1 (See Figure 45).
Rear Log
Metal Pins
Figure 42 - Installing Log No. 2
3. Place log #3 (crossover log) onto front log.
Make sure it is seated properly on surface of rear log and pin on front log as shown in Figure 43.
Rear Log
Figure 45 - Installing Logs No. 5 and No. 6
7. Place lava rock along sides and front of
rebox bottom in areas that are visible
only. It is not necessary to use all of the lava rock provided.
NOTICE: Do not put lava rock on burner or under burner. Placing lava rock on burner will cause
Front Log
Metal Pin
Figure 43 - Installing Log No. 3
4.
Place log #4 (right log) onto the landing on
right side of front log as shown in Figure 44.
Front Log
116647-01H 27
Log Landing
Figure 44 - Installing Log No. 4
www.fmiproducts.com
performance problems.
8. Pull ember material apart into pieces no larger than a dime. Place these pieces loosely and sparingly directly onto exposed section of front burner and along space
between burner and grate prongs (see Figure 46). This will create the glowing ember appearance as the ame touches
the ember material. Do not block air slots by using too much ember material in one area. Place small pieces of ember material to cover pilot ports. It is not necessary to use all of the ember material provided.
Ember Material
Figure 46 - Placing Ember Material on
Burner
9. Close glass door, lock door latches, replace
screen and close louvers (see steps 5 and 7 of Removing Glass Door, page 25).
FIREPLACE INSTALLATION
EV2
EV1
ORANGE
IGNITOR LEAD
GREEN
PILOT
TRANSFORMER
IS1070B
SYNETEK CONTROLS INC
24V AC
E4
E2
E3
E6
RED
E8
E12
BLUE
120V AC
GROUND
BLACK
WHITE
Continued
WALL SWITCH INSTALLATION
The installation of a wall switch allows you to ac-
tivate the gas control valve and turn the replace
on and off. The wall switch is to be connected to the incoming 120 volt regular household wir-
ing that supplies the electricity to the replace.
OPTIONAL REMOTE CONTROL INSTALLATION (Model WRC)
Note: If using optional wireless hand-held re­mote control, the wall switch must be in the ON position to be operational. The remote control then becomes the switching mechanism for
replace operation.
1. Open lower louver panel.
2. The WRC model receiver does not require a
battery. The receiver can be installed by rst
plugging the short extension cord into the
replace receptacle. Then plug the receiver
unit into the extension cord. Finally plug the ignition module plug into the receiver unit
(see Figure 47).
3. Activate the remote handset battery by removing the insulating tab on the back of
the handset (see Figure 48). The battery
is included pre-installed.
4. Once the battery is activated the unit is ready to use.
5. Close lower louver panel.
WIRING DIAGRAM
Fireplace Receptacle
Remote Control Receiver
Ignition Module
Extension Cord
Plug
Figure 47 - Installing the WRC Remote
Receiver
Battery Cover
12 Volt Battery
Back of Handset
Pull to Remove Insulation Tab
Figure 48 - Installing Battery into Back
of Handset
www.fmiproducts.com
116647-01H28
OPERATING FIREPLACE
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result causing property damage, per­sonal injury or loss of life.
A. This appliance is equipped with an igni-
tion device which automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch.
• Do not use any phone in your build-
ing.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas sup-
plier, call the re department.
C. Do not use this appliance if any part
has been under water. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
NOTICE: During initial operation
6. Wait ve (5) minutes to clear out any gas. Then smell for gas, including near the oor. If you smell gas, STOP! Fol-
low “B” in the safety information on
page 6. If you don’t smell gas, go to the next step.
7. Turn equipment shutoff valve counter­clockwise to the ON position. Do not force.
8. Close lower louver panel.
9.
Turn on all electric power to the appli­ance.
10. Turn the wall switch to the ON position.
11. Visually locate the pilot. The ignitor should begin to spark and the main burner should ignite once ame appears at pilot.
• If lighting the appliance for the rst
time each season, it may take several
attempts before the supply gas can reach the pilot and main burners.
• If the appliance will not stay lit after
several attempts, follow the instruc-
tions To Turn Off Gas To Appliance and call your service technician or
gas supplier.
Pilot Adjustment Screw
Equipment Shutoff Valve
Figure 49 - Turning Equipment Shutoff
Valve to the OFF Position
Sensing
Pilot Burner
Rod
Ignitor
of new replace, burning logs will give off a paper-burning smell. Orange ame will also be present. Open damper or window to vent smell. This will only last a few hours.
1. STOP! Read the safety information.
2. Turn off all electric power to the appli­ance.
3. Turn wall switch to the OFF position.
4. Open lower louver panel.
5. Turn equipment shutoff valve clockwise
116647-01H 29
to the OFF position (see Figure
49). Do not force.
www.fmiproducts.com
1. Turn off the wall switch.
2. Turn off all electric power to the appli­ance if service is to be performed.
3. Open lower louver panel.
4. Remove front hearth brick and control access panel.
5. Turn equipment shutoff valve clock­wise to OFF. Do not force.
6. Close lower louver panel.
Figure 50 - Pilot
TO TURN OFF GAS
TO APPLIANCE
OPERATING FIREPLACE
Continued
OPTIONAL REMOTE
OPERATION
Note: The WRC receiver and hand-held
remote control kit must be purchased separately (see Accessories, page 39). Follow installation instructions on page 27.
1. Turn equipment shutoff valve to ON posi­tion. You can now turn the burner on and off with the hand-held remote control unit.
IMPORTANT: Be sure to press the ON/
OFF buttons on the hand-held remote control unit for up to 3 seconds to as­sure proper operation.
2. Press the ON/OFF button to turn the burner on and off.
OPERATING OPTIONAL
BLOWER ACCESSORY
Locate the blower controls by opening the lower louver panel on the replace. Blower
controls are located on the left side of the
switch bracket to the right just inside the louver panel.
The BK manual blower and the BKT thermostatically-controlled blower have an ON setting and an OFF setting. The blower
will only run when the switch is in the ON
position. In the OFF position, the blower will not operate.
Note for BKT Only: If you are using BKT blower with optional thermostat (wall mounted or remote control) for the re­place, your replace and blower will not turn on and off at the same time. The fireplace may run for several minutes before the blower turns on. After the re­place modulates to the pilot position, the blower will continue to run. The blower will shut off after the rebox temperature decreases.
The blower helps distribute heated air from the replace. Periodically check the louvers of the rebox and remove any dust, dirt or other obstructions that will hinder the ow of air.
INSPECTING BURNERS
Check pilot ame pattern and burner ame
patterns often.
PILOT ASSEMBLY
The pilot assembly is factory preset for the
proper ame. Alterations may have occurred
www.fmiproducts.com
during shipping and handling. The pilot is located on the left hand side of the burner.
The ame must envelope 1/4" of top of the
ignitor/sensor and grounding stem. If your pilot assembly does not meet these
requirements:
• Turn the adjustment screw marked PILOT
clockwise to decrease or counterclockwise
to increase the ame to proper size (see Figure 49, page 28). Do not remove the adjustment screw.
• see Troubleshooting, page 31
BURNER FLAME PATTERN
Burner ames will be steady; not lifting or oat­ing. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions.
If the vent conguration is installed incorrectly, the ames will lift or "ghost". This can be dan­gerous. Inspect the ames after installation to
ensure proper installation and performance.
Figure 51 shows a typical ame pattern. If burner ame pattern differs from that de-
scribed:
• turn replace off (see To Turn Off Gas to Appliance, page 29)
• see Troubleshooting, page 32
Figure 51 - Typical Flame Pattern
CLEANING AND
MAINTENANCE
WARNING: Turn off replace
and let cool before cleaning.
CAUTION: You must keep control areas, burners and circulating air passageways of replace clean. Inspect these areas of replace before each use. Have replace inspected yearly by a qualied service person. Fireplace may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.
116647-01H30
CLEANING AND
MAINTENANCE
Continued
GLASS DOOR
WARNING: Handle glass door panel with care. Do not strike, slam or otherwise abuse glass. Do not operate replace with the glass door unlatched, removed, cracked or broken.
WARNING: Do not use abra­sive cleaners as this may damage glass. Use a nonabrasive house­hold glass cleaner to clean glass. Do not clean glass when hot.
Glass must be cleaned periodically. During start-up it is normal for condensation to form on the inside of the glass causing lint, dust and other airborne particles to cling to the glass
surface. During initial start-up a slight lm may
form on the glass due to paint curing. The glass should be cleaned several times with a non-ammonia, nonabrasive household clean-
er and warm water after the rst two weeks
of operation. Thereafter, clean the glass two or three times during each heating season, depending on the usage and circumstances present. Refer to Removing/Replacing Glass Door on page 24 of this manual when remov­ing glass door for cleaning.
WARNING: Only parts sup­plied by the manufacturer should be used when replacing broken or damaged glass door panel (see Replacement Parts, page
35). This glass door panel is a complete unit. No substitute materials may be used.
CAUTION: Wear gloves and safety glasses while handling or removing broken glass. Do not remove if glass is hot. Keep chil­dren and pets away from glass.
If glass has been broken, carefully remove
glass door (see Removing/Replacing Glass Door, page 24). Vacuum all glass pieces with
a shop vac.
116647-01H 31
www.fmiproducts.com
CAUTION: Do not vacuum if
pieces are hot.
Use only the tempered glass door replace-
ment intended for this replace (see Replace­ment Parts, page 35 for detail on ordering). No substitutions may be made. See Removing/ Replacing Glass Door, page 24 for instruc-
tions for replacing glass door.
WARNING: Do not operate
replace with the glass door
unlatched, removed, cracked
or broken.
PILOT AND BURNERS
• Remove ember material before cleaning
burners and replace when cleaning is complete.
• Burner and controls should be cleaned with
compressed air to remove dust, dirt or lint.
• Use a vacuum cleaner or small, soft bristled
brush to remove excess dust, dirt or lint.
LOGS
• If you remove logs for cleaning, refer to
Installing Logs, Lava Rock and Glowing Embers, page 26, to properly replace logs.
• Use a vacuum cleaner to remove any
carbon buildup on logs.
• Replace log(s) if broken. See Replacement Parts on page 35.
• Replace ember material periodically as
needed. See Replacement Parts on page 35.
VENTING SYSTEM
Conduct annual inspection of the venting system following these guidelines:
1. Check areas of venting system that are
exposed to the weather for corrosion (rust spots or streaks and, in extreme cases, holes).
Have these items replaced immediately by a
qualied service person.
2. Remove the vent cap and shine a ash-
light into the vent. Remove any foreign material.
3. Check for evidence of excessive condensa-
tion. Continuous condensation can cause
corrosion of caps, pipes and ttings and can
be caused by having excessive lateral runs, too many elbows or exterior portions of the system being exposed to cold weather.
4. Inspect joints to verify that no pipe section
or tting has been disturbed and loos-
ened. Check mechanical supports such as wall straps for rigidity.
TROUBLESHOOTING
WARNING: Turn off replace and let cool before servicing. Only
a qualied service person should service and repair replace.
CAUTION: Never use a wire, needle or similar object to clean
pilot. This can damage pilot unit.
Note: Before troubleshooting the system, make sure the gas shutoff valve is ON. The two most common causes of a malfunctioning gas appliance are:
1. Loose wiring connections
2. Construction debris clogging the pilot and/or gas control valve lter
OBSERVED PROBLEM
Ignitor will not spark or pilot will not light
POSSIBLE CAUSE
1. No gas supply or shutoff valve is OFF
2. Air in gas line
3. Construction debris clog-
ging pilot orice
4. Low gas pressure
5. Kinked pilot line
6. Control valve is not open­ing
7. No power to unit or the ignition module or power transformer is bad
8. Vent damper not fully open
REMEDY
1. Check to see if you have gas supply and that equip­ment shutoff valve is opened
2. Repeat lighting procedure several times to purge all air out of lines. If after repeated attempts appliance does not
light, call for qualied service
and repair.
3. Remove debris and dirt, inspect and clean any other possible obstructions
4. Contact your gas supplier to check pressure
5. Have a qualied technician
replace pilot line
6. Replace control valve (refer
to Replacement Parts, page
35)
7. Check that main power is on and that all wire con­nections are made correctly
to the ignition model (see Wiring Diagram, page 28).
Check for 24 VAC at the secondary side of the trans­former. If 24 VAC is present and the module does not operate, have the module replaced otherwise have the transformer replaced
8. Open vent damper until fully locked in OPEN position
www.fmiproducts.com
116647-01H32
OBSERVED PROBLEM
Pilot will not stay lit
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Loose wiring on ignitor wire to ignition module and/ or poor ground to ignition module
2. Pilot ame too low to sense
REMEDY
1. Check wiring connection. Refer to wiring diagram
(see Wiring Diagram, page
28) and/or check ground
wire to ignition module
2. Clean and adjust pilot burn­er and check gas supply and inlet pressure to unit
Note: Have a qualied techni- cian replace pilot assembly if broken or corroded
No gas to burner, although wall switch is set to the ON position
Frequent pilot outage
Fireplace produces a clicking/
ticking noise just after burner
is lit or shut off
Slight smoke or odor during initial operation
1. Wall switch wires defective or too long
1. Pilot flame may be too low, causing safety pilot to “drop out”
2. Improper venting or exces­sive blockage
1. Residues from manufac­turing processes and logs curing
1. Metal expanding while heating or contracting while cooling
1. Check electrical connec­tions
1. Clean and adjust pilot ame
for maximum flame im­pingement on thermopile
2. Have the vent system in­spected, including the ter­mination cap. Remove any restriction or obstruction
1. This is normal with most fireplaces. If noise is ex-
cessive, contact qualied
service person
1. Problem will stop after a few hours of operation
116647-01H 33
www.fmiproducts.com
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Fol­low the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
OBSERVED PROBLEM
Gas odor even when control knob is in OFF position
Gas odor during combustion
Glass soots
Dark residue on logs or inside
of replace
POSSIBLE CAUSE
1. Gas leak. See Warning
statement at top of page
2. Control valve defective
1. Foreign matter between control valve and burner
2. Gas leak. See Warning
statement at top of page
1. Flame impingement on logs
2. Debris around burner air mixer
1. Improper log placement
2. Air holes at burner inlet blocked
3. Burner ame holes blocked
4. Improper venting or exces­sive blockage
5. Excessive amounts of em­bers and pan material
REMEDY
1. Locate and correct all leaks
(see Checking Gas Connec­tions, page 23)
2. Replace control valve
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Con­nections, page 23)
1.
Adjust the log set so that the ame does not exces-
sively impinge on it
2.
Inspect the opening at the base of the burner to see that it is NOT packed with any type of material
1. Properly locate logs (see log
placement section on page
26)
2. Clean out air holes at burn­er inlets. Periodically repeat as needed
3. Remove blockage
4. Have the vent system in­spected, including the ter­mination cap. Remove any restrictions or obstruction
5. Clear excess embers until a minimum gap of 1/2" remains under the grate
www.fmiproducts.com
116647-01H34
REPLACEMENT PARTS
Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
Contact authorized retailers of this product. If they can not supply original replacement part(s), call FMI PRODUCTS, LLC’s Techni­cal Service Department at 1-866-328-4537.
When calling, have ready
• your name
• your address
• model and serial numbers of your re-
place
• how replace was malfunctioning
• type of gas used (propane/LP or natural gas)
• purchase date
Usually, we will ask you to return the part to the factory.
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• replace will not produce specied heat
• propane/LP gas supply might be low (pro­pane/LP units only)
You may feel your gas pressure is too low. If so, contact your local gas supplier.
SPECIFICATIONS
(V)T32EN(R)-A, (V)TV32EN
• Rating: 12,000/18,000 Btu/Hr
• Type Gas: Natural Gas Only
• Ignition: Piezo
• Manifold Pressure: 3.5" W.C.
• Minimum Inlet Gas Pressure (in. of water):
5.5"
• Dimensions (H x W x D) (Firebox only - Does not include nailing anges or standoffs):
32 1/4" x 34 1/2" x 16 5/8"
• Fireplace Weight*: Fireplace - 80 lb
• Shipping Weight*: 83 lb
(V)T32EP(R)-A, (V)TC32EP
• Rating: 11,000/17,000 Btu/Hr
• Type Gas: Propane/LP Gas Only
• Ignition: Piezo
• Manifold Pressure: 10" W.C.
• Minimum Inlet Gas Pressure (in. of water):
11"
• Dimensions (H x W x D) (Firebox only - Does not include nailing anges or standoffs):
32 1/4" x 34 1/2" x 16 5/8"
• Fireplace Weight*: 80 lb
• Shipping Weight*: 83 lb
*For refractory lined models add 45 lb
TECHNICAL SERVICE
You may have further questions about instal­lation, operation or troubleshooting. If so, contact FMI PRODUCTS, LLC’s Technical Service Department at 1-866-328-4537. When calling, please have your model and
serial numbers of your replace ready.
You can also visit FMI PRODUCTS, LLC’s technical service web site at www.fmiproducts.com.
116647-01H 35
www.fmiproducts.com
ILLUSTRATED PARTS BREAKDOWN
6
7
21
18
19
10
13
2
12
20
8
22-2
22-6
22-4
22-5
22-3
22-1
1
14
9
11
17
15
4
5
16
3
24
24
25
25
23
MODELS (V)T32E(N)(P)-A, (V)T32E(NB)(PB)-A, (V)T32E(NR)(PR)-A, (V) T32ENRB-A (V)T32EPRB-A, (V)TC32E(N)(P) AND (V)TC32E(NB)(PB)
www.fmiproducts.com
116647-01H36
This list contains replaceable parts used in your replace. When ordering parts, follow the
PARTS LIST
instructions listed under Replacement Parts on page 35 of this manual.
KEY NO.
(V)T32EN-A (V)T32EP-A (V)T32ENB-A (V)T32EPBA (V)TC32EN (V)TC32ENB
(V)T32ENR-A (V)T32EPR-A (V)T32ENRB-A (V)T32EPRB-A (V)TC32EPB (V)TC32EP DESCRIPTION QTY.
1 ** ** Firebox Assembly 1 2 ** ** Face Weldment 1 3 108892-01 108892-01 Door Assembly (T Models Only) 1
108892-02 108892-02 Door Assembly (VT Models Only) 1 4 108903-01 109155-01 Top Louver Assembly 1 5 108903-02 109155-02 Bottom Louver Assembly 1 6 ** ** Fireplace Top 1 7 ** ** Fireplace Top Insulation 1 8 ** ** Fireplace Surround 1 9 108885-03 108885-03 Burner Assembly (Natural Gas) 1
108885-04 108885-04 Burner Assembly (Propane/LP Gas) 1
(See pages 36 & 37)
10 108890-01 108890-01 Burner Base Gasket 1 11 109082-03 109082-03 Heat Shield 1 12 108897-01 108897-01 Rear Refractory Brick Panel (B Models Only) 1 13 108901-01 108901-01 Right Refractory Brick Panel (B Models Only) 1 14 108901-02 108901-02 Left Refractory Brick Panel (B Models Only) 1 15 11418 11418 Push-On Nut 2 16 108440-01 108440-01 Screen 2 17 109479-01 109479-01 Screen Rod 1 18 14123 14123 Strain Relief 1 19 21171 21171 Gas Knock-Out Cover 2 20 24353 24353 Handy Box Assembly 1 21 24460 24460 Gas Conduit Assembly 1 22 109222-01 109222-01 Log Set 1 22-1 109403-01 109403-01 Front Log (#1) 1 22-2 109404-01 109404-01 Rear Log (#2) 1 22-3 109407-01 109407-01 Base Log (#3) 1 22-4 109406-01 109406-01 Crossover Log (#4) 1 22-5 109405-01 109405-01 Left Top Log (#5) 1 22-6 109408-01 109408-01 Right Top Log (#6) 1 23 125408-03 125408-03 Screen Door (TC Models Only) 1 24 125519-01 125519-01 Door Latch Magnet (TC Models Only) 2 25 125558-01 125558-01 Door Latch Screw (TC Models Only) 8
PARTS AVAILABLE - NOT SHOWN
25487 25487 Lava Rock/Bag Assembly 1
27253 27253 Notice Label 1
55240 55240 Vent Label 1
** Not a eld replaceable part.
116647-01H 37
www.fmiproducts.com
IGN
PV
GND
PV/MV
TR
TH
MV
21
23
24
26
25
27
17
22
16
14
20
12
9
8
10
13
15
19
18
28
29
11
2
1
7
3
5
4
6
ILLUSTRATED PARTS BREAKDOWN
BURNER ASSEMBLY MODELS (V)T32E(N)(P)-A, (V)T32E(NB)(PB)-A, (V) T32E(NR)(PR)-A, (V)T32ENRB-A, (V)T32EPRB-A, (V)TC32E(N)(P) AND (V) TC32E(NB)(PB)
www.fmiproducts.com
116647-01H38
PARTS LIST
BURNER ASSEMBLY MODELS (V)T32E(N)(P)-A, (V)T32E(NB)(PB)-A, (V) T32E(NR)(PR)-A, (V)T32ENRB-A, (V)T32EPRB-A, (V)TC32E(N)(P) AND (V) TC32E(NB)(PB)
This list contains replaceable parts used in your replace. When ordering parts, follow the
instructions listed under Replacement Parts on page 35 of this manual.
KEY NO. PART NO. DESCRIPTION QTY.
1 111 0 2 Screw #8-32 x 3/8 PPH Zinc 2 2 111 0 5 Screw #10 x 1/2 Zinc 9 3 108886-01 Base Grate Assembly 1 4 108891-01 Burner 1 5 108866-01 Pilot Assembly (Natural) 1
108866-02 Pilot Assembly (Propane/LP) 1 6 27113 Air Deector 1 7 108889-01 Burner Assembly Base 1 8 26808 Valve Bracket 1 9 111 7 9 Screw #10-24 x 1/4 Zinc 4 10 14253 Flexible Connector 1 11 14500 Brass Fitting 2 12 14569 Electronic Valve (Natural) 1
14570 Electronic Valve (Propane/LP) 1 13 26827 Switch Bracket 1 14 104509-02 Aluminum Tubing Assembly 1 15 104506-25 Orice #47 (Natural) 1
14514 Orice #55 (Propane/LP) 1 16 14528 Brass Elbow Fitting 1 17 108863-01 Supply Connect Plug 1 18 23416 Electronic Components Board 1 19 14129 Transformer 1 20 11147 Screw, #10-24 x 1/2 PPH Blk 2 21 110286-01 Ignition Module, Synetek 1 22 11186 Screw, #8-32 x 1 Zinc 2 23 11201 Hex Nut 4 24 17223 Magnet 2 25 14520 Female Spade Connector 4 26 14134 18 Ga. Black Wire 5 27 14126 16 Ga. Green Wire 1 28 14115 Spade Tongue Connector 1 29 14149 Right Angle Spade Connector 4
116647-01H 39
www.fmiproducts.com
ACCESSORIES
NOTICE: All accessories may
not be available for all replace models.
Purchase these replace accessories from
your local retailer. If they can not supply these accessories, call FMI PRODUCTS, LLC’s Sales Department at 1-866-328-4537. for information. You can also write to the address listed on the back page of this manual.
BRICK LINER KIT (Not Shown)
BL32D - Refractory BLX32STL - Ledgestone Refractory Kit
BLX32SVF - Fiber Liner Kit
PLX32 - Porcelain Liner Kit This brick liner adds a touch of style to your
direct-vent replace. Complete installation
instructions included in this manual.
PROPANE/NATURAL GAS CONVERSION KIT (Not Shown)
PCDE-32T - Propane/LP Gas NCDE-32T - Natural Gas
FACE/LOUVER PANEL KIT (Not Shown)
RLD32 - Rolled, Black
ROLLED LOUVER TRIM KIT (Not Shown)
LT32B - Brushed Brass LT32P - Platinum
DEFLECTION HOODS (Not Shown)
HD32 - Hood - Black (2" Brow)
PERIMETER TRIM KIT (Not Shown)
PT32 - Black PT32B - Brushed Brass PT32P - Platinum
MANUAL BLOWER KIT - BK
Manual variable control blower accessory provides better heat distribution. Complete in­stallation and operation instructions included in this manual.
THERMOSTATICALLY-
CONTROLLED BLOWER KIT - BKT
Provides better heat distribution. Blower turns off and on automatically, as needed. Com­plete installation and operation instructions included in this manual.
REMOTE CONTROL KIT - WRC
SERIES Standard On/Off Electronic Remote Control Kit (Not Shown)
Allows the replace to be turned on and off
conveniently.
www.fmiproducts.com
116647-01H40
NOTES
_____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________
116647-01H 41
www.fmiproducts.com
NOTES
_____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________
www.fmiproducts.com
116647-01H42
NOTES
_____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________ _____________________________________________________
116647-01H 43
www.fmiproducts.com
WARRANTY
KEEP THIS WARRANTY
Model (
located on product or identication tag
Serial No. (
located on product or identication tag
Date Purchased __________________________
Keep receipt for warranty verication.
FMI PRODUCTS, LLC LIMITED WARRANTIES
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects
in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date
of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be
free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only
when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allowance
for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by FMI PROD­UCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs, unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
All warranty will be voided if this product is used with a thermostat.
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty
excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all
implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
New Products
Factory Reconditioned Products
Terms Common to All Warranties
) _____________________________
) __________________________
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
116647-01 Rev. J 04/13
Loading...