SAVE THIS BOOK
This book is valuable. In addition to instructing you
on how to install and maintain your appliance, it also
contains information that will enable you to obtain replacement parts or accessory items when needed. Keep
it with your other important papers.
This replace is approved for use as a wood burning replace or for use with a vented gas log approved to ANS
Z21.60 or Z21.84 standards or for use with a vent-free
gas log heater approved to ANS Z21.11.2 standard. A FMI
PRODUCTS, LLC hood must be installed when using a
vent-free log heater (see Accessories, page 16).
This wood burning replace complies with UL127CAN/ULS-S610-M87 standard as a FACTORY BUILT
APPLIANCE.
FOR CANADA: The authority having jurisdiction (such
as the municipal building department, re department,
etc.) should be contacted before installation to determine the need to obtain a permit.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
installation, adjustment,
alte ration, serv ice or
maintenance can cause
injury, property damage
or loss of life. Refer to this
manual for assistance or
additional information.
Consult a qualied installer or local distributor.
IMPORTANT: Check local codes
before installing this replace.
Before beginning installation of this replace,
read these instructions through completely.
• This FMI PRODUCTS, LLC replace and
its components are safe when installed
according to this installat ion manual.
Unless you use FMI PRODUCTS, LLC
components, which have been designed
and tested for the replace system, you
may cause a re hazard.
• The FMI PRODUCTS, LLC warranty will
be voided by and FMI PRODUCTS, LLC
disclaims any responsibility for the following
actions.
a. Mo dific ation of the firepl ace, com-
ponents, doors, air inlet system and
damper control.
b. Use of any component part not manufac-
tured or approved by FMI PRODUCTS,
LLC in combination with a FMI PROD-
UCTS, LLC replace system.
Proper installation is the most important step
in ensuring safe and continuous operation of
replace. Consult the local building codes as
to the particular requirements concerned with
the installation of all factory built replaces.
WARNING: Do not install a
replace insert in this box unless
the manufacturer's instructions
with the insert specically state
this replace has been tested for
use with this insert.
FOR YOUR SAFETY
• Do not store or use gasoline
or any other ammable vapors
or liquids in the vicinity of this
or any other appliance.
• Due to high temperatures, the
appliance should be located
out of trafc and away from
furniture and draperies.
• Do not place clothing or other
ammable materials on or near
the appliance.
• Never leave children unattended when a re is burning
in the replace.
WARNING: Use solid wood
or processed solid fuel relogs
only. When processed wood fuel
re logs are used, do not poke or
stir the logs while they are burn-
ing. Use only re logs that have
been evaluated for the application
in replace and refer to re log
warnings and caution markings
on packaging prior to use.
This replace is not intended to be
used as a substitute for a furnace
to heat an entire home. Use for
supplemental heat only.
www.fmiproducts.com
111026-01G2
SPECIFICATIONS
0" TO
BOTTOM
(LEFT SIDE ONLY)
OUTSIDE AIR
TOP SPACERS
BACK AND SIDES
3/4" AIR SPACE
HEARTH EXTENSION
66" X 20"
TO PERPENDICULAR
12"
EACH SIDE
NOT LESS
THAN 12"
1" AIRSPACE
TO COMBUSTIBLE
COMBUSTIBLE
WALL BOARD
0" TO
MATERIAL
NO COMBUSTIBLE
MATERIAL ON FACE
SIDEWALL
TERMINATION
SQUARE CHASE-TOP
GAS LINE
KNOCK OUT
AIR KIT
KNOCK OUTS
ROUND TOP TERMINATION
GAS LINE
KNOCK OUTS
ELECTRICAL
OUTLET
LEFT SIDE
RIGHT SIDE
8.125"
10.435"
14.437"
41.25"
37"
41"
35"
21"
8"
32.5"
14.25"
22"
2.5"
8.717"
1"
11 .217"
2.5"
8.125"
7.092"
8.717"
12.5"
41"
1"
0.625"
29"
21
111026-01G3
www.fmiproducts.com
21.875"
41.375"
41.250"
52.183"
17.253"
24.399"
73.798"
MAINTAIN
3
/4"
CLEARANCE A T
SIDES AND BACK
OF FIREPLACE
3
/4" CLEARANCE
NOT REQUIRED A T
NAILING FLANGES
FIREPLACE INSTALLATION
SELECTING LOCATION
To determine the safest and most efcient
location for the replace, you must take into
consideration the following guidelines:
1. The location must allow for proper clearances (see Figures 1 and 2).
2. Consider a location where the replace
will not be affected by drafts, air conditioning ducts, windows or doors.
3. A location that avoids the cutting of
joists or roof rafters will make installation
easier.
4. An outside air kit is available with this
replace (see Optional Outside Air Kit on
page 6).
MINIMUM CLEARANCE TO
COMBUSTIBLES
Back and sides of replace 3/4" minimum*
Floor** 0" minimum
Perpendicular wall to opening 12" minimum
Top spacers 0" minimum
Mantel clearances see Mantels, page 5
Chimney outer pipe surface 1" minimum
* Not required at nailing anges
** See step 2 of Framing
WARNING: Do not pack required air spaces with insulation
or other materials.
Minimum/Maximum Chimney Height for
Residential Installation
The minimum height of the chimney, measured from the base of the replace to the ue
gas outlet of the termination, is 14.5 feet for
straight ue or a ue with one elbow set. The
maximum distance between elbows is 6 feet.
For systems with two elbow sets, the minimum
height is 22 feet. The maximum height of any
system is 50 feet. This measurement includes
the replace, chimney sections and the height
of the termination assembly at the level of the
ue gas outlet (see Figure 18, page 11).
Minimum/Maximum Chimney Height for
Outdoor Installation
The minimum height of the chimney, measured from the base of the replace to the
ue gas outlet of the termination, is 7 1/2 feet
(minimum of 4 feet of chimney pipe sections
required for outdoor installation).
www.fmiproducts.com
FRAMING
1. Frame opening for fireplace using the
dimensions shown in Figures 1 and 2.
2. If replace is to be installed directly on
carpeting, tile (other than ceramic) or any
combustible material other than wood
ooring, the replace must be installed
upon a metal or wood panel extending
the full width and depth of replace.
3. Set replace directly in front of this opening and slide unit back until nailing anges
touch side framing.
4. Check the level of the replace and shim
with sheet metal if necessary.
5. Before securing fireplace to prepared
framing, the ember protector (provided)
must be placed between the hearth extension (not supplied) and under bottom
front edge of replace to protect against
glowing embers falling through. If replace
is to be installed on a raised platform, a Ztype ember protector (not supplied) must
be fabricated to t your required platform
height. The ember protector should extend under replace a minimum of 1 1/2".
The ember protector should be made of
galvanized sheet metal (28 gauge minimum) to prevent corrosion.
6. Using screws or nails, secure replace to
framing through anges located on sides
of replace.
Figure 1 - Framing Dimensions
Figure 2 - Corner Installation
111026-01G4
FIREPLACE INSTALLATION
FIREBOX
SAFE ZONE
Continued
DRAIN PAN (DP36)
For outdoor installations, the replace enclosure must allow for adequate drainage and
fresh air ventilation. It is recommended that
a sealed, corrosion resistant catch pan with
provision for drainage be installed under the
replace within the replace enclosure (see
Accessories on page 16).
HEARTH EXTENSION
A hearth extension projecting a minimum of
16" in front of and a minimum of 8" beyond
each side of the replace opening is required
to protect combustible floor construction
in front of the replace. Fabricate a hearth
extension using a material which meets the
following specications: a layer of noncombustible, inorganic material having a thermal
conductivity of K=0.84 BTU IN/FT, HR. F (or
less) at 1" thick. For example, if the material
selected has a K factor of 0.25, such as glass
ber, the following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "K" of materials can be
obtained from the manufacturer or supplier of
the noncombustible material. If the hearth extension is to be covered, use noncombustible
material such as tile, slate, brick, concrete,
metal, glass, marble, stone, etc. Provide a
means to prevent the hearth extension from
shifting and seal gap between the replace
frame and hearth extension with a noncombustible material (see Figure 3).
Seal Gap
Hearth
Extension
Seal Gap
www.fmiproducts.com
Fireplace Front
Ember Protector
Fireplace Front
Raised Hearth
Ember Protector
Fireplace Front
Elevated
Ember Protector
Figure 3 - Hearth Extension
111026-01G5
WARNING: Hearth extension
is to be installed only as shown
in Figure 3.
MANTELS
A mantel may be installed if desired (see
Figure 4). Woodwork such as wood trims,
mantels or any other combustible material
projecting from the front face must not be
placed within 12" of the replace opening.
Combustible materials above 12" and projecting more than 11/2" from the fireplace
must not be placed less than 15" from the
top opening of the replace (NFPA STD 211,
Sec. 7-3.3.3).
Mantels or any other combustible material
also may come up to the side edge of the
black metal face of the replace just as long
as the projection from the front face fall within
the limit shown in Figure 4.
Combustible
12 1/4" Ref.
6"
Ref.
12" Min.
Top View of Fireplace
33°
33°
3" Nom.
11/2" Max.
9" Min.
Fireplace Opening
8.0"
Min. to
Perpendicular
Side Wall
12"
Figure 4 - Mantel Clearances to
Combustible Material
Material
Safe
Zone for
Projection of
Combustible
Materials
Upper
Section of
Fireplace
2" Max.
3.0"
Combustible
Material Must
Not Overlap
Front Face
VENTING INSTALLATION
OPTIONAL OUTSIDE AIR KIT
(MODEL AK4/AK4F)
The installation of an outside air kit should be
performed during the rough framing of the replace due to the nature of it's location. Outside
combustion air is accessed through a vented
crawl space (AK4F) or through a sidewall (AK4).
See Figure 22 on page 13 for instruction of
operating air kit.
CAUTION: Combustion air
inlet ducts shall not terminate
in attic space.
The maximum height for the
air vent can not exceed 3 feet
below the ue gas outlet of the
termination.
Secure to Collars with Metal Tape, Screws
or Straps (Min. of 1/4" x 20" in size)
Air Inlet
Location
Must Allow
For Bushes
or Snow
Air Inlet
Eyebrow
Vented Crawl Space
(Check Local Codes
Before Installing in a
Vented Crawl Space)
Figure 5 - Outside Air Kit
CHIMNEY PIPE
The FMI PRODUCTS, LLC chimney system
consists of 12", 18", 24", 36" and 48" snaplock, double-wall pipe segments, planned
for maximum adaptability to individual site
requirements. Actual lengths gained after tting overlaps must be taken into consideration
(lineal gain) and are given in the lineal gain
chart (see Figure 6). Lineal gain is the actual
measurable length of a part after two or more
parts are connected. For Canada, use chimney
parts designated "HT".
Vent Hood
Required for
Wall Installation
www.fmiproducts.com
WARNING: The opening in
collar around chimney at top of
replace must not be obstructed. Never use blown insulation
to ll chimney enclosure.
PART NO.DESCRIPTIONGAIN
36"Fireplace40
12-8DM
12-8HT
18-8DM
18-8HT
24-8DM
24-8HT
36-8DM
36-8HT
48-8DM
48-8HT
RT-8DM Round Termination6 7/8"
RTL-8DM Round Termination7 3/4"
RTT-8DM
RTTL-8DM
ET-8DM Square Chase-Top12
ETO-8DM
ETL-8DM
ETLO-8DM
* The lineal gain for the terminations is measured to the ue gas outlet height.
12 3/8" Galvanized
Outer Pipe
8" Stainless
Inner Pipe
A
SSEMBLY AND INSTALLATION OF
DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists
of a galvanized outer pipe, a stainless steel
inner ue pipe and a wire spacer. The pipe
sections must be assembled independently
as the chimney is installed.
LINEAL GAIN
Pipe Section10 5/8"
Pipe Section16 5/8"
Pipe Section23 5/8"
Pipe Section34 5/8"
Pipe Section46 5/8"
Round Termination
with Slip Section
Round Termination
with Slip Section
Square Chase-Top
with Mesh
Square Chase-Top
with Slip Section
Square Chase-Top
with Mesh & Slip
Section
Figure 6 - Lineal Gain
"
6 7/8" to
23 1/8"*
8 1/2" to
21 1/2"*
*
"
*
12
"
7" to 15"*
12" to
25 1/2"
Hemmed
End
111026-01G6
*
*
*
VENTING INSTALLATION
Continued
When connecting chimney directly to the replace,
the inner ue pipe section must be installed rst
with the lanced side up. The outer pipe section
can then be installed over the ue pipe section with
the hemmed end up. Press down on each pipe
section until the lances securely engage the hem
on the replace starter. The wire will assure the
proper spacing between the inner and outer pipe
sections. Continue to assemble chimney sections
as outlined, making sure that both the inner and
outer pipe sections are locked together. When
installing double wall snap-lock chimney together,
it is important to assure the joint between the chimney sections is locked. Check by pulling chimney
upward after locking. The chimney will not come
apart if properly locked. It is not necessary to add
screws to keep the chimney together (exception see Figure 9, page 8).
USING ELBOW OFFSETS (30E-8DM)
1. To achieve desired offset, you may install
combinations of 12", 18", 24", 36" and 48"
length of double wall pipe (see offset chart
and Figure 7).
2. Chimney weight above offset rests on
return elbow. Straps must be securely
nailed to rafters or joists (see Figure 8,
details A and B on page 8).
3. Maximum length of pipe between supports
(return elbow or 12S-8DM) is 6' of angle
run. Maximum of two 6' angle run sections
per chimney system (see Figure 7).
4. All pipe connections between offset and
return must be secured with two screws
on outer pipe only (see Figure 9, page 8).
Do not penetrate inner stainless.
Firestop spacers are required at each point
where the chimney penetrates a oor space.
Their purpose is to establish and maintain
the required clearance between the chimney
and the combustible materials. When the pipe
passes through a framed opening into a living
space above, the restop must be placed onto
the ceiling from below as shown in Figure 10.
They also provide complete separation from
one oor space to another or attic space as
required by most codes. When the double wall
pipe passes through a framed opening into an
attic space, the restop must be placed into an
attic oor as shown in Figure 11.
Figure 11 - Firestop Spacer with Attic
Space Above Ceiling
PENETRATING ROOF
To maintain a 1" clearance to the pipe on a
roof with a pitch, a rectangular opening must
be cut.
1. Determine center point through which pipe
will penetrate roof.
2. Determine center point of roof. Pitch is the
distance the roof drops over a given span,
usually 12". A 6/12 pitch means that the
roof drops 6" for each 12" one measure
horizontally down from the roof rafters.
3. Use roof opening chart (Figure 12, page
9) to determine the correct opening length
and ashing required.
4. Remove the shingles around opening
measured. Cut out this section.
5. Add next sections of pipe until end penetrates roof line. Check to see that the
proper clearances are maintained. Extend
chimney by adding sections of double wall
pipe until pipe is minimum of 30" above the
highest point of the roof cutout. Termination
and chimney must extend a minimum of
36" above the highest point where it passes
through the roof.
www.fmiproducts.com
111026-01G8
VENTING INSTALLATION
14 3/8"
(36.5 cm)
30"
(76.2 cm)
1"
(2.5
cm)
1"
(2.5
cm)
Minimum Measurements
1"
(2.5 cm)
Opening "A"
Continued
Storm Collar Installation (SC1 or SC2)
Place storm collar over pipe and slide down
until it is snug against the open edge of the
ashing (see Figure 14). Use SC1 for all round
terminations and SC2 for all terminations with
slip sections. Apply waterproof caulk around the
perimeter of the collar to provide a proper seal.
Chimney
Pipe
Waterproof
Caulk
Storm
Collar
Flashing
PitchSlope Opening "A"
Flat0°15"V6F-8DM
0-6/1226.6°16 1/8"V6F-8DM
6/12-
45.0°20 3/8"V12F-8DM
12/12
Max.
Figure 12 - Roof Opening Measurements
FLASHING INSTALLATION (V6F-8DM
OR V12F-8DM)
Determine the ashing to be used with the roof
opening chart. Slide ashing over pipe until
base is at against roof. Replace as many
shingles as needed to cover exposed area
and ashing base. Secure in position by nailing through shingles (see Figure 13). DO NOT
NAIL THROUGH FLASHING CONE.
Installing Flashing on a Metal Roof
When installing ashing on a metal roof, it is
required that putty tape be used between the
Used Flashing
Model No.
Figure 14 - Storm Collar
Terminations/Spark Arrestor
The replace system must be terminated with
the listed round top or chase terminations. In
any case, refer to the installation instructions
supplied with the termination. The termination
approved for this replace are the RT-8DM and
RTL-8DM that can be used for ashing or chase
and ET-8DM, ETO-8DM, ETL-8DM and ETLO8DM for chase style termination only. Figure 15
shows an RTL-8DM round top termination.
CAUTION: Do not seal openings on the rooftop ashing. Follow the installation instructions
provided with the termination
being used.
ashing and roof. The ashing must be secured
to the roof using #8 x 3/4" screws and then
sealed with roof coating to prevent leakage
through screw holes. A roof coating must also be
applied around perimeter of ashing to provide
a proper seal.
Storm Collar
Flashing
Cone
Overlap
Shingles Top
and Sides Only
Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws
Overlap
Shingles Top
and Sides
Nail Only
Outer
Perimeter
of Flashing
Underlap Shingles
at Bottom
Figure 13 - Flashing Installation
111026-01G9
Figure 15 - Termination
www.fmiproducts.com
RTL-8D
Level of
Flue Gas
Outlet
Caulk
Collar
Flashing
Underlap
Shingles
Bottom Only
VENTING INSTALLATION
Continued
Terminations with 16" slip pipe sections are
available. The RTT-8DM and RTTL-8DM are
approved for flashing installations. When
needed, these adjustable terminations may be
used in combination with the pipe assembly to
achieve the correct chimney height.
Note: In the rare instance there is a problem
with the side driven rain or wind or the chimney is not drafting properly, an ADS-8DM
(Anti-Draft Shield) can be used with round
terminations.
CHASE INSTALLATIONS
Instructions for cha se installati on s are
included with the chase style termination
chosen. In a multiple chase installation, be
sure to provide adequate distance between
terminations to prevent smoke spillage from
one termination to another. We suggest that
terminations be separated at least 24", center
to center and stacked at a vertical height difference of 18" (see Figure 16).
Note: If a decorative shroud is to be installed,
contact the manufacturer for specications.
18"
Min.
Typ.
24" Min.
10 FOOT RULE
All ue gas outlet chimney terminations must
extend a minimum of 3 feet in height above the
highest point where it passes through the roof
and must be at least 2 feet above the highest point of the roof that is within a horizontal
distance of 10 feet (see Figure 17).
3' Min.
Level of
Flue Gas
Outlet
10'
2' Min.
3' Min.
10'
2' Min.
Figure 17 - 10 Foot Rule
FINISHING FIREPLACE
Combustible materials, such as wallboard,
gypsum board, sheet rock, drywall, plywood,
etc. may make direct contact with sides and top
around the replace face. It is important that
combustible materials do not overlap the face
itself. Brick, glass, tile or other noncombustible
materials may overlap the front face provided
they do not obstruct essential openings like
louvered slots or any other opening. When
overlapping with a noncombustible facing
material, use only noncombustible mortar or
adhesive.
24" Min.
Figure 16 - Multiple Chase Installation
www.fmiproducts.com
111026-01G10
30E-8DM
EFFECTIVE HEIGHT
OF TERMINATION CAP
EFFECTIVE HEIGHT
OF TERMINATION CAP
EFFECTIVE HEIGHT
OF TERMINATION CAP
EFFECTIVE HEIGHT
OF TERMINATION CAP
MINIMUM
HEIGHT
14.5 FT.
MINIMUM
UP TO
6FT. MAX.
UP TO
6FT. MAX.
HEIGHT
14.5 FT.
MIN. HEIGHT
OF 22 FT. (WITH
2 ELBOW SETS)
MAX. HEIGHT OF
50 FT.
MAX. HEIGHT
50 FT.
(ANY SYSTEM)
30E-8DM
Gas line hook up should be done by your
supplier or a qualied service person.
Note: Before you proceed, make sure your
gas supply is turned off.
Use only a 1/2" black iron pipe and appropriate ttings.
1. Remove knockout indentation on refrac-
2. Remove gas line cover plate located on
3. Run a 1/2" black iron gas line into the
111026-01G11
VENTING INSTALLATION
Continued
Figure 18 - Typical Residential Installations
OPTIONAL GAS LINE INSTALLATION
tory or rebrick wall located above the
refractory hearth floor. The knockout
indentation must be rmly tapped with any
solid object such as a 1/2" dowel until it is
released. Remove fragmented portions of
refractory (see Figure 19).
either side of replace and pull out insulation from gas line conduit sleeve. Save
insulation for reuse. Replace screws.
fireplace through the rear at gas line
conduit sleeve (if using a raised platform,
add height). Provide sufcient gas line into
replace chamber for tting connection
www.fmiproducts.com
(see Figure 20, page 12). Note: Secure
incoming gas line to wood framing to
provide rigidity for threaded end.
4. Repack insulation around gas line and into
sleeve opening. Seal any gaps between
gas line and refractory knockout hole with
refractory cement or commercial furnace
cement, Install the gas appliance or capoff gas line if desired.
Outside of
Fireplace
Gas Line
Conduit
Insulation
Side
Firebrick
Finished
Side
1/2" Dowel
Gas
Conduit
Cover
Figure 19 - Gas Line Knockout
Refractory
Knockout
Plug
OPTIONAL GAS LINE INSTALLATION
Continued
CAUTION: All gas piping
and connections must be tested
for leaks after the installation
is completed. After ensuring
that the gas valve is on, apply
soap and water solution to all
connections and joints. Bubbles
forming show a leak. Correct
all leaks at once. DO NOT USE
AN OPEN FLAME FOR LEAK
TESTING AND DO NOT OPER-
ATE ANY APPLIANCE IF A LEAK
IS DETECTED. LEAK TESTING
SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
Note: A FMI PRODUCTS, LLC hood must be
installed when using an unvented gas log set
(see Accessories on page 16).
Outside of
Fireplace
Gas
Line
Conduit
Repack
Insulation
Figure 20 - Gas Line Installation
Incoming
1/2" Black
Iron Pipe
Seal
Opening
with
Refractory
Cement
Provide Enough Threaded
End for Fitting Connection
Side
Firebrick
Finished
Side
WARNING: Do not operate an
unvented gas log set in this replace with the chimney removed.
If you install a decorative gas appliance
(vented gas log), the decorative gas appliance
must comply with the Standard for Decorative
Gas Appliance for Installation in Solid Fuel
Burning Fireplaces, ANS Z21.60, Z21.84 or
RG 2-72 and shall also be installed in accordance with the National Fuel Gas Code, ANSI
7223NFPA 54 latest edition.
WARNING: To avoid the risk of
damaging the replace materials
and increasing the risk of spread-
ing a re, do not use the replace
to cook or warm food.
WARNING: If the replace
has been used for wood burning,
the rebox and chimney must be
cleaned of soot, creosote and
ashes be a qualied chimney
cleaner. Creosote will ignite if
heavily heated.
WARNING: When using a
decorative vented gas log, the
damper must be removed or permanently locked in the fully open
position and the glass doors must
be in the fully open position.
OPERATION AND MAINTENANCE GUIDELINES
GLASS DOORS
Glass doors are optional with the replace.
When the replace is in operation, doors
must be fully opened or fully closed position
only or a re hazard may be created (see
Figure 21).
A replace equipped with glass doors operates mush differently than a replace with an
open front. A replace with glass doors has a
limited amount of air for combustion. Excessive heat within the replace can result if too
large a re is built or if the combustion air gate
is not completely open.
www.fmiproducts.com
Doors Fully Closed
Fireplace Front
Doors
Fully Opened
Fireplace Front
Figure 21 - Glass Doors
111026-01G12
OPERATION AND MAINTENANCE GUIDELINES
OPEN
CLOSE
Continued
The following tips should be followed to assure that both the replace and the glass door
retain their beauty and function properly. Both
the ue damper and the glass doors must be
fully opened before starting the re. This will
provide sufcient combustion air and maintain
safe temperatures in the rebox.
IMPORTANT: The glass must be allowed to
warm slowly and evenly. The tempered glass
will withstand a gradual temperature rise to
550° F, which is more than a normal re will
generate. Such materials as pitch/wax laden
logs, very dry mill end lumber and large
amounts of paper or cardboard boxes can
create an excessively hot re and should not
be burned in this replace. Always keep the
re well back from the doors and never allow
ames to contact the glass.
WARNING: Fireplaces
equi pped with glass doors
should be operated only with
doors fully opened or doors fully
closed. Doors, if left partly open,
may draw gas and ame out of
the replace opening creating
risks of both re and smoke.
Cleaning Glass
Clean the glass with any commercial glass
cleaner or soap and water. Do not use any
abrasive material to clean the glass. Do not
clean the glass with any cool water is the glass
is still hot from the re and smoke.
A gas line or gas log lighter may be installed
for the purpose of installing a vented or ventfree decorative gas appliance incorporating an
automatic shutoff device and complying with
the Standard for Decorative Gas Appliances
for Installation in Vented Fireplaces, ANSI
Z21.60 or American Gas Association draft
requirements for Gas Fired Log Lighters for
Wood Burning Fireplaces, Draft NO. 4 dated
August, 1993.
If you wish to install an unvented (vent-free)
gas log set, only unvented gas log sets which
have been found to comply with the standard
for unvented room heaters, ANSI Z21.11.2 are
to be installed in this replace.
OUTSIDE AIR AND DAMPER
HANDLE OPERATION
The damper handle, which opens and closes
the damper blade, is located in the upper front
face of the replace. Pushing the handle into
the left of the keyway slot will free the damper
blade to automatically open. Pushing the
handle in to the right will lock the damper
blade closed (see Figure 22).
The outside air kit handle is located at the left
hand side of the replace (see Figure 22).
Pulling the handle out will free the outside air
door to open. Pushing the handle in will lock
the door closed.
WARNING: Risk of re! Replace grate with FMI PRODUCTS,
LLC model 111028-01 only. This
grate has been designed to keep
the operation of your replace
safe and efcient.
For further operating guidelines, instructions
and warranty information, please refer to your
homeowner's guide or contact your authorized
dealer.
9106658-03 Left Refractory, Textured White Brick•1
108164-03 Left Refractory, Textured White Herringbone•1
106658-02 Left Refractory, Textured Red Brick••1
108164-02 Left Refractory, Textured Red Herringbone••1
106658-01 Left Refractory, Smooth White Brick•1
108164-01 Left Refractory, Smooth White Herringbone•1
10 106659-03 Right Refractory, Textured White Brick•1
108165-03 Right Refractory, Textured White Herringbone•1106659-02 Right Refractory, Textured Red Brick••1
108165-02 Right Refractory, Textured Red Herringbone••1106659-01 Right Refractory, Smooth White Brick•1
108165-01 Right Refractory, Smooth White Herringbone•1
11 106660-03 Rear Refractory, Textured White Brick•1
108166-03 Rear Refractory, Textured White Herringbone•1106660-02 Rear Refractory, Textured Red Brick••1
108166-02 Rear Refractory, Textured Red Herringbone••1106660-01 Rear Refractory, Smooth White Brick•1
108166-01 Rear Refractory, Smooth White Herringbone•1
12 110899-01 Bottom Rear Refractory, White Brick• •• •1
110899-02 Bottom Rear Refractory, Red Brick• •• •1
13 110900-01 Bottom Front Refractory, White Brick• •• •1
110900-02 Bottom Front Refractory, Red Brick• •• •1
S36
S36H
S36R
S36RH
VS36(1)
VS36H(1)
VS36R
VS36RH
www.fmiproducts.com
111026-01G16
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact
FMI PRODUCTS, LLC at 1-866-328-4537. When calling please have your model and serial
numbers of your heater ready.
You can also visit FMI PRODUCTS, LLC’s web site at www.fmiproducts.com.