FMI MMST43 Instructions Manual

Page 1
Instructions
ReportNo. 08-154
Masonry Firebox
Model MMST43
THIS WOOD-BURNING FIREPLACE COMPLIES WITH UL127 STANDARD AS A FACTORY-BUILT APPLIANCE.
WARNING: THIS FIREPLACE IS APPROVED FOR USE AS A WOOD BURNING FIREPLACE.
IT HAS NOT BEEN TESTED OR APPROVED FOR UNVENTED GAS LOGS.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN
CAUSE INJURY, PROPERTY DAMAGE OR LOSS OF LIFE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION. CONSULT A QUALIFIED INSTALLER OR LOCAL DISTRIBUTOR.
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or accessory items when needed. Keep with your other
important papers.
Installer: Leave these instructions with the consumer. Consumer: Retain for future reference.
Do not store gasoline or other ammable vapors and
liquids in the vicinity of this or any other appliance.
ICC Evaluation Services Report No. 2401
Page 2
This page has been left intentionally blank.
Page 3
CONTENTS
2701 S. Harbor Blvd. SANTA ANA, CA 92704
DATE OF MFG.
SERIAL No.
LISTED MASONRY FIREPLACE SYSTEM COMPLIES WITH APPLICABLE REQUIREMENTS OF UL127
Fireplace is designed for installation per the National Fire Protection Association Standard for Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances (NFPA 211).
MODEL
No.:
MMST43
DO NOT REMOVE THIS LABEL
See FMI’s installation and operating instructions for this model. Contact local building officials about restrictions and installation specifications in your area.
WARNING:
FOR USE ONLY WITH
12
" I.D.
FMI PRODUCTS, LLC LISTED FIREPLACE COMPONENTS: PIPE SECTIONS, FIRESTOP SPACERS, OFFSET AND RETURN ELBOWS, FLASHINGS, STORM COLLARS, TERMINATIONS AND WALL SHIELDS.
!
THIS APPLIANCE NEEDS FRESH AIR FOR SAFE OPERATION AND MUST BE INSTALLED SO THERE ARE PROVISIONS FOR ADEQUATE COMBUSTION AND VENTILATION AIR.
MANTEL CLEARANCES
0" - 3" : 1½" MAX. PROJ. 3" - 12" : 1½" - 8" MAX. PROJ.
MANTEL ABOVE OPENING:
MIN. - 3" SHEATHING OR TRIM TO OPENING SIDES 8"
FIREPLACE CLEARANCES TO COMBUSTIBLES:
UNIT FRONT, SIDES, REAR.............................................. 2" (51 mm)
COMBUSTIBLE FLOOR ............................................ 6
"
(152 mm)
COMBUSTIBLE SHEATHING ABOVE OPENING TOP.... 8
"
(203 mm)
SHEATHING OR TRIM TO OPENING SIDES.................. 8
"
(203 mm)
MANTLE ABOVE OPENING...........................................12
"
(305 mm)
OPENING TO SIDE WALL............................................. 24
"
(610 mm)
HEARTH EXTENSION BEYOND FRONT...................... 20
"
(508 mm)
HEARTH EXTENSION BEYOND SIDES........................12
"
(305 mm)
INSULATION FROM FIREBOX........................................... 2
"
(51 mm)
!
WARNING
:
THIS FIREPLACE HAS BEEN TESTED FOR USE ONLY WITH APPROVED GLASS DOORS. TO REDUCE THE RISK OF FIRE OR INJURY, CONSULT OWNER’S MANUAL.
THIS FIREPLACE IS DESIGNED FOR USE ONLY WITH SOLID WOOD LOGS, PLUMBED LPG OR NG LOG LIGHTERS OR PLUMBED ANSI Z21.60 DECORATIVE GAS LOGS. Consult instructions included with this firebox for further information.
PFS
®
US
CHIMNEY HEIGHT:
Max.: 40 ft. Min.: 14 ft.
(17 ft. with 1 or 2 offset
sections maximum)
6.5”
6.25
Report No. 08-154
ICC Evaluation Services Report No. 2401
Parts Lists ...............................................................................................................Pg. 2
Fireplace Overall & Framing Dimensions ................................................................Pg. 4
Fireplace Framing Dimensions (Combustible Floor Systems) ................................ Pg. 5
Safety Information ................................................................................................... Pg. 6
Product Overview ....................................................................................................Pg. 7
Clearance To Combustibles ....................................................................................Pg. 8
Fireplace & Chimney System ..................................................................................Pg. 8
Supporting Floor Systems .......................................................................................Pg. 9,10
Weight Determination ..............................................................................................Pg. 10
Component for combustible oors: 8” Metal Base .................................................. Pg. 11
Fireplace Assembly Procedures .............................................................................. Pg. 12 ~ 14
Firestop Radiation Shield ........................................................................................ Pg. 14
Firebrick Liners ........................................................................................................ Pg. 15
Electrical Line Feed ................................................................................................. Pg. 15
Fireplace Finishes and Combustible Trim Clearances ............................................ Pg. 16
Mantle and Mantle Shelf Clearances ...................................................................... Pg. 16
Installing Outside Air ............................................................................................... Pg. 16
Adding a Gas Pipe .................................................................................................. Pg. 16
Adding Electrical Connection .................................................................................. Pg. 16
Chimney Systems ................................................................................................... Pg. 17
Installing Damper and Chimney System ................................................................. Pg. 17
Fireplace Door Accessory ....................................................................................... Pg. 17
Owner’s Operation & Precautions ...........................................................................Pg. 18
Starting A Fire and Basic Operation ........................................................................ Pg. 18
Annual Fireplace Maintenance ................................................................................ Pg. 19
Technical Service ....................................................................................................Pg. 19
Replacement Parts .................................................................................................. Pg. 19
Appendix I ............................................................................................................... Pg. 20
Appendix II .............................................................................................................. Pg. 21
Warranty Information ............................................................................................... Pg. 22
Below is a sample picture of the rating plate that is located inside the lower dome side of your replace. Serial number and date
code should be stamped on the plate where required.
1
Page 4
MMST43 Fireplace Parts Diagrams
Figure 1
13
14
8
7
12
6
20
Combustible Floor Systems
9
10
Non-Combustible Floor Systems
Figure 2
13
14
8
7
12
6
20
9
10
19
17
1
19
3
3A
16
18
1
3
3A
2
Page 5
Optional Outside Ø4”
Combustion Air Kit
Model No.: MM4-AK
(Ø4” Ducting not included)
MMST43 Fireplace Parts List
ITEM P/N DESCRIPTION QTY
1 MFPST-43-1 HEARTH (Left or Right) 2
3 MFPST-43-3 SIDE WALL 5
3A MFPST-43-3A SIDE WALL W/4” KNOCKOUT 1
6 MFPST-43-6 LINTEL 1
7 MFPST-43-7 DOME SIDE - LOWER 2
8 MFPST-43-8 DOME SIDE - UPPER 2
9 MFPST-43-9 DOME TOP FOR 16” CLASS A CHIMNEY 1
10 MFPST-43-10 DOME FRONT/REAR - UPPER 2
12 125122-01 RATING PLATE, MM43ST 1
MM12AP
13
**
14
16 MMB43 STEEL SUPPORT PLATFORM 8 INCH HIGH 1
**
17
18 ** ASSY, FLOOR JOIST BRACE 4
19 ** #3 REBAR (Ø3/8”) x 36” 8
20 MMARC LINTEL TRIM (OPTIONAL) 2
Ø12” DAMPER / ANCHOR PLATE ---
INSULATION BLANKET ---
CEMENT BOARD ---
MM43STSHBL- Herringbone
MM43STFRBL- Running Bond
Refractory Firebrick Liners
(Herringbone Pattern shown, also available in Running Bond - see Pg.27)
Only the following doors have been tested and approved for use with this fireplace:
Crown-Breckinridge
or
McKenzie-Pendelton
3
Page 6
MMST43 Fireplace Overall Dimensions
62 7/8"
43 1/4"
29 1/8"
24 1/2"
3"
37 3/8"
A
A
18 7/8"12 1/8"
28"
14"
SECTION A-A
23 1/2"
38 5/8"
2 1/4"
Figure 3
Overall Dimensions
Figure 4
IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN. FROM TOP OF LINTEL AND 2 INCHES MIN.CLEARANCE MUST BE MAINTAINED ALL AROUND FIREPLACE DOME.
IF METAL FRAMING IS USED MAINTAIN A 1/2 INCH MIN. AIR SPACE FROM TOP OF LINTEL.
2” MIN. CLEARANCE TO
COMBUSTIBLES AROUND SIDES, REAR AND TOP OF FIREPLACE DOME.
Non-Combustible Floor Systems
Fireplace Framing Dimensions
57” I.D.
FRAMING
MAINTAIN THE 2” CLEARANCE TO
COMBUSTIBLES ABOVE THE DOME. DO NOT ATTACH COMBUSTIBLE MATERIALS ON TOP OF THE DOME.
28” O.D.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specically
approved with this appliance may result in property damage or personal injury.
4
Page 7
30 5/8"
65"
28”
1/2”
2”
Fireplace Framing Dimensions (Combustible Floor Systems)
20"
MIN
12"
MIN
12"
MIN
2" MIN
53"
Figure 5 - Combustible Floor
2” MIN**
8-1/2”
57” I.D.
FRAMING
2” MIN*
* 2 INCH CLEARANCE TO COMBUSTIBLES BOTH SIDES OF FIREPLACE
CLASS “A”
CHIMNEY
SEE FIG. 27 AND 28
SEE FIG. 26
** If using a raised hearth or metal base plate, note that a
combustible wood header must be no closer than 2” to the
top of the dome top.
Figure 6 - Non-Combustible Hearth Extension (by others*)
2” MIN*
53”
12”
MIN
20”
MIN
12”
MIN
* Not provided as part of replace
ONLY NON-COMBUSTIBLE
MATERIAL WITHIN 18” OF
TOP OF OPENING.
20”
Figure 7 - Combustible Floor
2” AIRSPACE
CLEARANCE TO COMBUSTIBLES FROM REAR AND SIDES
1/2” THICK
CONCRETE BOARD
8” METAL
PLATFORM
5
Page 8
Safety Information
WARNING: THIS FIREPLACE HAS NOT BEEN
TESTED FOR USE WITH AN UNVENTED GAS LOG SET. TO REDUCE THE RISK OF FIRE OR INJURY, DO NOT INSTALL AN UNVENTED GAS LOG SET INTO FIRE­PLACE.
WARNING: THIS FIREPLACE HAS BEEN TESTED
FOR USE WITH OPTIONAL GLASS DOORS: CROWN-
BRECKINRIDGE OR MCKENZIE-PENDELTON ONLY.
WARNING:
Install only approved, listed UL 103-16” I.D. Class A
Chimney System.
Chimney maximum height: 40 feet
Chimney minimum height: 14 feet (with offset = 17 feet)
2 offsets maximum.
Important: Follow the chimney pipe manufacturer’s instructions on the installation of their specic ue system.
GUIDELINES FOR USE:
All current and future users of FMI Products, LLC Fireplaces are charged with the responsibility for full knowledge of the
information contained within this manual which includes:
Strict requirements for assembly.
Detailed instructions for installation.
Cautionary guidelines for use.
On-going maintenance instructions.
It is the responsibility of the distributor, subcontractor and/or the general contractor – whoever shoulders the liability for installation of this product – to see to it that the work is in complete compliance with the guidelines and instructions in this manual. Note that the general contractor is the party accountable for seeing that adequate clearances are provided
from all rebox surfaces per specications in this manual.
DO NOT USE A FIREPLACE INSERT OR OTHER PRODUCTS NOT SPECIFIED FOR USE WITH THIS FIREPLACE.
The Grand Meridian is Designed for Use Only with:
- Solid Wood Logs
- Plumbed LPG or Natural Gas Log Lighter.
- Plumbed ANSI Z21.60 Decorative Gas Log.
DO NOT USE OR STORE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR GASES IN OR NEAR THE FIREPLACE!
ATTENTION: A re or an explosion could occur causing
property damage, injury or loss of life if you do not follow the information in this manual!
NOTE: THIS MANUAL MUST BE REPRODUCED ONLY
IN ITS ENTIRETY.
Before Beginning the Installation
Read these instructions carefully before beginning the
installation of this replace. Also, if installing an ANSI Z21.60
Decorative Gas Log, read the gas log appliance manufacturer’s literature regarding sizing and suitability for the installation into this Enclosure prior to installation.
Statement of Intended Use:
The Grand Meridian Fireplace is a modular refractory
masonry unit designed for eld assembly. The rebox is
constructed using pre-cast, interlocking refractory blocks. The blocks are then secured to each other using Mortar. The system includes all parts necessary for the assembly of a
complete masonry replace. In addition to the basic enclosure, a standard 1-1/8” thick, high temperature refractory brick is required to line the interior of the rebox.
These replaces are not intended to serve as a primary heat source, rather, the replace was expressly created as a
supplemental source of heat. The unit is designed for use with solid fuels such as cord wood.
WARNING:
Any application other than the “Intended Use” as stated above
is in violation of the manufacturer’s instructions and is hereby prohibited. Such violation may cause immediate hazard, property damage or loss of life and will void all liabilities to the manufacturer and will void all warranties explicit or implied.
6
Page 9
Product Overview
Introduction
We extend a warm welcome from all of us at FMI PRODUCTS, LLC. You may have thought long and hard before you chose the
replace which would grace your home. Rest assured that
every component of the Fireplace has been tested to ensure long-term durability.
Product Overview
FMI Products, LLC Fireplaces are designed as factory-
built blocks to be assembled on-site. These replaces may be installed on either combustible or non-combustible oors. In order for the replace to be installed on a combustible oor though, it is necessary that the replace be supported on a platform or sub-oor that is non-combustible.
The Four Components of the Grand Meridian Fireplace:
Combustible or Non-Combustible Floor Non-Combustible Raised Platform Grand MeridianFirebox and Smoke Dome UL103-16” class A listed chimney system required.
Important: Follow the chimney pipe manufacturer’s instructions on the installation of their specic ue system.
Figure 8 - Typical Installations
Internal
Wall
Installation
Island
Installation
Careful step-by-step instructions for each phase of the installation procedure will be given for the Grand Meridian
conventional radiant heat replaces. Those instructions generally fall into the following categories:
Spacing and clearance as it relates to combustible materials.
Familiarity of installation for all components.
The strength of the oor on which it rests.
Chimney system measurements.
Choice of materials and craftsmanship in replace and hearth nishing.
Note that each of these topics will be covered in detail and that the installer is expected to understand each phase completely before going on to subsequent instructions.
Attention: Be advised that all the illustrations in this manual
are for general reference only. Do not scale drawings. Actual design elements will vary from case to case. Pay attention to
specied minimum clearances to combustibles.
Testing and listing for the Grand Meridian Fireplace has been undertaken by PFS Inc. (Report No. 08-154) to UL 127.
Attention: You may need a residential building permit to install
a Grand Meridian Fireplace. Consult local jurisdictions before you get started!
If asked, advise the local authorities that the Grand Merid­ian Fireplace is designed for installation per the National Fire Protection Association Standard for Chimneys, Fireplaces, Vents and Solid Fuel-Burning Appliances (NFPA211).
When choosing the location of your Grand Meridian Fireplace,
keep in mind you must maintain 2” (two inches) minimum
clearance from left, right and rear of Fireplace to surrounding structure. Also, when choosing a location, consider outside air requirements to determine if it will be on the left or right side of the Fireplace. In the case of an island installation, outside
air accessibility may be obtained through sub-ooring. See
section on Installing Outside Air on page 17.
7
Page 10
Clearances to Combustibles
The distance to be maintained from the surfaces of the
replace to combustibles must be observed. Below is a list of the most common combustible materials to name a few:
Drywall Wood ooring Plywood Sub-ooring Wood Framing Particle board
Mill board Plywood paneling
Grand Meridian Fireplace & Chimney System
Prior to starting the installation, check with local, regional or state codes for any restrictions or required permits regarding
your replace installation.
The Grand Meridian is designed to be installed with a 1)
listed UL-103-16” I.D. Class A, Metal Chimney System.
Maintain the following clearances:
Unit front, sides, rear: 2” (50 mm) Combustible Floor: 8” (150 mm) Combustible Sheathing above opening top: 8” (200 mm) Sheathing or trim to opening sides: 8” (200 mm) Mantel above opening: (refer to Fig.9) Opening to sidewall: 24” (500 mm) Hearth extension beyond front: 20” (500 mm) Hearth extension beyond sides: 12” (300 mm) Insulation from rebox: 2” (50 mm)
Figure 9
Understanding Clearance to Combustibles
There is a build-up of considerable amount of radiant heat on the outer surfaces of the Grand Meridian Fireplace. It’s critical that proper clearances to combustibles be maintained so that this radiant heat is maintained to safe limits.
MMST43 Grand Meridian Fireplaces have been designed
with clearance to combustible oors at a minimum of 8-1/2” (eight and one half inches) as provided by the 8” metal base and 1/2” concrete board. Cover any part of the combustible oor system left exposed with 1” (one inch) thick ceramic ber
insulation rated up to 2,100°F.
This Grand Meridian replace is intended as a supplemental 2) heat source only. It is not intended as a primary heat source.
It is the responsibility of the contractor installer (not the 3) manufacturer) to ensure that adequate combustion air is
provided for proper function of this replace. Fireplaces
take up a large volume of replacement air from outside the house and if the house is of airtight construction, smoke spillage may occur if proper draft is not achieved.
There are many conditions beyond a manufacturer’s 4)
control regarding improper replace operation. The manufacturer cannot ensure “smoke free” operation,
nor can the manufacturer take on the responsibility for problems with surrounding construction; chimneys that have not been built at the right heights; system drafts caused by faulty mechanical systems; adverse weather conditions or any other inclement environmental situations over which the manufacturer has no control.
Inspect all replace & chimney components for evidence 5) of damage prior to starting installation. Consult your local distributor for replacement parts if necessary.
Under no circumstances should you make any adjustments 6)
or modications to the chimney system during the
installation procedure. If you do, you are not only liable for negating the warranty, but you could very well cause a
serious malfunction of the replace. You must follow your
chimney manufacturer’s instructions.
Caution is urged if it is decided to add insulation material 7) to any part of the Grand Meridian Fireplace or Chimney system, be certain that the insulation material is kept at
least 2” (two inches) away from any part of the system.
When using insulation or vapor barrier materials, cover with a layer of plywood, particle board or gypsum board to
maintain the specied 2” (two inch) clearance.
Air spaces around rebox must remain open. DO NOT ll 8)
these open spaces with insulation or packing material of any kind.
The Grand Meridian Steel Platform , the 1/2” concrete
board
above, the 1” ceramic ber blanket or board within the
platform (Fig.15) and the 2” clearance for dome front, and unit sides provide the temperature safety margin to combustible materials.
Chimney System Heights
When installed, the maximum overall height of the chimney
system from bottom of replace to the top/termination chimney
is 40 feet. The minimum installed height of the completed
Chimney System is 14 feet with a straight ue stack, 17 feet if
the chimney includes one or two offset sections.
8
Page 11
Supporting Floor Systems
I-JOISTS
Anchor Brackets
I-Joist
It is the ultimate responsibility of the installer to ensure that proper concrete slab supports are used.
Attach the rebox side wall anchors to steel support frame by inserting all-thread rods through holes on the bottom ange
on the steel support frame as shown in Figure 14. Secure with
two Ø 2” o.d. x Ø 9/16” i.d. x 0.10” Washers and two 1/2-13
UNC Nuts.
WARNING to the licensed design professional and/or building
contractor: It is your responsibility to be certain that the Grand Meridian can be properly supported by the combustible oor system on which the replace will rest.
For replace support foundations installed on concrete refer to
Appendix I and II (pages 20 & 21 ) for specic instructions.
Rebar locations
Lay-out the position of the replace and drill holes where
the rebar will be located. Secure eight #3 rebar 4 inches into concrete foundation with ITW Epoxy or Simpson Epoxy. Follow manufacturer’s instructions for installation of rebar into slab.
Wood Floor
Anchorage of replace to wood oor construction is required.
Refer to Figure 10 for anchorage locations. Four anchors are
required to attach to the sub-ooring framing.
Crawl Space or Upper Floor:
For installation of rebox over combustible crawl spaces or upper oors, anchorage of the rebox is required. Illustrations
of examples of possible anchorage methods are shown in
Figures 10 thru 13 depending upon the type of oor framing.
Final method of anchorage to be determined by licensed design professional.
Figure 10
Metal Base Assembly
2X FLOOR JOIST
EXAMPLE ONLY
Floor Sheathing not shown for clarity
A35 Brackets (16 required)
2X FLOOR JOIST
For conventional framing where the oor joists are parallel with the sides of the rebox, the addition of oor joists to align
with the anchor brackets allows the brackets to be directly
connected to the oor joists.
Note that additional oor joists may be required to support the weight of the rebox and chimney. Where the oor joists run parallel to the front of the rebox, anchorage can be
accomplished in like manner as shown in Figure 12 using
blocking between the oor joist.
For oors supported by I-Joists, the method of anchorage
is illustrated in Figures 10 and 11. Figure 12 illustrates the
general arrangement of anchorage to oor framing.
It is important to take into consideration that the load for the Grand Meridian Fireplace must be considered as additional
dead load that will have to be supported by the oor framing. Additional oor joists or I-joists may be required as determined
by the licensed design professional.
The weights to be considered are noted in Table I. It is the task and responsibility of the general contractor/installer to see that the proper reinforcement for weight loads are made by a
licensed design professional prior to the replace installation.
As stated above, it is desirable to place additional framing for alignment of anchor rods. Refer to Figure 14 for anchor rod locations.
Figure 11
I-Joist Anchoring Top View
Simpson Strong-Tie A-35 or equivalent
Figure 12
I-Joist Anchoring Bottom View
9
Example Only
Example Only
Page 12
Grand Meridian Weight Determination
48 3/4"
8"
12"
2” min clearance
Fireplace outline
10”
The following are dead load weight estimates for the Grand Meridian Fireplace.
Table I
Model: MMST43
Fireplace 835 lb..
Damper/Anchor Plate, Firebrick & Mortar
Steel Platform 70 lb..
Floor Area
Other Weight Considerations:
Fireplace nished facing (surround): This information needs to be obtained from the contractor.1)
Weight of metal ue: See chimney manufacturer’s weight specications. Some chimney systems can weigh up to 50 lb. per 2)
linear foot.
350 lb..
53” x 28”
(10.3 square feet)
Table II - Deection Limits
Construction L S or W D +L1
Floor Members
1
For wood structural members having a moisture content of less than 16 per cent at time of installation and used under dry
conditions, the deection resulting from L + 0.5D is permitted to be substituted for the deection resulting from L + D.
Note that Grand Meridian cannot accept responsibility for structural oor support details. All drawings are presented as mere illustrations to indicate the presence of the underlying oor system. It is the responsibility of the general contractor/installer to consult with a local licensed design professional for guidance in building a proper oor support system.
Figure 14
Floor framing anchor rods see Figure 15 for support of anchor rods by the steel support frames.
Figure 16
Typical Anchorage Layout
I/360 --- I/240
Figure 15
EXAMPLE ONLY
SECTION VIEW ROTATED 90CW
10
Page 13
Combustible Floor Installations
8” Metal Base
The Grand Meridian Metal Base ensures the minimum
8” (eight inch) clearance above combustible ooring is
maintained.
A layer of 1/2” minimum Concrete Board is required on
the top and mid section below as shown in Figure 17. The required sizes are shown in the table below.
1/2” Thick Cement Board Dimensions
Model A1 A2 B1 B2
MMST43 53” 28” 48” 23”
Figure 17
Place Cement Board on top rails of platform.
Place Cement Board on top of cross-members.
26 ga. galv. Hearth Ember Shields
Eight (8) All-Thread Rods are secured to the top ange
of the Metal Base with sixteen (16) at washers (2”OD x 9/16”ID x 0.10”) and sixteen (16) 1/2”-13 UNC Nuts.
Anchor Bracket All-Thread Rods are secured to the bottom ange
of the Metal Base with eight (8) at washers (2”OD x 9/16”ID x
0.10”) and eight (8) 1/2-13 UNC Nuts.
Remember to tighten up nuts below the oor after replace
installation in order to take up any slack in the threads.
Metal Base Assembly
A1
A2
B2
B1
IMPORTANT:
What You Will Need
You will nd that the Grand Meridian Fireplace is designed
to be completely assembled on-site, consisting of interlocking precast parts. You will need a thin-set type mortar for bonding.
The parts of the replace are made of incredibly strong blend
of specialty cement and a light weight aggregate.
IMPORTANT! When applying mortar, it is imperative that the concrete blocks be maintained moist (not soaking) so they don’t absorb the water out of the mortar and cause adhesion to fail. Frequently run a damp sponge to the parts before mortar is applied!
The installation of an anchor plate/damper is required but not supplied. You may purchase it from FMI PRODUCTS, LLC. Also, an optional combustion air inlet MM4-AK can be obtained from FMI PRODUCTS, LLC. Refractory Firebrick Liners also need to be installed. These
should be a minimum of 1-1/8” (one and one-eight inches)
thick. The liner will be applied within the walls and hearth area
of the rebox.
TOOLS NEEDED FOR INSTALLATION:
One 4 ft. level
Roto-hammer with ½” drill bit
Drill motor with mixer blade to mix Mortar
Two empty 5 gallon buckets to mix Mortar
One wheelbarrow and shovel to mix concrete
Grout bag
Triangular masonry trowel
Rubber hammer
Sponge and 2 water buckets to wipe down and moisten parts prior to applying mortar
MATERIALS NEEDED FOR INSTALLATION:
Epoxy for securing rebar in footing / foundation
Three (3) - 90 lb. bags of ready mix concrete with ¼” or
smaller aggregate
MATERIALS INCLUDED:
8 - ⅜” Rebar x 28” Long
8 - ⅜” Rebar x 12” Long
1 - 50 lb. bucket Mortar
20 - Small Wood Shims
Hearth Ember Shield:
Metal safety stripping is required between the front of the Fireplace Hearth and Hearth Extension (not supplied). A 26
gauge galvanized 4” wide metal strip can be used. The length needs to extend 2 inches beyond each side of the replace
opening. If two strips are used, make sure they overlap at
least two inches in the middle. The strip is placed about 2” into
the underside of the platform at the front of both openings on
the replace.
Note: When using an on-site-constructed hearth extension,
you may use a sand-cement grout between the hearth and extension instead.
11
Page 14
Fireplace Assembly Procedures
MMST43 Fireplace Assembly
Mixing the mortar – The mortar comes premixed and a) should be dry. Be sure to use clean water and work it up into a mixture that is pasty but not lumpy. If it’s too thin and the surfaces don’t stay moist, the components will not adhere. Load the mixture into a standard grout bag.
Apply about ½” (one-half inch) thread of mortar. The mortar b) bead should be approximately ½” (one-half inch) away
from all edges. The mortar has a considerable amount of holding power so do not overload the components with too much mortar. Keep the components moist at all times!
Some mortar will “ooze out” when placing components c) together, this is normal. Wipe excess away with a trowel. Do not cover component surfaces completely with mortar. Do not apply the mortar in thick bands even if the component you are working with is larger than the rest. You will want
to apply “stripes” of mortar in these situations.
Make sure components are level. It’s extremely important d) that you pay careful attention to how you are assembling the Grand Meridian Fireplace since every component builds on the next. If you have to make any kind of an adjustment,
do not try to do it “by loading an opening” with mortar, this will only result in a replace that will not be plumb or level.
Use wood shims instead. You will nd these small wood shims supplied with the Grand Meridian Fireplace and you can nudge them in between openings to achieve the precision you need in making component adjustments. Once you have inserted any shims, you will want to cover any gaps that may have resulted with the mortar.
1) Place the Grand Meridian Fireplace hearth base on top
of your non-combustible oor or metal base. For concrete slabs, supporting oor needs to be rated at ASTM 90.
a) 2) Combustible Floor Installations: Mix up a batch of mortar and place hearth slabs on
top of cement board which sits on top of the Raised Metal Platform (see Figure 15). All-thread rods should stick up through the holes on the hearth slabs.
b) Non-combustible Floor Installations: Draw an outline of the hearth area based on the dimensions shown in Figure 18. Position Hearth slabs and mark rebar center locations (see Pg. 10, Fig.14). Drill 4 inches into concrete slab and secure the four pieces of rebar with epoxy.
Figure 18
Apply mortar
between joints
28”
53”
LH Hearth 2nd
RH Hearth 1st
Four 26ga.galv. 4” wide
Hearth Ember Shields required (not supplied)
2” min
overlap typ.
Before installing the side walls, conrm placement of 3) outside combustion air side block (if required), this can be installed either side depending on which side is accessible to outside combustion air. Prepare side wall footprint with the prepared mortar.
Figure 19
Setting Firebox Sides
Keep the assembly of the next sections of the rebox 4) side walls moving up, keeping components moist, mixing mortar as you need it and threading the mortar appropriately as you stack each section, one onto the next. Constantly check for squareness and levelness while building each course of block. As you complete each section, make certain that you adhere the mortar at each and every joint.
12
Page 15
After the last side walls are in place it is time to install the 5) rebar. Mix approx. 2 cu. ft. of Ready-Mix Concrete. Insert
the 36” rebar vertically through the cells, into the holes in
the hearth, adjacent to the rebar and/or all-thread sticking up from the hearth. Fill all cells with Ready-Mix Concrete mix.
Figure 20
Keep damp at all times while applying mortar.
IMPORTANT! Keep in mind that, when applying the mortar, you must frequently run a damp sponge to the parts before mortar is applied!
Set the lintel in place as shown in 6) Figure 21. Check that all is level. If you need to make adjustments, use shims. Place one or more of these shims between the lowest wall component and the top surface of the base plate.
Once you are satised with the degree of levelness, you
can address any gap that may have occurred with an appropriate amount of mortar.
Figure 22
Lintel Assembly
Lintel
As you are connecting each Grand Meridian component, 10) be certain you are following the instructions given previously for using mortar. Stop to look at the smoke dome side, front and rear walls to see that they are aligning correctly and that the surfaces be smooth and uniform. Make sure connections are covered with an adequate amount of mortar. Remember that you have the option of using shims and covering them with mortar
if you need to. Make any adjustments to the replace
alignment before continuing to the next step.
Figure 23
Lower Side Dome Assembly
Lintel
Figure 21
Building Lower Firebox
Note: Although you are cautioned to use mortar sparingly because it does have such holding power, you
should look over the rebox assembly at the end and ll
in any gaps, especially joint connections, with the mortar. Needless to say, you must make adjustments to be sure
the replace is level and square while the mortar is still
wet.
Set the remaining lintel as shown in 7) Figure 22.
Now you are ready to start the smoke dome assembly. 8) Take the lower side dome positioned so that the beveled face lines up with the inward angles of the lintel sides (see Figure 23). Top surfaces should be level.
Now position the front/rear smoke dome parts on top of 9) dome. These parts require care in leveling, noting the parts have a slight bevel. Check for vertical with level (Figure 24).
Figure 24
Lower Dome Assembly
Check your assembly here. If things are proceeding as 11)
they should be, the nished top surface should be at
and level.
Now you can set the smoke dome top plate into position. 12)
Be sure that it is ush in every direction as you place it
on the crest of the smoke dome wall assembly.
13
Page 16
Figure 25
Completed Firebox
Firestop Radiation Shield
A Firestop Radiation Shield is required in multistory installations
at each oor penetration above that where the Support Box is
located.
Seal Anchor Plate using a 1” thick ceramic ber blanket. 13) Complete the Anchor Plate assembly by securing with (4) 1/4-inch masonry anchors as shown in Figure 26.
Figure 26
Chimney Anchor Plate Installation
Place 1” Ceramic Fiber
Blanket under Anchor Plates and secure with eight 1/4-inch masonry anchors.
Figure 27
Firestop Spacer with Living Space Above Ceiling
E x i s t i n g C e i l i n g Frame
Firestop Spacer
eight #8 x 3/4 Screws
Firestop Radiation Shields also provide complete separation
from one oor space to another or attic space as required
by most codes. When the double wall pipe passes through
a framed opening into an attic space, the restop must be placed into an attic oor as shown in Figure 28.
Figure 28
Firestop Spacer with Attic Space Above Ceiling
eight #8 x 3/4 Screws
Now that you have completed the smoke dome 14) assembly, all the components should stack up for a
smooth transition into the ue components. Setting the
smoke dome completes the Grand Meridian Firebox and Smoke Dome assembly. You are now ready to begin the
installation of the necessary rebrick lining and the ue
components.
WARNING: DO NOT PACK REQUIRED AIR SPACES WITH
INSULATION OR OTHER MATERIALS.
Firestop Spacer
E x i s t i n g C e i l i n g Frame
Follow your chimney manufacturer’s instructions on specic
guidelines pertaining to their chimney and Firestop Radiation Shield installation instructions.
14
Page 17
Grand Meridian Firebrick Liners
Custom Firebrick Lining
Custom Firebrick lining is not included with the replace. There
is, however, the option of modular pre-fabricated panels that can be obtained from FMI PRODUCTS, LLC. See exploded parts page for details.
If custom rebrick lining is desired, 1-1/8” inch thick liners will be required. The pattern for the rebrick lining is exclusively
your choice. Before you install the lining, remember to consider any holes your contractor may need to drill for gas, electrical or combustion air kit access holes.
Please use a certied mason to lay-in the brick. He will follow the proper instructions from the replace liner manufacturer
and also understand the type of adhesive or cement he is to use.
Make sure the replace is installed with the nished rebrick oor of the replace so that it is at least 11” (eleven inches) above the combustible oor system.
Figure 30
Sectioned Side View
If Optional Arches are used, corner notching will be required on all four places.
Figure 29
FINISHED FIREBRICK HEARTH LINER
11 INCHES MINIMUM TO COMBUSTIBLE
FLOOR
Finished Height to Combustible Floor
Disclaimer: FMI PRODUCTS, LLC wishes to express that
as the manufacturer of the Grand Meridian Fireplaces, they cannot take any liability or responsibility for they way the firebrick or the firebrick mortar performs. It is not unusual in the course of the life of the firebrick, or the firebrick mortar, for
heat stress cracks to appear. FMI PRODUCTS, LLC cannot be responsible for this and other wear and tear to the firebrick and mortar.
The following Firebrick Liners are available from FMI PRODUCTS, LLC:
Figure 31
Herringbone Brick Pattern
MMST43SHBL- Herringbone
MMST43FRBL- Running Bond
Modular Firebrick Lining
If using our Firebrick Liners, simply use an extra bucket of the
mortar we supply. Install Hearth Liner rst, then continue with
sides. Consider if brackets for grates will be required also if pre-drilling is required for gaslines, electrical or if the outside combustion air kit is to be installed. If the optional Arch is
used, the top corners of the rebrick side liners will need to be
notched (see Figure 30).
15
Figure 32
Running Bond Brick Pattern
Page 18
Fireplace Finishes & Combustible Trim Clearances
Hearth Material & Dimensions – Codes are strict regarding the use of proper materials for hearth extensions and the proper dimensional characteristics.
All hearth extensions must be made of code-rated, noncombustible materials such as tile, brick, concrete or stone. Grand Meridian Fireplaces usually have an opening of approximately 8 sq. ft. (eight square feet) that translates to a
hearth extension of about 20” (twenty inches) at the replace’s opening and about 12” (twelve inches) extension at each side.
These relative dimensions are also covered by code. Note that it is required that metal safety strips must be laid on the
oor of the non-combustible raised platform. These should be 26 gauge and measure 4” (four inches) wide. They need to
extend half way under the platform and half way under the hearth extension material (see Figure 18).
Attention: You will note that there will be a gap between the
replace front and the extension of the non-combustible hearth
material. Be certain that you seal this with non-combustible material.
Mantle and Mantle Shelf Clearances
As with any radiant heat replace, all Grand Meridian Fireplaces
must comply with building code safety clearances, for units that have openings of 6 sq. ft. (six square feet) or greater.
For Mantel clearances see Figure 9.
Walls that Adjoin – your replace cannot be installed closer
than 2 ft. (two feet) to any adjoining walls in the room where
the replace is.
Caution in Regards to Combustibles – If any part of the replace
or objects in the room (curtains, rugs, paint, cushions, etc.) start
to show warping or discoloration due to heat from the replace, it is time to take immediate action. Do not use the replace until you have gured out how to address the problem. You are facing a potential re hazard. FMI PRODUCTS, LLC cannot
be responsible for the make-up of material on the exterior of
the replace you have chosen, nor can FMI PRODUCTS, LLC
be held responsible for the materials in a room that may be responding negatively to heat. However, in almost all cases, there is a solution to the problem, either by making adjustments
to airow or the modications to the room itself.
Installing Outside Combustion (make-up) Air
1) The Grand Meridian Fireplace needs enough make-up air to function properly and some local building codes may require outside combustion air to be provided. If no make-up air is
provided, improper ue drafting may occur, creating negative
pressure whereby smoke may enter the home, especially in homes that are very well insulated and tightly sealed. Check
local building codes for specic requirements.
2) Install Combustion Air Kit MM4-AK into the Grand Meridian Firebox through the side wall opening provided. The tubing
that goes out of the rebox wall must feed into a exible
metal conduit as the source for outside combustible air. It can go straight out through an outside wall or into a ventilated crawl space. If crawl space is used, check codes for proper termination.
3) Be sure that you carefully check the source of the outside air before you choose the site for your air intake. You don’t want a place where snow will collect, where bushes or trees will be growing or a location that is too close to any other structure.
4) Install a screened termination cap to keep out animals.
Adding a Gas Pipe
You may elect to add a vented decorative gas appliance (gas log) to your Grand Meridian Fireplace. If so, follow the installation instructions from the Decorative Gas Appliance manufacturer. Familiarize yourself with requirements for installation as outlined by the National Fuel Gas Code, ANSI Z223.1. This gas pipe provision should only be used on a decorative gas appliance.
1) You can route the gas piping practically anywhere in the
rebox – the oor, back wall or side walls. You will just need
a masonry drill; the instructions from the gas appliance manufacturer will be very straightforward.
2) Fill in the holes you have drilled around the gas piping with the regular mortar.
3) Follow the Gas Log manufacturer’s instructions.
Adding Electrical Connection
Like the gas line, electrical feed lines can be run through
the oor, back wall, or side walls. Follow local building and
electrical code requirements.Grand Meridian Chimney
Systems:
The Grand Meridian Fireplace requires the following chimney
systems:
All chimney systems must be installed with an integrated damper/base plate installed on top of unit. Installers are cautioned to put the chimney system together exactly as instructed and shown in chimney manufacturer’s guide. Any variations may have serious consequences resulting in an accident or malfunction. If instructions are not followed, the warranty on the product will become null and void.
Note that the most important aspect of the installation is maintaining the minimum required clearances to combustible
16
Page 19
materials according to the chimney pipe manufacturer’s
recommendations, otherwise a potential re hazard may
occur.
Warning: do not interchange chimney manufacturer’s parts with any other parts except those specically required by
the chimney manufacturer’s recommendations otherwise a potential hazardous condition may be created.
Attention: When choosing a Chimney System it must meet the following requirements:
Designed for installation in accordance with the National
Fire Protection Standard and UL 103.
Meets the requirements of NFPA 211. Designed in accordance with ICC Codes.
Figure 33
Elbow
Return Elbow
Elbow
6' Max.
6' Max.
Return Elbow
Elbow
A
Elbow
Return Elbow
6' Max.
Ceiling
B
Support Pipe 12S-12DM
Return Elbow
6' Max.
Return Elbow
6' Max.
Assuming you have sections of vertical pipe that are more than 10’ (ten feet) measuring between elbows, you must insert – at midpoint – a chimney stabilizer. When installing the stabilizer, pull out the support straps with a good amount of tension and hammer to the frame.
Installing Damper and Chimney System
The Damper System/Anchor Plate assembly is required for the installation of these chimney systems. Consult the Chimney System manufacturer’s instructions.
Using the Damper/Anchor Plate Assembly, apply a 1/4” 1. (one-quarter inch) bead of gasket cement around the base of the Anchor Plate. Apply ceramic blanket gasket to the gasket cement.
Apply balance of gasket cement in a 1/4” (one-quarter 2. inch) bead on top of smoke dome top approx. 3” (3 inches)
outside of outlet hole. Install damper on top of unit pressing damper into cement.
Place chimney adapter onto top of damper plate and 3. center in opening using gasket supplied with adapter.
Attach adapter with (12) #8 cement fasteners supplied, 4. carefully drilling holes into damper plate.
Attach damper chain stop on center rear of lintel 3” 5. (three inch) vertical from opening using (3) #8 cement fasteners.
Fireplace
MMST43
Elbow
Chimney System
UL103-16” I.D. Class A
6' Max.
C
Attention: Clearance to combustible construction cannot be
reduced during course of construction. For the safe operation
of the nished replace, these clearances must be followed
when building the framework for the chimney system.
Finishing Your Installation
To complete your replace installation, a replace grate will be required for safe operation. The replace grate must be sized to 50% of the hearth maximum. Additionally, a replace
screen must be installed for safety.
Fireplace Door Accessory
IMPORTANT: Only Crown-Breckinridge or McKenzie­Pendelton Doors are approved for use with this replace.
For installation Instructions, see separate instructions included with doors.
17
Page 20
Grand Meridian Owner’s Operation & Precautions
Installers of the Grand Meridian are urged to leave the owner’s manual with the unit after installation is complete.
WARNING: Do not attempt to operate your replace
without a re safety screen installed.
CAUTION: The manufacturer cautions against using chemical
chimney cleaners. Never use charcoal or coal in the replace
under any circumstances.
First Lighting of the Grand Meridian – After construction 1)
is completed, all elements of the replace and chimney
system must be completely dry. This means that the unit
must stand without any ring for a minimum of 28 days. Only after that period of time can a rst lighting take place. The rst re must be small and well-controlled, started
with a small amount of kindling. Add no more than eight
pounds of wood, preferably small logs not more than 3”
(three inches) in diameter. You will probably burn no more
than three to four of these small logs. Do not let the re burn for more than one hour. After this rst lighting – when the replace has started to “cure” Do not set another re
for at least 24 hours.
Starting a Fire and Basic Operation
Before starting a re in your replace, open the damper to
its’ fully open position. Crumple some paper and place it on the log grate. Use some soft, dry wood as kindling and put it on top of the paper. Place some small logs or split logs atop the paper and kindling.
Finish off the fuel load with a couple of hardwood logs or split logs – oak or hickory. Check to see that you’re stacking the logs so that they will fall inside the grate as they burn.
To get the most out of your wood, it is recommended that you let it set and completely dry out for nine months to a year.
When you are satised with the arrangement of your wood
load, light the paper which in turn will ignite the kindling, then
the softer wood and nally, the harder wood logs. As the re burns, you can carefully lay additional logs on the ame, but
make sure you place them gently without forcing them into the opening.
Second Lighting – Start the re slowly and gradually as 2) you did with the rst lighting, but this time you can burn up to ten pounds of rewood, probably four to ve logs that are 3” (three inches) in diameter. With the second lighting you can let the re burn two hours – no more.
After First and Second Lightings – When the replace 3)
has been properly cured with 1st and 2nd lightings, you will be able to add a full fuel load to the Grand Meridian
which is about 10 to 15 pounds of rewood at any given
time. Consider that this typical fuel load is three to four dry
hardwood logs that are about 6” (six inches) to 8” (eight
inches) in diameter.
Without a grate for your rewood to rest on, you cannot 4) get the air ow you need under the re which makes for a hotter, more satisfying re.
Don’t “over burn” – Always remember, your Grand
Meridian Fireplace is an elegant addition to your home. It is not an indoor incinerator! If you start to use the
replace and begin a routine of “over burning,” you
can permanently and unalterably damage the unit. Under no circumstances should you be burning household trash, including chemicals and combustibles,
cardboard boxes, your ofce papers, scrap lumber
or stray branches from your yard, particularly pine.
WARNING: Burning of above mentioned materials will
cause an unsafe condition and will void your warranty!
18
Page 21
ANNUAL FIREPLACE MAINTENANCE
Your replace and chimney require seasonal and monthly tune-ups”. Like any piece of well-built equipment,
the Grand Meridian Fireplace and chimney needs routine maintenance.
The manufacturer recommends that inspection of the
replace and chimney take place on a monthly basis during the
heating season.
Start at the top, looking for birds’ nests, leaves or any other obstructions. Also check the spark arrestor, for creosote
or soot build-up. Twice a year, you will want to clean the rebox
and chimney yourself or hire a professional chimney sweep to do the job for you. If you elect to do it yourself, use a plastic, wood or steel brush for the inside of the chimney.
For the spark arrestor, scrub with a wire brush. To
dismantle the chimney cap for cleaning of the ue, unscrew
the four screws that hold it in place. For cleaning access from
below, open the damper in the rebox. It is best to use a exible
handle chimney cleaning brush made especially for the job.
If your replace system has any offset chimney sections, start cleaning with the exible brush from the top of the section downward to the elbow. Then clean from the rebox up to the
offset/return section.
SURFACE CRACKS
The Grand Meridian FIREPLACES are manufactured using high quality materials. During the drying process, surface
cracking may occur. These small cracks (under 1/16” will not effect the replace safety or performance). During the assembly process, ll surface cracks with thin-set mortar and brush when drying for a smooth surface nish.
Removal of Creosote and Soot Formation – Creosote
vapors are known to form in the relatively cool chimney ues of slow burning res, hence, creosote residue collects on the ue
lining. Because of soot and creosote build-up, it is recommended
that the replace and chimney cleaning be done twice a year. In
colder climates, cleaning should be done more often.
Always allow the replace to completely cool before
you work on it, which means, of course, shutting off all gas and electrical connections, also.
Be certain that you use only solid fuel in your replace.
You may use a natural or LP gas log lighter as a method to start
your wood re.
The ue damper must be in the OPEN position whenever there is heat in the replace.
Technical Service
Be sure that you have covered the oor of the replace
and out to the hearth with a damp sheet that has been taped securely in place. When all the soot has settled, remove the sheet and vacuum up – don’t sweep the excess soot.
Good old-fashioned “elbow grease” is enough to remove the extraneous matter from the inside of the rebox
and chimney. Never use any chemical cleaners as their residue
could introduce a re hazard after the task is completed.
Outside Inspection – During your once a month
inspection of the rebox and chimney, make it a point to also check the outside of the chimney, the metal ashing and weather seals that surround it. If you nd any cracks or openings around
screws or nails, seal them to avoid any roof or chimney chase leaks.
You may have further questions about installation, op­eration, or troubleshooting. If so, contact FMI PROD­UCTS, LLC at 1-866-328-4537.
When calling please have your model and serial num-
bers of your replace ready.
You can also visit our web site at
www.fmiproducts.com.
Replacement Parts
If this product is missing a part or has a broken com­ponent, please do not return it to the store. Call FMI PRODUCTS, LLC at 1-866-328-4537 to answer questions and replace parts under warranty.
Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
When calling, have ready:
• your name
• your address
• model and serial numbers of your replace
• how replace was malfunctioning
• purchase date
19
Page 22
AppendixI
For installations regulated by the International Residential Code, the
support foundation for the fireplace installed on concrete shall
consist of aminimum of6inchesthick reinforced concrete slab. The minimum specified compressive strength of
f’
c
,shall be as
required in Table R402.2 of the International Residential Code (IRC). Concrete subject to moderate or severe weathering as indicated
in Figure R301.2(3) of the International Residential Code (IRC) shall be air entrained as specified in TableR402.2ofthe International
Residential Code (IRC). The maximum weight of fly ash, other pozzolans, silica fume, slag or blended cements that is included in
concrete mixtures for garage floor slabs and for exterior porches, carport slabs and steps that will be exposed to deicingchemicals
shall not exceed the percentages of the total weight of cementitious materials specified in Section 4.2.3 of ACI 318. Materials
used to
produceconcrete and testingthereofshall comply with theapplicable standards listed in Chapter 3 of ACI 318.
For installations regulated by the International Building Code (IBC), the support foundation for the fireplace installed on concrete
shall consist of a minimum of 6 inches thick reinforced concrete slab. The concrete strength and durability shall comply with Sections
1903, 1904 and 1905 of the International Building Code (IBC).
TABLE R402.2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE
MINIMUM SPECIFIED COMPRESSIVE STRENGTH
a
(f’
c
)
Weathering Potential
b
TYPE OR LOCATION OF CONCRETE CONSTRUCTION
Negligible Moderate Severe
Basement walls, foundations and other concrete not exposed to theweather 2,500 2,500 2,500
c
Basement slabs and interior slabs on grade, except garage floor slabs 2,500 2,500 2,500
c
Basement walls, foundationwalls, exterior walls and other vertical concrete
work exposed to the weather
2,500 3,000
d
3,000
d
Porches, carport slabs and steps exposed to the weather, and garage floor slabs2,500 3,000
d,e,f
3,500
d,e,f
a. Strengthat28dayspsi.
b. SeeFigureR301.2(3) forweathering potential.
c. Concrete in these locationsthatmay be subject to freezing and thawing during construction shall be air-entrained concrete in
accordance with Footnote d.
d. Concrete shall be air-entrained.Total air content(percent by volume of concrete) shall be not less than 5 percent or more than
7 percent.
e. See Section R402.2 for maximumcementitious materials content.
f. For garagefloorswith a steel troweled finish, reduction of thetotal air content (percent by volume of concrete) to not less than
3 percentis permitted if the specified compressive strength of the concrete is increased to not less than 4,000 psi.
20
Page 23
AppendixII
FIGURE R301.2(3) WEATHERING PROBABILITY MAPFOR CONCRETE
a. Alaskaand Hawaii are classified as severe and negligible, respectively.
b. Lines defining areas are approximate only. Local conditions may be more or less severe than indicated by region classification. A
severe classificationiswhere weather conditions result in significant snowfall combined with extended periods during which there is
little or no natural thawing causing deicing salts to be used extensively.
21
Page 24
WARRANTY
KEEP THIS WARRANTY
Model (
Serial No. (
located on product or identication tag
located on product or identication tag
Date Purchased __________________
Keep receipt for warranty verication.
) _________________
) ______________
FMI PRODUCTS, LLC LIMITED WARRANTIES
New Products
FMI PRODUCTS, LLC warrants all Grand Meridian Fireplaces to be free from defects in materials that adversely affect replace
performance for a period of ten (10) years from the date of purchase, subject to the terms and conditions of this limited warranty. FMI PRODUCTS, LLC does not warrant accessory chimney, outside air ducts, gas control or burner system, ceramic logs, and devices not manufactured by FMI PRODUCTS, LLC. Valves and electronic parts are only covered for one year parts and labor per the log set manufacturer’s warranty.
This warranty covers only products manufactured by FMI PRODUCTS, LLC, specically the modular concrete rebox, and NO
WARRANTY, EXPRESS OR IMPLIED, EXTENDS TO ANY OF THE HARDWARE, FOUNDATION, VENTING, DUCTS, OR ACCESSORIES. THIS WARRANTY DOES NOT COVER DRAFTING, SMOKING, OR SOOTING OF THE FIREPLACE SYSTEM. Factors beyond the manufacturer’s control may affect drafting, smoking, and sooting, FMI PRODUCTS, LLC cannot guarantee these aspects of performance. If a component is found to be defective under the terms of this warranty, the party this warranty is extended to shall notify FMI PRODUCTS, LLC, 2701 S. Harbor Blvd. Santa Ana, CA 92704 in writing, by registered mail, within thirty (30) days following the discovery of the defect within the warranty period. The letter shall contain (1) the date of purchase; (2) place of purchase; (3) address of installation; (4) name, address and phone number of the homeowner; and (5) a brief description of the defect. FMI PRODUCTS, LLC, or any entity thereof, is not responsible for any labor costs or indirect costs incurred for the replacement of defective components. FMI PRODUCTS, LLC is not responsible for misuse or mishandling of component parts. Nothing in this warranty makes FMI PRODUCTS, LLC, or any entity thereof, liable in any respect for any injury or damage to the building or structure in which
the replace has been installed or to the persons or property therein arising out of the use, misuse, or installation of properly
manufactured FMI PRODUCTS, LLC product. FMI PRODUCTS, LLC, OR ANY ENTITY THEREOF, SHALL NOT BE HELD LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OR EXPENSES ARISING OUT OF THE USE OF THE FIREPLACE. ALL SUCH DAMAGES AND EXPENSES ARE HEREBY EXCLUDED.
This warranty is null and void when the replaces are not installed pursuant to the installation instructions provided by FMI
PRODUCTS, LLC and local building codes have not been followed completely.
This warranty applies only to those replaces installed in the continental United States, Hawaii, Alaska and Canada. If any part of
this warranty is found to be unenforceable,, the remaining parts shall remain in force and effect. FMI PRODUCTS, LLC HEREBY DISCLAIMS ALL GUARANTEES AND WARRANTIES, EXPRESS OR IMPLIED, BEYOND THE WARRANTIES SET FORTH HEREIN.
CUSTOMER SERVICE & PARTS REPLACEMENT:
Parts and accessories may be purchased from your local dealer. Additional information is available from FMI PRODUCTS, LLC.
Accessory orders will be accepted by mail, or you may call to order Monday through Friday from 8:00 a.m. to 5:00 p.m. (Central Standard Time) at: (800) 328-4537.
Please complete the following information for future reference and warranty verication:
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
125161-01 Rev. A 12/09
Loading...