FMI MF42INE, MF42IPE, VFGT24NE, VFGT24PE, VFGT30NE Owner's Operation And Installation Manual

...
Page 1
UNVENTED (VENT-FREE) GAS LOG HEATER
PFS
US
OWNER’S OPERATION AND INSTALLATION MANUAL
REMOTE CONTROL LOG SET AND BURNER SYSTEM MODELS
MF42INE, MF42IPE, MF48INE, MF48IPE, VFGT24NE, VFGT24PE,
VFGT30NE, VFGT30PE, VFGT36NE AND VFGT36PE
MF42 MODELS MAY BE USED WITH LMF36-SC AND LMF42-SC LOGS ONLY
MF48 MODELS MAY BE USED WITH LMF48-SC LOGS ONLY
VFGT24 MODELS MAY BE USED WITH GT24 LOGS ONLY VFGT30 MODELS MAY BE USED WITH GT30 LOGS ONLY VFGT36 MODELS MAY BE USED WITH GT36 LOGS ONLY
®
WARNING: If the information in this manual is not
followed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com
Page 2
TABLE OF CONTENTS
Safety .................................................................. 2
Product Identication ........................................... 5
Local Codes......................................................... 5
Unpacking............................................................ 5
Product Features ................................................. 6
Air For Combustion and Ventilation ..................... 6
Installation ........................................................... 8
Operation ........................................................... 23
Inspecting Burners............................................. 29
SAFETY
WARNING: Improper
installation, adjustment,
alteration, service or main-
tenance can cause injury or property damage. Refer
to this manual for correct
installation and operation­al procedures. For assis-
tance or additional infor-
mation consult a qualied installer, service agency or the gas supplier.
WARNING: This ap­pliance is for installation only in a solid-fuel burn­ing masonry or UL127 factory-built replace or in a listed ventless rebox enclosure. It is design-cer­tied for these installations
in accordance with ANSI
Z21.11.2. Exception: Do not install this appliance in a factory-built replace that
includes instructions stat-
ing it has not been tested or should not be used with unvented gas logs.
Cleaning and Maintenance ................................ 29
Specications .................................................... 30
Wiring Diagram .................................................. 31
Troubleshooting ................................................. 32
Accessories ....................................................... 39
Parts .................................................................. 40
Replacement Parts ............................................ 43
Service Hints ..................................................... 43
Technical Service............................................... 43
Warranty ..............................................Back Cover
WARNING: This is an
unvented gas-red heat­er. It uses air (oxygen)
from the room in which
it is installed. Provisions for adequate combustion
and ventilation air must
be provided. Refer to Air for Combustion and Ven­tilation section on page 6
of this manual.
This appliance may be in-
stalled in an aftermarket,*
permanently located, manufactured (mobile) home, where not prohib­ited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
www.fmiproducts.com
125795-01B2
Page 3
SAFETY
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the state of California
to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, re, explo­sion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs, the replace may not be
working properly. Get fresh air at once! Have replace serviced. Some people are more af­fected by carbon monoxide than others. These
include pregnant women, people with heart or lung disease or anemia, those under the inu-
ence of alcohol and those at high altitudes. Natural and Propane/LP
odor-making agent is added to these gases. The odor helps you detect a gas leak. How-
ever, the odor added to the gas can fade. Gas
may be present even though no odor exists. Make certain you read and understand all
warnings. Keep this manual for reference. It is your guide to safe and proper operation of
this replace.
gases are odorless. An
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the replace. Avoid any drafts that alter burner ame patterns. Ceiling fans can create drafts that alter burner ame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with heater. When using the hand­held remote accessory, keep se­lector switch in the OFF position to prevent children from turning on burners with remote.
You must operate this heater with the replace screen and hood in place. Make sure re­place screen and hood are in place before running heater.
WARNING: Do not use a
blower insert, heat exchanger insert or other accessory not ap­proved for use with this heater.
125795-01B 3
www.fmiproducts.com
Keep the appliance area clear and free from combustible ma­terials, gasoline and other am­mable vapors and liquids.
Page 4
SAFETY
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup­plier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. This heater shall not be installed in a bedroom or bathroom.
5. Before installing in a solid fuel burning re­place, the chimney ue and rebox must be cleaned of soot, creosote, ashes and loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue for damage. If damaged, repair ue and rebox before operating heater.
6. Do not burn solid-fuel in a masonry or
UL127 factory-built replace in which a
vent-free room heater is installed.
7. If replace has glass doors, never operate
this heater with glass doors closed. If you
operate heater with doors closed, heat buildup inside replace will cause glass to
burst. Make sure there are no obstructions
across openings of replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance, page 29.
9. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may
create a white powder residue within burner box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ven­tilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if enough fresh air is not available. See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see Troubleshooting, page 32.
11. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn paper or other objects.
13. Do not use heater if any part has been ex­posed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part of the control system and any gas control which has been under water.
14. Do not operate heater if any log is broken. Do not operate heater if a log is chipped
(dime-sized or larger).
15. Turn heater off and let cool before servic-
ing, installing or repairing. Only a qualied service person should install, service or
repair heater.
16. Make sure the remote is set to the OFF position when you are away from home for long periods of time.
17. Remote heaters must not be connected to any external electrical source.
18. Operating heater above elevations of
4,500 feet may cause pilot outage.
19. To prevent performance problems, do
not use propane/LP fuel tank of less than 100 lb. capacity (propane/LP units only).
20. Provide adequate clearances around air openings.
www.fmiproducts.com
125795-01B4
Page 5
Chassis
Glowing
Embers
PRODUCT IDENTIFICATION
Figure 1 - Product Identication
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
State of Massachusetts: The installa­tion must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Commonwealth of Massachusetts.
125795-01B 5
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
www.fmiproducts.com
data plates from the grate as­sembly. The data plates contain important warranty and safety information.
1. Remove logs and heater base assembly
Note: Do not pick up heater base assem-
2. Remove all protective packaging applied
3. Check heater for any shipping damage. If
UNPACKING
CAUTION: Do not remove the
from carton(s).
bly by burners. This could damage heater. Always handle base assembly by grate.
to logs and heater for shipment.
heater is damaged call FMI PRODUCTS,
LLC at 1-866-328-4537 for replacement parts before returning to dealer.
Page 6
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by
both realistic ames and glowing coals. This
heater is designed for vent-free operation
with ue damper closed. It has been tested
and approved to ANSI Z21.11.2 standard for unvented heaters.
SAFETY DEVICE
This heater has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This heater has an electronic ignitor to light heater fuel supply.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space unless the required volume of indoor combustion air is provided by the method described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable
local codes. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efcient than ever. New materials, increased insulation
and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. Dur-
ing heating months, home owners want their
homes as airtight as possible. While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning ap­pliances need fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion
and ventilation. However, in buildings of un­usually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 8. If your home does not meet all of the three
criteria above, proceed to Determining Fresh­Air Flow For Heater Location, page 7.
-11
kg per pa-sec-m2) or
www.fmiproducts.com
125795-01B6
Page 7
AIR FOR COMBUSTION AND VENTILATION
Continued
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet
per 1,000 Btu/hr (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are
installed*, through openings not furnished with doors, are considered a part of the un­conned space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Conned or Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
replace plus any adjoining rooms with door­less passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support) Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
125795-01B 7
www.fmiproducts.com
Vent-free replace __________ Btu/Hr Gas water heater* __________ Btu/Hr Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr Gas replace logs __________ Btu/Hr Other gas appliances* + _________ Btu/Hr Total = _________ Btu/Hr * Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/Hr Vent-free replace + _________ Btu/Hr
Total = _________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/ Hr used.
______Btu/Hr (maximum the space can
support)
______Btu/Hr (actual amount used) Example: 51,200 Btu/Hr (maximum the
space can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a conned
space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can sup­port. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an unconned space, remove door to adjoin­ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is an unconned space. You will need no additional
fresh air ventilation.
40,000 33,000 73,000
WARNING: If the area in which
the heater may be operated does not meet the required volume for indoor combustion air, combus­tion and ventilation air shall be provided by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code,
or applicable local codes.
Page 8
AIR FOR COMBUSTION AND VENTILATION
Outlet Air
Ventilated Attic
Outlet
A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Figure 2 - Ventilation Air from Inside Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two perma­nent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size
of ventilation grills or ducts. IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo­stat-controlled power vent. Heated air entering the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualied ser­vice person must install heater. Follow all local codes.
www.fmiproducts.com
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of re­place. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney ue damper.
125795-01B8
Page 9
INSTALLATION
Continued
WARNING: Before installing in a solid fuel burning replace, the chimney ue and rebox must be cleaned of soot, creo­sote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney ue may
CHECK GAS TYPE
Use the correct type of gas (natural or propane/ LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is equipped for either natural gas or propane/LP gas but not both. Gas type is indicated on the rat­ing plate. Field conversion is not permitted.
create and distribute soot within the house. Inspect chimney and rebox ue for damage. If dam-
INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
aged, repair ue and rebox before operating heater.
WARNING: Maintain the
minimum clearances. If you can,
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
where curtains, furniture, cloth-
ing or other ammable objects
are less than 36" from front, 42"
from top of heater; for side clear­ances see Figure 4, page 10
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next
to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, to­bacco smoke, aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventila-
tion, page 6.
125795-01B 9
www.fmiproducts.com
provide greater clearances from oor, ceiling and adjoining wall.
MINIMUM FIREPLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42"
Floor 5", Front: 36"
LOG SIZING REQUIREMENTS
Log
Size
LMF36-SC 29" 15.5" 32.5" 22.75" LMF42-SC 29" 15.5" 39" 26.75" LMF48-SC 29'' 20'' 47'' 33''
GT24 29'' 15.5'' 32.5'' 22.75'' GT30 29'' 15.5'' 39'' 26.75'' GT36 29'' 20'' 47'' 33''
* Also approved for use in Vantage Hearth Model
VFB42, VTFB42 and VUM42 replaces.
Carefully follow the instructions below. This
will ensure safe installation into a masonry, UL127-listed manufactured replace or listed vent-free rebox.
Minimum Clearances For Side Combustible Material, Side Wall and Ceiling
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4,
page 10.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This combustible material must be 4" from the
side of the replace cabinet (see Figure 4, page 10).
Minimum Firebox Size
Height Depth
Front
Width
Rear* Width
Page 10
INSTALLATION
Heat Resistant Material
(A)
Continued
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less than 42".
Noncombustible
Material Distance
Requirements for
Safe Installation
(A)
1
2" or more Noncombustible mate-
rial OK.
Between 8" and 12"
Install replace hood accessory (GA6050 or GA6053 see Accesso- ries, page 39).
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using Mantel. If not using a mantel, follow these instructions.
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible
material is less than 12", you must install the replace hood accessory (24" and 30" Models
Only). See Figure 5 for minimum clearances.
Less than 8"
Noncombustible mate­rial must be extended to at least 8". See
Between 8" and 12",
above. If you cannot
extend material, you
must operate heater
with ue damper open.
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be­hind it. Noncombustible material must extend at least 8" up (for all models). If noncom-
bustible material is less than 12", you must install the replace hood accessory. Even if noncombustible material is more than 12", you may need the hood accessory to deect
heat away from your mantel shelf. See Figure
5 and Figures 6 and 7, page 11, for minimum
clearances.
www.fmiproducts.com
125795-01B10
Page 11
INSTALLATION
14" Min.
Combustible Material
Noncombustible Material
Minimum Non­Combustible Material
Minimum Non­Combustible Material Height
Distances to Underside of Mantel
Top of Fireplace Opening
Underside of Mantel Shelf
12"
(A)
18" 20" 22" 24"
All minimum distances are in inches
2
1
/2
"
6"
8"
10"
Mantel Shelf
Minimum Noncombustible Material
8" Min.
12" 15" 18" 20"
2
1
/2
"
6"
8"
10"
12"
Distances to Underside of
Mantel
Hood (GA6050
or GA6053)
Top of Fireplace Opening
Underside
of Mantel
Shelf
Mantel Shelf
Hearth
5" Min.
Combustible Material
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 6, are not met, you must have a hood. When using a
hood there are still certain minimum mantel clearances required. Follow minimum clear-
ances shown in Figure 7, when using hood.
NOTICE: Surface temperatures of adjacent walls and mantels be­come hot during operation. Walls and mantels above the rebox may become hot to the touch. If installed properly, these tem­peratures meet the requirement of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does not meet the minimum clear­ances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the replace, you must install appliance at least 5" above the combustible ooring
(see Figure 9).
Figure 8 - Minimum Fireplace Clearances
Figure 7 - Minimum Mantel Clearances
125795-01B 11
When Using Hood
www.fmiproducts.com
Figure 9 - Minimum Fireplace Clearances
If Installed at Floor Level
Above Combustible Flooring
Page 12
INSTALLATION
INSTALLING HEATER BASE ASSEMBLY
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you
adjust controls. Moving heater may cause a gas leak.
WARNING: If installing in a sunken replace, special care is needed. You must raise the replace oor to allow access to heater control panel. This will in­sure adequate air ow and guard against sooting and controls being damaged. Raise replace oor with noncombustible mate­rial. Make sure material is secure.
Continued
3. Mark screw locations through holes in front panel of base (see Figure 11). If
installing in a brick-bottom replace, mark
screw locations in mortar joint of bricks.
4. Remove heater base from replace.
5. Drill holes at marked locations using 3/16" drill bit.
6. Attach base, through holes in back side pan­els of base, to replace oor using masonry
screws provided in hardware package (see Figure 11).
7. Connect to gas supply. See Connecting
To Gas Supply, page 13.
Heater Gas
Regulator
Flexible Gas Hose (Provided with Models, Install if
allowed by local codes)
CAUTION: Do not pick up heater base assembly by burn­ers. This could damage heater. Only handle base assembly by grates.
IMPORTANT: Make sure the heater burners are level.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings
provided (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
Note: Install optional MRC Series receiver and hand-held remote control kit (see Ac­cessories, page 39) before installing gas log heater. See installation instructions included with the kit.
1. Apply pipe joint sealant lightly to male
threads of the 3/8 NPT side of gas tting
elbow (provided) and connect to inlet
side of gas control. Remove gas tting from exible gas hose (provided) before
connecting to elbow (see Figure 10).
2. Position heater base assembly in re­place.
www.fmiproducts.com
Figure 10 - Attaching Flexible Gas Hose
to Heater Gas Regulator
Masonry Screw
Figure 11 - Attaching Base to Fireplace
Floor
125795-01B12
Page 13
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualied service person must connect heater to gas supply. Follow all local codes.
CAUTION: Never connect
propane/LP replace directly to the propane/LP supply. This heater requires an external regu­lator (not supplied). Install the external regulator between the heater and propane/LP supply.
WARNING: Never connect
natural gas replace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connec-
tor (if allowed by local codes) (not provided)
* An equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional equipment shutoff valve from your dealer.
For propane/LP units, the installer must
supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not re-
duce incoming gas pressure, heater regulator
damage could occur. Install external regulator
125795-01B 13
www.fmiproducts.com
with the vent pointing down as shown in Figure
12, page 14. Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. In­ternally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see
Figure 13, page 14).
IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Propane/LP Supply Tank
Figure 12 - External Regulator With Vent
Pointing Down
External Regulator with Vent Pointing Down
Page 14
INSTALLATION
Continued
PROPANE/LP From External Regulator (11" W.C.** to 14" W.C. Pressure)
NATURAL From Gas
Meter (5" W.C.** to 10.5" W.C. Pressure)
Tee Cap Pipe Joint Nipple
Sediment Trap
Figure 13 - Gas Connection
* Purchase the optional equipment shutoff
valve from your dealer.
**Minimum inlet pressure for purpose of input
adjustment.
We recommend that you install a sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contami­nants. This keeps them from going into heater controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
CAUTION: Avoid damage to gas control. Hold gas control with wrench when connecting it to gas piping and/or ttings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and external to unit, for leaks after
installing or servicing. Correct all leaks at once.
Equipment Shutoff Valve With 1/8" NPT Tap*
Approved
Flexible Gas
Hose (if allowed
by local codes)
3" Minimum
Gas
Regulator
www.fmiproducts.com
WARNING: Never use an open ame to check for a leak. Apply a noncorrosive leak detection uid to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed between propane/LP supply and heater. See guidelines under Con- necting to Gas Supply, page 13.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equip­ment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equip­ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection uid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply. Check reconnected
ttings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig­ure 15).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
3. Check all joints from gas meter to equip­ment shutoff valve for natural gas or pro­pane/LP supply to equipment shutoff valve for propane/LP (see Figure 15 or Figure
16). Apply noncorrosive leak detection uid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
125795-01B14
Page 15
INSTALLATION
Continued
PRESSURE TESTING HEATER GAS
CONNECTIONS
1.
Open equipment shutoff valve (see Figure 14).
2. Open main gas valve located on or near gas meter for natural gas or open pro­pane/LP supply tank valve.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from gas meter to equip­ment shutoff valve for natural gas or pro­pane/LP supply to equipment shutoff valve
for propane/LP (see Figure 15, or Figure
16). Apply noncorrosive leak detection uid
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operation, page 23). Check all other internal joints for leaks.
7.
Turn off heater (see To Turn Off Gas to
Appliance, page 23 for Remote models.
Equipment Shutoff Valve
Figure 14 - Equipment Shutoff Valve
Propane/LP Supply Tank
Figure 15 - Checking Gas Joints
(Propane/LP Only)
Equipment Shutoff Valve
Gas Meter
Figure 16 - Checking Gas Joints (Natural
125795-01B 15
Equipment Shutoff Valve
Gas Only)
Open
Closed
Control Valve Location
Control Valve Location
www.fmiproducts.com
POWER SUPPLY AND BATTERY
INSTALLATION
It is helpful to have a ashlight so you can
see the connections as described below. Lo­cate the battery power supply. It is the black box with the red and black wires. Locate the control module (see Figure 17). Connect the battery power supply to the control module by plugging the battery power supply to the mating receptacle on the control module. The receptacle is located on the side of the black
control module next to the word “SUPPLY”
which is molded in the control module’s black housing (see Figure 17). Be certain to push the plug fully into the receptacle. Install bat­teries in the battery power supply and hand held remote control.
S1 Button
Connect Battery Plug Here
Figure 17 - Control Module
TOUCH PAD INSTALLATION
Locate the touch pad wire harness and the
touch pad control (see Figure 18, page 16).
They are shipped from the factory in the clear plastic bag with your owner’s manual. Con­nect the black plastic connectors together as
shown in Figure 19, page 16. Connect the
remaining end with the white plastic connector to the control module in the socket marked
TOUCH LED (see Figure 20, page 16).
NOTE: The touch pad includes a red LED
display light. If the LED remains on, the black
plug is connected upside down. You must unplug the touch pad control from the touch
pad wire harness, turn over, and reconnect.
Page 16
INSTALLATION
Configuration
Select
Back
Off
No
Yes
0.5°C
Thermostat
Programming
Gap Temp
Fri 22:04
Pairing
Configuration
Change
Back
Yes
Yes
0.5°C
Thermostat
Programming
Gap Temp
Fri 21:47
Off
Pairing
Continued
Touch Pad Wire Harness
Touch Pad Control
Figure 18 - Touch Pad Wire Harness and
Touch Pad Control
Figure 19 - Touch Pad Control Cable
proceeding, locate the yellow/orange S1
button on the control module. You will need to access this button during the re-pairing procedure and only have 20 seconds to press and release it. A small nail or ink pen will also
be useful to press this button (see Figure 17,
page 15). Press and hold the “Off” button on the
remote control for 40 seconds. During this
time, the screen will go blank, this is normal.
See Figure 21.
Fri 20:45
OFF
u
°F
75
Lock MenuOn
OFF Button
Figure 21 - Main Screen
After 40 seconds, the conguration menu
appears (see Figure 22). With ''Pairing'' high­lighted press the middle ''select'' button. ''Off'' becomes highlighted (see Figures 22 and 23).
Figure 20 - Connecting end of Touch Pad
Cable
RE-PAIRING
IMPORTANT! This appliance is shipped with the remote control and control module
(receiver) paired. However, if more than one
Copreci brand electronic ignition system is to be used within a home or showroom, all but one appliance must have the remote control and control module re-paired in order for each appliance to operate on a unique
frequency. For multiple appliances, on all but
one follow the instructions under Re-Pairing on page 16 before moving to Installing Logs
on page 18. For single appliance installations, skip the RE-PARING section and proceed to
Installing Logs.
It is helpful to have a ashlight so you can see
the connections as described below. Before
www.fmiproducts.com
Fri 22:04
Configuration
Pairing
Thermostat Gap Temp Programming
Select
Off Yes
0.5°C No
Back
SELECT Button
Figure 22 - Conguration Menu
125795-01B16
Page 17
INSTALLATION
Configuration
Select
Back
Off
No
Yes
0.5°C
Thermostat
Programming
Gap Temp
Fri 22:05
Pairing
Continued
Fri 21:47
Configuration Pairing
Thermostat Gap Temp Programming Change
Figure 23 - Off Highlighted
IMPORTANT! Be prepared to press the S1 button as noted in the beginning of this sec-
tion. After the next step, you have only 20
seconds to push (press and release) the S1 button (yellow/orange) in the control module
(see Figure 17, page 15). NOTE: The control module may be turned dif-
ferently than shown in this gure. Look for the
matching text on the control module to help locate the small yellow / orange S1.
Fri 22:04
Pairing
Thermostat
Change Button
Gap Temp Programming
Change
Off
Yes
0.5°C Yes Back
Configuration
0.5°C
On
Yes
No Back
see signal bars within 30 seconds of hearing
the beep, then the repairing process was not completed successfully. If this occurs, remove the batteries from the remote control, wait 3 minutes, and restart the re-pairing process. If you see signal bars, then the remote control has paired properly. Go to the next step.
Fri 22:05
Configuration Pairing
Thermostat Gap Temp Programming Change
Off
Yes
0.5°C No Back
Figure 25 - Signal Bars
Press the “Back” button once to return the highlighted selection to “Pairing”. Press the “Middle” button and release. The indication on the “Pairing” will become “Off” (see Figure 26).
The re-pairing is over. To return to the main
screen, press the “Back” button until you get
to the main screen. The main screen is shown
in Figure 21, page 16.
Fri 22:05
Configuration
Figure 24 - Change OFF to ON
Press the left "Change" button and "Off" becomes "On" (see Figure 24, above). Press the S1 but­ton to re-pair the remote to the control module.
Once this operation is done, you will hear one
Middle Button
Pairing
Thermostat Gap Temp Programming
Select
Off Yes
0.5°C No
Back
Back Button
beep in the control module and the congura­tion menu will show signal bars: (see
Figure 25). If you do not hear the beep and then
125795-01B 17
www.fmiproducts.com
Figure 26 - Back and Middle Buttons
Page 18
INSTALLATION
Continued
MF SERIES BURNER SYSTEM-LOG
COMPATIBILITY CHART
Burner System Model
MF42INE,MF42IPE, LMF36-SC
MF48INE, MF48IPE,
Figure 27 - MF Series Burner System-
Log Compatibility Chart
INSTALLING LOGS, EMBERS AND LAVA ROCK
Refractory Concrete Logs For Use With This Burner System
LMF42-SC
LMF48-SC
1. Find the right front log (LMF36-SC and
VFGT24 inch models: D-061 or LMF42­SC and VFGT30 inch models: D-019 or LMF48-SC and VFGT36 inch models: D-027). See Figures 28, 28A, 28B, and
28C for reference. The log has a rectan-
gular shape on the bottom that ts against the lip on the black metal base, the square grate, and the round tube burner. Slide the
log in place as shown in Figures.
Right Front Log Burner Tube
(D061, D-019 or D027)
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specically approved with this heater may result in property damage or personal injury.
CAUTION: After installa-
tion and periodically thereafter, check to ensure that no ame comes in contact with any log.
With heater set to Hi, check to
see if ames contact any log. If so, reposition logs according to log installation instructions in this manual. Flames contacting logs will create soot.
LOG PLACEMENT
It is very important to install these logs exactly as instructed. Do not modify logs. Only use
logs supplied with heater or for MF models, as identied for use with the heater as shown
in Figure 27.
Note: Each log includes an identifying number cast in the log. Look at each log when plac­ing them on the burner system to be certain it is correct.
Note: For additional information, go to www.fmiproducts.com and click on the
technical Support tab for access to log placement videos.
www.fmiproducts.com
Grate Finger
Figure 28 - Installing Right Front Log
Round Tube Burner
Grate Finger
Figure 28A - Installing Right Front Log,
Burner Tube
Figure 28B - Installing Right Front Log,
Top View
Square Grate
Top View
125795-01B18
Page 19
INSTALLATION
Continued
Figure 28C - Installing Right Front Log,
Side View
2. Find the back left log (LMF36-SC and
VFGT24 inch models: D-060 or LMF42­SC and VFGT30 inch models: D-018 or LMF48-SC and VFGT36 inch models: D-026). See Figures 29, 29A, and 29B. Figure 29A shows how the log must t
against the end of the burner. Figure 29B
shows how the notch in log ts against the
vertical portion of the burner tube. Place this log on the base assembly by inserting it from the left side as shown in Figure 19. You will need to twist the log slightly to get
it to t against the burners properly. It will
rest even with the back edge of the pan.
Back Left Log (D-060,
D-018 or D026)
Log Notch
Flat Part of Log
Burner Tube
Figure 29 - Installing Back Left Log
Vertical Portion of Burner Tube
Figure 29B - Installing Back Left Log
(D-018) Rear View
3. Find the front left log (LMF36-SC and
VFGT24 inch models: D-059 or LMF42­SC and VTGF30 inch models: D-017 or LMF48-SC and VFGT36 inch models: D-025). See Figures 30, 30A, and 30B.
The log has a rectangular stand off on
the bottom that ts against the lip on the black metal base as shown in gure 30A. The bottom of this log has a slot that ts
over the second bar on the grate as shown
in Figure 30B, page 20. Place the log on the base assembly as shown in gures.
Front Left Log (D-059,
D-017 or D025)
Grate Fingers
Figure 30 - Installing Front Left Log
Log Notch
Burner Tube
Figure 30A - Installing Front Left Log
Figure 29A - Installing Back Left Log
125795-01B 19
www.fmiproducts.com
Side View
Page 20
INSTALLATION
Continued
Square Grate
Log Notch
Grate Finger
Log Slot
Figure 30B - Installing Front Left Log
4. Find the charred log (D-020). See Figures
31, 31A, and 31B. The log has a slot in the bottom that ts over the square grate and
rests against the burner tube as shown in Figure 31. Place this log on the base as
shown in gures.
Charred Log
Log Notch
Right Front Log
Figure 31 - Installing Charred Log
Figure 31B - Installing Charred Log Top
Side View
5. Find the middle split log (LMF36-SC and
VFGT24 inch models: D-063 or LMF42­SC and VFGT30 inch models: D-021 or LMF48-SC and VTGF36 inch models:
D-028). See Figures 32 and 32A. The split side of the log faces forward. The log has
a notch that ts around the burner tube on
the right side. The left side of the burner
tube ts into the notch on the back side of
this log. The log is placed properly when it sits parallel to the tube burner and the
square peg is pointing up. See gures
for reference.
Square Peg
Middle Split Log (D-063,
D-021 or D028)
Figure 32 - Installing Middle Split Log
(D-021)
Burner Tube
Log Notch
Figure 31A - Installing Charred Log Top
View
www.fmiproducts.com
Figure 32A - Installing Middle Split Log
Rear Top Side View
125795-01B20
Page 21
INSTALLATION
Continued
6. Find the right split crossover log (D-022) The bottom of the log has a rectangular
stand off that ts in the slots on the right
side of the front right log and the middle split log. Place this log as shown in Fig­ure 33.
Square Peg
Right Split Cross­over Log (D-022)
Back Top Log (D-062,
D-023 or D029)
Right Split Cross­over Log (D-022)
Right Front Log
Figure 33 - Installing Right Split
Crossover Log
7. Find the front top log (D-024). See Figure
34. The left end of this log has a square hole
that ts over a square peg that is on the top
of the middle split log. The right end of this log rests behind the knot on the top of the front right log.
Front Top Log (D-024)
Middle Split Log
Right Split Cross­over Log (D-022)
Rectangular Peg
Figure 34 - Installing Front Top Log
8. Find the back top log (LMF36-SC and
VFGT24 inch models: D-062 or LMF42-SC and VFGT30 inch models: D-023 or LMF48­SC and VTGF36 inch models: D-029). See Figures 35, and 35 A. The left end of this log has a round hole that ts over the round
peg that is on the top of the back left log. The right end of this log has a rectangular hole
that ts over the rectangular peg on the top
of the right crossover log.
Figure 35 - Installing Back Top Log and
Final Assembly
Figure 35A - Installing Back Top Log,
Top View
125795-01B 21
www.fmiproducts.com
Page 22
INSTALLATION
Continued
EMBER PLACEMENT
Two ember materials are supplied with this log set. Platinum Bright Embers give a bright glow appearing as hot coals. Should embers
need replacing, see Accessories, page 39.
Platinum Bright Ember placement.
Add embers to front, at burner. Gently
remove embers from bag. Separate pieces of ember material and place on
surface of at burner just behind hori­zontal ports as shown in Figure 36.
WARNING: Do not use any
other ember material not sup­plied with this unit.
WARNING: Do not operate unit without ember material correctly in place as shown in Figures 36 & 37. Do NOT place ember mate­rial anywhere else on the unit. Use only ember material supplied with unit. Excessive or incorrectly placed ember material may pro­duce carbon monoxide or soot.
LAVA ROCK PLACEMENT
• Rock Wool placement. Place rock wool
material on front at burner in areas away
from ports as shown in Figure 37.
• Add lava rock; Lava rock may cover 1/2 inch of the front burner(at metal ember
pan burner) but shall not be allowed to come in contact with either the burner ports or ame around base of heater if de­sired. DO NOT place rock or additional
logs on front burner or on logs except as directed above. Placing any material
on unit other than ember material on front burner may result in production of carbon monoxide or soot. A switch log is included with each log set. This log is designed to house a switch on remote ready models.
On variable remote models, this switch is
not needed. The log can be placed on the
oor of the replace to enhance the look
of the log set. Use lava rock to hide wires from switch/log to control valve. Place switch/log so the switch is easy to access.
Ember Material
Figure 36 - Platinum Bright Embers
Rock Wool
Figure 37 - Placement of Rock Wool (shown with Platinum Bright Embers)
www.fmiproducts.com
Flat Front Burner
125795-01B22
Page 23
OPERATION
NOTICE: During initial operation of new heater, burning logs will give off a paper-burning smell. Orange ame will also be pres­ent. Open damper or window to vent smell. This will only last a few hours.
WARNING:
• If replace has glass doors, never operate this heater with glass doors closed. If you op-
erate heater with doors closed,
heat buildup inside replace will cause glass to burst. Make sure there are no obstructions across openings of replace.
• You must operate this heater with a replace screen in place. Make sure replace screen is closed before running heater.
WARNING: Damper handle will be hot if heater has been running.
CAUTION: Do not try to ad-
just heating levels by using the equipment shutoff valve.
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not fol­low these instructions exactly,
a re or explosion may result causing property damage, per­sonal injury or loss of life.
A. This appliance has a pilot that is
equipped with an ignition device which automatically lights the pilot. Do not light the pilot by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
C. Do not use this appliance if any part
has been under water. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
1. STOP! Read the safety information.
2. Make sure equipment shutoff valve is fully open.
3. Press any button on the remote to power the remote on. If you see a Lock icon and the word ''Unlock'' in the lower left corner of the screen you will need to unlock the screen by pressing ''Unlock'' and ''OK''.
4. Press ''On'' and ''OK''. It may take up to 4 seconds before the control unit processes the command. You will hear a beep from the control unit and the pilot will start to spark before lighting.
Note: You may be running this heater for the
rst time after hooking up to gas supply.
If so, you may have to restart the unit several of times to allow the air to bleed from the system.
TO TURN OFF GAS
TO APPLIANCE
1. Press OFF (bottom button) on the remote control.
2. Close equipment shutoff valve.
125795-01B 23
www.fmiproducts.com
Page 24
OPERATION
gO
REMOTE CONTROL OPERATION
The remote control contains:
1. LCD display
2. Four buttons: OFF button Left button Middle button Right button
3. Battery Case (on the Back)
LCD Screen
Middle Button
Left Button
Batteries (Back Side)
Right Button
OFF Button
Continued
Figure 39 - LCD Display
The screen changes depending on the input
from the buttons, but the bottom row always
displays the button function labels (see Figure
40). The functions of each button depends on the options available on the current screen (except for the OFF button which has always the same function). Note: The bottom row of the screen is indicating buttons functionality. In this case:
LEFT ( ) button decreases the ame level
MIDDLE ( ) button increases the ame level
• RIGHT (Back) button goes back to the
previous screen (see Figure 40).
Figure 38 - Remote Control
LCD DISPLAY
The LCD screen shows information about the instructions given by the user (desired status) and the current situation of the device (actual
status). It also helps us select our choices,
see Figure 39.
A: Day of the week
B: Time
C: Signal Strength
D: Selected working mode
E: Selected setting
F: Current Flame status
• G: Current fan status
H: Current room temperature
I: Child lock status
J: Button labels (explained below)
www.fmiproducts.com
Mon 00-02
Configuration
Left Button
Pairin
Thermostatic
Gap Temp
Programming
0.5°C
BackSelect
ff
Off
Yes
Bottom Row
Middle Button
Right Button
Figure 40 - Screen Changes
OFF BUTTON
This button switches off the appliance. If it is
pressed and held for more than 40 seconds, the conguration menu is accessed.
LEFT, MIDDLE AND RIGHT BUTTON
These buttons change their function as shown by the on-screen labels. For some screens a button may have no function and is inactive. The active buttons for a particular screen are initially lit for 5 seconds to indicate that they are active.
125795-01B24
Page 25
OPERATION
Continued
MENU SYSTEM
The remote is organized by means of a menu
system.
After batteries are installed the rst time, the
remote starts at the ''OFF'' screen ( it is pos­sible that the remote is locked in the ''OFF'' screen: to unlock it just press the button below
''Unlock'', and then ''OK''. See Figure 41).
Available after
PROGRAM
MODE is
enabled, see
And then
Figure 42 - Adjusting Menu
SETTING THE CONTROL MODE
Figure 41 - Menu System
SWITCHING ON
IMPORTANT: When lighting the pilot and
burner for the rst time, air will be present in
the system that must be purged. The lighting sequence may have to be re-
peated 10 to 15 times before gas reaches the pilot. This is normal.
To turn the system on, press “On” (left but­ton) and “OK” (middle button). A beep from
the control module will be heard and the ignition process will start. This will take up to 20 seconds. Note that while in operation the signal bars will disappear for a few mo-
ments. If the pilot and burner do not light, press the “Off” button, wait 15 seconds then
repeat the ignition steps from the beginning of this paragraph. Note: each ignition step is accompanied by two short series of ignition sparks at the pilot.
ADJUST MENU
Before using the remote, there are various settings which should be made, such as the date, the language, the autolock option and
the comfort temperature.
For doing this, press ''Menu'' and then press
''Select'' to chose ''Adjust Menu''. There the
options shown in Figure 42, can be set. To
change any of these settings use the down arrow to select the feature and then press "Select" and "Change" to change the setting.
125795-01B 25
www.fmiproducts.com
There are three different modes for controlling the appliance:
Manual Auto Program
In Manual mode the main burner can be switched on and off.
Auto mode allows you to set a temperature, while in Manual mode the ame level may be set to HIGH, MEDIUM, or LOW. Program
mode offers automatic temperature control for
specic times of the day.
In the initial screen when the remote is
turned on, three options are available: AUTO,
MANUAL and MENU. Auto and Manual are two of the three differ-
ent modes for controlling the appliance with the remote.
MANUAL MODE
If ''Manual'' is pressed, the ame setting ap­pears as the selected setting. In the bottom row, and appear, indicating that the ame level can be changed by pressing the left or middle button. Pressing ''Back'' (right button)
returns to the initial screen (see Figure 40,
page 24). Note that a safety temperature can be set
in the configuration menu. This specifies the maximum the maximum permitted room temperature. This temperature can never be set higher than 40ºC (104ºF).
PROGRAM
MODE section on next page.
Page 26
OPERATION
Configuration
Change Back
Off
Yes
0.5°C
Thermostat Gap Temp
Fri 23:33
Pairing
Programming No
Fri 21:40
Lock MenuOn
OFF
°F
71
u
Continued
AUTO MODE
If ''Auto'' is pressed in the initial screen, 25ºC
(77ºF) appears as the desired temperature in
the selected setting. In the bottom row, and
appear, indicating that we can change the
desired temperature value by just pressing the left or middle button. In auto mode the appli­ance heats until this temperature is reached.
Pressing ''Back'' (right button), returns to the
initial screen. The Auto mode feature is optional and can
be enabled or disabled in the conguration
menu by changing ''Thermostat'' to either ''Yes'' (enabled) or to ''No'' (disabled). Access
to the conguration menu is described in the
next section.
PROGRAMMING
PROGRAM MODE
A program mode is available if desired. This mode allows the remote control to operate the gas log set in either weekly or daily set­tings. To enable the program mode access
the conguration menu. CONFIGURATION MENU ACCESS: Press
and hold the “OFF” button on the remote control for 40 seconds. During this time, the screen will go blank for a few seconds, this is normal. See Figure 43. After 40 seconds, the conguration menu appears (see Figure 44).
Fri 23:27
Configuration Pairing
Thermostat
Arrow Button
Gap Temp
Programming
Select
Figure 44 - Programming
Fri 23:33
Configuration Pairing
Thermostat Gap Temp Programming No Change Back
Off
Yes
0.5°C No
Back
0.5°C
Off
Yes
SELECT Button
Fri 20:45
OFF
u
°F
75
Lock MenuOn
Figure 43 - OFF Button
Press the arrow button ( ) until Programming is highlighted (see Figure 70). If Programming
has ''No'' next to it, press the ''Select'' button
Fri 22:04
Configuration
Pairing
Thermostat Gap Temp Programming
OFF Button
Select
Off Yes
0.5°C No
Back
to highlight ''No'' (see Figures 44 and 45).
www.fmiproducts.com
Figure 45 - Highlighting ''No''
Press ''Change'' (left button) to change Pro­gramming from ''No'' to ''Yes'' (see Figure 72).
To return to the main screen, press the''Back''
button until you get to the main screen. The
main screen is shown in Figure 47, page 27. The PROGRAM MODE is now enabled.
Fri 23:33
Configuration
Change Button
Pairing
Thermostat Gap Temp Programming Change Back
Off Yes
0.5°C Yes
Figure 46- Changing ''No'' to ''Yes''
125795-01B26
Page 27
OPERATION
Continued
Fri 21:40
OFF
u
°F
71
Lock MenuOn
Figure 47 - Main screen
There are two types of program mode: a daily mode and a weekly mode. In the daily mode,
every day uses the same program. In the
weekly mode, every day has its own program,
so it is possible have a different program for each day of the week (see Figure 48).
press ( ) (left button). To change the desired
temperature, go to the hour you want to
change by pressing (left button) and then press change (middle button). There are 3 temperature settings:
Off:
No temperature control (the appliance
is in pilot mode).
'Night Temp:
as desired temperature and the appliance will heat until this temperature is reached.
'Comfort Temp:
is set as the desired temperature and the appliance will heat until this temperature is reached.
Finally, to launch the program mode, in the main menu, set Program to ''On'', and select
the desired Program Type (Daily or Weekly) as shown in Figure 49.
The night temperature is set
The comfort temperature
Figure 49 - Day Programming Menu
Figure 48 - Setting Control Mode
DAY PROGRAMMING MENU (Menu Adjust Menu Change Program):
There are 8 menus like this. One for daily, and the others for each day (Monday, Tuesday, Wednesday, Thursday, Friday, Saturday and Sunday, see Figure 49). This day program-
ming screen consists of: Title: Daily Program. A: Selected (including ''Daily''). The select-
ed day can be changed by pressing ''Change'' (middle button).
B: Day Schedule Graphic. This bar displays the program for the whole day by showing the temperature setting for each hour of the
day. To access the day schedule graphic,
125795-01B 27
www.fmiproducts.com
OTHER FEATURES
How to lock and unlock the remote (child lock)
To unlock the remote, press the ''Unlock''
button and ''OK''.
To lock the remote, in the main screen press ''Menu'' go to the Lock option, press ''Select''
and then ''Change''. The remote will immedi­ately go into locked mode.
Automatic lock can be selected. This means
that if no button is pressed for while, the
remote automatically goes into locked mode.
How to select the temperature unit (ºC/ºF)
In the main screen, press ''Menu'' button. Se­lect ''Adjust Menu'' and then select ''Unit''. To change the temperature unit press ''Change'' button.
Page 28
OPERATION
Continued
TOUCH PAD OPERATION
This touch control has only 3 buttons for con-
trolling manually the ame of the appliance
(see Figure 50). The touch pad has:
1. Led display
2. ON/OFF button
3. UP button
4. DOWN button With this control it is possible to turn on the
re, turn off the re and control the ame level.
LED Display
ON/OFF Button
ON
OFF
UP Button
DOWN Button
Figure 50 - Touch Pad Control
SWITCHING OFF
To switch off the re, the ON/OFF button
should be pressed. After the system has emit-
ted a beep, the re switches off.
WARNING: Do not convert
heater to use different fuel type. Only use heater with fuel type specied.
Note: The touch pad includes a red LED display light. If the LED remains on, the black plug is connected upside down. Unplug, turn over, and reconnect.
SWITCHING ON
To turn the system on just press the ON/OFF button. The system will emit a beep and begin
the ignition process, which can take about
20 seconds. Once the start up process is
complete, the pilot ame is lit.
REGULATING THE FLAME LEVEL.
1. To increase the ame level, press the up button ( ). A beep and a ash of the LED indicate that the system has
accepted the order, and the ame will
increase instantly (see Figure 50).
2. To decrease the ame level, press the down button ( ). A beep and a ash of the LED indicate that the system has
accepted the order, and the ame will
decrease instantly (see Figure 50).
www.fmiproducts.com
125795-01B28
Page 29
INSPECTING BURNERS
Thermocouple
Figure 51 - Pilot (Natural)
Check pilot ame pattern and burner ame
patterns often.
PILOT FLAME PATTERN
Figure 52 shows a correct pilot ame pattern. Figure 53 shows an incorrect pilot ame pat­tern. The incorrect pilot ame is not touching
the thermocouple. This will cause the thermo-
couple to cool. When the thermocouple cools,
the heater will shut down.
If pilot ame pattern is incorrect, as shown
in Figure 53.
• turn heater off (see To Turn Off Gas to Ap­pliance, page 23
• see Troubleshooting, page 32
Note: The pilot ame on natural gas units will have a slight curve, but ame should be blue
and have no yellow or orange color.
Thermocouple
Figure 52 - Correct Pilot Flame Pattern
(Your pilot may vary from pilots shown)
Thermocouple
Figure 53 - Incorrect Pilot Flame Pattern (Your pilot may vary from pilots shown)
Ignitor Electrode
Pilot Burner
Pilot Burner
Pilot Burner
CLEANING AND
MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
CAUTION: You must keep control areas, burners and circulating air passageways of heater clean. Inspect these areas of heater before each use. Have heater inspected yearly by a quali­ed service person. Heater may need more frequent cleaning due to excessive lint from carpeting, pet hair, bedding material, etc.
WARNING: Failure to keep the primary air opening(s) of the burner(s) clean may result in sooting and property damage.
BURNER INJECTOR HOLDER AND
PILOT AIR INLET HOLE
The primary air inlet holes allow the proper amount of air to mix with the gas. This provides
a clean burning ame. Keep these holes clear of dust, dirt, lint and pet hair. Clean these air in-
let holes prior to each heating season. Blocked air holes will create soot. We recommend that you clean the unit every three months during operation and have heater inspected yearly by
a qualied service person.
We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 PSI.
Your local computer store, hardware store or
home center may carry compressed air in a
can. If using compressed air in a can, please
follow the directions on the can. If you don’t follow directions on the can, you could dam­age the pilot assembly.
1. Shut off unit, including pilot. Allow unit to
cool for at least thirty minutes.
2. Inspect burner, pilot and primary air inlet
holes on injector holder for dust and dirt
(see Figure 54, page 30).
3. Blow air through the ports/slots and holes in the burner.
125795-01B 29
www.fmiproducts.com
Page 30
CLEANING AND MAINTENANCE
Continued
4. Check injector holder located at end of burner tube again. Remove any large
particles of dust, dirt, lint or pet hair with a soft cloth or vacuum cleaner nozzle.
5. Blow air into the primary air holes on the injector holder.
6. In case any large clumps of dust have now been pushed into the burner repeat steps 3 and 4.
Clean pilot assembly also. Additional clean­ing may be needed for proper pilot operation based on use/lack of use. A yellow tip on the
pilot ame may indicate dust and dirt in the
pilot assembly. There is a small pilot air inlet
hole about from where the pilot ame comes
out of pilot assembly (see Figure 55). With
unit off, lightly blow air through air inlet hole.
You may blow through a drinking straw if compressed air is not available.
Injector Holder
LOGS
• If you remove logs for cleaning, refer to Installing Logs Embers and Lava Rock, page 18, to properly replace logs.
• Replace log(s) if broken or chipped (dime­sized or larger).
MAIN BURNER
Periodically inspect all burner ame holes with
heater running. All slotted burner flame holes
should be open with ame present. All round burner ame holes should be open with a small blue ame present. Some burner ame holes may become blocked by debris or rust, with no ame present. If so, turn off heater and let cool. Remove blockage, blocked burner ame holes will create soot.
WARNING: The injector hold­ers (air shutters) are not adjust­able. Do not move injector holders from their original positions.
Burner Tube
Primary Air Inlet Holes
Figure 54 - Injector Holder On Outlet
Burner Tube
Pilot Air Inlet Hole
Pilot Assembly
Figure 55 - Pilot Inlet Air Hole (Your pilot
may vary from pilot shown)
www.fmiproducts.com
SPECIFICATIONS
MF42INE, MF48INE, VFGT24NE, VFGT30NE, VFGT36NE,
• Rating (Variable): 28,000/38,000 Btu/Hr
• Type Gas: Natural
• Ignition: Electronic
• Manifold Pressure: 4.5" W.C.
• Inlet Gas Pressure (in. of water): Max - 10.5" W.C., Min* - 5" W.C.
*For purpose of input adjustment
MF42IPE, MF48IPE, VFGT24PE, VFGT30PE, VFGT36PE
• Rating (Variable): 31,000/39,000 Btu/Hr
• Type Gas: Propane/LP
• Ignition: Electronic
• Manifold Pressure: 8.0" W.C.
• Inlet Gas Pressure (in. of water): Max - 14" W.C., Min* - 11" W.C.
*For purpose of input adjustment
125795-01B30
Page 31
WIRING DIAGRAM
CONTROL MODULE
REMOTE CONTROL
POWER SUPPLY BOX
125795-01B 31
www.fmiproducts.com
Page 32
TROUBLESHOOTING
WARNING: Turn off heater and let cool before servicing. Only a
qualied service person should service and repair heater.
CAUTION: Never use a wire, needle or similar object to clean
ODS/pilot. This can damage ODS/pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
Either the remote or touch pad but­tons are pressed to start the burner ignition sequence and there is no function or response.
POSSIBLE CAUSE
1. Missing or weak batteries at power supply box or remote. Con­trol module may beep 10 times or may not beep at all. LCD display may show "BATTERY ERROR".
2. Unplugged power supply (battery) box
3. Touch pad not plugged in to mod­ule or plugged in incorrectly
4. Control valve wiring harness not plugged in or not in proper position
5. Remote not communicating with control module
REMEDY
1. Check batteries and replace if needed. (Batteries in the power supply box can be tested with a multimeter at the two connections at the back of the battery housing where the red and black wires are connected. Set the multimeter to
DC voltage, initiate the ignition sequence, and observe the volt-
age while the system is lighting (under load). The system will not function under 3.8 volts and bat­teries should be replaced if the voltage is under 4.0 volts.)
2. Plug power supply box to module see page 15.
3. Plug touch pad in module see
page 16, gure 19. Check to see
it is positioned as shown.
4. Check to see that the control valve wiring harness' blue connector is plugged in to the module. Check to see that it is aligned with the
mating pins. If any pins are visible,
then the connector is not in the
correct position. If this is the case, disconnect, align, and reconnect
to the module.
5. Check the display on the remote for signal bars. If the display is
blank, press any button one time
to activate the display. Watch the display for 30 seconds and ob­serve if the signal bars are shown. (The remote communicates with the module periodically. It doesn't communicate with the module continuously to conserve battery power.) If the remote is commu-
nicating with the module, signal
bars will be displayed temporarily.
If they are not displayed any, verify
the batteries are new and installed correctly. If the signal bars still do
not display, follow the Re-Pairing
instructions on page 16.
www.fmiproducts.com
125795-01B32
Page 33
OBSERVED PROBLEM
Either the remote or touch pad but­tons are pressed to start the burner ignition sequence and there is no function or response. (Continued from page 32).
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
6. LED is blinking
7. Ignitor cable is not connected
8. Ignitor cable pinched or wet
9. Broken Ignitor cable.
10. Ignitor electrode positioned wrong.
11. Ignitor electrode broken.
12. Control module sounds 2 cycles
of 3 beeps; LCD display may
show ROM ERROR
13. Control module sounds 2 cycles
of 5 beeps; LCD display may
show SUPPORT ERROR
14. Bad reception from remote
15. If LED on touch pad is continu-
ously on, the cable is connected
the wrong way.
16. The control module sounds 2 cycles of 5 beeps. The wiring assembly from the control valve is disconnected or broken.
REMEDY
6. This indicates the battery power is low. Replace the batteries in the power supply box.
7. Check the ignitor connection at both the control module and the ods pilot. Connect if loose.
8. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry.
9. Replace wire harness including ignitor cable.
10. Replace ods pilot assembly.
11. Replace ods pilot assembly.
12. Replace control module
13. Ground cable from control valve
wiring harness is not ground­ing properly. Reposition spade terminal so that it makes contact with burner chassis metal or valve body.
14. Change batteries in remote. Check reception of signal from a shorter distance. If still not work-
ing, try changing the channel in
the configuration menu. If this
does not x the problem, reset
the channel to A and follow the instructions in Re-Pairing on page
16. Replace remote and control
module as a nal action.
15. Disconnect the touch pad be-
tween the long and short cables,
turn the short cable with the touch pad over and reconnect.
16. Connect the wiring harness at the control module. Replace the valve assembly if all other cause/rem­edies fail to correct his problem.
125795-01B 33
www.fmiproducts.com
Page 34
OBSERVED PROBLEM
When ignitor button is pressed on the
remote or touch pad, the pilot sparks
but there is no ignition.
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Gas supply turned off or equip­ment shutoff valve closed
2. Air in gas lines.
3. Thermocouple circuit between the control valve and the control module is open.
4. No gas to the ods pilot
5. Depleted gas supply (propane/LP only)
6. Valve cable is disconnected or broken.
7. ODS pilot is clogged
8. Gas regulator setting is not correct
REMEDY
1. Turn on gas supply or open equip­ment shutoff valve.
2. Continue turning the burner sys­tem ON and OFF. Repeat igniting operation until air is removed.
On rst time ignitions, air in the
lines is common and it is not uncommon to repeat the ignition sequence 10 to 15 times before enough gas is at the ods pilot for it to light.
3. Check the thermocouple con­nection at the control valve and also at the control module. The thermocouple connection at the control valve should be hand tight plus 1/4 to 1/2 turn. You should not be able to loosen the thermocouple at the control valve with your hand. Check the thermocouple terminal connection
at the control module. If it is loose, remove it with needle nose pliers, using the pliers, slightly close the
terminal's opening and reinstall on to the control module.
4. While the pilot is sparking, check for gas ow at the ods pilot. If ow is present, try to light the pilot with
a long reach lighter. If it will not
light but the ame is disturbed,
air is in the line. Cycle through the ignition sequence to clear the line of air until gas is present. If no
ow is present at the gas valve,
check to see all shut off valves are open. Verify proper pressure is supplied to the valve. Exces­sive pressure can lock out the appliance's regulator. Also check to see that the wiring harness from the control valve is properly connected at the control module. The wiring harness connection
housing can be identied by it's
blue connector housing.
5. Contact local propane/LP gas company.
6. Connect valve cable correctly
7. Clean ods pilot (see Cleaning and
Maintenance , page 30) or replace
ods pilot assembly.
8. Replace gas regulator
www.fmiproducts.com
125795-01B34
Page 35
OBSERVED PROBLEM
ODS pilot lights but pilot ame goes
out before burners light.
Burner system lights from remote but not from touch pad
Burner system does not ignite the burner while the remote is in the program mode.
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Equipment shutoff valve not fully open
2. Missing or weak batteries at power supply box or remote.
3. Thermocouple circuit between the ods pilot and control module is loose or damaged.
4. Pilot ame not touching thermo­couple, which allows thermo­couple to cool, causing pilot ame
to go out. This problem could be caused by one or both of the fol­lowing: A) Low gas pressure or B)Dirty or partially clogged ODS pilot.
5. Thermocouple damaged
6. Control valve damaged.
1. Touch pad cable disconnected or broken
2. Defective touch pad
1. Program mode does not work if soft start is deactivated.
REMEDY
1. Fully open equipment shutoff valve.
2. Check batteries and replace if needed. (Batteries in the power supply box can be tested with a multimeter at the two connections at the back of the battery housing where the red and black wires are connected. Set the multimeter to
DC voltage, initiate the ignition sequence, and observe the volt-
age while the system is lighting (under load). The system will not function under 3.8 volts and bat­teries should be replaced if the voltage is under 4.0 volts.).
3. Check thermocouple terminal connection at the control module.
If it is loose, remove it with needle nose pliers, using the pliers,
slightly close the terminal's open­ing and reinstall on to the control module.
4. A) Contact local natural or pro­pane/LP gas company. B) Clean ODS pilot (see Cleaning
and Maintenance , page 30) or
replace ODS pilot assembly.
5. Replace ods pilot assembly.
6. Replace control valve
1. Connect or replace touch pad and cable.
2. Replace touch pad
1. Activate soft start in the remote.
Burner system shuts off after operating 6 seconds then sounds 5 beeps.
Low battery power in remote.
125795-01B 35
1. Short in touch pad wiring. BUT­TON ERROR is shown in remote display.
1. Batteries are weak. LOW BAT­TERY is shown in remote display.
www.fmiproducts.com
1. Replace touch pad and wiring harness.
1. Replace batteries in remote.
Page 36
OBSERVED PROBLEM
Burner system shuts off. Control module sounds 2 cycles of 3 beeps.
CONFIG. ERROR is shown in
remote display.
Burner system shuts off. Control module sounds 2 cycles of 3 beeps. EEPRON ERROR is shown in remote display.
Burner system shuts off. Control module sounds 20 beeps.
Burner system shuts off. Control module sounds 1 long beep. Remote displays TEMP ERROR.
Burner systems shuts off. Remote displays OVER TEMPERATURE.
Burner system lights or shuts off without touching the remote.
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Faulty control module
1. Remote and control module not communicating properly
2. Faulty control module
1. Loss of communication between control module and remote after 18 minutes.
1. Control module is too hot
1. The SAFETY temperature setting in the remote has shut the burner system off.
1. More than one burner system is present and operating on the same frequency.
REMEDY
1. Replace control module.
1. Follow Re-Pairing instructions on page 16 to re-pair remote to control module
2. Replace control module
1. Either the remote is too far from the burner system or the remote needs new batteries. The remote should work within 20 feet of the burner system. If it does not, re­place the batteries in the remote and battery supply box.
1. Check to see the replace size meets the minimum require­ments. Call technical service.
1. The remote includes a shut off that is preset at 40C (104F). If the remote is placed in a location that is at or above this temperature it will shut the burner system off. Placing the remote on a mantel may result in this problem. If it
occurs, relocate the remote to a
cooler location.
1. Follow the Re-Pairing section to re-pair the burner system(s). One burner system may be left on the original frequency.
www.fmiproducts.com
125795-01B36
Page 37
OBSERVED PROBLEM
Burners do not light after ODS/ pilot is lit
Delayed ignition of one or both burners
Burner backring during combustion
Yellow ame in middle burner during
burner combustion
Slight smoke or odor during initial operation
Heater produces a whistling noise when burners are lit
White powder residue forming within burner box or on adjacent walls or furniture
Moisture/condensation noticed on windows
Heater produces a clicking/ticking noise just after burners are lit or shut off
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Inlet gas pressure is too low
2. Burner orice(s) clogged
3. Mislocated crossover tube
1. Manifold pressure is too low
2. Burner orice(s) clogged
3. Mislocated crossover tube
1. Burner orice is clogged or dam­aged
2. Damaged burner
3. Gas regulator defective
1. Not enough air
2. Gas regulator defective
1. Residues from manufacturing processes and logs curing
1. Set the unit to HI by using the remote when burners are cold
2. Air in gas line
3. Air passageways on heater blocked
4. Dirty or partially clogged burner
orice(s)
1. When heated, vapors from furni­ture polish, wax, carpet cleaners,
etc. may turn into white powder residue
1. Not enough combustion/ventila­tion air
1. Metal expanding while heating or contracting while cooling
REMEDY
1. Contact local natural or propane/ LP gas company
2. Clean burner(s) (see Cleaning
and Maintenance, page 30) or replace burner orice(s)
3. Contact qualied service person
1. Contact local natural or propane/ LP gas company
2. Clean burner(s) (see Cleaning
and Maintenance, page 30) or replace burner orice(s)
3. Contact qualied service person
1. Clean burner (see Cleaning and Maintenance, page 30) or replace
burner orice
2. Replace damaged burner
3. Replace gas regulator
1. Check burner(s) for dirt and debris. If
found, clean burner(s) (see Cleaning and Maintenance, page 30)
2. Replace gas regulator
1. Problem will stop after a few hours of operation
1. Set the unit to LO by using the remote and let warm up for a minute
2. Operate burners until air is re­moved from line. Have gas line checked by local natural or pro­pane/LP gas company
3. Observe minimum installation clearances (see pages 9 through
11)
4. Clean burners (see Cleaning and
Maintenance, page 30) or replace burner orice(s)
1. Turn heater off when using furni-
ture polish, wax, carpet cleaners
or similar products
1. Refer to Air for Combustion and Ventilation requirements (page 6)
1. This is normal with most heaters.
If noise is excessive, contact qualied service person
125795-01B 37
www.fmiproducts.com
Page 38
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Fol­low the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning sup-
plies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc.,
create fumes. These fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Heater produces unwanted odors
POSSIBLE CAUSE
1. Heater burning vapors from
paint, hair spray, glues, cleaners, chemicals, new carpet, etc. (See
IMPORTANT statement above)
REMEDY
1. Open window to ventilate room. Stop using odor causing products while heater is running
Heater shuts off in use (ODS operates)
Gas odor even when control knob
is in OFF position
Gas odor during combustion
Log set cycles to pilot, but room tem-
perature drops to a lower than ideal level before log set comes back on
2. Low fuel supply (propane/LP only)
3. Gas leak. See Warning state-
ment at top of page
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See Warning state-
ment at top of page
2. Control valve or gas control defec­tive
1. Foreign matter between control valve and burner
2. Gas leak. See Warning state­ment at top of page
1. Optional Hand-held remote con­trol is too close to heater
2. Refill supply tank (propane/LP only)
3. Locate and correct all leaks (see
Checking Gas Connections, page
14)
1. Open window and/or door for ventilation
2. Contact local natural or propane/ LP gas company
3. Clean ODS/pilot (see Cleaning
and Maintenance, page 30)
1. Locate and correct all leaks (see
Checking Gas Connections, page
14)
2. Replace control valve or gas control
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks (see
Checking Gas Connections, page
14)
1. Move hand-held remote control unit farther away from the heater
www.fmiproducts.com
125795-01B38
Page 39
ACCESSORIES
Purchase these heater accessories from your local dealer. If they can not supply these
accessories, call FMI PRODUCTS, LLC at
1-866-328-4537 for referral information. You can also write to the address listed on the back page of this manual.
FIREPLACE HOOD
Black - GA6050 Antique Brass - GA6053 For all models. Helps deect heat away from
mantel or wall above replace. Fits openings
28" to 48" wide.
LAVA ROCK - GA6060
For all models. Order when additional rock is desired.
FLOOR MEDIA KIT - FM100
For all models. Includes lava rock, burner
embers, and burner cinders.
CONTROL COVER KIT - CC100
For all models. Includes control cover log
and 6 unique fall-away logs.
MAGNIFLAME ACCESORY LOG KIT
- LAMF
125795-01B 39
www.fmiproducts.com
Page 40
PARTS
1
2
4
6
7
8
9
10
11
12
24
12
13
15
15
16
17
18
19
20
21
22
14
5
3
7
23
REMOTE CONTROL MODELS
MF42INE, MF42IPE, MF48INE, MF48IPE, VFGT24NE, VFGT24PE, VFGT30NE, VFGT30PE, VFGT36NE AND VFGT36PE
www.fmiproducts.com
125795-01B40
Page 41
PARTS
REMOTE CONTROL MODELS
MF42INE, MF42IPE, MF48INE, MF48IPE, VFGT24NE, VFGT24PE, VFGT30NE, VFGT30PE, VFGT36NE AND VFGT36PE
This list contains replaceable parts used in your heater. When ordering parts, follow the instructions listed
under Replacement Parts on page 43 of this manual.
KEY
NO. PART NO. DESCRIPTION QTY.
1 125219-01 Burner MF Dual Yellow Flame • • • • • • • • • • 1 2 125213-01 Bracket Right Burner • • • • • • • • • • 1 3 125213-02 Bracket Left Burner • • • • • • • • • • 1 4 099415-28 Gas Regulator NG 1
099415-24 Gas Regulator LP 1 5 098264-02 Connector, Male 3/8 NPTF • • • • • • • • • • 1 6 125810-02 Bracket, Valve and Regulator • • • • • • • • • • 1 7 099387-08 Tube, Pilot. • • • • • • • • • • 1 8 125919-01 Kit Valve Service NG 1
125919-03 Kit Valve Service LP 1 9 125816-01 Fitting .375 Tube to .125 NPTF • • • • • • • • • • 1 10 125810-01 Leg Support • • • • • • • • • • 1 11 125247-01 Asm, Pan Burner • • • • • • • • • • 1 12 125023-01 Bracket, Front Burner • • • • • • • • • • 2 13 097384-01 Nut 10-24 Captive Washer • • • • • • • • • • 2 14 112829-02 Air Shutter • • • • • • • • • • 1 15 124933-01 Orice Holder 90 Degree Elbow • • • • • • • • • • 2 16 099056-46 Orice .051 (Pan) 1
099046-45 Orice .028 (Pan) 1 17 119321-01 Tube, Venturi • • • • • • • • • • 1 18 119795-01 Burner Gasket • • • • • • • • • • 1 19 125819-01 Bracket Caution Decal • • • • • • • • • • 1 20 125777-01 Module Control Board • • • • • • • • • • 1 21 099056-31 Orice, 0.07 (Rear) 1
099056-04 Orice, 0.1065 (Rear) 1 22 116559-03 Shutter Air 1
116559-04 Shutter Air 1 23 125780-01 Pilot NG 1
125780-02 Pilot LP 1 24 125515-01 Grate • • • • • • 1
125515-02 Grate • • • • 1
KEY
NO. PART NO. DESCRIPTION QTY.
100639-12 Decal, Caution Label • • • • • • • • • • 1
101137-02 Kit, Hardware • • • • • • • • • • 1
GA6060 Lava Rock • • • • • • • • • • 1 125070-01 Kit, Platinum Embers • • • • • • • • • • 2 125071-01 Kit, Rockwool Embers • • • • • • • • • • 2 125782-01 Plate Lighting Instructions • • • • • • • • • • 1 125775-01 Remote Control • • • • • • • • • • 1 125882-01 Manual Control Touch Pad • • • • • • • • • • 1 125882-02 Touch Pad Wire Harness • • • • • • • • • • 1 125817-02 Flex Line Regulator to Valve • • • • • • • • • • 1 125817-03 Flex Line Valve to Pan Burner • • • • • • • • • • 1 125817-04 Flex Line Valve to Rear Burner • • • • • • • • • • 1 125781-01 Harness Pilot Ignitor • • • • • • • • • • 1
PARTS AVAILABLE NOT SHOWN
VFGT24NE
VFGT30NE
VFGT24PE
VFGT30PE
VFGT36NE
VFGT36PE
MF42INE
MF42IPE
MF48INE
MF48IPE
125795-01B 41
www.fmiproducts.com
Page 42
PARTS
LOG SET FOR MODELS
MF42INE, MF42IPE, MF48INE, MF48IPE, VFGT24NE, VFGT24PE, VFGT30NE, VFGT30PE, VFGT36NE AND VFGT36PE
This list contains replaceable parts used in your heater. When ordering parts, follow the
instructions listed under Replacement Parts on page 43 of this manual.
7
8
4
2
5
3
6
1
9
MF42I(N,P)E:
LMF36-SC
VFGT24(N,P)E:
GT24
KEY
NO. PART NO. Log Id. # PART NO. Log Id. # PART NO. Log Id. # DESCRIPTION QTY.
1 125948-01 D-061 125573-01 D-019 125591-01 D-027 Log, Front Right 1 2 125948-02 D-060 125573-02 D-018 125591-02 D-026 Log, Back Left 1 3 125948-03 D-059 125573-03 D-017 125591-03 D-025 Log, Front Left 1 4 125573-04 D-020 125573-04 D-020 125573-04 D-020 Log, Charred 1 5 125948-04 D-063 125573-05 D-021 125591-04 D-028 Log, Middle Split 1 6 125573-06 D-022 125573-06 D-022 125573-06 D-022 Log, Right Split Crossover 1 7 125573-07 D-024 125573-07 D-024 125573-07 D-024 Log, Front Top 1 8 125948-05 D-062 125573-08 D-023 125591-06 D-029 Log, Back Top 1 9 125538-01 None 125538-01 None 125538-01 None Log Switch 1
MF42I(N,P)E:
LMF42-SC
VFGT30(N,P)E:
GT30
MF48I(N,P)E:
LMF48-SC
VFGT36(N,P)E:
GT36
Each log includes a reference number. The rst number indicates the order it is placed on the burner assembly. The next two numbers indicate the set size.
www.fmiproducts.com
125795-01B42
Page 43
REPLACEMENT PARTS
Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
Contact authorized dealers of this product.
If they can’t supply original replacement
part(s), call FMI PRODUCTS, LLC at
1-866-328-4537.
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• heater will not produce specied heat
• propane/LP gas supply may be low
You may feel your gas pressure is too low. If
so, contact your local propane/LP or natural
gas supplier.
When calling, have ready:
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• purchase date Usually, we will ask you to return the part to
the factory.
TECHNICAL SERVICE
You may have further questions about
installation, operation or troubleshooting. If so, contact FMI PRODUCTS, LLC at
1-866-328-4537. When calling please have your model and serial numbers of your heater ready.
You can also visit our web site at www.fmiproducts.com.
125795-01B 43
www.fmiproducts.com
Page 44
WARRANTY
KEEP THIS WARRANTY
Model (
located on product or identication tag
Serial No. (
located on product or identication tag
Date Purchased __________________________
Keep receipt for warranty verication.
FMI PRODUCTS, LLC LIMITED WARRANTIES
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allow-
ance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement
parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs, unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of
the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
Factory Reconditioned Products
Terms Common to All Warranties
) _____________________________
) __________________________
New Products
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
125795-01 Rev. B 01/12
Loading...