tenance can cause injury
or property damage. Refer
to this manual for correct
installation and operational procedures. For assis-
tance or additional infor-
mation consult a qualied
installer, service agency
or the gas supplier.
WARNING: This appliance is for installation
only in a solid-fuel burning masonry or UL127
factory-built replace or
in a listed ventless rebox
enclosure. It is design-certied for these installations
in accordance with ANSI
Z21.11.2. Exception: Do not
install this appliance in a
factory-built replace that
includes instructions stat-
ing it has not been tested
or should not be used with
unvented gas logs.
Cleaning and Maintenance ................................ 29
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 6
of this manual.
This appliance may be in-
stalled in an aftermarket,*
permanently located,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
www.fmiproducts.com
125795-01B2
Page 3
SAFETY
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the state of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the u,
with headaches, dizziness or nausea. If you
have these signs, the replace may not be
working properly. Get fresh air at once! Have replace serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart or
lung disease or anemia, those under the inu-
ence of alcohol and those at high altitudes.
Natural and Propane/LP
odor-making agent is added to these gases.
The odor helps you detect a gas leak. How-
ever, the odor added to the gas can fade. Gas
may be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
gases are odorless. An
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Heater base assembly becomes
very hot when running heater.
Keep children and adults away
from hot surface to avoid burns
or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the room
with heater. When using the handheld remote accessory, keep selector switch in the OFF position
to prevent children from turning
on burners with remote.
You must operate this heater
with the replace screen and
hood in place. Make sure replace screen and hood are in
place before running heater.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
125795-01B3
www.fmiproducts.com
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
Page 4
SAFETY
Continued
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP units
only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. This heater shall not be installed in a
bedroom or bathroom.
5. Before installing in a solid fuel burning replace, the chimney ue and rebox must
be cleaned of soot, creosote, ashes and
loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue for damage. If damaged, repair ue
and rebox before operating heater.
6. Do not burn solid-fuel in a masonry or
UL127 factory-built replace in which a
vent-free room heater is installed.
7. If replace has glass doors, never operate
this heater with glass doors closed. If you
operate heater with doors closed, heat
buildup inside replace will cause glass to
burst. Make sure there are no obstructions
across openings of replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
page 29.
9. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ventilation to run properly. This heater has an
Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the
heater if enough fresh air is not available.
See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see
Troubleshooting, page 32.
11. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn
paper or other objects.
13. Do not use heater if any part has been exposed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part
of the control system and any gas control
which has been under water.
14. Do not operate heater if any log is broken.
Do not operate heater if a log is chipped
(dime-sized or larger).
15. Turn heater off and let cool before servic-
ing, installing or repairing. Only a qualied
service person should install, service or
repair heater.
16. Make sure the remote is set to the OFF
position when you are away from home
for long periods of time.
17. Remote heaters must not be connected
to any external electrical source.
18. Operating heater above elevations of
4,500 feet may cause pilot outage.
19. To prevent performance problems, do
not use propane/LP fuel tank of less than
100 lb. capacity (propane/LP units only).
20. Provide adequate clearances around air
openings.
www.fmiproducts.com
125795-01B4
Page 5
Chassis
Glowing
Embers
PRODUCT IDENTIFICATION
Figure 1 - Product Identication
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel
Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
125795-01B5
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
www.fmiproducts.com
data plates from the grate assembly. The data plates contain
important warranty and safety
information.
1. Remove logs and heater base assembly
Note: Do not pick up heater base assem-
2. Remove all protective packaging applied
3. Check heater for any shipping damage. If
UNPACKING
CAUTION: Do not remove the
from carton(s).
bly by burners. This could damage heater.
Always handle base assembly by grate.
to logs and heater for shipment.
heater is damaged call FMI PRODUCTS,
LLC at 1-866-328-4537 for replacement
parts before returning to dealer.
Page 6
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by
both realistic ames and glowing coals. This
heater is designed for vent-free operation
with ue damper closed. It has been tested
and approved to ANSI Z21.11.2 standard for
unvented heaters.
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This heater has an electronic ignitor to light
heater fuel supply.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of
indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable
local codes. Read the following
instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors to
keep the cold air out and the warm air in. Dur-
ing heating months, home owners want their
homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three
criteria above, proceed to Determining FreshAir Flow For Heater Location, page 7.
-11
kg per pa-sec-m2) or
www.fmiproducts.com
125795-01B6
Page 7
AIR FOR COMBUSTION AND VENTILATION
Continued
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet
per 1,000 Btu/hr (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed
in that space. Rooms communicating directly
with the space in which the appliances are
installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
replace plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vented gas heater __________ Btu/Hr
Gas replace logs __________ Btu/Hr
Other gas appliances* + _________ Btu/Hr
Total = _________ Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/HrVent-free replace + _________ Btu/Hr
Total = _________ Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
______Btu/Hr (maximum the space can
support)
______Btu/Hr (actual amount used)
Example: 51,200 Btu/Hr (maximum the
space can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a conned
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your
options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides
an unconned space, remove door to adjoining room or add ventilation grills between
rooms. See Ventilation Air From Inside Building, page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
40,000
33,000
73,000
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
Page 8
AIR FOR COMBUSTION AND VENTILATION
Outlet
Air
Ventilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
Figure 2 - Ventilation Air from Inside Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering
the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualied service person must install heater.
Follow all local codes.
www.fmiproducts.com
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of replace. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney ue damper.
125795-01B8
Page 9
INSTALLATION
Continued
WARNING: Before installing
in a solid fuel burning replace,
the chimney ue and rebox
must be cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner.
Creosote will ignite if highly
heated. A dirty chimney ue may
CHECK GAS TYPE
Use the correct type of gas (natural or propane/
LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rating plate. Field conversion is not
permitted.
create and distribute soot within
the house. Inspect chimney and
rebox ue for damage. If dam-
INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
aged, repair ue and rebox
before operating heater.
WARNING: Maintain the
minimum clearances. If you can,
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
•
where curtains, furniture, cloth-
ing or other ammable objects
are less than 36" from front, 42"
from top of heater; for side clearances see Figure 4, page 10
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next
to heater. Installing heater next
to vinyl or cloth wall coverings or
operating heater where impurities
(such as, but not limited to, tobacco smoke, aromatic candles,
cleaning uids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See Air for Combustion and Ventila-
tion, page 6.
125795-01B9
www.fmiproducts.com
provide greater clearances from
oor, ceiling and adjoining wall.
will ensure safe installation into a masonry,
UL127-listed manufactured replace or listed
vent-free rebox.
Minimum Clearances For Side Combustible
Material, Side Wall and Ceiling
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4,
page 10.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material
and protrudes 3 1/2" from the wall. This
combustible material must be 4" from the
side of the replace cabinet (see Figure
4, page 10).
Minimum Firebox Size
Height Depth
Front
Width
Rear*
Width
Page 10
INSTALLATION
Heat Resistant
Material
(A)
Continued
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less
than 42".
Noncombustible
Material Distance
Requirements for
Safe Installation
(A)
1
2" or moreNoncombustible mate-
rial OK.
Between 8" and 12"
Install replace hood
accessory (GA6050 or
GA6053 see Accesso-ries, page 39).
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using
Mantel. If not using a mantel, follow these
instructions.
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind
it. Noncombustible material must extend at
least 8" up (for all models). If noncombustible
material is less than 12", you must install the
replace hood accessory (24" and 30" Models
Only). See Figure 5 for minimum clearances.
Less than 8"
Noncombustible material must be extended
to at least 8". See
Between 8" and 12",
above. If you cannot
extend material, you
must operate heater
with ue damper open.
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material behind it. Noncombustible material must extend
at least 8" up (for all models). If noncom-
bustible material is less than 12", you must
install the replace hood accessory. Even if
noncombustible material is more than 12",
you may need the hood accessory to deect
heat away from your mantel shelf. See Figure
5 and Figures 6 and 7, page 11, for minimum
clearances.
www.fmiproducts.com
125795-01B10
Page 11
INSTALLATION
14"
Min.
Combustible
Material
Noncombustible Material
Minimum NonCombustible
Material
Minimum NonCombustible
Material Height
Distances to
Underside of
Mantel
Top of Fireplace
Opening
Underside of
Mantel Shelf
12"
(A)
18" 20" 22" 24"
All minimum
distances are
in inches
2
1
/2
"
6"
8"
10"
Mantel Shelf
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18" 20"
2
1
/2
"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood (GA6050
or GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
Hearth
5"
Min.
Combustible
Material
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, are not
met, you must have a hood. When using a
hood there are still certain minimum mantel
clearances required. Follow minimum clear-
ances shown in Figure 7, when using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the replace, you must install appliance
at least 5" above the combustible ooring
(see Figure 9).
Figure 8 - Minimum Fireplace Clearances
Figure 7 - Minimum Mantel Clearances
125795-01B11
When Using Hood
www.fmiproducts.com
Figure 9 - Minimum Fireplace Clearances
If Installed at Floor Level
Above Combustible Flooring
Page 12
INSTALLATION
INSTALLING HEATER BASE
ASSEMBLY
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak.
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access to
heater control panel. This will insure adequate air ow and guard
against sooting and controls
being damaged. Raise replace
oor with noncombustible material. Make sure material is secure.
Continued
3. Mark screw locations through holes in
front panel of base (see Figure 11). If
installing in a brick-bottom replace, mark
screw locations in mortar joint of bricks.
4. Remove heater base from replace.
5. Drill holes at marked locations using 3/16"
drill bit.
6. Attach base, through holes in back side panels of base, to replace oor using masonry
screws provided in hardware package (see
Figure 11).
7. Connect to gas supply. See Connecting
To Gas Supply, page 13.
Heater Gas
Regulator
Flexible Gas Hose (Provided
with Models, Install if
allowed by local codes)
CAUTION: Do not pick up
heater base assembly by burners. This could damage heater.
Only handle base assembly by
grates.
IMPORTANT: Make sure the heater burners
are level.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings
provided (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
Note: Install optional MRC Series receiver
and hand-held remote control kit (see Accessories, page 39) before installing gas log
heater. See installation instructions included
with the kit.
1. Apply pipe joint sealant lightly to male
threads of the 3/8 NPT side of gas tting
elbow (provided) and connect to inlet
side of gas control. Remove gas tting
from exible gas hose (provided) before
connecting to elbow (see Figure 10).
2. Position heater base assembly in replace.
www.fmiproducts.com
Figure 10 - Attaching Flexible Gas Hose
to Heater Gas Regulator
Masonry Screw
Figure 11 - Attaching Base to Fireplace
Floor
125795-01B12
Page 13
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 3/8" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
WARNING: A qualied service
person must connect heater to
gas supply. Follow all local codes.
CAUTION: Never connect
propane/LP replace directly
to the propane/LP supply. This
heater requires an external regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
WARNING: Never connect
natural gas replace to private
(non-utility) gas wells. This
gas is commonly known as
wellhead gas.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connec-
tor (if allowed by local codes) (not provided)
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the optional equipment
shutoff valve from your dealer.
For propane/LP units, the installer must
supply an external regulator. The external
regulator will reduce incoming gas pressure.
You must reduce incoming gas pressure to
between 11" and 14" of water. If you do not re-
duce incoming gas pressure, heater regulator
damage could occur. Install external regulator
125795-01B13
www.fmiproducts.com
with the vent pointing down as shown in Figure
12, page 14. Pointing the vent down protects
it from freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing
may be used in certain areas.
Check your local codes. Use
pipe of 1/2" diameter or greater
to allow proper gas volume to
heater. If pipe is too small, undue
loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 13, page 14).
IMPORTANT: Install equipment shutoff valve
in an accessible location. The equipment
shutoff valve is for turning on or shutting off
the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
Propane/LP
Supply Tank
Figure 12 - External Regulator With Vent
Pointing Down
External
Regulator
with Vent
Pointing
Down
Page 14
INSTALLATION
Continued
PROPANE/LP From
External Regulator
(11" W.C.** to 14" W.C.
Pressure)
NATURAL From Gas
Meter (5" W.C.**
to 10.5" W.C.
Pressure)
Tee Cap Pipe
Joint Nipple
Sediment Trap
Figure 13 - Gas Connection
* Purchase the optional equipment shutoff
valve from your dealer.
**Minimum inlet pressure for purpose of input
adjustment.
We recommend that you install a sediment
trap in supply line as shown in Figure 13.
Locate sediment trap where it is within reach
for cleaning. Install in piping system between
fuel supply and heater. Locate sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contaminants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
CAUTION: Avoid damage to
gas control. Hold gas control
with wrench when connecting
it to gas piping and/or ttings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
Equipment Shutoff
Valve With 1/8"
NPT Tap*
Approved
Flexible Gas
Hose (if allowed
by local codes)
3" Minimum
Gas
Regulator
www.fmiproducts.com
WARNING: Never use an open
ame to check for a leak. Apply a
noncorrosive leak detection uid
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply and
heater. See guidelines under Con-necting to Gas Supply, page 13.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equipment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection uid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
ttings for leaks.
Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 15).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
3. Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP supply to equipment shutoff valve
for propane/LP (see Figure 15 or Figure
16). Apply noncorrosive leak detection uid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
125795-01B14
Page 15
INSTALLATION
Continued
PRESSURE TESTING HEATER GAS
CONNECTIONS
1.
Open equipment shutoff valve (see Figure 14).
2. Open main gas valve located on or near
gas meter for natural gas or open propane/LP supply tank valve.
3. Make sure control knob of heater is in the
OFF position.
4. Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP supply to equipment shutoff valve
for propane/LP (see Figure 15, or Figure
16). Apply noncorrosive leak detection uid
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operation, page 23).
Check all other internal joints for leaks.
7.
Turn off heater (see To Turn Off Gas to
Appliance, page 23 for Remote models.
Equipment
Shutoff
Valve
Figure 14 - Equipment Shutoff Valve
Propane/LP
Supply Tank
Figure 15 - Checking Gas Joints
(Propane/LP Only)
Equipment
Shutoff Valve
Gas Meter
Figure 16 - Checking Gas Joints (Natural
125795-01B15
Equipment Shutoff Valve
Gas Only)
Open
Closed
Control Valve
Location
Control Valve
Location
www.fmiproducts.com
POWER SUPPLY AND BATTERY
INSTALLATION
It is helpful to have a ashlight so you can
see the connections as described below. Locate the battery power supply. It is the black
box with the red and black wires. Locate the
control module (see Figure 17). Connect the
battery power supply to the control module
by plugging the battery power supply to the
mating receptacle on the control module. The
receptacle is located on the side of the black
control module next to the word “SUPPLY”
which is molded in the control module’s black
housing (see Figure 17). Be certain to push
the plug fully into the receptacle. Install batteries in the battery power supply and hand
held remote control.
S1 Button
Connect Battery Plug Here
Figure 17 - Control Module
TOUCH PAD INSTALLATION
Locate the touch pad wire harness and the
touch pad control (see Figure 18, page 16).
They are shipped from the factory in the clear
plastic bag with your owner’s manual. Connect the black plastic connectors together as
shown in Figure 19, page 16. Connect the
remaining end with the white plastic connector
to the control module in the socket marked
TOUCH LED (see Figure 20, page 16).
NOTE: The touch pad includes a red LED
display light. If the LED remains on, the black
plug is connected upside down. You must
unplug the touch pad control from the touch
pad wire harness, turn over, and reconnect.
Page 16
INSTALLATION
Configuration
Select
Back
Off
No
Yes
0.5°C
Thermostat
Programming
Gap Temp
Fri 22:04
Pairing
Configuration
Change
Back
Yes
Yes
0.5°C
Thermostat
Programming
Gap Temp
Fri 21:47
Off
Pairing
Continued
Touch Pad Wire Harness
Touch Pad Control
Figure 18 - Touch Pad Wire Harness and
Touch Pad Control
Figure 19 - Touch Pad Control Cable
proceeding, locate the yellow/orange S1
button on the control module. You will need
to access this button during the re-pairing
procedure and only have 20 seconds to press
and release it. A small nail or ink pen will also
be useful to press this button (see Figure 17,
page 15).
Press and hold the “Off” button on the
remote control for 40 seconds. During this
time, the screen will go blank, this is normal.
See Figure 21.
Fri 20:45
OFF
u
°F
75
Lock MenuOn
OFF
Button
Figure 21 - Main Screen
After 40 seconds, the conguration menu
appears (see Figure 22). With ''Pairing'' highlighted press the middle ''select'' button. ''Off''
becomes highlighted (see Figures 22 and 23).
Figure 20 - Connecting end of Touch Pad
Cable
RE-PAIRING
IMPORTANT! This appliance is shipped
with the remote control and control module
(receiver) paired. However, if more than one
Copreci brand electronic ignition system is
to be used within a home or showroom, all
but one appliance must have the remote
control and control module re-paired in order
for each appliance to operate on a unique
frequency. For multiple appliances, on all but
one follow the instructions under Re-Pairing
on page 16 before moving to Installing Logs
on page 18. For single appliance installations,
skip the RE-PARING section and proceed to
Installing Logs.
It is helpful to have a ashlight so you can see
the connections as described below. Before
www.fmiproducts.com
Fri 22:04
Configuration
Pairing
Thermostat
Gap Temp
Programming
Select
Off
Yes
0.5°C
No
Back
SELECT
Button
Figure 22 - Conguration Menu
125795-01B16
Page 17
INSTALLATION
Configuration
Select
Back
Off
No
Yes
0.5°C
Thermostat
Programming
Gap Temp
Fri 22:05
Pairing
Continued
Fri 21:47
Configuration
Pairing
Thermostat
Gap Temp
Programming
Change
Figure 23 - Off Highlighted
IMPORTANT! Be prepared to press the S1
button as noted in the beginning of this sec-
tion. After the next step, you have only 20
seconds to push (press and release) the S1
button (yellow/orange) in the control module
(see Figure 17, page 15).
NOTE: The control module may be turned dif-
ferently than shown in this gure. Look for the
matching text on the control module to help
locate the small yellow / orange S1.
Fri 22:04
Pairing
Thermostat
Change
Button
Gap Temp
Programming
Change
Off
Yes
0.5°C
Yes
Back
Configuration
0.5°C
On
Yes
No
Back
see signal bars within 30 seconds of hearing
the beep, then the repairing process was not
completed successfully. If this occurs, remove
the batteries from the remote control, wait 3
minutes, and restart the re-pairing process. If
you see signal bars, then the remote control
has paired properly. Go to the next step.
Fri 22:05
Configuration
Pairing
Thermostat
Gap Temp
Programming
Change
Off
Yes
0.5°C
No
Back
Figure 25 - Signal Bars
Press the “Back” button once to return the
highlighted selection to “Pairing”. Press the
“Middle” button and release. The indication on
the “Pairing” will become “Off” (see Figure 26).
The re-pairing is over. To return to the main
screen, press the “Back” button until you get
to the main screen. The main screen is shown
in Figure 21, page 16.
Fri 22:05
Configuration
Figure 24 - Change OFF to ON
Press the left "Change" button and "Off" becomes
"On" (see Figure 24, above). Press the S1 button to re-pair the remote to the control module.
Once this operation is done, you will hear one
Middle
Button
Pairing
Thermostat
Gap Temp
Programming
Select
Off
Yes
0.5°C
No
Back
Back
Button
beep in the control module and the conguration menu will show signal bars: (see
Figure 25). If you do not hear the beep and then
125795-01B17
www.fmiproducts.com
Figure 26 - Back and Middle Buttons
Page 18
INSTALLATION
Continued
MF SERIES BURNER SYSTEM-LOG
COMPATIBILITY CHART
Burner System Model
MF42INE,MF42IPE,LMF36-SC
MF48INE, MF48IPE,
Figure 27 - MF Series Burner System-
Log Compatibility Chart
INSTALLING LOGS, EMBERS AND
LAVA ROCK
Refractory Concrete
Logs For Use With This
Burner System
LMF42-SC
LMF48-SC
1. Find the right front log (LMF36-SC and
VFGT24 inch models: D-061 or LMF42SC and VFGT30 inch models: D-019 or
LMF48-SC and VFGT36 inch models:
D-027). See Figures 28, 28A, 28B, and
28C for reference. The log has a rectan-
gular shape on the bottom that ts against
the lip on the black metal base, the square
grate, and the round tube burner. Slide the
log in place as shown in Figures.
Right Front Log
Burner
Tube
(D061, D-019 or D027)
WARNING: Failure to position
the parts in accordance with these
diagrams or failure to use only
parts specically approved with
this heater may result in property
damage or personal injury.
CAUTION: After installa-
tion and periodically thereafter,
check to ensure that no ame
comes in contact with any log.
With heater set to Hi, check to
see if ames contact any log. If
so, reposition logs according to
log installation instructions in
this manual. Flames contacting
logs will create soot.
LOG PLACEMENT
It is very important to install these logs exactly
as instructed. Do not modify logs. Only use
logs supplied with heater or for MF models,
as identied for use with the heater as shown
in Figure 27.
Note: Each log includes an identifying number
cast in the log. Look at each log when placing them on the burner system to be certain
it is correct.
Note: For additional information, go to
www.fmiproducts.com and click on the
technical Support tab for access to log
placement videos.
www.fmiproducts.com
Grate Finger
Figure 28 - Installing Right Front Log
Round Tube
Burner
Grate Finger
Figure 28A - Installing Right Front Log,
Burner Tube
Figure 28B - Installing Right Front Log,
Top View
Square Grate
Top View
125795-01B18
Page 19
INSTALLATION
Continued
Figure 28C - Installing Right Front Log,
Side View
2. Find the back left log (LMF36-SC and
VFGT24 inch models: D-060 or LMF42SC and VFGT30 inch models: D-018 or
LMF48-SC and VFGT36 inch models:
D-026). See Figures 29, 29A, and 29B.
Figure 29A shows how the log must t
against the end of the burner. Figure 29B
shows how the notch in log ts against the
vertical portion of the burner tube. Place
this log on the base assembly by inserting
it from the left side as shown in Figure 19.
You will need to twist the log slightly to get
it to t against the burners properly. It will
rest even with the back edge of the pan.
Back Left Log (D-060,
D-018 or D026)
Log Notch
Flat Part of Log
Burner Tube
Figure 29 - Installing Back Left Log
Vertical Portion of Burner Tube
Figure 29B - Installing Back Left Log
(D-018) Rear View
3. Find the front left log (LMF36-SC and
VFGT24 inch models: D-059 or LMF42SC and VTGF30 inch models: D-017 or
LMF48-SC and VFGT36 inch models:
D-025). See Figures 30, 30A, and 30B.
The log has a rectangular stand off on
the bottom that ts against the lip on the
black metal base as shown in gure 30A.
The bottom of this log has a slot that ts
over the second bar on the grate as shown
in Figure 30B, page 20. Place the log on
the base assembly as shown in gures.
Front Left Log (D-059,
D-017 or D025)
Grate Fingers
Figure 30 - Installing Front Left Log
Log
Notch
Burner
Tube
Figure 30A - Installing Front Left Log
Figure 29A - Installing Back Left Log
125795-01B19
www.fmiproducts.com
Side View
Page 20
INSTALLATION
Continued
Square Grate
Log Notch
Grate Finger
Log Slot
Figure 30B - Installing Front Left Log
4. Find the charred log (D-020). See Figures
31, 31A, and 31B. The log has a slot in the
bottom that ts over the square grate and
rests against the burner tube as shown in
Figure 31. Place this log on the base as
shown in gures.
Charred
Log
Log Notch
Right Front Log
Figure 31 - Installing Charred Log
Figure 31B - Installing Charred Log Top
Side View
5. Find the middle split log (LMF36-SC and
VFGT24 inch models: D-063 or LMF42SC and VFGT30 inch models: D-021 or
LMF48-SC and VTGF36 inch models:
D-028). See Figures 32 and 32A. The split
side of the log faces forward. The log has
a notch that ts around the burner tube on
the right side. The left side of the burner
tube ts into the notch on the back side of
this log. The log is placed properly when
it sits parallel to the tube burner and the
square peg is pointing up. See gures
for reference.
Square Peg
Middle Split Log (D-063,
D-021 or D028)
Figure 32 - Installing Middle Split Log
(D-021)
Burner Tube
Log Notch
Figure 31A - Installing Charred Log Top
View
www.fmiproducts.com
Figure 32A - Installing Middle Split Log
Rear Top Side View
125795-01B20
Page 21
INSTALLATION
Continued
6. Find the right split crossover log (D-022)
The bottom of the log has a rectangular
stand off that ts in the slots on the right
side of the front right log and the middle
split log. Place this log as shown in Figure 33.
Square Peg
Right Split Crossover Log (D-022)
Back Top Log (D-062,
D-023 or D029)
Right Split Crossover Log (D-022)
Right Front Log
Figure 33 - Installing Right Split
Crossover Log
7. Find the front top log (D-024). See Figure
34. The left end of this log has a square hole
that ts over a square peg that is on the top
of the middle split log. The right end of this
log rests behind the knot on the top of the
front right log.
Front Top Log (D-024)
Middle Split Log
Right Split Crossover Log (D-022)
Rectangular
Peg
Figure 34 - Installing Front Top Log
8. Find the back top log (LMF36-SC and
VFGT24 inch models: D-062 or LMF42-SC
and VFGT30 inch models: D-023 or LMF48SC and VTGF36 inch models: D-029). See
Figures 35, and 35 A. The left end of this
log has a round hole that ts over the round
peg that is on the top of the back left log. The
right end of this log has a rectangular hole
that ts over the rectangular peg on the top
of the right crossover log.
Figure 35 - Installing Back Top Log and
Final Assembly
Figure 35A - Installing Back Top Log,
Top View
125795-01B21
www.fmiproducts.com
Page 22
INSTALLATION
Continued
EMBER PLACEMENT
Two ember materials are supplied with this
log set. Platinum Bright Embers give a bright
glow appearing as hot coals. Should embers
need replacing, see Accessories, page 39.
• Platinum Bright Ember placement.
Add embers to front, at burner. Gently
remove embers from bag. Separate
pieces of ember material and place on
surface of at burner just behind horizontal ports as shown in Figure 36.
WARNING: Do not use any
other ember material not supplied with this unit.
WARNING: Do not operate unit
without ember material correctly
in place as shown in Figures 36
& 37. Do NOT place ember material anywhere else on the unit.
Use only ember material supplied
with unit. Excessive or incorrectly
placed ember material may produce carbon monoxide or soot.
LAVA ROCK PLACEMENT
• Rock Wool placement. Place rock wool
material on front at burner in areas away
from ports as shown in Figure 37.
• Add lava rock; Lava rock may cover 1/2
inch of the front burner(at metal ember
pan burner) but shall not be allowed to
come in contact with either the burner
ports or ame around base of heater if desired. DO NOT place rock or additional
logs on front burner or on logs except
as directed above. Placing any material
on unit other than ember material on front
burner may result in production of carbon
monoxide or soot. A switch log is included
with each log set. This log is designed to
house a switch on remote ready models.
On variable remote models, this switch is
not needed. The log can be placed on the
oor of the replace to enhance the look
of the log set. Use lava rock to hide wires
from switch/log to control valve. Place
switch/log so the switch is easy to access.
Ember Material
Figure 36 - Platinum Bright Embers
Rock Wool
Figure 37 - Placement of Rock Wool (shown with Platinum Bright Embers)
www.fmiproducts.com
Flat Front Burner
125795-01B22
Page 23
OPERATION
NOTICE: During initial operation
of new heater, burning logs will
give off a paper-burning smell.
Orange ame will also be present. Open damper or window to
vent smell. This will only last a
few hours.
WARNING:
• If replace has glass doors,
never operate this heater with
glass doors closed. If you op-
erate heater with doors closed,
heat buildup inside replace
will cause glass to burst. Make
sure there are no obstructions
across openings of replace.
• You must operate this heater
with a replace screen in place.
Make sure replace screen is
closed before running heater.
WARNING: Damper handle
will be hot if heater has been
running.
CAUTION: Do not try to ad-
just heating levels by using the
equipment shutoff valve.
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly,
a re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot that is
equipped with an ignition device which
automatically lights the pilot. Do not
light the pilot by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the oor because some
gas is heavier than air and will settle
on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the re department.
C. Do not use this appliance if any part
has been under water. Immediately call
a qualied service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
LIGHTING
INSTRUCTIONS
1. STOP! Read the safety information.
2. Make sure equipment shutoff valve is
fully open.
3. Press any button on the remote to power
the remote on. If you see a Lock icon and
the word ''Unlock'' in the lower left corner
of the screen you will need to unlock the
screen by pressing ''Unlock'' and ''OK''.
4. Press ''On'' and ''OK''. It may take up to 4
seconds before the control unit processes
the command. You will hear a beep from
the control unit and the pilot will start to
spark before lighting.
Note: You may be running this heater for the
rst time after hooking up to gas supply.
If so, you may have to restart the unit
several of times to allow the air to bleed
from the system.
TO TURN OFF GAS
TO APPLIANCE
1. Press OFF (bottom button) on the remote
control.
2. Close equipment shutoff valve.
125795-01B23
www.fmiproducts.com
Page 24
OPERATION
gO
REMOTE CONTROL OPERATION
The remote control contains:
1. LCD display
2. Four buttons:
OFF button
Left button
Middle button
Right button
3. Battery Case (on the Back)
LCD Screen
Middle
Button
Left Button
Batteries
(Back Side)
Right
Button
OFF Button
Continued
Figure 39 - LCD Display
The screen changes depending on the input
from the buttons, but the bottom row always
displays the button function labels (see Figure
40). The functions of each button depends on
the options available on the current screen
(except for the OFF button which has always
the same function).
Note: The bottom row of the screen is
indicating buttons functionality. In this case:
• LEFT ( ) button decreases the ame level
• MIDDLE ( ) button increases the ame level
• RIGHT (Back) button goes back to the
previous screen (see Figure 40).
Figure 38 - Remote Control
LCD DISPLAY
The LCD screen shows information about the
instructions given by the user (desired status)
and the current situation of the device (actual
status). It also helps us select our choices,
see Figure 39.
• A: Day of the week
• B: Time
• C: Signal Strength
• D: Selected working mode
• E: Selected setting
• F: Current Flame status
• G: Current fan status
• H: Current room temperature
• I: Child lock status
• J: Button labels (explained below)
www.fmiproducts.com
Mon 00-02
Configuration
Left
Button
Pairin
Thermostatic
Gap Temp
Programming
0.5°C
BackSelect
ff
Off
Yes
Bottom Row
Middle
Button
Right
Button
Figure 40 - Screen Changes
OFF BUTTON
This button switches off the appliance. If it is
pressed and held for more than 40 seconds,
the conguration menu is accessed.
LEFT, MIDDLE AND RIGHT BUTTON
These buttons change their function as shown
by the on-screen labels. For some screens a
button may have no function and is inactive.
The active buttons for a particular screen are
initially lit for 5 seconds to indicate that they
are active.
125795-01B24
Page 25
OPERATION
Continued
MENU SYSTEM
The remote is organized by means of a menu
system.
After batteries are installed the rst time, the
remote starts at the ''OFF'' screen ( it is possible that the remote is locked in the ''OFF''
screen: to unlock it just press the button below
''Unlock'', and then ''OK''. See Figure 41).
Available
after
PROGRAM
MODE is
enabled, see
And then
Figure 42 - Adjusting Menu
SETTING THE CONTROL MODE
Figure 41 - Menu System
SWITCHING ON
IMPORTANT: When lighting the pilot and
burner for the rst time, air will be present in
the system that must be purged.
The lighting sequence may have to be re-
peated 10 to 15 times before gas reaches the
pilot. This is normal.
To turn the system on, press “On” (left button) and “OK” (middle button). A beep from
the control module will be heard and the
ignition process will start. This will take up
to 20 seconds. Note that while in operation
the signal bars will disappear for a few mo-
ments. If the pilot and burner do not light,
press the “Off” button, wait 15 seconds then
repeat the ignition steps from the beginning
of this paragraph. Note: each ignition step is
accompanied by two short series of ignition
sparks at the pilot.
ADJUST MENU
Before using the remote, there are various
settings which should be made, such as the
date, the language, the autolock option and
the comfort temperature.
For doing this, press ''Menu'' and then press
''Select'' to chose ''Adjust Menu''. There the
options shown in Figure 42, can be set. To
change any of these settings use the down
arrow to select the feature and then press
"Select" and "Change" to change the setting.
125795-01B25
www.fmiproducts.com
There are three different modes for controlling
the appliance:
Manual
Auto
Program
In Manual mode the main burner can be
switched on and off.
Auto mode allows you to set a temperature,
while in Manual mode the ame level may
be set to HIGH, MEDIUM, or LOW. Program
mode offers automatic temperature control for
specic times of the day.
In the initial screen when the remote is
turned on, three options are available: AUTO,
MANUAL and MENU.
Auto and Manual are two of the three differ-
ent modes for controlling the appliance with
the remote.
MANUAL MODE
If ''Manual'' is pressed, the ame setting appears as the selected setting. In the bottom
row, and appear, indicating that the ame
level can be changed by pressing the left or
middle button. Pressing ''Back'' (right button)
returns to the initial screen (see Figure 40,
page 24).
Note that a safety temperature can be set
in the configuration menu. This specifies
the maximum the maximum permitted room
temperature. This temperature can never be
set higher than 40ºC (104ºF).
PROGRAM
MODE
section on
next page.
Page 26
OPERATION
Configuration
ChangeBack
Off
Yes
0.5°C
ThermostatGap Temp
Fri 23:33
Pairing
ProgrammingNo
Fri 21:40
LockMenuOn
OFF
°F
71
u
Continued
AUTO MODE
If ''Auto'' is pressed in the initial screen, 25ºC
(77ºF) appears as the desired temperature in
the selected setting. In the bottom row, and
appear, indicating that we can change the
desired temperature value by just pressing the
left or middle button. In auto mode the appliance heats until this temperature is reached.
Pressing ''Back'' (right button), returns to the
initial screen.
The Auto mode feature is optional and can
be enabled or disabled in the conguration
menu by changing ''Thermostat'' to either
''Yes'' (enabled) or to ''No'' (disabled). Access
to the conguration menu is described in the
next section.
PROGRAMMING
PROGRAM MODE
A program mode is available if desired. This
mode allows the remote control to operate
the gas log set in either weekly or daily settings. To enable the program mode access
the conguration menu.
CONFIGURATION MENU ACCESS: Press
and hold the “OFF” button on the remote
control for 40 seconds. During this time, the
screen will go blank for a few seconds, this is
normal. See Figure 43. After 40 seconds, the
conguration menu appears (see Figure 44).
Fri 23:27
Configuration
Pairing
Thermostat
Arrow
Button
Gap Temp
Programming
Select
Figure 44 - Programming
Fri 23:33
Configuration
Pairing
Thermostat
Gap Temp
Programming No
ChangeBack
Off
Yes
0.5°C
No
Back
0.5°C
Off
Yes
SELECT
Button
Fri 20:45
OFF
u
°F
75
Lock MenuOn
Figure 43 - OFF Button
Press the arrow button ( ) until Programming
is highlighted (see Figure 70). If Programming
has ''No'' next to it, press the ''Select'' button
Fri 22:04
Configuration
Pairing
Thermostat
Gap Temp
Programming
OFF Button
Select
Off
Yes
0.5°C
No
Back
to highlight ''No'' (see Figures 44 and 45).
www.fmiproducts.com
Figure 45 - Highlighting ''No''
Press ''Change'' (left button) to change Programming from ''No'' to ''Yes'' (see Figure 72).
To return to the main screen, press the''Back''
button until you get to the main screen. The
main screen is shown in Figure 47, page 27.
The PROGRAM MODE is now enabled.
Fri 23:33
Configuration
Change
Button
Pairing
Thermostat
Gap Temp
Programming
ChangeBack
Off
Yes
0.5°C
Yes
Figure 46- Changing ''No'' to ''Yes''
125795-01B26
Page 27
OPERATION
Continued
Fri 21:40
OFF
u
°F
71
Lock MenuOn
Figure 47 - Main screen
There are two types of program mode: a daily
mode and a weekly mode. In the daily mode,
every day uses the same program. In the
weekly mode, every day has its own program,
so it is possible have a different program for
each day of the week (see Figure 48).
press ( ) (left button). To change the desired
temperature, go to the hour you want to
change by pressing (left button) and then
press change (middle button). There are 3
temperature settings:
Off:
No temperature control (the appliance
is in pilot mode).
'Night Temp:
as desired temperature and the appliance will
heat until this temperature is reached.
'Comfort Temp:
is set as the desired temperature and the
appliance will heat until this temperature is
reached.
Finally, to launch the program mode, in the
main menu, set Program to ''On'', and select
the desired Program Type (Daily or Weekly)
as shown in Figure 49.
The night temperature is set
The comfort temperature
Figure 49 - Day Programming Menu
Figure 48 - Setting Control Mode
DAY PROGRAMMING MENU (Menu
Adjust Menu Change Program):
There are 8 menus like this. One for daily, and
the others for each day (Monday, Tuesday,
Wednesday, Thursday, Friday, Saturday and
Sunday, see Figure 49). This day program-
ming screen consists of:
Title: Daily Program.
A:Selected (including ''Daily''). The select-
ed day can be changed by pressing ''Change''
(middle button).
B: Day Schedule Graphic. This bar displays
the program for the whole day by showing
the temperature setting for each hour of the
day. To access the day schedule graphic,
125795-01B27
www.fmiproducts.com
OTHER FEATURES
How to lock and unlock the remote (child
lock)
To unlock the remote, press the ''Unlock''
button and ''OK''.
To lock the remote, in the main screen press
''Menu'' go to the Lock option, press ''Select''
and then ''Change''. The remote will immediately go into locked mode.
Automatic lock can be selected. This means
that if no button is pressed for while, the
remote automatically goes into locked mode.
How to select the temperature unit (ºC/ºF)
In the main screen, press ''Menu'' button. Select ''Adjust Menu'' and then select ''Unit''. To
change the temperature unit press ''Change''
button.
Page 28
OPERATION
Continued
TOUCH PAD OPERATION
This touch control has only 3 buttons for con-
trolling manually the ame of the appliance
(see Figure 50).
The touch pad has:
1. Led display
2. ON/OFF button
3. UP button
4. DOWN button
With this control it is possible to turn on the
re, turn off the re and control the ame level.
LED Display
ON/OFF Button
ON
OFF
UP Button
DOWN Button
Figure 50 - Touch Pad Control
SWITCHING OFF
To switch off the re, the ON/OFF button
should be pressed. After the system has emit-
ted a beep, the re switches off.
WARNING: Do not convert
heater to use different fuel type.
Only use heater with fuel type
specied.
Note: The touch pad includes a red LED
display light. If the LED remains on, the black
plug is connected upside down. Unplug, turn
over, and reconnect.
SWITCHING ON
To turn the system on just press the ON/OFF
button. The system will emit a beep and begin
the ignition process, which can take about
20 seconds. Once the start up process is
complete, the pilot ame is lit.
REGULATING THE FLAME LEVEL.
1. To increase the ame level, press the
up button ( ). A beep and a ash of
the LED indicate that the system has
accepted the order, and the ame will
increase instantly (see Figure 50).
2. To decrease the ame level, press the
down button ( ). A beep and a ash of
the LED indicate that the system has
accepted the order, and the ame will
decrease instantly (see Figure 50).
www.fmiproducts.com
125795-01B28
Page 29
INSPECTING BURNERS
Thermocouple
Figure 51 - Pilot (Natural)
Check pilot ame pattern and burner ame
patterns often.
PILOT FLAME PATTERN
Figure 52 shows a correct pilot ame pattern.
Figure 53 shows an incorrect pilot ame pattern. The incorrect pilot ame is not touching
the thermocouple. This will cause the thermo-
couple to cool. When the thermocouple cools,
the heater will shut down.
If pilot ame pattern is incorrect, as shown
in Figure 53.
• turn heater off (see To Turn Off Gas to Appliance, page 23
• see Troubleshooting, page 32
Note: The pilot ame on natural gas units will
have a slight curve, but ame should be blue
and have no yellow or orange color.
Thermocouple
Figure 52 - Correct Pilot Flame Pattern
(Your pilot may vary from pilots shown)
Thermocouple
Figure 53 - Incorrect Pilot Flame Pattern
(Your pilot may vary from pilots shown)
Ignitor Electrode
Pilot Burner
Pilot Burner
Pilot Burner
CLEANING AND
MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
CAUTION: You must keep
control areas, burners and
circulating air passageways of
heater clean. Inspect these areas
of heater before each use. Have
heater inspected yearly by a qualied service person. Heater may
need more frequent cleaning due
to excessive lint from carpeting,
pet hair, bedding material, etc.
WARNING: Failure to keep
the primary air opening(s) of
the burner(s) clean may result
in sooting and property damage.
BURNER INJECTOR HOLDER AND
PILOT AIR INLET HOLE
The primary air inlet holes allow the proper
amount of air to mix with the gas. This provides
a clean burning ame. Keep these holes clear
of dust, dirt, lint and pet hair. Clean these air in-
let holes prior to each heating season. Blocked
air holes will create soot. We recommend that
you clean the unit every three months during
operation and have heater inspected yearly by
a qualied service person.
We also recommend that you keep the burner
tube and pilot assembly clean and free of dust
and dirt. To clean these parts we recommend
using compressed air no greater than 30 PSI.
Your local computer store, hardware store or
home center may carry compressed air in a
can. If using compressed air in a can, please
follow the directions on the can. If you don’t
follow directions on the can, you could damage the pilot assembly.
1. Shut off unit, including pilot. Allow unit to
cool for at least thirty minutes.
2. Inspect burner, pilot and primary air inlet
holes on injector holder for dust and dirt
(see Figure 54, page 30).
3. Blow air through the ports/slots and holes
in the burner.
125795-01B29
www.fmiproducts.com
Page 30
CLEANING AND MAINTENANCE
Continued
4. Check injector holder located at end of
burner tube again. Remove any large
particles of dust, dirt, lint or pet hair with
a soft cloth or vacuum cleaner nozzle.
5. Blow air into the primary air holes on the
injector holder.
6. In case any large clumps of dust have now
been pushed into the burner repeat steps
3 and 4.
Clean pilot assembly also. Additional cleaning may be needed for proper pilot operation
based on use/lack of use. A yellow tip on the
pilot ame may indicate dust and dirt in the
pilot assembly. There is a small pilot air inlet
hole about from where the pilot ame comes
out of pilot assembly (see Figure 55). With
unit off, lightly blow air through air inlet hole.
You may blow through a drinking straw if
compressed air is not available.
Injector
Holder
LOGS
• If you remove logs for cleaning, refer to
Installing Logs Embers and Lava Rock,
page 18, to properly replace logs.
• Replace log(s) if broken or chipped (dimesized or larger).
MAIN BURNER
Periodically inspect all burner ame holes with
heater running. All slotted burner flame holes
should be open with ame present. All round burner
ame holes should be open with a small blue ame
present. Some burner ame holes may become
blocked by debris or rust, with no ame present. If
so, turn off heater and let cool. Remove blockage,
blocked burner ame holes will create soot.
WARNING: The injector holders (air shutters) are not adjustable. Do not move injector holders
from their original positions.
Burner Tube
Primary Air
Inlet Holes
Figure 54 - Injector Holder On Outlet
Burner Tube
Pilot Air
Inlet Hole
Pilot Assembly
Figure 55 - Pilot Inlet Air Hole (Your pilot
may vary from pilot shown)
www.fmiproducts.com
SPECIFICATIONS
MF42INE, MF48INE, VFGT24NE,
VFGT30NE, VFGT36NE,
• Rating (Variable): 28,000/38,000 Btu/Hr
• Type Gas: Natural
• Ignition: Electronic
• Manifold Pressure: 4.5" W.C.
• Inlet Gas Pressure (in. of water):
Max - 10.5" W.C., Min* - 5" W.C.
*For purpose of input adjustment
MF42IPE, MF48IPE, VFGT24PE,
VFGT30PE, VFGT36PE
• Rating (Variable): 31,000/39,000 Btu/Hr
• Type Gas: Propane/LP
• Ignition: Electronic
• Manifold Pressure: 8.0" W.C.
• Inlet Gas Pressure (in. of water):
Max - 14" W.C., Min* - 11" W.C.
*For purpose of input adjustment
125795-01B30
Page 31
WIRING DIAGRAM
CONTROL MODULE
REMOTE CONTROL
POWER SUPPLY BOX
125795-01B31
www.fmiproducts.com
Page 32
TROUBLESHOOTING
WARNING: Turn off heater and let cool before servicing. Only a
qualied service person should service and repair heater.
CAUTION: Never use a wire, needle or similar object to clean
ODS/pilot. This can damage ODS/pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
Either the remote or touch pad buttons are pressed to start the burner
ignition sequence and there is no
function or response.
POSSIBLE CAUSE
1. Missing or weak batteries at
power supply box or remote. Control module may beep 10 times or
may not beep at all. LCD display
may show "BATTERY ERROR".
2. Unplugged power supply (battery)
box
3. Touch pad not plugged in to module or plugged in incorrectly
4. Control valve wiring harness not
plugged in or not in proper position
5. Remote not communicating with
control module
REMEDY
1. Check batteries and replace if
needed. (Batteries in the power
supply box can be tested with a
multimeter at the two connections
at the back of the battery housing
where the red and black wires are
connected. Set the multimeter to
DC voltage, initiate the ignition
sequence, and observe the volt-
age while the system is lighting
(under load). The system will not
function under 3.8 volts and batteries should be replaced if the
voltage is under 4.0 volts.)
2. Plug power supply box to module
see page 15.
3. Plug touch pad in module see
page 16, gure 19. Check to see
it is positioned as shown.
4. Check to see that the control valve
wiring harness' blue connector is
plugged in to the module. Check
to see that it is aligned with the
mating pins. If any pins are visible,
then the connector is not in the
correct position. If this is the case,
disconnect, align, and reconnect
to the module.
5. Check the display on the remote
for signal bars. If the display is
blank, press any button one time
to activate the display. Watch the
display for 30 seconds and observe if the signal bars are shown.
(The remote communicates with
the module periodically. It doesn't
communicate with the module
continuously to conserve battery
power.) If the remote is commu-
nicating with the module, signal
bars will be displayed temporarily.
If they are not displayed any, verify
the batteries are new and installed
correctly. If the signal bars still do
not display, follow the Re-Pairing
instructions on page 16.
www.fmiproducts.com
125795-01B32
Page 33
OBSERVED PROBLEM
Either the remote or touch pad buttons are pressed to start the burner
ignition sequence and there is no
function or response. (Continued
from page 32).
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
6. LED is blinking
7. Ignitor cable is not connected
8. Ignitor cable pinched or wet
9. Broken Ignitor cable.
10. Ignitor electrode positioned
wrong.
11. Ignitor electrode broken.
12. Control module sounds 2 cycles
of 3 beeps; LCD display may
show ROM ERROR
13. Control module sounds 2 cycles
of 5 beeps; LCD display may
show SUPPORT ERROR
14. Bad reception from remote
15. If LED on touch pad is continu-
ously on, the cable is connected
the wrong way.
16. The control module sounds 2
cycles of 5 beeps. The wiring
assembly from the control valve
is disconnected or broken.
REMEDY
6. This indicates the battery power is
low. Replace the batteries in the
power supply box.
7. Check the ignitor connection at
both the control module and the
ods pilot. Connect if loose.
8. Free ignitor cable if pinched by
any metal or tubing. Keep ignitor
cable dry.
9. Replace wire harness including
ignitor cable.
10. Replace ods pilot assembly.
11. Replace ods pilot assembly.
12. Replace control module
13. Ground cable from control valve
wiring harness is not grounding properly. Reposition spade
terminal so that it makes contact
with burner chassis metal or
valve body.
14. Change batteries in remote.
Check reception of signal from a
shorter distance. If still not work-
ing, try changing the channel in
the configuration menu. If this
does not x the problem, reset
the channel to A and follow the
instructions in Re-Pairing on page
16. Replace remote and control
module as a nal action.
15. Disconnect the touch pad be-
tween the long and short cables,
turn the short cable with the touch
pad over and reconnect.
16. Connect the wiring harness at the
control module. Replace the valve
assembly if all other cause/remedies fail to correct his problem.
125795-01B33
www.fmiproducts.com
Page 34
OBSERVED PROBLEM
When ignitor button is pressed on the
remote or touch pad, the pilot sparks
but there is no ignition.
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Gas supply turned off or equipment shutoff valve closed
2. Air in gas lines.
3. Thermocouple circuit between
the control valve and the control
module is open.
4. No gas to the ods pilot
5. Depleted gas supply (propane/LP
only)
6. Valve cable is disconnected or
broken.
7. ODS pilot is clogged
8. Gas regulator setting is not correct
REMEDY
1. Turn on gas supply or open equipment shutoff valve.
2. Continue turning the burner system ON and OFF. Repeat igniting
operation until air is removed.
On rst time ignitions, air in the
lines is common and it is not
uncommon to repeat the ignition
sequence 10 to 15 times before
enough gas is at the ods pilot for
it to light.
3. Check the thermocouple connection at the control valve and
also at the control module. The
thermocouple connection at the
control valve should be hand
tight plus 1/4 to 1/2 turn. You
should not be able to loosen
the thermocouple at the control
valve with your hand. Check the
thermocouple terminal connection
at the control module. If it is loose,
remove it with needle nose pliers,
using the pliers, slightly close the
terminal's opening and reinstall on
to the control module.
4. While the pilot is sparking, check
for gas ow at the ods pilot. If ow
is present, try to light the pilot with
a long reach lighter. If it will not
light but the ame is disturbed,
air is in the line. Cycle through
the ignition sequence to clear the
line of air until gas is present. If no
ow is present at the gas valve,
check to see all shut off valves
are open. Verify proper pressure
is supplied to the valve. Excessive pressure can lock out the
appliance's regulator. Also check
to see that the wiring harness
from the control valve is properly
connected at the control module.
The wiring harness connection
housing can be identied by it's
blue connector housing.
5. Contact local propane/LP gas
company.
6. Connect valve cable correctly
7. Clean ods pilot (see Cleaning and
Maintenance , page 30) or replace
ods pilot assembly.
8. Replace gas regulator
www.fmiproducts.com
125795-01B34
Page 35
OBSERVED PROBLEM
ODS pilot lights but pilot ame goes
out before burners light.
Burner system lights from remote
but not from touch pad
Burner system does not ignite
the burner while the remote is
in the program mode.
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Equipment shutoff valve not fully
open
2. Missing or weak batteries at
power supply box or remote.
3. Thermocouple circuit between
the ods pilot and control module
is loose or damaged.
4. Pilot ame not touching thermocouple, which allows thermocouple to cool, causing pilot ame
to go out. This problem could be
caused by one or both of the following:
A) Low gas pressure or
B)Dirty or partially clogged ODS
pilot.
5. Thermocouple damaged
6. Control valve damaged.
1. Touch pad cable disconnected or
broken
2. Defective touch pad
1. Program mode does not work if
soft start is deactivated.
REMEDY
1. Fully open equipment shutoff
valve.
2. Check batteries and replace if
needed. (Batteries in the power
supply box can be tested with a
multimeter at the two connections
at the back of the battery housing
where the red and black wires are
connected. Set the multimeter to
DC voltage, initiate the ignition
sequence, and observe the volt-
age while the system is lighting
(under load). The system will not
function under 3.8 volts and batteries should be replaced if the
voltage is under 4.0 volts.).
3. Check thermocouple terminal
connection at the control module.
If it is loose, remove it with needle
nose pliers, using the pliers,
slightly close the terminal's opening and reinstall on to the control
module.
4. A) Contact local natural or propane/LP gas company.
B) Clean ODS pilot (see Cleaning
and Maintenance , page 30) or
replace ODS pilot assembly.
5. Replace ods pilot assembly.
6. Replace control valve
1. Connect or replace touch pad and
cable.
2. Replace touch pad
1. Activate soft start in the remote.
Burner system shuts off after
operating 6 seconds then
sounds 5 beeps.
Low battery power in remote.
125795-01B35
1. Short in touch pad wiring. BUTTON ERROR is shown in remote
display.
1. Batteries are weak. LOW BATTERY is shown in remote display.
www.fmiproducts.com
1. Replace touch pad and wiring
harness.
1. Replace batteries in remote.
Page 36
OBSERVED PROBLEM
Burner system shuts off. Control
module sounds 2 cycles of 3 beeps.
CONFIG. ERROR is shown in
remote display.
Burner system shuts off. Control
module sounds 2 cycles of 3 beeps.
EEPRON ERROR is shown in
remote display.
Burner system shuts off. Control
module sounds 20 beeps.
Burner system shuts off. Control
module sounds 1 long beep. Remote
displays TEMP ERROR.
Burner systems shuts off. Remote
displays OVER TEMPERATURE.
Burner system lights or shuts off
without touching the remote.
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Faulty control module
1. Remote and control module not
communicating properly
2. Faulty control module
1. Loss of communication between
control module and remote after
18 minutes.
1. Control module is too hot
1. The SAFETY temperature setting
in the remote has shut the burner
system off.
1. More than one burner system
is present and operating on the
same frequency.
REMEDY
1. Replace control module.
1. Follow Re-Pairing instructions
on page 16 to re-pair remote to
control module
2. Replace control module
1. Either the remote is too far from
the burner system or the remote
needs new batteries. The remote
should work within 20 feet of the
burner system. If it does not, replace the batteries in the remote
and battery supply box.
1. Check to see the replace size
meets the minimum requirements. Call technical service.
1. The remote includes a shut off
that is preset at 40C (104F). If the
remote is placed in a location that
is at or above this temperature it
will shut the burner system off.
Placing the remote on a mantel
may result in this problem. If it
occurs, relocate the remote to a
cooler location.
1. Follow the Re-Pairing section to
re-pair the burner system(s). One
burner system may be left on the
original frequency.
www.fmiproducts.com
125795-01B36
Page 37
OBSERVED PROBLEM
Burners do not light after ODS/
pilot is lit
Delayed ignition of one or both
burners
Burner backring during combustion
Yellow ame in middle burner during
burner combustion
Slight smoke or odor during initial
operation
Heater produces a whistling noise
when burners are lit
White powder residue forming within
burner box or on adjacent walls or
furniture
Moisture/condensation noticed on
windows
Heater produces a clicking/ticking
noise just after burners are lit or
shut off
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Inlet gas pressure is too low
2. Burner orice(s) clogged
3. Mislocated crossover tube
1. Manifold pressure is too low
2. Burner orice(s) clogged
3. Mislocated crossover tube
1. Burner orice is clogged or damaged
2. Damaged burner
3. Gas regulator defective
1. Not enough air
2. Gas regulator defective
1. Residues from manufacturing
processes and logs curing
1. Set the unit to HI by using the
remote when burners are cold
2. Air in gas line
3. Air passageways on heater
blocked
4. Dirty or partially clogged burner
orice(s)
1. When heated, vapors from furniture polish, wax, carpet cleaners,
etc. may turn into white powder
residue
1. Not enough combustion/ventilation air
1. Metal expanding while heating or
contracting while cooling
REMEDY
1. Contact local natural or propane/
LP gas company
2. Clean burner(s) (see Cleaning
and Maintenance, page 30) or
replace burner orice(s)
3. Contact qualied service person
1. Contact local natural or propane/
LP gas company
2. Clean burner(s) (see Cleaning
and Maintenance, page 30) or
replace burner orice(s)
3. Contact qualied service person
1. Clean burner (see Cleaning and
Maintenance, page 30) or replace
burner orice
2. Replace damaged burner
3. Replace gas regulator
1. Check burner(s) for dirt and debris. If
found, clean burner(s) (see Cleaning
and Maintenance, page 30)
2. Replace gas regulator
1. Problem will stop after a few hours
of operation
1. Set the unit to LO by using the
remote and let warm up for a
minute
2. Operate burners until air is removed from line. Have gas line
checked by local natural or propane/LP gas company
3. Observe minimum installation
clearances (see pages 9 through
11)
4. Clean burners (see Cleaning and
Maintenance, page 30) or replace
burner orice(s)
1. Turn heater off when using furni-
ture polish, wax, carpet cleaners
or similar products
1. Refer to Air for Combustion and Ventilation requirements (page 6)
1. This is normal with most heaters.
If noise is excessive, contact
qualied service person
125795-01B37
www.fmiproducts.com
Page 38
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning sup-
plies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc.,
create fumes. These fumes may mix with combustion air and create odors. These odors will
disappear over time.
OBSERVED PROBLEM
Heater produces unwanted odors
POSSIBLE CAUSE
1. Heater burning vapors from
paint, hair spray, glues, cleaners,
chemicals, new carpet, etc. (See
IMPORTANT statement above)
REMEDY
1. Open window to ventilate room.
Stop using odor causing products
while heater is running
Heater shuts off in use (ODS
operates)
Gas odor even when control knob
is in OFF position
Gas odor during combustion
Log set cycles to pilot, but room tem-
perature drops to a lower than ideal
level before log set comes back on
2. Low fuel supply (propane/LP only)
3. Gas leak. See Warning state-
ment at top of page
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See Warning state-
ment at top of page
2. Control valve or gas control defective
1. Foreign matter between control
valve and burner
2. Gas leak. See Warning statement at top of page
1. Optional Hand-held remote control is too close to heater
2. Refill supply tank (propane/LP
only)
3. Locate and correct all leaks (see
Checking Gas Connections, page
14)
1. Open window and/or door for
ventilation
2. Contact local natural or propane/
LP gas company
3. Clean ODS/pilot (see Cleaning
and Maintenance, page 30)
1. Locate and correct all leaks (see
Checking Gas Connections, page
14)
2. Replace control valve or gas
control
1. Take apart gas tubing and remove
foreign matter
2. Locate and correct all leaks (see
Checking Gas Connections, page
14)
1. Move hand-held remote control
unit farther away from the heater
www.fmiproducts.com
125795-01B38
Page 39
ACCESSORIES
Purchase these heater accessories from
your local dealer. If they can not supply these
accessories, call FMI PRODUCTS, LLC at
1-866-328-4537 for referral information. You
can also write to the address listed on the
back page of this manual.
FIREPLACE HOOD
Black - GA6050
Antique Brass - GA6053
For all models. Helps deect heat away from
mantel or wall above replace. Fits openings
28" to 48" wide.
LAVA ROCK - GA6060
For all models. Order when additional rock
is desired.
Each log includes a reference number. The rst number indicates the order it is placed on the
burner assembly. The next two numbers indicate the set size.
www.fmiproducts.com
125795-01B42
Page 43
REPLACEMENT PARTS
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
Contact authorized dealers of this product.
If they can’t supply original replacement
part(s), call FMI PRODUCTS, LLC at
1-866-328-4537.
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• heater will not produce specied heat
• propane/LP gas supply may be low
You may feel your gas pressure is too low. If
so, contact your local propane/LP or natural
gas supplier.
When calling, have ready:
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• purchase date
Usually, we will ask you to return the part to
the factory.
TECHNICAL SERVICE
You may have further questions about
installation, operation or troubleshooting.
If so, contact FMI PRODUCTS, LLC at
1-866-328-4537. When calling please have
your model and serial numbers of your
heater ready.
You can also visit our web site at
www.fmiproducts.com.
125795-01B43
www.fmiproducts.com
Page 44
WARRANTY
KEEP THIS WARRANTY
Model (
located on product or identication tag
Serial No. (
located on product or identication tag
Date Purchased __________________________
Keep receipt for warranty verication.
FMI PRODUCTS, LLC LIMITED WARRANTIES
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects
in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date
of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be
free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this
warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only
when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allow-
ance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by
FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI
PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement
parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs,
unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of
the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty
excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all
implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on
new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not
be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
Factory Reconditioned Products
Terms Common to All Warranties
) _____________________________
) __________________________
New Products
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
125795-01
Rev. B
01/12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.