tenance can cause injury
or property damage. Refer
to this manual for correct
installation and operational procedures. For assis-
tance or additional infor-
mation consult a qualied
installer, service agency
or the gas supplier.
WARNING: This ap-
pliance is for installation
only in a solid-fuel burning masonry or UL127
factory-built fireplace or
in a listed ventless rebox
enclosure. It is design-certied for these installations
in accordance with ANSI
Z21.11.2. Exception: Do not
install this appliance in a
factory-built replace that
includes instructions stat-
ing it has not been tested
or should not be used with
unvented gas logs.
WARNING: This is an
unvented gas-red heater. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 6
of this manual.
This appliance may be in-
stalled in an aftermarket,*
perma n ently locat e d,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
www.fmiproducts.com
125001-01B2
SAFETy
Continued
WARNING: This product
con tains an d/or gen erates
chemicals known to the State
of California to cause cancer or
birth defects or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the replace may not
be working properly. Get fresh air at once!
Have replace serviced. Some people are
more affected by carbon monoxide than oth-
ers. These include pregnant women, people
with heart or lung disease or anemia, those
under the inuence of alcohol and those at
high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odormaking agent is added to these gases. The
odor helps you detect a gas leak. However,
the odor added to the gas can fade. Gas may
be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Heater base assembly becomes
very hot when running heater.
Keep children and adults away
from hot surface to avoid burns
or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the room
with heater.
You must operate this heater
with a replace screen in place.
Make sure replace screen is
closed before running heater.
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
125001-01B3
www.fmiproducts.com
SAFETy
Continued
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors (propane/LP units
only).
3. To prevent performance problems, the use
of a propane/LP tank of less than 100 lbs.
capacity is not recommended (propane/
LP units only).
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup-
plier’s instructions
• if you cannot reach your gas supplier,
call the re department
5. This heater shall not be installed in a
bedroom or bathroom.
6. Do not burn solid-fuel in a masonry or
UL127 factory-built replace in which a
vent-free room heater is installed.
7. Before installing in a solid fuel burning replace, the chimney ue and rebox must
be cleaned of soot, creosote, ashes and
loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue and rebox for damage. If damaged,
repair ue before operating heater.
8. If replace has glass doors, never operate
this heater with glass doors closed. If you
operate heater with doors closed, heat
buildup inside replace will cause glass to
burst. Make sure there are no obstructions
across openings of replace.
9. This log heater is designed to be smoke-
less. If logs ever appear to smoke, turn off
heater and call a qualied service person.
Note: During initial operation, slight smoking could occur due to log curing and
heater burning manufacturing residues.
10. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance,
page 19.
11. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If
heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls or furniture.
12. This heater needs fresh, outside air ven-
tilation to run properly. This heater has an
Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the
heater if not enough fresh air is available.
See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see
Troubleshooting, page 20.
13. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
14. Do not use this heater to cook food or burn
paper or other objects.
15. Do not use heater if any part has been ex-
posed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part
of the control system and any gas control
which has been under water.
16. Do not operate heater if any log is broken.
Do not operate heater if a log is chipped
(dime-sized or larger).
17. Turn heater off and let cool before servic-
ing. Only a qualied service person should
service and repair heater.
18. Operating heater above elevations of
4,500 feet could cause pilot outage.
19. Provide adequate clearances around air
openings.
20. Solid fuels shall not be burned in a replace where a decorative appliance is
installed.
21. Installation and the provisions for combustion and ventilation air must conform
with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
22. When installing as a vented appliance in a
manufactured home or mobile home, the
installation must conform with the Manu-
factured Home Construction and Safety
Standard, Title 24 CFR, Part 3280.
www.fmiproducts.com
125001-01B4
PRODUCT IDENTIFICATION
Control Knob
Figure 1 - Yellow Flame Vent-Free Gas Log Heater
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel
Gas Code ANSI Z223/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Log Set
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
UNPACkING
Note: Do not pick up heater base assem-
CAUTION: Do not remove the
data plates from the grate assembly. The data plates contain
important warranty and safety
information.
1. Remove logs and heater base assembly
from carton.
bly by burners. This could damage heater.
Always handle base assembly by grate.
2. Remove all protective packaging applied
to logs and heater for shipment.
3. Check heater for any shipping damage. If
heater is damaged call FMI PRODUCTS,
LLC at 1-866-328-4537 for replacement
parts before returning to dealer.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by
realistic, dancing yellow ames. This heater
is designed for vent-free operation with ue
damper closed. It has been tested and approved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some
areas prohibit the use of vent-free heaters.
125001-01B5
www.fmiproducts.com
SAFETY PILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
AIR FOR COMbUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable lo-
cal codes. Read the following instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors
to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code. ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
www.fmiproducts.com
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6x10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three
criteria above, proceed to Determining
Fresh-Air Flow For Heater Location.
Conned Space and Unconned Space
The National Fuel Gas Code ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed
in that space and an unconned space as a
space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
-11
kg per pa-sec-m2) or
DETERMINING FRESH-AIR FLOW
FOR FIREPLACE LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will
install replace plus any adjoining rooms with
doorless passageways or ventilation grills
between the rooms.
125001-01B6
Or
Remove
Door into
Adjoining
Room,
Option
3
Ve ntilation Grills
Into Adjoining Room,
Option 2
Ve ntilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
AIR FOR COMbUSTION AND VENTILATION
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x
20 = 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free replace __________ Btu/HrGas water heater* __________ Btu/Hr
Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr
Gas replace logs __________ Btu/Hr
Other gas appliances* + __________ Btu/Hr
Total = __________ Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/HrVent-free replace + __________ Btu/Hr
Total = __________ Btu/Hr
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
_______
support)
_______ Btu/Hr (actual amount of Btu/Hr
used)
Example: 51,200 Btu/ Hr (ma ximum the
71,500 Btu/Hr (actual amount of
The space in the example is a conned space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You
must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining
125001-01B7
Btu/Hr (maximum the space can
space can support)
Btu/Hr used)
40,000
31,500
71,500
Continued
room or add ventilation grills between rooms.
See Ventilation Air From Inside Building.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options 1
and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI Z223.1/
NFPA 54 Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Figure 2 - Ventilation Air from Inside Building
www.fmiproducts.com
Outlet
Air
V e ntilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
V e ntilated
Crawl Space
T o
Crawl
Space
T o Attic
AIR FOR COMbUSTION AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
vice person must install heater.
Follow all local codes.
WARNING: A qualied ser-
NOTICE: State or local codes may
only allow operation of this appliance in a vented conguration.
Check your state or local codes.
WARNING: Before installing
in a solid fuel burning replace,
the chimney ue and rebox
must be cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner.
Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within
the house. Inspect chimney ue
and rebox for damage. If damaged, repair ue before operating heater.
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of replace. If not, drafting may cause
pilot outage or sooting. Use a
heat-resistant sealant. Do not
seal chimney ue damper.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing or other ammable
objects are less than 36" from
front or 42" from top of heater.
For side clearances see Figure
4, page 9
• in high trafc areas
• in windy or drafty areas
www.fmiproducts.com
125001-01B8
INSTALLATION
Continued
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See Air for Combustion and Ventilation, page 6.
CHECK GAS TYPE
Use only the correct gas type (natural or propane/LP) for your unit. If your gas supply is not
correct, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rating plate. Field conversion is not
permitted.
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the
minimum clearances. If you
can, provide greater clearances
from oor, ceiling and adjoining
wall.
LOG SIZING REQUIREMENTS
Minimum Firebox Size
Height 17", Depth 13.5", Front Width 28",
Rear Width* 20.5"
*Measured at 13.5" Depth
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured replace or certied vent-free rebox.
MINIMUM CLEARANCES FOR SIDE
COMBUSTIBLE MATERIAL, SIDE WALL
AND CEILING
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3 1/2" from the wall. This com-
bustible material must be 4" from the side
of the replace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less
than 42".
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open.
If running heater with damper
open, noncombustible material
above replace opening is not
needed. Go to Installing Damper
Clamp Accessory for Vented
Operation, page 11.
Example
MINIMUM FIREPLACE CLEARANCE
TO COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42", Front 36"
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
125001-01B9
www.fmiproducts.com
*
Minimum
Noncombustible
Material
Minimum
Noncombustible
Material Height
Distances to
Underside of
Mantel
To p of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
12"
(A)
18" 20" 22" 24"
All
minimum
distances
are in
inches
2
1
/2"
6"
8"
10"
INSTALLATION
Heat Resistant
Material
(A)
Continued
MINIMUM NONCOMBUSTIBLE
MATERIAL CLEARANCES
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the information below.
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material behind it. Noncombustible material must extend
at least 12" up (for all models). See Figure 5
for minimum clearances.
Noncombustible
Material Distance (A)
12" or moreNoncombustible mate-
Between 8"
and 12"
Less than 8"Noncombustible material
Requirements for Safe
Installation
rial OK.
24" Models: Install re-
place hood accessory
(GA6050 or GA6053, see
Accessories, page 26).
18" Model: Noncombustible material OK.
must be extended to at
least 8". See Between
8" and 12", above. If you
cannot extend material,
you must operate heater
with ue damper open and
damper clamp installed.
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it.
Noncombustible material must extend at least
12" up. See Figures 5 and 6 and Figure 7 on
page 11 for minimum clearances.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
www.fmiproducts.com
Figure 6 - Minimum Mantel Clearances
Without Using Hood
125001-01B10
INSTALLATION
14"
Min.
Combustible
Material
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
Continued
NOTICE: Surface temperatures
of adjacent walls and mantels become hot during operation. Walls
and mantels above the rebox
may become hot to the touch.
If installed properly, these temperatures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• raise the mantel to an accept-
able height
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 7).
B. If combustible materials are less than 14"
to the replace, you must install appliance
at least 5" above the combustible ooring
(see Figure 8).
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, appliance must be installed only in a solid-fuel
burning replace with a working ue and constructed of noncombustible material.
For Massachusetts Residents Only: Installation of this gas log set as a vented appliance
in the Commonwealth of Massachusetts requires the damper be permanently removed
or welded in the fully open position.
If your heater is a manually-controlled model,
you may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The replace does not meet the clearance
to combustibles requirements for ventfree operation.
2. State or local codes do not permit ventfree operation.
3. You prefer vented operation.
If reasons number 1 or 2 above apply to you,
you must permanently open chimney ue
damper. You must install the damper clamp
accessory (to order, see Accessories, page
26). This will insure vented operation (see Fig-
ure 9,). The damper clamp will keep damper
open. Installation instructions are included
with clamp accessory.
Damper
Clamp
Damper
Damper
Clamp
Figure 7 - Minimum Fireplace Clearances
Figure 8 - Minimum Fireplace Clearances
125001-01B11
If Installed at Floor Level
Above Combustible Flooring
www.fmiproducts.com
Damper
Masonry Fireplace
Figure 9 - Attaching Damper Clamp
Manufactured Fireplace
Damper
INSTALLATION
Continued
See chart below for minimum permanent ue
opening you must provide. Attach damper
clamp so the minimum permanent ue opening will be maintained at all times.
data plates attached to the heater
base assembly. The data plates
contain important warranty and
safety information.
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak.
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access
to heater control panel. This
will insure adequate air ow
and guard against sooting and
controls being damaged. Raise
replace oor with noncombustible material. Make sure material
is secure.
CAUTION: Do not pick up
heater base assembly by the
burner. This could damage
heater. Only handle base assembly by grates.
IMPORTANT: Make sure heater burners are
level. If heater is not level, heater will not
work properly.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose (not provided)
(if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16" drill bit
• athead screwdriver
1. Apply pipe joint sealant lightly to male
threads of tting to be threaded into gas
regulator. Connect approved exible gas
hose to gas regulator of heater (see Figure 10).
IMPORTANT: Hold gas regulator with
wrench when connecting exible gas hose.
2. Lo cate masonry screws in hardware
package.
3. Position heater base assembly in re-
place.
4. Place logs in their proper position on heater
base (see Installing Logs, page 16).
5. Center heater base and logs front-to-front
and side-to-side in replace.
6. Carefully remove logs without moving
heater base.
Fitting
Heater Gas
Regulator
Flexible Gas Hose
(if allowed by local codes)
Figure 10 - Attaching Flexible Gas Hose
to Heater Gas Regulator
www.fmiproducts.com
125001-01B12
INSTALLATION
Continued
7. Mark screw locations through holes in
mounting brackets (see Figure 11). If
installing in a brick-bottom replace, mark
screw locations in mortar joint of bricks.
8. Remove heater base from replace.
9. Drill holes at marked locations using 3/16"
drill bit.
10. Attach base assembly to replace oor
using two masonry screws (in hardware
package) (see Figure 11).
Masonry
Screw
Mounting
Bracket
Figure 11 - Attaching Base Assembly to
Fireplace Floor
CONNECTING TO GAS SUPPLY
WARNING: This appliance
requires a 1/2" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
WARNING: A qualied service
person must connect heater to gas
supply. Follow all local codes.
CAUTION: Never connect
propane/LP heater directly to the
propane/LP supply. Propane/LP
heaters require an external regulator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
WARNING: For natural gas
units, never connect heater to
private (non-utility) gas wells.
This gas is commonly known
as wellhead gas.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
* A equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the optional equipment
shutoff valve from your dealer.
For propane/LP gas, installer must supply
an external regulator. External regulator will
reduce incoming gas pressure. You must
reduce incoming gas pressure to between
11" and 14" of water. If you do not reduce
incoming gas pressure, heater regulator damage could occur. Install external regulator with
vent pointing down as shown in Figure 12.
Pointing vent down protects it from freezing
rain or sleet.
Propane/LP
Supply Tank
External
Regulator
with Vent
Pointing
Down
Figure 12 - External Regulator With Vent
125001-01B13
www.fmiproducts.com
Pointing Down
INSTALLATION
Continued
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 13).
IMPORTANT: Install equipment shutoff valve
in an accessible location. Main gas valve is for
turning on or shutting off gas to appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
Natural
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Propane/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure
Figure 13 - Gas Connection
* Purchase optional equipment shutoff valve
from your dealer.
** Min. inlet pressure for purpose of input
adjustment.
Equipment Shutoff Valve
With 1/8" NPT Tap*
3" Min.
Tee Cap Pipe
Joint Nipple
Sediment Trap
Gas
Regulator
Approved
Flexible
Gas Hose (if
allowed by
local codes)
We recommend that you install sediment trap
in supply line as shown in Figure 13. Locate
sediment trap where it is within reach for
cleaning. Install in piping system between
fuel supply and heater. Locate sediment
trap where trapped matter is not likely to
freeze. A sediment trap traps moisture and
contaminants. This keeps them from going
into heater controls. If sediment trap is not
installed or is installed wrong, heater may
not run properly.
CAUTION: Avoid damage to
regulator. Hold gas regulator
with wrench when connecting it
to gas piping and/or ttings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections , internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open ame to check for a leak.
Apply a commercial leak detection solution to all joints.
Bubbles forming show a leak.
Correct all leaks at once.
CAUTION: For propane/LP
units, make sure external regulator has been installed between
propane/LP supply and heater.
See guidelines under Connect-ing to Gas Supply, page 13.
www.fmiproducts.com
125001-01B14
INSTALLATION
Continued
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equipment shutoff valve from gas supply piping.
Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping system. Apply a commercial leak detection
solution to all joints. Bubbles forming show
a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
ttings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 14).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
3. Check all joints from gas meter (natural
gas) or propane/LP supply to equipment
shutoff valve (see Figure 15 or 16). Apply
a commercial leak detection solution to all
joints. Bubbles forming show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 14).
2. Open main gas valve located on or near
gas meter for natural gas or open propane/LP supply tank valve.
3. Make sure control knob of heater is in the
OFF position.
4. Check all joints from gas meter (natural
gas) or propane/LP supply to equipment
shutoff valve (see Figure 15 or 16). Apply
a commercial leak detection solution to all
joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operation, page 17.
Check all other internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to
Appliance, page 18.
Equipment
Shutoff Valve
Figure 14 - Equipment Shutoff Valve
Propane/LP
Supply Tank
Figure 15 - Checking Gas Joints
Gas
Meter
Figure 16 - Checking Gas Joints
Equipment Shutoff Valve
(Propane/LP Gas Only)
Equipment Shutoff Valve
Control Valve Location
(Natural Gas Only)
Open
Closed
Control Valve
Location
125001-01B15
www.fmiproducts.com
INSTALLATION
Continued
INSTALLING LOGS
WARNING: Failure to position the parts in accordance
with these diagrams or failure
to use only parts specically
approved with this heater may
result in property damage or
personal injury.
CAUTION: After installa-
tion and periodically thereafter,
check to ensure that no ame
comes in contact with any log.
With the heater set to High, check
to see if ames contact any log. If
so, reposition logs according to
the log installation instructions
in this manual. Flames contacting logs will create soot.
It is very important to install these logs exactly
as instructed. Do not modify logs. Only use
logs supplied with heater.
1. Place rear log (#1) onto base. Holes in
bottom of log must seat over pins on base
as shown in Figure 17.
2. Place middle log (#2) onto base. Holes in
bottom of log must seat over pins on base
as shown in Figure 17.
3. Place front log (#3) onto grate as shown
in Figure 18.
4. Place left top log (#4) as shown in Figure
19. Match square peg on top of rear log
(#1) with square hole on bottom of left top
log (#4). Match round peg on top of middle
log (#2) with round hole on bottom of left
top log (#4).
5. Place right top log (#5) as shown in Figure
19. Match square peg on top of rear log
(#1) with square hole on bottom of right
top log (#5). Match round peg on top of
front log (#3) with round hole on bottom
of right top log (#5).
Front Log
Grate
Middle Log
Rear Log
Pin for
Hole in
Bottom
of Log
Burner
Figure 17 - Installing Rear and Middle
Logs
www.fmiproducts.com
Figure 18 - Installing Front Log
Left Top
Log
Round
Peg on
Middle
Log
Figure 19 - Installing Left and Right Logs
Square Peg
on Rear Log
125001-01B16
Right
Top
Log
Round
Peg on
Front Log
FOR YOUR SAFETY
READ BEFORE LIGHTING
OPERATION
LIGHTING
INSTRUCTIONS
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must
be ligh ted by hand. W hen lightin g
the pilot, follow these instructions
exactly.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the oor because some
gas is heavier than air and will settle
on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the re department.
C. Use only your hand to push in or turn
the gas control knob. Never use tools.
If the knob will not push in or turn by
hand, don’t try to repair it, call a qualied service technician or gas supplier.
Force or attempted repair may result in
a re or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call
a qualied service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
WARNING
• If replace has glass doors,
never operate this heater with
glass doors closed. If you op-
erate heater with doors closed,
heat buildup inside replace
will cause glass to burst. Make
sure there are no obstructions
across openings of replace.
• You must operate this heater
with a replace screen in place.
Make sure replace screen is
closed before running heater.
NOTICE: During initial operation
of new heater, burning logs will
give off a paper-burning smell.
Orange ame will also be present. Open damper or window to
vent smell. This will only last a
few hours.
Note: Home owners generally prefer to operate their heater with chimney damper closed.
This will put all of the heat into room. However,
there may be times you will desire full ames
of HI heat setting but will nd heat output
excessive. You can open chimney damper
(if you have one) fully or partially to release
some heat.
WARNING: Damper handle
will be hot if heater has been
running.
1. STOP! Read the saf ety inform ation,
column 1.
2. Make sure equipment shutoff valve is fully
open.
3. Press in and turn control knob clockwise
to the OFF position.
4. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the
oor. If you smell gas, STOP! Follow “B”
in the safety information, column 1. If you
don’t smell gas, go to the next step.
125001-01B17
www.fmiproducts.com
OPERATION
PILOT
OFF
LO
HI
Continued
5. Press in control knob and turn counter-
clockwise to the PILOT position
(see Figure 20). The ignitor will spark
once. Keep control knob pressed in for 5
seconds. If control knob does not pop up
when released, contact a qualied service
person or gas supplier for repairs.
Note: You may be running this heater for
the rst time after hooking up to gas supply. If so, the control knob may need to be
pressed in for 30 seconds or more. This will
allow air to bleed from the gas system.
6. Turn control knob clockwise to
OFF position. Press in control knob and
turn counterclockwise to PILOT
position. This will light pilot. Pilot is attached to rear of burner. If needed, repeat
this process until pilot lights.
Note: If pilot does not stay lit, contact a
qualied service person or gas supplier
for repairs. Until repairs are made, light
pilot with match. To light pilot with match,
see Manual Lighting Procedure.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds,
release control knob.
Note: If pilot goes out, repeat steps 3
through 7.
Control Knob
Figure 20 - Control Knob and Ignitor
Button Location
• If control knob does not pop out when
released, contact a qualified service
person or gas supplier for repairs.
8. Slightly press and turn control knob counterclockwise to desired heating
level. The burner should light. Set control
knob to HI or LO.
WARNING: Do not operate
heater between PILOT and HIGH
positions.
9. To leave pilot lit and shut off burners only,
turn control knob clockwise to the
PILOT position.
CAUTION: Do not try to ad-
just heating levels by using the
equipment shutoff valve.
TO TURN OFF GAS
TO APPLIANCE
1. Turn control knob clockwise to OFF
position.
2. Close equipment shutoff valve (see Figure
14, page 15).
MANUAL LIGHTING
PROCEDURE
1. Follow steps 1 through 5 under Lighting
Instructions beginning on page 17.
2. Press control knob and light pilot with
match.
3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds,
release control knob. Now follow step 8
under Lighting Instructions, above.
INSPECTING bURNERS
Check pilot ame pattern and burner ame
patterns often.
PILOT FLAME PATTERN
Figure 21 shows a correct pilot ame pattern.
Figure 22 shows an incorrect pilot ame pattern. Incorrect pilot ame is not touching thermocouple. This will cause the thermocouple
to cool. When thermocouple cools, heater
will shut down.
If pilot ame pattern is incorrect, as shown
in Figure 22
• turn heater off (see To Turn Off Gas to
Appliance, above
• see Troubleshooting, page 20
www.fmiproducts.com
Pilot Burner
Thermocouple
Figure 21 - Correct Pilot Flame Pattern
Thermocouple
Pilot Burner
Figure 22 - Incorrect Pilot Flame Pattern
125001-01B18
INSPECTING bURNERS
Continued
Note: Pilot ame on natural gas units will have
a slight curve, but ame should be blue and
have no yellow or orange color.
BURNER PRIMARY AIR HOLES
Air is drawn into burner through holes in tting at entrance to burner. These holes may
become blocked with dust or lint. Periodically
inspect these holes for any blockage and
clean as necessary. Blocked air holes will
create soot.
MAIN BURNER
Periodically inspect all burner ame holes
with heater running. All slotted burner ame
holes should be open with yellow ame present. All round burner ame holes should be
open with a small blue ame present. Some
burner ame holes may become blocked by
debris or rust, with no ame present. If so,
turn off heater and let cool. Remove blockage,
blocked burner ame holes will create soot.
CLEANING AND MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
CAUTION: You must keep control areas, burner and circulating
air passageways of heater clean.
Inspect these areas of heater
before each use. Have heater
inspected yearly by a qualied
service person. Heater may need
more frequent cleaning due to
excessive lint from carpeting,
bedding material, pet hair, etc.
WARNING: Failure to keep
the primary air opening(s) of
the burner(s) clean may result in
sooting and property damage.
Once every year a qualied agency or certied
chimney sweep should examine and clean the
venting system of replace.
ODS/PILOT AND BURNER
Use a vacuum cleaner or small, soft bristled
brush to clean.
BURNER ORIFICE HOLDER AND
PILOT AIR INLET HOLE
The primary air inlet holes allow the proper
amount of air to mix with the gas. This provides a clean burning ame. Keep these holes
clear of dust, dirt and lint. Clean these air inlet
holes prior to each heating season. Blocked
air holes will create soot. We recommend that
you clean the unit every three months during
operation and have heater inspected yearly
by a qualied service person.
125001-01B19
www.fmiproducts.com
We also recommend that you keep burner tube
and pilot assembly clean and free of dust and
dirt. To clean these parts we recommend using
compressed air no greater than 30 PSI. Your
local computer store, hardware store or home
center may carry compressed air in a can. If
using compressed air in a can, please follow
directions on can. If you don’t follow directions
on can, you could damage pilot assembly.
1. Shut off unit, including pilot. Allow unit to
cool for at least thirty minutes.
2. Inspect burner, pilot and primary air inlet
holes on orice holder for dust and dirt
(see Figure 23).
3. Blow air through ports/slots and holes in
burner.
4. Check orice holder located at end of
burner tube again. Remove any large
particles of dust, dirt, lint or pet hair with
a soft cloth or vacuum cleaner nozzle.
Orice Holder (May Be Brass or
Aluminum Depending on Model)
Burner Tube
Primary Air Inlet
Holes (Shape of
Holes May Vary
by Model)
Figure 23 - Orice Holder On Outlet
Burner Tube
Pilot
Assembly
Pilot Air Inlet Hole
Figure 24 - Pilot Inlet Air Hole
CLEANING AND MAINTENANCE
Continued
5. Blow air into primary air holes on orice
holder.
6. In case any large clumps of dust have now
been pushed into burner, repeat steps 3
and 4.
Clean pilot assembly also. A yellow tip on pilot
ame indicates dust and dirt in pilot assembly.
There is a small pilot air inlet hole about 2"
from where pilot ame comes out of pilot assembly (see Figure 24, page 19). With unit off,
lightly blow air through air inlet hole. You may
blow through a drinking straw if compressed
air is not available.
LOGS
• If you remove logs for cleaning, refer to Installing Logs, page 16, to properly replace logs.
• Replace log(s) if broken or chipped (dimesized or larger).
BURNER PRIMARY AIR HOLES
Air is drawn into burner through the 8 holes
in brass tting at entrance to burner. These
holes may become blocked with dust or lint.
Periodically inspect these holes for any blockage and clean as necessary. Blocked air holes
will create soot.
TROUbLESHOOTING
WARNING: Turn off and unplug heater and let cool before servicing.
Only a qualied service person should service and repair heater.
CAUTION: Never use a wire, needle or similar object to clean
ODS/pilot. This can damage ODS/pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
When control knob is pressed
in and turned to PILOT, there
is not spark at ODS/pilot
POSSIBLE CAUSE
1. Ignitor electrode not connected to ignitor cable
2. Ignitor cable pinched or
wet
3. Broken ignitor cable
4. Bad piezo ignitor
5. Ignitor electrode broken
6. Ignitor electrode positioned
wrong
REMEDY
1. Reconnect ignitor cable
2. Free ignitor cable if pinched
by a ny meta l or tubing.
Keep ignitor cable dry
3. Replace valve
4. Replace valve
5. Replace valve
6. Replace valve
When control knob is pressed
in and turned to PILOT, there
is spark at ODS/pilot but no
ignition
1. Gas supply turned off or
equipmen t shutoff valve
closed
2. Control knob not in PILOT
position
3. Control knob not pressed in
while in PILOT position
4. Air in gas lines when in-
stalled
5. Depleted gas supply (propane/LP only)
6. ODS/pilot is clogged
7. Gas regulator setting is not
correct
www.fmiproducts.com
1. Turn on gas supply or open
equipment shutoff valve
2. Turn control knob to PILOT
position
3. Press in control knob while
in PILOT position
4. Continue holding down control knob. Repeat igniting operation until air is removed
5. Contact local propane/LP
gas company
6. C lean O D S / pilot ( s e e
Cleaning and Maintenance,
page 19) or replace ODS/
pilot assembly
7. Replace gas regulator
125001-01B20
OBSERVED PROBLEM
ODS/pilot lights but flame
goes out when control knob
is released
TROUbLESHOOTING
Continued
POSSIBLE CAUSE
1. Con t r ol k n ob no t ful l y
pressed in
2. Control knob not pressed in
long enough
3. Equipment shutoff valve not
fully open
4. Pilot flame not touching
thermocouple, which allows thermocouple to cool,
causing pilot ame to go
out. This problem could be
caused by one or both of
the following:
A) Low gas pressure
B) Dirty or partially clogged
ODS/pilot
5. Thermocouple connection
loose at control valve
6. Thermocouple damaged
7. Control valve damaged
REMEDY
1. Press in control knob fully
2. After ODS/pilot lights, keep
control knob pressed in 30
seconds
3. Fully open equipment shutoff valve
4. A) Contact local natural or
propane/LP gas company
B) Clean ODS/pilot (see
Cleaning and Maintenance,
page 19) or replace ODS/
pilot assembly
5. Hand tighten until snug,
then tighten 1/4 turn more
6. Replace pilot assembly
7. Replace control valve
Burner does not light after
ODS/pilot is lit
Delayed ignition of burner
Burner backring during combustion
1. Burner orice clogged
2. Inlet gas pressure is too
low
1. Manifold pressure is too
low
2. Burner orice clogged
1. Burner orice is clogged or
damaged
2. Damaged burner
3. Gas regulator defective
1. Clean burner (see Cleaning
and Maintenance, page 19)
or replace burner orice
2. Contact loca l natural or
propane/LP gas company
1. Contact loca l natural or
propane/LP gas company
2. Clean burner (see Cleaning
and Maintenance, page 19)
or replace burner orice
1. Clean burner (see Cleaning
and Maintenance, page 19)
or replace burner orice
2. Replace damaged burner
3. Replace gas regulator
125001-01B21
www.fmiproducts.com
OBSERVED PROBLEM
Slight smoke or odor during
initial operation
TROUbLESHOOTING
Continued
POSSIBLE CAUSE
1. Not enough air
2. Gas regulator defective
3. Residues from manufacturing processes and logs
curing
REMEDY
1. Check burner for dirt and
de b ris . If fo u nd, cl e an
burner (see Cleaning and
Maintenance, page 19)
2. Replace gas regulator
3. Problem will stop after a few
hours of operation
Moisture/condensation no-
ticed on windows
Heater produces a whistling
noise when burner is lit
White powder residue forming
within burner box or on adjacent walls or furniture
Heater produces a clicking/
ticking noise just after burner
is lit or shut off
1. Not enough combustion/
ventilation air
1. Turning control knob to HI
positio n whe n burner is
cold
2. Air in gas line
3. Air passageways on heater
blocked
4. Dirty or partially clogged
burner orice
1. When heated, vapors from
furniture polish, wax, carpet
cleaners, etc. may turn into
a white powder residue
1. Met al exp a ndi ng whi l e
heating or contracting while
cooling
1. Refer to Air for Combustion and Ventilation requirements (page 6)
1. Turn control knob to LO
position and let warm up
for a minute
2. Operate burner until air is
removed from line. Have
gas line checked by local
natural or propane/LP gas
company
3. Observe minimum installat i on clea r anc e s (s ee
page 9)
4. Clean burner (see Cleaning
and Maintenance, page 19)
or replace burner orice
1. Turn heater off when using furniture polish, wax,
carpet cleaners or similar
products
1. This is normal with most
heaters. If noise is excessive, contact qualied service person
www.fmiproducts.com
125001-01B22
TROUbLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint
remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These
fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Heater produces unwanted
odors
Heater shuts off in use (ODS
operates)
Gas odor even when control
knob is in OFF position
Gas odor during combustion
POSSIBLE CAUSE
1. Heater burning vapors from
paint , hair spra y, glue s,
cleaners, chemicals, new
carpet, etc. (See IMPOR-
TANT statement above)
2. Low fuel supply (propane/
LP only)
3. Gas leak. See Warning
statement above
1. No t eno ug h fresh air i s
available
2. Low line pressure
3. O D S / p i l o t i s p a rtially
clogged
1. Gas leak. See Warning
statement above
2. Control valve defective
1. Forei gn matter b etween
control valve and burner
2. Gas leak. See Warning
statement above
REMEDY
1. Open window and ventilate room. Stop using odor
ca usi ng prod ucts wh ile
heater is running
2. Rell supply tank (propane/
LP only)
3. Locate and correct all leaks
(see Checking Gas Con-
nections, page 14)
1. Open window and/or door
for ventilation
2. Contact loca l natural or
propane/LP gas company
3. C lean O D S / pilot ( s e e
Cleaning and Maintenance,
page 19)
1. Locate and correct all leaks
(see Checking Gas Con-nections, page 14)
2. Replace control valve
1. Take apart gas tubing and
remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Con-nections, page 14)
125001-01B23
www.fmiproducts.com
PARTS
1
9
10
2
16
4
15
15
8
11
13
5
12
3
14
7
6
17e
17c
17a
17d
17b
MODELS HDL18NA, HDL18PA, HDL24NA AND HDL24PA,
www.fmiproducts.com
125001-01B24
This list contains replaceable parts used in your heater. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 26 of this manual.
123190-07 Center Log• •1
17c 123190-03 Front Log• •1
123190-08 Front Log• •1
17d 123190-04 Top Right Log• •1
123190-09 Top Right Log• •1
17e 123190-10 Top Left Log• •1
123190-05 Top Left Log• •1
PARTS AVAILABLE — NOT SHOWN
100563-01 Warning Plate• • • •1
101055-08 Lighting Instructions Plate• • • •1
100639-01 Caution Decal• • • •1
101137-02 Hardware Kit• • • •1
GA6060Lava Rock• • • •1
** Not a eld replaceable part.
HDL18NA
HDL18PA
HDL24NA
HDL24PA
125001-01B25
www.fmiproducts.com
SPECIFICATIONS
HDL18PA, HDL24PA
• Rating (Variable): 19,000/36,000 Btu/Hr
• Type Gas: Propane/LP
• Ignition: Piezo
• Pressure Manifold: 10.0" W.C.
• Inlet Gas Pressure (in. of water):
Maximum 14" W.C., Minimum* 11" W.C.
• Shipping Weight: 27 lbs.
* For input adjustment
REPLACEMENT PARTS
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
Contact authorized dealers of this product.
If they can’t supply original replacement
pa r t(s ), ca l l FMI PR ODU CTS , LLC at
1-866-328-4537.
HDL18NA, HDL24NA
• Rating (Variable): 19,000/36,000 Btu/Hr
• Type Gas : Natural Gas
• Ignition: Piezo
• Pressure Manifold: 4.5" W.C.
• Inlet Gas Pressure (in. of water):
Maximum 10.5" W.C., Minimum* 5" W.C.
• Shipping Weight: 29 lbs.
* For input adjustment
When calling, have ready
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• type of gas used (propane/LP or natural
gas)
• purchase date
Usually, we will ask you to return the part to
the factory.
TECHNICAL SERVICE
You may have further questions about
installation, operation or troubleshooting.
If so, c ontact FMI PRODUCTS, LLC at
1-866-328-4537. When calling please have
your mod el a nd s erial numb ers of your
heater ready.
You can also visit our web site atwww.fmiproducts.com.
ACCESSORIES
Purchase these accessories from your local
dealer. If they can not supply these acces-
sories, either contact your nearest Parts
Central or call FMI PRODUCTS, LLC at
1-866-328-4537 for information. You can
also write to the address listed on the back
page of this manual.
DAMPER CLAMP - GA6080
For all models. Permanently opens chimney
ue damper for vented operation.
www.fmiproducts.com
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• heater will not produce specied heat
• propane/LP gas supply may be low
You may feel your gas pressure is too low. If
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects
in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date
of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be
free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this
warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only
when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allowance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by
FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI
PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement
parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs,
unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of
the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty
excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all
implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on
new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not
be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
Factory Reconditioned Products
Terms Common to All Warranties
) _____________________________
) __________________________
New Products
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
125001-01
Rev B
07/10