tenance can cause injury
or property damage. Refer
to this manual for correct
installation and operational procedures. For assis-
tance or additional infor-
mation consult a qualied
installer, service agency
or the gas supplier.
WARNING: This ap-
pliance is for installation
only in a solid-fuel burning
masonry or UL127 fac-
tory-built fireplace or in
a listed ventless rebox
enclosure. It is design-certied for these installations
in accordance with ANSI
Z21.11.2. Exception: Do not
install this appliance in a
factory-built replace that
includes instructions stat-
ing it has not been tested
or should not be used with
unvented gas logs.
WARNING: This is an
unvented gas-red heater. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 5
of this manual.
This appliance may be in-
stalled in an aftermarket,*
perma n ently locat e d,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
www.fmiproducts.com
125500-01A2
Page 3
SAFETY
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the State of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the replace may not
be working properly. Get fresh air at once!
Have replace serviced. Some people are
more affected by carbon monoxide than oth-
ers. These include pregnant women, people
with heart or lung disease or anemia, those
under the inuence of alcohol and those at
high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odor-making agent is added to these gases. The odor
helps you detect a gas leak. However, the odor
added to the gas can fade. Gas may be present
even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Heater base assembly becomes
very hot when running heater.
Keep children and adults away
from hot surface to avoid burns
or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the room
with heater.
You must operate this heater
with a replace screen in place.
Make sure replace screen is
closed before running heater.
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
1. This appliance is only for use with type of
gas indicated on rating plate. This appli-
ance is not convertible for use with other
gases.
125500-01A 3
www.fmiproducts.com
Page 4
SAFETY
Continued
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP
units only).
3. To prevent performance problems, the
use of a propane/LP tank of less than
100 lbs. capacity is not recommended
(propane/LP units only).
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor ’s phone. Follow the gas
supplier’s instructions
• if you cannot reach your gas supplier,
call the re department
5. This heater shall not be installed in a
bedroom or bathroom unless installed as
a vented appliance (see Installing Damper
Clamp Accessory for Vented Operation,
page 11). This gas log set may not be
installed as a vented appliance in a bed-
room or bathroom in the Commonwealth
of Massachusetts.
6. Do not burn solid-fuel in a masonry or
UL127 factory-built replace in which a
vent-free room heater is installed.
7. Before installing in a solid fuel burning replace, the chimney ue and rebox must
be cleaned of soot, creosote, ashes and
loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue and rebox for damage. If damaged,
repair ue before operating heater.
8.
If replace has glass doors, never operate
this heater with glass doors closed. If you
operate heater with doors closed, heat
buildup inside replace will cause glass to
burst. Make sure there are no obstructions
across openings of replace.
9. This log heater is designed to be smoke-
less. If logs ever appear to smoke, turn off
heater and call a qualied service person.
Note: During initial operation, slight smok-
ing could occur due to log curing and
heater burning manufacturing residues.
10. To prevent the creation of soot, follow
the instructions in Cleaning and Maintenance, page 20.
www.fmiproducts.com
11. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls or furniture.
12. This heater needs fresh, outside air ven-
tilation to run properly. This heater has an
Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the
heater if not enough fresh air is available.
See Air for Combustion and Ventilation,
page 5. If heater keeps shutting off, see
Troubleshooting, page 22.
13. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
14. Do not use this heater to cook food or burn
paper or other objects.
15. Do not use heater if any part has been ex-
posed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part
of the control system and any gas control
which has been under water.
16. Do not operate heater if any log is broken.
Do not operate heater if a log is chipped
(dime-sized or larger).
17. Turn heater off and let cool before servic-
ing. Only a qualied service person should
service and repair heater.
18. Operating heater above elevations of
4,500 feet could cause pilot outage.
19. Provide adequate clearances around air
openings.
PRODUCT
IDENTIFICATION
Grate
Heater Base
Control Knob
Figure 1 - Product Idetication
125500-01A4
Page 5
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel
Gas Code ANSI Z223/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Note: Where listed vented decorative logs are
required, thermostat models are not permitted.
UNPACkING
CAUTION: Do not remove the
data plates from the grate assembly. The data plates contain
important warranty and safety
information.
1. Remove log and heater base assembly
from cartons.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by
realistic, dancing yellow ames. This heater
is designed for vent-free operation with ue
dampe r clo sed. It has b een tested and
approved to ANSI Z21.11.2 standard for
unvented heaters. State and local codes
in some areas prohibit the use of vent-free
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
Note: Do not pick up heater base assem-
bly by burners. This could damage heater.
Always handle base assembly by grate.
2. Remove all protective packaging applied
to log and heater for shipment.
3. Check heater for any shipping damage. If
heater is damaged call FMI PRODUCTS,
LLC at 1-866-328-4537 for replacement
parts before returning to dealer.
heaters. Non-thermostat models may also
be operated as a vented decorative (ANSI
Z21.60) product by opening ue damper.
SAFETY PILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable lo-
cal codes. Read the following instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
125500-01A 5
www.fmiproducts.com
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors to
keep the cold air out and the warm air in. During heating months, home owners want their
homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Page 6
AIR FOR COMBUSTION AND VENTILATION
Continued
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the
house to operate. You must provide adequate
fresh air for these appliances. This will insure
proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code. ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 5 through 7 will
help you classify your space and provide
adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6x10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 7.
If your home does not meet all of the three
criteria above, proceed to Determining
Fresh-Air Flow For Heater Location.
Conned Space and Unconned Space
The National Fuel Gas Code ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
-11
kg per pa-sec-m2) or
www.fmiproducts.com
1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed
in that space and an unconned space as a
space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
DETERMINING FRESH-AIR FLOW
FOR FIREPLACE LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
replace plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x
20 = 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free replace _________ Btu/HrGas water heater* _________ Btu/Hr
Gas furnace _________ Btu/Hr
Vented gas heater _________ Btu/Hr
Gas replace logs _________ Btu/Hr
Other gas appliances* + _________ Btu/Hr
Total = _________Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
125500-01A6
Page 7
Or
Remove
Door into
Adjoining
Room,
Option
3
Ve ntilation Grills
Into Adjoining Room,
Option 2
Ve ntilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
Outlet
Air
V e ntilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
V e ntilated
Crawl Space
T o
Crawl
Space
T o Attic
AIR FOR COMBUSTION AND VENTILATION
Continued
Example:
Gas water heater _________ Btu/HrVent-free replace + _________Btu/Hr
Total = _________Btu/Hr
40,000
31,500
71,500
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/Hr
used.
_______ Btu/Hr (maximum the space can
support)
_______ Btu/Hr (actual amount of Btu/Hr
used)
Example: 51,200 Btu/Hr (maxim um th e
space can support)
71,500 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a conned space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You
must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining
room or add ventilation grills between rooms.
See Ventilation Air From Inside Building,
page 7.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 7.
C. Install a lower Btu/Hr replace, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
125500-01A 7
www.fmiproducts.com
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
Figure 2 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
Page 8
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualied service person must install heater.
Follow all local codes.
NOTICE: State or local codes may
only allow operation of this appliance in a vented conguration.
Check your state or local codes.
WARNING: Before installing
in a solid fuel burning replace,
the chimney ue and rebox
must be cleaned of soot, creosote, ashes and loose paint by a
qualied chimney cleaner. Creosote will ignite if highly heated. A
dirty chimney ue may create and
distribute soot within the house.
Inspect chimney ue and rebox
for damage. If damaged, repair
ue before operating heater.
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of replace. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney ue damper.
WARNING: Never install the
heater
•
in a bedroom or bathroom unless installed as a vented appliance (see page 11)
• in a recreational vehicle
•
where curtains, furniture, cloth-
ing or other ammable objects
are less than 36" from front and
42" from top of heater; for side
clearances see Figure 4, page 9
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next
to heater. Installing heater next
to vinyl or cloth wall coverings or
operating heater where impurities
(such as, but not limited to, tobacco smoke, aromatic candles,
cleaning uids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See Air for Combustion and Ventilation, page 5.
CHECK GAS TYPE
Use only the correct gas type (natural or
propane/LP) for your unit. If your gas sup-
ply is not correct, do not install heater. Call
dealer where you bought heater for proper
type heater.
WARNING: This appliance is
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rating plate. Field conversion is not
permitted.
www.fmiproducts.com
125500-01A8
Page 9
INSTALLATION
Continued
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the
minimum clearances. If you can,
provide greater clearances from
oor, ceiling and adjoining wall.
Minimum Fireplace Clearance to
Combustible Materials
Side Wall 16", Ceiling 42", Front 36"
Minimum Firebox Size
Height 17", Depth 14", Front Width 24",
Rear Width 20" (measured at 14" depth).
Car efully follow instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured replace or certied vent-free rebox.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from side of replace cabinet
to any combustible material and wall
should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3 1/2" from the wall. This com-
bustible material must be 4" from the side
of the replace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less
than 42".
Example
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open. If
running heater with damper open,
noncombustible material above replace opening is not needed. Go to
Installing Damper Clamp Accessory
for Vented Operation, page 11.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel, page 10. If not using a mantel, follow
the information below.
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2 inch thick. With sheet
metal, you must have noncombustible material behind it. Noncombustible material
must extend at least 8" up (for all models).
If noncombustible material is less than 12",
you must install the replace hood accessory
(for all models). See Figure 5 on page 10 for
minimum clearances.
Noncombustible
Material Distance
(A)
12" or moreNoncombustible material
Between 8" and
12"
Less than 8"Noncombustible material
Requirements for Safe
Installation
okay.
Install replace hood
accessory (GA6050 or
GA6053 see Accesso-
ries, page 30).
must be extended to at
least 8". See Between
8" and 12", above. If you
cannot extend material,
you must operate heater
with ue damper open.
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
125500-01A 9
www.fmiproducts.com
Page 10
Minimum
Noncombustible
Material
Minimum
Noncombustible
Material Height
Distances to
Underside of
Mantel
Top of
Fireplace
Opening
Underside of
Mantel Shelf
Mantel Shelf
8"
(A)
8" 14" 17" 20"
All minimum
distances are
in inches
Log Set
All Models
2 1/2"
6"
8"
10"
INSTALLATION
Heat Resistant
Material
(A)
Continued
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it.
Noncombustible material must extend at least
8" up. See Figure 5, page 9, and Figure 6 for
minimum clearances.
IMPORTANT: If you cannot meet these mini-
mum clearances, you must operate heater
with chimney ue damper open. Go to Install-
ing Damper Clamp Accessory for Vented
Operation, page 11.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
You must meet the minimum clearances
between the mantel shelf and the top of the
replace opening as shown in Figure 6.
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 10,
are not met, you must have a hood. When
using a hood there are still certain minimum
mantel clearances required. Follow minimum
clearances shown in Figure 7 page 11 when
using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
Figure 6 - Minimum Mantel Clearances
Without Using Hood
www.fmiproducts.com
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on oor level, you
must maintain the minimum distance of
14" to combustibles (see Figure 8 page
11).
B. If combustible materials are less than 14"
to replace, you must install appliance at
least 5" above combustible ooring (see
Figure 9 page 11).
125500-01A10
Page 11
INSTALLATION
14"
Min.
Combustible
Material
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18" 20"
2½"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050 or
GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
Continued
Figure 7 - Minimum Mantel Clearances
When Using Hood
1. The replace does not meet the clearance to combustibles requirements for
vent-free operation.
2. State or local codes do not permit ventfree operation.
3. You prefer vented operation.
If reasons number 1 or 2 apply to you, you
must permanently open chimney ue damper.
You must install the damper clamp accessory
(to order, see Accessories, page 31). This
will insure vented operation (see Figure 10).
The damper clamp will keep damper open.
Installation instructions are included with
clamp accessory.
See chart below for minimum permanent ue
opening you must provide. Attach damper
clamp so the minimum permanent ue opening will be maintained at all times.
Figure 8 - Minimum Fireplace Clearances
Figure 9 - Minimum Fireplace Clearances
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, appliance must be installed only in a solid-fuel
burning fireplace with a working flue and
constructed of noncombustible material.
You may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
data plates attached to the heater
base assembly. The data plates
contain important warranty and
safety information.
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak.
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access to
heater control panel. This will insure adequate air ow and guard
against sooting and controls being damaged. Raise replace oor
with noncombustible material.
Make sure material is secure.
Continued
gas hose to gas regulator of heater (see
Figure 11).
IMPORTANT: Hold gas regulator with
wrench when connecting exible gas hose.
2. Lo cate masonry screws in hardware
package.
3. Position heater base assembly in replace.
4. Place log in proper position on heater base
(see Installing Logs, page 15).
5. Center heater base and logs front-to-front
and side-to-side in replace.
6. Carefull y remove log with out movi ng
heater base.
7. Mark screw locations through holes in
mounting brackets (see Figure 12). If
installing in a brick-bottom replace, mark
screw locations in mortar joint of bricks.
8. Remove heater base from replace.
9. Drill holes at marked locations using 3/16"
drill bit.
10. Attach base assembly to replace oor
using two masonry screws (in hardware
package) (see Figure 12).
Fitting
Heater Gas
Regulator
CAUTION: Do not pick up
heater base assembly by the
burner. This could damage heater. Only handle base assembly
by grates.
IMPORTANT: Make sure heater burners are
level. If heater is not level, heater will not
work properly.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose (if allowed by
local codes)
•
sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16" drill bit
• athead screwdriver
1. Apply pipe joint sealant lightly to male
threads of the tting to be threaded into
gas regulator. Connect approved exible
www.fmiproducts.com
Flexible Gas Hose
(if allowed by local codes)
Figure 11 - Attaching Flexible Gas Hose
to Heater Gas Regulator
Masonry
Screw
Mounting
Bracket
Figure 11 - Attaching Base Assembly to
Fireplace Floor
125500-01A12
Page 13
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 1/2" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
WARNING: A qualified
service person must connect
heater to gas supply. Follow
all local codes.
CAUTION: Never connect
propane/LP heater directly to the
propane/LP supply. Propane/LP
heaters require an external regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
WARNING: For natural gas
units, never connect heater to
private (non-utility) gas wells.
This gas is commonly known
as wellhead gas.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
* A equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the optional equipment
shutoff valve from your dealer.
For propane/LP gas, the installer must supply
an external regulator. An external regulator
will reduce incoming gas pressure. You must
reduce incoming gas pressure to between 11"
and 14" of water. If you do not reduce incoming
gas pressure, heater regulator damage could
occur. Install external regulator with vent pointing down as shown in Figure 13. Pointing vent
down protects it from freezing rain or sleet.
CAUTION: Use only new, black
iron or steel pipe. Internally-tinned
copper tubing may be used in
certain areas. Check your local
codes. Use pipe of 1/2" diameter or
greater to allow proper gas volume
to heater. If pipe is too small, undue
loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 14 page 14).
IMPORTANT: Install equipment shutoff valve
in an accessible location. Main gas valve is
for turning on or shutting off gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
Propane/LP
Supply Tank
External
Regulator
with Vent
Pointing
Down
Figure 13 - External Regulator With Vent
125500-01A 13
www.fmiproducts.com
Pointing Down
Page 14
INSTALLATION
Continued
We recommend that you install sediment
trap in supply line as shown in Figure 14.
Locate sediment trap where it is within reach
for cleaning. Install in piping system between
fuel supply and heater. Locate sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contaminants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
CAUTION: Avoid damage to
regulator. Hold gas regulator with
wrench when connecting it to gas
piping and/or ttings.
Natural
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Propane/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure
Figure 14 - Gas Connection
* Purchase the optional equipment shutoff
valve from your dealer.
** Min. inlet pressure for purpose of input
adjustment.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
Equipment Shutoff Valve
With 1/8" NPT Tap*
3" Min.
Tee Cap Pipe
Joint Nipple
Sediment Trap
Gas
Regulator
Approved
Flexible
Gas Hose (if
allowed by
local codes)
CAUTION: For propane/LP
units, make sure external regulator has been installed between
propane/LP supply and heater.
See guidelines under Connecting to Gas Supply, page 13.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping.
Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping system.
Apply a commercial leak detection solution
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
ttings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 15).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
Equipment
Shutoff Valve
Open
WARNING: Never use an
open ame to check for a leak.
Apply a commercial leak detection solution to all joints.
Bubbles forming show a leak.
Correct all leaks at once.
www.fmiproducts.com
Closed
Figure 15 - Equipment Shutoff Valve
125500-01A14
Page 15
INSTALLATION
Continued
3. Check all joints from gas meter (natural
gas) or propane/LP supply to equipment
shutoff valve (see Figure 16 or 17). Apply
a commercial leak detection solution to all
joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Propane/LP
Supply Tank
Figure 16 - Checking Gas Joints
(Propane/LP Gas Only)
Equipment Shutoff Valve
Gas
Meter
Figure 17 - Checking Gas Joints
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure
15, page 14).
2. Open main gas valve located on or near
gas meter for natural gas or open propane/LP supply tank valve.
3. Make sure control knob of heater is in the
OFF position.
4. Check all joints from gas meter (natural
gas) or propane/LP supply to equipment
shutoff valve (see Figure 16 or 17). Apply
a commercial leak detection solution to all
joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operation page 18).
Check all other internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to
Appliance, page 19).
125500-01A 15
Equipment Shutoff Valve
Control Valve
Location
Control Valve Location
(Natural Gas Only)
www.fmiproducts.com
INSTALLING LOGS
WARNING: Failure to position
the parts in accordance with these
diagrams or failure to use only
parts specically approved with
this heater may result in property
damage or personal injury.
CAUTION: After installa-
tion and periodically thereafter,
check to ensure that no ame
comes in contact with any log.
With the heater set to High, check
to see if ames contact any log.
If so, reposition log according to
the log installation instructions
in this manual. Flames contacting log will create soot.
MODELS LVS18-VO AND LVS24-VO
It is very important to install these logs exactly
as instructed. Do not modify logs. Only use
logs supplied with heater.
1. Place grate into square holes on heater
base as shown in Figure 18.
2. Place front log on burner so that it sits
between grate ngers and burner (see
Figure 18).
The Front Log Should Be
Centered Left To Right.
Front Log
Grate
Heater Base
Figure 18 - Installing Grate and Logs
Page 16
INSTALLATION
Continued
3. Place rear log on heater base behind the
metal burner. The bottom of the rear log
has recess areas on the left and right side
for the base to set into. Pull the rear log
forward until it touches the front log (see
Figure 18, page 15).
4. Place the left crossover log as shown
in Figure 19. The bottom of the log is
marked with a “L” for left. Match round
peg on left side of top of rear log with
round hole in bottom of left crossover.
Match square peg on left side of top of
front log with square hole in bottom of left
crossover log.
Left Crossover
Log
Center
Crossover
Log
Figure 20 - Installing Center Crossover Log
Right
Crossover
Log
Figure 19 - Installing Left Crossover Log
5. Place the center crossover log as shown in
Figure 20. The bottom of the log is marked
with a “C” for center. Match square peg
on center of rear log with square hole in
bottom of center crossover. Match round
peg on center of front log with round hole
in bottom of center crossover log.
6. Place the right crossover log as shown in
Figure 21. The bottom of the log is marked
with a “R” for right. Match square peg on
right side of rear log with square hole in
bottom of right crossover. Match round
peg on right side of front log with round
hole in bottom of right crossover log.
7. Add lava rock around base of heater if
desired. Do not place any lava rock on
logs or burner.
www.fmiproducts.com
Figure 21 - Installing Left Crossover Log
125500-01A16
Page 17
INSTALLATION
Continued
MODELS LVS18-PP AND LVS24-PP
It is very important to install these logs exactly
as instructed. Do not modify logs. Only use
logs supplied with heater.
1. Place grate into square holes on heater
base as shown in Figure 22.
2. Place front log on burner so that it sits
between grate ngers and burner (see
Figure 22).
3. Place rear log so that locating projections
t inside mating holes on back of front
log. The log should rest behind the metal
burner (see Figure 22).
4. Add lava rock around base of heater if
desired. Do not place lava rock on log
or burner.
5. During operation, the logs are positioned
correctly when the ame is between the
front and rear logs, but does not touch
any surface on either of the two logs. If
the ame does touch a log, turn the log
set off and reposition the logs in position
as described in steps 1 thru 3.
Rear Log
Front Log
Grate
Heater Base
Figure 22 - Installing Grate and Logs
125500-01A 17
www.fmiproducts.com
Page 18
FOR YOUR SAFETY
READ BEFORE LIGHTING
OPERATION
LIGHTING
INSTRUCTIONS
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must
be ligh ted by hand. W hen lightin g
the pilot, follow these instructions
exactly.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the oor because some
gas is heavier than air and will settle
on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the re department.
C. Use only your hand to push in or turn
the gas control knob. Never use tools.
If the knob will not push in or turn by
hand, don’t try to repair it, call a qualied service technician or gas supplier.
Force or attempted repair may result in
a re or explosion.
D.
Do not use this appliance if any part has
been under water. Immediately call a
qualied service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
WARNING:
• If replace has glass doors,
never operate this heater with
glass doors closed. If you op-
erate heater with doors closed,
heat buildup inside replace
will cause glass to burst. Make
sure there are no obstructions
across openings of replace.
• You must operate this heater
with a fireplace screen in
place. Make sure fireplace
screen is closed before running heater.
NOTICE: During initial operation
of new heater, burning logs will
give off a paper-burning smell.
Orange ame will also be present. Open damper or window to
vent smell. This will only last a
few hours.
Note: Home owners generally prefer to operate their heater with the chimney damper
closed. This will put all the heat into the room.
However, there may be times you will desire
the full ames of the HI heat setting but will
nd the heat output excessive. You can open
the chimney damper (if you have one) fully or
partially to release some of the heat.
WARNING: Damper handle
will be hot if heater has been
running.
www.fmiproducts.com
125500-01A18
Page 19
PILOT
OFF
LO
HI
OPERATION
Continued
1. STOP! Read the safety information in
column 1.
2. Make sure equipment shutoff valve is fully
open.
3. Press in and turn control knob clockwise
to the OFF position.
4. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the
oor. If you smell gas, STOP! Follow “B”
in the safety information, page 18. If you
don’t smell gas, go to the next step.
5. Press in control knob and turn counterclock-
wise to the PILOT position. The
ignitor will spark once. Keep control knob
pressed in for 5 seconds. If control knob does
not pop up when released, contact a qualied
service person or gas supplier for repairs.
Note: You may be running this heater for
the rst time after hooking up to gas supply. If so, the control knob may need to be
pressed in for 30 seconds or more. This will
allow air to bleed from the gas system.
6. Turn control knob clockwise to
OFF position. Press in control knob and
turn counterclockwise to PILOT
position. This will light pilot. Pilot is attached to rear of burner. If needed, repeat
this process until pilot lights.
Note: If pilot does not stay lit, contact a
qualied service person or gas supplier
for repairs. Until repairs are made, light
pilot with match. To light pilot with match,
see Manual Lighting Procedure.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds,
release control knob.
Note: If pilot goes out, repeat steps 3
through 7.
• If control knob does not pop out when
released, contact a qualified service
person or gas supplier for repairs.
8. Slightly press and turn control knob counterclockwise to desired heating
level. The burner should light. Set control
knob to HI or LO.
Control Knob
Figure 23 - Control Knob and Ignitor
Button Location
125500-01A 19
www.fmiproducts.com
WARNING: Do not operate
heater between PILOT and HIGH
positions.
9. To leave pilot lit and shut off burners only,
turn control knob clockwise to the
PILOT position.
Thermocouple
Ignitor Electrode
Pilot Burner
Figure 24 - Pilot
VARIABLE CONTROL
OPERATION
The variable control valve can be set to high
or low, by simply turning the control knob
until that setting is attained. Even the lowest setting provides realistic, dancing yellow
ames. Selecting higher settings produces
greater heat output. This results in increased
heating comfort.
CAUTION: Do not try to ad-
just heating levels by using the
equipment shutoff valve.
TO TURN OFF GAS
TO APPLIANCE
1. Press in and turn control knob clockwise
2. Close equipment shutoff valve (see Figure
1. Follow steps 1 through 5 under Lighting
2. De press control knob a nd light pilot
3. Keep control knob pressed in for 30 sec-
to the OFF position.
15, page 14).
MANUAL LIGHTING
PROCEDURE
Instructions, page 18.
with match.
onds after lighting pilot. After 30 seconds,
release control knob. Now follow step 8
under Lighting Instructions, page 18.
Page 20
INSPECTING BURNERS
Check pilot ame pattern and burner ame
patterns often.
PILOT FLAME PATTERN
Figure 25 shows a correct pilot ame pattern.
Figure 26 shows an incorrect pilot ame pattern. The incorrect pilot ame is not touching the
thermocouple. This will cause the thermocouple
to cool. When the thermocouple cools, the
heater will shut down.
If pilot ame pattern is incorrect, as shown
in Figure 26
• turn heater off (see To Turn Off Gas to Appliance, page 19)
• see Troubleshooting, page 22
Note: The pilot ame on natural gas units will
have a slight curve, but ame should be blue
and have no yellow or orange color.
Pilot Burner
Thermocouple
Figure 25 - Correct Pilot Flame Pattern
Thermocouple
Pilot Burner
Figure 26 - Incorrect Pilot Flame Pattern
BURNER PRIMARY AIR HOLES
Air is drawn into the burner through the holes
in the tting at the entrance to the burner.
These holes may become blocked with dust
or lint. Periodically inspect these holes for any
blockage and clean as necessary. Blocked air
holes will create soot.
MAIN BURNER
Periodically inspect all burner ame holes with
the heater running. All slotted burner ame
holes should be open with yellow ame present. All round burner ame holes should be
open with a small blue ame present. Some
burner ame holes may become blocked by debris or rust, with no ame present. If so, turn off
heater and let cool. Remove blockage, blocked
burner ame holes will create soot.
CLEANING AND MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
CAUTION: You must keep
control areas, burner and circulating air passageways of heater
clean. Inspect these areas of
heater before each use. Have
heater inspected yearly by a
qualied service person. Heater
may need more frequent cleaning due to excessive lint from
carpeting, bedding material, pet
hair, etc.
www.fmiproducts.com
WARNING: Failure to keep
the primary air opening(s) of
the burner(s) clean may result in
sooting and property damage.
ODS/PILOT AND BURNER
Use a vacuum cleaner or small, soft bristled
brush to clean.
BURNER ORIFICE HOLDER AND
PILOT AIR INLET HOLE
The primary air inlet holes allow the proper
amount of air to mix with the gas. This provides a clean burning ame. Keep these holes
clear of dust, dirt and lint. Clean these air inlet
holes prior to each heating season. Blocked
air holes will create soot. We recommend that
you clean the unit every three months during
operation and have heater inspected yearly
by a qualied service person.
125500-01A20
Page 21
CLEANING AND MAINTENANCE
Continued
We also recommend that you keep the burner
tube and pilot assembly clean and free of dust
and dirt. To clean these parts we recommend
using compressed air no greater than 30 PSI.
Your local computer store, hardware store or
home center may carry compressed air in a
can. If using compressed air in a can, please
follow the directions on the can. If you don’t
follow directions on the can, you could dam-
age the pilot assembly.
1. Shut off unit, including pilot. Allow unit to
cool for at least thirty minutes.
2. Inspect burner, pilot and primary air inlet
holes on orice holder for dust and dirt
(see Figure 27).
3. Blow air through the ports/slots and holes
in the burner.
4. Check orice holder located at the end of
the burner tube again. Remove any large
particles of dust, dirt, lint or pet hair with
a soft cloth or vacuum cleaner nozzle.
Burner Tube
Orice Holder (May
Be Brass or Aluminum
Depending on Model)
5. Blow air into the primary air holes on the
orice holder.
6. In case any large clumps of dust have now
been pushed into the burner repeat steps
3 and 4.
Clean pilot assembly also. A yellow tip on the
pilot ame indicates dust and dirt in the pilot
assembly. There is a small pilot air inlet hole
about 2" from where the pilot ame comes out
of the pilot assembly (see Figure 28). With the
unit off, lightly blow air through the air inlet
hole. You may blow through a drinking straw
if compressed air is not available.
Pilot
Assembly
Pilot Air
Inlet Hole
Figure 28 - Pilot Inlet Air Hole
Primary Air
Inlet Holes
Figure 27 - Orice Holder On Outlet
125500-01A 21
Burner Tube
www.fmiproducts.com
Page 22
TROUBLESHOOTING
WARNING: Turn off and unplug heater and let cool before servicing.
Only a qualied service person should service and repair heater.
CAUTION: Never use a wire, needle or similar object to clean
ODS/pilot. This can damage ODS/pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
When control knob is pressed
in and turned to PILOT, there
is not spark at ODS/pilot
POSSIBLE CAUSE
1. Ignitor electrode not connected to ignitor cable
2. Ignitor cable pinched or
wet
3. Broken ignitor cable
4. Bad piezo ignitor
5. Ignitor electrode broken
6. Ignitor electrode positioned
wrong
REMEDY
1. Reconnect ignitor cable
2. Free ignitor cable if pinched
by any metal or tubing. Keep
ignitor cable dry
3. Replace valve
4. Replace valve
5. Replace pilot
6. Reposition ignitor electrode
When control knob is pressed
in and turned to PILOT, there
is spark at ODS/pilot but no
ignition
1. Gas supply turned off or
equipmen t shutoff valve
closed
2. Control knob not in PILOT
position
3. Control knob not pressed in
while in PILOT position
4. Air in gas lines when in-
stalled
5. Depleted gas supply (propane/LP only)
6. ODS/pilot is clogged
7. Gas regula tor settin g is
not correct
1. Turn on gas supply or open
equipment shutoff valve
2. Turn control knob to PILOT
position
3. Press in control knob while
in PILOT position
4. Continue holding down control knob. Repeat igniting operation until air is removed
5. Contact local propane/LP
gas company
6. Clean ODS/pilot (see Clean-ing and Maintenance, page
20) or replac e ODS /pilot
assembly
7. Replace gas regulator
www.fmiproducts.com
125500-01A22
Page 23
OBSERVED PROBLEM
ODS/pilot lights but flame
goes out when control knob
is released
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Con t r ol k n ob no t ful l y
pressed in
2. Control knob not pressed in
long enough
3. Equipment shutoff valve not
fully open
4. Pilot flame not touching
thermocouple, which allows thermocouple to cool,
causing pilot ame to go
out. This problem could be
caused by one or both of
the following:
A) Low gas pressure
B) Dirty or partially clogged
ODS/pilot
5. Thermocouple connection
loose at control valve
6. Thermocouple damaged
7. Control valve damaged
REMEDY
1. Press in control knob fully
2. After ODS/pilot lights, keep
control knob pressed in 30
seconds
3. Fully open equipment shutoff valve
4. A) Contact local natural or
propane/LP gas company
B) Clean ODS/pilot (see
Cleaning and Maintenance,
page 20) or replace ODS/
pilot assembly
5. Hand tighten until snug,
then tighten 1/4 turn more
6. Replace pilot assembly
7. Replace control valve
Burner does not light after
ODS/pilot is lit
Delayed ignition of burner
Burner backring during combustion
1. Burner orice clogged
2. Inlet gas pressure is too
low
1. Manifold pressure is too
low
2. Burner orice clogged
1. Burner orice is clogged or
damaged
2. Damaged burner
3. Gas regulator defective
1. Clean burner (see Cleaning
and Maintenance, page 20)
or replace burner orice
2. Contact loca l natural or
propane/LP gas company
1. Contact loca l natural or
propane/LP gas company
2. Clean burner (see Cleaning
and Maintenance, page 20)
or replace burner orice
1. Clean burner (see Cleaning
and Maintenance, page 20)
or replace burner orice
2. Replace damaged burner
3. Replace gas regulator
125500-01A 23
www.fmiproducts.com
Page 24
OBSERVED PROBLEM
Slight smoke or odor during
initial operation
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Not enough air
2. Gas regulator defective
3. Residues from manufacturing processes and log
curing
REMEDY
1. Check burner for dirt and
de b ris . If fo u nd, cl e an
burner (see Cleaning and
Maintenance, page 20)
2. Replace gas regulator
3. Problem will stop after a few
hours of operation
Moisture/condensation no-
ticed on windows
Heater produces a whistling
noise when burner is lit
White powder residue forming
within burner box or on adjacent walls or furniture
Heater produces a clicking/
ticking noise just after burner
is lit or shut off
1. Not enough combustion/
ventilation air
1. Turning control knob to HI
positio n whe n burner is
cold
2. Air in gas line
3. Air passageways on heater
blocked
4. Dirty or partially clogged
burner orice
1. When heated, vapors from
furniture polish, wax, carpet
cleaners, etc. may turn into
a white powder residue
1. Met al exp a ndi ng whi l e
heating or contracting while
cooling
1. Refer to Air for Combustion and Ventilation require-
ments (page 5)
1. Turn control knob to LO
position and let warm up
for a minute
2. Operate burner until air is
removed from line. Have
gas line checked by local
natural or propane/LP gas
company
3. Observe minimum installat i on clea r anc e s (s ee
page 8)
4. Clean burner (see Cleaning
and Maintenance, page 20)
or replace burner orice
1. Turn heater off when using furniture polish, wax,
carpet cleaners or similar
products
1. This is normal with most
heaters. If noise is excessive, contact qualied service person
www.fmiproducts.com
125500-01A24
Page 25
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint
remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These
fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Heater produces unwanted
odors
POSSIBLE CAUSE
1. Heater burning vapors from
paint , hair spra y, glue s,
cleaners, chemicals, new
carpet, etc. (See IMPOR-
TANT statement above)
2. Low fuel supply (propane/
LP only)
3. Gas leak. See Warning
statement above
REMEDY
1.
Open window and ventilate
room. Stop using odor
causing products while
heater is running
2. Rell supply tank (propane/
LP only)
3. Locate and correct all leaks
(see Checking Gas Con-
nections, page 14)
Heater shuts off in use (ODS
operates)
Gas odor even when control
knob is in OFF position
Gas odor during combustion
125500-01A 25
1. No t eno ug h fresh air i s
available
2. Low line pressure
3. O D S / p i l o t i s p a rtially
clogged
1. Gas leak. See Warning
statement above
2. Control valve defective
1. Forei gn matter b etween
control valve and burner
2. Gas leak. See Warning
statement above
www.fmiproducts.com
1. Open window and/or door
for ventilation
2. Contact loca l natural or
propane/LP gas company
3. C lean O D S / pilot ( s e e
Cleaning and Maintenance,
page 20
1. Locate and correct all leaks
(see Checking Gas Con-nections, page 14)
2. Replace control valve
1. Take apart gas tubing and
remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Con-nections, page 14)
Page 26
PARTS
15
3
14
16
11
10
4
2
12
8
5
14
13
7
9
1
15
15
VARIABLE MANUALLY-CONTROLLED BURNER SYSTEMS VS1824NM AND
VS1824PM
www.fmiproducts.com
125500-01A26
Page 27
This list contains replaceable parts used in your heater. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 30 of this manual.
099415-24Gas Regulator, LP•1
8122142-01Manual Valve with Ignitor, NG•1
122142-02Manual Valve with Ignitor, LP•1
9122141-01Manual Valve Outlet Tube• •1
10122146-02Natural Gas Plate•1
11107186-05Orice 0.099•1
107186-06Orice 0.057•1
12098354-01Control Knob• •1
13099387-08Pilot Tube• •1
14M11084-38HWH AB 8-18 x 0.38 Screw• •1
15M11084-26HWH AB 10-16 x 0.38 Screw• •8
16098303-01HWH AB 6-20 x 0.25 Screw• •2
• Inlet Gas Pressure (in. of water):
Maximum 14" W.C., Minimum 11"* W.C.
• Shipping Weight: 27 lbs.
Models VS1824NM
• Rating (Variable): 16,000/26,000 Btu/Hr
• Gas Type: Propane/LP
• Ignition: Piezo
• Manifold Pressure: 8.0" W.C.
• Inlet Gas Pressure (in. of water):
Maximum 14" W.C., Minimum 11"* W.C.
• Shipping Weight: 27 lbs.
TECHNICAL SERVICE
You may have further questions about installation, operation or troubleshooting. If so, contact
FMI PRODUCTS, LLC at 1-866-328-4537.
When calling please have your model and
serial numbers of your heater ready.
You can also visit our web site atwww.fmiproducts.com.
REPLACEMENT PARTS
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
Contact authorized dealers of this product.
If they can’t supply original replacement
pa r t(s ), ca l l FMI PR ODU CTS , LLC at
1-866-328-4537.
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• heater will not produce specied heat
• propane/LP gas supply may be low
You may feel your gas pressure is too low. If
so, contact your local natural or propane/LP
gas supplier.
When calling, have ready:
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• type of gas used (propane/LP or natural
gas)
• purchase date
Usually, we will ask you to return the part to
the factory.
www.fmiproducts.com
125500-01A30
Page 31
ACCESSORIES
Purchase these replace accessories from
your local dealer. If they can not supply these
accessories, either contact your nearest
Parts Central or call FMI PRODUCTS, LLC
at 1-866-328-4537 for information. You can
also write to the address listed on the back
page of this manual.
FIREPLACE HOOD
Black - GA6050
Antique Brass - GA6053
For all models. Helps deect heat away from
mantel or wall above replace. Fits openings
28" to 48" wide.
DAMPER CLAMP - GA6080
For variably-controlled models. Perma-
nently opens chimney ue damper for vented
operation.
FLOOR MEDIA KIT - FM100
For all models. Includes lava rock, burner
embers, and burner cinders
CONTROL COVER KIT - CC100
For all models. Includes control cover log
and 6 unique fall-away logs.
LAVA ROCK - GA6060
For all models. Order when additional rock
is desired.
125500-01A 31
www.fmiproducts.com
Page 32
WARRANTY
kEEP THIS WARRANTY
Model (
located on product or identication tag
Serial No. (
located on product or identication tag
Date Purchased __________________________
Keep receipt for warranty verication.
FMI PRODUCTS, LLC LIMITED WARRANTIES
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects
in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date
of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be
free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this
warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only
when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allowance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by
FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI
PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement
parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs,
unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of
the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty
excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all
implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on
new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not
be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
New Products
Factory Reconditioned Products
Terms Common to All Warranties
) _____________________________
) __________________________
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
125500-01
Rev. A
07/10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.